Rosemount 8800D Operating Manual

00809-0100-4004, Rev DC

Rosemount™ 8800D Series Vortex Flowmeter

Reference Manual
May 2016
00809-0100-4004, Rev DC
Contents

1Section 1: Introduction

2Section 2: Configuration

Table of Contents
May 2016
1.1 How to use this manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.2 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
1.3 System description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
2.1 Process variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.1.1 Primary Variable (PV) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.1.2 Percent of Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.1.3 Analog Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.1.4 Process Variable Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 Basic setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
2.2.1 Tag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.2.2 Long Tag . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.2.3 Process configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
2.2.4 Reference K-factor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
2.2.5 Flange Type. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.2.6 Pipe ID . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.2.7 Variable mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
2.2.8 Process Variable Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
2.2.9 Analog Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
2.2.10 Damping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.2.11 Optimize DSP (Digital Signal Processing) . . . . . . . . . . . . . . . . . . . . . . . . . 16

3Section 3: Installation

3.1 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
3.2 Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .23
3.2.1 Flowmeter sizing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.2.2 Flowmeter orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
3.2.3 Wetted material selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.2.4 Environmental considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.3 Hazardous locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
3.4 Hardware configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .26
Table of Contents
3.4.1 Failure mode vs. saturation output values . . . . . . . . . . . . . . . . . . . . . . . . 27
3.4.2 LCD indicator option . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
1
Table of Contents
May 2016
Reference Manual
00809-0100-4004, Rev DC
3.5 Meter body installation tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
3.5.1 Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
3.5.2 Flow direction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3.5.3 Gaskets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29
3.5.4 Flange bolts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3.5.5 Wafer-style flowmeter alignment and mounting . . . . . . . . . . . . . . . . . . 31
3.5.6 Flanged-style flowmeter mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.5.7 Flowmeter grounding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.6 Electronics considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .35
3.6.1 High-temperature installations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3.6.2 Conduit connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3.6.3 High-point installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3.6.4 Cable gland . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
3.6.5 Grounding the transmitter case . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.6.6 Wiring procedure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
3.6.7 Remote electronics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
3.6.8 Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
3.7 Software configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
3.7.1 Installing the indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
3.8 Transient protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46
3.8.1 Installing the transient protector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

4Section 4: Operation

4.1 Diagnostics/service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49
4.1.1 Device Alerts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
4.1.2 Loop Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
4.1.3 Flow Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
4.1.4 Analog Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
4.1.5 Scaled Analog Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
4.1.6 Shedding Frequency at URV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
4.2 Advanced functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .52
4.2.1 Pulse Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
4.2.2 Temperature Compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .55
4.2.3 SMART Fluid Diagnostic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
4.2.4 Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59
4.2.5 Burst Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
4.2.6 Local Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
4.2.7 Signal Processing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61
2
Table of Contents
00809-0100-4004, Rev DC

5Section 5: Troubleshooting

Table of Contents
May 2016
4.2.8 Device Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
4.2.9 Change HART Revisions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
4.2.10 Locate Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .66
5.1 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68
5.2 Troubleshooting tables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .68
5.3 Advanced troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
5.3.1 Diagnostic messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .69
5.3.2 Electronics test points. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
5.3.3 TP1—Test point 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .73
5.4 Diagnostic messages on LCD display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .75
5.5 Testing procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .76
5.6 Hardware replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .77
5.6.1 Replacing the terminal block in the housing . . . . . . . . . . . . . . . . . . . . . . 77
5.6.2 Replacing the electronics boards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
5.6.3 Replacing the electronics housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
5.6.4 Replacing the sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
5.6.5 Replacing the sensor: removable support tube . . . . . . . . . . . . . . . . . . . . 82
5.6.6 Remote electronics procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
5.6.7 Coaxial cable at the electronics housing . . . . . . . . . . . . . . . . . . . . . . . . . . 92
5.6.8 Changing the housing orientation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
5.6.9 Temperature sensor replacement (MTA option only). . . . . . . . . . . . . . . 94
5.7 Return of material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .95
AAppendix A: Specifications and Reference Data
A.1 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .97
A.2 Functional specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .97
A.3 Performance specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
A.4 Physical specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
A.5 Dimensional drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Table of Contents
BAppendix B: Product Certifications
B.1 Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
B.2 Product certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
B.2.1 Approved Manufacturing Locations. . . . . . . . . . . . . . . . . . . . . . . . . . . . .141
B.2.2 Flameproof enclosure Ex d protection type in accordance with IEC
60079-1, EN 60079-1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .141
3
Table of Contents
May 2016
CAppendix C: Electronics Verification
Reference Manual
00809-0100-4004, Rev DC
B.2.3 Type n protection type in accordance with IEC 60079-15,
EN60079-15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .141
B.3 European Directive Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
B.4 ATEX Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
B.5 European Pressure Equipment Directive (PED). . . . . . . . . . . . . . . . . . . . . . . . . . 141
B.6 Hazardous Location Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
B.6.1 North American Certifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .142
B.6.2 European Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .142
B.6.3 International IECEx Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .144
B.6.4 Chinese Certifications (NEPSI). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .145
B.6.5 Brazilian Certifications (INMETRO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .147
B.6.6 EurAsian Conformity (EAC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .147
C.1 Safety messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163
C.2 Electronics verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
C.2.1 Electronics verification using flow simulation mode. . . . . . . . . . . . . . .164
C.2.2 Fixed flow rate simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .164
C.2.3 Varying flow rate simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .164
C.2.4 Electronics verification using an external frequency generator . . . . .165
C.2.5 Calculating output variables with known input frequency . . . . . . . . .167
C.3 Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
C.3.1 English units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .169
C.3.2 SI units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .172
DAppendix D: HART® Fast Keys
4
Table of Contents
Reference Manual
00809-0100-4004, Rev DC
Rosemount™ 8800D Series Vortex Flowmeter
Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product.
The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact your local Emerson Process Management Sales Representative.
Title Page
May 2016
This product is intended to be used as a flowmeter for liquid, gas, or steam applications. Any use other than for which it was intended may result in serious injury or death.
Title Page
i
Title Page
May 2016
Reference Manual
00809-0100-4004, Rev DC
ii
Title Page
Reference Manual
00809-0100-4004, Rev DC

Section 1 Introduction

1.1 How to use this manual

This manual provides installation, configuration, operation, troubleshooting, and other procedures for the use of the Rosemount
ordering information, see the Rosemount 8800D Series Vortex Flowmeter Product Data
Sheet.
Section 2: Configuration contains information on entering and verifying basic configuration
parameters.
Section 3: Installation contains mechanical and electrical installation instructions.
Section 4: Operation contains information on advanced configuration parameters and
functions that can aid in maintaining the 8800D.
Section 5: Troubleshooting provides troubleshooting techniques, diagnostic information,
and transmitter verification procedures.
8800D Vortex Flowmeter. For model code
Introduction
May 2016
Appendix A: Specifications and Reference Data provides reference and specification data.
Appendix B: Product Certifications provides specific information for approval codes.
Appendix C: Electronics Verification provides a short procedure for verification of electronic
output to assist in meeting the quality standards for ISO 9001 certified manufacturing processes.
Appendix D: HART® Fast Keys provides command tree, and Fast Key Sequence tables for the
Field Communicator when used in conjunction with the Rosemount 8800D.

1.2 Safety messages

Procedures and instructions in this manual may require special precautions to ensure the safety of the personnel performing the operations. Refer to the safety messages, listed at the beginning of each section, before performing any operations.

1.3 System description

The Rosemount 8800D Vortex Flowmeter consists of a meter body and transmitter, and measures volumetric flow rate by detecting the vortices created by a fluid passing by the shedder bar.
The meter body is installed in-line with process piping. A sensor is located at the end of the shedder bar which creates a sine wave signal due to the passing vortices. The transmitter measures the frequency of the sine wave and converts it into a flowrate.
Introduction
1
Introduction
May 2016
Reference Manual
00809-0100-4004, Rev DC
2
Introduction
00809-0100-4004, Rev DC

Section 2 Configuration

Process variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Basic setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 11

2.1 Process variables

Configuration
May 2016
FastKeys
Process Variables for the Rosemount™ 8800D provides the flowmeter output. When commissioning a flowmeter, review each process variable, its function and output, and take corrective action if necessary before using the flowmeter in a process application.
3, 2, 1

2.1.1 Primary Variable (PV)

FastKeys
The measured value of the variable mapped to the primary variable. This can be either Process Temperature (MTA option only) or Flow. Flow variables are available as mass, volume, corrected volume, or velocity. When bench commissioning, the flow values for each variable should be zero and the temperature value should be the ambient temperature.
If the units for the flow or temperature variables are not correct, refer to “Process Variable
Units” on page 4. Use the Process Variable Units function to select the units for your
application.
2, 2, 2, 1

2.1.2 Percent of Range

FastKeys
3, 4, 3, 2
The primary variable as a percentage of range provides a gauge as to where the measured flow rate of the meter is within the configured range of the meter. For example, the range may be defined as 0 gal/min to 20 gal/min. If the measured flow rate is 10 gal/min, the percent of range is 50 percent.

2.1.3 Analog Output

FastKeys
The analog output variable provides the analog value for the primary variable. The analog output refers to the industry standard output in the 4–20 mA range. Check the analog output value against the actual loop reading given by a multi-meter. If it does not match, a 4–20 mA trim is required. See “Analog Trim” on page 51.
Configuration
3, 4, 3, 1
3
Configuration
May 2016

2.1.4 Process Variable Units

Reference Manual
00809-0100-4004, Rev DC
FastKeys
Allows for the viewing and configuration of Process Variable Units such as Volume, Velocity, Mass Flow, Electronics Temperature, Process Density, and Corrected Volume units, including corrected volume Special Units configuration.
2, 2, 2, 6
Volume Flow
FastKeys
Allows the user to view the volumetric flow rate value.
3, 2, 1
Volume Flow Units
FastKeys
Allows the user to select the volumetric flow units from the available list.
gallons per second imperial gallons per minute
gallons per minute imperial gallons per hour
gallons per hour imperial gallons per day
gallons per day liters per second
cubic feet per second liters per minute
2, 2, 2, 6, 1
cubic feet per minute liters per hour
cubic feet per hour liters per day
cubic feet per day cubic meters per second
barrels per second cubic meters per minute
barrels per minute cubic meters per hour
barrels per hour cubic meters per day
barrels per day mega cubic meters per day
imperial gallons per second special units
4
Configuration
00809-0100-4004, Rev DC
Corrected Volumetric Flow Units
Configuration
May 2016
FastKeys
Allows the user to select the corrected volumetric flow units from the available list.
gallons per second imperial gallons per hour
gallons per minute imperial gallons per day
gallons per hour liters per second
gallons per day liters per minute
cubic feet per second liters per hour
standard cubic feet per minute liters per day
standard cubic feet per hour normal cubic meters per minute
cubic feet per day normal cubic meters per hour
barrels per second normal cubic meters per day
barrels per minute cubic meters per second
barrels per hour cubic meters per minute
barrels per day cubic meters per hour
imperial gallons per second cubic meters per day
imperial gallons per minute special units
2,2,2,6,2
Note
When measuring corrected volumetric flow, a base density and process density must be provided.
Mass Flow
FastKeys
Allows the user to view the mass flow rate value and units.
3, 2, 1
Configuration
5
Configuration
May 2016
Reference Manual
00809-0100-4004, Rev DC
Mass Flow Units
FastKeys
Allows the user to select the mass flow units from the available list. (1 STon = 2000 lb; 1 MetTon = 1000 kg)
grams per hour pounds per day
grams per minute special units
grams per second short tons per day
kilograms per day short tons per hour
kilograms per hour short tons per minute
kilograms per minute pounds per second
kilograms per second tons (metric) per day
pounds per minute tons (metric) per hour
pounds per hour tons (metric) per minute
Note
If you select a Mass Flow Units option, you must enter process density in your configuration.
2, 2, 2, 6, 5
Velocity Flow
FastKeys
Allows the user to view the velocity flow rate value and units.
3, 2, 1
Velocity Flow Units
FastKeys
Allows the user to select the Velocity Flow Units from the available list.
feet per second
meters per second
2, 2, 2, 6, 3
Velocity Measurement Base
FastKeys
Determines if the velocity measurement is based on the mating pipe ID or the meter body ID. This is important for Reducer
2, 2, 2, 6, 4
Vortex Applications.
6
Configuration
00809-0100-4004, Rev DC
Special Units
Configuration
May 2016
FastKeys
2,2,2,7 (Volume) 2,2,2,8 (Mass) 2,2,2,9 (Corrected Volume)
Allows the user to create flow rate units that are not among the standard options. Configuration of a special unit involves entry of these values: base flow unit, base time unit, user defined unit and conversion number. Suppose the user wants the Rosemount 8800D to display flow in beer barrels per minute instead of gallons per minute, and one beer barrel is equal to 31 gallons.
Base volume unit: gal
Base time unit: min
User defined unit: br
Conversion number:
1
/31.0
See the specific variables listed below for more information on setting special units.
Base Flow Unit
FastKeys
The unit from which the conversion is made. Select one of the Field Communicator defined unit options:
2,2,2,7,1 (Volume) 2,2,2,8,1 (Mass) 2,2,2,9,1 (Corrected Volume)
Volumetric flow Mass flow Corrected volume flow
U.S. gallon gram U.S. gallon
liter kilogram liter
imperial gallon metric ton imperial gallon
cubic meter pound barrel
barrel short ton standard cubic foot
cubic foot normal cubic foot
Base Time Unit
FastKeys
Provides the time unit from which to calculate the special units. For example, if the special unit is a volume per minute, select minutes. Choose from the following units:
Seconds (s)
Minutes (min)
Hours (h)
Days (d)
2,2,2,7,4 (Volume) 2,2,2,8,4 (Mass) 2,2,2,9,4 (Corrected Volume)
Configuration
7
Configuration
May 2016
Reference Manual
00809-0100-4004, Rev DC
Special Flow Unit
FastKeys
A user created custom flow unit. The special unit is limited to four characters. The Field Communicator indicates the special unit with SPCL. The LCD display will display the actual four character user defined special unit.
2,2,2,7,5 (Volume) 2,2,2,8,5 (Mass) 2,2,2,9,5 (Corrected Volume)
Conversion Number
FastKeys
Used to relate base units to special units. For a straight conversion of volume units from one to another, the conversion number is the number of base units in the new unit.
For example, if it is desired to convert from gallons to beer barrels there are 31 gallons in a beer barrel. The conversion equation is as follows (where beer barrels is the new volume unit):
1 gallon = 0.032258 bbl.
2,2,2,7,2 (Volume) 2,2,2,8,2 (Mass) 2,2,2,9,2 (Corrected Volume)
Tota l
FastKeys
2, 2, 4, 3, 1
Provides the output reading of the totalizer. Its value is the amount of liquid or gas that has passed through the flowmeter since the totalizer was last reset.
Totalizer Control
FastKeys
Allows the totalizer to be started, stopped, or reset.
Start—Starts the totalizer counting from its current value.
Stop—Interrupts the totalizer count until it is restarted again. This feature is often used during pipe cleaning or other maintenance operations.
Reset—Returns the totalizer value to zero. If the totalizer was running, it will continue to run starting at zero.
2, 2, 4, 3, 2
8
Configuration
00809-0100-4004, Rev DC
Totalizer Config
Configuration
May 2016
FastKeys
Used to configure the flow parameter (volume, mass, velocity, or corrected volume flow) that will be totaled.
Note
The totalizer value is saved in the non-volatile memory of the electronics every three seconds. Should power to the transmitter be interrupted, the totalizer value will start at the last saved value when the power is re-applied.
Note
Changes that affect the density, density ratio, or compensated K-Factor will affect the totalizer value being calculated. These changes will not cause the existing totalizer value to be recalculated.
Note
In order to totalize in compensated mass flow or compensated corrected volume flow, for units with the MTA option only, set pulse output to match the totalizer configuration even if the pulse output was not ordered.
2, 2, 4, 3, 3
Pulse Frequency
FastKeys
Allows the user to view the pulse output frequency value. To configure the pulse output, refer to the section on pulse output found on page 54.
3, 2, 5, 3
Shedding Frequency
FastKeys
Allows the user to view the shedding frequency directly off of the sensor.
3, 2, 5, 1
Electronics Temperature
FastKeys
Allows the user to view the Electronics Temperature value and units.
3, 2, 6, 2
Electronics Temperature Units
FastKeys
Allows the user to select the Electronics Temperature Units from the available list.
deg C
deg F
2, 2, 2, 6, 6 (without MTA) 2, 2, 2, 6, 7 (with MTA)
Configuration
9
Configuration
May 2016
Reference Manual
00809-0100-4004, Rev DC
Calculated Process Density
FastKeys
3, 2, 1
Allows the user to view the calculated process density value when the transmitter is configured for temperature compensated steam or temperature compensated liquid applications.
Process Density Units
FastKeys
Allows the user to configure the Process Density Units from the available list.
g/Cucm (cm
g/L
kg/Cum (m
lb/Cuft (ft
lb/Cuin (in
2, 2, 2, 6, 7 (without MTA) 2, 2, 2, 6, 8 (with MTA)
3
)
3
)
3
)
3
)
Process Temperature
FastKeys
Allows the user to view the Process Temperature value when the transmitter has the temperature sensor option, MTA.
3, 2, 1
Process Temperature Units
FastKeys
Allows the user to configure the units for the process temperature from the available list.
deg C
deg F
deg R
Kelvin
2, 2, 2, 6, 6 (only with MTA)
Temperature Sensor Failure Mode
FastKeys
Allows the user to configure the temperature sensor failure mode. In the event that the temperature sensor fails, the vortex can go either into an alarm output mode, or continue to operate normally using the Fixed Process Temperature value. See Fixed Process Temperature on page 12. This mode is only relevant with the MTA option.
Note
If the Primary Variable is set to Process Temperature and there is an error, the output will always go to alarm and this setting will be ignored.
2, 2, 1, 3, 1
10
Configuration
00809-0100-4004, Rev DC

2.2 Basic setup

Configuration
May 2016
FastKeys
The Rosemount 8800D must be configured for certain basic variables in order to be operational. In most cases, all of these variables are pre-configured at the factory. Configuration may be required if your Rosemount 8800D is not configured or if the configuration variables need revision. The basic setup wizard will take you through all the steps required to set up the Rosemount Vortex meter for basic operation.
The remainder of this section contains details about how to enter basic configuration parameters in order to manually configure the Rosemount 8800D.

2.2.1 Tag

FastKeys
The quickest way to identify and distinguish between flowmeters. Flowmeters can be tagged according to the requirements of your application. The tag may be up to eight
characters long. Long Tag is available for HART

2.2.2 Long Tag

FastKeys
Available for HART 7 and allows for up to 32 characters.
2, 1, 1, 1
2, 2, Device Information, 1, 1
2,2,Device Information,1,2
®
7 and allows for up to 32 characters.

2.2.3 Process configuration

The flowmeter can be used for liquid or gas/steam applications, but it must be configured specifically for the application. If the flowmeter is not configured for the proper process, readings will be inaccurate. Select the appropriate process configuration parameters for your application:
Transmitter Mode
FastKeys
For units with an integral temperature sensor, the temperature sensor can be activated here.
Without Temperature Sensor
With Temperature Sensor
Set Process Fluid
FastKeys
Select the fluid type—either Liquid, Gas/Steam, Tcomp Sat Steam, or Tcomp Liquids. Tcomp Sat Steam and Tcomp Liquids require the MTA Option and provide dynamic density compensation based on the process temperature reading.
2, 2, 1, 1, 1
2, 2, 1, 1, 3
Configuration
11
Configuration
DensityRatio
density at actual (flowing) conditions
density at s dard (base)tan conditions
------------------------------------------------------------------------------------------------------- -=
May 2016
Reference Manual
00809-0100-4004, Rev DC
Fixed Process Temperature
FastKeys
Needed for the electronics to compensate for thermal expansion of the flowmeter as the process temperature differs from the reference temperature. Process temperature is the temperature of the liquid or gas in the line during flowmeter operation.
May also be used as a back-up temperature value in the event of a temperature sensor failure if the MTA option is installed.
2, 2, 1, 1, 4
Fixed Process Density
FastKeys
A Fixed Process Density must be accurately configured if mass flow or corrected volume flow measurements are used. In mass flow it is used to convert volume flow to mass flow. In corrected volume flow it is used with the base process density to derive a density ratio which in turn is used to convert volume flow to corrected volume flow. In temperature compensated fluids the fixed process density is still required as it is used to convert volume flow sensor limits to sensor limits for temperature compensated fluids.
Note
If mass or corrected volume units are chosen, you must enter the density of your process fluid into the software. Be careful to enter the correct density. The mass flow rate and density ratio are calculated using this user-entered density, and unless the transmitter is in TComp Sat Steam or TComp Liquids mode where changes in density are automatically being compensated for, any error in this number will cause error in the measurement.
2, 2, 3, 1
Base Process Density
FastKeys
The density of the fluid at base conditions. This density is used in corrected volume flow measurement. It is not required for volume flow, mass flow, or velocity flow. The Base Process Density is used with the Process Density to calculate the Density Ratio. In temperature compensated fluids, the Process Density is calculated by the transmitter. In non-temperature compensated fluids the Fixed Process Density is used to calculate a fixed Density Ratio. Density Ratio is used to convert actual volumetric flow to standard volumetric flow rates based on the following equation:
2, 2, 3, 2, 1

2.2.4 Reference K-factor

FastKeys
A factory calibration number relating the flow through the meter to the shedding frequency measured by the electronics. Every 8800 meter manufactured by Emerson is run through a water calibration to determine this value.
2, 2, 1, 2, 1
12
Configuration
00809-0100-4004, Rev DC

2.2.5 Flange Type

Configuration
May 2016
FastKeys
2, 2, 1, 4, 2
Enables the user to specify the type of flange on the flowmeter for later reference. This variable is preset at the factory but can be changed if necessary.
WaferASME 150ASME 150 ReducerASME 300ASME 300 ReducerASME 600ASME 600 ReducerASME 900ASME 900 ReducerASME 1500ASME 1500 ReducerASME 2500ASME 2500 ReducerPN10PN10 ReducerPN16PN16 Reducer
PN25 PN25 Reducer PN40 PN40 Reducer PN64 PN64 Reducer PN100 PN100 Reducer PN160 PN160 Reducer JIS 10K JIS 10K Reducer JIS 16K/20K JIS 16K/20K Reducer JIS 40K JIS 40K Reducer Spcl

2.2.6 Pipe ID

FastKeys
The pipe ID (inside diameter) of the pipe adjacent to the flowmeter can cause entrance effects that may alter flowmeter readings. Configuring the actual mating pipe inside diameter will correct for theses effects. Enter the appropriate value for this variable.
Pipe ID values for schedule 10, 40, and 80 piping are given in Ta bl e 2 - 1 . If the mating pipe ID is not listed in the table, confirm pipe ID with manufacturer or measure the pipe ID.
Table 2-1. Pipe IDs for Schedule 10, 40, and 80 Piping
Pipe size
inches (mm)
½ (15) 0.674 (17.12) 0.622 (15.80) 0.546 (13.87)
1 (25) 1.097 (27.86) 1.049 (26.64) 0.957 (24.31)
1½ (40) 1.682 (42.72) 1.610 (40.89) 1.500 (38.10)
2 (50) 2.157 (54.79) 2.067 (52.50) 1.939 (49.25)
3 (80) 3.260 (82.80) 3.068 (77.93) 2.900 (73.66)
4 (100) 4.260 (108.2) 4.026 (102.3) 3.826 (97.18)
2, 2, 1, 1, 6
Schedule 10
inches (mm)
Schedule 40
inches (mm)
Schedule 80
inches (mm)
Configuration
13
Configuration
May 2016
Reference Manual
00809-0100-4004, Rev DC
Pipe size
inches (mm)
6 (150) 6.357 (161.5) 6.065 (154.1) 5.761 (146.3)
8 (200) 8.329 (211.6) 7.981 (202.7) 7.625 (193.7)
10 (250) 10.420 (264.67) 10.020 (254.51) 9.562 (242.87)
12 (300) 12.390 (314.71) 12.000 (304.80) 11.374 (288.90)
Schedule 10
inches (mm)

2.2.7 Variable mapping

FastKeys
Allows the user to select which variables the 8800D will output.
Primary Variable
FastKeys
The variable mapped to the analog output. Selections for the primary variable are Mass Flow, Volumetric Flow, Corrected Volume Flow, Velocity Flow, and Process Temperature.
Secondary Variable
FastKeys
2, 2, 2, 5
2, 2, 2, 1
2, 2, 2, 2
Schedule 40
inches (mm)
Schedule 80
inches (mm)
Selections for the secondary variable include all variables that can be mapped to the Primary Variable, and also Shedding Frequency, Pulse Frequency, Calculated Process Density, and Electronics Temperature. The full list is given below:
Mass Flow
Volumetric Flow
Corrected Volumetric Flow
Direct Shedding Frequency
Pulse Output Frequency
Tot a li ze r
Veloc ity
Process Temperature (MTA only)
Calculated Process Density (MTA only)
Thermocouple Cold Junction Temperature (MTA only)
Electronics Temperature
Signal Strength
Third Variable
FastKeys
2, 2, 2, 3
14
Selections for the Third Variable are identical to those of the Secondary Variable.
Configuration
00809-0100-4004, Rev DC
Fourth Variable
Configuration
May 2016
FastKeys
Selections for the Fourth Variable are identical to those of the Secondary Variable.
2, 2, 2, 4

2.2.8 Process Variable Units

FastKeys
This selection allows the user to set the units of measure for all available process variables.
2, 2, 2, 6

2.2.9 Analog Output

FastKeys
Enables you to set the upper and lower range values in order to maximize the resolution of the analog output. The meter is most accurate when operated within the expected flow ranges for your application. Setting the range to the limits of expected readings will maximize flowmeter performance.
The range of expected readings is defined by the Lower Range Value (LRV) and Upper Range Value (URV). Set the LRV and URV within the limits of flowmeter operation as defined by the line size and process material for your application. Values set outside that range will not be accepted.
Primary Variable Upper Range Value (PV URV)
3, 4, 3, 1
FastKeys
This is the 20 mA set point for the meter.
2, 2, 4, 1, 3
Primary Variable Lower Range Value (PV LRV)
FastKeys
This is the 4 mA set point for the meter, and is typically set to 0 when the primary variable is a flow variable.
2, 2, 4, 1, 4
Configuration
15
Configuration
May 2016

2.2.10 Damping

Reference Manual
00809-0100-4004, Rev DC
FastKeys
Damping changes the response time of the flowmeter to smooth variations in output readings caused by rapid changes in input. Damping is applied to the Analog Output, Primary Varia ble, Percent of Range, and Vortex Frequency.
The default damping value is 2.0 seconds. This can be configured to any value between 0.2 to 255 seconds when PV is a flow variable or 0.4 to 32 seconds when PV is Process Temperature. Determine the appropriate damping setting based on the necessary response time, signal stability, and other requirements of the loop dynamics in your system.
Note
If the vortex shedding frequency is slower than the damping value selected, no damping is applied. Process Temperature damping can be modified when PV is set to Process Tem p er at ur e.
2, 1, 4, 1

2.2.11 Optimize DSP (Digital Signal Processing)

FastKeys
A function that can be used to optimize the range of the flowmeter based on the density of the fluid. The electronics uses process density to calculate the minimum measurable flow rate, while retaining at least a 4:1 signal to the trigger level ratio. This function will also reset all of the filters to optimize the flowmeter performance over the new range. If the configuration of the device has changed, this method should be executed to ensure the signal processing parameters are set to their optimum settings. For dynamic process densities, select a density value that is lower than the lowest expected flowing density.
2, 1, 1, 3
16
Configuration
00809-0100-4004, Rev DC
Configuration
May 2016
Table 2-2. Fast Keys for Rosemount 8800D HART 7 Device Revision 2 (DD Revision 1)/ HART 5 Device Revision 3 (DD Revision 1)
Function Fast Key Function Fast Key
Analog Output 3, 4, 3, 1 Polling Address 2, 2, – Analog Trim 3, 4, 3, 7 Primary Variable 2, 2, 2, 1 Base Mass Unit (MF) 2, 2, 2, 8, 1 Process Fluid Type 2, 2, 1, 1, 3 Base Process Density 2, 2, 3, 2, 1 Process Variables 3, 2, 3 Base Time Unit (CVF) 2, 2, 2, 9, 4 Pulse Output 3, 2, 5, 3 Base Time Unit (MF) 2, 2, 2, 8, 4 Pulse Output Test 3, 5, 3, 4 Base Time Unit (VF) 2, 2, 2, 7, 4 Reference K-Factor 2, 2, 1, 2, 1 Base Volume Unit (CVF) 2, 2, 2, 9, 1 Reset Transmitter 3, 4, 4, 1, 2 Base Volume Unit (VF) 2, 2, 2, 7, 1 Restore Default Filters 2, 1, 4, 6 Compensated K-Factor 2, 2, 1, 2, 2 Restore Factory Calibration 3, 4, 3, 9 Conversion Factor (CVF) 2, 2, 2, 9, 2 Revision Numbers 2, 2, – Conversion Factor (MF) 2, 2, 2, 8, 2 Scaled Analog Trim 3, 4, 3, 8 Conversion Factor (VF) 2, 2, 2, 7, 2 Second Variable 2, 2, 2, 2 Date 2, 2, –
(1)
, 1, 5
Self Test 3, 4, 4, 1, 1 Corrected Volumetric Flow 3,2,1 Set Damping 2, 1, 4, 1 Corrected Volumetric Flow Units 2,2,2,6,2 Set Low Flow Cutoff 2, 1, 4, 3 Density Ratio 2, 2, 3, 4 Set Low-pass Corner Frequency 2, 1, 4, 4 Descriptor 2, 2, – Device ID 2, 2, –
(1)
, 1, 6 Set Trigger Level 2, 1, 4, 5
(1)
, 1 Shedding Frequency 3, 2, 5, 1 Device Status 1, 1 Signal Strength 3, 4, 2, 1, 4 Display 2, 1, 1, 2 Special Flow Unit (CVF) 2, 2, 2, 9, 5 Electronics Temp 3, 2, 6 Special Flow Unit (MF) 2, 2, 2, 8, 5 Electronics Temp Units 2, 2, 2, 6, 7 Special Flow Unit (VF) 2, 2, 2, 7, 5 Final Assembly Number 2, 2, 1, 4, 3 Special Volume Unit 2, 2, 2, 7, 3 Fixed Process Density 2, 2, 1, 1, 5 Ta g 2, 2, – Fixed Process Temperature 2, 2, 1, 1, 4 Third Variable 2, 2, 2, 3 Flange Type 2, 2, 1, 4, 2 To t al 2, 2, 4, 3, 1 Flow Simulation 3, 5, 1, 2, 1 Totalizer Configuration 2, 2, 4, 3, 3 Fourth Variable 2, 2, 2, 4 Totalizer Control 2, 2, 4, 3, 2 Loop Test 3, 5, 2, 7 Transmitter Mode 2, 2, 1, 1, 1 Lower Range Value 2, 2, 4, 1, 4 Upper Range Value 2, 2, 4, 1, 3 Lower Sensor Limit 2, 2, 4, 1, 6 Upper Sensor Limit 2, 2, 4, 1, 5 Mass Flow 3, 2, 1 Variable Mapping 2, 2, 2, 5 Mass Flow Units 2, 2, 2, 6, 5 Velocit y Flow 3, 2, 1 Message 2, 2, –
(1)
, 1, 7 Velocity Flow Units 2, 2, 2, 6, 3 Meter Factor 2, 2, 1, 1, 7 Velocity Measurement Base 2, 2, 2, 6, 4 Minimum Span 2, 2, 4, 1, 7 Volume Flow 3, 2, 1 Optimize DSP 2, 1, 1, 3 Volume Flow Units 2, 2, 2, 6, 1 Percent of Range 3, 4, 3, 2 Wetted Material 2, 2, 1, 4, 1 Pipe Inside Diameter 2, 2, 1, 1, 6 Write Protect 2, 2, –
(1)
(1)
(1)
(1)
, 2, 1
, 2
, 1, 1
, 4, 1
1. These items are in a list format without numeric labels. To access these features, you must scroll to this option in the HART Communicator.
Configuration
17
Configuration
Overview
Configure
Service Tools
Device Status Comm Status
1
Primary Variable Primary Variable Value Status
1
Volume Flow Status
1
Process Temp Status
1
Analog Output Device Information
Refresh Alerts Clear Config Changed Flag Active Alerts
Identification Revision Numbers Sensor Alarm Type and Security
Tag Long Tag
1
Model Serial Number Date Description Message
Universal Field Device Software Hardware DD Revision
Process Flow Sensor Temperature Sensor Meter Body
Transmitter Mode Process Fluid Fixed Proc Temp Fixed Proc Density Pipe Inside Diameter Meter Factor
Reference K-factor Compensated K-factor Upper Sensor Limit Lower Sensor Limit
T/C Failure Mode
Wetted Material Flange Type Meter Body Num Body Num Suffix
Alarm Configuration Security Refresh
Alarm Direction Alarm Level High Alarm High Saturation Low Alarm Low Saturation
Write Protect Device is Locked
1
NOTES:
1
HART 7 only
Availability of options depends on configuration, such as using temperature compensation (MTA option). The order in which parameters display may vary.
May 2016
Figure 2-1. Overview Menu Map
Reference Manual
00809-0100-4004, Rev DC
18
Configuration
Overview
Configure
Service Tools
Guided Setup
Manual Setup
Initial Setup
Process
Outputs
Signal Processing
Analog Output
Config Pulse Output
Variable Mapping
Special Units
Burst Mode
Basic Setup
Configure Display
Optimize DSP
Set Pipe Inside Diameter
Set Proc Temp
Set Fixed Density
Burst Message 1
Message 1 Content
Message 1 Variables
Set Damping
Set Meter Factor
Set Low Flow Cutoff
Set LoPass Crn Frq
Set Trigger Level
Restore Dflt Filter
Sensor
Variable Mapping
Process
Outputs
Signal Processing
SMART Fluid
Licenses
Tcomp Liquid
Display
HART
Device Information
Process
Flow Sensor
Temperature Sensor
Meter Body
Process Configuration
Analog Output
Correct Vol Flow
Calc Process Density
Electronics Temp
Mass Flow
Percent of Range
Primary Variable
Process Temp
Pulse Frequency
Shedding Frequency
Signal Strength
Total
Velocity Flow
Volume Flow
Primary Variable
Secondary Variable
Third Variable
Fourth Variable
Variable Mapping
Proc Variable Units
Special Units VF
Special Units MF
Special Units CVF
Process Conditions
Base Conditions
Process Pressure
Density Ratio
Analog Output
Pulse Output
Totalizer
Output Configuration
Transmitter Mode
Set Trans Mode
Process Fluid
Fixed Proc Temp
Fixed Proc Density
Pipe Inside Diameter
Meter Factor
Reference K-factor
Compensated K-factor
Upper Sensor Limit
Lower Sensor Limit
Set Process Fluid
Set Proc Temp
Set Fixed Process Density
Set Pipe Inside Diameter
Wetted Material
Flange Type
Meter Body Num
Body Num Suffix
T/C Failure Mode
Process Data
Filter Settings
Min Low Flow Cutoff
Damping
Signal Proc Config
Volume Flow/
Velocity Flow/
Mass Flow/
Process Temp
Shedding Frequency
Shed Freq at URV
Signal Strength
LFC in Eng Units
Low Flow Cutoff
LFC Response
LoPass Filt Value
Trigger Level
Flow Damping
Temp Damping
Optimize DSP
Restore Dflt Filter
Enable
Conf and Optimize
Manual Adjust
Status Gas Detect
Acknowledge Alarm
Alarm Count
Reset
Device ID
Universal
Field Device
Software
License Key
Upgrade License
SMART Fluid
Temp Comp Liquid
Process Conditions
User Defined
Proc Pressure
Temperature Unit
Proc Density
Number of Points
Table
Variable Mapping
Com Settings
Broadcast Inform
Primary Variable
Secondary Variable
Third Variable
Fourth Variable
Variable Mapping
Polling Address
Chng Poll Address1Num of Resp Preams
Universal
Change HART Rev
Message 1 Content
1
Message 2 Content
1
Message 3 Content
1
View/Conf Msg1
1
View/Conf Msg2
1
View/Conf Msg3
1
Identification
Revision Numbers
Alarm/Saturation Levels
Security
Tag
Long Tag1Model
Serial Number
Date
Description
Message
Alarm Direction
Alarm Level
High Alarm
High Saturation
Low Alarm
Low Saturation
Refresh
Universal
Field Device
Software
Hardware
DD Revision
Write Protect
Device is Locked/Unlocked1Lock/Unlock1Refresh
Volume Flow
Correct Vol Flow
Velocity Flow
Vel Measure Base
Mass Flow
Proc Temp
Elec Temp
Process Density
Base Volume Unit
Conversion Factor
Special Volume Unit
Base Time Unit
Special Flow Unit
Base Mass Unit
Conversion Factor
Special Mass Unit
Base Time Unit
Special Flow Unit
Base Volume Unit
Conversion Factor
Spec Cor Vol Unit
Base Time Unit
Special Flow Unit
Fix Proc Dens
Fix Proc Dens Units
Base Proc Dens
Base Proc Dens Units
Primary Variable
Unit
Upper Range Value
Lower Range Value
Upper Sensor Limit
Lower Sensor Limit
Minimum Span
Flow Damping
Temp Damping
Pulse Frequency
Pulse Output Mode
Pulse Scaling
Total
Totalizer Control
Totalizer Config
Analog Output
Config Pulse Output
Variable Mapping
NOTES:
1
HART 7 only
NOTES:
1
HART 7 only
Availability of options depends on configuration, such as using temperature compensation
(MTA option). The order in which parameters display may vary.
00809-0100-4004, Rev DC
Figure 2-2. Configure Menu Map
Configuration
May 2016
Configuration
19
Overview
Configure
Service Tools
Alerts
Variables
Trends
Maintenance
Simulate
Refresh Alerts
Clear Config Changed Flag
Active Alerts
Volume Flow
Status1Correct Vol Flow
Status1Velocity Flow
Status1Mass Flow
Status1Process
Status1Process Density
Status1Total
Shedding Frequency
Status1Pulse Frequency
Status1Electronics Temp
Status1Cold Junction Temp
Status
1
Variable Summary
Mapped Variables
Process Variables
Flow
Frequency
Diagnostics
Primary Variable
Secondary Variable
Third Variable
Fourth Variable
Analog Output
Primary Variable
PV Gauge
Status
Secondary Variable
SV Gauge
Status
Third Variable
TV Gauge
Status
Fourth Variable
QV Gauge
Status
PV Gauge
Status1Total
Status1Volume Flow Gauge
Status1Process Temp Gauge
Status1Calc Proc Density Gauge
Status
1
Volume Flow Gauge
Status1Cor Vol Flow Gauge
Status1Mass Flow Gauge
Status1Velocity Flow Gauge
Status1Total
Status
1
Process Trends
Frequency Trends
Diagnostic Trends
Volume Flow
Cor Vol Flow
Velocity Flow
Mass Flow
Process Temperature
Calc Proc Density
Shedding Frequency
Pulse Frequency
Signal Strength
Electronics Temperature
Meter Verification
Signal Processing
Analog Calibration
Reset/Restore
Flow Simulation
Analog Output
Pulse Output
Primary Variable
Primary Variable Value
Shedding Frequency
Analog Output
Pulse Frequency
Simulate Flow
Enable Norm Flow
Density Test Calc
Process Data
Filter Settings
Min Low Flow Cutoff
Damping
Signal Proc Config
Analog Output
Percent of Range
Primary Variable
Primary Variable Value
Upper Range Value
Lower Range Value
Analog Trim
Scaled Analog Trim
Restore Factry Cal
Transmitter Tests
Locate Device
1
Shed Freq Gauge
Status1Pulse Freq Gauge
Status
1
Sig Strength Gauge
Elect Temp Gauge
Status1Max Elect Temp
Min Elect Temp
PV Config
Flow Simulation Methods
Output Variables
Primary Variable
Unit
Upper Range Value
Lower Range Value
Upper Sensor Limit
Lower Sensor Limit
Minimum Span
Simulate Flow
Enable Norm Flow
Variable Mapping
Primary Variable Value
Shedding Frequency
Analog Output
Pulse Frequency
Analog Output
Percent of Range
Primary Variable
Primary Variable Value
Upper Range Value
Lower Range Value
Loop Test
Pulse Frequency
Pulse Output Mode
Pulse Scaling
Pulse Output Test
Volume Flow/Velocity Flow/Mass Flow/Process Temp
Shedding Frequency
Shed Freq at URV
Signal Strength
LFC in Eng Units
Low Flow Cutoff
LFC Response
Lowpass Corner Freq
LoPass Filt Value
Trigger Level
Flow Damping
Temp Damping
Optimize DSP
Restore Dflt Filter
Self Test
Reset Transmitter
NOTES:
1
HART 7 only
NOTES:
1
HART 7 only
Availability of options depends on configuration, such as using temperature compensation
(MTA option). The order in which parameters display may vary.
Configuration
May 2016
Figure 2-3. Service Tools Menu Map
Reference Manual
00809-0100-4004, Rev DC
20
Configuration
00809-0100-4004, Rev DC

Section 3 Installation

Safety messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 21
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 23
Hazardous locations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 26
Hardware configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 26
Meter body installation tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 28
Electronics considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 35
Software configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 43
Transient protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 46
Installation
May 2016
This section provides installation instructions for the Rosemount Flowmeter. Dimensional drawings for each Rosemount 8800D variation and mounting configuration are included in Appendix A: Specifications and Reference Data.
The options available for the Rosemount 8800D Flowmeter are also described in this section. The numbers in parentheses refer to the codes used to order each option.

3.1 Safety messages

Instructions and procedures in this section may require special precautions to ensure the safety of the personnel performing the operations. Please refer to the following safety messages before performing any operation in this section.
Explosions could result in death or serious injury.
Do not remove the transmitter cover in explosive atmospheres when the circuit is
alive.
Before connecting a HART
sure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
Verify the operating atmosphere of the transmitter is consistent with the appropriate
hazardous locations certifications.
Both transmitter covers must be fully engaged to meet explosion-proof requirements.
8800D Vortex
®
-based communicator in an explosive atmosphere, make
Installation
Failure to follow these installation guidelines could result in death or serious injury.
Make sure only qualified personnel perform the installation.
21
Installation
Is
Configuration
OK?
Mount
Flowmeter
Wire
Flowmeter
Power
Flowmeter
DONE
Mount
Conduit
START HERE
FIELD
INSTALL
CONFIGURE
Ta g
Process Config
Transmitter ModeProcess FluidFixed Process Temp.Base Density
(Std. or Normal Volumetric Flow Units Only)
Fixed Process Density
(Mass or Corrected Volume Flow Units Only)
No
Bench
Commissioning?
Review
Configuration
Yes
No
Yes
Did you
Configure on
Bench?
No
Yes
Configure if
Necessary
Go to
Review
Configuration
A
A
A
Go to
B
Go to
B
Reference
K-Factor
Mating Pipe ID
Variable Mapping
Flange Type
PV Unit
Range Values
PV Damping
Auto Adjust Filter
Using
LCD Display?
Yes
Configure
Local
Display
Using Pulse
Output?
No
Using
Tot a li ze r ?
Meter
Installed?
Configure
Pulse
Output
Yes
No
Configure
Tot a li ze r
Yes
No
Yes
No
DONE
May 2016
Figure 3-1. Installation Flowchart
Reference Manual
00809-0100-4004, Rev DC
22
Installation
Loading...
+ 158 hidden pages