Rotork IQM, IQML User Manual

Page 1
‘IQM’ & ‘IQML’ RANGE
Publication E420E issue 7/02
CONTROL AND
MONITORING
FACILITIES
Page 2
SPECIFICATION
The type IQM actuator specification is generally as described in Publication No. E410E having a solid state reversing starter in place of the electro-mechanical contactors, suitably rated 4­pole winding, low inertia motor and with the “hammerblow” backlash omitted from the output gear train.
All other standard and optional IQ actuator features are available with IQM modulating actuators subject to the following:
Supply Voltage - maximum 480 volts, 50/60Hz.
Apply for higher voltages up to 575 volts.
Minimum voltage for the size IQM30 is 380 volts, 50/60Hz.
PERFORMANCE
The actuators are suitable for up to 1200 starts per hour with a duty in accordance with IEC 34-1 to S4 50%. See E410E for temperature rating.
SOLID STATE STARTER
The actuator design incorporates a solid state starter to achieve an increased design life. Five pairs of 1600 volt thyristors switch all three phases of the incoming power supply. Thyristors are considered to be more suitable than triacs for reversing applications and have a higher resistance to transients in the power supply.
The design also includes snubbing and transient protection circuits.
DYNAMIC BRAKING
The facility for dynamic braking is included as standard with the ability to select this function by fitting an electrical link at the actuator terminal block.
POSITIONAL ACCURACY
Repeatability with pulse control is 0.1 output turns.
POWER FUSE
It is essential that the power supply for each actuator is protected by suitably rated high speed fuses mounted at the power distribution panel. The required fuse characteristics are as follows:
IQM10 to IQM20 IQM25 and IQM35
Rated current 10A 20A Pre-arcing 1
2
t 5.4 A2s1
2
t 30 A2s
Total 12t 55 A2s1
2
T 250 A2s Rated voltage 660V (IEC) 660V (IEC) Suggested fuse Ferraz G330010 Ferraz K330013
CIRCUIT DIAGRAM
Standard IQM actuators are in accordance with wiring diagram 5000-000 as shown on page 6.
For aplications requiring seperately mounted starters, please see details of M Range Syncroset actuators given on page 11.
CONTROL
Opto-isolators are used to interface the actuator’s internal logic circuits with the remote controls. The basic circuits permit various control facilities to be selected whether internally or externally fed. As standard the actuators are designed for positive switching remote control from digital signals.
Various control functions may be configured on site at the time of commisioning using the Rotork IQ Setting Tool. In the absence of specific instructions, actuators will be dispatched with the control functions configured as shown on the diagram on page 6.
PULSE CONTROL
Where pulse control is used the minimum pulse length should be 18ms and the minimum time between pulses should be 500ms. Typical duration of motor energisation in response to each minimum pulse control signal in the same direction will be between 20 and 30ms. Where special units designed for use with AC remote control supplies are required, the minimum pulse length should be 300ms.
REMOTE CONTROL POWER SUPPLIES
Remote controls may be powered by the internally derived 24 volt DC power supply. Alternatively remote controls may be powered by an external supply of 24DC. The appropriate connections are shown on page 6. Please apply if suitability for other remote control supplies is required.
LOCAL CONTROLS
The actuator is provided with Open, Close and Stop facilities and Local/Remote selection, Local, Open and Close control is configurable to either self-maintained or push-to-run.
EXTERNAL INTERLOCKS
Facilities are provided for the connection of external contacts to inhibit Open and/or Close valve operation.
STATUS FEEDBACK
Four configurable status feedback contacts and monitor relay are available as standard with IQM actuators.
PROTECTION
The motor is protected against single phasing or incorrect phase rotation by the Rotork patented, Syncrophase circuit and against overheating by the thermostat in the motor winding. Opto-isolators provide protection against high voltage transients for the interface with the remote controls.
EMERGENCY SHUTDOWN (ESD)
The ESD facility may be configured for Open or Close operation with the option of by-passing the motor protection thermostat, using the IQ Setting Tool.
IQM - STANDARD FACILITIES
Page 3
3
OPTIONAL FACILITIES
The following optional facilities are available, and are covered by the appropriate alternative wiring diagrams as indicated in the wiring diagram number matrix on page 5.
FOLOMATIC CONTROLLER
The Folomatic enables standard IQM actuators to control the position of a valve in proportion to an analogue current or voltage signal.
A voltage derived from the actuator position sensor is electronically compared with a voltage proportional to the input signal. The difference between them (error) triggers the open or close thyristor circuit, via logic circuits, to drive the actuator in the direction which will cancel the error. Valve position is therefore automatically adjusted in proportion to analogue signal. Unnecessarily frequent switching is prevented by the Motion Inhibit feature.
The Folomatic can be configured to suit the following:
Analogue signals/ 0-5mA/1k ohm 0-5v/1 M ohm input impedence: 0-10mA/500 ohm 0-10v/78 kohm
0-20mA/250 ohm 0-20V/52 kohm
Position corresponding Closed limit, or percentage Open to low input signal: or Open limit.
Position corresponding Closed limit, or percentage Open to high imput signal: or Open limit.
Deadband: 0-9.9% of travel between Open
and Closed limit positions.
Motion Inhibit time: 2-99 secs. between actuator
movements.
Action on loss of Stay-put or move to high signal input signal: position or move to low signal
position. Available for minimum set ‘low’ signal of 0.5mA. Response on loss of signal will occur if signal falls below 50% of set ‘low’ signal.
Overall accuracy (actuator 0.5% of maximum signal with mechanical output position/
dynamic braking and minimum
demand value): of 10 turns for full valve stroke,
assuming a deadband setting of <0.2%.
CONNECTIONS
The analogue signal should be connected to terminals 26 (+ve) and 27 (-ve). If no remote manual control is required, link terminals 39 to 5 and 41 to 4. Terminal 39 is provided for remote manual/auto selection. The remote control connections for actuators to standard wiring diagrams are as follows:
CURRENT POSITION TRANSMITTER (CPT)
The CPT provides an internally powered electrically isolated 4­20mA analogue valve position feedback signal, which is available at terminals 22 (+ve) and 23 (-ve). The maximum external impedence that may be connected to the signal is 500 ohms. Repeatability is within ±1% and linearity ±2.5% of total valve travel.
ALARM RELAYS
A set of three alarm relays can be provided with the following functions:
Relay 1 ‘Battery low’ signal (Normally open contact
rated for 5A 250 volts AC, 30 volts DC).
Relay 2 ‘Thermostat tripped’ signal (change-over
contact rated for 30 Watts, 62.5VA, 110 Volts).
Relay 3 ‘Remote selected’ signal (contact as Relay 2)
The following optional facilities available on standard IQ actuators are also available on IQM units.
Negative Switching (see publication E120E) Interrupter Timer (see publication E120E) Pakscan (see publication S000E)
IQM - OPTIONAL FACILITIES
Page 4
4
IQM - ACTUATOR CONTROL CIRCUITS
BASIC IQM ACTUATOR WIRING DIAGRAM 5000-000
Positive switching remote controls. Refer to Rotork for non­standard voltage option. Circuit is drawn with power supply off.
Transformer Tapping Options
Type 1
TAP NOM 50/60HZ 50HZ 60HZ
W 220/230 176-242 198-259
X 380/400 304-418 342-446
Y 415/420 332-457 374-487
Z 440/460 352-484 396-517
Fuse FS1 - 250mA Anti-Surge
Type 2
TAP NOM 50/60HZ 50HZ 60HZ
W 346/380 285-388 321-419
X 480/500 406-552 432-564
Y 240/240 192-261 216-282
Z* 550/575 445-605 501-654
Fuse FS1 250mA Anti-Surge
NOTE *150mA Anti-Surge
The actuator must be protected using suitably rated high speed semi-conductor fuses on the incoming supply. Suggested fuses:-
IQ10-20: 10 Amp Ferraz G330010 IQ25-35: 20 Amp Ferraz K330013
All transformer types - PS1 Self resetting fuse
NOTE
Where customers wish to have the thermostat by-passed during emergency shutdown operation, it should be noted that any actuator hazardous enclosure certification will be invalidated while the thermostat is by-passed.
Max external load on terminals 4&5 to be 5W.
For typical remote control indicating,monitoring and alarm circuits see publication E420E
Control signal threshold voltages to be minimum ‘ON’ 20V AC/DC maximum ‘OFF’= 3V minimum control signal duration to be 100mS.
Current drawn from each remote control signal is 5mA on 24V DC
Wires are identified at each end by terminal No. or tag No.
Iindication contacts S1-S4 are shown in their default configuration. Contacts may be configured for any of the functions described in E170E.
OPEN
%
S4
S1
S2
S3
MONITOR
RELAY
SK.3
SK.1
SK.4
2
1
3
1
2
3
4
5
6
7
8
24
30
SK.14
SK.10
SK2
SK1 SK4
SSS MODULE
SK9
SK11
MOTOR
3456
2A 2B
1
LK1
U
V
U
W
XWYZ
24V DC SUPPLY
0V DC SUPPLY
3
24VDC
0VDC
24VDC
NOMINAL SUPPLY
2
1
5
4
1
5
4
PS1
W
U
V
1
3
2
SK.1
SK.3
FS1
E
3 PHASE SUPPLY
CIRCUIT DRAWN WITH POWER SUPPLY OFF
9
7
10
13
11
12
8
6
43
44
42
SK.12SK.1
LOCAL
CONTROL
PCB
SK.7
SK.9
2
1
LIMIT
PCB
SENSING
SK.1
-
+
BATTERY
FS2 100mA(ONLY FITTED ON CENELEC ACTUATORS)
32
31
38
25
36
34
37
40
35
33
T/STAT BYPASS - ESD
OPEN
CLOSE INTERLOCK
OPEN INTERLOCK
STOP/MAINTAIN
CLOSE
COMMON -VE 24V DC
COMMON -VE 24V DC
SK.2
SK.8
3
4
2
1
5
1
4
3
5
2
TORQUE SENSOR
4
5
SK.6
SK.5
FS2
INFRA-RED
DIGITAL POSITION
INDICATION UNIT
2W
1
V
U
1pm 2pm 3pm
3
MAKE AT FULLY
SHUT
MAKE AT FULLY
OPEN
BREAK AT FULLY
SHUT
BREAK AT FULLY
OPEN
Page 5
5000-000 5100-000 5000-100 5100-100
5010-000 5110-00 5010-100 5110-100
5
IQM - OPTIONAL FEATURES
STANDARD ACTUATOR DIAGRAMS
The typical remote control interlock and monitoring circuits illustrated are applicable to actuators with the following standard Rotork wiring diagrams.
NOTES
1 Data logger - diagram number changes to ‘1’ for fifth digit, e.g. 600-000 becomes 600-010.
2 For negative switching - diagram number changes to ‘7’ for first digit, e.g. 600-000 becomes 700-000.
IQ SETTING TOOL
The IQ Setting Tool makes it possible to read and set all the actuator functions, such as valve travel and torque or travel limit control, without removing any covers. The IQ Setting Tool transmits signals to an infra-red receiver built into the actuator.
The IQ Setting Tool has a ‘programming’ mode which enables the valve manufacturer to configure the actuator to suit his valve and the site commisioning engineer to configure the actuator for a variety of different control functions. The IQ Setting Tool also has a ‘checking’ mode which enables all the existing actuator settings to be interrogated. Protection against unauthorized changes to setting is provided by a ‘password’.
CONFIGURATION
The following actuator functions are configured by the IQ Setting Tool:
Direction of actuator output rotation for closing the valve.
Selection of torque or turns limitation for valve opening and closing travel.
Torque setting for Open and Close valve operation.
Setting of actuator output turns to suit the valve travel.
“Open/close” remote control signal priority.
Selection of function and contact mode for each of the four standard indication contacts.
Valve to Open or Close with ESD signal.
External interlock facility.
The standard configuration for the IQM actuator is given on page 6.
In addition, the IQ Setting Tool will enable configuration of the following optional assemblies when fitted to the actuator:
CPT - selection of open or closed valve position corresponding to a maximum signal.
Pakscan - address, baud rate and protocol.
Folomatic - signal range, increasing signal is to correspond to opening or closing of the valve, action on loss of signal,
amount of deadband and the motion inhibit time delay.
Publication E170E, supplied with each actuator gives full instructions for the operation of the IQ Setting Tool.
Page 6
6
IQM - REMOTE DIGITAL CONTROL CIRCUITS
The infra red setting tool enables various different remote controls to be configured. Unless specified requirements are stated with the order, actuators will be supplied configured as follows:
Maintained local control
Clockwise to close
Thermostat by-passed on ESD
Open and closed interlocks enabled
Close signal priority
The typical remote control circuits shown below apply to these unless otherwise stated.
Max. external load on 24v DC supply from acutuator terminals 4 - 5 to be 5W.
Form A
Open/close push to run control (local control remains self maintained).
Form F
Emergency shut-down to close valve overriding thermostat (actuator hazardous enclosure certification is invalidated while thermostat overidden) and any existing signal may be added to any of the circuits above.
Actuators may be configured so that thermostat is not by-passed during ESD operation.
To override external interlocks on ESD additional remote contacts must be provided.
Brake enable connections
† Note
Remote controls may be fed from the internal 24V DC supply at terminal 5 when terminals 4-36 must be linked, or from an external supply when the zero/-ve of the supply should be connected to terminal 36.
Terminals 4-36 also to be linked for form A and F control.
The input to the IQ series actuator logic circuits associated with the remote controls may be used with cable capacitance of up to 2µF between cores.
Page 7
7
IQML10 TO IQML25 ACTUATOR DIMENSIONS
IQML10 IQML25
Page 8
As part of a process of on-going product development, Rotork reserves the right to amend and change specifications without prior notice.
Published data may be subject to change.
For the very latest version release, visit our website at www.rotork.com
The name Rotork is a registered trademark. Rotork recognizes all registered trademarks. Published and produced in the UK by Rotork Controls Limited.
A full listing of our worldwide sales and service network is available on our website at
www.rotork.com
UK head office
Rotork Controls Limited
telephone Bath 01225 733200 telefax 01225 333467 email mail@rotork.co.uk
USA head office
Rotork Controls Inc
telephone Rochester (585) 328 1550 telefax (585) 328 5848 email info@rotork.com
Rotork Controls Ltd, Bath, UK
Rotork Controls Inc, Rochester, USA
‘IQM’ & ‘IQML’ RANGE
CONTROL AND
MONITORING
FACILITIES
Loading...