This guide provides basic guidelines for the Rosemount™ 8800D Series
Vortex Flowmeter. It does not provide instructions for detailed configuration,
diagnostics, maintenance, service, troubleshooting, Explosion-proof,
Flameproof, or Intrinsically Safe (I.S.) installations. Refer to the reference
manual for more instruction. The manuals and this quick start guide are also
available electronically on EmersonProcess.com/Rosemount.
WARNING!
Explosions could result in death or serious injury.
Installation of this transmitter in an explosive environment must be in
accordance with the appropriate local, national, and international standards,
codes, and practices. Review the approvals section of thereference manual
for any restrictions associated with a safe installation.
• Before connecting a handheld communicator in an explosive
atmosphere, make sure the instruments in the loop are installed in
accordance with intrinsically safe or non-incendive field wiring practices.
• Verify the operating atmosphere of the flowmeter is consistent with the
appropriate product certifications.
• In an Explosion-proof/Flameproof installation, do not remove the
flowmeter covers when power is applied to the unit. Electrical shock can
result in death or serious injury.
April 2018
WARNING!
Electrical shock can result in death or serious injury.
• Avoid contact with the leads and terminals. High voltage that may be
present on leads can cause electrical shock.
1.1
2Rosemount 8800D Series Vortex Flowmeter
Return policy
Emerson procedures must be followed when returning equipment. These
procedures ensure legal compliance with government transportation
agencies and help provide a safe working environment for Emerson
employees. Failure to follow Emerson procedures will result in your
equipment being refused delivery.
April 2018Quick Start Guide
1.2Emerson Flow customer service
Email:
• Worldwide: flow.support@emerson.com
• Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South AmericaEurope and Middle EastAsia Pacific
Qatar431 0044Malaysia800 814 008
Kuwait663 299 01
South Africa800 991 390
Saudi Arabia800 844 9564
UAE800 0444 0684
+31 (0) 704 136
666
+41 (0) 41 7686
111
9811
New Zealand099 128 804
9000
Japan+81 3 5769
South Korea+82 2 3438
6803
4600
6426
Quick Start Guide 3
Quick Start Guide
2Installation
2.1Mount the flowmeter
Design process piping so the meter body will remain full, with no entrapped
air. The vortex flowmeter can be installed in any orientation without affecting
accuracy. However, the following are guidelines for certain installations.
2.1.1Vertical mounting
If the vortex flowmeter will be installed in a vertical orientation:
• Install upward or downward flow for gas or steam.
• Install upward flow for liquids.
Vertical installationFigure 2-1:
April 2018
BA
A. Gas flow
B. Liquid or gas flow
4Rosemount 8800D Series Vortex Flowmeter
April 2018
2.1.2Horizontal mounting
Horizontal installationFigure 2-2:
Quick Start Guide
A
A. Preferred installation—meter body installed with electronics to side of pipe
B. Acceptable installation—meter body installed with electronics above pipe
For steam and fluids with small solids content, it is recommended to have the
flowmeter installed with the electronics to the side of the pipe. This will
minimize potential measurement errors by allowing the condensate or solids
to flow under the shedder bar without interrupting the vortex shedding.
2.1.3High temperature mounting
The maximum temperature for integral electronics is dependent on the
ambient temperature where the flowmeter is installed. The electronics must
not exceed 185 °F (85 °C).
Figure 2-3 shows combinations of ambient and process temperatures needed
to maintain a housing temperature of less than 185 °F (85 °C).
B
Quick Start Guide 5
Quick Start Guide
A
A. Ambient temperature °F (°C)
B. Process temperature °F (°C)
C. 185 °F (85 °C) Housing temperature limit.
Note
The indicated limits are for horizontal pipe and vertical meter position, with meter
and pipe insulated with 3 in. (77 mm) of ceramic fiber insulation.
200 (93)
180(82)
160 (71)
140 (60)
120 (49)
100 (38)
80 (27)
60 (16)
April 2018
Ambient/Process temperature limitsFigure 2-3:
C
0
100 (38)
200 (93)
300 (149)
400 (204)
500 (260)
600 (316)
700 (371)
800 (427)
900 (482)
1000 (538)
B
The following orientations are recommended for applications with high
process temperatures.
• Install with electronics head beside or below process pipe.
• Insulation around pipe may be necessary to maintain ambient
temperature below 185 °F (85 °C).
Note
Insulate pipe and meter body only. Do not insulate support tube bracket or
transmitter so heat can be dissipated.
2.1.4Steam installations
Avoid installation shown in Figure 2-4. Such conditions may cause a waterhammer condition at start-up due to trapped condensation.
6Rosemount 8800D Series Vortex Flowmeter
April 2018
Improper installationFigure 2-4:
2.1.5Upstream/downstream requirements
The flowmeter may be installed with a minimum of ten straight pipe
diameters (D) upstream and five straight pipe diameters (D) downstream by
following the K-factor corrections as described in the 8800 Installation Effects
Technical Data Sheet (00816-0100-3250). No K-factor correction is required
if 35 straight pipe diameters upstream (35D) and 10 straight pipe diameters
downstream (10D) are present.
Quick Start Guide
2.1.6External pressure/temperature transmitters
When using pressure and temperature transmitters in conjunction with the
flowmeter for compensated mass flows, install the transmitters downstream
of the flowmeter as shown in Figure 2-5.
Quick Start Guide 7
Quick Start Guide
Upstream/Downstream pipingFigure 2-5:
A. Pressure transmitter
B. Four straight pipe diameters downstream
C. Temperature transmitter
D. Six straight pipe diameters downstream
2.1.7Wafer style installation
April 2018
C
A
B
D
Wafer style installationFigure 2-6:
B
B
A
D
C
A. Installation studs and nuts (supplied by customer)
B. Alignment ring
C. Gaskets (supplied by customer)
D. Flow direction
8Rosemount 8800D Series Vortex Flowmeter
April 2018
2.1.8Flanged style installation
Flanged style installationFigure 2-7:
A
Quick Start Guide
B
C
A. Installation bolts and nuts (supplied by customer)
B. Gaskets (supplied by customer)
C. Flow direction
Note
The required bolt load for sealing the gasket joint is affected by several factors,
including operating pressure, gasket material, width, and condition. A number of
factors also affect the actual bolt load resulting from a measured torque,
including condition of bolt threads, friction between the nut head and the flange,
and parallelism of the flanges. Due to these application-dependent factors, the
required torque for each application may be different. Follow the guidelines
outlined in ASME PCC-1 for proper bolt tightening. Make sure the flowmeter is
centered between flanges of the same nominal size as the flowmeter.
2.1.9Insert integral temperature sensor (MTA option only)
Note
Step number of procedure corresponds with number in Figure 2-8.
Quick Start Guide 9
Quick Start Guide
Procedure
1. Slide the thermocouple bolt (1) over the thermocouple (TC).
2. Place the 2-part ferrule (2) over the end tip of the thermocouple (TC).
3. Insert the thermocouple in to the thermowell hole (TW) on the bottom
side of the meter body.
April 2018
Thermocouple assemblyFigure 2-8:
Important
Carefully push the thermocouple in to the thermowell completely. This is
critical to get the proper insertion depth. Then thread the thermocouple
bolt in to the hole.
4. When the thermocouple bolt is hand tight, mark the position of the bolt
in relation to the meter body (the mark will help determine rotations).
Using a ½-in. wrench turn the bolt clockwise ¾ turn to seat the ferrule.
Note
After completing Step 4, the ferrule and thermocouple bolt will be
permanently installed on the thermocouple.
5. Verify the rubber O-ring is installed on the electronics connection end of
the thermocouple.
6. Verify the 2.5 mm hex head screw is installed.
7. Insert the electronics end connector in to the transmitter housing.
Tighten the screw with a 2.5 mm hex bit to secure the connection.
10Rosemount 8800D Series Vortex Flowmeter
April 2018
Important
Do not over tighten hex screw.
2.2Install remote electronics
If you order one of the remote electronics options (options R10, R20, R30, or
RXX), the flowmeter assembly ships in two parts:
1. The meter body with an adapter installed in the support tube and an
interconnecting coaxial cable attached to it.
2. The electronics housing installed on a mounting bracket.
If you ordered the armored remote electronics options, follow the same
instructions as for the standard remote cable connection with the exception
that the cable may not need to be run through conduit. Armored includes the
glands.
Refer to Figure 2-9 and these steps to connect the loose end of the coaxial
cable to the electronics housing.
Quick Start Guide
Quick Start Guide 11
Quick Start Guide
April 2018
Remote electronics installationFigure 2-9:
A
B
C
J
D
E
F
P
G
O
H
N
K
I
M
L
A. 1/2 NPT conduit adapter or cable gland (supplied by customer)
B. Coaxial cable
C. Meter adapter
D. Union
E. Washer
F. Nut
G. Sensor cable nut
H. Support tube
I. Meter body
J. Electronics housing
K. Coaxial cable nut
L. Conduit adapter (optional-supplied by customer)
M. Housing adapter screws
N. Housing adapter
O. Housing base screw
P. Ground connection
Prerequisites
1. Mount the meter body in the process flow line as described in Section 2.1.
2. Mount the bracket and electronics housing in the desired location. The
housing can be repositioned on the bracket to facilitate field wiring and
conduit routing.
12Rosemount 8800D Series Vortex Flowmeter
April 2018
Quick Start Guide
Procedure
1. If you plan to run the coaxial cable in conduit, carefully cut the conduit to
the desired length to provide for proper assembly at the housing. A
junction box may be placed in the conduit run to provide a space for extra
coaxial cable length.
CAUTION!
The coaxial remote cable cannot be field terminated or cut to length. Coil
any extra coaxial cable with no less than a 2-in. (51 mm) radius.
2. Slide the conduit adapter or cable gland over the loose end of the coaxial
cable and fasten it to the adapter on the meter body support tube.
3. If using conduit, route the coaxial cable through the conduit.
4. Place a conduit adapter or cable gland over the end of the coaxial cable.
5. Remove the housing adapter from the electronics housing.
6. Slide the housing adapter over the coaxial cable.
7. Remove one of the four housing base screws.
8. Attach and securely tighten the coaxial cable nut to the connection on
the electronics housing.
9. Attach the coaxial cable ground wire to the housing via the housing base
ground screw.
10. Align the housing adapter with the housing and attach with two screws.
11. Tighten the conduit adapter or cable gland to the housing adapter.
CAUTION!
To prevent moisture from entering the coaxial cable connections, install
the interconnecting coaxial cable in a single dedicated conduit run or use
sealed cable glands at both ends of the cable.
Note
Refer to the reference manual for details for the CPA option.
Quick Start Guide 13
Quick Start Guide
3Consider housing rotation
The entire electronics housing may be rotated in 90° increments for easy
viewing. Use the following steps to change the housing orientation,
1. Loosen the three housing rotation set screws at the base of the
electronics housing with a 5/32” hex wrench by turning the screws
clockwise (inward) until they clear the support tube.
2. Slowly pull the electronics housing out of the support tube.
CAUTION!
Do not pull the housing more than 1.5 in. (40 mm) from the top of the
support tube until the sensor cable is disconnected. Damage to the
sensor may occur if this sensor cable is stressed.
3. Unscrew the sensor cable from the housing with a 5/16” open end
wrench.
4. Rotate the housing to the desired orientation.
5. Hold it in this orientation while you screw the sensor cable onto the base
of the housing.
April 2018
CAUTION!
Do not rotate the housing while the sensor cable is attached to the base
of the housing. This will stress the cable and may damage the sensor.
6. Place the electronics housing into the top of the support tube.
7. Use a hex wrench to turn the three housing rotation screws counterclockwise (outward) to engage the support tube.
14Rosemount 8800D Series Vortex Flowmeter
April 2018
4Set jumpers
Adjust jumpers to desired settings.
4.1HART jumpers
If alarm and security jumpers are not installed, the flowmeter will operate
normally with the default alarm condition alarm high and the security off.
HART jumpers and LCD displayFigure 4-1:
Quick Start Guide
4.2Foundation fieldbus
If security and simulate enable jumpers are not installed, the flowmeter will
operate normally with the default security “OFF” and simulate enable “OFF”.
HI
SECURITY
ON
LO
ALARM
OFF
Quick Start Guide 15
Quick Start GuideApril 2018
Foundation fieldbus jumpers and LCD displayFigure 4-2:
OFF
SIMULATE ENABLE
SECURITY
ON
OFF
ON
16Rosemount 8800D Series Vortex Flowmeter
April 2018
5Connect wiring and power up
5.1Power supply (HART)
The dc power supply should provide power with less than two percent ripple.
The total resistance load is the sum of the resistance of the signal leads and
the load resistance of the controller, indicator, and related pieces. Note that
the resistance of intrinsic safety barriers, if used, must be included.
Load limitationFigure 5-1:
1500
1250
1000
750
A
500
250
0
10.8 16.822.828.834.842
B
Quick Start Guide
A. Rloop in ohms
B. Power supply voltage
Maximum Loop Resistance = 41.7 (Power Supply Voltage - 10.8) The Field
Communicator requires a minimum loop resistance of 250 ohms.
5.2
5.3
Quick Start Guide 17
Power supply (Foundation fieldbus)
The flowmeter requires 9-32 Vdc at the power terminals. Each fieldbus power
supply requires a power conditioner to decouple the power supply output
from the fieldbus wiring segment.
Conduit installation
Prevent condensation in any conduit from flowing into the housing by
mounting the flowmeter at a high point in the conduit run. If the flowmeter is
mounted at a low point in the conduit run, the terminal compartment could
fill with fluid.
If the conduit originates above the flowmeter, route conduit below the
flowmeter before entry. In some cases a drain seal may need to be installed.
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.