Rosemount 8782 Transmitter Manuals & Guides

Page 1
Supplemental Guide
00825-1100-8782, Rev AB
December 2020
Replacing a Rosemount™ 8712H Transmitter with a Rosemount 8782 Transmitter
Page 2
Supplemental Guide December 2020

1 Safety

WARNING
Failure to follow these installation guidelines could result in serious injury
or death.
Installation and servicing instructions are for use by qualified personnel
only. Do not perform any servicing other than that contained in the operating instructions, unless qualified.
Potential electrostatic charging hazard: Rosemount Magnetic flow
meters ordered with non-standard paint options or non-metallic labels may be subject to electrostatic discharge. To avoid electrostatic charge build-up, do not rub the flow meter with a dry cloth or clean with solvents.
Verify that the operating environment of the sensor and transmitter is
consistent with the appropriate Agency Approval.
If installed in an explosive atmosphere, verify that the device certification
and installation techniques are suitable for that particular environment.
To prevent ignition of flammable or combustible atmosphere,
disconnect power before servicing circuits.
Explosion hazard: Do not disconnect equipment when a flammable or
combustible atmosphere is present.
Do not connect a Rosemount 8782 Transmitter to a non-Rosemount
sensor.
Follow national, local, and plant standards to properly earth ground the
transmitter and sensor. The earth ground must be separate from the process reference ground.
Shock hazard: Shut off power before servicing. Do not operate without
power compartment cover.
2 Replacing a Rosemount™ 8712H transmitter with a Rosemount 8782 transmitter
Page 3
December 2020 Supplemental Guide
CAUTION
The sensor liner is vulnerable to handling damage. Liner damage can
render the sensor useless. Failure to observe these instructions could result in severe damage to the sensor lining and possible sensor replacement.
To avoid possible damage to the sensor liner ends:Do not use metallic or spiral-wound gaskets. If spiral wound or
metallic gaskets are required for the application, lining protectors must be used.
If frequent removal is anticipated, attach short spool pieces to the
sensor ends.
Tighten bolts in the proper sequence to the specified torque limits.
Correct flange bolt tightening is crucial for proper sensor operation and life.
In cases where high voltage/high current are present near the meter
installation, ensure proper protection methods are followed to prevent stray voltage/current from passing through the meter. Failure to adequately protect the meter could result in damage to the transmitter and lead to meter failure.
Completely remove all electrical connections from both sensor and
transmitter prior to welding on the pipe. For maximum protection of the sensor, consider removing it from the pipeline.
Supplemental Guide 3
Page 4
Supplemental Guide December 2020

2 Introduction

This document provides specific instructions for replacing a Rosemount 8712H transmitter with a Rosemount 8782 Magnetic Slurry wall-mount transmitter, when used with a Rosemount 8707 sensor only.
For additional transmitter installation information, configuration,
maintenance, and troubleshooting, refer to the Rosemount™ 8782
Magnetic Slurry Flow Meter with HART Protocol Reference Manual
For sensor installation refer to the Rosemount™ 8700 Series Magnetic
Flowmeter Sensors Reference Manual
All user documentation can be found at www.emerson.com. For more contact information see Emerson Flow customer service.

2.1 Return policy

Emerson procedures must be followed when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Emerson employees. Failure to follow Emerson procedures will result in your equipment being refused delivery.
4 Replacing a Rosemount™ 8712H transmitter with a Rosemount 8782 transmitter
Page 5
December 2020 Supplemental Guide

2.2 Emerson Flow customer service

Email:
Worldwide: flow.support@emerson.com
Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America Europe and Middle East Asia Pacific
United States 800 522 6277 U.K. 0870 240
Canada +1 303 527
5200
Mexico +41 (0) 41
7686 111
Argentina +54 11 4837
7000
Brazil +55 15 3413
8000
Venezuela +58 26 1731
3446
The Netherlands
France 0800 917 901 India 800 440 1468
Germany 0800 182
Italy 8008 77334 China +86 21 2892
Central & Eastern Europe
Russia/CIS +7 495 995
Egypt 0800 000
Oman 800 70101 Thailand 001 800 441
Qatar 431 0044 Malaysia 800 814 008
Kuwait 663 299 01
South Africa 800 991 390
Saudi Arabia 800 844 9564
UAE 800 0444
1978
+31 (0) 704 136 666
5347
+41 (0) 41 7686 111
9559
0015
0684
Australia 800 158 727
New Zealand 099 128 804
Pakistan 888 550 2682
9000
Japan +81 3 5769
6803
South Korea +82 2 3438
4600
Singapore +65 6 777
8211
6426
Supplemental Guide 5
Page 6
Supplemental Guide December 2020

3 Replacement

Review the entire transmitter Quick Start Guide that was shipped with the transmitter. If you do not have the Quick Start Guide, contact an Emerson Flow representative (see back page) before performing this procedure.
1. Put the loop in manual control and record the current flow rate on the existing transmitter.
The recorded value will be necessary to calculate the meter factor (correction) for the new transmitter. If the existing transmitter is inoperable, you will need to run the process at a known flow rate to calculate the meter factor during configuration.
2. Power down the existing 8712H transmitter.
3. Label and remove each wire connected to the existing transmitter terminals with the number from the terminal from which it was removed. For the Analog Output wires connected to Terminal #7 and #8, include the polarity, either negative or positive, on the labels.
4. Remove the blade connectors from the wires, and prepare the wires for use with the screw terminals on the new transmitter.
The same wiring that was used to wire the existing transmitter can be used to wire the new transmitter. No new wiring is required. The wires can be minimally stripped or prepared with spade terminals as desired. If replacing any cabling, ensure the electrode cabling includes a separate drain wire for optimum noise mitigation.
5. Complete the removal of the cables and connectors so they are completely free of the existing transmitter housing.
6. Physically remove the existing transmitter and replace it with the new transmitter. The new transmitter can use the same mounting method as the existing transmitter without modification.
7. Run the cables with the prepared wires through the appropriate conduit openings on the new transmitter.
8. Connect the sensor to transmitter wires to the same numbered terminals to which they were connected on the existing transmitter (Terminals #1, #2, #17, #18, and #19); the coil ground (drain) wire from the existing transmitter is connected to Terminal #3 on the new transmitter. Terminal locations and identification are shown in Figure
3-1.
6 Replacing a Rosemount™ 8712H transmitter with a Rosemount 8782 transmitter
Page 7
5 6 7 8 17 18 19
L1
1 2
N
9 10 16 20
A
B
December 2020 Supplemental Guide
Figure 3-1: Compared Rosemount 8712H and 8782 terminal configurations
A. Rosemount 8712H terminal configuration B. Rosemount 8782 terminal configuration
9. Connect any Input/Output wires to the same-labeled terminals to which they were connected on the existing transmitter, with one likely exception for the Analog Output wires.
For the Analog Output wires, pay special attention to the polarity of the terminals, because it may be different between the 8712H and
8782. For the 8712H, Terminal #7 was positive (+) and Terminal #8 was negative (–). The polarity of the Analog Output terminals for the 8782 is dependent on the power source type, which is determined by a hardware switch. See Table 3-1 for the Analog Output terminal polarity.
Supplemental Guide 7
Page 8
Supplemental Guide December 2020
Table 3-1: 8782 terminal assignment by Analog Output power source type
Power source Terminal #7 Terminal #8
Internal 4–20 mA negative (–) 4–20 mA positive (+)
External 4–20 mA positive (+) 4–20 mA negative (–)
10. Verify that power to the transmitter is still disconnected, and then connect the power supply wires to the same labeled terminals to which they were connected on the existing transmitter.
Important
Do not connect the power supply ground wire to Terminal #3; connect it to the earth ground terminal screw in the upper left corner of the terminal compartment.
11. Seal the conduit in accordance with local and plant electrical codes.
12. Close terminal compartment, tightening the cover screw until a tight metal-to-metal contact is obtained.
13. If the 8782 is DC powered (8782AW2xxxxx) and is replacing an 8712H with F0227, ensure the power going to the 8782 is 12– 24V DC.
14. Power on the transmitter and verify that there are no errors or fault messages.
8 Replacing a Rosemount™ 8712H transmitter with a Rosemount 8782 transmitter
Page 9
December 2020 Supplemental Guide

4 Configuration

Review the entire transmitter Quick Start Guide that was shipped with the transmitter. If you do not have the Quick Start Guide, contact an Emerson Flow representative (see back page) before performing this procedure.
Basic configuration
Complete the basic setup as described in the transmitter Quick Start Guide, to configure the Calibration number, flow units (PV), Line size, URV, and LRV.
Advanced configuration
Advanced Configuration enhances the performance of the 8782 when paired with a legacy sensor. Perform the Advanced Configuration steps to get the most out of the 8782 without an MS sensor. Review the transmitter product reference manual, which is available online (see back page), for more information about advanced transmitter configuration.
1. If possible, perform an Auto Zero Trim. The flow must be stopped and the pipe full.
2. Restart the flow at the same known, stable flow rate that was used when the flow rate was recorded prior to removing the 8712H transmitter.
3. If the 8782 transmitter is reading a different flow rate than the 8712H, calculate the Meter Factor to correct the 8782. Use one of the following methods:
With the process moving at the same flow rate as earlier, when
the flow rate was recorded, divide the recorded rate by the current flow rate being reported by the new transmitter.
With the process moving at a known flow rate, divide the known
flow rate by the current flow rate being reported by the new transmitter.
The resulting Meter Factor must be a number between 0.2000 and
1.8000, with most Meter Factors for this application being between
0.9500 to 0.9999. For example, if the recorded flow rate from the 8712H was 100 GPM, and the current flow rate reading on the 8782 is 102 GPM, the meter factor is 100 / 102 = 0.9804.
4. Enter the calculated Meter Factor into the transmitter. The menu path is Detailed Setup More Params Meter Factor. With the Meter Factor applied, the measured flow rate should match the known flow rate.
5. If the measured flow rate does not acceptably match the known flow rate, verify the calculation and entry of the Meter Factor, and repeat if necessary.
Supplemental Guide 9
Page 10
Supplemental Guide December 2020

5 Product Certifications

For detailed approval certification information and installation drawings, please see the appropriate document listed below:
Document number 00825-MA00-0009: Rosemount 8782 and MS
Approval Document - Class Division
Document number 00825-MA00-0010: Rosemount 8782 and MS
Approval Document - IECEx and ATEX
Document number 00825-MA00-0011: Rosemount 8782 and MS
Approval Document - North America Zone
Document number 00825-MA00-0012: Rosemount 8785 Approval
Document
Document number 00825-MA00-0013: Rosemount 8782 and MS
Approval Document - EAC EX
10 Replacing a Rosemount™ 8712H transmitter with a Rosemount 8782 transmitter
Page 11
December 2020 Supplemental Guide
Supplemental Guide 11
Page 12
*00825-1100-8782*
Supplemental Guide
00825-1100-8782, Rev. AB
December 2020
Emerson Automation Solutions USA
7070 Winchester Circle Boulder, Colorado USA 80301 T +1 303-527-5200 T +1 800-522-6277 F +1 303-530-8459
www.emerson.com
Emerson Automation Solutions Europe
Neonstraat 1 6718 WX Ede The Netherlands T +31 (0) 318 495 555 F +31 (0) 318 495 556
©
2020 Rosemount, Inc. All rights reserved.
The Emerson and Rosemount logos are trademarks and service marks of Emerson Electric Co. All other marks are property of their respective owners.
Emerson Automation Solutions Asia
1 Pandan Crescent Singapore 128461 Republic of Singapore T +65 6363-7766 F +65 6770-8003
Emerson Automation Solutions United Kingdom
Emerson Process Management Limited Horsfield Way Bredbury Industrial Estate Stockport SK6 2SU U.K. T +44 0870 240 1978 F +44 0800 966 181
Loading...