Rosemount 8800D Installation Guide

Quick Start Guide
00825-0100-4004, Rev FD
Rosemount® 8800D Series Vortex Flowmeter
April 2018
Quick Start Guide

1 About this guide

This guide provides basic guidelines for the Rosemount™ 8800D Series Vortex Flowmeter. It does not provide instructions for detailed configuration, diagnostics, maintenance, service, troubleshooting, Explosion-proof, Flameproof, or Intrinsically Safe (I.S.) installations. Refer to the reference manual for more instruction. The manuals and this quick start guide are also available electronically on EmersonProcess.com/Rosemount.
WARNING!
Explosions could result in death or serious injury. Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Review the approvals section of thereference manual for any restrictions associated with a safe installation.
Before connecting a handheld communicator in an explosive
atmosphere, make sure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
Verify the operating atmosphere of the flowmeter is consistent with the
appropriate product certifications.
In an Explosion-proof/Flameproof installation, do not remove the
flowmeter covers when power is applied to the unit. Electrical shock can result in death or serious injury.
April 2018
WARNING!
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be
present on leads can cause electrical shock.
1.1
2 Rosemount 8800D Series Vortex Flowmeter

Return policy

Emerson procedures must be followed when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Emerson employees. Failure to follow Emerson procedures will result in your equipment being refused delivery.
April 2018 Quick Start Guide

1.2 Emerson Flow customer service

Email:
Worldwide: flow.support@emerson.com
Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America Europe and Middle East Asia Pacific
United States 800 522 6277 U.K. 0870 240 1978 Australia 800 158 727 Canada +1 303 527
Mexico +41 (0) 41 7686
Argentina +54 11 4837
Brazil +55 15 3413
Venezuela +58 26 1731
5200
111
7000
8000
3446
The Nether­lands
France 0800 917 901 India 800 440 1468
Germany 0800 182 5347 Pakistan 888 550 2682
Italy 8008 77334 China +86 21 2892
Central & East­ern
Russia/CIS +7 495 981
Egypt 0800 000 0015 Singapore +65 6 777 8211 Oman 800 70101 Thailand 001 800 441
Qatar 431 0044 Malaysia 800 814 008 Kuwait 663 299 01 South Africa 800 991 390 Saudi Arabia 800 844 9564 UAE 800 0444 0684
+31 (0) 704 136 666
+41 (0) 41 7686 111
9811
New Zealand 099 128 804
9000
Japan +81 3 5769
South Korea +82 2 3438
6803
4600
6426
Quick Start Guide 3
Quick Start Guide

2 Installation

2.1 Mount the flowmeter

Design process piping so the meter body will remain full, with no entrapped air. The vortex flowmeter can be installed in any orientation without affecting accuracy. However, the following are guidelines for certain installations.

2.1.1 Vertical mounting

If the vortex flowmeter will be installed in a vertical orientation:
Install upward or downward flow for gas or steam.
Install upward flow for liquids.
Vertical installationFigure 2-1:
April 2018
BA
A. Gas flow B. Liquid or gas flow
4 Rosemount 8800D Series Vortex Flowmeter
April 2018

2.1.2 Horizontal mounting

Horizontal installationFigure 2-2:
Quick Start Guide
A
A. Preferred installation—meter body installed with electronics to side of pipe B. Acceptable installation—meter body installed with electronics above pipe
For steam and fluids with small solids content, it is recommended to have the flowmeter installed with the electronics to the side of the pipe. This will minimize potential measurement errors by allowing the condensate or solids to flow under the shedder bar without interrupting the vortex shedding.

2.1.3 High temperature mounting

The maximum temperature for integral electronics is dependent on the ambient temperature where the flowmeter is installed. The electronics must not exceed 185 °F (85 °C).
Figure 2-3 shows combinations of ambient and process temperatures needed
to maintain a housing temperature of less than 185 °F (85 °C).
B
Quick Start Guide 5
Quick Start Guide
A
A. Ambient temperature °F (°C) B. Process temperature °F (°C) C. 185 °F (85 °C) Housing temperature limit.
Note
The indicated limits are for horizontal pipe and vertical meter position, with meter and pipe insulated with 3 in. (77 mm) of ceramic fiber insulation.
200 (93)
180(82)
160 (71) 140 (60)
120 (49) 100 (38)
80 (27) 60 (16)
April 2018
Ambient/Process temperature limitsFigure 2-3:
C
0
100 (38)
200 (93)
300 (149)
400 (204)
500 (260)
600 (316)
700 (371)
800 (427)
900 (482)
1000 (538)
B
The following orientations are recommended for applications with high process temperatures.
Install with electronics head beside or below process pipe.
Insulation around pipe may be necessary to maintain ambient
temperature below 185 °F (85 °C).
Note
Insulate pipe and meter body only. Do not insulate support tube bracket or transmitter so heat can be dissipated.

2.1.4 Steam installations

Avoid installation shown in Figure 2-4. Such conditions may cause a water­hammer condition at start-up due to trapped condensation.
6 Rosemount 8800D Series Vortex Flowmeter
April 2018
Improper installationFigure 2-4:

2.1.5 Upstream/downstream requirements

The flowmeter may be installed with a minimum of ten straight pipe diameters (D) upstream and five straight pipe diameters (D) downstream by following the K-factor corrections as described in the 8800 Installation Effects Technical Data Sheet (00816-0100-3250). No K-factor correction is required if 35 straight pipe diameters upstream (35D) and 10 straight pipe diameters downstream (10D) are present.
Quick Start Guide

2.1.6 External pressure/temperature transmitters

When using pressure and temperature transmitters in conjunction with the flowmeter for compensated mass flows, install the transmitters downstream of the flowmeter as shown in Figure 2-5.
Quick Start Guide 7
Quick Start Guide
Upstream/Downstream pipingFigure 2-5:
A. Pressure transmitter B. Four straight pipe diameters downstream C. Temperature transmitter D. Six straight pipe diameters downstream
2.1.7 Wafer style installation
April 2018
C
A
B
D

Wafer style installationFigure 2-6:

B
B
A
D
C
A. Installation studs and nuts (supplied by customer) B. Alignment ring C. Gaskets (supplied by customer) D. Flow direction
8 Rosemount 8800D Series Vortex Flowmeter
April 2018
2.1.8 Flanged style installation

Flanged style installationFigure 2-7:

A
Quick Start Guide
B
C
A. Installation bolts and nuts (supplied by customer) B. Gaskets (supplied by customer) C. Flow direction
Note
The required bolt load for sealing the gasket joint is affected by several factors, including operating pressure, gasket material, width, and condition. A number of factors also affect the actual bolt load resulting from a measured torque, including condition of bolt threads, friction between the nut head and the flange, and parallelism of the flanges. Due to these application-dependent factors, the required torque for each application may be different. Follow the guidelines outlined in ASME PCC-1 for proper bolt tightening. Make sure the flowmeter is centered between flanges of the same nominal size as the flowmeter.

2.1.9 Insert integral temperature sensor (MTA option only)

Note
Step number of procedure corresponds with number in Figure 2-8.
Quick Start Guide 9
Quick Start Guide
Procedure
1. Slide the thermocouple bolt (1) over the thermocouple (TC).
2. Place the 2-part ferrule (2) over the end tip of the thermocouple (TC).
3. Insert the thermocouple in to the thermowell hole (TW) on the bottom side of the meter body.
April 2018
Thermocouple assemblyFigure 2-8:
Important
Carefully push the thermocouple in to the thermowell completely. This is critical to get the proper insertion depth. Then thread the thermocouple bolt in to the hole.
4. When the thermocouple bolt is hand tight, mark the position of the bolt in relation to the meter body (the mark will help determine rotations). Using a ½-in. wrench turn the bolt clockwise ¾ turn to seat the ferrule.
Note
After completing Step 4, the ferrule and thermocouple bolt will be permanently installed on the thermocouple.
5. Verify the rubber O-ring is installed on the electronics connection end of the thermocouple.
6. Verify the 2.5 mm hex head screw is installed.
7. Insert the electronics end connector in to the transmitter housing. Tighten the screw with a 2.5 mm hex bit to secure the connection.
10 Rosemount 8800D Series Vortex Flowmeter
April 2018
Important
Do not over tighten hex screw.

2.2 Install remote electronics

If you order one of the remote electronics options (options R10, R20, R30, or RXX), the flowmeter assembly ships in two parts:
1. The meter body with an adapter installed in the support tube and an interconnecting coaxial cable attached to it.
2. The electronics housing installed on a mounting bracket.
If you ordered the armored remote electronics options, follow the same instructions as for the standard remote cable connection with the exception that the cable may not need to be run through conduit. Armored includes the glands.
Refer to Figure 2-9 and these steps to connect the loose end of the coaxial cable to the electronics housing.
Quick Start Guide
Quick Start Guide 11
Quick Start Guide
April 2018
Remote electronics installationFigure 2-9:
A
B
C
J
D
E F
P
G
O
H
N
K
I
M
L
A. 1/2 NPT conduit adapter or cable gland (supplied by customer) B. Coaxial cable C. Meter adapter D. Union E. Washer F. Nut G. Sensor cable nut H. Support tube I. Meter body J. Electronics housing K. Coaxial cable nut L. Conduit adapter (optional-supplied by customer) M. Housing adapter screws N. Housing adapter O. Housing base screw P. Ground connection
Prerequisites
1. Mount the meter body in the process flow line as described in Section 2.1.
2. Mount the bracket and electronics housing in the desired location. The housing can be repositioned on the bracket to facilitate field wiring and conduit routing.
12 Rosemount 8800D Series Vortex Flowmeter
April 2018
Quick Start Guide
Procedure
1. If you plan to run the coaxial cable in conduit, carefully cut the conduit to the desired length to provide for proper assembly at the housing. A junction box may be placed in the conduit run to provide a space for extra coaxial cable length.
CAUTION!
The coaxial remote cable cannot be field terminated or cut to length. Coil any extra coaxial cable with no less than a 2-in. (51 mm) radius.
2. Slide the conduit adapter or cable gland over the loose end of the coaxial cable and fasten it to the adapter on the meter body support tube.
3. If using conduit, route the coaxial cable through the conduit.
4. Place a conduit adapter or cable gland over the end of the coaxial cable.
5. Remove the housing adapter from the electronics housing.
6. Slide the housing adapter over the coaxial cable.
7. Remove one of the four housing base screws.
8. Attach and securely tighten the coaxial cable nut to the connection on the electronics housing.
9. Attach the coaxial cable ground wire to the housing via the housing base ground screw.
10. Align the housing adapter with the housing and attach with two screws.
11. Tighten the conduit adapter or cable gland to the housing adapter.
CAUTION!
To prevent moisture from entering the coaxial cable connections, install the interconnecting coaxial cable in a single dedicated conduit run or use sealed cable glands at both ends of the cable.
Note
Refer to the reference manual for details for the CPA option.
Quick Start Guide 13
Quick Start Guide

3 Consider housing rotation

The entire electronics housing may be rotated in 90° increments for easy viewing. Use the following steps to change the housing orientation,
1. Loosen the three housing rotation set screws at the base of the electronics housing with a 5/32” hex wrench by turning the screws clockwise (inward) until they clear the support tube.
2. Slowly pull the electronics housing out of the support tube.
CAUTION!
Do not pull the housing more than 1.5 in. (40 mm) from the top of the support tube until the sensor cable is disconnected. Damage to the sensor may occur if this sensor cable is stressed.
3. Unscrew the sensor cable from the housing with a 5/16” open end wrench.
4. Rotate the housing to the desired orientation.
5. Hold it in this orientation while you screw the sensor cable onto the base of the housing.
April 2018
CAUTION!
Do not rotate the housing while the sensor cable is attached to the base of the housing. This will stress the cable and may damage the sensor.
6. Place the electronics housing into the top of the support tube.
7. Use a hex wrench to turn the three housing rotation screws counter­clockwise (outward) to engage the support tube.
14 Rosemount 8800D Series Vortex Flowmeter
April 2018

4 Set jumpers

Adjust jumpers to desired settings.

4.1 HART jumpers

If alarm and security jumpers are not installed, the flowmeter will operate normally with the default alarm condition alarm high and the security off.
HART jumpers and LCD displayFigure 4-1:
Quick Start Guide

4.2 Foundation fieldbus

If security and simulate enable jumpers are not installed, the flowmeter will operate normally with the default security “OFF” and simulate enable “OFF”.
HI
SECURITY
ON
LO
ALARM
OFF
Quick Start Guide 15
Quick Start Guide April 2018
Foundation fieldbus jumpers and LCD displayFigure 4-2:
OFF
SIMULATE ENABLE
SECURITY
ON
OFF
ON
16 Rosemount 8800D Series Vortex Flowmeter
April 2018

5 Connect wiring and power up

5.1 Power supply (HART)

The dc power supply should provide power with less than two percent ripple. The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller, indicator, and related pieces. Note that the resistance of intrinsic safety barriers, if used, must be included.
Load limitationFigure 5-1:
1500 1250
1000
750
A
500 250
0
10.8 16.8 22.8 28.8 34.8 42
B
Quick Start Guide
A. Rloop in ohms B. Power supply voltage
Maximum Loop Resistance = 41.7 (Power Supply Voltage - 10.8) The Field Communicator requires a minimum loop resistance of 250 ohms.
5.2
5.3
Quick Start Guide 17

Power supply (Foundation fieldbus)

The flowmeter requires 9-32 Vdc at the power terminals. Each fieldbus power supply requires a power conditioner to decouple the power supply output from the fieldbus wiring segment.

Conduit installation

Prevent condensation in any conduit from flowing into the housing by mounting the flowmeter at a high point in the conduit run. If the flowmeter is mounted at a low point in the conduit run, the terminal compartment could fill with fluid.
If the conduit originates above the flowmeter, route conduit below the flowmeter before entry. In some cases a drain seal may need to be installed.
Loading...
+ 39 hidden pages