Rosemount 8782 Quick Start Guide

Quick Start Guide
00825-0100-8782, Rev AA
November 2019
Rosemount™ 8782 Slurry Magnetic Flow Meter Transmitter
Quick Start Guide November 2019

1 Safety

Failure to follow these installation guidelines could result in serious injury
or death.
Installation and servicing instructions are for use by qualified personnel
only. Do not perform any servicing other than that contained in the operating instructions, unless qualified.
Potential electrostatic charging hazard: Rosemount Magnetic flow
meters ordered with non-standard paint options or non-metallic labels may be subject to electrostatic discharge. To avoid electrostatic charge build-up, do not rub the flow meter with a dry cloth or clean with solvents.
Verify that the operating environment of the sensor and transmitter is
consistent with the appropriate Agency Approval.
If installed in an explosive atmosphere, verify that the device certification
and installation techniques are suitable for that particular environment.
To prevent ignition of flammable or combustible atmosphere,
disconnect power before servicing circuits.
Explosion hazard: Do not disconnect equipment when a flammable or
combustible atmosphere is present.
Follow national, local, and plant standards to properly earth ground the
transmitter and sensor. The earth ground must be separate from the process reference ground.
Shock hazard: Shut off power before servicing. Do not operate without
power compartment cover.
CAUTION
In cases where high voltage/high current are present near the meter
installation, ensure proper protection methods are followed to prevent stray voltage/current from passing through the meter. Failure to adequately protect the meter could result in damage to the transmitter and lead to meter failure.
Completely remove all electrical connections from both sensor and
transmitter prior to welding on the pipe. For maximum protection of the sensor, consider removing it from the pipeline.
2 Rosemount™ 8782 Slurry Magnetic Flow Meter Transmitter
November 2019 Quick Start Guide

2 Introduction

This document provides basic installation guidelines for the Rosemount 8782 Magnetic Slurry wall-mount transmitter.
For sensor installation refer to the Rosemount™ MS Magnetic Slurry Flow
Meter Sensor Quick Installation Guide
For additional installation information, configuration, maintenance, and
troubleshooting, refer to the Rosemount™ 8782 Magnetic Slurry Flow
Meter with HART Protocol Reference Manual
All user documentation can be found at www.emerson.com. For more contact information see Emerson Flow customer service.

2.1 Return policy

Emerson procedures must be followed when returning equipment. These procedures ensure legal compliance with government transportation agencies and help provide a safe working environment for Emerson employees. Failure to follow Emerson procedures will result in your equipment being refused delivery.
Quick Start Guide 3
Quick Start Guide November 2019

2.2 Emerson Flow customer service

Email:
Worldwide: flow.support@emerson.com
Asia-Pacific: APflow.support@emerson.com
Telephone:
North and South America Europe and Middle East Asia Pacific
United States 800 522 6277 U.K. 0870 240
Canada +1 303 527
5200
Mexico +41 (0) 41
7686 111
Argentina +54 11 4837
7000
Brazil +55 15 3413
8000
Venezuela +58 26 1731
3446
The Netherlands
France 0800 917 901 India 800 440 1468
Germany 0800 182
Italy 8008 77334 China +86 21 2892
Central & Eastern
Russia/CIS +7 495 995
Egypt 0800 000
Oman 800 70101 Thailand 001 800 441
Qatar 431 0044 Malaysia 800 814 008
Kuwait 663 299 01
South Africa 800 991 390
Saudi Arabia 800 844 9564
UAE 800 0444
1978
+31 (0) 704 136 666
5347
+41 (0) 41 7686 111
9559
0015
0684
Australia 800 158 727
New Zealand 099 128 804
Pakistan 888 550 2682
9000
Japan +81 3 5769
6803
South Korea +82 2 3438
4600
Singapore +65 6 777
8211
6426
4 Rosemount™ 8782 Slurry Magnetic Flow Meter Transmitter
November 2019 Quick Start Guide

3 Pre-installation

Before installing the transmitter, there are several pre-installation steps that should be completed to make the installation process easier:
Identify options and configurations that apply to your application
Set the hardware switches if necessary
Consider mechanical, electrical, and environmental requirements
Note
Refer to the product reference manual for more detailed requirements.
Identify options and configurations
The typical transmitter installation includes a device power connection, a 4-20mA output connection, and sensor coil and electrode connections. Other applications may require one or more of the following configurations or options:
Pulse output
Discrete input/discrete output
HART multidrop configuration
The transmitter may have up to four user-selectable hardware switches. These switches set the alarm mode, internal/external analog power, internal/external pulse power, and transmitter security. The standard configuration for these switches when shipped from the factory is as follows:
Table 3-1: Hardware switch default settings
Setting Factory configuration
Alarm mode High
Internal/external analog power Internal
Internal/external pulse power External
Transmitter security Off
The analog power switch and pulse power switches are not available when ordered with intrinsically safe output, ordering code B.
In most cases, it is not necessary to change the setting of the hardware switches. If the switch settings need to be changed, refer to the product reference manual.
Be sure to identify any additional options and configurations that apply to the installation. Keep a list of these options for consideration during the installation and configuration procedures.
Quick Start Guide 5
Quick Start Guide November 2019
Mechanical considerations
The mounting site for the transmitter should provide enough room for secure mounting, easy access to conduit entries, full opening of the transmitter covers, and easy readability of the Local Operator Interface (LOI) screen (if equipped).
6 Rosemount™ 8782 Slurry Magnetic Flow Meter Transmitter
November 2019 Quick Start Guide
Figure 3-1: Rosemount 8782 Dimensional Drawing
9.0
(229)
(71)
2.8 (79)
3.1
C
12.0
(306)
11.2
(283)
D
17.7
(449)
(89)
3.5
11.4
(49)
1.9
1.7
1.9
(43)
(49)
(289)
A
B
3.9
(99)
7.8
(198)
(40)
1.6
A. Conduit entry, ½–14 NPT (4 places) B. Ground lug C. LOI keypad cover
D. Lower cover opens for electrical connections
Note
Dimensions are in inches (Millimeters)
Electrical considerations
Before making any electrical connections to the transmitter, consider national, local, and plant electrical installation requirements. Be sure to have
Quick Start Guide 7
Quick Start Guide November 2019
the proper power supply, conduit, and other accessories necessary to comply with these standards.
The transmitter requires external power. Ensure access to a suitable power source.
Table 3-2: Electrical Data
Electrical data
Power input AC power:
90–250 VAC ( ), 1.5A, 120 VA
Standard DC power: 12–42 VDC ( ), 8.6 A, 120 W
Pulsed circuit Internally powered (Active): Outputs up
4-20mA output circuit Internally Powered (Active): Outputs up
Um 250 V
Coil excitation output 2.0 A, 85 V max, 80 W max
to 12 VDC, 12.1 mA, 73 mW Externally powered (Passive): Input up to
28 VDC, 100 mA, 1 W
to 25 mA, 24 VDC, 600 mW Externally Powered (Passive): Input up to
25 mA, 30 VDC, 750 mW
Environmental considerations
Remote mounted transmitters may be installed in the control room to protect the electronics from the harsh environment and to provide easy access for configuration or service.
Table 3-3: Transmitter housing environmental ratings
Type Rating
Ingress protection IP66, IP69
NEMA 4X
Pollution Degree 2
Maximum altitude rating 13,123 ft (4000 m) at rated input
power voltage (90–250 VAC)
16,404 ft (5000 m) at maximum
input power voltage of 150 VAC
Note
For complete environmental and other specifications, refer to the product reference manual.
8 Rosemount™ 8782 Slurry Magnetic Flow Meter Transmitter
November 2019 Quick Start Guide

4 Mounting

Wall mount transmitters are shipped with mounting hardware for use on a 2 inch (50 mm) pipe or flat surface.
Figure 4-1: Mounting bracket
A
B
B
A
B
B
A. U-bolt B. Fasteners
4.1
Quick Start Guide 9

Pipe mounting

1. Assemble the hardware and transmitter housing on the pole as shown in Figure 4-1.
2. Tighten the nuts to ensure a snug fit.
Quick Start Guide November 2019

4.2 Surface mounting

Attach the transmitter to the mounting location using customer supplied mounting screws. The installation of the transmitter shall be rated for four (4) times the weight of the transmitter or 44lbs (20kgs).
10 Rosemount™ 8782 Slurry Magnetic Flow Meter Transmitter
Loading...
+ 22 hidden pages