rotork IQ Range, IQ Multi-Turn, IQT Part-Turn Full Configuration, Status And Monitoring User Manual

IQ Range
IQ and IQT full configuration,
status and monitoring user manual
Keeping the World Flowing
IQ Multi-Turn and IQT Part-Turn
Electric Valve Actuators
2

Table of Contents

1. Introduction

1. Introduction __________________________3
ACTUATOR
SETTING TOOL
1.1 Using the Rotork Setting Tool ___________4
1.2 Connecting to the actuator _____________6
1.3 Password Security _____________________7
2. Settings ______________________________8
2.1 Settings – Limits _______________________8
2.2 Settings – Indication __________________11
2.3 Settings – Control ___________________ 14
2.4 Settings – ESD ______________________ 32
2.5 Settings – Security ___________________ 34
2.6 Settings – Defaults ___________________ 35
3. Status ______________________________ 36
3.1 Status – Control _____________________ 36
3.2 Status – Alarms _____________________ 40
3.3 Status – Movement ___________________41
3.4 Status – Indication ___________________ 42
3.5 Status – Diagnostics __________________ 43
4. Data Log ___________________________ 44
4.1 Data Log – Torque Logs ______________ 45
4.2 Data Log – Event Logs ________________ 47
4.3 Data Log – Trend Logs ________________51
4.4 Data Log – Operation Logs ____________ 54
4.5 Data Log – Partial Stroke Logs _________ 58
4.6 Data Log – Set Log Date ______________ 59
This manual provides instruction on the
setup and analysis of the actuator.
It is structured so that instruction on using the Setting Tool, navigation and password security is contained in Section 1. This must then be applied when changing settings and viewing information as set out in Sections 2 - 5.
The user must therefore be familiar with the operations contained in Section 1 before proceeding.
This manual should be read in conjunction with PUB002-039 IQ Range Instructions for Safe Use, Installation, Basic Setup and Maintenance and PUB002-065 IQT Range Instructions for Safe Use, Installation, Basic Setup and Maintenance supplied with the actuator.
5. Assets ______________________________ 60
5.1 Assets – Actuator ___________________ 61
5.2 Assets – Valve _______________________ 64
5.3 Assets – 2nd Stage Gear Box __________ 64
5.4 Assets – Service History ______________ 65
5.5 Assets – Service Alarms ______________ 65
5.6 Assets – NAMUR 107 ________________ 66
5.7 Assets – Online Help _________________ 67
IQ3 Full Confi guration Man ual – Secti on: Introduc tion 3
ACTUATOR SETTING TOOL

1.1 Using the Rotork Setting Tool

The Setting Tool is used to connect to the actuator, navigate through menus, change settings and view information presented on the actuator display.
1
9
4
7
8
5
11
3
6
2
10
Name General Operation
1. Key Scroll up.
2. Key Scroll down / Connect via Bluetooth®.
3. Key Decrease value / Toggle setting / Scroll left.
4. Key Increase value / Toggle setting / Scroll right.
5. Key Select the highlighted item. Save the highlighted setting. Stop actuator running (when Setting Tool control is enabled, refer to 2.3.1).
6. Key Return to previous menu.
7. Key Cycle between standard and zoom view on data logger torque graphs.
8. Key Actions the pre-configured mission stored on the Rotork Bluetooth® Setting Tool Pro.
9. Infrared transmitter window.
10. Key Send a close command to the connected actuator (when enabled refer to 2.3.1).
11. Key Send an open command to the connected actuator (when enabled refer to 2.3.1).
Navigation
To navigate through screens, menus and pages, the
and keys are used. A single key press results in one movement. Holding the key will result multiple movements in succession. Menus, pages and dropdowns wrap round. This means that an item at the bottom of a screen can be accessed by pressing while at the top.
Shorthand Instructions
This manual uses shorthand instruction (example): (meaning select, edit setting, save) to prompt the user with the key operations required. The display will also indicate the relevant
keys at the bottom left.
Pages, Functions and Index
The display indicates the number of each function as it is highlighted along with the total number of functions on that page. In the example below, Action is function 2 out of a total of 15 functions on that page:
2/15
This manual uses the display function number as reference for instructions.
Action (highlighted) is function 2 out of a total 15
on the LIMITS page.
Selection
The key is used to select a main menu item, menu items or instruction buttons. For a setting, is used to select when a change is required. The first time this occurs in a communication session, a password will be requested, refer to 1.3. Subsequent changes within the same session will not require the entry of a password. When selected, a menu item will be opened or a setting or function will be highlighted.
Information, instruction and password entry screens require an
or button to be selected. Navigate to highlight
the required button using or and press to select.
Setting controls
There are four types of setting control used. When a function is selected, the ability to change the function, setting or value is made available using drop down list boxes, check boxes, slider controls or numerical values.
Drop down list boxes
Drop down list boxes are indicated by .
Contacts
Monitor Relay
Mode Available
S1
Function Closed Limit
Contact
Position 0%
Function Open Limit Contact
Position 0%
2/37
The example of the S1 indication contact Function (highlighted) dropdown list box is shown on the next page. When selected (password entered if applicable, refer to 1.3), the current set function will be highlighted within the drop down list.
N/O N/C
S2
N/O N/C
4 IQ3 Full Co nfiguration M anual – Sec tion: Introd uction
1.1 Using the Rotork Setting Tool
continued
ACTUATOR SETTING TOOL
Contacts
Monitor Relay
Mode Available
Function Closed Limit
Contact
Position 0%
Function Open Limit Contact
Position 0%
2/37
Disabled
S1
Closed Limit
Open Limit
N/O N/C
End Position Pos. % Open
S2
Mid Travel Motor Running
N/O N/C
Closing
The symbol in the drop down box indicates more functions are available by scrolling or .
Use or to scroll through the list until the required function is highlighted. Press to select. The drop down list box will close and the selected function will be saved and shown on the page.
To exit the drop down list without saving a new setting press to return to the previous page.
Checkboxes
Check boxes are indicated by or .
Contacts
Monitor Relay
Mode Available
S1 Function Closed Limit
Contact
Position 0%
Function Open Limit Contact
Position 0%
3/37
An example for the S1 indication contact type check box is shown above.
Mode Available
Function Closed Limit
Contact
Position 0%
Function Open Limit Contact
Position 0%
3/37
When selected (password entered if applicable, refer to 1.3), the current mode will be highlighted.
Use either the or to toggle between modes.
Once the required mode is checked, press to select. The selected mode will be saved and shown as checked on the page.
To exit the checkbox without saving a new setting, press
to return to the page.
N/O N/C
S2
N/O N/C
Contacts
Monitor Relay
S1
N/O N/C
S2
N/O N/C
Slider controls
Slider controls graphically indicate the set value followed by the exact numerical value, for example:
Position 35%
The range covered by the slider is fixed and is determined by its function.
Contacts
Monitor Relay
Mode Available
S1 Function Pos % Open Contact
Position 35%
Function Open Limit Contact
Position 0%
4/37
N/O N/C
S2
N/O N/C
An example of the S1 indication position value is shown above. The S1 contact function of Pos.% Open indication will show the valve position at which the contact will change state.
Press (enter password if applicable, refer to 1.3). Use or to decrease or increase the value.
Slider controls wrap round so a key press on a minimum value will wrap round and indicate the maximum value. The value step changes increase as or is held down.
Once the required value is set press to select. The selected value will be saved and shown on the page.
To exit the slider control without saving a new setting, press to return to the page.
Numerical values
Numerical values relate to fields such as time or address - shown in the example below.
Stopped
Pakscan
Address 3
Baud Rate 2400
Position Update Times (s) Deviation 5%
Update Times (s) 5
Press (enter the password if applicable, refer to 1.3).
Use or to decrease/increase the numerical value. Press to select.
To exit the numerical value control without saving a new value, press to return to the previous page.
1
Torque
1/8
IQ3 Full Confi guration Man ual – Secti on: Introduc tion 5
ACTUATOR SETTING TOOL

1.2 Connecting to the actuator

The Rotork Bluetooth® Setting Tool Pro incorporating Bluetooth wireless technology is shown below. It is identified by the key symbols and a clear band between the top and bottom casings being transparent.
The Rotork Infrared Setting Tool Pro is identified by solid yellow keys and a yellow band between casings:
Yellow: Rotork Infrared Setting Tool Pro Clear: Rotork Blueto oth® Setting Tool Pro
Connecting to the actuator using Bluetooth
The actuator must be powered up to connect using Bluetooth. The default security set in the actuator for Bluetooth connection is by initiation using an infrared command. This means that the user must be in close proximity and in direct line of sight of the actuator.
Point the Setting Tool at the infrared sensor located at the lower right of actuator display window within a range of 0.25 m (10 in) and press until the key flashes blue.
The screen will change to the Main Menu screen.
Open Limit
The Setting Tool will automatically connect using Bluetooth which takes up to 5 seconds.
Connection is indicated by a blue light on the tool and in the actuator display window. Once connected, the tool can be used without pointing it at the actuator display window.
Bluetooth connection will be maintained while Setting Tool key commands are made. After a period of 6 minutes with no key commands, Bluetooth connection will be turned off and the Setting Tool and display blue lights will go out. To manually disconnect Bluetooth at any time, press and together.
Connecting to the actuator using Infrared
Infrared communication is used when:
Bluetooth communication has been disabled (refer to 2.5).
• configuration is required without power being applied to the actuator.
• legacy infrared only Rotork Setting Tool is used (yellow banded tool).
The Infrared only tool has solid yellow keys and a yellow band between casings.
Communication is by direct line of site infrared commands within a range of 0.25 m (10 in). Keys have the same function as shown in this manual. Each key press sends a discreet infrared command and therefore the tool must be in range.
6 IQ3 Full Co nfiguration M anual – Sec tion: Introd uction

1.3 Password Security

ACTUATOR SETTING TOOL
Menus, pages and settings may be viewed when the actuator is set to Remote, Stop or Local. To change a setting, the actuator must be selected to Local or Stop using the red selector and the correct password must be entered.
The password will be requested the first time a function is selected. Once correctly entered, other changes can be made without re-entering the password for the duration of the Setting Tool session with the actuator.
If the actuator is selected to Remote and a setting is selected, the following information screen will be displayed:
Press to return to the page. Set the red selector to Local or Stop to proceed with setting.
With the actuator selected to Local or Stop and when any setting function is selected, the Password screen will be displayed:
If the user has set their own password the following screen will be displayed:
Enter user selected Password:
Use to highlight new password entry box and press
Use
to scroll through alphanumeric values to display
required character.
Use to move to the next character.
Use to delete the highlighted character.
Use when selected password is complete.
Navigate to the OK button using
.
Press
The factory set default password ROTORK is displayed and the OK button is highlighted.
Press . The setting page from which the function was selected will be displayed with the function highlighted.
IQ3 Full Confi guration Man ual – Secti on: Introduc tion 7

2. Settings 2.1 Settings – Limits

Limits Indication Control ESD Security Defaults
2. Settings Menu Page
2.1 Limits 8
2.2 Indication 11
2.2.1 Contacts 11
2.2.2 Local Display 12
2.2.3 Analogue 14
2.3 Control 14
2.3.1 Local Control 15
2.3.2 Remote Control 16
2.3.3 Interrupter Timer 31
2.4 ESD 32
2.5 Security 34
2.6 Defaults 35
Settings
Limits
Settings
Indication Control ESD Security Defaults
Close Settings
Direction Clock Anti
Action Torque 40% Set Limit
Action Torque 40% Set Limit
Turns 14.9 Position
*
Speed
Opening
OP Bypass Pos 5%
Closing On Off
CL Bypass Pos 95%
1/15
Limit Torque
Open Settings
Limit Torque
49.6
90%
Torque Limit Bypass
On Off
* IQT builds only
The Limits page is shown above with the default settings.
Close Settings
1/15 Close Direction
Sets the output rotation direction required to close the valve. Using the handwheel, manually operate the actuator to establish valve closing direction.
Clock (default) – clockwise rotation of the actuator closes the valve.
Anti – anti-clockwise (counter clockwise) rotation of the actuator closes the valve.
To change, closing direction.
2/15 Close Action
The actuator can be configured to close on torque for seating valve types or limit for non-seating valve types.
Refer to Valve manufacturer for recommended setting. In the absence of valvemaker instruction refer to the following table:
. The checkbox will indicate the set
8 IQ3 Full Co nfiguration M anual – Sec tion: Setti ngs
2.1 Settings – Limits
continued
Valve Type
Close Action
Open Action
Wedge gate Torque Limit
Globe Torque Limit
Butterfly Limit Limit
Through conduit Limit Limit
Ball Limit Limit
Plug Limit Limit
Sluice gate Limit Limit
Penstock Limit Limit
Parallel slide Limit Limit
Limit (default) – The actuator will move the valve to the set Closed Limit position and stop.
Tor que – The actuator will move the valve to the set Closed Limit position and then apply the set torque (3/15) to seat the valve.
To change, closing action.
3/15 Close Torque
The value of torque available to close the valve can be limited between 40% and 100% of its nameplate rated torque. If the actuator experiences the set torque when closing between the limits, it will stop and must then be reversed before it will move closed again. Operational torque can be monitored using the data log (refer to 4) and using the torque-position home screen (refer to 2.2.2).
The default setting for closed torque limit is 40%. If a value of torque was specified at time of order, the % value equating to the specified torque will have been set by Rotork.
If the actuator was delivered complete with valve, the valvemaker may have set the closed torque limit based on testing and/or design requirements.
In the absence of valvemaker instruction, set the minimum value required to close the valve under process conditions.
To change, closing torque value.
4/15 Close Limit
Limits must only be set when the actuator is coupled to the valve.
The minimum number of output turns between set Closed and Open Limits is 2.5 or 30º (IQT). A Closed Limit position cannot be set if the actuator is at its set Open Limit or within 2.5 (30º) turns of an Open Limit position. Should a condition arise where this occurs, for example where an actuator at its Closed Limit position is coupled to a valve at its open position, refer to 2.6 Defaults - Limits.
If the actuator was delivered complete with valve, the valvemaker should have set the Closed and Open limit position, refer to testing below.
The Closed Limit position must be set by moving the actuator to the valve Closed Limit position and pressing
The actuator will display the following Instruction:
. The checkbox will indicate the set
. The slider will indicate the set
.
Move the actuator and valve to the close position. Allow for overrun by winding open by ½ to 1 output turn.
Press to select OK.
The Closed Limit will be set at the current valve position. If not previously illuminated, the closed indication LED (default green, refer to 2.2.2) will be turned on.
Testing: The limit position can be confirmed by opening the actuator until the indication LED changes colour and then moving closed until the Closed Limit indication LED colour is turned on at the set Closed Limit position.
Open Settings
5/15 Open Action
The actuator can be configured to open on torque for back­seating valve types or limit for non back-seating valve types.
Refer to valve manufacturer for recommended setting. In the absence of valvemaker instruction set open action to Limit.
Limit (default) – The actuator will move the valve to the set
Open Limit position and stop.
Tor que – The actuator will move the valve to the set Open Limit position and then apply the set torque (6/15) to back-seat the valve.
To change, opening action.
6/15 O pen Torq ue
The value of torque available to open the valve can be limited between 40% and 100% of its nameplate rated torque. If the actuator experiences the set torque when opening between the limits, it will stop and must then be reversed before it will move open again. Operational torque can be monitored using the data log (refer to 4) and using the torque-position home screen (refer to 2.2.2).
The default setting for open torque limit is 40%. If a value of torque was specified at time of order, the % value equating to the specified torque will have been set by Rotork.
If the actuator was delivered complete with valve, the valvemaker may have set the closed torque limit based on testing and/or design requirements.
In the absence of valvemaker instruction, set the minimum value required to open the valve under process conditions but higher than that set for closed torque.
To change, of opening torque value.
. The checkbox will indicate the set
. The slider will indicate the set limit
IQ3 Full Confi guration Man ual – Secti on: Setting s 9
2.1 Settings – Limits
continued
7/15 Set Open Limit
Limits must only be set when the actuator is coupled to the valve.
The minimum number of output turns between set Open and Closed Limits is 2.5. An Open Limit position cannot be set if the actuator is at a set Closed Limit position or within 2.5 turns of a Closed Limit position. Should a condition arise where this occurs, for example where an actuator at its Open Limit position is coupled to a valve at its closed position, refer to 2.6 Defaults
- Limits.
If the actuator was delivered complete with valve, the valvemaker should have set the Closed and Open limit positions, refer to testing below.
The Open Limit position must be set by moving the actuator to the valve Open Limit position and pressing
The actuator will display the following Instruction:
Move the actuator and valve to the open position. Allow for overrun by winding closed by ½ to 1 output turn.
Press to select OK.
The Open Limit will be set at the current valve position. If not previously illuminated, the open indication LED (default red, refer to 2.2.2) will be turned on.
Testing: The limit position can be confirmed by closing the actuator until the indication LED changes colour and then moving open until the Open Limit indication LED is turned on at the set Open Limit position.
8/15 Tu rns
Shows the actuator output turns between the set Closed and Open Limit positions.
9/15 Position (non-editable)
Shows the actuator current position on 0-100%.
10/15 Speed (IQT only)
The default speed for a standard IQT is 100% (rated) or 50% for IQTM. Speed can be adjusted to suit operation/process needs.
To cha nge , set speed.
. The slider will indicate the current
.
Torque Limit Bypass
The default setting for opening and closing torque limit bypass is Off (torque protection active at all times). Bypassing the torque protection allows torque up to approximately 150% of rated to be available.
The valve maker or integrator should be consulted to confirm the valve structure and interface components can withstand the additional torque/thrust.
11/15 Opening
Opening torque limit protection can be bypassed over a portion of the opening stroke, refer to 12/15. When set to On, torque of up to approximately 150% of rated is available for opening "sticky" valves.
To cha nge , opening torque limit bypass status.
12/15 Opening Bypass position
When opening torque limit bypass is set to On (refer to 11/15), the position over the opening stroke where torque limit protection is bypassed can be set. If torque limit bypass open is set to Off, the opening bypass position control will be greyed out.
The available position range over which torque limit protection is bypassed is 0% (Closed Limit) to 95% open. Outside the set bypass position, torque switch protection will revert to that set for 6 /15.
To cha nge , set position range over which opening torque limit is bypassed.
13/15 Closing
Closing torque limit protection can be bypassed over a portion of the closing stroke, refer to 14/15. When set to On, torque of up to approximately 150% of rated is available for closing the valve.
To cha nge , closing torque limit bypass status.
14/15 Closing Bypass position
When closing torque limit bypass is set to On (refer to 13/15), the position over the closing stroke where torque limit protection is bypassed can be set. If torque limit bypass closed is set to Off, the closing bypass position control will be greyed out.
The available position range over which torque limit protection is bypassed is 100% (Open Limit) to 5% open. Outside the set bypass position, torque switch protection will revert to that set for 3 /15.
To cha nge , position range over which closing torque limit is bypassed.
. The checkbox will indicate the set
. The slider will indicate the
. The checkbox will indicate the set
. The slider will indicate the set
10 IQ3 Full Co nfiguratio n Manual – Sec tion: Sett ings
15/15 Auto Limit Setting
Sets the open and close limits automatically. Then end of travel for the lower and upper limits is established when 40% torque has been reached in each direction. The Actuator must be in Local to complete this function.

2.2 Settings – Indication

Limits
Indication
Control ESD Security Defaults
Instruction is provided on:
2.2.1 Contacts
2.2.2 Local display
2.3.3 Analogue

2.2.1 Indication – Contacts

Settings
Limits
Indication
Control ESD Security Defaults
Contacts
Local Display Analogue
Mode Available
Function Closed Limit Contact
Position 0%
Function Open Limit Contact
Position 0%
Function Closed Limit Contact
Position 0%
Function Open Limit Contact
Position 0%
1/37
The Monitor Relay and S contact settings page is shown in their default setting.
Refer to actuator wiring diagram for available contacts.
Settings
Indication
Contacts
Monitor Relay
S1
N/O N/C
S2
N/O N/C
S3
N/O N/C
S4
N/O N/C
1/37 Monitor Relay – Mode
The monitor relay provides remote indication of actuator status. It provides a volt free change over contact, refer to actuator circuit diagram. There are 2 modes that can be set:
Available (default) – Actuator available for remote control. Monitors power supplies, motor thermostat, detected internal fault and remote control selected. A loss in one or more will cause the monitor relay to de-energise indicating "not available" for remote control.
Fault – Actuator fault. Monitors power supplies, motor thermostat and detected internal fault. A loss in one or more will cause the monitor relay to de-energise indicating "actuator fault".
To change the mode, will close and the selected mode will be shown:
. The drop down list box
S Contact function, contact type and position
Each relay contact can be set to one of the functions shown in the table below and its contact type can be set as Normally Open (NO) or Normally Closed (NC). If Pos % Open function is selected, the position at which the relay operates can be set. For all other functions the position control slider will be greyed out.
Standard Contacts S1-S4, Option S5-S8 and S9-S12 Contacts when fitted
The method for setting all S contacts is the same. S1 to S4 are fitted as standard. A further 8 extra contacts are available as options grouped: S5 to S8 and S9 to S12, refer to actuator wiring diagram. If extra contacts are fitted their configuration screens are accessed by scrolling down. If not fitted their configuration settings will be greyed out.
2/37 Contact Function
The available contact functions included in the drop down list box are shown below.
To change the contact function, down list box will close and the selected function will be shown:
Function Indication:
Disabled Contact disabled
Closed Limit Closed limit position (exact)
Open Limit Open limit position (exact)
End Position Both Closed and Open Limit positions
Pos % open Set position mid-travel – opening and closing
Mid Travel Not at Closed or Open Limits
Motor Running Motor running
Closing Travelling in the close direction - motor or handwheel
Opening Travelling in the open direction - motor or handwheel
Moving Travelling – motor or handwheel
Handwheel During handwheel operation
Blinker Travelling (make/break at 1 second intervals)
Valve Alarm On torque trip mid-travel or motor stall condition
Torque Trip CL Torque trip closing - any position
Torque Trip OP Torque trip opening - any position
. The drop
Continued over page
IQ3 Full Confi guration Man ual – Secti on: Setting s 11
2.2.1 Indication – Contacts
continued

2.2.2 Indication – Local Display

Function Indication:
Torque Trip Torque trip closing or opening - any position
Torque Trip Mid Torque trip mid-travel, closing or opening
Motor Stall
Mid Travel Stall
Stop Selected Red selector set to STOP
Local Selected Red selector set to Local
Remote Selected Red selector set to Remote
Control Alarm ESD signal and/or interlock active
Monitor Monitor relay de-energised
ESD Active ESD signal applied
OP Interlock Active Open Interlock active
CL Interlock Active Close interlock active
Interlock Active Open and/or closed interlock active
Actuator Alarm Internal fault detected
Motor Over Temp Motor thermostat has tripped
Lost Phase 3-phase only: monitored phase 3 lost
24 V Supply Fail Internal 24 VDC supply failed (Terminals 4 & 5)
P Stroke Active Partial stroke underway
P Stroke Fail Partial stroke not completed
P Stroke Pass Partial stroke completed
Bluetooth Bluetooth communication in progress
Battery Low Battery low
Battery Discharged Battery discharged or missing
Digital Output Network option controlled
Maintenance Scheduled maintenance due
Hi Torque Alarm Set Hi torque value reached
Hi Hi Torque Alarm Set Hi-Hi torque value reached
Src 1 Coms Loss Communication failure with option 1 card
Src 2 Coms Loss Communication failure with option 2 card
NAMUR Maint. A NAMUR maintenance condition is active
NAMUR Out Of Spec. A NAMUR out of specification condition is active
NAMUR Func. Check A NAMUR function check condition is active
NAMUR Failure A NAMUR failure condition is active
Over Modulation Starts per hour has been exceeded
Motor Enable
Maintain Enabled Open/Close signals are maintained
HMI Loss HMI will not be lit up
General alarm
Bat Backup Avail
Bat Backup Ctrl Checks if the battery is in control
At limit, motor energised – no output movement detected
Not at limit, motor energised – no output movement detected
Active when motor enable is inhibiting electrical operation
Anything which constitutes an alarm out of the ‘function’ list triggers this alarm
Checks availability of battery, checks if battery is charged
4/37 Position
If the relay function relates to an actuator position, for example Pos % Open, this setting will become available to edit. Range 0% - 100%.
To change use the set position value.
Limits
Indication
Control ESD Security Defaults
Contacts
Local Display
Analogue
Home Screen Position
Power Save On Off
Close LED Green Red Mid Travel LED Off
Alarm LED Alarms
LCD / LED Test
1/7
. The slider control will indicate
Settings
Indication
Local Display
LCD
LED
The Local Display settings page is shown in its default setting.
LCD
The displayed home screen language can be selected and power save mode can be activated.
1/7 Home Screen
If NAMUR 107 relay functions are used, refer to 5.6 for NAMUR 107 condition settings.
3/37 Contact
Each relay contact output can be configured as normally open (make on condition) or normally closed (break on condition).
N/O - The contact will complete the circuit when the set function is present, normally open, refer to 2/37 Contact Function.
N/C - The contact will break the relay circuit when the set function is present, normally closed, refer to 2/37 Contact Function.
To change use selected contact type.
. The checkbox will indicate the
12 IQ3 Ful l Configurati on Manual – Se ction: Set tings
Refer also to PUB002-039 (IQ) or PUB002-065 (IQT)
Available Home screens included in the drop down list box:
Position (default) - Display indicates the current valve position to one decimal place. Icons are used for closed and open limit positions.
Torque (A) + Pos – Display indicates current valve position to one decimal place as Position (above) plus analogue torque indication scaled 0% to 100% of rated torque, shown at the top of the display.
Torque (D) + Pos – Display indicates current valve position to one decimal place as Position (above) plus digital torque indication scaled 0% to 99% of rated torque. If the actuator develops torque greater than 99% then "Hi" will be displayed.
2.2.2 Indication – Local Display
continued
Positioner – Used only with analogue or network position control. Display indicates current valve position ( ) to one decimal place plus the position equating to the applied demand signal ( ). In addition, an analogue indication of demand and position is provided scaled 0% to 100% of valve position.
To set the home screen, list box will close and the selected home screen will be indicated.
2/7 Power Save
The LCD has a white backlight to maximise contrast of the segment display and matrix characters. It may be switched off when not required if a bright display is disruptive within its environment.
Off (default) - The display backlight is permanently illuminated when the actuator is powered up.
On - The display backlight automatically switches off when the actuator is not operating. The segments/matrix remain on. The display backlight will switch on when the local control selectors are moved, electrical or handwheel operation takes place or when the Setting Tool is communicating with the actuator. The backlight will switch off again approximately 30 seconds after the above events have taken place.
To change the power save mode, will indicate the selected mode.
. The drop down
. The checkbox
LED
The function of the display green, red and yellow LED lights can be set.
3/7 Close Colour
Green (default) – The green lights illuminate at the Closed Limit
position, red at open.
Red – The red lights illuminate at the Closed Limit position, green at open.
To change the Closed Limit position indication light,
colour.
4/7 Mid Travel LED
. The checkbox will indicate the selected closed
5/7 Alarm LED
Alarm LED Function will be greyed out unless 4/7 Mid Travel LED is set to On/Alarm or Off/Alarm.
Disabled (default) – The yellow lights do not indicate an active alarm.
Alarms – The yellow lights indicate active alarms.
Service – The yellow lights indicate active service alarms only.
A service alarm indicates the actuator requires service due to set duty parameters being met. Refer to Section 5.5.
Service/Alarms – The yellow lights indicate active alarms and active service alarms. A service alarm indicates the actuator requires service due to set duty parameters being met. Refer to Section 5.5.
Information regarding the nature of the alarm(s) will be shown at the top of the display.
To change the Alarm LED Mode, down list box will close and the selected mode will be shown.
6/7 LCD / LED Test
The LCD/LED test function operates a test procedure to check all of the local display functions. It will cycle periodically between screen and LED functions to provide visual indication that the display is in fully working order.
Press local display menu once the test is complete.
7/7 Language
The language used on the display can be selected.
English (default), French, German and Spanish are available as standard. Other available languages may be downloaded from the Rotork website, loaded into the Setting Tool using Insight2 and uploaded into the actuator. Visit www.rotork.com
To change the display language, down list box will close and the selected language will be active for all screens and pages.
Available for actuators with a build date after December 2013 (12/13).
to begin the test. The screen will return to the
. The drop
. The drop
On (default) – The yellow lights are on when mid-travel.
Off – The yellow lights are off when mid-travel.
Blinker – The yellow lights flash at approximately 0.5 second
intervals when travelling in mid-travel (electric or handwheel operation). When stationary, the lights will remain on.
On/Alarm – The yellow lights are on when mid-travel. If an alarm is active the yellow lights flash alternately at approximately
0.5 second intervals. Refer to 5/7 Alarm LED.
Off/Alarm – The yellow lights are off when mid-travel. If an alarm is active the yellow lights flash alternately at approximately
0.5 second intervals. Refer to 5/7 Alarm LED.
Information regarding the nature of the alarm(s) will be shown at the top of the display.
To change the mid-travel LED Mode, down list box will close and the selected mode will be shown.
. The drop
IQ3 Full Confi guration Man ual – Secti on: Setting s 13

2.2.3 Indication – Analogue

2.3 Settings – Control

Limits
Indication
Control ESD Security Defaults
Indication
Contacts Local Display
Analogue
Analogue
Analogue
Invert On Off
1/1
Settings
Limits Indication
Control
ESD Security Defaults
Instruction is provided on:
2.3.1 Local control
Settings for vandal resistant build, Setting Tool control, maintained local control, delay control and action on loss of actuator user interface.
2.3.2 Remote control
Settings for control source; hardwired, networks, analogue and partial stroke setup.
2.3.3 Interrupter Timer
The Interrupter Timer is an optional extra, check circuit diagram for inclusion. If it is not enabled it will not be included in the display menu. It is used to control closing and/or opening operating time under both local and remote control.
Settings
Analogue position indication screen is shown above with its default setting.
Analogue position indication (4-20 mA) is an optional extra, refer to circuit diagram for inclusion. If the option is not fitted the Analogue menu item will not be present in the Indication menu.
The analogue output signal auto ranges to the set limits and cannot be calibrated.
1/1 Invert
Off (default) – 4 mA output at Closed Limit position / 20 mA
output at Open Limit position.
On – 4 mA output at Open Limit position / 20 mA output at Closed Limit position.
To change the analogue output mode, checkbox will indicate the selected mode.
. The
14 IQ3 Ful l Configurati on Manual – Se ction: Set tings

2.3.1 Control – Local

Limits Indication
Control
ESD Security Defaults
Settings
Local
Remote Interrupter Timer
Control
Local Control
Vandal Disabled
Setting Tool Yes No Maintained Yes No Delay Control Yes No Loss Of HMI Stayput Remote
Remote Hand Station
Enabled On Off
1/6
The local control configuration page is shown with the default settings.
1/6 Vandal
Actuators built as vandal resistant type 1 do not have the black and red control selectors fitted. Selection of Local control (using the Setting Tool open, close and stop keys) and Remote control is made using the vandal setting:
Disabled (default) – Actuator is not vandal resistant build and control selectors are present.
Local – Actuator selected for Local control using the Setting Tool (Bluetooth or infrared), refer to 1.1. Infrared local control has a range of approximately 0.25 m (10") and must be in direct line of site. Bluetooth Local control has a range up to approximately 10 m (30 ft) depending on environment.
Remote – Actuator selected for Remote control. Setting Tool control keys are inactive and the actuator responds only to remote control signals.
Switched – This option is available with an external PCB (i.e. DIO), the actuator uses the input to switch the vandal between local and remote.
To change, the selected control mode will be indicated.
. The drop down list will close and
2/6 Setting Tool
With control selectors fitted to the actuator, the Setting Tool close, open and stop control keys can be used to operate the actuator:
Yes – Setting Tool control keys active, control is possible only
when the red selector is set to Local, refer to 1.1 – using the Setting Tool. Infrared local control has a range of approximately
0.25 m (10") and must be in direct line of site. Bluetooth Local control has a range up to approximately 10 m (30 ft) depending on environment. The black close/open selector remains active.
No (default) – Setting Tool close, open and stop control keys disabled. Local control is by close/open/ stop selectors fitted to the actuator.
To change, selected Setting Tool control mode.
. The checkbox will indicate the
3/6 Maintained
Sets the action as a response to local open or close control signals:
Yes (default) – The actuator will self-maintain as a response to a fleeting local open or close control signal. It will run until it receives a stop command, it reaches a travel limit or is reversed – Maintained control.
No – The actuator will run only while an open or close control signal is applied – Push to run local control.
To change, selected action.
. The checkbox will indicate the
4/6 Delay Control
If there is a risk of a local close or open control signal being applied due to the selector moving inadvertently or by being hit momentarily, a delay can be set to help prevent an unintended operation:
Yes – A local close or open signal must be held for approximately
2 seconds before the actuator responds.
No (default) – The actuator responds immediately to a local close or open control signal.
To change, selected local selector response.
. The checkbox will indicate the
5/6 Loss of HMI
The Human Machine Interface consists of the actuator display and red and black selectors. If for any reason the HMI stops responding, the response of the actuator can be set.
Stayput (default) – The actuator will stayput and alarm using the monitor relay. It will not respond to remote control signals.
Remote – The actuator will alarm using the monitor relay. It will
continue to respond to remote control signals.
To change, selected HMI failure response.
. The checkbox will indicate the
6/6 Remote Hand Station
When fitted, the Remote Hand Station (RHS) can be enabled by this setting.
Off (default) – RHS not activated and the sub-menus will be hidden.
On – RHS enabled and the sub-menus will appear in the main Control menu. Refer to PUB002-059 for full setup.
IQ3 Full Confi guration Man ual – Secti on: Setting s 15

2.3.2 Control – Remote

Limits Indication
Control
ESD Security Defaults
Local
Remote
Interrupter Timer
Hardwired Control Source Partial Stroke Positioning Auxiliary Mask Analogue Pakscan Profibus HART Modbus
Extra I/O
Settings
Control
Remote Control
The Remote Control menu is shown left listing all possible entries. Some menu items shown are optional remote control forms requiring additional hardware to be fitted in the actuator (see table below). The menu list displayed on the actuator will show only the option(s) fitted. Options not fitted will not be included in the menu list, check wiring diagram for option inclusion.
The table below lists the available standard and option remote control forms, their type and the section of this manual where instruction is provided.
Remote Control Form Included as: Type Section
Hardwired Standard Hardwired
Control Source Standard Software
Partial Stroke Standard Hardwired
Positioning Option See Note
Auxiliary Mask Option See Note
Analogue Option Analogue
Pakscan Option Network
Profibus Option Network
HART Option Analogue
Modbus Option Network
Extra I/O* Option Hardwired
Foundation Fieldbus* Option Network
* When Foundation Fieldbus is fitted it will be included in the remote control menu for information only. The Foundation Fieldbus option is configured remotely over the Fieldbus network and therefore does not have a setup page. Control Source, Positioning and Auxiliary Mask pages will be included to allow associated setting to be made when Foundation Fieldbus is fitted.
Extra I /O is an option card providing additional digital inputs to the standard build. Inputs may be control or indication (configurable).
2.3.2-1
2.3.2-2
2.3.2-3
2.3.2-4
2.3.2-5
2.3.2-6
2.3.2-7
2.3.2-8
2.3.2-9
2.3.2-10
2. 3 . 2 -11
N/A
Instruction is provided on the setup of standard hardwired and remote control options.
Note: When any of the analogue or network remote
control options are fitted, Auxiliary Mask and Positioning are automatically included in the remote control menu. These items allow access to settings that are common to all fitted options. See Examples below.
Example 1: For a basic actuator with no control options fitted, the remote control menu is shown below.
Hardwired
Control Source Partial Stroke
Remote Control
Example 2: For an actuator with a remote control option, the remote control menu will automatically display the appropriate items relating to that option. The example below shows the menu for an actuator including the Profibus option with the associated Positioning and Auxiliary Mask items.
Hardwired
Control Source Partial Stroke Positioning Auxiliary Mask Profibus
Remote Control
16 IQ3 Full Co nfiguratio n Manual – Sec tion: Sett ings
2.3.2-1 Control – Remote – Hardwired
Hardwired
Control Source Partial Stroke
Remote Control
Remote Control
2-Wire Priority Stop
Interlocks
Mode Disabled
Motor Enable
Motor Enable Disabled
1/3
Hardwired Control is a standard feature. The default settings are shown above.
Hardwired Control is a standard remote control form available on all actuators. It allows settings for hardwired 2-wire priority control and interlocks.
1/3 2-Wire Priority
Sets the action the actuator perform when a close and open signal are applied simultaneously. Hardwired remote control form C uses the priority action (open or closed) to set the actuator response when 2 signals are applied. Refer to the wiring diagram and its referenced RWS control diagram.
On applying hardwired close and open signals together, the actuator will:
Open – The actuator will move open.
Stop (default)
The actuator will not move, or will stop if running.
Close – The actuator will move closed.
To change, the selected 2-wire control mode will be indicated.
. The drop down list will close and
Conditional – Close and open interlock inputs are enabled, interlocking is available and will be active in remote control only. The actuator will not run under remote control unless
interlock signals are applied to the closed control and closed interlock input or the open control and open interlock input. Remote control is conditional on 2 signals being applied simultaneously and therefore integrity of operation due to spurious control signals is increased. Local control is available without interlock inputs.
Partial Stroke – Partial stroke testing demonstrates the operational integrity of the valve and actuator by moving them for a set portion of stroke. A remote "partial stroke" hardwired signal applied to the open interlock input is used to initiate a partial stroke test. For setting the partial stroke test parameters, refer to 2.3.2-3. When set to partial stroke, the closed interlock is disabled. Partial stroke initiated via a network command (with a network option fitted), does not require the interlocks to be configured for partial stroke.
To change the settings use list will close and the selected interlock mode will be
. The drop down
indicated.
3/3 Motor Enable
Sets the remote control maintain function when the motor enable feature is used. When using motor enable, the maintain line on terminal 34 becomes the permissive input.
Disabled (default) – Maintain function is controlled by applying a signal to terminal 34.
Push to Run – Remote controls are push to run. On removal of the remote open or close command, movement will stop.
Maintained – Remote controls are self maintained so only a pulse is required. Removal of the remote open or close signal will not stop operations. To stop movement, you must remove the motor enabled signal.
2/3 Interlocks
Sets the mode for the interlock inputs, refer to wiring diagram. External interlocks can be used to prevent operation of the actuator until a certain process condition is met. An example is a main and bypass valve system. The main valve is interlocked with the bypass valve such that it cannot be opened until the bypass valve is fully open.
Disabled (default) – The interlock inputs are disabled, interlocking is not available.
Enabled – Close and open interlock inputs are enabled, interlocking is available and will be active in both local and remote control. The actuator will not run in local or remote control unless interlock signals are applied to the closed or the open interlock input. If only one interlock is required, for example an interlock to prevent closed operation, the open interlock must be linked out.
IQ3 Full Confi guration Man ual – Secti on: Setting s 17
2.3.2-2 Control – Remote – Control Source
Hardwired
Control Source
Partial Stroke Positioning Auxiliary Mask Analogue
Remote Control
Option Control
Ctrl Source 1 Analogue
Ctrl Source 2 Disabled Ctrl Selection Source 1
Options Fitted
Analogue Disabled Disabled Disabled
Analogue Lost Sig Time (s) 0 Lost Signal Act. Signal Loss Pos. 0%
1/20
Off
The Control Source setting page shown above is an example of an actuator with the Analogue remote control option.
The actuator display will indicate fitted options.
Refer to wiring diagram for options fitted.
Introduction
In addition to standard hardwired control, the actuator can have up to two remote control options fitted. For most remote control systems employed by end-users, only one control option is used.
For control systems using Analogue control only or where Analogue and Network (such as Modbus) control is used, control (Hardwired/Analogue or Analogue/ Network) can be switched by the user using the Manual/Auto input available with the analogue option and the settings made in Control Source. When Analogue and Network options are fitted and Analogue is switched to control, the Network option cannot control the actuator but will continue to report actuator status.
The control source will be set by Rotork to the defaults required for the option(s) fitted. Refer to Table: Control Source Settings.
For analogue control, if both Manual (hardwired control inputs) and Auto (analogue control) is to be used, the control selection will require re-setting. If only analogue control is required, the default settings for Control Source will be correct. Refer also to 2.3.2-6.
The control source is used to:
• Control Source 1/Source 2 - Associate fitted control option(s) to a source of control (source 1 or source 2).
• Control Selection - Set which control source (1 or 2) has priority when Manual/Auto input is used to switch between Analogue and Network option sources.
• Lost Signal - Determines the actuator response to a lost analogue signal or network communication.
Table: Control Source Settings
Options Control
Settings
Hardwired
(no options)
Analogue Only
Ctrl Source 1 Disabled Analogue Analogue Network Analogue
Ctrl Source 2 Disabled Disabled Disabled Disabled Network
Ctrl Selection Hardwired Source 1
Options Fitted
Disabled Analogue Analogue Network Network
Disabled Disabled Disabled Disabled Analogue
Disabled Disabled Disabled Disabled Disabled
Disabled Disabled Disabled Disabled Disabled
Analogue and
Hardwired
Hardwired /
Source 1
Network Only
Analogue
and Network
Source 1 Src1 (Ang) / Source 2
KEY: For "Network", display will indicate the fitted option(s): Pakscan/Profibus/Modbus/Foundation Fieldbus (FF)/HART.
18 IQ3 Full Co nfiguratio n Manual – Sec tion: Sett ings
2.3.2-2 Control – Remote – Control Source
continued
1/20 Control Source 1
Control Source 1 will be set by Rotork for the fitted remote Analogue or Network control option(s). Refer to Table: Control Source Settings.
2/20 Control Source 2
Control Source 2 will be set by Rotork for the fitted remote Analogue or Network control option(s). Refer to Table: Control Source Settings.
3/20 Ctrl Selection
Control Selection is used to select the control source and if required, for Analogue option or Analogue with Network options, allow hardwired switching between sources using the Manual/Auto input.
Disabled – All remote control disabled. The actuator can only be operated using the local controls.
Hardwired – Remote control by hardwired inputs only. This setting is the default for actuators with no option cards fitted.
If a Network option is fitted but is not required for control,
to select Hardwired.
Source1 – Control by the option listed for Control Source 1.
If Control Source 1 is a Network option, control will be via its auxiliary mask inputs, refer to 2.3.2-5.
Hardwired / Source1 – Control available only when Analogue option is fitted. This mode enables the user to select between control by hardwired inputs or source 1 (Analogue) control by applying or removing a signal to the Manual/Auto input, refer to wiring diagram. Manual will enable hardwired control and Auto will enable Source1 control.
If an Analogue option is fitted and Manual/Auto switching is required,
to select Hardwired/Source 1.
Source 1 (Ang) / Source 2 – Control by Analogue and a
Network option only. This mode enables the user to select between Source 1 (Analogue) and Source 2 (Network) control, by applying or removing a signal to the Manual/Auto input available with the Analogue option, refer to wiring diagram. Manual will enable source 2 and Auto will enable source 1, refer to 2.3.2-6.
Source 1 / Source 2 – For future use with two Network control options.
If Analogue and Network options are fitted and Manual/ Auto switching is required, (Ang) / Source 2.
to select Source 1
4/19 to 7/19 Options Fitted
Not editable. Factory set for the control options fitted. Up to 4 options can be fitted and will be indicated in the list. Unused allocations will be set to Disabled.
If a control option is fitted after manufacture, the allocation will be set to the fitted option type by Rotork Service. Where the user upgrades an actuator to include a new control option using a kit supplied by Rotork, this must be set before the control mode settings can be made. Contact Rotork for access.
8/20 to 19/20 Lost Signal
Sets the actuator response for when the analogue signal or Network communications of the control source are lost.
There are 3 settings for determining the actuator response on loss of signal and these are common for all option types fitted. Each group of 3 will be headed with the applicable option type
- example Analogue. For actuators including one control option, settings 8/20 to 10/20 will be available and settings 11/20 to 20/20 will be greyed out. For 2 options fitted, 8/20 to 13/20 will be available and so on up to 4 options. This instruction is therefore common for as many options as are fitted.
8/19 Lost Signal Time
Sets the amount of time in seconds that a signal must be lost before the set lost signal action is performed. Range 0 to 65 seconds:
For the analogue option, time must be set to 0 seconds.
To change, signal action will be implemented and indicated.
. The time set after which the lost
9/19 Lost Signal Action
Sets the action performed when the signal is lost:
Off (default) – The lost signal feature is disabled. An actuator with Analogue control will run to the set low signal position. An actuator with Network Control will stay at its current position when communication is lost.
Stayput – If the actuator is not moving it will Stayput, if it is moving it will Stop.
Close – The actuator will run to the Close Limit.
Open – The actuator will run to the Open Limit.
Position – The actuator will run to the mid-travel position set for
Signal Loss Position, refer to 10/19.
To change, the selected action will be indicated.
. The drop down list will close and
10/19 Lost Signal Position
When the lost signal action is set to Position the actuator will run to the mid-travel position set. Range is 0% (Closed Limit) to 100% (Open Limit). This control should be used if a lost signal position in mid-travel is required.
Whenever the actuator is running under positioning mode, the parameters in the Positioning menu will apply. Refer to 2.3.2-4.
To change, mid-travel position the actuator will move to when the
. The slider control will indicate the
control/network signal is lost.
IQ3 Full Confi guration Man ual – Secti on: Setting s 19
2.3.2-3 Control – Remote – Partial Stroke
Hardwired Control Source
Partial Stroke
Positioning Auxiliary Mask Analogue
Remote Control
Partial Stroke
Enable No Yes
From Limit To Position 95% Out Time (s) Return Time (s) 60
Test
1/6
Open Close
60
Partial Stroke is a standard feature. The default settings are shown above.
Partial stroke testing is used to demonstrate the operational integrity of the valve and actuator by moving over a set portion of valve stroke. In addition, partial stroking may be used to exercise infrequently operated valves to help keep them mechanically free. Partial stroke test can only be initiated when the actuator is at the set From Limit position.
A partial stroke test may be initiated by a remote partial stroke signal applied to the open interlock*, a network command (network option fitted) or using the test control on the partial stroke page.
*Interlocks must be set to partial stroke, refer to 2.3.2-1.
Partial stroke test results (torque and pass/ failure status) are captured by the data log.
Partial stroke operation, pass and failure can be indicated by the S contacts, refer to 2.2.1.
1/6 Enable
No (default) – Partial stroking testing is disabled
Yes – Partial stroke testing is enabled.
To change, stroke test status.
. The checkbox will indicate partial
2/6 From Limit
Selects the start/finish limit position for the partial stroke test.
Open (default) – The partial stroke test will start from the Open Limit position, move close to the position set for 3/6 To Position and then return to the Open Limit position.
Close – The partial stroke test will start from the Closed limit position, move open to the position set for 3/6 To Position and then return to the Close Limit position.
To change, stroke start/finish position.
. The checkbox will indicate partial
3/6 To Position
Range 0% (closed) to 97% Open
Selects the intermediate position for the partial stroke test.
Sets the position in valve stroke to where the actuator will move when a partial stroke test is initiated. For example a test starting at Open Limit with a To Position of 70% set, will move from Open Limit to 70% open and then return to the Open Limit. A minimum of 3% travel is required to adequately perform the partial stroke test.
To change, position the actuator will move to for the partial stroke
. The slider control will indicate the
test.
4/6 - 5/6 Out Time - Return Time
Range 0 to 3600 seconds.
For IQ actuators, out time and return time must be set to the same value. They are used to ensure that the partial stroke test is completed in a quantified period of time. Alarms can be set to indicate a failure in meeting the set time, indicating a valve problem.
Measure or calculate the time to complete the set partial stroke test. Add 10% to this value then half it. The resulting time should be entered into both Out Time and Return Time.
To change, time will be indicated.
. The set partial stroke out/return
6/6 Test
To initiate a partial stroke test using the Setting Tool, the actuator must be set to Local control using the red selector and at the limit position set for 2/6 From Limit.
To initiate a partial stroke test, . The partial stroke test will be initiated as set.
20 IQ3 Full Confi guration Ma nual – Sect ion: Settin gs
2.3.2-4 Control – Remote – Positioning
Hardwired Control Source Partial Stroke
Positioning
Auxiliary Mask Analogue
Remote Control
Positioning
Deadband 5%
Hysteresis 2% Inhibit Time (s) Low Signal Pos. 0% High Signal Pos. 100%
1/5
2
The Positioning option settings page with its default settings is shown above.
Applicable for Analogue and HART control options and for all Network control options where positioning control is required. Settings are used to tune the actuator positioning response.
• Deadband and Hysteresis are combined to set positioning accuracy.
• Inhibit Time is used to set a dwell in the actuators response.
• Low/High Signal Position sets the range of the valve stroke where positioning is required.
1/5 Deadband
Range 0% - 25.5%. Default setting: 5%.
Affects positioning accuracy as a response to the process control system desired value (DV) signal position. A smaller deadband increases accuracy, however the widest deadband should be set whilst maintaining good control in order to protect the mechanical valve from excessive wear and/or to keep the actuator within its electrical rating.
Deadband setting should be combined with 2/5 Hysteresis setting. The actuator will run towards the DV position until the actual position is within the set deadband minus the hysteresis setting. This has the effect of the actuator stopping nearer to the DV position. The actuator will not restart unless it overshoots and runs outside the deadband or a new command places the new desired position outside the deadband. Refer to figure 2.3-1.
To change, deadband setting.
. The slider control will indicate the
2/5 Hysteresis
Range 0% - 25.5%. Default setting: 2%.
Affects positioning accuracy as a response to the process control system desired value (DV) signal position. A larger Hysteresis setting will increase accuracy but the value set must not be greater than that set for Deadband.
Hysteresis setting should be combined with 1/5 Deadband setting. The actuator will run towards the DV position until the actual position is within the set deadband minus the hysteresis setting. This has the effect of the actuator stopping nearer to the DV position. The actuator will not restart unless it overshoots and runs outside the deadband or a new command places the new desired position outside the deadband. Refer to figure 2.3-1.
To change, hysteresis setting.
. The slider control will indicate the
3/5 Inhibit Time
Range 0 – 255 seconds. Default setting: 5 seconds.
Sets a delay after the actuator stops as a result of reaching a position consistent with a new DV position. For the period set, the actuator will not respond to a change in DV. Inhibit time is used to prevent unwanted operation as a result of a rapidly oscillating or fluctuating DV signal or to slow actuator response in order to protect the mechanical valve from excessive wear and/or maintain actuator within its electrical rating.
To change,
. The time set will be indicated.
IQ3 Full Confi guration Man ual – Secti on: Setting s 21
Loading...
+ 47 hidden pages