Rosemount 3308 Series Wireless Guided Wave Radar, 3308A Manuals & Guides

Page 1
Reference Manual
00809-0100-4308, Rev CE
Rosemount™ 3308 Series Wireless Guided Wave Radar, 3308A
March 2022
Page 2
Rosemount™ 3308 Series Wireless Guided Wave Radar Level Transmitter
NOTICE
Read this manual before working with the product. For personal and system safety, and for optimum product performance, ensure you thoroughly understand the contents before installing, using, or maintaining this product.
For technical assistance, contacts are listed below:
Customer Central
Technical support, quoting, and order-related questions.
United States - 1-800-999-9307 (7:00 am to 7:00 pm CST)
Asia Pacific- 65 777 8211
North American Response Center
Equipment service needs.
1-800-654-7768 (24 hours a day — includes Canada)
Outside of these areas, contact your local Emerson representative.
NOTICE
Power module considerations.
Each power module contains primary lithium/thionyl chloride batteries. Under normal conditions, the battery materials are
self-contained and are not reactive as long as the batteries and the pack integrity are maintained. Care should be taken to prevent thermal, electrical or mechanical damage. Contacts should be protected to prevent premature discharge.
Battery hazards remain when cells are discharged.
Power modules should be stored in a clean and dry area. For maximum battery life, storage temperature should not exceed 86
°F (30 °C).
The power module may be replaced in a hazardous area. The power module has surface resistivity greater than one gigaohm
and must be properly installed in the wireless device enclosure. Care must be taken during transportation to and from the point of installation to prevent electrostatic charge build-up.
Shipping considerations for wireless products.
The unit was shipped to you without the power module installed. Remove the power module prior to any re-shipping.
Each Black Power Module (model number 701PBKKF) contains two “C” size primary lithium batteries. Primary lithium
batteries (charged or discharged) are regulated in transportation by the U. S. Department of Transportation, and are also covered by IATA (International Air Transport Association), ICAO (International Civil Aviation Organization), and ARD (European Ground Transportation of Dangerous Goods). It is the responsibility of the shipper to ensure compliance with these or any other local requirements. Consult current regulations and requirements before shipping.
Each Blue Power Module (A0701PBU) contains two "D" size primary lithium batteries. Primary lithium batteries (charged or
discharged) are regulated in transportation by the U.S. Department of Transportation, and are also covered by IATA (International Air Transport Association), ICAO (International Civil Aviation Organization), and ARD (European Ground Transportation of Dangerous Goods). It is the responsibility of the shipper to ensure compliance with these or any other local requirements. Please consult current regulations and requirements before shipping.
2
Page 3
WARNING
Explosions could result in death or serious injury.
Verify that the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.
Installation of device in an explosive environment must be in accordance with appropriate local, national, and international
standards, codes, and practices.
Ensure device is installed in accordance with intrinsically safe or non-incendive field practices.
Electrical shock could cause death or serious injury.
Ground device on non-metallic tanks (e.g. fiberglass tanks) to prevent electrostatic charge build-up.
Single lead probes are sensitive for strong electromagnetic fields and therefore not suitable for non-metallic tanks.
Care must be taken during transportation of power module to prevent electrostatic charge build-up.
Probes covered with plastic and/or with plastic discs may generate an ignition-capable level of electrostatic charge under
certain extreme conditions. Therefore, when the probe is used in a potentially explosive atmosphere, appropriate measures must be taken to prevent electrostatic discharge.
Process leaks could result in death or serious injury.
Only qualified personnel should install the equipment.
Install transmitter prior to process start-up.
Install and tighten process connectors before applying pressure.
Handle the transmitter carefully.
Do not remove the transmitter while in operation.
If the process seal is damaged, gas could escape from the tank when removing the transmitter head from the probe.
Failure to follow these installation guidelines could result in death or serious injury.
Verify that the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications.
Ensure the transmitter is installed by qualified personnel and in accordance with applicable code of practice.
Use the equipment only as specified. Failure to do so may impair the protection provided by the equipment.
Electronic boards are electrostatically sensitive. Failure to observe proper handling precautions for static-sensitive components can result in damage to the electronic components. Do not remove the electronic boards from the transmitter.
To ensure long life for your radar transmitter, and to comply with hazardous location installation requirements, tighten covers on both sides of the electronics housing.
Any substitution of non-recognized parts may jeopardize safety. Repair (e.g. substitution of components) may also jeopardize safety and is not allowed under any circumstances.
WARNING
Physical access
Unauthorized personnel may potentially cause significant damage to and/or misconfiguration of end users’ equipment. This could be intentional or unintentional and needs to be protected against.
Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility.
3
Page 4
CAUTION
This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions:
This device must accept any interference received, including interference that may cause undesired operation.
This device must be installed to ensure a minimum antenna separation distance of 8 in. (20 cm) from all persons.
Use caution when handling the power module. The Power Module may be damaged if dropped from heights in excess of 20 ft. (6 m).
Changes or modifications to the equipment not expressly approved by Rosemount Inc. could void the user’s authority to operate the equipment.
CAUTION
The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings. For information on Rosemount nuclear-qualified products, contact your local Emerson Sales Representative.
4
Page 5
Reference Manual Contents
00809-0100-4308 March 2022

Contents

Chapter 1 Introduction.............................................................................................................. 9
1.1 Using this manual........................................................................................................................ 9
1.2 Product recycling/disposal...........................................................................................................9
Chapter 2 Transmitter overview...............................................................................................11
2.1 Theory of operation................................................................................................................... 11
2.2 Measuring range........................................................................................................................14
2.3 Emerson Wireless...................................................................................................................... 15
2.4 Application characteristics.........................................................................................................15
2.5 Application examples.................................................................................................................17
2.6 Components of the transmitter................................................................................................. 18
2.7 Probe selection guide................................................................................................................ 20
Chapter 3 Installation...............................................................................................................23
3.1 Safety messages........................................................................................................................ 23
3.2 Installation procedure................................................................................................................24
3.3 Review mounting considerations...............................................................................................24
3.4 Review mounting preparations..................................................................................................32
3.5 Centering disc for pipe installations........................................................................................... 39
3.6 Anchor the probe.......................................................................................................................44
3.7 Mount device on tank................................................................................................................ 47
3.8 Ground the device..................................................................................................................... 69
3.9 Install the power module........................................................................................................... 70
3.10 Position the antenna................................................................................................................71
3.11 Utilize the device display..........................................................................................................72
Chapter 4 Configuration...........................................................................................................75
4.1 Overview................................................................................................................................... 75
4.2 Safety messages........................................................................................................................ 75
4.3 Configuration procedure........................................................................................................... 77
4.4 System readiness.......................................................................................................................77
4.5 Get started with your preferred configuration tool.....................................................................78
4.6 Join device to wireless network.................................................................................................. 81
4.7 Configure device using guided setup......................................................................................... 91
4.8 Run verify level...........................................................................................................................94
Chapter 5 Operation................................................................................................................ 95
5.1 Safety messages........................................................................................................................ 95
5.2 Device display screen messages.................................................................................................96
5.3 View measurement data............................................................................................................99
Reference Manual 5
Page 6
Contents Reference Manual
March 2022 00809-0100-4308
5.4 Check device status................................................................................................................. 100
Chapter 6 Service and troubleshooting.................................................................................. 103
6.1 Safety messages...................................................................................................................... 103
6.2 Alert messages........................................................................................................................ 104
6.3 Troubleshooting guide............................................................................................................ 112
6.4 Service and troubleshooting tools............................................................................................116
6.5 Application challenges.............................................................................................................126
6.6 Replace power module............................................................................................................ 134
6.7 Replace the transmitter head...................................................................................................136
6.8 Replace the probe....................................................................................................................138
6.9 Service support........................................................................................................................139
Appendix A Specifications and reference data........................................................................... 141
A.1 Performance specifications......................................................................................................141
A.2 Functional specifications......................................................................................................... 149
A.3 Physical specifications............................................................................................................. 158
A.4 Spare parts and accessories..................................................................................................... 163
A.5 Dimensional drawings............................................................................................................. 179
Appendix B Product Certifications............................................................................................ 189
B.1 European directive information............................................................................................... 189
B.2 Ordinary location certification................................................................................................. 189
B.3 Telecommunication compliance..............................................................................................189
B.4 FCC and IC............................................................................................................................... 189
B.5 Installing equipment in North America.................................................................................... 190
B.6 USA..........................................................................................................................................190
B.7 Canada.................................................................................................................................... 191
B.8 Europe.....................................................................................................................................192
B.9 International............................................................................................................................192
B.10 Brazil......................................................................................................................................193
B.11 China.....................................................................................................................................193
B.12 Japan..................................................................................................................................... 193
B.13 Technical Regulations Customs Union (EAC)..........................................................................194
B.14 Additional certifications.........................................................................................................194
B.15 Approval drawings.................................................................................................................194
Appendix C High gain remote antenna option...........................................................................197
C.1 Safety messages......................................................................................................................197
C.2 Functional and physical specifications..................................................................................... 197
C.3 Review installation considerations...........................................................................................198
C.4 Transient/lightning considerations..........................................................................................199
C.5 Install the high gain remote antenna....................................................................................... 199
Appendix D Configuration parameters......................................................................................203
6 Rosemount 3308 Series
Page 7
Reference Manual Contents
00809-0100-4308 March 2022
D.1 Menu overview of the Device Descriptor (DD)......................................................................... 203
D.2 Configuration parameters.......................................................................................................204
Appendix E Alert message mapping..........................................................................................225
E.1 Alert messages and descriptions..............................................................................................225
Reference Manual 7
Page 8
Contents Reference Manual
March 2022 00809-0100-4308
8 Rosemount 3308 Series
Page 9
Reference Manual Introduction
00809-0100-4308 March 2022

1 Introduction

1.1 Using this manual

The sections in this manual provide information on installing, configuring, operating, and maintaining the Rosemount™ 3308 Series Transmitter.
The sections are organized as follows:
Transmitter overview provides an introduction to theory of operation and description of
the transmitter. Information on applications and a probe selection guide are also included.
Installation contains mechanical and electrical installation instructions. Configuration provides instructions on how to configure and make the transmitter join the
wireless network.
Operation contains operation techniques such as viewing measurement data and display
functionality.
Service and troubleshooting provides troubleshooting techniques for the most common
operating problems, as well as diagnostic and error messages, and service instructions.
Specifications and reference data supplies reference and specification data, as well as
ordering information.
Product Certifications contains hazardous locations certifications and approval drawings. High gain remote antenna option contains specification and installation information of the
high gain remote antenna option.
Configuration parameters provides a menu overview for the Device Descriptor in AMS
Wireless Configurator and the handheld communicator. Description of the configuration parameters is also included.
Alert message mapping outlines the most important alerts in the HART® command 48
Additional Status Field for Rosemount 3308 Series.

1.2 Product recycling/disposal

Recycling of equipment and packaging should be taken into consideration and disposed of in accordance with local and national legislation or regulations.
Reference Manual 9
Page 10
Introduction Reference Manual
March 2022 00809-0100-4308
10 Rosemount 3308 Series
Page 11
K
$
%
&
*+
)
,
('
-
Reference Manual Transmitter overview
00809-0100-4308 March 2022

2 Transmitter overview

2.1 Theory of operation

The Rosemount™ 3308 Series is the first true wireless level transmitter that is based on the Time Domain Reflectometry (TDR) principle. Low power nano-second-pulses are guided along a probe submerged in the process media. When a pulse reaches the surface of the material it is measuring, part of the energy is reflected back to the transmitter, and the time difference between the generated and reflected pulse is converted into a distance from which the total level or interface level is calculated (see Figure 2-1).
Figure 2-1: Guided Wave Radar Operating Principle
A. Reference peak
Reference Manual 11
B. Product surface peak C. Product level
D. Interface peak
E. Interface level
F. Upper reference point G. Probe length H. Tank height
I. Zero reference point J. Signal amplitude
K. Time
Page 12
$
%
&
'
(
)
*
,+-
Transmitter overview Reference Manual
March 2022 00809-0100-4308
The reflectivity of the product is a key parameter for measurement performance. A high dielectric constant of the media gives better reflection and a longer measuring range.
See Figure 2-2 for a schematic overview of the signal processing.
Figure 2-2: Flowchart of the Signal Processing
2.1.1
2.1.2
2.1.3
A. Microwave module B. A/D converter C. Peak search
D. Peak interpolation
E. Echo identifier
F. Distance filtering G. Variable calculation H. Aout handler
I. LCD handler J. HART
®

Reference peak

This peak is caused by the transition between transmitter and the tank vapor space or air. It is used by the transmitter as a starting reference point for distance to the level surface.

Product surface peak

This peak indicates the product level and is caused by a reflection from the product surface.

Interface peak

This peak indicates the interface level. The peak is caused by reflection from the interface between an upper product and a bottom product with a relatively high dielectric constant. This peak is identified when the measurement mode is set to Product Level and Interface Level or Interface Level with Submerged Probe.
12 Rosemount 3308 Series
Page 13
$
(
)
%&'
Reference Manual Transmitter overview
00809-0100-4308 March 2022

2.1.4 Probe end peak

It is caused by reflection from the probe end. If the probe is grounded, the peak will be positive. If the probe end is submerged in a high dielectric media, such as water, it will not be visible.

2.1.5 Upper Reference Point

The Upper Reference Point is located at the underside of the threaded adapter, transmitter flange, or Tri-Clamp®, as illustrated in Figure 2-3.
Figure 2-3: Upper Reference Point
A. NPT B. BSPP (G) C. Flange
D. Tri-Clamp
E. Upper Reference Point
F. Total Probe Length
2.1.6
2.1.7

Zero reference point

The Zero Reference Point is selected by the user and is usually located close to or at the bottom of the tank. The Zero Reference Point can be set to any position in the tank by adjusting the Tank Height.

Tank height

The Tank Height is the distance from the Upper Reference Point to the Zero Reference Point. The transmitter measures the distance to the product surface and subtracts this value from the Tank Height to determine the level.
Reference Manual 13
Page 14
$
%
&
%
'
Transmitter overview Reference Manual
March 2022 00809-0100-4308

2.1.8 Probe length

The probe length is the distance between the Upper Reference Point and the end of the probe. If a weight is used at the end of the probe it shall be included.

2.2 Measuring range

The measuring range depends on probe type, dielectric constant of the product, and installation environment, and is limited by the Blind Zones at the very top and bottom of the probe. In the Blind Zones, the accuracy exceeds ±1.18 in. (30 mm), and measurements may not be possible. Measurements close to the Blind Zones will have reduced accuracy.
Figure 2-4 illustrates how the measuring range is related to the Blind Zones and the areas
with reduced accuracy.
Figure 2-4: Blind Zones and Areas with Reduced Accuracy
A. Upper Blind Zone B. Reduced accuracy C. Recommended measuring range
14 Rosemount 3308 Series
D. Lower Blind Zone
Note
Measurements may not be possible in the Blind Zones, and measurements close to the Blind Zones will have reduced accuracy. Therefore, the alarm points should be configured outside these zones.
Related information
Accuracy over measuring range
Page 15
I
N
E
X
P
L
O
S
I
V
E
A T
M
O S
P
H
E
R E
K E
E
P
T I
G
H
T
W
H
E
N
C
I
R
C
U
I
T
Reference Manual Transmitter overview
00809-0100-4308 March 2022

2.3 Emerson Wireless

Emerson Wireless is a self-organizing network solution. Wireless field instruments send data to a Gateway, directly or routed through any of the wireless devices in the network, as illustrated in Figure 2-5. Multiple communication paths are managed and analyzed in parallel to assure optimal communication and sustained network reliability even if obstructions are introduced.
Figure 2-5: Emerson Wireless Network
Gateways interface with existing host systems using industry standard protocols, and native integration into DeltaV™ and Ovation™ is transparent and seamless.
Interference from other radios, Wi-Fi®, and EMC sources is avoided through Time Synchronized Channel Hopping and Direct Sequence Spread Spectrum (DSSS). Also, a layered security implementing industry standard Encryption, Authentication, Verification, Anti-Jamming, and Key Management ensures that data transmissions are secure and received only by the Gateway.
The Rosemount 3308A is a member of the Emerson Wireless portfolio, whose wireless network experience totals billions of operating hours, hundreds of thousands of field devices, and tens of thousands of networks around the world.

2.4 Application characteristics

2.4.1 Tank shape

The guided wave radar transmitter is insensitive to the tank shape. Since the radar signal travels along a probe, the shape of the tank bottom has no effect on the measurement performance. The transmitter handles flat or dish-bottom tanks equally well.
Reference Manual 15
Page 16
$
%
%
Transmitter overview Reference Manual
March 2022 00809-0100-4308

2.4.2 In-tank obstructions

The Rosemount 3308 Series Transmitter is relatively insensitive to objects in the tank since the radar signal is transmitted along a probe.
Avoid physical contact between probes and agitators as well as applications with strong fluid movement unless the probe is anchored. If the probe can move within 1 ft. (30 cm) away from any object, such as an agitator, during operation then probe tie-down is recommended.
In order to stabilize the probe for side forces, you have the option to either hang a weight at the probe end (flexible probes only) or fix/guide the probe to the tank bottom.

2.4.3 Interface level measurement

Rosemount 3308 Series Transmitter is well suited for measuring the interface of oil and water, or other liquids with significant dielectric differences.
Figure 2-6: Interface Level Measurement
A. Product level B. Interface level
All probes can be used for measuring interfaces. Single probes are the preferred choice in almost all applications but depending on the application and installation geometries a coaxial probe or a twin probe may be a better fit.
For measuring the interface level, the transmitter uses the residual wave of the first reflection. Part of the wave, which was not reflected at the upper product surface, continues until it is reflected at the lower product surface. The speed of this wave depends fully on the dielectric constant of the upper product.
The maximum allowable upper product thickness/measuring range is primarily determined by the dielectric constants of the two liquids. Target applications include interfaces between oil/oil-like and water/water-like liquids. For such applications the upper product dielectric constant is low (<3) and the lower product dielectric constant is high (>20).
16 Rosemount 3308 Series
Page 17
Reference Manual Transmitter overview
00809-0100-4308 March 2022
Related information
Interface measurements
Emulsion layers
Sometimes there is an emulsion layer (mix of the products) between the two products which, depending on its characteristics, will affect interface measurements. For assistance with emulsion applications, consult your local Emerson representative.

2.5 Application examples

The Rosemount 3308 Series Transmitter is suited for aggregate (total) level measurements on a wide range of liquids, semi-liquids, and liquid to liquid interfaces.
Moreover, the reliable and accurate guided wave radar technology offers a versatile solution that is virtually unaffected by process conditions such as temperature, pressure, vapor gas mixtures, density, turbulence, bubbling/boiling, varying dielectric media, pH, and viscosity.
Storage and buffer tanks
The Rosemount 3308 Series Transmitter is ideal for storage or buffer tanks for almost any liquid, such as oil, gas condensate, water, or chemicals.
Low pressure separators
The Rosemount 3308 Series Transmitter can measure both level and interface level, such as for separator applications.
Reference Manual 17
Page 18
Transmitter overview Reference Manual
March 2022 00809-0100-4308
Waste tanks and sump pits
The Rosemount 3308 Series Transmitter is a good choice for waste tanks and underground tanks, such as sump pits.
Open applications —ponds, basins, sumps
The Rosemount 3308 Series Transmitter can be installed in open air to measure liquids not contained in a tank.
Chamber applications
The Rosemount 3308 Series Transmitter is a good choice for both chamber and pipe installations.

2.6 Components of the transmitter

The Rosemount 3308 Series transmitter housing contains advanced electronics for signal processing. The transmitter housing is made of aluminum or stainless steel, depending on specified option code.
The radar electronics produces an electromagnetic pulse, which is guided by the probe. There are different probe types available for various applications: flexible single lead, rigid
single lead, segmented rigid single lead, flexible twin lead, and coaxial.
18 Rosemount 3308 Series
Page 19
$
&
%
(
)
+,-./
*
'
Reference Manual Transmitter overview
00809-0100-4308 March 2022
Figure 2-7: Transmitter Components
A. Radar electronics B. Flanged process connections C. Probe
D. Dual compartment housing
E. Threaded process connections
F. BSPP (G) G. NPT H. Flexible single lead with weight
I. Rigid single lead J. Flexible twin lead with weight
K. Coaxial
L. Segmented rigid single lead probe
Reference Manual 19
Page 20
Transmitter overview Reference Manual
March 2022 00809-0100-4308

2.7 Probe selection guide

Use the following guidelines to choose appropriate probe for your Rosemount 3308 Series transmitter:
Table 2-1: Probe Selection Guide
G=Good, NR=Not Recommended, AD=Application Dependent (consult factory)
Flexible single lead Rigid single lead,
segmented rigid single lead
Measurements
Level G G G G
Interface (liquid/ liquid)
Process medium characteristics
Changing density G G G G
Changing dielectric
Wide pH variations G G G G
Pressure changes G G G G
Temperature changes G G G G
Condensing vapors G G G G
Bubbling/boiling surfaces
Foam (mechanical avoidance)
Foam (top of foam measurement)
G G G G
(2)
G G G G
G G G G
NR NR NR AD
AD AD AD NR
Flexible twin lead Coaxial
(1)
Foam (foam and liquid measurement)
Clean liquids G G G G
Liquid with dielectric
(3)
<2.0
Coating liquids
Viscous liquids
Crystallizing liquids AD AD NR NR
Solids/Powders NR NR NR NR
Fibrous liquids G G NR NR
20 Rosemount 3308 Series
(4)
(4)
AD AD AD NR
AD AD AD AD
G G NR NR
G G AD NR
Page 21
Reference Manual Transmitter overview
00809-0100-4308 March 2022
Table 2-1: Probe Selection Guide (continued)
Flexible single lead Rigid single lead,
segmented rigid single lead
Tank environment considerations
Probe is close (<12
NR NR AD G in./30 cm) to disturbing objects
Tall and narrow
AD AD AD G mounting nozzles
(diameter <6 in./15 cm and height>diameter + 4 in./10 cm)
Probe might touch
NR NR NR G nozzle / disturbing object
Liquid or vapor spray
NR NR NR G might touch probe
High turbulence AD
Turbulent conditions
(5)
G AD
AD NR AD NR causing breaking forces
Non-metallic tanks or
AD
(6)
AD
(6)
open atmosphere applications
Flexible twin lead Coaxial
AD
(5)
(6)
G
G
(1) Not in fully submerged applications. (2) For overall level applications a changing dielectric has no effect on the measurement. For interface measurements a
changing dielectric of the top fluid will degrade the accuracy of the interface measurement.
(3) See Table A-2 for more information. (4) See Table A-1 for more information. (5) Ok If probe is anchored. (6) Not suitable in applications with disturbing EMC from nearby equipment.
Reference Manual 21
Page 22
Transmitter overview Reference Manual
March 2022 00809-0100-4308
22 Rosemount 3308 Series
Page 23
Reference Manual Installation
00809-0100-4308 March 2022

3 Installation

3.1 Safety messages

Instructions and procedures in this section may require special precautions to ensure the safety of the personnel performing the operations. Information that potentially raises safety issues is indicated by a warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.
WARNING
Failure to follow safe installation and servicing guidelines could result in death or serious injury.
Ensure the transmitter is installed by qualified personnel and in accordance with
applicable code of practice.
Use the equipment only as specified in this manual. Failure to do so may impair the
protection provided by the equipment.
Explosions could result in death or serious injury.
Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
Installation of device in an explosive environment must be in accordance with
appropriate local, national, and international standards, codes, and practices.
Ensure device is installed in accordance with intrinsically safe or non-incendive field
practices.
Electrical shock could cause death or serious injury.
Ground device on non-metallic tanks (e.g. fiberglass tanks) to prevent electrostatic
charge build-up.
Single lead probes are sensitive for strong electromagnetic fields and therefore not
suitable for non-metallic tanks.
Care must be taken during transportation of power module to prevent electrostatic
charge build-up.
Device must be installed to ensure a minimum antenna separation distance of 8 in. (20
cm) from all persons.
Probes covered with plastic and/or with plastic discs may generate an ignition-capable
level of electrostatic charge under certain extreme conditions. Therefore, when the probe is used in a potentially explosive atmosphere, appropriate measures must be taken to prevent electrostatic discharge.
Reference Manual 23
Page 24
Installation
March 2022 00809-0100-4308
Reference Manual
WARNING
Process leaks could result in death or serious injury.
Only qualified personnel should install the equipment.
Install transmitter prior to process start-up.
Install and tighten process connectors before applying pressure.
Handle the transmitter carefully.
Do not remove the transmitter while in operation.
If the process seal is damaged, gas could escape from the tank when removing the
transmitter head from the probe.

3.2 Installation procedure

Follow these steps for proper installation:
Procedure
1. Review installation considerations.
2. Review mounting preparations. a) Measure tank height.
b) Optional: Shorten the probe.
c) Optional: Mount a centering disc for pipe installations.
d) Optional: Anchor the probe.
3. Mount device on tank.
4. Ground the device.
5. Install the power module.
6. Position the antenna.
7. Utilize the display.

3.3 Review mounting considerations

Before installing the Rosemount 3308 Series Transmitter, consider recommendations for sufficient free space, mounting position, and special needs for non-metallic tanks.
3.3.1
24 Rosemount 3308 Series

Recommended mounting position for liquids

When finding an appropriate mounting position for the transmitter, the conditions of the tank must be carefully considered. The transmitter should be mounted so that the influence of disturbing objects is reduced to a minimum. For easy access to the transmitter, ensure that it is mounted with sufficient service space.
Page 25
&
%
$
Reference Manual
00809-0100-4308 March 2022
Figure 3-1: Mounting Position
Installation
A. Inlet pipe B. Agitator C. Heating coils
The following guidelines should be considered when mounting the transmitter:
Do not mount close to inlet pipes.
Do not mount close to agitators. If the probe can move to within 12 in. (30 cm) away
from an agitator, the probe should be anchored.
If the probe tends to sway due to turbulent conditions in the tank, the probe should be
anchored.
Avoid mounting close to heating coils.
Position the probe such that it is subject to a minimum of lateral force.
The probe should not come into contact with the nozzle or other objects in the tank.
Note
Violent fluid movements causing high sideway forces may break rigid probes.
3.3.2

Free space requirement

If the probe is mounted close to a wall, nozzle or other tank obstruction, noise might appear in the level signal. Therefore the following minimum clearance, according to Table
3-1, must be maintained.
Reference Manual 25
Page 26
/
Installation Reference Manual
March 2022 00809-0100-4308
Figure 3-2: Free Space Requirement
L. Clearance to tank wall
Table 3-1: Recommended Minimum Free Space for Optimal Performance
Probe type Condition Minimum clearance
(L)
Rigid single lead/Segmented rigid single lead
Flexible single Smooth metal tank wall 4 in. (100 mm)
(1)
Coaxial
Flexible twin N/A 4 in. (100 mm)
(1) Minimum clearance from tank bottom for the coaxial and rigid single probes is 0.2 in. (5 mm).
(1)
Smooth metal tank wall 4 in. (100 mm)
Disturbing objects such as pipes and beams
16 in. (400 mm)
Plastic, concrete or rugged metal tank wall
Disturbing objects such as pipes and beams
16 in. (400 mm)
Plastic, concrete or rugged metal tank wall
N/A 0 in. (0 mm)
26 Rosemount 3308 Series
Page 27
$
%
&
Reference Manual Installation
00809-0100-4308 March 2022

3.3.3 Flange connection on nozzles

Figure 3-3: Mounting in Nozzles
A. Maximum nozzle height B. Minimum nozzle diameter C. Confirm the nozzle does not extend into the tank.
The transmitter can be mounted in nozzles by using an appropriate flange. It is recommended that the nozzle size is within the dimensions given in Table 3-2.
Note
The probe must not be in contact with the nozzle (except for the coaxial probe).
Table 3-2: Nozzle Considerations for Optimal Performance
Description Flexible single
lead probe
Recommended nozzle diameter
Minimum nozzle diameter
Maximum nozzle height
(1) The Trim Near Zone (TNZ) function may be necessary or an Upper Null Zone (UNZ) setup may be
(2) Recommended maximum nozzle height. For coaxial probes there is no limitation on nozzle
(3) For nozzles taller than 4 in. (100 mm), the long stud version is recommended (option code LS) to
(1)
(2)
required to mask the nozzle.
height.
prevent the flexible portion from touching the edge of the nozzle.
4 in. (100 mm) or more
1.5 in. (38 mm) 1.5 in. (38 mm)
4 in. (100 mm) + nozzle diameter
Rigid single lead probe/ Segmented rigid single lead
4 in. (100 mm) or more
for probe type 4A 2 in. (50 mm) for
probe type 4B and 4S
4 in. (100 mm) +
(3)
nozzle diameter
Flexible twin lead probe
4 in. (100 mm) or more
2 in. (50 mm) > probe diameter
4 in. (100 mm) + nozzle diameter
Coaxial probe
> probe diameter
N/A
Reference Manual 27
Page 28
Installation Reference Manual
March 2022 00809-0100-4308

3.3.4 Installation in still pipe/chamber

General chamber considerations
Dimensioning the chamber/pipe correctly and selecting the appropriate probe is key to the success in these applications. When selecting a smaller chamber/pipe diameter, such as 2-in., a flexible probe is not suitable due to the chance of it coming into contact with the walls. Also, relatively large side inlets may interfere with the signal.
When gas lift and/or turbulence may occur (e.g. boiling hydrocarbons), a 3- or 4-in. chamber/pipe diameter is recommended for maximum measurement reliability. This is especially true in high pressure and high temperature installations.
Table 3-3: Recommended and Minimum Chamber/Still Pipe Diameters for Different Probes
Probe type Recommended diameter Minimum diameter
Rigid single/segmented rigid single
Flexible single 4 in. (100 mm) Consult your local Emerson
Flexible twin
Coaxial 3 or 4 in. (75 or 100 mm) 1.5 in. (37.5 mm)
(1) The center rod must be placed more than 0.6 in. (15 mm) away from the pipe wall.
(1)
3 or 4 in. (75 or 100 mm) 2 in. (50 mm)
representative
4 in. (100 mm) Consult your local Emerson
representative
Note
Metal pipes are preferred, especially in applications with low dielectric constant, to avoid disturbances from objects near the pipe.
For more information and installation requirements, refer to the Best Practices for Using Radar in Still Pipes and Chambers Technical Note.
Related information
Dimensional drawings
Rosemount chamber
A Rosemount chamber allows external mounting of process level instrumentation. It supports a variety of process connections, and optional drain and vent connections. The standard Rosemount chambers are designed according to ASME B31.3. Rosemount chambers compliant with the Pressure Equipment Directive (PED) are available. Customer specific engineered solutions for Rosemount chambers are available upon request. Use option code XC to order together with the Rosemount 3308A Series Transmitters.
28 Rosemount 3308 Series
Page 29
'
&
&
(
$$
%
Reference Manual Installation
00809-0100-4308 March 2022
Figure 3-4: Side-to-Side and Side-to-Bottom Chambers
A. Dimension A B. Dimension B C. Dimension CC
D. Side-to-side chamber
E. Side-to-bottom chamber
When mounting in a Rosemount chamber, see Table 3-4 for information on probe length determination.
Table 3-4: Probe Length Determination for Rosemount CMB Chambers
Chamber type Probe length
Side-to-side chamber A + CC + B - 80 mm
Side-to-bottom chamber A + CC - 80 mm
Use a centering disc the same diameter as the chamber if the probe length >3.3 ft. (1 m). See Table 3-8 for which disc to use.
Existing chamber
A Rosemount 3308 Series Transmitter is the perfect replacement in an existing displacer chamber. Proprietary flanges are offered, enabling use of existing chambers to make installation easy.
Reference Manual 29
Page 30
$
&
%
Installation
Reference Manual
March 2022 00809-0100-4308
Figure 3-5: Existing Displacer Chamber
A. Replace chamber flange B. Probe length C. Displacer length
Considerations when changing to Rosemount 3308 Series:
The Rosemount 3308 Series flange choice and probe length must be correctly matched
to the chamber. Both standard ASME and EN (DIN), as well as proprietary chamber flanges, are available. See Proprietary flanges to identify the proprietary flanges.
See Table 3-8 for guidelines on which disc size to use.
See Table 3-5 for guidelines on the required probe length.
Table 3-5: Required Probe Length in Chambers
Chamber manufacturer Probe length
Major torque-tube manufacture (249B, 249C, 249K, 249N, 259B)
Masoneilan™ (torque tube operated), proprietary flange
Other - torque tube
Magnetrol® (spring operated)
Others - spring operated
(1) If flushing ring is used, add the ring height to the probe length. (2) For other manufacturers, there are small variations. This is an approximate value; actual length
should be verified.
(3) Lengths vary depending on model, SG, and rating, and should be verified.
(2)
(3)
(2)
Displacer + 9 in. (229 mm)
Displacer + 8 in. (203 mm)
Displacer + 8 in. (203 mm)
Displacer + between 7.8 in. (195 mm) to 15 in. (383 mm)
Displacer + 19.7 in. (500 mm)
(1)
For additional information, see the Replacing Displacers with Guided Wave Radar
Technical Note.
Probe type in chamber considerations
When installing a Rosemount 3308A in a chamber, the single lead probe is recommended. The probe must not touch the chamber wall, should extend the full height of the chamber,
but not touch the bottom of the chamber.
30 Rosemount 3308 Series
Page 31
Reference Manual Installation
00809-0100-4308 March 2022
The probe length determines if a single rigid or single flexible probe should be used:
Less than 19.7 ft. (6.0 m): Rigid single probe is recommended. Use a centering disc for
probe > 3.3 ft. (1 m). When mounting space is limited, use a flexible single probe with a weight and centering disc.
More than 19.7 ft. (6.0 m): Use flexible single probe with a weight and centering disc.

3.3.5 Installation in non-metallic tanks and open-air applications

Avoid major sources of electrical disturbance in proximity of the installation (e.g. electrical motors, stirrers, servo mechanisms).
Figure 3-6: Avoid Electromagnetic Disturbances
For clean liquids, use a coaxial probe to reduce effect of potential electrical disturbances.
Figure 3-7: Coaxial Probe in an Open-Air Application
Reference Manual 31
Page 32
$
%
Installation Reference Manual
March 2022 00809-0100-4308
For optimal single lead probe performance in non-metallic tanks, the probe must be mounted with a metal flange, or screwed in to a metal sheet (d > 14 in./350 mm) if a threaded version is used.
Figure 3-8: Mounting in Non-Metallic Tanks
A. Metal flange B. Metal sheet (d > 14 in./350 mm)
3.3.6

Minimum distance between two single probes

When installing multiple Rosemount 3308A Level Transmitters with single probes in the same tank, ensure to place the devices at proper distance from each other to avoid the risk of interference caused by cross-talk. Table 3-6 provides recommended minimum distance between two probes. A coaxial probe or a probe installed in a still pipe will not cause any cross-talk.
Table 3-6: Minimum Distance between Single Probes
Product Minimum distance between probes
Oil (DC = 2.1) 5.2 ft. (1.6 m)
Water (DC = 80) 3.3 ft. (1.0 m)

3.4 Review mounting preparations

3.4.1 Measure tank height

The Tank Height is defined as the measured distance from the Upper Reference Point to the Zero Reference Point.
32 Rosemount 3308 Series
Page 33
$
&
%
Reference Manual Installation
00809-0100-4308 March 2022
Figure 3-9: Measure Tank Height
A. Upper Reference Point B. Tank Height C. Zero Reference Point
3.4.2

Shorten the probe

In order to leave some clearance distance between the probe end and the tank bottom, the probe might have to be shortened. The goal is to have the probe hang straight so that it does not touch the wall; 2 in. (5 cm) is a suggested value. The probe can be shortened in field. Use the following form to calculate the probe length:
Probe length = tank height - 2 in. (5 cm) After shortening the probe make sure to update the transmitter configuration to the new
probe length, see Probe length.
Reference Manual 33
Page 34
%
$
1 2
3
4
5
6
7
8
0
Installation Reference Manual
March 2022 00809-0100-4308
Figure 3-10: Calculate Probe Length
A. Probe Length B. 2 in. (5 cm) clearance
Shorten the flexible single/twin lead probe
Prerequisites
Note
The PTFE covered probes must not be cut in field.
Procedure
1. Mark where to cut the probe.
34 Rosemount 3308 Series
Page 35
Reference Manual Installation
00809-0100-4308 March 2022
2. Remove enough spacers to make place for the weight (only flexible twin lead probes).
3. Loosen the weight.
4. Slide the weight up.
Reference Manual 35
Page 36
Installation
March 2022 00809-0100-4308
5. Cut the probe at the mark.
6. Fasten the weight with the following torque:
Small weight (W1): 5 Nm
Short weight (W2): 5 Nm
Reference Manual
Heavy weight (W3): 5 Nm
Weight, flexible twin: 6 Nm
Postrequisites
After shortening the probe be sure to update the transmitter configuration to the new probe length.
Related information
Probe length
Shorten the rigid single lead probe
Prerequisites
The minimum probe length is 15.7 in. (400 mm).
Note
The PTFE covered probes must not be cut in field.
36 Rosemount 3308 Series
Page 37
1 2 3
4
5
6
7
8
0
Reference Manual Installation
00809-0100-4308 March 2022
Note
Ensure the lead is fixed while cutting.
Procedure
1. Mark where to cut the probe.
2. Cut the probe at the mark.
Postrequisites
After shortening the probe be sure to update the transmitter configuration to the new probe length.
Related information
Probe length
Reference Manual 37
Page 38
/
/
$
&
'
%
Installation Reference Manual
March 2022 00809-0100-4308
Shorten the coaxial probe
Prerequisites
Figure 3-11: Maximum Shortening of Coaxial Probe
A. Ordered probe length (L) > 49 in. (1250 mm) B. Ordered probe length (L) ≤ 49 in. (1250 mm) C. Maximum shortening length: 23.6 in. (600 mm)
D. Minimum probe length: 15.7 in. (400 mm)
Procedure
1. Mark where to cut the probe.
Pipes longer than 49 in. (1250 mm) can be shortened by as much as 23.6 in.
(600 mm).
Pipes shorter than 49 in. (1250 mm) can be cut as long as the remaining length
is not less than 15.7 in. (400 mm).
38 Rosemount 3308 Series
Page 39
Reference Manual
00809-0100-4308 March 2022
2. Insert the centering piece. The centering piece is delivered from factory and should be used to prevent the
spacers centering the rod from coming loose.
3. Cut the tube to the desired length.
4. Move the centering piece.
Installation
5. Cut the rod inside the tube. Ensure the rod is fixed with the centering piece while cutting.
Postrequisites
After shortening the probe be sure to update the transmitter configuration to the new probe length.
Related information
Probe length

3.5 Centering disc for pipe installations

To prevent the probe from contacting the chamber or pipe wall, centering discs are available for flexible single, rigid single, and flexible twin lead probes. The disc is attached to the end of the probe. Discs are made of stainless steel, Alloy C-276, Duplex 2205, or PTFE.
For the segmented rigid single lead probe, up to five PTFE centering discs can be mounted along the probe, but keep a minimum distance of two segments between the discs. Additionally, a disc in SST or PTFE (part number 03300-1655-xxxx) can be attached to the end of the probe.
Reference Manual 39
Page 40
'
Installation Reference Manual
March 2022 00809-0100-4308
When mounting a centering disc, it is important that it fits correctly in the chamber/pipe. See Figure 3-12 for Dimension D. Table 3-8 shows which centering disc diameter to choose for a particular pipe.
Figure 3-12: Dimension D for Centering Discs
Table 3-7: Centering Disc Dimensions
Disc size Actual disc diameter (D)
2-in. 1.8 in. (45 mm)
3-in. 2.7 in. (68 mm)
4-in. 3.6 in. (92 mm)
6-in. 5.55 in. (141 mm)
8-in. 7.40 in. (188 mm)
Table 3-8: Centering Disc Size Recommendation for Different Pipe Schedules
Pipe size Pipe schedule
5s, 5 and 10s,10 40s, 40 and 80s, 80 120 160
2-in. 2-in. 2-in. N/A
3-in. 3-in. 3-in. N/A
4-in. 4-in. 4-in. 3-in. 3-in.
5-in. 4-in. 4-in. 4-in. 4-in.
6-in. 6-in. 6-in. 4-in. 4-in.
7-in. N/A
(1)
6-in. N/A
8-in. 8-in. 8-in. 6-in. 6-in.
(1) Schedule is not available for pipe size. (2) No centering disc is available.
(1)
(1)
(1)
N/A
2-in.
N/A
(2)
(1)
40 Rosemount 3308 Series
Page 41
13 mm
Reference Manual
00809-0100-4308 March 2022
Installation

3.5.1 Mount a centering disc on flexible single/twin lead probe

Procedure
1. Mount the centering disc at the end of the weight.
3.5.2
2. Secure the bolt by folding the tab washer.

Mount a centering disc on rigid single lead probe (8 mm)

Note
Centering discs shall not be used with PTFE covered probes.
Reference Manual 41
Page 42
$
Installation Reference Manual
March 2022 00809-0100-4308
Procedure
1. Drill one hole using the drilling fixture (included in your shipment).
2. Mount the bushing, centering disc, and washer at the probe end.
Note
Do not mount the washer (A) if the centering disc material is PTFE, Alloy C-276, Duplex 2205, or Alloy 400.
3. Insert the split pin through the bushing and the probe.
4. Secure the split pin.
42 Rosemount 3308 Series
Page 43
0.16 in. (4 mm)
0.08 in. (2 mm)
Reference Manual Installation
00809-0100-4308 March 2022

3.5.3 Mount a centering disc on rigid single lead probe (13 mm)

Procedure
1. Drill two holes using the drilling fixture (included in your shipment).
2. Mount the bushings and centering disc at the probe end.
3. Adjust distance by shifting hole for split pin in lower bushing.
Reference Manual 43
Page 44
Installation
Reference Manual
March 2022 00809-0100-4308
4. Insert the split pins through the bushings and the probe.
5. Secure the split pins.

3.6 Anchor the probe

In turbulent tanks it may be necessary to fix the probe. Depending on the probe type, different methods can be used to guide the probe to the tank bottom. This may be needed in order to prevent the probe from hitting the tank wall or other objects in the tank, as well as preventing a probe from breaking.
Flexible single/twin lead probe
The flexible single lead probe itself can be used for anchoring. Pull the probe rope through a suitable anchoring point (e.g. a welded eye), and fasten it with a chuck.
Table 3-9: Required Torque and Hex Key Dimensions
Probe Required torque Hex key dimension
Flexible twin lead 4.4 ft-lb (6 Nm) 4 mm
Flexible single lead 4 mm wire, stainless
steel
4 mm wire, Alloy C-276 1.8 ft-lb (2.5 Nm) 3 mm
4 mm wire, Alloy 400 1.8 ft-lb (2.5 Nm) 3 mm
4 mm wire, Duplex 2205
The length of the loop will add to the Blind Zone. The location of the chuck will determine the beginning of the Blind Zone.
3.7 ft-lb (5 Nm) 4 mm
1.8 ft-lb (2.5 Nm) 3 mm
44 Rosemount 3308 Series
Page 45
$
%
Reference Manual Installation
00809-0100-4308 March 2022
The Probe Length should be configured as the distance from the Upper Reference Point to the top of the chuck.
Figure 3-13: Flexible Single Lead Probe with Chuck
A ring (customer supplied) can be attached to the weight in a threaded (M8x14) hole at the end of the weight. Attach the ring to a suitable anchoring point.
Figure 3-14: Flexible Twin/Single Lead Probe with Weight and Ring
A. Weight with internal threads M8x14 B. Ring
A magnet (customer supplied) can be fastened in a threaded (M8x14) hole at the end of the weight. The probe can then be guided by placing a suitable metal plate beneath the magnet.
Reference Manual 45
Page 46
$
$
Installation Reference Manual
March 2022 00809-0100-4308
Figure 3-15: Flexible Twin/Single Lead Probe with Weight and Magnet
A. Magnet
Rigid single lead probe
The rigid single lead probe can be guided by a tube welded on the tank bottom. Tubes are customer supplied. Ensure that the probe can move freely in order to handle thermal expansion. The measurement accuracy will be reduced close to the tube opening.
Figure 3-16: Rigid Single Lead Probe with Tube
A. Drain
Coaxial probe
The coaxial probe can be secured to the tank wall by fixtures fastened to the tank wall. Fixtures are customer supplied. Ensure the probe can move freely due to thermal expansion without getting stuck in the fixture.
46 Rosemount 3308 Series
Page 47
$
$
Reference Manual Installation
00809-0100-4308 March 2022
Figure 3-17: Coaxial Probe Secured to the Tank Wall
A. Ø 1.1 in. (28 mm)
The coaxial probe can be guided by a tube welded on the tank bottom. Tubes are customer supplied. Ensure that the probe can move freely in order to handle thermal expansion. The measurement accuracy will be reduced close to the tube opening.
Figure 3-18: Coaxial Probe with Tube
A. Drain

3.7 Mount device on tank

Mount the transmitter with flange on a nozzle on top of the tank. The transmitter can also be mounted on a threaded or Tri-Clamp® connection.
3.7.1

Threaded tank connection

Prerequisites
Note
PTFE covered probes must be handled carefully to prevent damage to the coating.
Reference Manual 47
Page 48
Installation Reference Manual
March 2022 00809-0100-4308
Procedure
1. For adapters with BSPP (G) threads, place a suitable gasket on top of the tank flange.
2. For adapters with NPT threads, use anti-seize paste or PTFE tape according to your site procedures.
3. Lower the transmitter and probe into the tank.
48 Rosemount 3308 Series
Page 49
60 mm
52 mm / 60 mm
60 mm
Torque 30 Lbft (40 Nm)
Reference Manual Installation
00809-0100-4308 March 2022
4. Loosen the nut that connects the transmitter head to the probe slightly.
5. Screw the adapter into the process connection.
6. Rotate the transmitter head so the device display faces the desired direction.
7. Tighten the nut.
Reference Manual 49
Page 50
$
Installation Reference Manual
March 2022 00809-0100-4308
Postrequisites
Continue with the grounding step.

3.7.2 Tank connection with flange

Prerequisites
Note
PTFE covered probes must be handled carefully to prevent damage to the coating.
Procedure
1. Place a suitable gasket on top of the tank flange.
Note
Gasket should not be used for PTFE covered probe with protective plate.
A. PTFE covered probe with protective plate
2. Lower the transmitter and probe with flange into the tank.
50 Rosemount 3308 Series
Page 51
60 mm
Reference Manual Installation
00809-0100-4308 March 2022
3. Tighten bolts and nuts with sufficient torque for the flange and gasket choice.
4. Loosen the nut that connects the transmitter head to the probe slightly.
5. Rotate the transmitter head so the device display faces the desired direction.
Reference Manual 51
Page 52
60 mm
Torque 30 Lbft (40 Nm)
60 mm
Installation Reference Manual
March 2022 00809-0100-4308
6. Tighten the nut.
Postrequisites
Continue with the grounding step.
3.7.3

Tank connection with loose flange (plate design)

The transmitter is delivered with head, flange and probe assembled into one unit. If, for some reason, these parts have been disassembled, mount the transmitter as described below.
Prerequisites
Note
PTFE covered probes must be handled carefully to prevent damage to the coating.
Procedure
1. Mount the flange on the probe and tighten the flange nut.
2. Place a suitable gasket on top of the tank flange.
52 Rosemount 3308 Series
Page 53
60 mm
Torque 30 Lbft (40 Nm)
Reference Manual Installation
00809-0100-4308 March 2022
3. Lower the probe with flange into the tank.
4. Tighten bolts and nuts with sufficient torque for the flange and gasket choice.
5. Mount the transmitter head.
Postrequisites
Continue with the grounding step.
Reference Manual 53
Page 54
4X
A
B
4X
3X
Installation
March 2022 00809-0100-4308
Reference Manual

3.7.4 Bracket mounting

Procedure
1. Mount the bracket to the pipe/wall. On pipe:
3.7.5
A. Horizontal pipe B. Vertical pipe
On wall:
2. Mount the transmitter with probe to the bracket.
Tank connection with Tri-Clamp
®
54 Rosemount 3308 Series
Prerequisites
Note
PTFE covered probes must be handled carefully to prevent damage to the coating.
Page 55
60 mm
Reference Manual Installation
00809-0100-4308 March 2022
Procedure
1. Place a suitable gasket on top of the tank flange.
2. Lower the transmitter and probe into the tank.
3. Tighten the clamp to the recommended torque (see the manufacturer’s instruction manual).
4. Loosen the nut that connects the transmitter head to the probe slightly.
Reference Manual 55
Page 56
60 mm
Torque 30 Lbft (40 Nm)
Installation Reference Manual
March 2022 00809-0100-4308
5. Rotate the transmitter head so the device display faces the desired direction.
6. Tighten the nut.
Postrequisites
Continue with the grounding step.
56 Rosemount 3308 Series
Page 57
31.5
(800)
15.2
(385)
A
E
E
F
B
C
D
G
H
D
D
J
I
I
D
Reference Manual
Installation
00809-0100-4308 March 2022

3.7.6 Segmented probe

Segmented probe parts
Figure 3-19: Segmented Probe Parts
A. Safety ring B. Screw C. Top segment
D. Split pin
E. PTFE washer (optional)
F. Centering disc in PTFE (optional) G. Middle segment H. Bottom segment (length varies depending on total probe length)
I. Bushing (for the centering disc at the probe end) J. Bottom centering disc in PTFE or stainless steel (optional)
Verifying probe length
Reference Manual 57
Segmented probe ordered with model code 4S
Before installation, verify the probe length (L) on the label. If the probe length needs to be adjusted, see Adjust the probe length.
Page 58
$
%
Installation Reference Manual
March 2022 00809-0100-4308
Figure 3-20: Label
A. Probe segments box B. Probe length
Segmented probe ordered as spare part kit
Before installation, the number of segments that add up to the desired probe length must be determined. Also, the bottom segment may need to be shortened. See Adjust the
probe length.
Assemble the segmented probe
Prerequisites
Note
If there is enough space beside the tank, the probe can be assembled before inserting it into the tank.
58 Rosemount 3308 Series
Page 59
7RS6HJPHQW
Reference Manual Installation
00809-0100-4308 March 2022
Procedure
1. Insert the stop screw to the top segment. Tighten approximately two turns.
2. Pre-assemble the safety ring.
Reference Manual 59
Page 60
%RWWRP6HJPHQW
%RWWRP6HJPHQW
Installation Reference Manual
March 2022 00809-0100-4308
3. Optional: If ordered, mount the centering disc on the bottom segment of the probe.
4. Insert the support tool.
60 Rosemount 3308 Series
Page 61
Reference Manual Installation
00809-0100-4308 March 2022
5. Optional: If ordered, mount the centering disc.
Maximum five pcs/probe
Minimum two segments between each centering disc
6. Mount a middle segment (hand tight).
Reference Manual 61
Page 62
Installation Reference Manual
March 2022 00809-0100-4308
7. Secure the split pin.
8. Insert the second support tool.
62 Rosemount 3308 Series
Page 63
Reference Manual Installation
00809-0100-4308 March 2022
9. Remove the first support tool and lower the probe into the tank.
10. Repeat Step 5-Step 9 until all segments are mounted. Be sure to finish with the top segment of the probe.
11. Seal and protect threads. Use anti-seize paste or PTFE tape according to your site procedures.
Only for NPT threaded tank connection.
Reference Manual 63
Page 64
$
&
'
(
%
Installation Reference Manual
March 2022 00809-0100-4308
12. Attach the probe to the device.
Note
For safety reasons, at least two people are needed when mounting the device. Hold the device above the tank. High loads can break the support tool.
A. Flange/Tri-Clamp B. Threaded C. Gasket
D. Sealant on threads (NPT)
E. Gasket (BSPP (G))
64 Rosemount 3308 Series
Page 65
Reference Manual Installation
00809-0100-4308 March 2022
13. Tighten the stop screw and slide the safety ring into the groove.
14. Remove the support tool.
Reference Manual 65
Page 66
$
%
&
Torque 30 Lbft (40 Nm)
60 mm
Installation Reference Manual
March 2022 00809-0100-4308
15. Mount the device on the tank.
A. Flange B. Tri-Clamp C. Threaded
16. Rotate the housing to the desired direction.
17. Tighten the nut.
18. Continue with the grounding step.
66 Rosemount 3308 Series
Page 67
/
Q
Q
<
<
<
<
Reference Manual Installation
00809-0100-4308 March 2022
Adjust the probe length
Procedure
1. Determine L, the desired probe length.
L, desired probe length:
2. Determine n, the number of middle segments needed for the desired probe length. See Table 3-10.
n, number of middle segments:
3. Calculate Y, the length of the bottom segment. See Table 3-10.
Y, length of bottom segment:
4. Continue as follows:
Length of bottom segment (Y)
Y < 0.4 in. (10 mm)
Y ≥ 0.4 in. (10 mm)
Y = 31.5 in. (800 mm)
Action
Continue with step 7. Do not use the
bottom segment.
Continue with step 5 and cut the bottom
segment.
a. Add one extra middle segment to the
calculated n.
b. Continue with step 7.
Reference Manual 67
Page 68
1 2
3
4
5
6
7
8
0
1 2
3
0
<
<
Installation Reference Manual
March 2022 00809-0100-4308
5. Mark where to cut the bottom segment.
6. Cut the bottom segment at the mark.
Note
Ensure the bottom segment is fixed while cutting.
68 Rosemount 3308 Series
Page 69
Reference Manual
Installation
00809-0100-4308 March 2022
7. Optional: If a bottom centering disc is ordered, then drill two holes on the bottom segment using the drilling fixture.
Table 3-10: Determination of Probe Segments for Standard Seal
Desired probe length (L) Number of
in. mm in. mm
15.8 ≤ L ≤ 47.2 400 ≤ L ≤ 1200 0 pc Y = L -15.8 Y = L - 400
47.2 < L ≤ 78.7 1200 < L ≤ 2000 1 pc Y = L - 47.2 Y = L - 1200
78.7 < L ≤ 110.2 2000 < L ≤ 2800 2 pcs Y = L - 78.7 Y = L - 2000
110.2 < L ≤ 141.7 2800 < L ≤ 3600 3 pcs Y = L - 110.2 Y = L - 2800
141.7 < L ≤ 173.2 3600 < L ≤ 4400 4 pcs Y = L - 141.7 Y = L - 3600
173.2 < L ≤ 204.7 4400 < L ≤ 5200 5 pcs Y = L - 173.2 Y = L - 4400
204.7 < L ≤ 236.2 5200 < L ≤ 6000 6 pcs Y = L - 204.7 Y = L - 5200
236.2 < L ≤ 267.7 6000 < L ≤ 6800 7 pcs Y = L - 236.2 Y = L - 6000
267.7 < L ≤ 299.2 6800 < L ≤ 7600 8 pcs Y = L - 267.7 Y = L - 6800
299.2 < L ≤ 330.7 7600 < L ≤ 8400 9 pcs Y = L - 299.2 Y = L - 7600
330.7 < L ≤ 362.2 8400 < L ≤ 9200 10 pcs Y = L - 330.7 Y = L - 8400
362.2 < L ≤ 393.7 9200 < L ≤ 10000 11 pcs Y = L - 362.2 Y = L - 9200

3.8 Ground the device

middle segments (n)
Length of bottom segment (Y)
The Rosemount 3308 Series Wireless Guided Wave Radar transmitter operates with the housing grounded or floating. Floating systems can cause extra noise that may affect many types of readout devices. If the signal appears noisy or erratic, grounding at a single point may solve the problem.
Grounding of the electronics enclosure should be done in accordance with local and national installation codes. Grounding is accomplished by using the external case grounding terminal.
Non-metallic tanks
Ground device on non-metallic tanks (e.g. fiberglass tanks) to prevent electrostatic charge build-up.
Reference Manual 69
Page 70
$
Installation Reference Manual
March 2022 00809-0100-4308
There is one grounding screw connection provided, located on the housing (see Figure
3-21). The ground screw is identified by a ground symbol:
Figure 3-21: Ground Screw
A. Ground screw
Note
Always use facility recommended wiring practices.
Note
Flexible twin lead probe or coaxial probe are the recommended choice for non-metallic tanks. Single lead probes are not suited for non-metallic tanks or open atmosphere applications, due to high susceptibility to strong electromagnetic fields.

3.9 Install the power module

Prerequisites
Only use an Emerson approved power module designed for use with the Rosemount 3308A. The power modules are only compatible with their respective covers.
CAUTION
Use caution when handling the power module, it may be damaged if dropped from heights in excess of 20 ft. (6 m).
70 Rosemount 3308 Series
Page 71
$
Reference Manual Installation
00809-0100-4308 March 2022
Procedure
1. Install the power module into the transmitter.
2. Close the housing cover and tighten to site or safety specifications. Always ensure a proper seal by tightening the electronics housing covers so that metal touches metal, but do not overtighten.
A. Keep cover tight
Related information
Emerson Wireless Black SmartPower Solutions Product Data Sheet Emerson Wireless Blue SmartPower Solutions Product Data Sheet

3.10 Position the antenna

The antenna should be positioned vertically, either straight up or straight down, and it should be approximately 3 ft. (1 m) from any large structure, building, or conductive surface to allow for clear communication to other devices.
Reference Manual 71
Page 72
$%&'
Installation
March 2022 00809-0100-4308
Figure 3-22: Antenna Positioned Vertically
Reference Manual

3.11 Utilize the device display

If a device display is ordered, it will be shipped attached to the transmitter. The display is ordered in the transmitter model number, option code M5.
3.11.1

Rotate the device display

The device display can be rotated in 90-degree increments.
Procedure
1. Squeeze the two black tabs on opposite sides of the display. Refer to Figure 3-23.
2. Gently pull out the display.
3. Rotate the display to the desired orientation, and snap the display into place.
Figure 3-23: Device Display
A. Display pins B. Black tabs C. Display
D. Cover
Note
If the device display four-pin connector is inadvertently removed from the interface board, carefully reinsert the connector before snapping the device display back into place.
72 Rosemount 3308 Series
Page 73
Reference Manual Installation
00809-0100-4308 March 2022

3.11.2 Retrofitting

If an existing transmitter with no display (flat electronics cover) is to be retrofitted with a new display, order spare part kit number 00753-9004-0001(aluminum display kit) or 00753-9004-0004 (stainless steel display kit). These kits contain an extended cover with a display viewing window, a display board, and a display pin connector. Replace the flat cover with the extended display and tighten.
Reference Manual 73
Page 74
Installation Reference Manual
March 2022 00809-0100-4308
74 Rosemount 3308 Series
Page 75
Reference Manual Configuration
00809-0100-4308 March 2022

4 Configuration

4.1 Overview

This chapter provides information about configuration, configuration tools, and configuration parameters.
For a proper configuration, follow the steps listed in Configuration procedure.
The configuration can be performed using one of the described configuration tools:
AMS Wireless Configurator or a handheld communicator. AMS Wireless Configurator and Handheld communicator describe what preparations must be done in order to use the configuration tool.
Configuration parameters provides extended information about the configuration
parameters. An overview of Device Descriptor (DD) menu is presented in Menu
overview of the Device Descriptor (DD). All configuration parameters are described in Configuration parameters.

4.2 Safety messages

Instructions and procedures in this section may require special precautions to ensure the safety of the personnel performing the operations. Information that potentially raises safety issues is indicated by a warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.
Reference Manual 75
Page 76
Configuration Reference Manual
March 2022 00809-0100-4308
WARNING
Explosions could result in death or serious injury.
Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
Installation of device in an explosive environment must be in accordance with
appropriate local, national, and international standards, codes, and practices.
Ensure device is installed in accordance with intrinsically safe or non-incendive field
practices.
Electrical shock could cause death or serious injury.
Ground device on non-metallic tanks (e.g. fiberglass tanks) to prevent electrostatic
charge build-up.
Single lead probes are sensitive for strong electromagnetic fields and therefore not
suitable for non-metallic tanks.
Care must be taken during transportation of power module to prevent electrostatic
charge build-up.
Process leaks could result in death or serious injury.
Only qualified personnel should install the equipment.
Handle the transmitter carefully.
If the process seal is damaged, gas could escape from the tank when removing the
transmitter head from the probe.
To ensure long life for your radar transmitter, and to comply with hazardous location installation requirements, tighten covers on both sides of the electronics housing.
CAUTION
Use caution when handling the power module. The Power Module may be damaged if dropped from heights in excess of 20 ft. (6 m).
This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions:
This device must accept any interference received, including interference that may
cause undesired operation.
This device must be installed to ensure a minimum antenna separation distance of 8 in.
(20 cm) from all persons.
76 Rosemount 3308 Series
Page 77
Reference Manual Configuration
00809-0100-4308 March 2022

4.3 Configuration procedure

Follow these steps for proper configuration:
Procedure
1. Get started with your preferred configuration tool.
2. Join device to wireless network. a) Insert power module.
b) Connect to device.
c) Configure update rate.
d) Obtain network ID and join key.
e) Enter network ID and join key.
f) Verify device joins Network.
3. Configure device. a) Connect to device.
b) Configure using basic setup.
c) Consider optional setup.
4. Verify level.

4.4 System readiness

4.4.1 Confirm correct device driver

Verify the latest Device Descriptor (DD) is loaded on your systems to ensure proper communication.
Procedure
1. Within Table 4-1, use the HART® Universal Revision and Device Revision numbers to
find the correct DD.
2. Download the latest DD at Emerson.com/DeviceInstallKits.
Reference Manual 77
Page 78
Configuration Reference Manual
March 2022 00809-0100-4308
Table 4-1: Identification and Compatibility According to NAMUR NE 53
Release date Device identification DD identification Review
instructions
NAMUR hardware revision
December-15 1.0.xx 1.0.xx 2 7 1 00809-0100-
January-18 1.1.xx 1.1.xx 3 7 2 High accuracy
(1) NAMUR revision is located on the transmitter label. Differences in level 3 changes, signified above by xx, represent
minor product changes as defined per NE53. Compatibility and functionality are preserved and product can be used interchangeably.
(2) HART software revision can be read using a HART capable configuration tool (select Overview Device Information
Revisions).
(1)
NAMUR software revision
(1)
HART software revision
(2)
HART universal revision
Device revision
Manual document number
4308
Review functionality
Change description
Extended length and added probe support
output and Rosemount VeriCase support

4.5 Get started with your preferred configuration tool

4.5.1 AMS Wireless Configurator

The AMS Wireless Configurator (version 12.0 or later) is the recommended software tool for the wireless network devices, and is supplied with the Emerson Wireless Gateway.
Configuration can be done by connecting to the wireless network devices either point-to­point using a HART modem as shown in Figure 4-1, or wirelessly through the Gateway as shown in Figure 4-2. Initial configuration to join a device to the wireless network must be done point-to-point.
78 Rosemount 3308 Series
Page 79
$
$
Reference Manual Configuration
00809-0100-4308 March 2022
Figure 4-1: Connect Point-to-Point using HART Modem
A. Communication terminals
Figure 4-2: Connect Wirelessly through the Wireless Gateway
A. Wireless Gateway
Download the latest Device Descriptor (DD)
The Device Descriptor (DD) is a configuration tool that is developed to assist the user through the configuration.
Procedure
Download the latest DD at Emerson.com/DeviceInstallKits.
Add the DD to AMS Wireless Configurator
Prerequisites
The Rosemount 3308A DD is typically installed together with AMS Wireless Configurator.
Procedure
1. Close AMS Wireless Configurator.
Reference Manual 79
Page 80
Configuration Reference Manual
March 2022 00809-0100-4308
2. Go to Start Programs AMS Device Manager and select Add Device Type.
3. Browse to the downloaded DD files and select Ok.
Need help?
In the Add Device Type application, select the Help button for more information on how to complete this operation.
Configure the HART® modem interface
Before connecting to the device using a HART modem, the HART modem interface must be configured in AMS Wireless Configurator.
Procedure
1. Close AMS Wireless Configurator.
2. Go to Start Programs AMS Device Manager and select Network Configuration.
3. Select Add.
4. In the drop down list, select HART modem and then select Install.
5. Follow the on-screen instructions.
4.5.2
Need help?
In the Network Configuration application, select the Help button for more information on how to complete this operation.
Configure the wireless network interface
Before connecting to the device wirelessly using a Wireless Gateway, the wireless network must be configured in AMS Wireless Configurator.
Procedure
1. Close AMS Wireless Configurator.
2. Go to Start Programs AMS Device Manager and select Network Configuration.
3. Select Add.
4. In the drop-down list select Wireless Network and then select Install.
5. Follow the on-screen instructions.
Need help?
In the Network Configuration application, select the Help button for more information on how to complete this operation.

Handheld communicator

This section describes how to prepare the handheld communicator to communicate with a Rosemount 3308A. The handheld communicator can be used to configure the device with a point-to-point connection. Connect the leads on the handheld communicator to the communication terminals of the device.
80 Rosemount 3308 Series
Page 81
$
1 2 3
4 5 6
7 809
Reference Manual Configuration
00809-0100-4308 March 2022
Figure 4-3: Connect Point-to-Point using a Handheld Communicator
A. Communication terminals
Get the latest Device Descriptor (DD)
If the DD is not installed in your handheld communicator, see the appropriate handheld communicator User’s Manual available at Emerson.com/FieldCommunicator for instructions on how to update the handheld communicator with the latest DD.

4.6 Join device to wireless network

4.6.1 Power up the wireless device

Prerequisites
Make sure that the Wireless Gateway is installed and functioning properly before any wireless field devices are powered.
Wireless devices should be powered up in order of proximity from the Gateway, beginning with the closest. This will result in a simpler and faster network installation.
Procedure
1. Install the power module.
2. Enable Active Advertising on the Gateway to ensure that new devices join the network faster.
Related information
Install the power module
Startup screen sequence
The following screens will be displayed in sequence when the power module is first connected to the Rosemount 3308 Series Transmitter.
Reference Manual 81
Page 82
Configuration Reference Manual
March 2022 00809-0100-4308
Table 4-2: Startup Screen Sequence
Sequence Description Screen
1. All segments ON Used to visually determine if there are any bad segments on the device display.
2. Device identification Identification string used to determine the device type.
3. Device information: Tag User entered tag, 8 characters long. This screen will not display if all characters are blank.
4. Software revision Used to determine device software revision.
5. Device information: Status This screen will only appear if there is a critical error which may prevent the device from operating correctly. Check additional status screens for more information about failure source, refer to Table 5-1.
6. Primary variable Measurement value of mapped primary variable.
82 Rosemount 3308 Series
Page 83
Reference Manual Configuration
00809-0100-4308 March 2022
Table 4-2: Startup Screen Sequence (continued)
Sequence Description Screen
7. Secondary variable Measurement value of mapped second variable.
8. Electronics temperature Temperature value of device electronics.
9. Supply voltage Voltage reading of the power module.
> 6 V Good
5.2 V – 6.0 V Low
< 5.2 V Very low
10. Percent of range Level value in percent of total measurement range.
11. Active alert present This screen will only appear if there is at least one active alert present. For detailed information of the failure source and recommended actions, go to the Active Alerts screen in AMS Wireless Configurator or the handheld communicator. Refer to Check device status.
Some active alerts will be displayed on the LCD display as part of the diagnostic button screen sequence, refer to Table 5-1.
Reference Manual 83
Page 84
$
&
%
1 2 3
4 5 6
7 809
Configuration Reference Manual
March 2022 00809-0100-4308

4.6.2 Connect to device

Procedure
1. Connect a handheld communicator or a HART® modem to the communication terminals as shown in Figure 4-4.
Figure 4-4: Connect to Device
4.6.3
A. Communication terminals B. Handheld communicator C. HART modem
2. Do one of the following:
AMS Wireless Configurator:
a. Start AMS Wireless Configurator.
b. Select View Device Connection View.
c. Double click the device under the HART modem.
Handheld communicator:
Turn on the handheld communicator and connect to the device.
Related information
AMS Wireless Configurator Handheld communicator

Configure update rate

The Update Rate is the frequency at which a new measurement is transmitted over the wireless network. The default update rate is one minute. This may be changed at
84 Rosemount 3308 Series
Page 85
Reference Manual Configuration
00809-0100-4308 March 2022
commissioning, or at any time via AMS Wireless Configurator or a handheld communicator. The Update Rate is user selectable from 4 seconds to 60 minutes.
Procedure
1. Select Configure Guided Setup Wireless Setup.
2. Select Configure Update Rate, and follow the instructions.
Note
Set the Update Rate so that there is enough safety margin in the system for high/low alerts. If the time between each update is too long, the high/low alerts may be triggered too late.
Postrequisites
Run Check Level Response to make sure that configured Update Rate is sufficient for the application.
Related information
Consider optional setup
4.6.4

Obtain network ID and join key

In order to communicate with the Wireless Gateway, and ultimately the host system, the Rosemount 3308A must be configured to communicate on the wireless network. This step is the wireless equivalent of connecting wires from a device to the host system.
Procedure
From the Wireless Gateway's integrated web interface, select System Settings Network Network Settings.
Figure 4-5: Gateway Network Settings
Reference Manual 85
Page 86
Configuration Reference Manual
March 2022 00809-0100-4308

4.6.5 Enter network ID and join key

The device must be configured with the same Network ID and Join Key as the Gateway in order to join the network.
Procedure
1. Select Configure Guided Setup Wireless Setup.
2. Select Join Device to Network and follow on-screen the instructions.
Postrequisites
If the device is not to be commissioned yet, remove the power module and fasten the housing cover. This is to conserve power module life and to ensure safe transportation. The power module should be inserted only when the device is ready to be commissioned.
4.6.6

Verify device joins network

Network connection can be verified in four ways, further described in this section:
At the device display
Using the AMS Wireless Configurator
In the Wireless Gateway's integrated web interface
Using the handheld communicator
If the Rosemount 3308A was configured with the Network ID and Join Key, and sufficient time has passed, the device should be connected to the network. It usually takes a few minutes for the device to join the network.
Related information
Troubleshooting guide
Verify by device display
Procedure
1. Unscrew the device display cover.
86 Rosemount 3308 Series
Page 87
Reference Manual Configuration
00809-0100-4308 March 2022
2. Press the DIAG button. The display will show: Tag, Device Serial Number, Software Revision, Network ID,
Network Connection Status, and Device Status screens.
When the network diagnostic status is displayed as “NETWK OK”, the device has successfully joined the network.
Network connection status screens
When joining the wireless network, the status displayed will be changed through the sequence until the device finally has joined the network. Table 4-3 presents the different network connection status screens.
Reference Manual 87
Page 88
Configuration Reference Manual
March 2022 00809-0100-4308
Table 4-3: Network Connection Status Screens
Screen Status Description
Network Unknown The device is still in the process of
being activated.
Network Restarted The device has just restarted.
Network Idle The device is starting to join the
process.
Disconnected from Network The device is in a disconnected state
and requires a “Force Join” command to join the network.
Searching for Network The device is searching for the
network.
Joining the Network The device is attempting to join the
network.
88 Rosemount 3308 Series
Page 89
Reference Manual Configuration
00809-0100-4308 March 2022
Table 4-3: Network Connection Status Screens (continued)
Screen Status Description
Connected but in a “quarantined” state
Connected with Limited Bandwidth The device is joined and
Connected The device has successfully joined
The device is connected to the network, but is in a “quarantined” state.
operational, but is running with limited bandwidth for sending periodic data.
the network.
Reference Manual 89
Page 90
Configuration Reference Manual
March 2022 00809-0100-4308
Verify with AMS Wireless Configurator
Procedure
1. Start the AMS Wireless Configurator.
2. Navigate to the Smart Wireless Gateway icon. When the device has joined the network, it will appear in the AMS Wireless
Configurator window.
Network connection status
Figure 4-6 presents the different network connection status images that are shown in the
AMS Wireless Configurator Overview screen.
Figure 4-6: Network Connection Status Images
Verify by Gateway
Procedure
1. From the Emerson Wireless Gateway home page, navigate to the Devices page. This page shows whether the device has joined the network and if it is
communicating properly.
2. Locate the device in question and verify all status indicators are good (green). It may take several minutes for the device to join the network and be seen on the
Gateway's integrated web interface.
90 Rosemount 3308 Series
Page 91
Reference Manual Configuration
00809-0100-4308 March 2022
Figure 4-7: Wireless Gateway Devices Page
Verify with handheld communicator
Prerequisites
Do not remove the power module. Removing the power module may cause the device to drop off the network.
Note
In order to communicate with a handheld communicator, the device must be powered by the power module.
Procedure
1. Connect the handheld communicator.
2. Select Service Tools Communications.
3. Select Join Status.

4.7 Configure device using guided setup

4.7.1 Connect to device

Procedure
1. Connect to the device using your preferred configuration tool, as shown in Figure
4-8 and Figure 4-9.
2. Do one of the following:
AMS Wireless Configurator:
a. Start AMS Wireless Configurator.
Reference Manual 91
Page 92
$
&
%
1 2 3
4 5 6
7 809
$
Configuration Reference Manual
March 2022 00809-0100-4308
b. Select View Device Connection View.
c. Double click the device under the HART modem.
Handheld communicator:
Turn on the handheld communicator and connect to the device.
Figure 4-8: Connect to Device
4.7.2
A. Communication terminals B. Handheld communicator C. HART modem
Figure 4-9: Connect to Device - Wirelessly
A. Wireless Gateway

Configure using basic setup

Procedure
1. Select Configure.
2. Select Guided Setup Initial Setup.
92 Rosemount 3308 Series
Page 93
Reference Manual Configuration
00809-0100-4308 March 2022
3. Select Basic Setup, and follow the instructions.
Figure 4-10: Guided Setup Screen
Related information
Configuration parameters
4.7.3
Reference Manual 93

Consider optional setup

Consider Optional Setup such as Volume, Device Display, Echo Tuning, and Check Level Response, found in the Guided Setup. Run Check Level Response to review the maximum level change between updates with the current configuration.
Procedure
1. Select Configure.
2. Select Guided Setup Optional Setup.
3. Select the desired Optional Setup, and follow the instructions.
Additional configuration parameters are available in the Manual Setup menu.
Related information
Configuration parameters
Page 94
Configuration Reference Manual
March 2022 00809-0100-4308

4.8 Run verify level

The Verify Level tool matches the product level reported by the device to a reference measurement (for example hand-dipping with a measurement tape).
If any difference, the Calibration Offset parameter will be adjusted. A minor adjustment using Calibration Offset is normal. There may, for example be a deviation between the actual tank height and the configured value.
Prerequisites
Ensure that:
The product surface is calm.
The tank is not being filled or emptied.
The actual level is well above the probe end.
Procedure
1. Select Configure.
2. Select Guided Setup Initial Setup.
3. Select Verify Level to check your level measurement.
4. Follow the on-screen instructions.
Related information
Calibration offset
94 Rosemount 3308 Series
Page 95
Reference Manual Operation
00809-0100-4308 March 2022

5 Operation

5.1 Safety messages

Instructions and procedures in this section may require special precautions to ensure the safety of the personnel performing the operations. Information that potentially raises safety issues is indicated by a warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.
WARNING
Explosions could result in death or serious injury.
Verify that the operating atmosphere of the transmitter is consistent with the
appropriate hazardous locations certifications.
Installation of device in an explosive environment must be in accordance with
appropriate local, national, and international standards, codes, and practices.
Ensure device is installed in accordance with intrinsically safe or non-incendive field
practices.
Electrical shock could cause death or serious injury.
Ground device on non-metallic tanks (e.g. fiberglass tanks) to prevent electrostatic
charge build-up.
Single lead probes are sensitive for strong electromagnetic fields and therefore not
suitable for non-metallic tanks.
Care must be taken during transportation of power module to prevent electrostatic
charge build-up.
Process leaks could result in death or serious injury.
Only qualified personnel should install the equipment.
Handle the transmitter carefully.
If the process seal is damaged, gas could escape from the tank when removing the
transmitter head from the probe.
To ensure long life for your radar transmitter, and to comply with hazardous location installation requirements, tighten covers on both sides of the electronics housing.
Reference Manual 95
Page 96
Operation Reference Manual
March 2022 00809-0100-4308
CAUTION
Use caution when handling the power module. The Power Module may be damaged if dropped from heights in excess of 20 ft. (6 m).
This device complies with Part 15 of the FCC Rules. Operation is subject to the following conditions:
This device must accept any interference received, including interference that may
cause undesired operation.
This device must be installed to ensure a minimum antenna separation distance of 8 in.
(20 cm) from all persons.

5.2 Device display screen messages

The device display can be used to present different variables and a diagnostic screen sequence.
5.2.1

Variable screens

If the Display Mode is set to Periodic, the device display shows a periodic sequence of user­chosen variables during operation. A new screen appears according to configured wireless update rate. The device display will also show ALERT PRESNT if at least one alert is present.
The transmitter can display the following variables:
Figure 5-1: LCD Display Variables
Percent of Range
Total Volume Interface Distance Interface Level
Level Distance
96 Rosemount 3308 Series
Page 97
Reference Manual Operation
00809-0100-4308 March 2022
Upper Product Thickness Electronics Temperature Supply Voltage
5.2.2
Signal Quality
Related information
Device display

View diagnostic screens

The diagnostic button screen sequence on the device display can be used to obtain detailed diagnostic information.
Procedure
1. Unscrew the device display cover.
Reference Manual 97
Page 98
Operation Reference Manual
March 2022 00809-0100-4308
2. Press and hold the DIAG button until the first diagnostic button screen appears on the device display. Release the DIAG button.
The device display will now automatically show the diagnostic screens.
Diagnostic button screen sequence
Table 5-1: Diagnostic Button Screen Sequence
Screen Sequence Description
1. Device Information: Tag User entered tag which is 8 characters long. This screen will not
display if all characters are blank.
2. Device Serial Number Used to determine Device Serial Number.
3. Software Revision Used to determine Device Software Revision.
4. Network ID Used to determine the entered Network ID in the device.
98 Rosemount 3308 Series
Page 99
Reference Manual
00809-0100-4308 March 2022
Table 5-1: Diagnostic Button Screen Sequence (continued)
Screen Sequence Description
5. Network Connection Status The screen displayed is dependent on the progress of the
device in joining the wireless network.
Operation
6. Active Alert Screens (if
present)
7.Variable Screens At the end of the sequence, the device display shows all
8. Active Alert Present This screen will only appear if there is at least one Active Alert
See Device display alerts for a full list of Active Alerts that may appear on this position of the sequence.
selected variable screens.
present. For detailed information of the failure source and recommended actions, go to the Active Alerts screen in AMS Wireless Configurator or handheld communicator. Refer to
Check device status.

5.3 View measurement data

Measurement values can be viewed using AMS Wireless Configurator and handheld communicator.
5.3.1
Reference Manual 99

View current measurement values

Current measurement data of the Primary Variable (PV) and Secondary Variable (SV) are presented on the Overview screen. You can also view all current measurement values in AMS Wireless Configurator and on the handheld communicator.
Procedure
1. Select Service Tools Variables.
2. Select the desired group of measurement values to view.
To view gauges for the Primary Variable (PV), Secondary Variable (SV), Third
Variable (TV) and Fourth variable (QV), select Mapped Variables.
Page 100
Operation
March 2022 00809-0100-4308
To view process values such as Level, Distance, Percent of Range, select Process.
To view device values such as Electronics Temperature, Supply Voltage, select
Device.
To view Signal Quality, select Signal Quality.
Reference Manual

5.3.2 View trends

Measurement values can be logged and displayed in a graph or a table.
Procedure
1. Select Service Tools Trends.
2. Select to log measurement values either in a graph or a table.
To log Level and Interface Level values in a graph, select Level.
To log Distance values in a graph, select Distance.
To log Total Volume in a graph, select Volume.
5.3.3
To log Signal Quality in a graph, select Signal Quality.
To log the trend of 12 data points shown in a table, select Data History, and
then select View Data History.
Note
Values are logged in the trend graphs only as long as the Trends item is selected.
Related information
Configure data history

Interpret measurement status

A “Good” or “Bad” status next to a value is an indication of the reliability or integrity of the data being received, not an indication of whether or not the value is within the configured upper or lower ranges. A value that triggers an alert, such as a high or low temperature indication, will change the overall status of the device, but the measurement might still be indicated as “Good” if the reliability of the data is good.
Figure 5-2: Measurement Status Bars

5.4 Check device status

The overall device status is presented under the Overview screen. The device reports diagnostic alerts when there is a device malfunction.
Procedure
1. Go to the Overview screen to view the overall device status.
100 Rosemount 3308 Series
Loading...