Rosemount 3308 Hardware Revision
HART® Device Revision
Field Communicator Field Device Revision
Read this manual before working with the product. For personal and system safety, and for
optimum product performance, make sure you thoroughly understand the contents before
installing, using, or maintaining this product.
The United States has two toll-free assistance numbers and one international number.
Customer Central
1-800-999-9307 (7:00 a.m. to 7:00 p.m. CST)North AmericanResponse Center
1-800-654-7768 (24 hours a day)
Equipment service needs
International
1-952-906-8888
The products described in this document are NOT designed for nuclear-qualified
applications.
Using non-nuclear qualified products in applications that require nuclear-qualified hardware
or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact your local Emerson
Process Management Sales Representative.
1
1
Dev v1, DD v1
www.rosemount.com
The Rosemount 3308 and all other wireless devices should be installed only after the Smart
Wireless Gateway has been installed and is functioning properly. Wireless devices should
also be powered up in order of proximity from the Smart Wireless Gateway, beginning with
the closest. This will result in a simpler and faster network installation.
Page 4
PRELIMINARY
NOTICE
NOTICE
Failure to follow these installation guidelines could result in death or serious injury:
• Only qualified personnel should perform the installation
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with the
appropriate local, national, and international standards, codes, and practices. Please review
the Product Certifications section for any restrictions associated with a safe installation.
• Before connecting a Field Communicator in an explosive atmosphere, ensure the
instruments are installed in accordance with intrinsically safe or non-incendive field
wiring practices
Process leaks may cause harm or result in death:
• Do not remove the transmitter while in operation
• Install device prior to process start-up
• Install and tighten process connectors before applying pressure
Electrical shock can result in death or serious injury:
• Avoid contact with the leads and terminals. High voltage that may be present on
leads can cause electrical shock
This device complies with Part 15 of the FCC Rules. Operation is subject to the following
conditions: This device may not cause harmful interference. This device must accept any
interference received, including interference that may cause undesired operation. This
device must be installed to ensure a minimum antenna separation distance of 20 cm (8 in.)
from all persons.
Power Module Considerations
Each Power Module contains two "C" size primary lithium/thionyl chloride batteries. Each
battery contains approximately 2.5 grams of lithium, for a total of 5 grams in each pack.
Under normal conditions, the battery materials are self-contained and are not reactive as
long as the batteries and the pack integrity are maintained. Care should be taken to prevent
thermal, electrical or mechanical damage. Contacts should be protected to prevent
premature discharge.
Battery hazards remain when cells are discharged.
Power modules should be stored in a clean and dry area. For maximum battery life, storage
temperature should not exceed 30° C.
The Power Module may be replaced in a hazardous area. The Power Module has surface
resistivity greater than one gigaohm and must be properly installed in the wireless device
enclosure. Care must be taken during transportation to and from the point of installation to
prevent electrostatic charge build-up.
Shipping considerations for wireless products
The unit was shipped to you without the Power Module installed. Please remove the Power
Module prior to shipping the unit.
Each Power Module contains two "C" size primary lithium/thionyl chloride batteries. Primary
lithium batteries are regulated in transportation by the U.S. Department of Transportation,
and are also covered by IATA (International Air Transport Association), ICAO (International
Civil Aviation Organization), and ARD (European Ground Transportation of Dangerous
Goods). It is the responsibility of the shipper to ensure compliance with these or any other
local requirements. Please consult current regulations and requirements before shipping
SAFETY MESSAGESProcedures and instructions in this manual may require special preca utions to
ensure the safety of the personnel performing the operations. Information that
raises potential safety issues is indicated by a warning symbol ( ). Refer to
the safety messages listed at the beginning of each section before performing
an operation preceded by this symbol.
Failure to follow these installation guidelines could result in death or serious
injury.
• Make sure only qualified personnel perform the installation.
• Use the equipment only as specified in this manual. Failure to do so may
impair the protection provided by the equipment.
Explosions could result in death or serious injury.
• Verify that the operating environment of the transmitter is consistent with the
appropriate hazardous locations certifications.
®
• Before connecting a HART
make sure the instruments in the loop are installed in accordance with
intrinsically safe or non-incendive field wiring practices.
Electrical shock could cause death or serious injury.
• Use extreme caution when making contact with the leads and terminals.
-based communicator in an explosive atmosphere,
www.rosemount.com
Any substitution of non-recognized parts may jeopardize safety. Rep air, e.g. substitution
of components etc., may also jeopardize safety and is under no circumstances allowed.
Page 10
PRELIMINARY
Rosemount 3308
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
MANUAL OVERVIEWThis manual provides installation, configuration and maintenance information
for the Rosemount 3308 transmitter.
Section 2: Transmitter Overview
•Theory of operation
•Application examples
•System architecture
•Process and vessel characteristics
•Description of the transmitter
Section 3: Wireless Configuration
•Mounting considerations
•Mechanical installation
•Electrical installation
Section 4: Installation
•Mounting considerations
•Mechanical installation
•Electrical installation
Section 5: Start-Up/Commissioning
•Configuration instructions
•Configuration using the HART Communicator
•Configuration using the RCT software
Section 6: Operation and Maintenance
•Display functionality
•Error messages
•Alarm and write protection
Section 7: Service and Troubleshooting
•Advanced configuration
•Service
•Diagnostic messages
Appendix A: Reference Data
•Specifications
•Ordering Information
Appendix B: Product Certifications
•Examples of labels
•EU conformity
•European ATEX Directive information
•FM approvals
•CSA approvals
•Approval drawings
1-2
Page 11
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
SERVICE SUPPORTTo expedite the return process outside of the United States, contact the
nearest Emerson Process Management representative.
Within the United States, call the Emerson Process Management Instrument
and Valves Response Center using the 1-800-654-RSMT (7768) toll-free
number. This center, available 24 hours a day, will assist you with any needed
information or materials.
The center will ask for product model and serial numbers, and will provide a
Return Material Authorization (RMA) number. The center will also ask for the
process material to which the product was last exposed.
Individuals who handle products exposed to a hazardous substance can avoid injury if
they are informed of and understand the hazard. If the product being returned was
exposed to a hazardous substance as defined by Occupational Safety and Health
Administration (OSHA), a copy of the required Material Safety Data Sheet (MSDS) for
each hazardous substance identified must be included with the returned goods.
Emerson Process Management Instrument and Valves Response Center
representatives will explain the additional information and procedures
necessary to return goods exposed to hazardous substances.
PRODUCT
RECYCLING/DISPOSAL
Recycling of equipment and packaging should be taken into consideration
and disposed of in accordance with local and national legislation/regulations.
SAFETY MESSAGESInstructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or serious
injury:
• Only qualified personnel should perform the installation
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with
the appropriate local, national, and international standards, codes, and practices.
Please review the Product Certifications section for any restrictions associated with a
safe installation.
• Before connecting a Field Communicator in an explosive atmosphere, make
sure that the instruments are installed in accordance with intrinsically safe or
non-incendive field wiring practices
Process leaks may cause harm or result in death:
• Do not remove the transmitter while in operation
• Install the transmitter prior to process start-up
Electrical shock could cause death or serious injury:
• Avoid contact with the leads and terminals. High voltage that may be present
on leads can cause electrical shock
This device complies with Part 15 of the FCC Rules. Operation is subject to the
following conditions: This device may not cause harmful interference. This device must
accept any interference received, including interference that may cause undesired
operation. This device must be installed to ensure a minimum antenna separation
distance of 20 cm (8 in.) from all persons.
www.rosemount.com
Page 14
PRELIMINARY
Rosemount 3308
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
ROSEMOUNT 3308Features of the Rosemount 3308 Wireless Guided Wave Radar include:
•An installation-ready solution that provides a variety of mounting
options, transmitter configurations, and switches
•Flexibility to meet your most demanding applications
•Wireless output with >99% data reliability delivers rich HART® data,
protected by industry leading security
•Single or dual switch input with logic for limit contact and opposing
contact applications
•The integral LCD conveniently displays the primary switch input and
diagnostics of the transmitter
•Simple and easy installation practices currently being used for robust
installations
Smart Wireless delivers innovative wireless solutions for level measurement
and overall transmitter performance
•Self-organizing network delivers information rich data with >99% data
reliability and establishes a highly stable network
•Smart Wireless capabilities extend the full benefits of PlantWeb
previously inaccessible temperature measurement locations
•Emerson SmartPower™ Solutions provide an intrinsically safe Power
Module, allowing field replacements without remo vin g th e tra n sm itte r
from the process, keeping personnel safe, and reducing mainte nance
costs
•Emerson Process Management's layered approach to wireless network
security ensures that data transmissions are secure
®
to
2-2
Page 15
Reference Manual
Time
Reference Pulse
Level
Interface Level
Signal Amplitude
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
THEORY OF OPERATIONThe Rosemount 3308 Wireless Guided Wave Radar Level Transmitter is a
continuous level transmitter that is based on Time Domain Reflectometry
(TDR) principles. Low power nano-second-pulses are guided along a probe
immersed in the process media. When a pulse reaches the surface of the
material it is measuring, part of the energy is r eflected back to the transmitter,
and the time difference between the generated and reflected pulse is
converted into a distance from which the total level or interface level is
calculated (see below).
The reflectivity of the product is a key parameter for measurement
performance. A high dielectric constant of the media gives better reflection
and a longer measuring range. A calm surface gives better reflection than a
turbulent surface.
Figure 2-1. Measurement
Principle.
APPLICATION
EXAMPLES
The Rosemount 3308 transmitter is suited for aggregate (total) level
measurements on most liquids, semi-liquids, and liquid/liquid interfaces.
Guided microwave technology offers highest reliability and precision which
ensure measurements are virtually unaffected by temperature, pressure,
vapor gas mixtures, density, turbulence, bubbling/boiling, low level, varying
dielectric media, pH, and viscosity.
Guided wave radar technology in combination with advanced signal
processing make the Rosemount 3308 transmitter suitable fo r a wide range of
applications.
2-3
Page 16
Rosemount 3308
PRELIMINARY
Boiling conditions with vapor and turbulence
For these applications the Coaxial probe is particularly
suitable.
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
Bridle applications
The Rosemount 3308 transmitter is well suited for bridle
applications, such as distillation columns.
2-4
Page 17
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
Separator tanks
The Rosemount 3308 measures both level and inte rface
level.
Underground tanks
The Rosemount 3308 transmitter is a good choice for
underground tanks since it is installed on the tank top
with the radar pulse concentrated near the probe. It can
be equipped with probes that are unaf fecte d by high and
narrow openings or nearby objects.
Small ammonia, NGL and LPG tanks
Guided wave radar technology is a good choice for
reliable measurements in small ammonia, NGL and LPG
tanks.
The Rosemount 3308 transmitter is battery powered with wireless
communication which means the unit works completely independent.
By using the optional HART Tri-loop, it is possib le to convert the HAR T signal
to up to three additional 4-20 mA analog signals.
With the HART protocol it is possible to use multidrop configuration. In this
case communication is restricted to digital since current is fixed to the 4 mA
minimum value.
The transmitter can be connected to display Ros em o un t 75 1 Fi eld Signal
Indicator or it can be equipped with an integral display.
The transmitter can easily be configured by using the AMS suite software or
by using a Field Communicator. A PC with the Radar Configuration Tool
software can also be used for configuration.
For HART communication a minimum load resistance o f 250 within the loop
is required.
2-6
Page 19
Reference Manual
Level
Interface Level
Level = Interface Level
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
InterfaceRosemount 3308 is the ideal choice for measuring the interface of oil and
water, or other liqui ds with significant dielectric differences.
Figure 2-3. Interface
measurement with a
Rosemount 3308
All probes can be used for measuring interfaces. The coaxial probe is the
preferred choice for clean liquids and when the bridle is not fully immersed . In
applications with a fully immersed probe, the twin lead probes are
recommended for nozzle installations, and the rigid single lead probe is best
for bridle mounting.
For measuring the interface level, the transmitter uses the residual wave of
the first reflection. Part of the wave, which was not reflected at the upper
product surface, continues until it is reflected at the lower product surface.
The speed of this wave depends fully on the dielectric constant of the upper
product.
If interface is to be measured, the following criteria have to be fulfilled:
•The dielectric constant of the upper product must be kn own. The Radar
Configuration Tools software has a built-in dielectric constant calculator
to assist users in determining the dielectric constant of the upper
product.
•The dielectric constant of the upper product must have a lower
dielectric constant than the lower product in order to have a distinct
reflection.
•The difference between the dielectric constants for the two products
must be larger than 10.
•Maximum dielectric constant for the upper product is 10 for the coaxial
probe and 5 for twin lead probes.
•The upper product thickness must be larger than 8 inches (0.2 m) for
the flexible twin lead probe and 4 inches (0.1 m) for the rigid twin lead
and coaxial probes in order to distinguish the echoes of the two liquids.
The maximum allowable upper product thickness/measuring range is
primarily determined by the dielectric constants of the two liquids.
Target applications include interfaces between oil/oil-like and water/water-like
liquids. For such applications the upper product dielectric constant is low (<3)
and the lower product dielectric constant is high (>20), and the maximum
measuring range is only limited by the length of the coaxial and rigid twin lead
probes.
2-7
Page 20
Rosemount 3308
PRELIMINARY
Emulsion Layers
Sometimes there is an emulsion layer (mix of the products) between the two
products which, depending on its characteristics, will affect interface
measurements.
Please consult factory for guidelines on how to handle emulsion layers.
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
2-8
Page 21
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
V E SSEL
CHARACTERISTICS
Heating Coils, AgitatorsThe Rosemount 3308 transmitter is relatively insensitive to objects in the tank
since the radar signal is transmitted along a probe.
Avoid physical contact between probes and agitators as well as applications
with strong fluid movement unless the probe is anchored. If the probe can
move within 1 ft (30 cm) away from any object, such as an agitator, during
operation then probe tie-down is recommended.
In order to stabilize the probe for side forces, it is possible to hang a weight at
the probe end (flexible probes only) or fix/guide the probe to the tank bottom.
Tank ShapeThe guided wave radar transmitter is insensitive to the tank shape. Since the
radar signal travels along a probe, the shape of the tank bottom has virtually
no effect on the measurement performance. The transmitter handles flat or
dish-bottom tanks equally well.
2-9
Page 22
Rosemount 3308
Radar Electronics
Probe
Dual Compartment Housing
Threaded Process
Connections
Flanged Process
Connections
BSP (G)
NPT
Coaxial
F
le
x
ible
T
w
in
L
e
a
d
w
it
h
w
e
ig
h
t
Rigid
S
i
ngle
Lead
Flexib
l
e Sing
l
e Lead
w
ith weight
PRELIMINARY
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
COMPONENTS OF THE
TRANSMITTER
Figure 2-4. Transmitter
components.
The Rosemount 3308 transmitter has an aluminum transmitter hou sing which
contains advanced electronics for signal processing.
The radar electronics produces an electromagnetic pulse which is guided by
the probe.
There are different probe types available for various applications: Flexible
Twin Lead, Rigid Single Lead, Flexible Single Lead, and Coaxial.
2-10
Page 23
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
PROBE SELECTION
GUIDE
Use the following guidelines to choose appropriate probe for your
Rosemount 3308 transmitter:
Probe is close
(<12 in./30 cm) to tank wall
/ disturbing objects
High turbulenceGGADGAD
Turbulent conditions
causing breaking forces
Long and small mounting
nozzles
(diameter <6 in./15 cm,
height>diameter + 4 in./10
cm)
Probe might touch nozzle /
disturbing object
Liquid or vapor spray might
touch probe
Disturbing EMC
environment in tank
(1) Not in fully immersed applications.
(2) For overall level applications a changing dielectric has no effect on the measurement. For interface measurements a changing diele ct r ic of the top fluid
will degrade the accuracy of the interface measurement.
(3) OK when installed in pipe.
(2)
(1)
Process Medium Characteristics
GGGGG
ADNRNRNRNR
NRADADADAD
NRADADNRNR
Tank Environment Considerations
GADADNRNR
NRNRADNRAD
G ADNRNRNR
G NRNRNRNR
G NRNRNRNR
ADNRNRNRNR
GGNRNR
(3)
NR
2-11
Page 24
PRELIMINARY
4mA
20mA
Upper Transition Zone
Lower Transition Zone
Range 0 -100 %
Maximum Measuring
Range
Upper Reference Point
Rosemount 3308
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
Transition ZonesThe measuring range depends on probe type and properties of the product.
The Upper Transition Zone is the minimum measurement di stance between
the upper reference point and the product surface. The Upper Transition Zone
varies between 4 - 20 in. (0.1 and 0.5 m) depending on probe type and
product.
At the end of the probe the measuring range is reduced by the Lower Trans ition Zone. The Lower Transition Zone also varies depending on
probe type and product.
Figure 2-5 illustrates how the measuring range is related to the Transition
Zones:
Figure 2-5. Transition Zones
Table 2-2. Transition Zones for different probe types
Dielectric
Constant
Upper
Transition Zone
Lower
Transition Zone
2TO BE ADDED
80
2
80
NOTE
The measurement accuracy is reduced in the Transition Zones. It may even
be impossible to make any measurements at all in those regions. Therefore,
the alarm limit points should be configured outside the Transition Zones.
2-12
Coaxial ProbeFlexible Twin
Lead Probe
Rigid Single
Lead Probe
Flexible Single
Lead Probe
Page 25
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
SERVICE SUPPORTTo expedite the return process outside of North America, contact your
Emerson Process Management representative,
Within the United States, call the Emerson Process Management Response
Center toll-free number 1 800 654 7768. The center, which is available 24
hours a day, will assist you with any needed information or materials.
The center will ask for product model and serial numbers, and will provide a
Return Material Authorization (RMA) number. The center will also ask for the
process material to which the product was last exposed.
Individuals who handle products exposed to a hazardous substance can avoid injury if they
are informed of, and understand, the hazard. If the product being returned was exposed to a
hazardous substance as defined by OSHA, a copy of the required Material Safety Data
Sheet (MSDS) for each hazardous substance identified must be included with the returned
goods.
PRODUCT
RECYCLING/DISPOSAL
SHIPPING CONSIDERATIONS FOR WIRELESS PRODUCTS (LITHIUM
BATTERIES)
The unit was shipped with the Power Module not installed. Please remove the
Power Module from the unit before shipping.
Each Power Module contains two "C" size primary lithium/thionyl chloride
batteries. Primary lithium batteries (charged or discharged) are regulated
during transportation by the U.S. Department of T ransport ation. They are also
covered by IA TA (International Air Transport Association), ICAO (International
Civil Aviation Organization), and ARD (European Ground Transportation of
Dangerous Goods). It is the responsibility of the shipper to ensure compliance
with these or any other local requirements. Consult current regulations and
requirements before shipping.
Recycling of equipment and packaging should be taken into consideration
and disposed of in accordance with local and national legislation/regulations.
SAFETY MESSAGESInstructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or serious
injury:
• Only qualified personnel should perform the installation
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with
the appropriate local, national, and international standards, codes, and practices.
Please review the Product Certifications section for any restrictions associated with a
safe installation.
• Before connecting a Field Communicator in an explosive atmosphere, make
sure that the instruments are installed in accordance with intrinsically safe or
non-incendive field wiring practices
Process leaks may cause harm or result in death:
• Do not remove the transmitter while in operation
• Install the transmitter prior to process start-up
Electrical shock could cause death or serious injury:
• Avoid contact with the leads and terminals. High voltage that may be present
on leads can cause electrical shock
This device complies with Part 15 of the FCC Rules. Operation is subject to the
following conditions: This device may not cause harmful interference. This device must
accept any interference received, including interference that may cause undesired
operation. This device must be installed to ensure a minimum antenna separation
distance of 20 cm (8 in.) from all persons.
Probe Connection; warnings associated with probe connections
www.rosemount.com
Page 28
PRELIMINARY
Rosemount 3308
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
WIRELESS
CONSIDERATIONS
GeneralThe Wireless Guided Wave Radar Tr ansmitter has the capability to measure
level, distance, interface level or volume. The Rosemount 3308 converts the
measurement data into mapped variables and diagnostic information that are
transmitted through a wireless signal.
Power Up Sequence
The Smart Wireless Gateway (Gateway) should be installed and functioning
properly before any wireless field devices are powered. Install the Black
Power Module, SmartPower™ Solutions model number 701PBKKF into the
3308 transmitter to power the device. Wireless devices should also be
powered up in order of proximity from the Gateway, beginning with the
closest. This will result in a simpler and faster network installation. Enable
Active Advertising on the Gateway to ensure that new devices join the
network faster. For more information, see the Gateway Product Manual
(Document Number 00809-0200-4420).
Antenna Position
Figure 3-1. Recommended
Antenna Position
The antenna should be positioned vertically, either straight up or straight
down. It should be approximately 3 ft (1 m) from any large structure, building,
or conductive surface to allow for clear communication to other devices.
Conduit Entries
Unit comes with both conduit entries sealed with conduit plugs using an
approved thread sealant.
3-2
Page 29
Reference Manual
Conduit Entry
Conduit Entry
P/N 00753-9200-2410
P/N 00753-9200-2410
00809-XXXX-4811, Rev AA
February 2012
Figure 3-2. Conduit Entries
PRELIMINARY
Rosemount 3308
Field Communicator Connections
The Power Module needs to be installed in the device for the Fiel d
Communicator to interface with the Rosemount 3308 transmitter. This
transmitter uses the Black Power Module; please order model number
701PBKKF. Field communication with this device requires a HART-based
Field Communicator using the correct Rosemount 3308 Wireless DD. Field
communicator connections are located on the terminal block. The correct DD
for the available protocol should be selected. Refer to Figure 3-3 for
instructions on connecting the Field Communicator to the Rosemount 3308.
Figure 3-3. Field Communicator
Connection Diagram
MechanicalLocation
When choosing an installation location and position, take into accoun t access
to the transmitter for easy Power Module replacement. For b est performance,
the antenna should be vertical with space between objects in a parallel metal
plane, such as a pipe or metal framework, as the pipes or framework may
adversely affect the antenna's performance.
3-3
Page 30
PRELIMINARY
Rosemount 3308
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
ElectricalThe Rosemount 3308 Wireless Guided Wave Radar transmitter is
self-powered. The Black Power Module contains two "C" size primary
lithium/thionyl chloride batteries. Each battery contains approximately 2.5
grams of lithium, for a total of 5 grams in each Power Module. Under normal
conditions, the battery materials are self-contained and are not reactive as
long as the batteries and the Power Module are maintained. Care should be
taken to prevent thermal, electrical, or mechanical damage. Contacts should
be protected to prevent premature discharge.
Use caution when handling the power module; it may be damaged if dropped
from heights in excess of 20 ft (6.10 m).
3-4
Page 31
Reference Manual
TO BE UPDATED
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
POWER MODULE
INSTALLATION
Figure 3-4. Black Power Module
Installation
NOTE
Wireless devices should be powered up in order of proximity from the Smart
Wireless Gateway, beginning with the closest device to the Smart Wireless
Gateway. This will result in a simpler and faster network installation.
1. Install the Power Module.
NOTE
Use caution when handling the power module, it may be damaged if dropped
from heights in excess of 20 ft (6 m).
Figure 3-5. Possible Antenna
Rotations
2. Close the housing cover and tighten to site or safety specifications.
Always ensure a proper seal by installing the electronics housing covers
so that metal touches metal, but do not over tighten.
3. Position the antenna such that it is vertical, either straight up or straight
down, as shown in Figure 3-5. The antenna should be approximatel y 3 ft
(1 m) from any large structures or buildings to allow clear communication
to other devices.
NOTE
Possible antenna rotation shown. Antenna rota tion allows for best installation
practices in any configuration.
3-5
Page 32
Rosemount 3308
PRELIMINARY
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
DEVICE
CONFIGURATION
DEVICE NETWORK
CONFIGURATION
Remove the Power Module-side housing cover to expose the terminal block
and HART communication terminals, then connect the Power Module to
power the unit for configuration.
The Rosemount 3308 transmitter will receive any HART communication from
a handheld Field Communicator or AMS Wireless Configurator. When using a
Field Communicator, any configuration changes must be sent to the
transmitter using the Send key (F2). AMS Wireless Configurator configuration
changes are implemented when the Apply button is clicked.
®
Wireless Configurator
AMS
AMS Wireless Configurator is capable of connecting to devices dir ectly, using
a HART modem, or remotely using the Gateway.
When configuring on the bench with a HART modem, double click the device
icon, then choose the Configure/Setup tab (or right click and select
Configure/Setup). Configure the device settings using the Direct Connection
menu.
When configuring with the Gateway, double click the device icon then choose
the Configure/Setup tab (or right click an d select Con figur e/Setup ). Conf igure
the device settings using the Wireless Connection menu.
To communicate with the Gateway, and ultimately the host system, the
transmitter must be configured to communicate with the wireless network.
Using a Field Communicator or AMS Wireless Configurator, enter the
Network ID and Join Key so they match the Network ID and Join Key of the
Gateway and the other devices in the network. If the Network ID and Join Key
are the same as the Gateway, the transmitter will not communicate with the
network. The Network ID and Join Key may be obtained from the Gateway on
the Setup>Network>Settings page on the Gateway's integrated web server,
shown in Figure 3-6.
Figure 3-6. Gateway Network
Settings
3-6
Page 33
Reference Manual
COMM terminals
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
AMSRight click on the Rosemount 3308 transmitter and select Configure. When
the menu opens, select Join Device to Network and complete the method to
enter the Network ID and Join Key.
Field CommunicatorConnect the field communicator leads to the COMM terminals on th e terminal
block as shown in Figure 3-7.
Figure 3-7. Terminal Block with
COMM terminals
P/N 00753-9200-2410
The Network ID and Join Key may be changed in the wireless device on a
Field Communicator by using the Fast Key Sequence shown in Table 3-1.
Table 3-1. Rosemount 3308
Fast Key Sequence
FunctionKey SequenceMenu Items
Join Device to Network2, 1, 2Network ID, Set Join Key
Fast Key SequencesTable 3-1 lists the fast key sequence for common transmitter functions.
Table 3-2. Rosemount 3308
Fast Key Sequence
REMOVE POWER
MODULE
FunctionKey SequenceMenu Items
Device Information2, 2, 4Manufacturer, Model, Final Assembly Number,
Universal, Field Device, Software, Hardware
Descriptor, Message, Date, Model Number, I, II,
III, SI Unit Restriction, Country
Guided Setup2, 1Join Device to Network, Configure Update Rate,
Configure Sensor, Calibrate Sensor, Configure
Display, Configure Process Alarms
Manual Setup2, 2Wireless, Process Sensor, Percent of Range,
Device Temperature, Device Information,
Device Configure, Other
Wireless2, 2, 1Network ID, Join Device to Network, Configure
Update Rate, Configure Broadcast Power Level,
Power Mode, Power Source
If doing a bench top configuration, after the sensor and network have been
configured, remove the Power Module and replace the transm itter co ver. The
Power Module should be inserted only when the device is ready for
commissioning.
SAFETY MESSAGESProcedures and instructions in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
raises potential safety issues is indicated by a warning symbol (). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Failure to follow safe installation and servicing guidelines could result in death or
serious injury:
Make sure only qualified personnel perform the installation.
Use the equipment only as specified in this manual. Failure to do so may impair the
protection provided by the equipment.
Do not perform any service other than those contained in this manual unless you are
qualified.
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with the
appropriate local, national, and international standards, codes, and practices. Please review
the Product Certifications section for any restrictions associated with a safe installation.
Verify that the operating environment of the transmitter is consistent with the appropriate
hazardous locations certifications.
Before connecting a HART-based communicator in an explosive atmosphere, make sure
the instruments in the loop are installed in accordance with intrinsically safe or
non-incendive field wiring practices.
In an Explosion-proof/Flameproof installation, do not remove the transmitter cover when
power is applied to the unit.
Process leaks could result in death or serious injury:
Make sure that the transmitter is handled carefully. If the Process Seal is damaged, gas
might escape from the tank if the transmitter head is removed from the probe.
• Do not remove the transmitter while in operation
• Install device prior to process start-up
www.rosemount.com
Page 36
Rosemount 3308
PRELIMINARY
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
Electrical shock can result in death or serious injury:
• Avoid contact with the leads and terminals. High voltage that may be present on
leads can cause electrical shock.
Probes covered with plastic and/or with plastic discs may generate an ignition-capable level
of electrostatic charge under certain extreme conditions. Therefore, when the probe is used
in a potentially explosive atmosphere, appropriate measures must be taken to prevent
electrostatic discharge.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following
conditions: This device may not cause harmful interference. This device must accept any
interference received, including interference that may cause undesired operation. This
device must be installed to ensure a minimum antenna separation distance of 20 cm (8 in.)
from all persons.
4-2
Page 37
Reference Manual
Review Installation
Considerations
(see page 4-5)
Mount the transmitter
(see page 4-11)
Make sure covers
and cable/conduit
connections are
tight.
Power Up the
transmitter
Configure the
transmitter
(see page 5-1)
Verify measurements
Set the Write
Protection Switch
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
INSTALLATION
PROCEDURE
Follow these steps for proper installation:
4-3
Page 38
PRELIMINARY
Rosemount 3308
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
BEFORE YOU INSTALLElectronic boards are electrostatically sensitive. Failure to observe proper
handling precautions for static-sensitive components can result in damage to
the electronic components. Do not remove the electronic boards from the
Rosemount 3308 transmitter.
NOTE
To ensure long life for your radar transmitter, and to comply with hazardous
location installation requirements, tighten covers on both sides of the
electronics housing.
Software write protectSecurity write protection prevents unauthorized access to configuration data
through a Field Communicator or AMS Suite software.
4-4
Page 39
Reference Manual
Mounting on tank roofMounting in threaded pipe
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
MOUNTING
CONSIDERATIONS
Before installing the Rosemount 3308 transmitter, consider specific mounting
requirements, vessel characteristics and process characteristics.
Process ConnectionThe Rosemount 3308 transmitter has a threaded connection for easy
mounting on the tank roof. It can also be mounted on a nozzle by using
different flanges.
Threaded Connection
Figure 4-1. Mounting on tank
roof using threaded connection
4-5
Page 40
Rosemount 3308
H
D2 = min. diameter with Upper Null
Zone adjustment
H
UNZ
D1 = min. diameter
Figure 4-2. Mounting in nozzles
PRELIMINARY
Flange Connection on Nozzles
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
The transmitter can be mounted in nozzles by using an appropr iate flange. It
is recommended that the nozzle size is within the dimensions given in
Table 4-1. For small nozzles it may be necessary to increase the Upper Null
Zone (UNZ) in order to reduce the measuring range in the upper part of the
tank. By setting the UNZ equal to the nozzle height, the impact on the
measurement due to interfering echoes from the nozzle will be reduced to a
minimum. See also section “Disturbances at the Top of the Tank“ on page 7-10. Amplitude Threshold adjustments may also be needed in this
case.
NOTE
Except for the Coaxial Probe the probe must not be in co ntact with the n ozzle.
Table 4-1. Minimum nozzle diameter D1/D2 and maximum nozzle height H (inch/mm).
Rigid Twin LeadFlexible Twin LeadCoaxialSingle LeadFlexible Single
(1)
D1
(2)
D2
(5)
H
(1) Upper Null Zone=0.
(2) Upper Null Zone>0.
(3) Process connection 1.5 inch.
(4) Process connection 1 inch.
(5) Recommended maximum nozzle height. For coaxial probes there is no limitation on nozzle height.
(6) Nozzle diameter.
(7) For tall nozzles the Long Stud version is recommended (option code LS).
4/1004/100> Probe diameter6/1506/150
2/502/50> Probe diameter2/50
4/100 + D
(6)
4/100 + D
(6)
-4/100 + D
1.5/38
(3)
(4)
(6)
2/50
4/100 + D
(6) (7)
4-6
Page 41
Reference Manual
Metal flange Ø > 2 in. (DN50)
Metal sheet Ø > 8 in. (200 mm)
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
Installation of Single
Lead Probes in
Non-metallic Tanks
Figure 4-3. Mounting in
non-metallic tanks.
For optimal single lead probe performance in non-metallic tanks the probe
must be mounted with a metal flange, or screwed in to a metal sheet
(d>8 in./200 mm) if the threaded version is used.
Avoid introducing EMI environment near the tank. Installation in metallic tank
is recommended.
4-7
Page 42
Rosemount 3308
Ø
L
N
Rigid Single
Ø
Flexible Single
Ø
Flexible Twin
Ø
PRELIMINARY
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
Mounting in Still
pipes/by-pass pipes
Figure 4-4. Mounting in
Still Pipes.
In order to prevent the probe from contacting the bridle wall when replacing
displacers or installing in pipes, centering discs are available for the Rigid
Single, Flexible Single and Flexible Twin Lead probes. The disc is attache d to
the end of the probe and thus keeps the probe centered in the bridle. The
discs are available in stainless steel and PTFE. See also “Mounting a Centering Disc for Pipe Installations“ on page 4-17.
Note! It is not recommended that flexible
probes are installed in by-pass pipes.
Rigid Single Lead.
Pipe diameter Ø2 in. (50 mm).
Inlet pipe diameter N<Ø.
L12 in. (300 mm).
Flexible Single Lead.
Pipe diameter Ø4 in. (100 mm).
Note! For smaller pipes please consult
factory.
Make sure that the probe is at the center of
the Still pipe by, for example, using a
centering disc.
Note! It is not recommended that flexible
probes are installed in by-pass pipes.
Flexible Twin Lead.
Pipe diameter Ø4 in. (100 mm).
Note! For smaller pipes please consult
factory.
The center rod must be placed more than
0.6 in. (15 mm) away from the pipe wall. The
probe may under no circumstances get into
contact with the pipe wall. It is recommended
that a centering disc is used.
4-8
Coaxial Lead.
Pipe diameter Ø1.5 in. (38 mm).
Page 43
Reference Manual
L
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
Free SpaceFor easy access to the transmitter make sure that it is mounted with sufficient
service space. For maximum measurement performance the transmitter
should not be mounted too close to the tank wall or other objects in the tank.
If the probe is mounted close to a wall, nozzle or other tank obstruction noise
might appear in the level signal. Therefore the following minimum clearance,
according to the table below, must be maintained:
Figure 4-5. Free Space
Requirement
Table 4-2. Recommended
minimum free space L to tank
wall or other objects in the tank.
Table 4-3. Recommended
minimum free space L to tank
wall or other objects in the tank
for Single Lead probes.
CoaxialFlexible Twin
0 in. (0 mm)4 in. (100 mm)
Rigid Single/Flexible Single
4 in. (100 mm)Smooth metal wall.
12 in. (300 mm)
Disturbing objects such as pipes and beams, concrete or plastic tank
walls, rugged metal tank walls.
4-9
Page 44
Rosemount 3308
Inlet pipe
Heating coils
Agitator
PRELIMINARY
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
Recommended Mounting
Position
Figure 4-6. Mounting Position
When finding an appropriate mounting position for the transmitter the
conditions of the tank must be carefully considered. The transmitter should be
mounted so that the influence of disturbi ng ob jec ts is reduced to a minim u m.
In case of turbulence the probe may need to be anchored to the bottom. See
“Mechanical Installation“ on page 4-11 for more information.
The following guidelines should be considered when mounting the transmitter:
•Do not mount close to inlet pipes.
•Do not mount close to agitators. If the probe can move to within
12 in. (30 cm) away from an agitator a probe tie-down is
recommended.
•If the probe tends to sway due to turbulent conditions in the tank, the
probe should be anchored to the tank bottom.
•Avoid mounting close to heating coils.
•Make sure that the nozzle does not extend into the tank.
•Make sure that the probe does not come into contact with the nozzle or
other objects in the tank.
•Position the probe such that it is subject to a minimum of lateral force.
NOTE!
Violent fluid movements causing high sideway forces may break rigid probes.
4-10
Page 45
Reference Manual
Sealant on threads or
gasket (for BSP/G threads)
Nut
Tank connection
Probe
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
MECHANICAL
INSTALLATION
Figure 4-7. Threaded tank
connection.
Mount the transmitter with flange on a nozzle on top of the tank. The
transmitter can also be mounted on a threaded connection. Make sure only
qualified personnel perform the installation.
NOTE
If you need to remove the transmitter head from the probe, make sure that the
Process Seal is carefully protected from dust and water. See “Service“ on page 7-9 for further information.
1. For tank connections with BSP/G threads,
place a gasket on top of the tank flange, or
use a sealant on the threads of the tank
connection.
2. Lower the transmitter and probe into the
tank.
3. Screw the adapter into the process
connection.
4. Loosen the nut that connects the
transmitter housing to the probe slightly.
5. Rotate the transmitter housing so the
cable entries/display face the desired
direction.
6. Tighten the nut.
7. Continue with the Power Module
Installation.
NOTE!
For adapters with NPT threads, pressure-tight
joints require a sealant.
4-11
Page 46
Rosemount 3308
Transmitter head
Gasket
Flange
Tank flange
Nut
Probe
Bolts
Transmitter head
Gasket
Flange
Tank flange
Probe
Flange nut
Bolts
Nut
Figure 4-8. T an k connection with
flange.
PRELIMINARY
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
1. Place a gasket on top of the tank flange.
2. Lower the transmitter and probe with
flange into the tank.
3. Tighten the bolts.
4. Loosen the nut that connects the
transmitter housing to the probe slightly.
5. Rot ate the transmitter housing so the
cable entries/display face the desired
direction.
6. Tighten the nut.
7. Continue with the Power Module
Installation.
NOTE!
PTFE covered probes must be handled
carefully to prevent damage to the coating.
Figure 4-9. T an k connection with
loose flange (“plate design”).
The transmitter is delivered with head, flange
and probe assembled into one unit. If, for
some reason, these parts have been
disassembled mount the transmitter as
described below:
1. Place a gasket on top of the tank flange.
2. Mount the flange on the probe and
tighten the flange nut.
3. Mount the transmitter head.
4. Lower the transmitter and probe with
flange into the tank.
5. Tighten the bolts.
6. Loosen the nut that connects the
transmitter housing to the probe slightly.
7. Rot ate the transmitter housing so the
cable entries/display face the desired
direction.
8. Tighten the nut.
9. Continue with the Power Module
Installation.
4-12
Page 47
Reference Manual
Allen
screws
Minimum:
1.6 in.
(40 mm)
Spacer
Cut
PRELIMINARY
00809-XXXX-4811, Rev AA
February 2012
Shortening the ProbeFlexible Twin/Single Lead
Rosemount 3308
1. Mark off the required probe length. Add at
least 1.6 in. (40 mm) to the required probe
length to be inserted into the weight.
2. Loosen the Allen screws.
3. Slide the weight upwards as much as
needed in order to cut the probe.
4. Cut the probe. The minimum probe length
is 3.33 ft (1 m). If necessary, remove a
spacer to make room for the weight.
5. Slide the weight down to the required
cable length.
6. Tighten the screws.
7. Update the transmitter configuration to the
new probe length, see “Probe Length“ on
page 5-9.
If the weight was removed from the cables
when cutting, make sure that at least 1.6 in.
(40 mm) of the cable is inserted when the
weight is replaced.
Rigid Single Lead
1. Cut the Single Lead probe to the desired length.
2. Update the transm itter configuration to the new prob e length, see “Probe
Length“ on page 5-9.
NOTE!
The PTFE covered probes must not be cut in field.
4-13
Page 48
Rosemount 3308
Centering piece
Maximum shortening
23.6 in. (600 mm)
L > 49 in.
(1250 mm)
Minimum probe length
15.7 in. (400 mm)
L 49 in.
(1250 mm)
PRELIMINARY
Coaxial
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
To cut a coax ial pr ob e do the
following:
1. Insert the centering piece.
(The centering piece is
delivered from factory and
should be used to prevent the
spacers centering the r od from
coming loose).
2. Cut the tube to the desired length.
3. Move the centering piece.
4. Cut the rod inside the tube. Make
sure that the rod is fixed with the
centering piece while cutting.
• Pipes longer than
49 in. (1250 mm) can be
shortened by as much as
23.6 in. (600 mm).
• Pipes shorter than
49 in. (1250 mm) can be cut as
long as the remaining length is not
less than
15.7 in. (400 mm).
4-14
5. Update the transmitter
configuration to the new probe
length, see “Probe Length“ on
page 5-9.
Page 49
Reference Manual
Weight with
internal threads
M8x14
Ring
Magnet
1.1 in. (28 mm)
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
AnchoringIn turbulent tanks it may be necessary to fix the probe. Depending on the
probe type different methods can be used to guide the probe to the tank
bottom. This may be needed in order to prevent the probe from hitting the
tank wall or other objects in the tank, as well as preventing a pro be from
breaking.
Flexible Twin/Single Lead probe
with weight and ring.
A ring (customer supplied) can be
attached to the weight in a threaded
(M8x14) hole at the end of the
weight. Attach the ring to a suitable
anchoring point.
Flexible Twin/Single Lead probe
with weight and magnet.
A magnet (customer supplied) can
be fastened in a threaded (M8x14)
hole at the end of the weight. The
probe can then be guided by placing
a suitable metal plate beneath the
magnet.
Coaxial probe fixed to the tank wall.
The coaxial probe can be guided to
the tank wall by fixtures fastened to
the tank wall. Fixtures are customer
supplied. Make sure the probe can
move freely due to thermal
expansion without getting stuck in
the fixture.
4-15
Page 50
Rosemount 3308
Drain
PRELIMINARY
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
Coaxial probe.
The Coaxial probe can be guided by
a tube welded on the tank bottom.
Tubes are customer supplied. Make
sure that the probe can move freely
in order to handle thermal expansion.
Flexible Single Lead probe with
weight.
TO BE ADDED
Flexible Single Lead probe.
The probe rope itself can be used for
anchoring. Pull the probe rope
through a suitable anchoring point,
e.g. a welded eye and fasten it with
two clamps.
The length of the loop will add to the
transition zone.The location of the
clamps will determine the beginning
of the transition zone. The probe
length should be configured as the
length from the underside of the
flange to the top clamp. See section
“Transition Zones“ on page 2-12 for
further information on Transition
Zones.
4-16
Page 51
Reference Manual
Centering disc
Weight
Bolt
Tab washer
Tab washer
Bushing
Split pin
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
Mounting a Centering
Disc for Pipe
Installations
Flexible Single/Twin Lead probe
1. Mount the centering disc at the
end of the weight.
2. Make sure that the tab washer is
properly inserted in the centering
disc.
3. Fasten the centering disc with
the bolt.
4. Secure the bolt by folding the tab
washer.
Rigid Single Lead probe
1. Mount the centering disc at the
end of the probe.
2. Fasten the disc by inserting the
split pin through the bushing
and the probe.
3. Secure the split pin.
NOTE!
Centering discs may not be used with PTFE covered probes.
4-17
Page 52
PRELIMINARY
LCD Display
LCD Cover
LCD
Pins
LCD Display
LCD Cover
LCD
Pins
Rosemount 3308
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
LCD DISPLAY NOTE!
Do not remove the instrument cover in explosive environments when the
circuit is live.
GeneralIf the LCD display is ordered in the transmitter model number (option code
M5), it will be shipped attached to the transmitter.
NOTE
If ordering spare parts for a replacement LCD, only use Rosemount Wireless
LCD Part Number: 00753-9004-0002. This will provide a replacement
LCD/electronics board, and LCD pin connector.
LCD RotationThe optional LCD display can be rotated in 90-degree increments by
squeezing the two black tabs on opposite sides of the display, gently pulling
out the display, rotating to the desired orientation, and snapping back the
display into place. Refer to Figure 4-10 for a graphical illustration.
Figure 4-10. LCD Rotation
If the LCD pins are inadvertently removed from the interface board, carefully
re-insert the pins before snapping the LCD display back into place.
RetrofittingIf an existing transmitter with no display (flat electronics cover) is to be
retrofitted with a new display , order spare p art number 00753- 9004-0001. This
kit contains an extended aluminum cover with an LCD viewing window, an
LCD/electronics board, and an LCD pin connector . The co ntents of this kit are
shown in Figure 4-11.
Figure 4-11. LCD Display
Retrofit Kit
To install the LCD display, remove the electronics-side flat cover. Insert the
four-pin connector into the LCD display, rotate the LCD to the desired
LCD ConfigurationHow to configure parameters displayed, update rate, always off, etc.
orientation, and gently snap into place. Replace the flat cover wi th the LCD
cover and tighten. Refer back to Figure 4-10 for a graphical illustration.
4-18
Page 53
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
GROUND THE
TRANSMITTER
How to Ground the
Device
The Rosemount 3308 Wireless Guided W ave Radar transmitter operate s with
the housing grounded or floating. Floating systems can cause extra noise that
may affect many types of readout devices. If the signal appears noisy or
erratic, grounding at a single point may solve the problem. Grounding of the
electronics enclosure should be done in accordance with local and national
installation codes. Grounding is accomplished through the process
connection using the internal or external case grounding terminal.
SAFETY MESSAGESProcedures and instructions in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
raises potential safety issues is indicated by a warning symbol (). Refer to
the safety messages listed at the beginning of each section before performing
an operation preceded by this symbol.
Failure to follow safe installation and servicing guidelines could result in death or
serious injury:
Make sure only qualified personnel perform the installation.
Use the equipment only as specified in this manual. Failure to do so may impair the
protection provided by the equipment.
Do not perform any service other than those contained in this manual unless you are
qualified.
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with
the appropriate local, national, and international standards, codes, and practices.
Please review the Product Certifications section for any restrictions associated with a
safe installation.
• Before connecting a Field Communicator in an explosive atmosphere, ensure
the instruments are installed in accordance with intrinsically safe or
non-incendive field wiring practices.
• In an Explosion-proof/Flameproof installation, do not remove the transmitter
cover when power is applied to the unit.
Process leaks may cause harm or result in death:
• Do not remove the transmitter while in operation
• Install device prior to process start-up
Electrical shock could cause death or serious injury:
• Avoid contact with the leads and terminals. High voltage that may be present
on leads can cause electrical shock.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following
conditions: This device may not cause harmful interference. This device must accept
any interference received, including interference that may cause undesired operation.
This device must be installed to ensure a minimum antenna separation distance of 20
cm (8 in.) from all persons.
www.rosemount.com
Page 56
Rosemount 3308
COMM terminals
PRELIMINARY
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
DEVICE NETWORK
CONFIGURATION
Figure 5-1. Gateway Network
Settings
To communicate with the Gateway, and ultimately the host system, the
transmitter must be configured to communicate with the wireless network.
Using a Field Communicator or AMS Wireless Configurator, enter the
Network ID and Join Key so they match the Network ID and Join Key of the
Gateway and the other devices in the network. If the Network ID and Join Key
are the same as the Gateway, the transmitter will not communicate with the
network. The Network ID and Join Key may be obtained from the Gateway on
the Setup>Network>Settings page on the Gateway's integrated web server,
shown in Figure 5-1.
AMSRight click on the Rosemount 3308 transmitter and select Configure. When
the menu opens, select Join Device to Network and complete the method to
enter the Network ID and Join Key.
Field CommunicatorConnect the field communicator leads to the COMM terminals on th e terminal
block as shown in Figure 5-2.
Figure 5-2. Terminal Block with
COMM terminals
P/N 00753-9200-2410
The Network ID and Join Key may be changed in the wireless device on a
Field Communicator by using the Fast Key Sequence shown in Table 5-1.
Table 5-1. Rosemount 3308
Fast Key Sequence
FunctionKey SequenceMenu Items
Join Device to Network2, 1, 2Network ID, Set Join Key
5-2
Page 57
Reference Manual
LRV
URV
Tank Height
Upper Null Zone
Product Level
Upper Reference Point
Lower Reference Point
Interface
Level
Probe
Length
NPTBSP (G)FLANGE
Upper Reference Point
Adapter
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
CONFIGURATION
PARAMETERS
The Rosemount 3308 transmitter can be configured for level, volume,
interface level, and interface distance measurements.
The Rosemount 3308 transmitter can be pre-configured according to the
ordering specifications in the Configuration Data Sheet.
Basic ConfigurationThe basic transmitter configuration includes setting the tank geometry
parameters. For interface measurements the dielectric constant of the top
liquid must also be given. For some applications with heavy vapor, the vapor
dielectric must be given as well.
Figure 5-3. Tank Geometry
Figure 5-4. Upper Reference
Point
For the different tank co nnections the Up per Reference Point is loca ted at the
underside of the threaded adapter or at the underside of the welde d flange, as
illustrated in Figure 5-4:
5-3
Page 58
Rosemount 3308
PRELIMINARY
Tank Height
The Tank Height is the distance from the Upper Reference Point to the bottom
of the tank. The transmitter m easures the d ist a nce to the prod uct surface a nd
subtracts this value from the Tank Height to determine the level.
Probe Length
The probe length is the distance betwee n the Upper Reference Point and the
end of the probe. If a weight is used at the end of the probe it shall not be
included.
This parameter is pre-configured at factory. It must be changed if the probe is
shortened.
Probe Type
The transmitter is designed to optimize measurement performance for each
probe type.
This parameter is pre-configured at factor y. This value needs to be changed if
the probe type is changed.
Dielectric Constant of Upper Product
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
For interface measurements the dielectric constant of the upper product is
essential in order to obtain good accuracy. See section “Interface” on
page 2-7 for further information on dielectric constants.
If the dielectric constant of the lower product is significantly smaller than the
dielectric constant of water, you may need to make special adjustments. See
section “Interface Measurements for Semi-Transparent Bottom Products” on
page 7-5 for further information.
For level measurements the Upper Product Dielectric parameter corresponds
to the actual dielectric constant of the product in the tank. Normally this
parameter does not need to be changed even if the actual dielectric constant
of the product deviates from the Upper Product Dielectric parameter value.
However, for so me products measurement performance can be optimize d by
setting the proper product dielectric constant.
Dielectric Constant of Vapor
In some applications there is heavy vapor above the prod uct surface having a
significant influence on the level measurement. In such cases the vapor
dielectric can be entered to compensate for this effect.
The default value is equal to 1 which corresponds to th e die lectricity of
vacuum. Normally this value does not need to be changed since the effect on
measurement performance is very small for most vapors.
5-4
Page 59
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
Upper Null Zone
This parameter should only be chang ed if there are measuremen t problems in
the upper part of the tank. Such problems may occur if there are disturbing
objects close to the probe. By setting the Upper Null Zone, the measuring
range is reduced. See Section 7: Disturbances at the Top of the Tank for
further information.
NOTE
Measurements are not performed within the Upper Null Zone.
Probe angle
If the transmitter is not mounted vertically, the angle from the vertical position
must be given.
5-5
Page 60
PRELIMINARY
Actual tank bottom may look like this.
Using only 3 strapping points results in a level-to-volume profile
that is more angular than the actual shape.
Using 6 of the points at the bottom of the tank yields a
level-to-volume profile that is similar to the actual tank bottom.
Rosemount 3308
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
Volume ConfigurationFor volume calculations you can choose one of the standard tank shapes or
the strapping option. Choose None if volume calculation is not used.
Tank Type
You can choose one of the following options:
•Strap table
•Vertical Cylinder
•Horizontal Cylinder
•Vertical Bullet
•Horizontal Bullet
•Sphere
•None
Strapping Table
Use a strapping table if a standard tank type does not provide sufficient
accuracy . Use most o f the strapp ing point s in region s where th e ta nk shape is
non-linear. A maximum of 10 points can be added to the strapping table.
Figure 5-5. Strapping points
5-6
Page 61
Reference Manual
Diameter
Height
Diameter
Height
Diameter
Height
Diameter
Height
Diameter
00809-XXXX-4811, Rev AA
February 2012
Figure 5-6. Standard tank
shapes
PRELIMINARY
Rosemount 3308
Standard Tank Shapes
Vertical Cylinder
Vertical Cylinder t anks are sp ecified by
Diameter and Height.
Horizontal Cylinder
Horizontal Cylinders are specified by
Diameter and Height.
Vertical Bullet
Vertical Bullet tanks are specified by
Diameter and Height. The volume
calculation model for this tank type
assumes that the radius of the bullet
end is equal to the Diameter/2.
Horizontal Bullet
Horizontal Bullets are specified by
Diameter and Height. The volume
calculation model for this tank type
assumes that the radius of the bullet
end is equal to the Diameter/2.
Sphere
Spherical tanks are specified by
Diameter.
5-7
Page 62
Rosemount 3308
Function Key
Navigation Keys
Alphanumeric Keys
Backlight adjustment key
Tab Key
Enter Key
Replace with 475
PRELIMINARY
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
CONFIGURATION USING
A FIELD
COMMUNICATOR
Figure 5-7. The Field
Communicator.
This section describes how to configure the Rosemount 3308 transmitter by
using a Field Communicator. A HART Communicator may also be used.
For information on all the capabilities, refer to the Field Communicator
Product Manual (Document No. 00809-0100-4276).
5-8
Page 63
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
BASIC CONFIGURATIONThis section describes the various HART commands used to co nfigure the
Rosemount 3308 transmitter for level measurements. The tr ansmitter outpu ts
a digital HART wireless signal.
Transmitter Variables
HART Comm
TO BE
ADDED
Measurement Units
HART Comm
TO BE
ADDED
Tank Height
HART Comm
TO BE
ADDED
Probe Length
HART Comm
TO BE
ADDED
Y ou may assign up to fou r transmitter variables. T yp ically, the primary variable
(PV) is configured to be Aggregate Level, Interface Level or Volume.
Set transmitter units for level and temperature.
The Tank Height is the distance from the Upper Reference Point to the bottom
of the tank (see Figure 5-3 on page 5-3). When setting the Tank Height, keep
in mind that this value is used for all level measurements performed by the
Rosemount 3308 transmitter.
The Tank Height must be set in linear (level) units, such as feet or meters,
regardless of primary variable assignment.
The probe length is the distance from the Upper Reference Point to the end of
the probe, see Figure 5-3. If the probe is anchored to a weight do not include
the height of the weight. This parameter is pre-configured at factory. The
Probe Length needs to be changed if, for example, the probe is shortened.
5-9
Page 64
Rosemount 3308
Probe Type
PRELIMINARY
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
HART Comm
TO BE
ADDED
Product Dielectric
HART Comm
TO BE
ADDED
The transmitter automatically makes an initial calibration based on the type of
probe that is used. This parameter is pre-configured at factory and only needs
to be set if the probe is changed to another type. Choose one of the fo llowing
options:
•Flexible Twin
•Coaxial
•Rigid Single, Rigid Single PTFE
•Flexible Single, Flexible Single PTFE
For interface measurements the dielectric constant of the upper product is
essential for calculating the interface level and the upper product thickness.
By default the Product Dielectric parameter is about 2.
If the dielectric constant of the lower product is significantly smaller than the
dielectric constant of water, you may need to make special adjustments. See
section “Interface Measurements for Semi-Transparent Bottom Products” on
page 7-5 for further information.The dielectric constant of the product is used
for setting the appropriate signal amplitude thresholds, see Section 7: Ser vice
and Troubleshooting for more information on amplitude threshold settings.
Normally this parameter does not need to be changed for level
measurements. However, for some products measurement performance can
be optimized by setting the proper product dielectric constant.
The AMS Suite software includes a Dielectric Chart which lists the dielectric
constants of a wide range of products. AMS also includes a tool which allows
you to calculate dielectric constants based on measurements of the Upper
Product Thickness.
Va por Dielectric
HART Comm
5-10
TO BE
ADDED
In some applications there is heavy vapor above the prod uct surface having a
significant influence on the level measurement. In such cases the vapor
dielectric can be entered to compensate for this effect.
The default value is equal to 1 which corresponds to the dielectric constant of
vacuum. Normally this value does not need to be changed since the effect on
measurement performance is very small for most vapors.
Page 65
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
Measurement Mode
PRELIMINARY
Rosemount 3308
HART Comm
TO BE
ADDED
Table 5-2. Measurement Mode
Probe Angle
HART Comm
TO BE
ADDED
Normally the Measurement Mode does not need to be changed. The
transmitter is pre-configured according to the specified model:
ModelMeasurement Mode
(1)
3308Level, Level and Interface
(1) Default setting
, Interface Immersed probe
Interface Immersed Probe is used for applications where the probe is fully
immersed in liquid. In this mode the transmitter ignores the upper product
level. See Section 7: Interface Measurements with Fully Immer sed Probes for
more information.
NOTE!
Only use Interface Immersed Probe for applications where interface is
measured for a fully immersed probe.
Enter the angle between the probe and the vertical line. The default value is
equal to zero. Do not change this value if the transmitter is mounted with the
probe along the vertical line (which is normally the case).
Maximum Upper Product
Thickness
HART Comm
TO BE
ADDED
Display
HART Comm
TO BE
ADDED
For interface measurements the Maximum Upper Product Thickness
parameter may be used in special cases when the dielectric constant of the
upper product is relatively high. By setting this parameter you can avoid that
interface measurements are getting out of range.
Choose variabels to be displayed.
5-11
Page 66
Rosemount 3308
Upper Range Value (URV)
Upper Transition Zone
Product Level
Interface Level
Lower Transition Zone
Lower Range Value (LRV)
Upper Reference Point
Range 0-100 %
Figure 5-8. Range Values
PRELIMINARY
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
5-12
Page 67
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
VOLUME
CONFIGURATION
Transmitter Variables
PRELIMINARY
Rosemount 3308
HART Comm
Volume Units
HART Comm
Tank Type
HART Comm
TO BE
ADDED
TO BE
ADDED
TO BE
ADDED
Select the Volume option in o rder to configure the transmitter for volume
measurements.
Choose one of the following units:
•Gallons
•Liters
•Imperial Gallons
•Cubic Meters
•Barrels
•Cubic Yards
•Cubic Feet
•Cubic Inch
Choose a standard tank shape, or select the strapping option. Standard
SAFETY MESSAGESInstructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
potentially raises safety issues is indicated by a warning symbol ( ). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
Failure to follow safe installation and servicing guidelines could result in death or
serious injury:
Make sure only qualified personnel perform the installation.
Use the equipment only as specified in this manual. Failure to do so may impair the
protection provided by the equipment.
Do not perform any service other than those contained in this manual unless you are
qualified.
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with
the appropriate local, national, and international standards, codes, and practices.
Please review the Product Certifications section for any restrictions associated with a
safe installation.
• Before connecting a Field Communicator in an explosive atmosphere, ensure
the instruments are installed in accordance with intrinsically safe or
non-incendive field wiring practices.
• In an Explosion-proof/Flameproof installation, do not remove the transmitter
cover when power is applied to the unit.
Process leaks may cause harm or result in death:
• Do not remove the transmitter while in operation
• Install device prior to process start-up
Electrical shock could cause death or serious injury:
• Avoid contact with the leads and terminals. High voltage that may be present
on leads can cause electrical shock.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following
conditions: This device may not cause harmful interference. This device must accept
any interference received, including interference that may cause undesired operation.
This device must be installed to ensure a minimum antenna separation distance of 20
cm (8 in.) from all persons.
www.rosemount.com
Page 72
Rosemount 3308
X X X X X
X X X X x x x
x x x x x x
702
W I r e l s
A b c d e
f g h
s n s r1
True
LCD SCREEN
MESSAGES
PRELIMINARY
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
Startup Screen
Sequence
The following screens will display when the power module is first connected to
the Rosemount 3308.
All Segments On: used to visually determine if
there are any bad segments on the LCD
Device Identification: used to determine Device
Type.
Device Information - Tag: user entered tag which
is 8 characters long - will not display if all characters
are blank
PV Screen - Measurement of mapped Primary
Variable (default is XX)
6-2
Page 73
Reference Manual
S N S R 2
True
D E V
2 5. 2 5
d e g c
S u p l y
7. 2 1
v o l t s
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
SV Screen - Measurement of mapped Second
Variable (default is XX)
Electronics Temperature
Supply Voltage
DISPLAY OPERATIONDuring steady state operation, the LCD gives a periodic display of
user-chosen variables at the configured wireless upda te rate. These variables
can be chosen from a list of XX: Level, …………………
The LCD Display will display the variables at the configured update rate, but
no faster than XXX. Refer to page XX for instructions on configuring the
display.
Diagnostic Button
Screen Sequence
Detailed diagnostic information can be obt ained by removing the display
cover of the Rosemount 3308 transmitter, and momentarily depressing the
"DIAG" button. The LCD will display the diagnostic screens as shown below.
Press the Diagnostic button to display the TAG, Device ID, Network ID, Network Join Status, and Device Status screens.
The following five screens will display when the device is operating properly
and the Diagnostic Button has been pressed.
6-3
Page 74
Rosemount 3308
A b c d e
f g h
i d - X X
X X X X X X
n e t w k
13 0 5
I D
n e t w k
O K
S u p l y
7. 2 1
v o l t s
PRELIMINARY
Diagnostic Button Screen 1: Tag
Diagnostic Button Screen 2: Device
Identification - used to determine Device ID
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
Diagnostic Button Screen 3: Network ID
Diagnostic Button Screen 4: the device has
joined a network and has been fully con figured and
has multiple parents. Also see “Network
Connection Status Screens” on page 6-5.
Diagnostic Button Screen 5: voltage reading at
the Power Module terminals. Also see
6-4
Page 75
Reference Manual
n e t w k
u n k n w n
n e t w k
I N I T
n e t w k
i d l e
n e t w k
D I S C N T
N E T w K
S R C H N G
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
Network Connection
Status Screens
One of the following network diagnostic status screens will display in the
fourth position of the Diagnostic Button Screen sequence. The screen
displayed is dependent on the progress of the device in joining the wireless
network.
Diagnostic Button Screen 4.1: the device is still
in the process of being activated
Diagnostic Button Screen 4.2: the device has
just started
Diagnostic Button Screen 4.3: the device has
just started to join the network
Diagnostic Button Screen 4.4: the device is in a
disconnected state and requires a "Force Join"
command to join the network
Diagnostic Button Screen 4.5: the device is
searching for the network
6-5
Page 76
Rosemount 3308
n e t w k
N E G O T
n e t w k
c o n e c t
n e t w k
L I M - O P
n e t w k
O K
b o a r d
f a i l u r
PRELIMINARY
Diagnostic Button Screen 4.6: the device is
attempting to join a network
Diagnostic Button Screen 4.7: the device is
connected to the network, but is in a “quarantined”
state
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
Diagnostic Button
Screen Sequence
(continued)
Diagnostic Button Screen 4.8: the device is
joined and operational, but is running with limited
bandwidth for sending periodic data
Diagnostic Button Screen 4.9: the device has
joined a network and has been fully con figured and
has multiple parents
The following screens will show the device diagnostics depending on the state
of the device, continuing after Diagnostic Button Screen 5.
Diagnostic Button Screen 6.1: there is a critical
error which may prevent the electronics board from
operating correctly
6-6
Page 77
Reference Manual
b o a r d
w a r n
s u p l y
f a i l u r
s u p l y
l o w
r a d i o
f a i l u r
c o n f g
f a i l u r
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
Diagnostic Button Screen 6.2: there is a warning
which should be addressed, but should not affect
the device output.
Diagnostic Button Screen 7.1: the terminal
voltage has dropped below level of operating limit.
Replace the Black Power Module model number
701PBKKF
(Part Number: 00753-9220-0001)
Diagnostic Button Screen 7.2: the terminal
voltage is below the recommended operating
range
- if this is a self-operated device, the power module
should be replaced - for line powered devices, the
supply voltage should be increased
Diagnostic Button Screen 8: the device cannot
retrieve information from the radio in the device the device may still be operational and publishing
HART data
Diagnostic Button Screen 9: configuration of the
transmitter is invalid such that critical operation of
the device may be affected - check the extended
configuration status to identify which configuration
item(s) need to be corrected
6-7
Page 78
Rosemount 3308
s n s r
f a i l u r
B D W T H
L I M I T D
PRELIMINARY
Diagnostic Button Screen 10: a switch attached
to the transmitter has failed, and valid readings
from that probe are no longer possible - check the
probe and probe wiring connections - check
additional status for more detailed information of
the failure source
Diagnostic Button Screen 11: the device has not
yet received all of the requested wireless
bandwidth needed to operate as configur ed
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
Diagnostic Button Screen 12: the device has not
yet received all of the requested wireless
bandwidth needed to operate as configur ed
Diagnostic Button Screen 13+: all of the periodic
screens except Supply Voltage will now be
displayed to conclude the Diagnostic Button
Screen Sequence. These screens are:
PV Measurement
SV Measurement
Electronics Temperature
ALERTSThe Rosemount 3308 can be configured to report alerts based on the
measured variables. The Rosemount 3308 also reports diagnostic alerts
when there is a device malfunction. For information on these alerts, refer to
Section 6: Troubleshooting. The following figures show how the AMS Suite
Intelligent Device Manager overview screen looks for each of the alert
conditions.
6-8
Page 79
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
Figure 6-1. AMS Device
Manager Overview Screen,
Normal Conditions
The Rosemount 3308 provides 4 user configurable alerts.
HI HI
HI
LO
LO LO explain all and add image.
Alert Setup
There are three methods that can be used to set up these alerts u sing AMS
Wireless Configurator or a field communicator.
Add methods.
6-9
Page 80
Rosemount 3308
PRELIMINARY
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
POWER MODULE
REPLACEMENT
Expected Power Module life is XX years at reference conditions
Add warnings
When the Power Module needs to be replaced, remove the Power Module
cover and the depleted Power Module. Replace the powe r module with a n ew
Black Power Module, SmartPower™ Solutions model number 701PBKKF.
Replace the cover and ensure that the power module cover is fully tightened
to prevent moisture ingress. The lip of the power module cover should be in
contact with the metal enclosure to ensure a pro per seal. Do not over tighten.
Handling Considerations
The Black Power Module with the wireless unit contains two "C" size primary
lithium/thionyl chloride batteries. Each battery contains approximately 2.5
grams of lithium, for a total of 5 grams in each Power Module. Under normal
conditions, the battery materials are self-contained and are not reactive as
long as the batteries and the battery pack integrity are maintained. Care
should be taken to prevent thermal, electrical or mech anical damage.
Contacts should be protected to prevent premature discharge.
Use caution when handling the power module, it may be damaged if dropped
from heights in excess of 20 ft (6 m).
Battery hazards remain when cells are discharged.
Environmental Considerations
As with any battery, local environmental rules and regulations should be
consulted for proper management of spent batteries. If no specific
requirements exist, recycling through a qualified recycler is encouraged.
Consult the materials safety data sheet for battery specific information.
(1)
.
Shipping Considerations
The unit was shipped to you without the power module inst alled. Please
remove the power module prior to shipping.
Each Black Power Module contains two "C" size primary lithium batteries.
Primary lithium batteries are regulated in transportation by the U.S.
Department of Transportation, and are also covered by International Air
Transport Association ( IA TA), International Civil Aviation Organization (ICAO),
and European Ground Transportation of Dangerous Goods (ARD). It is the
responsibility of the shipper to ensure compliance with these or any other
local requirements. Please consult current regulations and requirements
before shipping.
(1) Reference conditions are 70° F (21° C), transmit rate of once per minute, and routing data
SAFETY MESSAGESProcedures and instructions in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
raises potential safety issues is indicated by a warning symbol (). Please
refer to the following safety messages before performing an operation
preceded by this symbol.
.
Explosions could result in death or serious injury.
Verify that the operating environment of the gauge is consistent with the appropriate
hazardous locations certifications.
Before connecting a HART-based communicator in an explosive atmosphere, make
sure the instruments in the loop are installed in accordance with intrinsically safe or
non-incendive field wiring practices.
In an Explosion-proof/Flameproof installation, do not remove the transmitter cover when
power is applied to the unit.
Failure to follow safe installation and servicing guidelines could result in death or
serious injury.
Make sure only qualified personnel perform the installation.
Use the equipment only as specified in this manual. Failure to do so may impair the
protection provided by the equipment.
Do not perform any service other than those contained in this manual unless you are
qualified.
High voltage that may be present on leads could cause electrical shock.
Avoid contact with leads and terminals.
Make sure the main power to the Rosemount 3308 transmitter is off and the lines to any
other external power source are disconnected or not powered while wiring
the gauge.
Probes covered with plastic and/or with plastic discs may generate an ignition-capable
level of electrostatic charge under certain extreme conditions. Therefore, when the
probe is used in a potentially explosive atmosphere, appropriate measures must be
taken to prevent electrostatic discharge.
Process leaks could result in death or serious injury.
Make sure that the transmitter is handled carefully. If the Process Seal is damaged, gas
might escape from the tank if the transmitter head is removed from the probe.
www.rosemount.com
Page 82
Rosemount 3308
Tank Height
Product Level
Upper Reference Point
Transmitter
Reference Point
Calibration
Offset
PRELIMINARY
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
ADVANCED
CONFIGURATION
User defined Upper
Reference Point
Figure 7-1. Tank Geometry
This section covers non-standard configuration.
If you want to specify your own Upper Reference Point you can do this by
setting the Calibration Offset parameter.
7-2
To set the desired upper reference point do the following:
1. Adjust the Tank Height to the distance from the tank bottom to the
desired Upper Reference Point.
2. Add the distance betw een th e Upper Reference Point and the
Transmitter Reference Point to the Calibration Offset value that is
stored in the transmitter database.
With the HART Communicator the Calibration Offset is available as
HART Fast Key sequence [1, 4, 5, 5].
In Radar Configuration Tool (RCT) the Calibration Offset is available
under the Advanced section in the RCT Project Bar:
Device Commands>Basic>Set Calibration Offset.
Page 83
Reference Manual
Upper Null Zone
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
Plotting the
Measurement Signal
Figure 7-2. Waveform plot in RCT
The Radar Configuration Tool (RCT) has powerful tools for advanced
troubleshooting. By using the Waveform Plot function you get an instant view
of the tank signal. Measurement problems can be solved by studying the
position and amplitude of the different pulses.
To plot the measurement signal:
1. Start the Radar Configuration Tool program.
2. Choose the View>Plotting menu option, or choose the Plotting icon in
the RCT workspace (Advanced page at the left side of the workspace)
and click the Read button.
-
In a typical measurement situation the following pulses app ear in the dia gram:
P1 - Reference pulse. This pulse is caused by the transition between
transmitter head and probe. It is used by the transmitter as a reference at
level measurements.
P2 - Product surface. This pulse is caused by a reflection on the product
surface. In Measurement Mode=Interface when Immersed Probe however , P2
indicates the interface since the surface of the upper product is ignored.
P3 - Interface or probe end. This pulse is caused by reflection on th e interface
between an upper product and a bottom product with a relatively high
dielectric constant. It may also be caused by the probe end if there is no
product above. This pulse is shown when the transmitter is in Measurement
Mode=Level & Interface.
Different amplitude thresholds are used in order to filter out unwanted signals.
The following amplitude thresholds are used for the Rosemount 3308
transmitter:
T1 - amplitude threshold for detection of the Reference pulse P1.
T2 - amplitude threshold for detection of the product level peak P2.
T3 - amplitude threshold for detection of the interface level peak P3.
T4 - amplitude threshold that is used to detect whether the probe is fully
immersed in the upper product or not.
7-3
Page 84
Rosemount 3308
Start disk logging
Start monitoring
Number of plots
Read plot interval
Read action type
Figure 7-3. Disk logging
Waveform p lot
PRELIMINARY
Normally the thresholds are adjusted to approximately 50% of the signal peak
amplitude. To adjust the Amplitude Thresholds open the Advanced section
in the RCT Project Bar and choose Device Commands>Details>Set Nominal
Thresholds. To reset the default values set Amplitude Threshold=0 (zero).
Logging and saving to disk
The Waveform plot can be automatically logge d and saved to file by
specifying the read plot interval and the number of plots to log.
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
7-4
The Read Plot Interval entry field specifies the time interval between plots
that are saved to disk. For example, type 10 if you want the waveform plot to
be updated every ten minutes.
Number of plots to log specifies the maximum number of plot files that will
be stored. The default value is 100.
Click the Start Disk Logging button to start the log. Make sure that Read
Action type is set to Multiple Read. Otherwise RCT will only save one log file.
Choose a destination folder and enter a file name. For each new file the
corresponding number is appended to the end of the file name.
Page 85
Reference Manual
The amplitude threshold is above
the measurement signal peak
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
Interface Measurements
for Semi-Transparent
Bottom Products
In interface applications where the bottom product has a low dielectric
constant, or if the signal is attenuated in the upper product, the amplitude of
the reflected signal is relatively low and dif ficult for the transmitter to detect. In
such a case it may be possible to detect the reflected signal if the
corresponding amplitude threshold is adjusted.
The Radar Configuration Tool (RCT) lets you view a waveform plot to analyze
the measurement signal. The plot shows the signal and the thresholds used
for the different amplitude peaks. By adjusting amplitude threshold T3 it is
possible to detect even weak interface signals.
Guidelines for amplitude threshold settings:
•The amplitude threshold T3 should be approximately 50 % of the
interface signal amplitude.
•Threshold T3 should not be less than 3.
•If possible, T3 should be higher than T2.
You can use the RCT software or a Field Communicator to change the
amplitude thresholds. For the Field Communicator use the HART command
[1, 4, 5, 3]. See also “Amplitude Threshold Settings” on page 7-12.
RCT lets you view a plot of the measurement signal along with the current
thresholds:
1. From the View menu choose the Plotting option, or double-click the
Plotting icon in the Advanced section of the RCT Project Bar.
2. Click the Read button .
3. To adjust the Amplitude Thresholds open the Advanced section in the
RCT Project Bar and choose Device Commands>Details>Set Nominal
Thresholds.
Figure 7-4. Waveform plot
indicating that the amplitude
threshold for the interface peak
is too high.
7-5
Page 86
Rosemount 3308
The amplitude threshold is
adjusted below the peak to allow
the interface peak to be detected
Figure 7-5. After changing the
amplitude threshold the
transmitter detects the interface
PRELIMINARY
Figure 7-4 illustrates a situation where amplitude threshold T3 is too high. The
signal amplitude peak at the interface between the upper and lower prod ucts
is not detected in this case. By adjusting amplitude threshold T3, the peak at
the interface between the upper and lower products is detected as illustrated
in Figure 7-5:
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
7-6
Page 87
Reference Manual
Damping
Output tab
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
High Level RatesThe measurement signal is filtered in order to minimize the influence of
disturbing noise. In most measurement situations this does not have a
noticeable effect on the response time to level changes. If high level rates
occur it may however be necessary to reduce the damping value in order to
allow the transmitter to respond quicker. If there is too much noise the
damping value may be increased in order to get a stab le measurement sign al.
You can use the RCT software or a Field Communicator to change the
Damping value. For the HART Communicator use the key sequence
[1, 3, 5].
In the RCT software open the Setup>Output tab and enter the desired
Damping value:
The Damping parameter determines how quickly the tr ansmitter responds to
level changes and how robust the measurement signal is against noise.
Technically, a damping value of 10 means that in 10 seconds the output from
the transmitter is about 63% of the new level value. Consequen tly, when there
are rapid level changes in the tank, it may be necessary to decr ease the
Damping value for the transmitter to be able to track the surface. On the other
hand, in noisy environments, and if level rates are low, it may be better to
increase the damping value to have a stable output signal.
7-7
Page 88
Rosemount 3308
Interface Distance
Interface Level
Product Level
is ignored
Interface Level is
measured
PRELIMINARY
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
Interface Measurements
with Fully Immersed
Probes
The Rosemount 3308 transmitter has a measurement option which makes it
possible to handle interface measurements when the product level is not
visible, for example in a full bridle pipe as illustrated in Figure 7-6. In this case
the probe is fully immersed into the upper product, and o nly the interface level
is detected by the transmitter. Even if the upper product level drops, it is
ignored by the transmitter which continues to measure only the interface level,
but the measurement accuracy is reduced since the transmitter does not take
into account the influence of the air gap above the product surface.
The Measurement Mode parameter is available via the
HART command [1, 3, 3, 4]. Choose the Interface when Immersed Probe
option.
Measurement mode Interface when Immersed Probe can also be activated in
the RCT software:
1. Open the Setup window.
2. Select the Tank Config tab.
3. Choose Measurement Mode Interface when Immersed Probe.
4. Click the Send Page button.
NOTE!
Do not use Measurement Mode Interface when Immersed Probe in “stand ard”
applications when both Interface Level and Product Level are measured.
Figure 7-6. Interface Level
measurements in a full bridle
pipe.
If the product level drops, the air filled region in the upper part of the pipe will
slightly reduce the measurement accuracy of the interface level. To achieve
high accuracy in this measurement mode the probe must be fully immersed.
7-8
NOTE!
Adjust Threshold T2 if the level pulse is not detected.
Page 89
Reference Manual
Level
Reference Point
Tank Height
Distance
Reference Point
00809-XXXX-4811, Rev AA
February 2012
SERVICE
PRELIMINARY
Rosemount 3308
Level and Distance
Calibration
When calibrating the transmitter it is important that the product surface is calm
and that the tank is not being filled or emptied.
A complete calibration is performed in two steps:
1. Calibrate the Distance measurement by adjusting the Calibration Offset
parameter.
2. Calibrate the Le ve l measu re m en t by adju stin g the Tank Height.
Distance calibration
1. Measure the actual distance between the Upper Reference Point and the
product surface.
2. Adjust the Calibration Offset so that the Distance measured by the
transmitter corresponds to the actual distance.
The Calibration Offset parameter is available via
HART command [1, 4, 5, 5],
or
RCT: open the Advanced section in the Project Bar and choose Device
Commands>Basics>Set Calibration Offset.
Level calibration
1. Measure the actual Product Level.
2. Adjust the Tank Height so that the measured Product Level corresponds
with the actual level.
Figure 7-7. Distance and Level
calibration
7-9
Page 90
Rosemount 3308
PRELIMINARY
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
Disturbances at the Top
of the Tank
Using the Trim Near Zone Function
For transmitters using the Guided Wave Radar technology the performance In
the Near Zone (referred to as the reg ion between 0-1.6 ft (0-0.5 m) below the
Upper Reference Point) is normally somewhat limited. However, the
Rosemount 3308 transmitter is equipped with software functionality that
minimizes the Upper Transition Zone. The factory setting is normally sufficient
and doesn’t need to be repeated after installation.
However, since the setting is optimized depending on actual installation,
further trimming may be necessary in the case of unfavorable conditions. This
may for example be the case if a Single Lead probe is mounted in a small
nozzle, or if there are disturbing obstacles in the Near Zone. The trimming
means that the measurement performance in the Near Zone is maintained
even under these conditions and prevents false echo indic at i on .
To trim the Near Zone performance do the following:
1. Make sure that the product level is below the Near Zone region
(0-1.6 ft (0-0.5 m) below the Upper Reference Point).
2. Start the Radar Configuration Tools (RCT).
3. Choose the Device Commands option from the View menu.
4. Open the Details folder.
5. Click the Trim Near Zone option.
6. Select the Update option and click the OK button.
NOTE!
The Trim Near Zone function should only be used for reducing impact from
constant disturbances. It is not suitable for occasional disturbances.
To reset the transmitter to factory settings do the following:
1. Start the Radar Configuration Tools (RCT).
2. Choose the Device Commands option from the View menu.
3. Open the Details folder.
4. Click the Trim Near Zone option.
5. Select the Reset to Factory Settings option and click the OK button.
Changing the Upper Null Zone
Measurements are not performed within the Upper Null Zone (UNZ). By
setting the UNZ parameter to zero, measurements can be performed in the
region close to the flange (Near Zone). However, it is very important that there
are no disturbances in that region if UNZ is set to zero.
If there are measurement problems in the upper part of the tank you may use
the Trim Near Zone function as described above.
If the desired measurement range is below the Near Zone, or if disturbing
objects are located below the Near Zone, the Upper Null Zone parameter can
be used to avoid measurements above a certain level.
7-10
Page 91
Reference Manual
Tank Height
Upper Null
Zone
Product Level
Upper Reference Point
Upper Null Zone
Disturbance
00809-XXXX-4811, Rev AA
February 2012
Figure 7-8. Upper Null Zone
PRELIMINARY
Rosemount 3308
To set the Upper Null Zone do one of the following:
1. Select the HART command [1, 3, 3, 1].
2. Enter the desired value,
or
1. Start the Radar Configuration Tool (RCT).
2. Click the Setup icon in the RCT workspace Project Bar.
3. Choose the Tank Config tab in the Setup window.
4. Click the Receive Page button.
5. Type the desired value in the Upper Null Zone field.
6. Click the Send Page button. Now the Upper Null Zone is stored in the
transmitter memory.
Figure 7-9. Identifying the Upper
Null Zone in the RCT Waveform
Plot
--
7-11
Page 92
Rosemount 3308
T2 is above the
Level peak
P1
P2
P3
T1
T2
T3
Amplitude
100
80
60
-60
40
-40
20
-20
0
100
50
0
150
200
250
Actual surface
Disturbing echo
misinterpreted as
product surface
PRELIMINARY
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
Amplitude Threshold
Settings
Figure 7-10. Example 1:
amplitude threshold T2 is too
high.
The amplitude thresholds are automatically adjusted to appropriate values in
order to filter out noise and other non-valid measurements from the
measurement signal.
The amplitude of the measurement signal, i.e. the amplitude of the signal that
is reflected by the product surface, is related to the actual dielectric constant
of the product. The amplitude threshold that is used by the transmitter is
based on the parameter configuration of the current product dielectric
constant (see Section 5: Basic Configuration). Normally no other threshold
adjustment is needed, but if the transmitter still does not track the product
surface correctly it may be necessary to adjust the threshold values.
The Radar Configuration Tool (RCT) has a plot function allowing you to view
the reflections along the probe.
If the amplitude threshold is too high the product level is not detected as
illustrated in Figure 7-10.
100
80
60
40
20
0
Amplitude
-20
-40
-60
-
T3
T2
T1
P1
-
250
200
150
100
50
0
Figure 7-11. Example 2:
amplitude threshold T2 is too
low.
7-12
If there are disturbing objects in the tan k the threshold must be carefully set in
order to avoid locking on the wrong amplitude peak. In Figure 7-11 the
transmitter has locked on a peak above the actual product surface, i.e. a
disturbance was interpreted as the product surface, whereas the actual
product surface was interpreted as an interface or the probe end.
Page 93
Reference Manual
After T2 is adjusted the product
surface is correctly detected
00809-XXXX-4811, Rev AA
February 2012
Figure 7-12. Waveform plot after
threshold T2 was adjusted
PRELIMINARY
Rosemount 3308
By adjusting the amplitude threshold T2 the product surface is detected
correctly as illustrated in Figure 7-12.
100
80
60
40
20
0
Amplitude
-20
-40
-60
T3
T1
P1
P2
T2
To adjust the amplitude thresholds select HART command [1, 4, 5, 3]
250
200
150
100
50
0
or
1. Start the Radar Configuration Tool (RCT).
2. Choose the Device Commands option from the View menu.
3. Open the Details folder.
4. Click the Set Nominal Thresholds option.
The thresholds T2 and T3 should be set to about 50% of the measured signal
amplitude for the product surface and the interface peaks, respectively.
NOTE
Amplitude thresholds should not be set to values less than 3.
NOTE
Check that the dielectric constant parameter setting is reasonably close to the
actual dielectric constant value of the upper product before changing the
amplitude thresholds.
NOTE
Default Amplitude thresholds can be set by typing 0 as th e ne w thr es hol d
value.
7-13
Page 94
Rosemount 3308
Start disk logging
Start monitoringCounterLog interval
PRELIMINARY
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
Logging Measurement
Data
To start logging do the following:
1. Click the Monitor icon in the RCT workspace or choose the Monitor
option from the View menu.
2. Choose the desired variables to be monitored and click the Start Monitor
button.
Saving the log to disk
1. Choose the desired variables to be monitored.
2. Click the Log interval button and enter a time interval. For example,
type 10 if you want data to be logged every tenth second.
3. Click the Counter button and enter the maximum number of files to be
stored. The Counter is used to limit the amount of data stored on the
hard disk. Each time the maximum number of entries in a log file is
reached, the current log file is saved and a new file is created. This
procedure continues up to the maximum number of files given by the
Counter value. The file size is limited to 60,000 entries which can easily
be handled by spreadsheet programs like MS Excel.
4. Select the desired options for Timer, Time and Date. By selecting a
check box the corresponding time indication is stored for each log entry
in the log file.
5. Click the Start disk logging button.
6. Choose a destination folder and enter a file name.
7-14
Page 95
Reference Manual
Save Setup
File name
00809-XXXX-4811, Rev AA
February 2012
PRELIMINARY
Rosemount 3308
Saving the Transmitter
Configuration
The Radar Configuration Tool offers different methods to save the current
transmitter configuration:
•Save only the configuration specified in the Setup window.
•Use the more extensive function in the Memory Map window.
You can use a stored configuration file as a backup of the current
configuration, or it can be distributed for service purposes.
To save the current transmitter setup do the following:
1. Click the Setup icon in the RCT workspace or choose the Setup option
from the View menu to open the Setup window.
2. Click the right mouse button and choose the Receive All option,
or
from the Setup menu choose the Receive All option.
Alternatively, you can use the Receive Page option on each individual
page.
NOTE!
All pages must be received before the setup can be saved.
3. Click the right mouse button and choose the Save Setup option.
4. Choose a destination folder and enter a file name.
5. Click the Save button.
7-15
Page 96
Rosemount 3308
Open Setup
PRELIMINARY
To load a setup
1. Click the Setup icon in the RCT workspace or choose the Setup option
from the File menu.
2. In the Setup window click the right mouse button and choose the Open Setup option, or
from the File menu choose the Open Setup option.
3. Open the source folder and select the desired setup file.
4. Click the Open button.
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
Memory Map
The Memory Map window lets you view the current transmitter database
registers. It is also possible to save the current database for backup or service
purposes, and it is also possible to download a backup database to the
transmitter. To save configuration data in the Memory Map window:
1. Start the RCT program.
2. Choose the View>Memory option, or click the Memory Map icon in the
RCT workspace (Advanced section at the left side of the worksp ace
window).
3. Choose the All EE option from the drop-down list.
4. Click the Receive button. (It may take a few minutes to read the
database).
5. Click the right mouse button and choose the Save Memory As option.
6. Type the desired file name and click the OK button. Now the current
database is stored.
See the Online Help in RCT for further information on how to open a saved
database and how to download a database to the transmitter.
7-16
Page 97
Reference Manual
Nut
Process Seal
Put the protection
plug here!
FLANGE VERSION
Nut
Process Seal
Adapter
THREADED VERSION
Put the protection
plug here!
00809-XXXX-4811, Rev AA
February 2012
Removing the
Transmitter Head
PRELIMINARY
Rosemount 3308
1. Loosen the nut that connects the
transmitter housing to the Process Seal.
2. Carefully lift the transmitter head.
3. Make sure that th e up pe r su rfa ce of th e
Process Seal is clean and the
spring-loaded pin at the center of the
Process Seal is properly inserted (the pin
should move back when pushed into the
hole).
4. Attach the protection plug to the Process
Seal.
NOTE
Do not remove the Process Seal from the
adapter!
7-17
Page 98
Rosemount 3308
Nut
Pr
o
b
e
Transmitter
head
Process
Seal
Changing the Probe
PRELIMINARY
Reference Manual
00809-XXXX-4811, Rev AA
February 2012
1. Loosen the nut.
2. Remove the transmitter head from the old probe.
3. On the new probe, make sure that the protection plug is removed and the
upper surface of the Process Seal is clean. Also make sure that the
spring-loaded pin at the center of the Process Seal is properly inserted.
4. Mount the transmitter head on the new probe.
5. Fasten the nut again.
6. If the new probe is not of the same type as the old one, update the
transmitter configuration by setting the Probe Type parameter to the
appropriate value:
HART Fast Key sequence [1, 3, 2, 3],
or
RCT Setup/Tank Config.
7. Measure the probe length and enter the measured value:
HART Fast Key sequence [1, 3, 2, 2],
or
RCT Setup/Tank Config.
8. Verify that the transmitter is calibrated.
7-18
Page 99
Reference Manual
PRELIMINARY
00809-XXXX-4811, Rev AA
February 2012
Rosemount 3308
DIAGNOSTIC
MESSAGES
TroubleshootingIf there is a malfunction despite the ab se nc e of dia g no stic mes sa ge s, se e
Table 7-1 for information on possible causes.
Table 7-1. Troubleshooting
chart
SymptomPossible causeAction
Both P2 and P3 are detected but Interface
Level is reported as Not A Number (NAN)
in the waveform plot.
Both Level and Interface Level are
reported as NAN.
Both P2 and P3 are detected but the
interface level is equal to the product
Level.
P2 is detected but Level is incorrectly
reported as Full or Empty.
The reference pulse is not detected.
Level accuracy seems off.
Integral display does not work.
Measurement Mode is set to “Level Only”. Set Measurement Mode to “Level and
Probe is not connected.Use the command “Read Gauge Status”
• P3 is identified as a double bounce.
• P2 and P3 are very close.
• The tank is full.
• The transmitter is configured with
wrong probe type.
• Amplitude Threshold T1 is not correct.
• Configuration error.• Check the Tank Height parameter.
Interface” (see “Basic Configuration” on
page 5-9).
and check if error “Probe Failure” is
active. If this is the case, check the probe
connection.
Adjust thresholds T2 and T3, see
“Amplitude Threshold Settings” on
page 7-12 for more information.
Use the command “Read Gauge Status”
and check if the warning “Probe
Immersed” is active. If this is the case
check that:
• the transmitter is configured with
correct probe type,
• the reference pulse (P1) is below
amplitude threshold T4. If not, adjust
T4 to an appropriate value.
• Check the product level.
• Check that correct probe type is
configured.
• Check Amplitude Threshold T1.
• Check status information and
diagnostic information.
• Check the display configuration.
• Check Display connection.
Table 7-2. Maintenance and Troubleshooting Suggestions
Poor wireless connectivity1. Verify device oriented for optimal connections (See Section 2: Transmitter Overview
of this document)
2. Verify wireless network best practices are followed (See Appendix C for more
information)
Acoustic Transmitter not joining network1. Verify the device has power
2. Verify the device is within effective communications range
3. Verify the proper Network ID has been entered into the device
4. See troubleshooting section of the Smart Wireless Gateway for more information
(Document No. 00808-0200-4420)
Limited Bandwidth Error1. Use the slowest acceptable update Rate
2. Increase communication paths by adding more wireless points
3. Check that the device has been online for at least an hour
4. Create a new network with an additional Smart Wireless Gateway
7-19
Page 100
PRELIMINARY
Error indication
Reference Manual
00809-XXXX-4811, Rev AA
Rosemount 3308
February 2012
ErrorsTable 7-3 is a list of diagnostic messages that may be displayed on the
Integral Display, on the Field Communicator, in AMS Suite or by the Radar
Configuration Tools (RCT) software. Errors normally result in Analog Output
alarm.
Errors are indicated in RCT by the message “Transmitter malfunction”:
To see the error message do one of the following:
•Click the Read Gauge Status icon in the toolbar at the top of the
RCT workspace.
•1. Open the Advanced section in the RCT workspace Project Bar and
click the Device Commands icon,
or
choose the Device Commands option from the View menu.
2. Open the folder named Diag and double-click the Read Gauge
Status option.
Table 7-3. Error messages.
Invalid configuration.
LCD error code: CNFIG.
RAM failure was detected
during startup test.
LCD error code: 00001.
EEprom user checksum error.
LCD error code: 00008.
Software error.
LCD error code: 00010.
Probe failure.
LCD error code: 00013.
MessageDescriptionAction
At least one configuration parameter
is outside allowed range.
NOTE: the default values are used
until the problem is solved.
The transmitter performs an
immediate reset.
The transmitter performs an
immediate reset.
This error is probably caused by
hardware failure.
Checksum error in the factory
configuration parameters. Can be
caused by power failure during
configuration or by hardware error.
NOTE: the default values are used
until the problem is solved.
Caused by error in the User
Configuration parameters. Can be
caused by power failure during
configuration or by hardware error.
NOTE: the default values are used
until the problem is solved
Contact Rosemount service
Probe is not detected.Check that the probe is correctly
• Load default database and restart
the transmitter.
• Cont act Emerson customer service
if the problem persists.
Contact Rosemount service
department.
Contact Rosemount service
department.
Contact Rosemount service
department.
Contact Rosemount service
department.
• Load default database and restart
the transmitter.
• Cont act Emerson customer service
if the problem persists.
department.
mounted (see “Changing the Probe”
on page 7-18).
7-20
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.