Rotel RMZ-955 User Manual

Page 1
MULTI-ZONE CUSTOM CONTROLLER RMZ-955
MULTI-ZONE CUSTOM CONTROLLER RMZ-955
POWER
POWER
RMZ-955
MULTI-ROOM
SYSTEM
DIGITALLY CONTROLLED AUDIO PROCESSING
DIGITALLY CONTROLLED AUDIO PROCESSING
ZONE A
ZONE A
ZONE B
CODE
CODE
ZONE B
CODE
CODE
ZONE C
ZONE C
ZONE D
CODE
CODE
ZONE D
CODE
CODE
I.R. TRANSMITTER
I.R. TRANSMITTER
Installation & Operation
Manual
Operating
Instructions
begin on Page 23
1
Page 2
MULTI-ROOM SYSTEM CONTROLLER RMZ-955
CAUTION
RISK OF ELECTRIC SHOCK
DO NOT OPEN
CAUTION: TO REDUCE THE RISK OF ELECTRIC SHOCK, DO
NOT REMOVE COVER. NO USER-SERVICEABLE PARTS INSIDE.
REFER SERVICING TO QUALIFIED SERVICE PERSONNEL.
APPLICABLE FOR USA, CANADA OR WHERE APPROVED FOR THE USAGE
CAUTION: TO PREVENT ELECTRIC SHOCK, MATCH WIDE BLADE OF PLUG TO WIDE SLOT. INSERT FULLY.
ATTENTION: POUR EVITER LES CHOCS ELECTRIQUES, INTRODUIRE LA LAME LA PLUS LARGE DE LA FICHE DANS LA BORNE CORRESPONDANTE DE LA PRISE ET POUSSER JUSQU AU FOND.
This symbol is to alert the user to the presence of uninsulated dangerous voltages inside the product's enclosure that may constitute a risk of electric shock.
This symbol is to alert the user to important operating and maintenance (service) instructions in this manual and literature accompanying the product.
WARNING: There are no user serviceable parts inside. Refer all servicing to qualified service personnel.
WARNING: To reduce the risk of fire or electric shock, do not expose the RMZ-955 to moisture or water. Do not allow foreign objects to get into the enclosure. If the unit is exposed to moisture, or a foreign object gets into the enclosure, immediately disconnect the power cord from the wall. Take the unit to a qualified service person for inspection and necessary repairs.
Read all the instructions before connecting or operating the RMZ-955 . Keep this manual so you can refer to these safety instructions.
Heed all warnings and safety information in these instructions and on the product itself. Follow all operating instructions.
Clean the RMZ-955 only with a dry cloth or a vacuum cleaner.
Keep the ventilation inlets on the unit unobstructed. For example, do not place the unit on a bed, sofa, rug, or similar surface that could block the ventilation slots. If the RMZ-955 is placed in a bookcase or cabinet, there must be suffi­cient clearance around the unit and ventilation of the cabinet to allow proper cooling.
Keep the RMZ-955 away from radiators, heat registers, stoves, or any other appliance that produces heat.
The RMZ-955 must be connected to a power supply only of the type and volt­age specified on the rear panel of the unit.
Connect the RMZ-955 to the power outlet only with the supplied 3-pin polarized grounded power supply cable or an exact equivalent. Do not modify the sup­plied cable in any way. Do not attempt to defeat grounding and/or polarization provisions. The cable should be connected to a 3-pin polarized grounded wall outlet, matching the wide blade of the plug to the wide slot of the receptacle. Do not use extension cords.
Do not route the power cord where it will be crushed, pinched, bent at severe angles, exposed to heat, or damaged in any way. Pay particular attention to the power cord at the plug and where it exits the back of the unit.
The power cord should be unplugged from the wall outlet if the unit is to be left unused for a long period of time.
Immediately stop using the RMZ-955 and have it inspected and/or serviced by a qualified service agency if:
• The power supply cord or plug has been damaged.
• Objects have fallen into or liquid has been spilled into the unit.
• The unit has been exposed to rain.
• The unit shows signs of improper operation
• The unit has been dropped or damaged in any way
Place the RMZ-955 on a fixed, level surface strong enough to support its weight. Do not place the RMZ-955 on a moveable cart that could tip over.
MULTI-ZONE CUSTOM CONTROLLER RMZ-955
MULTI-ZONE CUSTOM CONTROLLER RMZ-955
DIGITALLY CONTROLLED AUDIO PROCESSING
POWER
POWER
ZONE A
ZONE A
CODE
CODE
ACTIVE
ACTIVE
~
~
2 3 41
2 3 41
L
L
R
R
IN OUT IN OUT IN OUT IN OUT
IN OUT IN OUT IN OUT IN OUT
ACTIVE
ACTIVE
UNSWITCHED SWITCHED
UNSWITCHED SWITCHED
INPUTS
INPUTS
ZONE B
ZONE B
CODE
CODE
PAGING
PAGING
TRIGGER
TRIGGER
AUDIO IN
AUDIO IN
AUDIO OUT
AUDIO OUT
ACTIVE
ACTIVE
LINK IN
LINK IN
LINK OUT
LINK OUT
LEFT RIGHT
LEFT RIGHT
–+–+
–+–+
ZONE C
ZONE C
CODE
CODE
MULTI-ZONE CUSTOM CONTROLLER
MULTI-ZONE CUSTOM CONTROLLER
MODEL NO. RMZ-955
MODEL NO. RMZ-955
POWER CONSUMPTION: 430W
POWER CONSUMPTION: 430W
AC120V
AC120V
DESIGNED AND MANUFACTURED
DESIGNED AND MANUFACTURED
ZONE D
ZONE D
PRE-OUT
PRE-OUT
DATA
DATA
123456
123456
~ 60HZ
~ 60HZ
IN ENGLAND
IN ENGLAND
PRE-OUT
PRE-OUT
123456
123456
ACTIVE
ACTIVE
ZONE D
ZONE D
ZONE C
ZONE C
DATA
DATA
CODE
CODE
SPEAKER IMPEDANCE
SPEAKER IMPEDANCE
LEFT RIGHT
LEFT RIGHT
–+–+
–+–+
CAUTION
CAUTION
CAUTION
RISK OF ELECTRIC SHOCK
RISK OF ELECTRIC SHOCK
RISK OF ELECTRIC SHOCK
DO NOT OPEN
DO NOT OPEN
DO NOT OPEN
4 OHM MINUMUM
4 OHM MINUMUM
SPEAKERSSPEAKERS
SPEAKERSSPEAKERS
LEFT RIGHT
LEFT RIGHT
–+–+
–+–+
DIGITALLY CONTROLLED AUDIO PROCESSING
I.R. TRANSMITTER
I.R. TRANSMITTER
WARNING:
WARNING:
OF FIRE OR ELECTRICAL SHOCK DO
OF FIRE OR ELECTRICAL SHOCK DO
NOT EXPOSE THIS EQUIPMENT TO
NOT EXPOSE THIS EQUIPMENT TO
RAIN OR MOISTURE.
RAIN OR MOISTURE.
ZONE B
ZONE B
PRE-OUT
PRE-OUT
DATA
DATA
123456
123456
TO REDUCE THE RISK
TO REDUCE THE RISK
RC-5N/C
RC-5N/C
RC-5N/C
PRE-OUT
PRE-OUT
123456
123456
DATA
DATA
ZONE A
ZONE A
SPEAKERSSPEAKERS
SPEAKERSSPEAKERS
LEFT RIGHT
LEFT RIGHT
–+–+
–+–+
WE1
WE1
WE2
WE2
WE3
WE3
WE4
WE4
TX-FORMAT
TX-FORMAT 123456
123456
T
T
X
X
O
O
U
U
T
T
P
P
U
U
T
T
S
S
2
Page 3
CONTENTS
Getting Started 4
Controlling the Remote Zones 4 System Flexibility 4 System Highlights 4
Component Description _______________________________ 4
RMZ-955 Controller/Amplifier 4
System Planning _____________________________________ 4
RR-952 IR Remote Control 5 RSM-901 Sensor/Display 5 RKP-901 Keypad 5 RSM-901/RKP-901 Combination 5 Placement 6 Connections: 6 IR Flood Emitter 6 IR Repeater Jacks 6
System Wiring Considerations ________________________ 6
Data Cable and Connectors 6 Speaker Cables 7
Zone Configuration ___________________________________ 7
Basic Zone Complement 7 Loudspeakers 7
Installation: RMZ-955 Controller 8
RKP-901 Keypad _____________________________________ 17
RKP-901 Mounting 17 RKP-901 Data Connections 17
Zone Connection Strategies __________________________ 18
Installation: Multi-controller Systems 18
AC Power ___________________________________________ 20
AC Connections 20 AC Link 20 Manual AC Override 20
Source Connections _________________________________ 20 IR Connections ______________________________________ 21
For 2 RMZ-955s (5 to 8 zones): 21 For 3 RMZ-955s (9-12 zones): 21 For 4 RMZ-955s (13-16 zones): 22 Exception: Multiple IR Flood Emitters 22 Paging Connections 22
Notes on multi-controller set-up ______________________ 23
Power Toggle Set-up 23 Source Component Set-up 23 “Engaged” Indicator 23
System Set-up & Programming 24
AC Line Connections _________________________________ 8
AC for the RMZ-955 8 AC for Source Components 8 Rotel RLC-900 AC line conditioner/switcher 8 Special AC features 8
Source connections __________________________________ 9
Source inputs 9 Source outputs 9
Speaker Connections ________________________________ 10 Preamp outputs _____________________________________ 11
Variable vs. Fixed Level 11
Data cable connections ______________________________ 12 Infrared Control System _____________________________ 13
Front Panel IR Flood Emitter 13 Rear Panel IR Repeaters 13
Paging Input ________________________________________ 14
Paging Inhibit 14
Installation: Zone Control Devices 15
RSM-901 Sensor/Display _____________________________ 15
RSM-901 Mounting 15 RSM-901 Data Connections 16 Battery Enable 16 Zone Configuration 16 Source Component Labels 16 Master/Slave Configuration 16 System Reset 17 Source Component Set-up 17
Source Commands __________________________________ 24 Source Command Set-up ____________________________ 24 Power Toggle _______________________________________ 25
Operating Instructions 26
RR-952 Hand-held Remote ___________________________ 26
Input Selector Buttons 26 Tuner control buttons 26 CD control buttons 27 Tape/Satellite TV control buttons 27 Video/LD control buttons 27 Mute 27 VOLUME UP/VOLUME DOWN 27 STBY 27 “X” 27
RKP-901 Keypad _____________________________________ 28
Input Select commands 28 System commands 28 Source Control Commands 28
RSM-901 Sensor/Display _____________________________ 29
Controls and Displays 29 Dot Matrix Display 29 Setting Alarm, Time, and Custom Functions 30
For Assistance ______________________________________ 31
3
Page 4
MULTI-ROOM SYSTEM CONTROLLER RMZ-955

Getting Started

The Rotel RMZ-955 Multi-Room Control System distributes audio signals from a single set of source components to as many as four separately controlled remote zones or listening areas. The centrally located RMZ-955 controller/amplifier contains source selection, microprocessor controlled communications circuitry and independent preamplifier/power amplifiers for all zones.
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

Component Description

RMZ-955 Controller/Amplifier

MULTI-ZONE CUSTOM CONTROLLER RMZ-955
MULTI-ZONE CUSTOM CONTROLLER RMZ-955
DIGITALLY CONTROLLED AUDIO PROCESSING
POWER
POWER
DIGITALLY CONTROLLED AUDIO PROCESSING

Controlling the Remote Zones

Users can select either of two ways to control remote zone op­eration. The first is the RR-952 hand held remote. This generates infrared (IR) control pulses read by the wall-mounted RSM-901 sensor/display. The RSM-901 sensor/display then transmits com­mands to the RMZ-955 through hard-wired connections.
The second method uses the wall-mounted RKP-901 keypad to transmit commands directly to the RMZ-955. The RKP-901 is also hard-wired to the RMZ-955 controller/amplifier.
Users can select a combination of sensor and keypad operation for any zone. The system accepts inputs from up to three sensor/ displays and three keypads (for a total of six input devices) per zone.

System Flexibility

The Rotel RMZ-955 Multi-Room Control System is exceptionally flexible. In addition to the RMZ-955 controller/amplifier, a simple two zone system might include just one RR-952 hand held con­troller/RSM-901 IR sensor/display combination for one zone and one RKP-901 keypad in the second.
In a more elaborate configuration, a single RMZ-955 accepts commands from four separate zones via twelve IR sensor/dis­plays and twelve keypads.
Up to four RMZ-955 controllers can be linked together for a sys­tem with as many as sixteen independent zones.

System Highlights

• Keypad or handheld remote operation of source components. No programming required – built-in codes for Rotel and other popu­lar components.
• Single button operation for source selection and “play”.
• Full user control, including system standby from any zone.
ZONE B
ZONE A
ZONE A
CODE
CODE
ACTIVE
ACTIVE
ZONE B
CODE
CODE
ACTIVE
ACTIVE
ZONE C
ZONE C
CODE
CODE
ACTIVE
ACTIVE
ZONE D
ZONE D
CODE
CODE
ACTIVE
ACTIVE
I.R. TRANSMITTER
I.R. TRANSMITTER
The RMZ-955 Controller/Amplifier is the heart of the RMZ-955 Multi-Room Control System, featuring:
• Four separate microprocessor-controlled stereo preamplifier/ power amplifier sections, one for each remote zone
• RCA inputs for up to four sources
• “Loop through” RCA outputs which allow multiple RMZ-955 con­trollers to be linked together for large systems up to 16 zones.
• RCA line level preamp outputs for use with external amplifier systems. These outputs can be internally configured to provide a variable level signal or a fixed level signal.
• Screw-type quick connect speaker outputs
• Control data input for each zone is via industry-standard 6 pin Methode connectors
• 3.5 mm stereo jack “AC Link” connections for full system control from any zone in large, multi-controller systems
• RCA output jack for RC-5 remote control protocol components
• High power front panel IR flood emitter to transmit remote zone commands to associated source components
• Four mini-plug IR repeater outputs
• Two polarized AC convenience outlets with 100 watts capacity each: one switched to allow easy remote control of total system power if desired, the other unswitched
• Front panel LED indicators for Power On/Off, zone status, com­mand pulse processing
• Built-in Paging input with muting in selected zones.
• Near-universal Infra-red repeating system. Remote control avail­able even when a zone is not active.
• Alarm clock function with independent wake-up in each zone.
4
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

System Planning

The RMZ-955 is designed to be used as a stand-alone control center for a multi-zone distribution system using dedicated source components. It features loop-through source connec-
Page 5
GETTING STARTED

RR-952 IR Remote Control

The RR-952 infrared remote control serves a dual purpose. In ad­dition to providing dedicated pushbuttons for the most needed functions of both the RMZ-955 controller/amplifier and source components, it also serves as a quick set-up tool during initial configuration.
The RR-952 has a special high intensity IR transmitter. In con­junction with the system’s sensitive receiver modules, this trans­mitter assures reliable operation under a wide variety of conditions.

RSM-901 Sensor/Display

You’ll find details of the display in the Set Up and Operation sec­tions of this manual.
NOTE: An RSM-901 connected to the Zone A data input MUST be used during initial set-up.

RKP-901 Keypad

The RKP-901 is a wall-mounted keypad for convenient remote operation of the entire system. The keypad can be used as a stand-alone control device, although it is most functional when installed with the RSM-901 sensor-display. Its 12 key design is the optimum balance between flexibility and simplicity, providing single-key control of the system and source components (select­ing and starting a CD player, for example). In addition, the RKP-901 allows total system shut-down from a remote location. It mounts conveniently in a standard single width wall box or in a dual width box with a RSM-901 sensor/display. (see page 25)
The wall-mounted RSM-901 Sensor/Display receives commands from the RR-952 hand held remote and, after processing to en­sure maximum data integrity, sends these codes to the RMZ-955 controller/amplifier.
In addition, the RSM-901 provides continuous system status in­formation (source, time, volume setting, etc.) at each remote lo­cation with a dot matrix display. Also available is a programmable alarm function.

RSM-901/RKP-901 Combination

Mounting both the sensor/display and keypad in one double­width wall box carries several advantages. It simplifies the in­stallation. It also focuses the user on one location in each zone, i.e. walk to the keypad or aim the hand held remote control at the same wall-plate.
5
Page 6
MULTI-ROOM SYSTEM CONTROLLER RMZ-955
tions which allow linking additional RMZ-955 controllers for large systems. Depending on the design of the associated compo­nents, these pass-through source connections may alternatively be used to “share” source components with a separate home theater or audio system.

Placement

Place the RMZ-955 on a stable surface in an equipment rack or cabinet. Note that the RMZ-955 is slightly deeper than most source components (tuners, CD players, cassette decks, etc.) and should not generally be placed on top of these units.

Connections:

Make sure that you have enough room to run all the connecting cables and dress them appropriately behind the RMZ-955. Al­though we’ll explain each connection fully in following sections of this manual, glance through the following list of possible con­nections and decide how much space you’ll need.
a) Four pair of RCA interconnects – one pair from each source.
b) Eight heavy gauge speaker cables (two for each zone).
c) Four six-conductor + shield data cables, each terminated with
the proper IDC strip connector.
If the RMZ-955 is on an open shelf, the emitter’s signal must first travel to an IR-reflective surface (an opposing wall, for example) and then to the source component.
20 feet or less
AM/FM Tuner
Cassette Deck
CD Player
DVD Player
RMZ-955 controller
Keep total IR signal travel to 40' or less. Remember that it must travel to a hard reflective surface and back again.
Note: If an RSM-901 sensor display is located in the same room as the RMZ-955 controller, it is essential that the output form the front-panel IR flood emitter NOT reach the RSM-901 sensor. IR loop problems can cause intermittent operation.
d) One shielded RCA to RCA interconnect for RC-5 remote control
code connection.
e) One pair of RCA to RCA interconnects to power amplifiers from
each corresponding zone’s “Pre-out” terminals.
f) Up to four mini-plug (3.5 mm) cables from the RMZ-955’s “Infra
Red” outputs to remote IR transmitters.
g) Four more pair of RCA to RCA interconnect cables – one each to
the appropriate input of the next RMZ-955 in large multi-control­ler systems.
h) Additional loudspeaker connections as required for systems us-
ing more than one RMZ-955 controller/amplifier.
i) 3.5 mm to 3.5 mm cable for AC “link” connections as required for
systems using more than one RMZ-955 controller/amplifier.
j) Up to six “TX-FORM” terminal block jumper wires needed when
cascading multiple RMZ-955 controller/amplifiers.
We STRONGLY RECOMMEND that you attach a tag or strip to each cable and wire to identify it (e.g. “To Input 3 from tape deck.”). This will help in troubleshooting as well as make future service calls or system add-ons much less frustrating.

IR Flood Emitter

The RMZ-955 has a high intensity front panel IR flood emitter de­signed to transmit commands from the remote zones to the ap­propriate source component. Although exact performance will vary, this high power transmitter has an effective operating range of approximately 40' under normal conditions.
6

IR Repeater Jacks

The RMZ-955 also has four rear panel IR output jacks for use with industry standard IR repeaters (made by Xantech and oth­ers). The use of these external repeaters on each source compo­nent is ideal in situations where output from the front panel flood IR emitter is blocked from the source components by a door, full depth shelf, etc. It is also an ideal solution when the front panel flood emitter output could reach an RSM-901. When IR repeaters are used, the front-panel flood emitter can be easily disabled.
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

System Wiring Considerations

Data Cable and Connectors

The data path between the RMZ-955 controller/amplifier and RSM-901 sensor/displays and RKP-901 keypads must be made with cable with six insulated conductors plus a foil and/or braided outer shield. We recommend a Belden 9536 equivalent for best results. The RMZ-955 system data connectors work only with cables using 24 gauge conductors. Make sure that all data cables conform to this requirement.
Data cable termination is via industry-standard 6 pin IDC connectors made by Methode and others. (The Methode part number is 1300-106-424.) Data cable connection instructions are found in the
Installation
section of this manual (see page 9).
Page 7

Speaker Cables

Unshielded two conductor 18 gauge (AWG) speaker wire is the minimum acceptable standard for connections between the RMZ-955 controller/ amplifier and zone loudspeakers. Par­ticularly long runs may call for use of heavier wire.
○○○○○○○○○○○○○○○○○○○○

Zone Configuration

Basic Zone Complement

Each remote zone must include at least one control device and a pair of loudspeakers. The control device may be a RR-952 hand held remote and an RSM-901 sensor/display combination. Or it can be a RKP-901 keypad, either stand-alone or with a RSM-901.
MULTI-ZONE CUSTOM CONTROLLER RMZ-955
MULTI-ZONE CUSTOM CONTROLLER RMZ-955
POWER
POWER
GETTING STARTED
AM/FM Tuner
CD Player
Tape Deck
LD/DVD Player
DIGITALLY CONTROLLED AUDIO PROCESSING
DIGITALLY CONTROLLED AUDIO PROCESSING
Remember that the RSM-901 sensor/ display also provides useful visual clues to total system operation and ad­ditional convenience features. Most zones will use multiple control devices, with the combination of one RSM-901 sensor/display, one RKP-901 keypad, and one RR-952 being the most com­mon.
The RSM-901 sensor/display reads in­frared signals generated by the RR-952 hand held remote and, after translating them into a digital code that is highly resistant to interference, sends them to the RMZ-955 controller/amplifier. The RKP-901 simply translates key pushes into digital code before send­ing them to the controller/amplifier.

Loudspeakers

These will vary with installation requirements and user expectations. The RMZ-955’s amplifier sections are optimized for impedance loads of four ohms or higher.
ZONE B
ZONE A
ZONE A
CODE
CODE
ACTIVE
ACTIVE
ZONE B
CODE
CODE
ACTIVE
ACTIVE
ZONE C
ZONE C
CODE
CODE
ACTIVE
ACTIVE
ZONE D
ZONE D
CODE
CODE
ACTIVE
ACTIVE
I.R. TRANSMITTER
I.R. TRANSMITTER
Living Room
RECEIVE
CD
TUNER
AUX
TUNER
TUNER
CD
CD
TAPE/SAT
TAPE/SAT
VIDEO/LD
VIDEO/LD
FAV STN
FAV STN
STOP
STOP
VOL
VOL
VOL
VOL
STOP
STOP
MUTE
MUTE
STOP
STOP
PAUSE
PAUSE
– PRESETS +
– PRESETS +
RANDOM
RANDOM
SKIP
SKIP
– CHNL +
– CHNL +
DISC
DISC
STBY
STBY
RR-952
RR-952
X
X
VIDEO
MODE
VOLUME
PM
DISC
HOUR
*
ALARM
OFF
MUTE
MIN
Family Room
RECEIVE
CD
TUNER
AUX
TUNER
TUNER
CD
CD
TAPE/SAT
TAPE/SAT
VIDEO/LD
VIDEO/LD
FAV STN
FAV STN
STOP
STOP
VOL
VOL
VOL
VOL
STOP
STOP
MUTE
MUTE
STOP
STOP
PAUSE
PAUSE
– PRESETS +
– PRESETS +
RANDOM
RANDOM
SKIP
SKIP
– CHNL +
– CHNL +
DISC
DISC
STBY
STBY
RR-952
RR-952
X
X
VIDEO
MODE
VOLUME
PM
DISC
HOUR
*
ALARM
MUTE
OFF
MIN
Bedroom
RECEIVE
CD
TUNER
VIDEO
TUNER
TUNER
CD
CD
TAPE/SAT
TAPE/SAT
VIDEO/LD
VIDEO/LD
FAV STN
FAV STN
STOP
STOP
VOL
VOL
VOL
VOL
STOP
STOP
MUTE
MUTE
STOP
STOP
PAUSE
PAUSE
– PRESETS +
– PRESETS +
RANDOM
RANDOM
SKIP
SKIP
– CHNL +
– CHNL +
DISC
DISC
STBY
STBY
RR-952
RR-952
X
X
AUX
MODE
VOLUME
PM
DISC
HOUR
*
ALARM
OFF
MUTE
MIN
Kitchen
RECEIVE
CD
TUNER
VIDEO
TUNER
TUNER
CD
CD
TAPE/SAT
TAPE/SAT
VIDEO/LD
VIDEO/LD
FAV STN
FAV STN
STOP
STOP
VOL
VOL
VOL
VOL
STOP
STOP
MUTE
MUTE
STOP
STOP
PAUSE
PAUSE
– PRESETS +
– PRESETS +
RANDOM
RANDOM
SKIP
SKIP
– CHNL +
– CHNL +
DISC
DISC
STBY
STBY
RR-952
RR-952
X
X
AUX
MODE
VOLUME
PM
DISC
HOUR
*
ALARM
OFF
MUTE
MIN
7
Page 8
MULTI-ROOM SYSTEM CONTROLLER RMZ-955

Installation: RMZ-955 Controller

This section covers all hardware installation and configuration issues related to the RMZ-955 controller, including wiring con­nections for AC power, source connections, speaker connec­tions, pre-amp connections, data cable connections to the remote zones, Infrared control connections, and special features such as the paging feature. The next section of the manual (see page 12) covers similar topics related to the installation, wiring, and hardware configuration of the zone control devices – the RSM-901 Sensor/Display and the RKP-901 Keypad.
For the sake of simplicity, these two sections cover the installa­tion of a basic 4-zone system with a single RMZ-955 controller, since this is the most typical system configuration. There is a separate section that covers installation, wiring, and configuration topics related to larger, more complex systems with multiple RMZ-955 control­lers.
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○
Installation: Multi-controller Systems
(page 15)

AC Line Connections

AC for the RMZ-955

Plug the RMZ-955 controller/amplifier into an unswitched AC source only, i.e. a wall outlet. It is essential for proper system op­eration that the RMZ-955 be plugged into a constant source of AC power, since it has “stand-by” circuitry that must receive power for full control from any zone at any time.
The switched outlet provides the mechanism for “powering up” or “powering down” all of the source components from the re­mote zones. We recommend plugging the AC power cords from the source components into the switched outlet on the back of the RMZ-955.
Rotel RLC-900 AC line conditioner/switcher
We strongly recommend the use of the RLC-900 AC line condi­tioner/switcher to improve both the performance and convenient operation of all system components. The RLC-900’s benefits in­clude increased protection from AC power line surges and im­proved system AC power management for proper turn-on and turn-off sequences.
To incorporate the RLC-900, follow these steps:
a) Plug all system source components into the RLC-900’s “Digital
Equipment” or “Accessories” outlets as appropriate.
b) Plug the RMZ-955’s AC power cord into the RLC-900’s
“UNSWITCHED” outlet.
c) Plug the RLC-900’s “Control Cord” into the RMZ-955’s SWITCHED
outlet.
d) Plug the RLC-900’s “Main Power” cord into an unswitched AC
outlet such as a wall receptacle, etc.
When a system activation command is sent from a remote zone, the
RLC-900 turns on all source components automatically.

Special AC features

We recommend a powerline filter as the RMZ-955 contains a number of microprocessor ICs that may benefit from the extra protection afforded by a quality filter/surge protector.

AC for Source Components

The RMZ-955 has two rear panel AC convenience outlets, one switched and the other unswitched. These may be used to sup­ply power for components used with the RMZ-955. Each outlet carries a maximum load rating of 100 watts.
Unswitched AC outlet: The RMZ-955’s Unswitched AC outlet supplies AC current whenever the RMZ-955 is plugged into a live AC source. This outlet is NOT controlled by the setting of the RMZ-955’s front panel power switch.
Switched AC outlet: This outlet provides a mechanism for con­trolling AC power to other components, such as source compo­nents. When the RMZ-955’s front panel switch is Off, the switched AC outlet is also off. Even when the front panel switch is turned On (i.e., when the RMZ-955 first powers up to “Standby” mode), the switched outlet remains off until the RMZ-955 receives a zone activation command from one of the remote zones. The switched AC outlet then remains on until the front panel power switch is turned Off or the RMZ-955 receives a “system shutdown” command from a remote zone.
Some source components power up in a standby mode when AC power from a switched outlet turns them on. These components require a separate command to fully activate them. The RMZ-955 has a built-in software function, called “power toggle” that can handle this “power up” sequence, if necessary. This feature is fully described in the this manual on page 22.
System Set-up & Programming
section of
8
Page 9
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

Source connections

INSTALLATION: RMZ-955 CONTROLLER
Note 1: The RMZ-955 does not accept a phono cartridge’s output directly. If required, use a separate phono preamp (such as Rotel’s RQ-970BX) to boost phono signal to line level.
The RMZ-955 has four pair of RCA inputs for four source compo­nents, as well as four pair of RCA “loop-through” outputs that can send the source signals to other components.

Source inputs

Connect LINE LEVEL sources (CD player, tuner, etc.) to the RMZ-955’s rear panel inputs as follows.
Using shielded RCA-RCA cables, connect the source’s output to the corresponding source input on the RMZ-955. Connect analog outputs from the source components as indicated to assure clear operation with both the RR-952 hand held remote and the RKP-901 keypad:
Tuner CD player Tape deck / DSS Satellite CD2 / VCR / DVD / LD
Make sure to observe correct channel continuity from source to RMZ-955. The RMZ-955’s RCA inputs are labelled for easy identi­fication with Left Channel connections on the top row and Right Channel connections on the bottom row.
RMZ-955 Input 1
RMZ-955 Input 2
RMZ-955 Input 3
RMZ-955 Input 4
Note 2: Use only FIXED LEVEL source outputs to the RMZ-955.

Source outputs

Each source input on the RMZ-955 has a matching pair of “loop­through” output RCA jacks. The primary use of these “loop­through” outputs is to pass the signal from each source component to additional RMZ-955 controllers in large multi-zone systems (see page 15 for details on installing large systems).
In some cases, these “loop-through” outputs may alternatively be used to “share” the source components with a separate home theater or audio system. If the source is shared by another system, connect each pair of RMZ-955 source outputs to the appropriate inputs of the main system’s preamplifier as shown in the hook-up illustration.
Note: The source sharing does not work with all combinations of components. Specifically, home theater and audio systems with micro-processor controlled source input switching may result in problems such as interference or “mixing” between shared sources.
IN OUT LINE OUT
~
L
R
IN OUT IN OUT IN OUT IN OUT
TUNER CD AUX1 AUX2
UNSWITCHED SWITCHED
INPUTS
2 3 41
INPUTSTAPE MONITOR
OUTPUT
PAGING
TRIGGER
AUDIO IN
AUDIO OUT
RIGHT
LEFT
LINK IN
LINK OUT
LEFT RIGHT –+–+
ZONE D
123456
DATA
MULTI-ZONE CUSTOM CONTROLLER
MODEL NO. RMZ-955
POWER CONSUMPTION: 430W
AC120V
PRE-OUT
~ 60HZ
IN ENGLAND
PRE-OUT
123456
ZONE C
DATA
DESIGNED AND MANUFACTURED
CAUTION
CAUTION
RISK OF ELECTRIC SHOCK
RISK OF ELECTRIC SHOCK
DO NOT OPEN
DO NOT OPEN
SPEAKER IMPEDANCE
4 OHM MINUMUM
SPEAKERSSPEAKERS
LEFT RIGHT
LEFT RIGHT
–+–+
–+–+
PREAMPLIFIER
WARNING:
TO REDUCE THE RISK OF FIRE OR ELECTRICAL SHOCK DO NOT EXPOSE THIS EQUIPMENT TO RAIN OR MOISTURE.
RC-5N/C
ZONE B
PRE-OUT
DATA
123456
PRE-OUT
123456
TUNER
DATA
ZONE A
SPEAKERSSPEAKERS
LEFT RIGHT
–+–+
WE1
WE2
WE3
WE4
TX-FORMAT 123456
T X O U T P U T S
Tuner connected to Source 1 input (with optional pass-through to preamp for shared use with separate system).
9
Page 10
MULTI-ROOM SYSTEM CONTROLLER RMZ-955
STOM CONTROLLER
~
60HZ
SPEAKER IMPED
4 OHM MINUMU
ZON
SPEAKERS
SPEAKERS
DATA
123456
ZONE C
–+–+
LEFT RIGHT
–+–+
LEFT RIGHT
ZON
SPEAKERS
SPEAKERS
DATA
123456
ZONE C
STOM CONTROLLER
~
60HZ
SPEAKER IMPED
4 OHM MINUMU
–+–+
LEFT RIGHT
–+–+
LEFT RIGHT
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

Speaker Connections

The RMZ-955 is supplied with eight quick-connect screw termi­nal plugs for speaker connections – one twin-terminal plug is used for each speaker, two for each zone. Make the wire con­nections from a speaker to a quick-connect plug and then insert the plug into the appropriate receptacle on the back panel of the RMZ-955, as illustrated.
Strip back each speaker wire’s insulation by 1/4 inch. Insert the bare wire into one “slot” on the quick-connect plug and secure by tightening the corresponding clamping screw. Repeat for the other conductor, making sure that there are no loose strands of wire which could cause a short. Repeat for the second speaker in zone one and then continue with the other zones.
Remember to observe proper polarity when connecting all loud­speakers. The amplifier’s “+” output should connect to the proper speaker’s “+” terminal. “Out of phase” loudspeaker hook­ups (where one speaker in a stereo pair is inadvertently con­nected “+” to “-” and vice versa) may not be immediately noticeable but will not be as pleasing as a properly connected stereo pair. BE CAREFUL AND BE PATIENT.
L
R
IN OUT IN OUT IN OUT IN OUT
INPUTS
2 3 41
–+
SPEAKER
INPUTS
LEFT
UNSWITCHED SWITCHED
~
PAGING
TRIGGER
AUDIO IN
AUDIO OUT
LINK IN
LINK OUT
LEFT RIGHT –+–+
–+
SPEAKER
INPUTS
RIGHT
MULTI-ZONE CUSTOM CONTROLLER
MODEL NO. RMZ-955
POWER CONSUMPTION: 430W
AC120V
DESIGNED AND MANUFACTURED
IN ENGLAND
ZONE D
PRE-OUT
DATA
123456
PRE-OUT
LINE IN
~ 60HZ
123456
DATA
ZONE C
LEFT RIGHT –+–+
CAUTION
CAUTION
RISK OF ELECTRIC SHOCK
RISK OF ELECTRIC SHOCK
DO NOT OPEN
DO NOT OPEN
SPEAKER IMPEDANCE
4 OHM MINUMUM
SPEAKERSSPEAKERS
LEFT RIGHT
–+–+
LEFT
RIGHT
–+ SPEAKER
INPUTS
LEFT
ZONE B
PRE-OUT
DATA
123456
WARNING:
TO REDUCE THE RISK OF FIRE OR ELECTRICAL SHOCK DO NOT EXPOSE THIS EQUIPMENT TO RAIN OR MOISTURE.
RC-5N/C
PRE-OUT
DATA
123456
SPEAKERS
–+
WE1
WE2
SPEAKERSSPEAKERS
LEFT RIGHT
–+–+
WE3
WE4
TX-FORMAT 123456
ZONE A
POWER
AMPLIFIER
–+
SPEAKER
INPUTS
RIGHT
T X O U T P U T S
Speaker connections from Zone D of RMZ-955
10
Also showing Zone C preamp output connections
for use with optional power amplifier
Page 11
INSTALLATION: RMZ-955 CONTROLLER
The long runs from amplifier to speaker typically found in multi­zone installations demand heavy gauge, low resistance speaker wire. Small diameter wire reduces effective amplifier power and adds substantial distortion to the audio signal. Avoid problems by following these minimum recommendations:
Under 150' 150' - 300'
➠ ➠
18 gauge wire 16 gauge wire
Loudspeaker runs over 300' are discouraged.
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

Preamp outputs

Two RCA jacks (Left and Right Channel) labeled “Pre-out” pro­vide line level outputs for each of the four zones. These are pri­marily used for systems with external power amplifiers driving speakers in one or all of the remote zones.
Each zone’s preamp output is fully buffered and may be used ei­ther independently or along with the RMZ-955’s internal amplifi­ers to provide additional flexibility for demanding installations.
If a zone requires additional amplification, use standard RCA­RCA shielded interconnects from these outputs to a separate power amplifier’s unbalanced line inputs as shown in the hook­up illustration on the preceding page. Connect the left channel “Pre-out” jack to the left channel input on the power amplifier for that zone; then repeat for the right channel connections.

Variable vs. Fixed Level

As delivered, the preamp outputs are configured to provide a variable level output, i.e. the volume level of the signal can be adjusted with a volume control in each zone. Alternatively, the pre-amp outputs for one or more zones can be converted to pro­vide a fixed level line drive signal, i.e. a signal that is always at a fixed gain (0.25dBV below that of the source component). This may be useful in certain custom applications.
RMZ-955 Circuit Board
115
115
ZONE A ZONE B ZONE C ZONE D
151
PRE-OUT
Factory default:
variable level
pre-amp output
115
LINE DRIVER
151
151
115
For fixed-level line-driver
output, remove module,
rotate 180° and reinstall
using other set of pins.
PRE-OUT
151
LINE DRIVER
back
front
151
151
Note that the side of the module with the actual electronic com­ponents remains facing to the left side of the RMZ-955, regard­less of which set of header pins you use. Also note that the pins and the socket are labeled 1 — 15. Pin 1 is always inserted into Socket 1, etc.
Note You can configure each of the four zones independently, by rotating just its module. Some zones can be configured as vari­able outputs, while others are reconfigured as fixed outputs by reorienting some or all of the modules.
Converting the pre-amp outputs to fixed level operation requires removing the top cover of the RMZ-955 and locating the four “line driver” plug-in modules. Looking from the front of the unit, these are small vertical circuit boards located in front of the heat sink. They are labeled Zone A through Zone D, from left to right.
Notice that the modules are printed circuit boards that plug into the main board. Each module has two rows of “pins”, one on the bottom (which is plugged into a socket as delivered from the fac­tory) and the other pointing up. To reconfigure from variable level pre-amp outputs to fixed level pre-amp outputs, simply remove the module from the socket on the main circuit board, rotate it 180 degrees, and reinsert it in the same socket using the row of pins on the opposite end.
11
Page 12
MULTI-ROOM SYSTEM CONTROLLER RMZ-955
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

Data cable connections

Data communication to and from the RMZ-955 controller and the remote zones’ RSM-901 sensor/displays and RKP-901 keypads is by 6 conductor shielded cable.
Note: One, and only one, data cable runs from the RMZ-955 to each zone. Multiple sensor/display and keypad combinations in one zone should be wired via series connections detailed in the section on Zone Connection Strategies (page 15).
We recommend the use of Belden 9536 cable or the equivalent. The Methode data connectors supplied with the RMZ-955 only accept cable with 24 gauge conductors.
Using cable with a foil and/or braided shield is absolutely essen­tial in maintaining data integrity over the long runs between the controller/amplifier and a zone’s control code generating de­vices. Make sure that the shield is firmly connected at both the RMZ-955 and at any command device terminal.
We recommend that you run each zone’s data cable and speaker cables together to save time. There is absolutely no performance penalty for doing so.
The supplied Methode connectors need to be crimped to lock to the data cable’s 24 gauge conductors.
Note: Do not use a screwdriver, metal ruler or knife blade to “crimp” these connections. You may think these tools will work but you will be mistaken. USE THE DEDICATED CRIMPING TOOL SPECIFICALLY DESIGNED FOR THESE CONNECTORS. This tool is available from Rotel.
• Strip about 1.5" of the outer cable insulation using a sharp knife. Separate the outer shield from the conductors and trim it off flush with the outer insulation, being careful not to trim off the shield or “drain” wire.
• DO NOT strip insulation off the six individual conductors as the connector automatically makes contact with the conductor core when crimped.
• Place the shield or “drain” wire into slot 1 of the connector. Then, place the BLACK conductor immediately on top of the drain wire in slot 1, hold them both in place and push the crimp­ing tool handle until you hear a slight “click.” Both conductors should now be locked into slot 1. The rachet action of the crimp­ing tool ensures proper connection. The clicking sound tells you that the connector slot contacts have pierced the conductor’s insulation.
PROPER DATA CABLE TERMINATION IS CRITICAL. All connec­tions for RMZ-955 and the remote zone’s RSM-901 sensor/dis­plays and RKP-901 keypads use the color code shown in the following illustration:
DATA CONNECTOR WIRING CODE
1 2 3 4 5 6
Pin 1• black & shield Pin 2• white Pin 3• red Pin 4• brown Pin 5• blue Pin 6• green
Connections are made in the same order at both ends of the cables.
• Continue the process following the color code guide above until all other conductors are locked in the appropriate connector slots. Remember that slot 1 is the ONLY ONE to get the drain wire and a conductor. All other slots receive only a conductor.
After attaching the cable conductors to the connector, insert it into the appropriate zone’s 6 pin data terminal on the RMZ-955’s rear panel. Be careful to center the connector over the terminal pins before inserting.
The maximum cable length for guaranteed operation is 300'. Longer lengths may be practical in some installations with low RF (radio frequency) and EMI (Electro-Magnetic Interference).
12
Page 13
RC-5N/C
SPEAKER IMPEDANCE
4 OHM MINUMUM
TX-FORMAT 123456
T
X O U
T
P U
T
S
ZONE B
DATA
123456
PRE-OUT
DATA
123456
PRE-OUT
SPEAKERSEAKERS
SPEAKERS
ZONE A
WE1
WE2
WE3
WE4
CAUTION
RISK OF ELECTRIC SHOCK
DO NOT OPEN
CAUTION
RISK OF ELECTRIC SHOCK
DO NOT OPEN
WARNING:
TO REDUCE THE RISK OF FIRE OR ELECTRICAL SHOCK DO NOT EXPOSE THIS EQUIPMENT TO RAIN OR MOISTURE.
+– +
T RIGHT
–+–+
LEFT RIGHT
–+–+
LEFT RIGHT
INSTALLATION: RMZ-955 CONTROLLER
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

Infrared Control System

The RMZ-955’s IR system provides extensive control flexibility accepting remote control codes generated by keypads and/or hand-held remotes, relaying them to the system controller, and passing them along to the source components via a front-panel flood emitter or individual remote IR emitters plugged into the rear panel. However, please note the following points:
The IR codes generated by the RR-952 hand held remote are RMZ-955 “system specific” codes and ARE NOT the same codes generated by a source component’s own controller, even for functions that appear identical such as “CD play,” for example. In other words, you can not use the RR-952 to directly control a Rotel CD player but must use it through an RSM-901 sensor/dis­play from a remote zone.
The RMZ-955 IR control system does the following:
• An RSM-901 sensor/display receives the remote’s code se­quence and translates it into proprietary 5 bit digital code.
• This digital code travels over the data cable to the RMZ-955 controller/amplifier.
• The RMZ-955’s translator card restores the code’s original con­figuration (when required) and sends it to both the IR flood emit­ter and the rear panel IR outputs for use by the appropriate source component.
To disable the IR flood emitter, remove the jumper wire between screws 2 and 3 of the TX FORMAT terminal block located on the lower right hand side of the RMZ-955’s rear panel.
Optional remote IR emitters for use in place of front panel IR flood emitter. One required for each source component.
Remove this jumper to disable front panel IR flood emitter.
NOTE: There is a very low intensity red LED mounted behind the emitter’s window which flashes whenever it is transmitting IR codes. Use this LED to verify the emitter’s operating status.

Rear Panel IR Repeaters

In addition to passing RMZ-955 system codes, the IR system will pass ALMOST any IR code sequence from an RSM-901 to a source component. (These few exceptions use a non-standard IR transmission frequency.) This allows you to control transport functions of a VCR from a remote zone, for example, with the VCR’s dedicated hand held remote.

Front Panel IR Flood Emitter

The RMZ-955 features a front-panel flood emitter for sending IR codes to the source components own front-panel IR sensors.
Note: It is essential that the output of the front-panel flood emit­ter NOT be allowed to reach an RSM-901 sensor/display. This could result in an IR loop and unstable system operation includ­ing “lock-up”
RMZ-955s are shipped with the front panel IR flood emitter en­gaged. However, there may be applications (system installations on open shelves in very large, bright rooms, for example) where the IR flood emitter might interfere with proper source compo­nent operation or will not be particularly effective in communi­cating control pulses. Or, there may be systems where an RSM-901 display/sensor located in the same room as the RMZ-
955. In these cases, disable the front-panel flood emitter and use individual IR emitters connected the RMZ-955’s rear panel and placed over each source components IR sensor.
In many system configurations, the most reliable, trouble-free means of passing IR control codes to the source components is with individual IR emitters, one for each source. Use these op­tional repeaters in situations where the RMZ-955 will be located some distance away from the source components or where the IR flood emitter may have difficulty transmitting reliable source control data. Disable the flood emitter when using the optional IR remote emitters.
The RMZ-955 rear panel has four paralleled 3.5mm mini-plug sockets labeled “TX OUTPUTS.” They accept standard “stick on” IR emitter like Xantech’s Video Link 282-00. Plug a repeater into one of the sockets and place it over the source component’s IR sensor. Repeat for the other three sources.
Note: Some source components, such as some Rotel sources, al­low a direct connection from a 3.5 mm rear panel IR emitter con­nection to a matching 3.5 mm connection on the source component, eliminating the need for stick-on IR emitters.
13
Page 14
MULTI-ROOM SYSTEM CONTROLLER RMZ-955
INPUTS
MULTI-Z
M
POWE
DESIG
UNSWITCHED
100W MAX AC 120V 60HZ
SWITCHED (RLC-900)
100W MAX AC 120V 60HZ
SPEAKERS
ZONE D
DATA
123456
PRE-
PAGING
TRIGGER
AUDIO IN
AUDIO OUT
34
–+–+
LEFT RIGHT
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

Paging Input

The paging input allows announcements to be made over the system, and, if required, for Zones to be momentarily muted, in conjunction with a doorbell or a phone system.
The paging feature needs to be activated from an external source via the “paging trigger” RCA-type input jack on the back of the RMZ-955. Any device which shorts the trigger input will cause the controller to enter its paging mode. For example, a doorbell, a phone system , or a keyed announcement micro­phone system could provide this control.
The “Paging Audio In” RCA jack is connected to the audio output of the announcement system (phone or microphone amplifier).
The “Paging Audio Output” jack can be connected to the Paging Audio Input on a second controller (in a large multi-controller system) or to the RCA input of an external amplifier.
Door Bell
Relay
(if required)
trigger trigger
Phone
System
audio
Microphone
Amplifier

Paging Inhibit

The paging function is individually configurable for each zone. The installer can select which Zones will receive or not receive an announcement when the paging is activated. Each Zone has an internal micro switch which is used to set the paging function ON/OFF for that zone. These switches are accessed by removing the top cover of the RMZ-955 by a qualified technician. Make
sure that the AC power line is disconnected before removing the cover.
RMZ-955 Circuit Board
ZONE A ZONE B ZONE C ZONE D
PAGING ON PAGING OFF
Notes:
If a Zone is in Standby (or is listening to Input 1, 2, or 3) and its paging switch is set to OFF, the Zone will remain in its present status when the paging is activated for the rest of the system. It will not be muted and no announcement will be heard.
If a Zone is listening to Input 4, the paging input will be heard when activated, regardless of whether its paging switch is set to ON or OFF.
back
front
14
paging audio output to
paging audio input
on second RMZ-955
Page 15

INSTALLATION: ZONE CONTROL DEVICES

Installation: Zone Control Devices
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

RSM-901 Sensor/Display

RECEIVE
MODE
PM
HOUR
ALARM
MIN

RSM-901 Mounting

The RSM-901 Sensor/Display mounts in a single-width wall box or in a double width box with the RKP-901 keypad.
PLACEMENT SUGGESTIONS: Exact placement will vary with each installation but we strongly recommend AGAINST place­ment where the RSM-901 will be exposed to direct sunlight, pow­erful fluorescent illumination or the output of a high intensity spotlight, etc. These light sources contain high levels of infrared energy themselves and may cause intermittent operation by saturating the RSM-901.
Note: Avoid infrared “loops” by making sure that an RSM-901 sensor/display is not placed where it might pick up signals from a source component’s IR repeater or the RMZ-955’s IR front panel flood emitter.
Lastly, make sure that each RSM-901 is on a relatively uninter­rupted “line-of-sight” path to all likely locations from which the hand held RR-952 remote might be used. You’ll find the RSM-901/ RR-952 combination much less susceptible to signal interference than other IR remote control links, but planning will ensure de­pendable operation under an even wider variety of conditions.
CD
TUNER
AUX
VIDEO
VOLUME
DISC
*
MUTE
OFF
~
2 3 41
L
R
IN OUT IN OUT IN OUT IN OUT
UNSWITCHED SWITCHED
INPUTS
OUT IN OUT IN
RECEIVE
CD
TUNER
AUX
VIDEO
MODE
PM
ALARM
VOLUME
DISC
HOUR
*
MUTE
MIN
RECEIVE
MODE
PM
HOUR
ALARM
MIN
IN
OUT
CAUTION
CAUTION
RISK OF ELECTRIC SHOCK
RISK OF ELECTRIC SHOCK
SPEAKER IMPEDANCE
4 OHM MINUMUM
SPEAKERSSPEAKERS
LEFT RIGHT
LEFT RIGHT
–+–+
–+–+
DO NOT OPEN
DO NOT OPEN
ZONE B
123456
PAGING
TRIGGER
AUDIO IN
AUDIO OUT
LINK IN
LINK OUT
LEFT RIGHT
–+–+
MULTI-ZONE CUSTOM CONTROLLER
MODEL NO. RMZ-955
POWER CONSUMPTION: 430W
AC120V
DESIGNED AND MANUFACTURED
IN ENGLAND
ZONE D
PRE-OUT
DATA
123456
~ 60HZ
PRE-OUT
ZONE C
DATA
123456
IN
WARNING:
OF FIRE OR ELECTRICAL SHOCK DO NOT EXPOSE THIS EQUIPMENT TO RAIN OR MOISTURE.
PRE-OUT
DATA
CD
AUX
VOLUME
*
MUTE
TUNER
VIDEO
DISC
OFF
OUTOUT
TO REDUCE THE RISK
RC-5N/C
PRE-OUT
123456
DATA
ZONE A
SPEAKERSSPEAKERS
LEFT RIGHT
–+–+
WE1
WE2
WE3
WE4
TX-FORMAT 123456
T X O U T P U T S
OUT IN OUT IN OUT
RECEIVE
CD
TUNER
AUX
VIDEO
MODE
PM
OFF
ALARM
VOLUME
DISC
HOUR
*
MUTE
OFF
MIN
CD
TUNER
AUX
VIDEO
VOLUME
DISC
*
MUTE
OFF
15
Page 16
MULTI-ROOM SYSTEM CONTROLLER RMZ-955

RSM-901 Data Connections

Prepare the data cable with the supplied termination plug using the same color coding as previously described for the RMZ-955.
ON
123456
OFF
ON
123456
OFF
DIP SWITCH See instructions for configuration settings
RESET SWITCH SW1 Press after changing configuration
JP1
OUTIN
JUMPER 1
install jumper
to enable battery
INPUT DATA CONNECTOR Connect to RKP-901 Keypad or slave RSM-901 display/sensor
backup
OUTPUT DATA CONNECTOR Connect to RMZ-955 controller/amplifier

Zone Configuration

Each RSM-901 must be configured or “addressed” as being in Zone A, Zone B, Zone C, or Zone D. You select the proper zone by setting Switches 1 & 2 on the DIP switch shown in the illustra­tion. Use the following settings:
Zone Switch 1 Switch 2
A (default) OFF OFF B OFF ON C ON OFF DONON

Source Component Labels

Each RSM-901 must be configured to display the correct label for each source component. It always displays “Tuner” for source input 1 and “CD” for source input 2. However, source input 3 can display “Tape” or “Sat” depending on the setting of Switch 3 and source input 4 can display “CD2”, “VCR”, “Ld”, or “DVD” de­pending on the setting of Switch 4 and Switch 5. Use the follow­ing settings:
Source Input 3 Switch 3
Tape (default) OFF Sat ON
Source Input 4 Switch 4 Switch 5
CD2 ON ON VCR ON OFF LD OFF ON DVD (default) OFF OFF
Note: Remember to set these switches on all RSM-901s.
Note that each RSM-901 has two data terminals labeled “In” and “Out” respectively. Connect the remote zone end of the data cable from the RMZ-955 to the “Out” connector on the RSM-901.
The “In” connector is used to “daisy-chain” additional RSM-901 display/sensors or RKP-901 keypads in the same zone. See
Connection Strategies
on page 15 for details.
A number of configuration settings must be made using the switches and jumpers on the back of the RSM-901. These are de­tailed below.

Battery Enable

Each RSM-901 has a rechargeable back-up battery which main­tains the clock and configuration information when power to the controller is switched off. When fully charged, the battery will then maintain the configuration information for several weeks.
The battery must be enabled when the RSM-901 is installed. To enable the battery, place the jumper JP1 to link the two pins as shown in the illustration above.
Note: After initial installation, leave the RMZ-955 turned on con­tinuously for a few days to ensure that the battery is charged.
Zone

Master/Slave Configuration

Each RSM-901 must be configured as a Master or Slave by set­ting Switch 6. Because it is possible to have more than one RSM-901 in any zone, follow the simple rules to ensure that the required functions are available:
Each zone used in a system must have a Master RSM-901. In a zone with more than one RSM-901, only one must be set as a Master and each other must be set as a Slave. The Master must be the first device on the data cable to the zone from the RMZ-955.
The Master/Slave settings for Switch 6 are:
Master/Slave Switch 6
Master OFF (default) Slave ON
Note: Clock and Alarm functions can only be set from a Master.
16
Page 17

System Reset

After changing any of the above configurations, reset the RSM-901 by pressing the RESET switch (SW1). This is essential to allow the new setting to take effect.

Source Component Set-up

INSTALLATION: ZONE CONTROL DEVICES
RECEIVE
TUNER
CD
AUX
VIDEO
After installation, refer to
21)
for configuring the proper data codes for source component
System Set-up and Programming
(page
operation.
Remember that an RSM-901 connected to the Zone A data cable terminal MUST be used for initial set-up, particularly in systems where non-Rotel source components are included.
Note: After completing the installation and component set-up, power down the system, wait approximately 30 seconds, and then power it up again. Test all functions.
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

RKP-901 Keypad

TUNER
CD
AUX
VIDEO
PM
ALARM
MODE
HOUR
MIN
MUTE
VOLUME
DISC
*
OFF

RKP-901 Data Connections

RKP-901s do not need to be set for particular zones or configured as Master/Slaves because they do not display zone or system status information.
Data cable terminations and connections are made the same way as previously detailed. As does the RSM-901, each RKP-901 has two data terminals (“In” and “Out”) located at the bottom of its circuit board. Connect the “Out” terminal, either to the “In” terminal of an RSM-901 in the zone, or to the RMZ-955 controller if the zone does not have a RSM-901.
VOLUME
DISC
*
OFF
MUTE

RKP-901 Mounting

The RKP-901 keypad mounts in a wall box in the same manner as the RSM-901 sensor/display. There are no restrictions on where the RKP-901 can be located. Common sense and user conve­nience should be the determining factors. Alternatively, the RKP-901 can be mounted in a double-width wall box with an RSM-901 sensor/display. This is the most sensible arrangement from an installation viewpoint (fewer cable runs) but may not be practical in all rooms.
INPUT DATA CONNECTOR
Connect from output of
RKP-901 or subsequent
RSM-901 in the zone.
OUTIN
OUTPUT DATA CONNECTOR Connect to RSM-901 Input or to RMZ-955 if used without RSM-901
17
Page 18
MULTI-ROOM SYSTEM CONTROLLER RMZ-955
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

Zone Connection Strategies

Each zone will support up to three RSM-901s and three RKP-901s. All of the command devices for one zone should con­nect to each other in serial fashion using their appropriate cir­cuit board-mounted “In” and “Out” terminals.
Each RSM-901 signals when it receives and processes a com­mand. This happens regardless of whether the command was generated by a keypad or a hand held remote. However, a key­pad located “downstream” of a sensor/display will that sensor’s command processing indicator.
not
trigger

Installation: Multi-controller Systems

Each RMZ-955 provides independently controlled audio distribu­tion from four sources to four separate zones. To satisfy the re­quirements of more elaborate systems, up to four RMZ-955s can be cascaded to build a system with as many as 16 independent zones. Under these circumstances, all RMZ-955 controller/ampli­fiers share one set of four source components.
When system complexity calls for more than one RMZ-955, we have no cautions about stacking controller/amplifiers on top of each other. As long as there is sufficient room to allow relatively unrestricted air flow, heat should not be a problem.
Whenever possible, we suggest that you configure each zone so that all keypads are “upstream” from all sensor/displays. Al­though not always practical depending on the zone configura­tion, this arrangement will reduce user confusion.
Regardless of other considerations, we suggest that you always wire an RSM/RKP double wall box so that the RSM is located “downstream” from adjacent RKP (i.e., between the RKP and the RMZ-955 controller/amplifier). This assures that the sensor/dis­play always signals the user when the adjacent keypad is used.
Installation is the first step towards enjoying an RMZ-955 system. Proper set-up ensures that the RMZ-955 will function optimally with all associated source components and provide total system control.
In most respects, installing a multi-controller system is no differ­ent than a single controller system. Source input connections, speaker output connections, data cable connections to the re­mote zones, and other configuration steps are essentially the same. Review plete information.
There are, however, some additional considerations and installa­tion steps required for a system with multiple RMZ-955 control­lers. These steps all deal with the need to link the controllers:
Installation: RMZ-955 Controller
(page 5) for com-
a) AC connections for fully-integrated system control
b) Sharing four sources among all controllers
c) Passing IR commands from one controller to the rest
d) Linking special features like system-wide paging
All hookup instructions in this section assume that Zones 1-4 will be handled by the first RMZ-955 (called “A”), Zones 5-8 by the RMZ-955 immediately above it (“B”), Zones 9-12 by third unit (“C”), and Zones 13-16 by the top unit (“D”). In most cases, we do not illustrate all four controllers, as additional controllers are merely added in the same fashion as the second or third con­troller.
There is no functional distinction between the first RMZ-955 and additional controllers in a system. However, for convenience and simplicity, we assume that the first controller will handle some additional responsibilities, such as source inputs and sending IR signals to the sources. This approach makes it easy on the in­staller, particularly when starting with a single RMZ-955 and later expanding with additional controllers. Essentially, the work done installing a single RMZ-955 remains unchanged and additional zones are handled by “add-on” RMZ-955 controllers.
18
Page 19
INSTALLATION: MULTI-CONTROLLER SYSTEMS
RMZ-955 "C"
~
L
R
IN OUT IN OUT IN OUT IN OUT
UNSWITCHED SWITCHED
INPUTS
2 3 41
RMZ-955"B"
~
L
R
IN OUT IN OUT IN OUT IN OUT
UNSWITCHED SWITCHED
INPUTS
2 3 41
RMZ-955 "A"
PAGING
TRIGGER
AUDIO IN
AUDIO OUT
PAGING
TRIGGER
AUDIO IN
AUDIO OUT
Optional +5V external trigger
MULTI-ZONE CUSTOM CONTROLLER
MODEL NO. RMZ-955
LINK IN
LINK OUT
LEFT RIGHT –+–+
LINK IN
LINK OUT
LEFT RIGHT –+–+
POWER CONSUMPTION: 430W
AC120V
DESIGNED AND MANUFACTURED
ZONE D
PRE-OUT
DATA
123456
MULTI-ZONE CUSTOM CONTROLLER
MODEL NO. RMZ-955
POWER CONSUMPTION: 430W
AC120V
DESIGNED AND MANUFACTURED
ZONE D
PRE-OUT
DATA
123456
~ 60HZ
IN ENGLAND
PRE-OUT
~ 60HZ
IN ENGLAND
PRE-OUT
ZONE C
DATA
123456
ZONE C
DATA
123456
CAUTION
CAUTION
RISK OF ELECTRIC SHOCK
RISK OF ELECTRIC SHOCK
SPEAKER IMPEDANCE
4 OHM MINUMUM
SPEAKERSSPEAKERS
LEFT RIGHT
LEFT RIGHT
–+–+
–+–+
CAUTION
CAUTION
RISK OF ELECTRIC SHOCK
RISK OF ELECTRIC SHOCK
SPEAKER IMPEDANCE
4 OHM MINUMUM
SPEAKERSSPEAKERS
LEFT RIGHT
LEFT RIGHT
–+–+
–+–+
DO NOT OPEN
DO NOT OPEN
ZONE B
DO NOT OPEN
DO NOT OPEN
ZONE B
PRE-OUT
DATA
123456
PRE-OUT
DATA
123456
WARNING:
TO REDUCE THE RISK OF FIRE OR ELECTRICAL SHOCK DO NOT EXPOSE THIS EQUIPMENT TO RAIN OR MOISTURE.
RC-5N/C
ZONE A
SPEAKERSSPEAKERS
PRE-OUT
LEFT RIGHT
DATA
–+–+
123456
WARNING:
TO REDUCE THE RISK OF FIRE OR ELECTRICAL SHOCK DO NOT EXPOSE THIS EQUIPMENT TO RAIN OR MOISTURE.
RC-5N/C
ZONE A
SPEAKERSSPEAKERS
PRE-OUT
LEFT RIGHT
DATA
–+–+
123456
WE1
WE2
WE3
WE4
TX-FORMAT 123456
WE1
WE2
WE3
WE4
TX-FORMAT 123456
T X O U T P U T S
T X O U T P U T S
~
L
R
IN OUT IN OUT IN OUT IN OUT
UNSWITCHED SWITCHED
INPUTS
2 3 41
Source component
OUTPUT
RIGHT
LEFT
For multi-contoller systems, connect source sharing links (connections
CAUTION
PAGING
TRIGGER
AUDIO IN
AUDIO OUT
LINK IN
LINK OUT
LEFT RIGHT –+–+
MULTI-ZONE CUSTOM CONTROLLER
MODEL NO. RMZ-955
POWER CONSUMPTION: 430W
AC120V
DESIGNED AND MANUFACTURED
IN ENGLAND
ZONE D
PRE-OUT
DATA
123456
PRE-OUT
~ 60HZ
DATA
123456
ZONE C
LEFT RIGHT
CAUTION
RISK OF ELECTRIC SHOCK
RISK OF ELECTRIC SHOCK
SPEAKER IMPEDANCE
4 OHM MINUMUM
SPEAKERSSPEAKERS
LEFT RIGHT
–+–+
–+–+
DO NOT OPEN
DO NOT OPEN
ZONE B
PRE-OUT
DATA
123456
WARNING:
OF FIRE OR ELECTRICAL SHOCK DO NOT EXPOSE THIS EQUIPMENT TO RAIN OR MOISTURE.
RC-5N/C
TUNER
shown on left side), AC control links (connections shown in center),
and IR repeater links (connections shown on right side).
TO REDUCE THE RISK
ZONE A
SPEAKERSSPEAKERS
PRE-OUT
LEFT RIGHT
DATA
123456
–+–+
WE1
WE2
WE3
WE4
TX-FORMAT 123456
T X O U T P U T S
19
Page 20
MULTI-ROOM SYSTEM CONTROLLER RMZ-955
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

AC Power

Multiple controller systems require handling AC connections in a way that allows any zone to “power up” or “power down” the system. In other words, there must be a provision for zones con­nected to additional RMZ-955 controllers to control the system’s switched AC outlets.
A special feature of the RMZ-955, called “AC Link” simplifies the installation of multi-controller systems with a simple control line connection between units for AC control.

AC Connections

Plug all RMZ-955 controllers into unswitched AC outlets, provid­ing a constant AC supply.
Plug all source components into the switched outlets located on the rear panels of the RMZ-955 controllers. As in a single-con­troller system, the recommended approach is to use a Rotel RLC­900 power conditioner/switcher in conjunction with the first RMZ-955’s rear panel outlets. This allows the first RMZ-955 to handle all AC switching for the system.
With the “AC Linking” feature, it is also possible to plug source components into any switched outlet on the rear panel of any RMZ-955. All of these outlets are controlled in unison. When the system is “powered up” from any zone, the switched outlets on the first RMZ-955 and all other controllers are turned on. When a “power down” command is sent, all RMZ-955’s go into standby and their rear panel switched outlets are turned off.
“power down” command is given from any zone, the RMZ-955 controllers go into Standby mode, the rear panel switched AC outlets are shut off, and this control signal goes to 0V.
This external trigger requires the same 3.5 mm stereo mini-jack as the “AC Link” connections. The “tip” of the connector carries the +5V DC control voltage.

Manual AC Override

There is a provision to manually override the “AC Link” control of the switched outlets. While not common, there may be custom system configurations where being able to manually power up all of the switched outlets and components connected to them.
To enable the manual override, connect Pin 1 and Pin 6 of the rear panel TX FORMAT jumper block with a jumper wire. As long as these two pins are connected, the switched AC outlets on all RMZ-955’s will be powered on. When the two pins are uncon­nected, control of the AC outlets will revert to standard control from the zones, depending on whether the system has been acti­vated from a zone or not.
In practice, the manual override jumper described above would be replaced with a simple single-pole switch connected be­tween Pin 1 and Pin 6 of the “TX-FORM” block. When the switch is closed, manual override is active. When the switch is open, activation of the AC outlets reverts to standard zone control.
TX-FORMAT
123456
TX-FORMAT
123456

AC Link

Unified AC control in multi-controller systems is achieved by a special “AC Link” connection from the first RMZ-955 to the sec­ond and so on down the line. This connection uses standard 3.5 mm stereo mini-jacks at both ends of a 3-conductor cable.
Note: It is essential to use a stereo mini-jack for the “AC Link” connection between controllers (such as Radio Shack #274-389). Do not substitute a mono 2-conductor cable.
To make the connection, plug one end of the 3.5 mm stereo cable into the 3.5 mm jack labeled “Link Out” on the first RMZ-955. Then plug the other end of the cable into the jack labeled “Link In” on the second RMZ-955. Then link the second RMZ-955 by connecting its “Link Out” to the third RMZ-955’s “Link In” jack with another cable. And, so on until there is an “AC Link” con­nection between all RMZ-955 controllers.
External 5V Trigger: Once you have completed all of the “AC Link” connections, the “Link Out” connector on the last RMZ-955 is still available. This jack can provide a +5V D.C. control voltage that could be used to activate external devices in an elaborate custom system. When the Rotel system is activated from any zone, this control signal goes to +5V. When the total system
To manually turn on all
switched AC outlets, connect
pins 1 & 6 with a jumper
or closed switch
For automatic system
control of switched AC
outlets, remove jumper
or open switch
Note: In multi-controller systems, Pin 6 must be connected from the first controller to the Pin 6 on the next, and so on daisy­chainging all RMZ-955s to enable the manual override.
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

Source Connections

Multi-controller systems share the same four source compo­nents. Therefore, it is necessary to pass the signal from each source to all of the RMZ-955 controllers in a system.
Connect all sources to the first RMZ-955 per the instructions as shown
Installation: RMZ-955 Controller
on page 6.
20
Page 21
INSTALLATION: MULTI-CONTROLLER SYSTEMS
Then, using standard shielded RCA-RCA audio interconnet cables, connect Source 1’s “loop through” outputs on the first RMZ-955 “A” to the corresponding Source 1 inputs on the sec­ond RMZ-955 “B”. Repeat this procedure for all four sources.
If a system requires a third RMZ-955, repeat this procedure but, this time, connect the “loop-though” source output on the sec­ond RMZ-955 “B” to the corresponding input on the third RMZ-955 “C” and so for a fourth controller “D”.
NOTE: It is important to observe proper channel continuity when connecting source components to more than one RMZ-955.
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

IR Connections

Systems with multiple RMZ-955 controllers follow generally the same approach to distributing IR signals to the source compo­nents as a single RMZ-955 system. Therefore, review the section on IR installation, particularly on the choice of using the front­panel flood emitter or the back-panel “remote” emitter connec­tions.
When 2 or more RMZ-955s are used in the same system, we sug­gest that you connect them so that only the first RMZ-955 distrib­utes IR commands to the source components and that the IR emitter functions of all additional RMZ-955 controllers is dis­abled. This avoids potential interference leading to erratic operation, particularly when using the front panel IR flood emit­ters.
Note: This is a suggestion only and not a hard and fast rule. There may be some unusual system layouts which benefit from multiple RMZ-955s distributing IR to the sources. This option is covered below as an exception to the standard practice.
The general approach to configuring IR connections for multi­controller systems involves three steps:
Use the following connections for multiple RMZ-955 systems:

For 2 RMZ-955s (5 to 8 zones):

• Remove the jumper between terminals 2 & 3 of the TX FORMAT block on RMZ-955 “B” to disable its IR flood emitter. Leave the jumper in place on RMZ-955 “A” if you are using its front-panel flood emitter. Remove the jumper if you are using remote IR emiiters con­nected to the back panel of
RMZ-955
“A”.
• Link IR signals to the first controller by connecting terminal 3 of the RMZ-955 “B” TX FORMAT block to terminal 4 on RMZ-955 “A”. This completes the IR signal link to the IR flood or “remote” emitter on RMZ-955 “A”.
RMZ-955
"A"
TX-FORMAT
123456
Use this jumper arrangement with 3 RMZ-955 controllers. Disables the IR flood emitters on all but the first controller.
Remove gray jumper if using back panel IR repeaters
from the first RMZ-955 instead of the flood emitter.
RMZ-955
"B"
TX-FORMAT
123456

For 3 RMZ-955s (9-12 zones):

• Remove the jumpers between terminals 2 and 3 of the TX FOR­MAT blocks on RMZ-955 “B” and “C” to disable their flood emit­ters. Leave the jumper in place on the first RMZ-955 “A” to use its front-panel flood emitter. Remove this jumper as well do dis­able the flood emitter when using remote IR emitters.
• Connect terminal 3 of the RMZ-955 “C” TX FORMAT block to terminal 4 on RMZ-955 “B”.
• Connect terminal 3 of the RMZ-955 “B” TX FORMAT block to terminal 4 on RMZ-955 “C”. This completes the signal link to the IR flood emitter on RMZ-955 “A” from the other two RMZ-955s.
a) Configure the first RMZ-955 “A” to distribute IR codes to the
sources (either through its front-panel flood emitter or its “re­mote” IR emitters as described in the section on installing single controller systems.
b) Disable the flood emitter on all other RMZ-955 controllers by re-
moving the “TX-Form” jumper connecting Pins 2 and 3.
c) Relay IR codes from additional RMZ-955 controllers to the first
one by installing a series of jumper wires connected to the “TX­Form” terminal block as outlined below.
RMZ-955
"A"
TX-FORMAT
123456
Use this jumper arrangement with 3 RMZ-955 controllers. Disables the IR flood emitters on all but the first controller.
Remove gray jumper if using back panel IR repeaters
from the first RMZ-955 instead of the flood emitter.
RMZ-955
"B"
TX-FORMAT 123456
RMZ-955
"C"
TX-FORMAT
123456
21
Page 22
MULTI-ROOM SYSTEM CONTROLLER RMZ-955

For 4 RMZ-955s (13-16 zones):

• Remove the jumpers between terminals 2 and 3 of the TX FOR­MAT blocks on RMZ-955 “B” and “C” and “D” to disable their flood emitters. Leave the jumper in place on the first RMZ-955 “A” to use its front-panel flood emitter. Remove this jumper to disable the flood emitter when using back panel IR repeaters.
• Connect terminal 3 of the RMZ-955 “D” TX FORMAT block to terminal 4 on RMZ-955 “C”.
• Connect terminal 3 of the RMZ-955 “C” TX FORMAT block to terminal 4 on RMZ-955 “B”.
• Connect terminal 3 of the RMZ-955 “B” TX FORMAT block to terminal 4 on RMZ-955 “C”. This completes the signal link to the IR flood emitter on RMZ-955 “A” from the other two RMZ-955s.
RMZ-955
"A"
TX-FORMAT 123456
Use this jumper arrangement with 4 RMZ-955 controllers. Disables the IR flood emitters on all but the first controller.
Remove gray jumper if using back panel IR repeaters
from the first RMZ-955 instead of the flood emitter.
RMZ-955
"B"
TX-FORMAT 123456
RMZ-955
"C"
TX-FORMAT 123456
RMZ-955
"D"
TX-FORMAT
123456
For example, the gray jumper wire in the following illustration is used to activate the front-panel flood emitter on RMZ-955 “B” in addition to “A”.
RMZ-955
"A"
TX-FORMAT 123456
Use this jumper arrangement to enable the front
panel IR flood emitters on the first two RMZ-955s.
RMZ-955
"B"
TX-FORMAT
123456
RMZ-955
"C"
TX-FORMAT 123456
RMZ-955
"D"
TX-FORMAT
123456
Here, the gray jumper wire is used to activate the flood emitter on all four RMZ-955 controllers:
RMZ-955
"A"
TX-FORMAT 123456
Use this jumper arrangement to enable the front
panel IR flood emitters on all four RMZ-955s.
RMZ-955
"B"
TX-FORMAT
123456
RMZ-955
"C"
TX-FORMAT 123456
RMZ-955
"D"
TX-FORMAT
123456

Exception: Multiple IR Flood Emitters

As stated above, the general practice is to send IR commands to the source components from only the first RMZ-955 and to dis­able the flood emitters on all other RMZ-955 controllers. The pur­pose of this rule is to prevent IR signals from two different flood emitters interfering with each other and confusing the source component.
An exception to this general rule might arise in systems where some source components are housed in one closed cabinet and others in a different closed cabinet. In this case, you may wish to use two or more RMZ-955 controllers, one in each cabinet, to distribute the IR signals from their flood emitters to the source components.
This can be accomplished with a jumper wire from Terminal 2 of the first RMZ-955’s TX-Form block to Terminal 2 on any other RMZ-955 that needs to have its front-panel flood emitter acti­vated.

Paging Connections

When using the Paging feature in a multi-controller system, two additional installation steps are required. See page 11 for an overview of the paging feature.
a) To trigger the muting and/or paging function, it is necessary to
connect the Paging Trigger input to all RMZ-955 controllers. This requires making multiple connections from whatever device or mechanism is used to supply a shorting input.
b) For announcements to be heard in all zones connected to all
RMZ-955s, the paging audio signal must be distributed to all con­trollers. This can be done by connecting the Paging Audio Output on the first RMZ-955 to the Paging Audio Input on the second RMZ-955, using a standard RCA to RCA interconnect cable. Re­peat this connection from the second to the third controller and from the third to the fourth, if necessary.
22
Page 23
INSTALLATION: MULTI-CONTROLLER SYSTEMS
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

Notes on multi-controller set-up

Power Toggle Set-up

We recommend in systems with multiple RMZ-955 controllers (with full AC control from any Zone) that you select source com­ponents that do not require a “power toggle” command, i.e. com­ponents that fully power up when AC power is applied, instead of going into a standby mode.
If sources requiring a “power toggle” command are used, only one RMZ-955 controller should have the “power toggle” feature activated (i.e. set to “y” during setup). Make sure that the
“Power Toggle” command is DEACTIVATED for all other RMZ-955(s).
Even though the default “Power Toggle” setting is OFF, verify that this has not changed by temporarily connecting an RSM-901 to the Zone A data terminal of each remaining RMZ-955, entering Set-up Mode as outlined and pressing the RLC-900 “n” (for No) key. Continue to hold the “n” key and press the other set-up key “y” to exit setup.
This is a critical step in a system using multiple RMZ-955s. If the “Power Toggle” is not deactivated for the additional RMZ-955(s), source components will not turn on and off properly — in fact, source components may actually turn off when RMZ-955s turn on.

Source Component Set-up

Programming of command code sets for source components is covered in the following section of the manual. However, keep in mind that in systems with multiple RMZ-955 controllers, it will be necessary to reprogram these codes for each RMZ-955 in the system. This must be done from an RSM-901 sensor display con­nected to Zone A on each controller.

“Engaged” Indicator

The “Engaged” indicator on a remote zone’s RSM-901 sensor/ display(s) will indicate other same-source users only in zones connected to that particular RMZ-955 controller/amplifier.
For example, in an 8-zone system using two RMZ-955s, a CD lis­tener in Zone 7 (connected to the second RMZ-955) would have no indication that another user in Zone 2 (connected to the first RMZ-955) was listening to the same source. If a third listener in Zone 4 then selected CD, only the listeners in Zones 2 and 4 (both connected to the same RMZ-955) would know that someone else was sharing the same source.
23
Page 24
MULTI-ROOM SYSTEM CONTROLLER RMZ-955

System Set-up & Programming

○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

Source Commands

The RMZ-955 is factory set for use with Rotel source components, including Rotel multi-disc CD players. No adjustments are neces­sary for these components.
In addition to Rotel source components, the RMZ-955 can be set to operate the following:
Input 1 Tuners: Rotel, Sony, Pioneer, Yamaha, Denon
Input 2 CD: Rotel, Sony, Pioneer, Yamaha, Denon, RC5
Input 3 Tape Deck: Rotel, Sony, Pioneer, Yamaha, Denon
Satellite TV: RCA, Sony
Input 4 CD 2: Sony, Pioneer
Laser Disc: Pioneer VCR: Sony, Panasonic DVD Player: Pioneer, Toshiba
Note 1: Assign each type of component to the input specified
above so that the label displayed by the RSM-901 (Tuner, CD, etc.) matches the component when each input is selected. Note 2: Two CD players of the same brand cannot be used in the same system. Chose a different brand for CD.2
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

Source Command Set-up

a) Locate Zone A’s RSM-901 sensor/display. Source command sets
cannot be changed from any other Zone or even from Zone A’s
keypad. If in doubt, send a command with the RR-952 hand held remote and monitor Zone A’s green Code LED on the RMZ-955’s front panel: it will flash when the RMZ-955 recognizes and processes a command.
b) Select an input (Tuner, CD, Tape/Sat, or VCR/DVD) on the RR-952
so that the corresponding label shows on Zone A’s RSM-901 sen­sor/display.
c) Place the Set-up Card over the RR-952’s pushbuttons.
d) With the RR-952 pointing at the RSM-901 sensor/display, enter
“Set-up” mode by pushing both Set-up buttons simultaneously for a few seconds until the RSM-901 displays “Set ?”, indicating that the system is awaiting further instructions.
TAPE
LD / CD2
VCR / DVD
TUNER
TUNER
A
ROTEL
CD
CD
E
SONY
TAPE/SAT
TAPE/SAT
VIDEO/LD
VIDEO/LD
VOL
VOL
VOL
VOL
MUTE
MUTE
Power Toggle
I
PIONEER
M
YAMAHA
DENON
CD
B
FAV STN
FAV STN
ROTEL
F
STOP
STOP
SONY
STOP
STOP
STOP
STOP
PAUSE
PAUSE
T
U
RC-5
Y
TOSH DVD
J
PIONEER
N
YAMAHA
DENON
TUNER
SAT
D
C
– PRESETS +
– PRESETS +
ROTEL
PION LD
G
SKIP
SKIP
y
SETUP 1
K
PION CD2
O
PANA VCR
R
– CHNL +
– CHNL +
SONY VCR
RR-952
RR-952
DISC
DISC
STBY
STBY
SONY
SONY CD2
RANDOM
RANDOM
Q
Set-Up Card
H
n
SETUP 2
L
PIONEER
YAMAHA
X
X
P
S
DENON
RCA SAT
V
X
SONY SAT
Note: Remember that any RSM-901 sensor/display can be con-
nected to the Zone A data terminal for this procedure. Even if Zone A is equipped with a wall mounted sensor/display, it is probably more convenient to temporarily disconnect the data cable from that unit and substitute another RSM-901 placed near the RMZ-955 and source components.
To avoid the possibility of an IR loop when using an RSM-901 lo­cated near the RMZ-955, temporarily remove the jumper be­tween Terminals 2 and 3 of the TX FORMAT terminal block on the rear panel of the RMZ-955. Also make sure that any RSM-901 used in this set-up sequence has the circuit board DIP switches set for Zone A and “Master” (See page 13).
24
Page 25
SYSTEM SET-UP & PROGRAMMING
e) Push the desired command code button for the component you
want to change. The available choices for that input are grouped together on the Set Up Card. Upon receiving your selection, the RSM-901 will display one of the following characters to indicate your choice of custom command sets:
A Rotel Tuner B Rotel CD Changer RCC-945 C Pioneer LD/DVD D Rotel Tape Deck E Sony Tuner F Sony CD G Sony CD 2 H Sony Tape Deck I Pioneer Tuner J Pioneer CD K Pioneer CD 2 L Pioneer Tape Deck M Yamaha Tuner N Yamaha CD O Panasonic VCR P Yamaha Tape Deck Q Denon CD R Sony VCR S Denon Tape Deck T Denon Tuner U Rotel CD Changer RCC-935 V RCA DSS Sat TV W Toshiba DVD X Sony DSS Sat TV
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

Power Toggle

If you choose to power source components from the RMZ-955’s Switched AC outlet and your system includes components which normally power on in a standby mode, you will need to ACTIVATE the RMZ-955’s software-based “Power Toggle” command.
The “Power Toggle” command fully activates these components even though they usually go into a quiescent or Standby mode when first plugged into the wall or when AC power becomes available.
Source components connected through a switched outlet or the RLC-900 are totally disconnected from AC when the outlets are switched off. Consequently, when the RMZ-955 first activates the source components, some go into a “standby” mode where a few sensors and microprocessors are powered but where major circuitry blocks are still inactive. The “Power Toggle” command tells the sensors and microprocessors to “wake up” the rest of the component.
The following steps will illustrate how the “Power Toggle” com­mand works:
• RMZ-955 in “Standby” mode, source components OFF.
• Zone activation command received. RMZ-955 ON, Switched AC outlet activated, source components switched ON or to “Standby” mode.
f) Repeat the above procedure for the other inputs. After you’ve se-
lected the command codes for all the component categories you wish to change, exit “Set-up” by holding the right-hand SET-UP 2 button and pushing the left-hand SET-UP 1 button. The word “SAVE” will appear on the RSM-901 display to indicate that the new configuration has been memorized.
g) For the new command sets to take effect, the RMZ-955 must be
turned OFF (using the front panel power button) and then turned ON again after 30 seconds.
All changes are stored in non-volatile memory and can not be accidentally erased, even by unplugging the RMZ-955. The only way to change command code operation is to access Set-up mode again.
Note: See Page 5 for further details on the “Power Toggle” com­mand required when the RMZ-955 system (and associated source components) use the switched outlet or recommended RLC-900 Power Line Conditioner as an AC power source.
• RMZ-955 sends “Power Toggle” command to source compo­nents. “Power Toggle” triggers change from “Standby” to “On”.
• All source components ready for remote zone use.
The “Power Toggle” command default is OFF but it can be easily activated. “Power Toggle” is activated or deactivated depending on which of the two SET-UP bottons is pressed first when exiting the Set-up Mode. Press the “y” (for Yes) key first to activate “Power Toggle”. Continue holding the “y” key and press the “n” key to exit Set-up. This activates the RMZ-955’s software-based “Power Toggle” command.
If source components are powered directly from an AC wall out­let, make sure the “Power Toggle” command is DEACTIVATED (the RMZ-955’s default condition) and that any source compo­nents featuring a “Standby” mode are “ON” before using the RMZ-955. To deactivate “Power Toggle”, press and hold the “n” key first. Then, press the “y” key to exit Set-up.
25
Page 26
MULTI-ROOM SYSTEM CONTROLLER RMZ-955

Operating Instructions

As detailed in above, the RMZ-955 should ALWAYS be plugged into an uninterruptable AC source. This ensures that essential RMZ-955 system benefits such as remote controlled zone activa­tion and source selection are always available. Zone control de­vices (the RKP-901 keypad and RSM-901 sensor/display) are powered from the data cables and are always active as long as the RMZ-955 is connected to AC.
INPUT
BUTTONS
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

RR-952 Hand-held Remote

The RR-952 remote provides easy and convenient system opera­tion from any zone equipped with a RSM-901 sensor/display. You will find that the RR-952/RSM-901’s operating range is longer and the angle of acceptance is wider than with many other hand held controllers. This increased operating convenience is a direct re­sult of a more powerful transmitter in the remote and more sensi­tive receiving circuitry in the sensor/displays. Enjoy the difference.
To use the RR-952 remote control, simply aim it at a wall­mounted RSM-901 sensor/display.

Input Selector Buttons

These buttons provide “one-touch” operation of the system, playing the selected source component in the requesting zone. The actual function of the buttons depends on the current sys­tem status, but the net effect is the same: activate the system (if necessary), select the desired component, put it in play mode (if necessary), and direct its signal to the local zone.
Depending on system status, pressing any of these buttons will
TUNER
TUNER
FAV STN
FAV STN
– PRESETS +
– PRESETS +
TUNER BUTTONS
do one of the following:
a) If the entire system is “Off” (i.e., the RMZ-955 is in “Standby”
CD
CD
STOP
TAPE/SAT
TAPE/SAT
STOP
STOP
STOP
RANDOM
RANDOM
SKIP
SKIP
DISC
DISC
CD BUTTONS
TAPE / SAT BUTTONS
mode and all source components are either Off or in “Standby” ), pressing any input selector button will activate the entire system (including source components) for distribution as requested.
b) If only the requesting zone is in “Standby” (and the rest of the
system, including sources, is active), selecting an input will en­able that zone’s microprocessor-controlled switching circuitry
VIDEO/LD
VIDEO/LD
VOL
VOL
VOL
VOL
MUTE
MUTE
STOP
STOP
PAUSE
PAUSE
– CHNL +
– CHNL +
STBY
STBY
X
X
VIDEO / LD BUTTONS
and direct that source’s output to the requesting zone. If the re­quested source is not already in use by another zone, selecting the source will also engage Play mode.
c) If the requesting zone is already playing a source, pushing an-
other input selector button will simply choose the new source.
d) Input selector buttons for CD, TAPE and VIDEO double as “Play”
command buttons for their respective sources. This is important when a source is in “Pause” mode: Simply press the proper input selector again to resume play.
RR-952
RR-952

Tuner control buttons

FAV STN (Favorite Station): This will select the first station (Pre­set #1) programmed into the tuner’s memory.
– PRESET + : These select the next PRE-PROGRAMMED station lower or higher in frequency than the one playing.
26
Page 27
OPERATING INSTRUCTIONS

CD control buttons

RANDOM: This instructs the CD player to play tracks (and discs for multi-disc changer) in whatever random order the CD player chooses.
DISC: This advances the CD player to the next available disc. (functional only with multi-play CD players)
SKIP : These advance the CD player to the next track,
backward or forward , on the disc being played.
STOP: This stops the CD player. Press the CD button to resume playing.

Tape/Satellite TV control buttons

STOP: This button stops tape. Press the TAPE/SAT button to re­sume playing.
(Rewind): This rewinds the tape. Press the TAPE input se-
lect pushbutton to put the deck back into PLAY mode again. For Satellite TV, this changes to the next lower channel.
(Fast forward): Same as above but in the opposite direction.
For Satellite TV, this changes to the next higher channel.

Mute

This temporarily reduces zone volume to very quiet levels for telephone conversations, etc. Press Mute again to restore origi­nal volume settings. You can also press Volume Up, Volume Down or any Input button to restore original levels.

VOLUME UP/VOLUME DOWN

Nothing surprising here – simply press the appropriate button to increase or decrease playback levels as desired.

STBY

This button has two functions:
a) A brief push will put the Zone from which the command originated
into Standby status. All other zones will remain unaffected. Source components will remain on.
b) A continuous push (more than 4 seconds) performs a total sys-
tem-wide “power down”.
This system “power down” includes deactivating all zones, shut­ting off AC power to all components connected to the RMZ-955’s switched AC outlets, and putting all RMZ-955’s in standby mode.

Video/LD control buttons

STOP: Stops the video tape or disc. Press the VIDEO/LD button to resume playing.
PAUSE: This button momentarily stops disc play until it is pushed again.
– CHNL : If a DVD disc is playing, this button backs up to the be­ginning of that track and continues playing. Two quick pushes backs the player to the beginning of the PREVIOUS track or chapter. If a VCR is selected, this changes its tuner to the next lower channel. If CD2 is playing, this button selects “Random Play”
CHNL + : If a DVD is playing, this button goes forward to the be­ginning of the next track. If a VCR is selected, this changes its tuner to the next higher channel. If CD2 is playing, this button se­lects the next disc.
(Reverse Scan): This begins a high speed reverse scan use-
ful for returning to a desired point in a movie, etc. Press the VIDEO/LD input selector button to go back to Play mode when you’ve reached the desired point on the disc. If CD2 is playing, this button skips to the beginning of the current track.
(Forward Scan): The same as above but in the opposite (i.e.,
forward) direction.
“X”
Reserved for future use and inoperative at the present time.
Note: Should you need more advanced IR controls for a particu­lar source, you may be able to use the source’s own dedicated IR remote control. In most cases, the RSM-901 and the IR repeater system will be able to pass IR codes directly to the source from any remote control.
27
Page 28
MULTI-ROOM SYSTEM CONTROLLER RMZ-955
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

RKP-901 Keypad

CD
TUNER
AUX
VIDEO
VOLUME
DISC
*
OFF
MUTE
The RKP-901 keypad offers easy access to most RMZ-955 system functions. The major functional difference between the RKP-901 keypad and RR-952 hand held remote controller is that the wall­mounted keypad has only twelve keys.

Input Select commands

These buttons provide “one-touch” operation. If the system is cur­rently inactive, pushing any of the four input source selection but­tons will “power up” the RMZ-955’s and the source components, send the play command to the selected source, and send the sig­nal from that source to the zone from which the button is pushed. Assuming the tuner is tuned to a station, a disc in the CD player, etc., you will hear music with the push of a single button.
you hear a different source, sending a Play command if neces­sary. Finally, the Input Select button can be used as a Play button to resume operation following a previous Pause command.
The details are not important. If you want to hear a source in your room, just press the Input Select button for that source and the system will worry about the details for you.
TUNER: Selects the tuner as the active source.
CD: Selects the CD player as the active source and sends the play
command to begin operation, if necessary.
AUX: Selects the source component connected to Input 3 (tape deck, or satellite TV) as the active source and sends the play command to begin operation, if necessary.
VIDEO: Selects the video component (VCR, CD2, or DVD) as the active source and sends the play command, if necessary.

System commands

– VOLUME + : Press to decrease or increase volume.
MUTE: Temporarily reduces system volume to almost full attenua-
tion. Restore preselected volume levels by pressing MUTE again, VOL+, VOL– or any input selector.
OFF: A brief push puts the Zone from which the command is sent in Standby status. All other zones are unaffected. A continuous push of more than 4 seconds will send a stop command to all source components and power down the entire system.

Source Control Commands

and
: These buttons are “up” and “down” controls for operat-
ing source components. Their function varies depending on the type of source currently active. See chart below.
28
The function of the button changes slightly if the system is already active. For example, if the source selected is already playing in another zone, pushing the Input Select button will not send a Play command, but will simply let you hear what is already playing. If your zone is already active, pressing an Input Select button lets
CD PLAYER TUNER VIDEO (LD) VIDEO (CD2) VIDEO (VCR) VIDEO (DVD) AUX (TAPE) AUX (SAT)
Track skip (back) Preset – Chapter Skip (back) Track Skip (back) F. Rewind/Scan Skip Back Rewind Channel (down)
Track skip (forward) Preset – Chapter Skip (forward) Track Skip (forward) F. Forward/Scan Skip Forward Fast Forward Channel (up)
DISC: This advances a multi-disc CD player to the next available disc. This button has no function for other components.
: This button is a multi-purpose control, depending on the cur-
*
rently active source component. For most source components, it will send the STOP command to the source. However, it may also be used for a special function on some components. See chart.
*
Random/Shuffle Play Favorite Station Stop Random/Shuffle Play Stop Stop Stop No function
DISC
Next Disc No function No function No function No function No function No function No function
Page 29
OPERATING INSTRUCTIONS
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

RSM-901 Sensor/Display

The RSM-901 sensor/display receives IR signals from the RR-952 hand held controller and other IR devices. It also provides feed­back on system status through a dot matrix LED display and indi­cators. In addition, it provides convenience features including a time of day display and a “wake to music” alarm clock function.
Note: The RSM-901 passes remote control IR commands to the RMZ-955 controller at any time, regardless of whether its zone is currently active or not.
RECEIVE LED
MODE BUTTON
HOUR BUTTON
MINUTE BUTTON
DOT
MATRIX
DISPLAY
PM LED
ALARM
LED
PM
ALARM
RECEIVE
MODE
HOUR
MIN

Dot Matrix Display

The dot matrix display shows the following status information:
Clock Display and Greeting: When the Zone is INACTIVE, the display shows the current time of day in a 4-digit 12-hour format.
When the Zone is first activated, a time-appropriate greeting will display momentarily, followed by a display of the selected source component. To check the time while the Zone is ACTIVE, press the MODE button.
Source Selected: When the Zone is ACTIVE, the display shows the selected source component:
Tuner CD Player
Tape Deck Satellite TV

Controls and Displays

Dot Matrix Display: Shows a variety of system and zone status information, including time of day (when the zone is inactive) and source component selection (when the zone is active).
RECEIVE LED: Flashes when the RSM-901 receives an IR control code from the RR-952 handheld remote or RKP-901 keypad.
PM LED: Lights up when the 12 hour clock time is after 12 noon and before 12 midnight.
ALARM LED: Lights to show that the “wake to music” alarm has been set and will execute at the set time, activating ONLY the Zone from which is has been set, not the whole system. If this LED is not lit, no alarm is in effect.
MODE Button: Used to set and activate various RSM-901 func­tions, including setting the time, setting the alarm, etc.
HOUR Button: Used in conjunction with the MODE button to set up the RSM-901. It has no function when the Zone is active.
MIN Button: Used in conjunction with the MODE button to set up the RSM-901. It has no function when the Zone is active.
VCR DVD Player
Engaged Indicator: It is useful to know when someone in another Zone is listening to the same source component that is active in your zone. If your Zone has exclusive use of the active source, the Source indicator’s first character will be a capital letter. If the source is “engaged” or being shared with another zone, the first character will change to lower case.
Exclusive use
of source
Source engaged
in another zone
29
Page 30
MULTI-ROOM SYSTEM CONTROLLER RMZ-955
Volume Level: When the Volume setting is changed in the Zone, the RSM-901 will momentarily display the new setting:
Minimum Volume Maximum Volume
When a MUTE signal is sent, the volume display will ramp down to zero and show the message “MUTE”. When the Zone is un­muted, the display will ramp up to its previous level.
If a Paging signal is received, the display will ramp down to zero and show a “(())” message during the page. If the Zone is muted, the Paging indicator will show immediately. If the Zone is in standby, the Paging indicator will be preceded by the turn-on greeting.
a) Turning Alarm ON or OFF:
Press the MIN button to activate the wake-up alarm. Press the HOUR button to deactivate. The ALARM LED reminds you that the alarm has been activated. When finished, press the MODE but­ton to record your changes and advance to the next step.
RECEIVE
MODE
PM
ALARM
HOUR
MIN
ALARM OFF
ALARM ON
b) Setting Alarm Time:
The display will show the last alarm time set. Use the HOUR and MINUTE buttons to advance to the desired Alarm time.
sure that the PM indicator shows the desired 12 hour period for the alarm.
When finished, press the MODE button to record your
changes and advance to the next step.
Make
Muting Indicator Paging Indicator
Setting Alarm, Time, and Custom Functions
The following custom functions are programmed from the RSM-901’s Set-Up mode:
• Activating Wake-up Alarm
• Setting Alarm Time
• Setting default source that plays when Alarm activates
• Setting Time of Day
To enter the Set-Up mode, press the MODE button when the Zone is in stand-by mode (clock display showing). Continuing to press the MODE button will toggle through the four set-up choices above and then back to the standby mode.
After the first function has been selected, the RSM-901 will auto­matically exit the Set-Up mode and return to stand-by status if no button is pressed for approximately 10 seconds. Any changes made to the set-up configuration will be stored.
To set the alarm and time, press the MODE button to step through the following procedure. The diagrams show momentary indications of the functions being set prior to their status being shown.
PM
ALARM
RECEIVE
MODE
HOUR
MIN
HOUR BUTTON
MINUTE BUTTON
30
Page 31
OPERATING INSTRUCTIONS
c) Select the Default Source:
Select the source component that you want to begin playing when the alarm goes off. Press the HOUR button to select the TUNER. Press the MINUTE button to select the CD (make sure there is a disc in the player). When finished, press the MODE button to record your changes and advance to the next step.
RECEIVE
MODE
PM
ALARM
HOUR
MIN
TUNER
CD
d) Setting Clock Time:
The display will show the current time of day. Use the HOUR and MINUTE buttons to make any changes.
indicator shows the correct 12 hour period.
Make sure that the PM
When finished, press
the MODE button to record changes and exit the Set-Up mode.
○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○○

For Assistance

We hope this manual has been of assistance in planning and in­stalling your multi-room sound distribution system. Although we’ve gone to great lengths to make this as complete as pos­sible, we’re sure we haven’t covered every aspect of every pos­sible system installation. Please feel free to contact our Technical Support department if you have any questions.
Rotel of America
54 Concord Street North Reading, MA 01864-2699 Phone: 978-664-3820 Fax: 978-664-4109
In addition, your local Rotel Authorized retailer is an invaluable source of information and assistance, particularly in the area of custom audio systems.
Thank you very much for purchasing a Rotel system.
RECEIVE
MODE
PM
ALARM
HOUR
MIN
HOUR BUTTON
MINUTE BUTTON
Note 1:
The clocks in different zones may be slightly out of synch due to drift or inaccurate setting. They will be re-synchronized auto­matically with the master system clock in Zone A at 12 noon each day .
Note 2:
If a RSM-901 is set as a SLAVE (see Page 13), only the clock can be set. Only one alarm in each zone is permitted and it must be set from the MASTER RSM-901 in each zone.
31
Page 32
MULTI-ROOM SYSTEM CONTROLLER RMZ-955
RMZ-955
MULTI-ROOM SYSTEM
Printed in the USA. RTL-02-98-026
The Rotel Co., Ltd.
10-10 Shinsen-Cho
Meguro-Ku
Tokyo 150, Japan
Phone: +81-3-5458-5325
Fax: +81-3-5458-5310
Rotel of America
54 Concord Street
North Reading, MA 01864-2699
Phone: 978-664-3820
Fax: 978-664-4109
Rotel Deutschland
Kleine Heide 12
D-33790 Halle/Westf., Germany
Phone: 05201-87170
Fax: 05201-73370
32
Loading...