Rosemount 2160 Operating Manual

Reference Manual
00809-0100-4160, Rev AD January 2013
Rosemount 2160 Wireless
Vibrating Fork Liquid Level Switch
www.rosemount.com
Reference Manual
NOTICE
00809-0100-4160, Rev AD January 2013
Rosemount 2160
Rosemount 2160 Wireless Vibrating Fork Liquid Level Switch
Rosemount 2160 Hardware Revision 2
®
Device Revision 2
HART Field Communicator Field Device Dev v1, DD v2
Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product.
For technical assistance, contacts are listed below:
Customer Central
Technical support, quoting, and order-related questions. United States: 1 800 999 9307 (7:00 am to 7:00 pm CST) Asia Pacific: 65 777 8211 Europe/ Middle East/ Africa: 49 (8153) 9390
North American Response Center
Equipment service needs. 1 800 654 7768 (24 hours—includes Canada) Outside of these areas, contact your local Emerson Process Management representative.
The products described in this document are NOT designed for nuclear-qualified applications.
Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact an Emerson Process Management Sales Representative.
Replacement equipment or spare parts not approved by Emerson for use as spare parts could reduce the capabilities of the 2160, and may render the instrument dangerous.
• Use spare parts supplied or sold by Emerson
www.rosemount.com
Rosemount 2160
NOTICE
Reference Manual
00809-0100-4160, Rev AD
January 2013
Failure to follow these installation guidelines could result in death or serious injury
• The Rosemount 2160 is a wireless liquid level switch. It must be installed, connected, commissioned, operated, and maintained by suitably qualified personnel only , observing any national and local requirements that may apply
• Use the equipment only as specified in this manual. Failure to do so may impair the protection provided by the equipment
Explosions could result in death or serious injury
• Installation of the 2160 in a hazardous environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the approvals section of the 2160 Reference Manual for any restrictions associated with an installation
• Before connecting a Field Communicator in an explosive atmosphere, ensure the installation is in accordance with intrinsically safe or non-incendive field wiring practices
• Verify that the operating atmosphere of the level switch is consistent with the appropriate hazardous locations certifications
External Surface may be hot
• Care must be taken to avoid possible burns
Process leaks could result in death or serious injury
• Install and tighten process connectors before applying pressure
• Do not attempt to loosen or remove process connectors while the 2160 is in service
Electrical shock could cause death or serious injury
• If the liquid level switch is installed in a high voltage environment and a fault condition or installation error occurs, high voltage may be present on leads and terminals
• Use extreme caution when making contact with the leads and terminals
• Make sure that power to the 2160 is off while making connections
Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Shipping considerations for wireless products:
The unit was shipped to you without the Black Power Module installed. Please remove the power module prior to shipping.
Each power module contains two “C” size primary lithium batteries. These batteries are regulated in transportation by the U. S. Department of Transportation, and are also covered by IATA (International Air Transport Association), ICAO (International Civil Aviation Organization), and ARD (European Ground Transportation of Dangerous Goods). It is the responsibility of the shipper to ensure compliance with these or any other local requirements. Please consult current regulations and requirements before shipping.
The power module with the wireless unit contains two “C” size primary lithium/thionyl chloride batteries. Each battery contains approximately 2.5 grams of lithium, for a total of 5 grams in each pack. Under normal conditions, the battery materials are self-contained and are not reactive as long as the batteries and the pack integrity are maintained. Care should be taken to prevent thermal, electrical or mechanical damage. Contacts should be protected to prevent premature discharge.
Battery hazards remain when cells are discharged. Batteries should be stored in a clean and dry area. For maximum battery life, storage temperature
should not exceed 86 °F (30 °C).
II
Reference Manual
00809-0100-4160, Rev AD January 2013
Rosemount 2160

Table Of Contents

SECTION 1 OVERVIEW
SECTION 2 CONFIGURATION
Safety Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-1
Warnings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-1
Using This Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-2
Definitions And Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-2
Models Covered. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
About the 2160 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3
Switch Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3
Measurement Principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Short Fork Technology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-4
Special Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Rosemount 2160 Application Examples . . . . . . . . . . . . . . . . . . . . . . . .1-5
Extended Fork Supports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Switchpoint . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-7
Service Support. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-9
Product Recycling/Disposal. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-9
Safety Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1
Warnings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Required Bench Top Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-2
Squawk Feature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
AMS Wireless Configurator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-2
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-2
Field Communicator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-4
Menu Tree. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Device Network Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-7
Join to Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-7
Configure Update Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-7
Operation Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-7
Remove Black Power Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-7
Review Configuration Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-8
Review Device Identification Information . . . . . . . . . . . . . . . . . . . . . . . 2-8
Review Radio Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Check Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-9
Temperature Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-9
Operation Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-9
Sensor Output Delay. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
Media Density . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-10
Write Protect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-10
Data Logging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
LCD Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
LCD Display Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
Detailed Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-12
Configure Alerts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-12
Sensor Stabilization Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-13
Measurement Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-13
Allowable Change In Dry Fork Frequency. . . . . . . . . . . . . . . . . . . . . .2-13
III
Rosemount 2160
Reference Manual
00809-0100-4160, Rev AD
January 2013
Sensor Fault Delay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Power Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Power Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Diagnostics and Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-15
Load User Defaults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-15
Join Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-16
Communication Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-16
Join Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-16
Available Neighbors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-17
Advertisements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-17
Join Attempts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-17
Sensor Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-17
Temperature Compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18
Uncompensated Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-18
Sensor State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-18
Dry Fork Frequency / Switch Points . . . . . . . . . . . . . . . . . . . . . . . . . . 2-19
Sensor State . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-19
Counters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-20
Timers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-21
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-21
Dry Fork Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-21
Sensor Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-21
Calibrate Dry Fork. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-22
Sensor Calibration Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-22
Calibration Count . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-22
Reset Calibration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-22
Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-23
Sensor Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-23
Fork Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-23
Advanced Functions for HART Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . 2-24
Saving, Recalling, and Cloning Configuration Data . . . . . . . . . . . . . .2-24
SECTION 3 INSTALLATION
IV
Safety Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-1
Warnings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-1
Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-2
General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-2
Wireless Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-2
Environmental Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-2
Installation Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-3
Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-6
Battery Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Installing the LCD Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-7
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-8
Correct Fork Alignment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Tightening the 2160 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Insulation (2160***E Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
Operations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-12
Reference Manual
00809-0100-4160, Rev AD January 2013
Rosemount 2160
SECTION 4 COMMISSIONING
SECTION 5 OPERATION AND MAINTENANCE
APPENDIX A SPECIFICATIONS AND REFERENCE DATA
Safety Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-1
Warnings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-1
Verify Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-2
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Local Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-2
Smart Wireless Gateway. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-3
AMS Wireless Configurator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-4
How to Use Squawk . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-4
Safety Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-1
Warnings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-1
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-2
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-2
LCD Screen Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-3
Startup Screen Sequence. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-3
Diagnostic Button Screen Sequence . . . . . . . . . . . . . . . . . . . . . . . . . .5-4
Network Diagnostic Status Screens . . . . . . . . . . . . . . . . . . . . . . . . . . .5-5
Device Diagnostic Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7
Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-10
Power Module Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-10
Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-1
Physical. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-1
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-1
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-3
Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-3
Functional . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-3
Dimensional Drawings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-6
2160 Thread Mounting (Standard Length) . . . . . . . . . . . . . . . . . . . . . .A-6
2160 Thread Mounting (Extended Length) . . . . . . . . . . . . . . . . . . . . . .A-7
2160 Flange Mounting (Standard Length) . . . . . . . . . . . . . . . . . . . . . .A-8
2160 Flange Mounting (Extended Length) . . . . . . . . . . . . . . . . . . . . . .A-9
2160 Hygienic Fitting (Standard Length). . . . . . . . . . . . . . . . . . . . . . .A-10
2160 Hygienic Fitting (Extended Length) . . . . . . . . . . . . . . . . . . . . . .A-12
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-13
Spare Parts and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .A-15
APPENDIX B PRODUCT CERTIFICATIONS
European Directive Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-1
Telecommunication Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-1
FCC and IC Approvals. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-1
Canadian Registration Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-2
Hazardous Locations Certifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-2
American and Canadian Approvals. . . . . . . . . . . . . . . . . . . . . . . . . . . .B-2
European Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-2
Rest Of The World Approvals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .B-3
V
Rosemount 2160
Reference Manual
00809-0100-4160, Rev AD
January 2013
VI
Reference Manual
00809-0100-4160, Rev AD January 2013
Rosemount 2160

Section 1 Overview

Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1
Using This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-2
Definitions And Abbreviations . . . . . . . . . . . . . . . . . . . . . page 1-2
Models Covered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-2
About the 2160 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-3
Service Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-9
Product Recycling/Disposal . . . . . . . . . . . . . . . . . . . . . . .page 1-9

SAFETY MESSAGES Procedures and instructions in this manual may require special precautions to

ensure the safety of the personnel performing the operations. Infor mation that raises potential safety issues is indicated by a caution symbol ( ). The external hot surface symbol ( ) is used when a surface is hot and care must be taken to avoid possible burns. If there is a risk of an electrical shock the ( ) symbol is used. Refer to the safety messages listed at th e be gin n ing of each section before performing an operation preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or serious injury
• The Rosemount 2160 is a wireless liquid level switch. It must be installed, connected, commissioned, operated, and maintained by suitably qualified personnel only , observing any national and local requirements that may apply
• Use the equipment only as specified in this manual. Failure to do so may impair the protection provided by the equipment
Explosions could result in death or serious injury
• Installation of the 2160 in a hazardous environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the approvals section of the 2160 Reference Manual for any restrictions associated with an installation
• Before connecting a Field Communicator in an explosive atmosphere, ensure the installation is in accordance with intrinsically safe or non-incendive field wiring practices
• Verify that the operating atmosphere of the level switch is consistent with the appropriate hazardous locations certifications
External Surface may be hot
• Care must be taken to avoid possible burns
Process leaks could result in death or serious injury
• Install and tighten process connectors before applying pressure
• Do not attempt to loosen or remove process connectors while the 2160 is in service
Electrical shock could cause death or serious injury
• If the liquid level switch is installed in a high voltage environment and a fault condition or installation error occurs, high voltage may be present on leads and terminals
• Use extreme caution when making contact with the leads and terminals
• Make sure that power to the 2160 is off while making connections
www.rosemount.com
Reference Manual
00809-0100-4160, Rev AD
Rosemount 2160
January 2013

USING THIS MANUAL This manual provides information on installing, operating, and maintaining the

Rosemount 2160 Wireless liquid level switch.
Section 2: Configuration provides instruction on commissioning and operating the Rosemount 2160. Information on software functions, configuration parameters, and online variables is also included.
Section 3: Installation contains mechanical and electrical installation instructions.
Section 4: Commissioning contains techniques for properly commissioning the device.
Section 5: Operation and Maintenance contains operation and maintenance techniques.
Appendix A: Specifications and Reference Data supplies reference and specification data, as well as ordering information.
Appendix B: Product Certifications contains approval information.

DEFINITIONS AND ABBREVIATIONS

The following definitions are used in this manual:
Dry The 2160 fork (sensor) is submerged to a depth of less than 0.5 in. (13 mm) Wet The 2160 fork (sensor) is submerged to a depth of greater than 0.5 in. (13 mm) Fault The fork frequency is outside the normal frequency band Normal
Mode Enhanced
Mode
The operating mode in which the 2160 considers a 0 Hz fork frequency to represent a Wet condition (and not a Fault)
The operating mode in which the 2160 considers a 0 Hz fork frequency to represent a fault condition
The following abbreviations are used in this manual:
DD Device Description IS Intrinsically Safe PV Primary Value or Process Value SV Secondary Value TV Tertiary Value (Third Value) QV Quaternary Value (Fourth Value)

MODELS COVERED The following models of the Rosemount 2160 Wireless liquid level switch are

covered in this manual:
The standard temperature 2160***S
The extreme temperature 2160***E
1-2
Reference Manual
Wetted Materials in 316/316L SST (1.4401/1.4404), or Alloy C (UNS N10002) and Alloy C-276 (UNS N10276)
NEMA Type 4X (IP66) Housing in Aluminum. Removable Covers on Both Sides
Short Fork Length with Extensions up to 118 in. (3 m)
Threaded, Flanged, or Hygienic Connections
Thermal Tube (2160***E Only)
Fast Drip Design
ATEX, FM, CSA, IECEx, and NEPSI Intrinsically Safe
Antenna
Optional LCD Display
00809-0100-4160, Rev AD January 2013
Rosemount 2160
ABOUT THE 2160 Switch Overview The Rosemount 2160 Wireless is a wireless liquid point level switch.
Based on vibrating short fork technology, the 2160 is suitable for virtually all liquid applications:
Vir tually unaf fected by flow, bubbles, turbulence, foam, vibration, solids content, coating, properties of the liquid, and product variations
Operation in extreme temperatures of –94 to 500 °F (–70 to 260 °C)
No need for calibration and requires minimum installation procedures
No moving p arts or crevices means virtually no maintenance
Electronic self-checking and condition monitoring
Programmable switching delay for turbulent or splashing applications
Short fork length with extensions up to 118 in. (3 m)
“Fast Drip” fork design gives quick response time
General area and Intrinsically Safe options
This combination of features makes the 2160 an ideal choice for a wide variety of challenging applications in the chemical, power generation, and oil and gas industries.
Figure 1-1. Features of the 2160
1-3
Reference Manual
00809-0100-4160, Rev AD
Rosemount 2160
January 2013
Measurement Principle The Rosemount 2160 is designed using the principle of a tuning fork.
A piezo-electric crystal oscillates the forks at their natural frequency . Changes to this frequency are continuously monitored.
The frequency of the vibrating fork sensor changes depending on the medium in which it is immersed. The denser the liquid, the lower the frequency.
When used as a low level alarm, the liquid in the tank or pipe drains down past the fork, causing a change of natural frequency that is detected by the electronics and switches the output state to a Dry condition.
When the 2160 switch is used as a high level alarm, the liquid rises in the tank or pipe making contact with the fork, causing the output state to switch to a Wet condition.
The output state, along with other parameters , are regularly transmitted over a secure wireless connection to a Smart Wireless Gateway.
Short Fork Technology The natural frequency (~1400Hz) of the fork avoids interference from plant
vibration that may cause false switching. This allows for minimum intrusion into the tank or pipe through the use of a short fork.
Using Short Fork Technology, the Rosemount 2160 can be used in almost all liquid applications. Extensive research has maximized the operational effectiveness of the fork design, making it suitable for most liquids including coating liquids, aerated liquids, and slurries.
Special Features Instrument Health Monitor and Continuous Self-Check
The 2160 continuously performs instrument health diagnostics to self-check the condition of the fork and sensor. These diagnostics can detect damage to the forks including corrosion, internal or external damage to the forks, and breakages to the internal wiring.
See “Operation Mode” on page 2-9 for further information.
Fork Design
The “fast drip” fork design draws liquid away from the fork tips, and together with a short switching delay , allows the 2160 to react quickly and with greater sensitivity to density variations.
Battery Powered
The 2160 is powered by an integral battery. The fork sensor requires very little power and the battery life remains long even with fast update rates.
See “Battery Installation” on page 3-6 for further information.
Adjustable Time Delay
There is also a user-selectable time de lay to virtually eliminate the risk of false switching in turbulent or splashing applications.
See “Sensor Output Delay” on page 2-10 for further information.
1-4
Reference Manual
00809-0100-4160, Rev AD January 2013
Rosemount 2160
Rosemount 2160 Application Examples
For most liquids, including coating, aerated liquids and slurries, the fun ction is virtually unaffected by flow, turbulence, bubbles, foam, vibration, solid particles, build-up, or properties of the liquid.
See Figure 1-5 on page 1-8 for application examples. The 2160 switch can be used in hazardous (IS) or non-hazardous (safe)
areas but supports higher process temperatures up to 500 °F (260 °C). The switch can be mounted in almost any position in an open or closed tank
or pipe. There is a wide range of threaded, flanged, or hygienic connections.
Application Considerations:
Ensure the process is operating within the instrument op er a ting temperature and pressure ranges (see “Specifications” on page A-1)
Ensure the liquid viscosity is within the recommended viscosity range (see “Specifications” on page A-1)
Check that the liquid density is higher than 31.2 lb/ft (see “Specifications” on page A-1)
Check for risk of build-up on the forks Avoid situations where drying and coating products may create
excessive build-up (see Figure 1-2)
Ensure there is no risk of ‘bridging’ the forks Examples of products that can create bridgin g of forks are dense p aper
slurries and bitumen
Check the solids content in the liquid
3
(500 kg/m3)
Figure 1-2. Avoid Product Build-up
As a guideline, the maximum solid particle diameter in the liquid is
0.2 in. (5 mm). Extra consideration is needed when dealing with particles bigger than 0.2 in. (5 mm). Consult the factory for advice.
Problems may occur if product coats and dries causing caking.
In almost all cases, the 2160 is insensitive to foams (i.e. does not see the foam).
However in rare occasions, some very dense foams may be seen as liquid; a known example of this is found in ice-cream and orange juice manufacturing.
OK
1-5
Rosemount 2160
3.28 ft. (1.0 m)
3.28 ft. (1.0 m)
3.28 ft. (1.0 m)
3.28 ft. (1.0 m)
Maximum
3.28 ft.
(1.0 m)
Maximum
3.28 ft. (1.0 m)
Extended Fork Supports
Figure 1-3. Supports Needed for Extended Forks
OK
Reference Manual
00809-0100-4160, Rev AD
January 2013
OK
OK
OK
1-6
Reference Manual
SP = Switchpoint (H20) HY = Switching Hysteresis
±0.039 in.
(1 mm)
±0.5 in.
(13 mm)
±0.5 in.
(13 mm)
00809-0100-4160, Rev AD January 2013
Switchpoint
Figure 1-4. Switchpoint
Rosemount 2160
SP
HY
SP
NOTE:
A lower density media will give a switchpoint closer to the connection. A higher density media will give a switchpoint closer to the fork tip.
1-7
Rosemount 2160
Figure 1-5. Rosemount 2160 Application Examples
Overfill Protection
Spillage caused by overfilling can be hazardous to people and the environment, resulting in lost product and potentially high clean up costs.
High and Low Level Alarm
Maximum and minimum level detection in tanks containing different types of liquids are ideal applications. The Rosemount 2160 is robust and operates continuously across the temperature range of –94 to 500 °F (–70 to 260 °C) and operating p ressures of up to 1450 psig (100 barg), making it perfect for use as a high or low level alarm. It is common practice to have an independent high level alarm switch as a backup to an installed level device in case of primary failure.
Reference Manual
00809-0100-4160, Rev AD
January 2013
Pump Control (Limit Detection)
Batch processing tanks often contain stirrers and agitators to ensure mixing and product ‘fluidity’. The standard user-selectable time delay, from 0 to 3600 seconds, virtually eliminates the risk of false switching from splashing.
Pump Protection or Empty Pipe Detection
With the fork projecting only 2 in. (50 mm) (dependant on connection type), the 2160 can be installed in small diameter pipes. Short forks mean minimum intrusion on the wetside and allow for simple, low cost installation at any angle into pipes or tanks. The 2160 is ideal for reliable pump control and can be used to protect against pumps running dry.
Extreme Temperature Applications
The 2160***E is designed for extreme temperatures and is suitable for continuous operation within the temperature range of –94 to 500 °F (–70 to 260 °C).
Hygienic Applications
With the highly polished forks option providing a surface finish (Ra) better than 0.4 µm, the 2160 meets the most stringent hygienic requirements used in food and beverage, and pharmaceutical applications.
1-8
Reference Manual
NOTICE
00809-0100-4160, Rev AD January 2013
Rosemount 2160

SERVICE SUPPORT To expedite the return process outside of North America, contact the nearest

Emerson Process Management representative. Within the United States, call the Emerson Process Management Response
Center toll-free number 1 800 654 7768. This center, available 24 hours a day, will assist you with any needed information or materials.
The center will ask for product model and serial numbers, and will provide a Return Material Authorization (RMA) number. The center will also ask for the process material to which the product was last exposed.
Individuals who handle products exposed to a hazardous substance can avoid injury if they are informed of, and understand, the hazard. If the product being returned was exposed to a hazardous substance as defined by OSHA, a copy of the required Material Safety Data Sheet (MSDS) for each hazardous substance identified must be included with the returned goods.

PRODUCT RECYCLING/DISPOSAL

Shipping considerations for wireless products (lithium batteries):
The unit was shipped to you without the power module installed. Please remove the power module prior to shipping.
Primary lithium batteries (charged or discharged) are regulated in transportation by the U. S. Department of Transportation. They are also covered by IATA (International Air Transport Association), ICAO (International Civil Aviation Organization), and ARD (European Ground Transportation of Dangerous Goods). It is the responsibility of the shipper to ensure compliance with these or any other local requirements. Please consult current regulations and requirements before shipping.
Recycling of equipment and packaging should be taken into consideration and disposed of in accordance with local and national legislation/regulations.
1-9
Rosemount 2160
Reference Manual
00809-0100-4160, Rev AD
January 2013
1-10
Reference Manual
00809-0100-4160, Rev AD January 2013

Section 2 Configuration

Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 2-2
Required Bench Top Configuration . . . . . . . . . . . . . . . . .page 2-2
Device Network Configuration . . . . . . . . . . . . . . . . . . . . . page 2-7
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-4
Review Configuration Data . . . . . . . . . . . . . . . . . . . . . . . . page 2-8
Check Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-9
Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 2-9
LCD Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 2-11
Detailed Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 2-12
Diagnostics and Service . . . . . . . . . . . . . . . . . . . . . . . . . .page 2-15
Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-21
Simulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-23
Advanced Functions for HART Protocol . . . . . . . . . . . . .page 2-24
Rosemount 2160

SAFETY MESSAGES Procedures and instructions in this section may require special precautions to

ensure the safety of the personnel performing the operations. Infor mation that raises potential safety issues is indicated by a warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.
Warnings
Failure to follow these installation guidelines could result in death or serious injury
• The Rosemount 2160 is a wireless liquid level switch. It must be installed, connected, commissioned, operated, and maintained by suitably qualified personnel only, observing any national and local requirements that may apply
• Use the equipment only as specified in this manual. Failure to do so may impair the protection provided by the equipment
Explosions could result in death or serious injury
• Installation of the 2160 in a hazardous environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the approvals section of the 2160 Reference Manual for any restrictions associated with an installation
• Before connecting a Field Communicator in an explosive atmosphere, ensure the installation is in accordance with intrinsically safe or non-incendive field wiring practices
• Verify that the operating atmosphere of the level switch is consistent with the appropriate hazardous locations certifications
External Surface may be hot
• Care must be taken to avoid possible burns
Process leaks could result in death or serious injury
• Install and tighten process connectors before applying pressure
• Do not attempt to loosen or remove process connectors while the 2160 is in service
www.rosemount.com
Reference Manual
00809-0100-4160, Rev AD
Rosemount 2160
Electrical shock could cause death or serious injury
• If the liquid level switch is installed in a high voltage environment and a fault condition or installation error occurs, high voltage may be present on leads and terminals
• Use extreme caution when making contact with the leads and terminals
• Make sure that power to the 2160 is off while making connections
January 2013

OVERVIEW This section contains information on commissioning and verification that

should be performed prior to installation. Field Communicator and AMS
functions. For convenience, Field Communicator fast key sequences are labeled “Fast Keys” for each software function below the appropriate headings.
Example Software Function
Fast Keys
1, 2, 3, etc.
®
instructions are given to perform configuration

REQUIRED BENCH TOP CONFIGURATION

Bench top configuration requires a Field Communicator, AMS, or any Wireless Communicator.
Bench top configuration consists of testing the transmitter and verifying transmitter configuration data. The 2160 can be configured before or after installation (field hook-up). However, configuring the 2160 on the bench before installation ensures that all network settings are working correctly.
When using a Field Communicator , any configuration ch anges made must be sent to the 2160 by using the “Send” key (F2). AMS configuration changes are implemented when the “Apply” button is clicked.
Squawk Feature The 2160 feature called “Squawk” can be used to visually identify an
individual 2160 in a wireless network. This can be a useful check during the configuration and commissioning of multiple 2160 transmitters.
To find out more about this feature, see “How to Use Squawk” on page 4-4.
AMS Wireless Configurator
AMS is capable of connecting to devices either directly using a HART® modem or wirelessly via the Smart Wireless Gateway.
When configuring on the bench with a HART modem, double click the device icon, then choose the Configure/Setup tab (or right click and select Configure/Setup).
When configuring with the Gateway, dou ble click the device icon and then choose the Configure/Setup tab (or right click and select Configure/Setup).
Field Communicator Remove the power mod ule-side housing cover to expose the terminal block
and HART communication terminals, then connect the Black Power Module to power the unit for configuration. Connect the Field Communicator leads to the terminals labeled “COMM” on the terminal block. See Figure 2-1 on page 2-3. Turn on the Field Communicator by pre ssing the ON/OFF key.
2-2
Reference Manual
COMM
P/N 00753-9200-0010
00809-0100-4160, Rev AD January 2013
Figure 2-1. Field Communicator Connection
Rosemount 2160
The Field Communicator will search for a HART-compatible device and indicate when the connection is made. If the Field Communicator fails to connect, it indicates that no device was found and you should re-check the connections.
NOTE
Before connecting a Field Communicator in an explosive atmosphere, make sure the instruments are installed in accordance with intrinsically safe or non-incendive field wiring practices.
P/N 00753-9200-0010
COMM
P/N 00753-9200-0010
COMM
A 2160 DD (Device Description) is required for HART communication. To obtain the latest DD, visit the Emerson Process Management Easy Upgrade Site at:
http://www2.emersonprocess.com/en-US/documentation/deviceinstallkits
2-3
Rosemount 2160
FIELD COMMUNICATOR Field Communicator Menu Tree
Reference Manual
00809-0100-4160, Rev AD
January 2013
1. Overview
2. Configure
3. Service Tools
1. Device Status 1. Identification
2. Comm Status 2. Revisions
3. PV – 1.0=Wet/0.0=Dry
4. PV Status 4. Security
5. Update Rate
6. Device information
1. Guided Setup
2. Manual Setup
3. Alert Setup
3. Radio
1. Basic Setup
2. Join to Network
3. Configure Update Rate (*1)
4. Configure Device Display
5. Configure Alerts
1. Wireless
2. Operation
3. Display
4. Data Logging
5. Security
6. Device Temperature
7. Device Information
8. Power
1. Alert 1
2. Alert 2
3. Alert 3
4. Alert 4
See Page 2-7
1. Device Image
2. Tag
3. Long Tag
4. Model
5. Serial Number
6. Device ID
7. Date
8. Descriptor
9. Message
10. Model number I
11. Model number II
1. HART
2. Field Device
3. Software
4. Hardware
5. DD
1. Manufacture
2. Device Type
3. Device Revision
4. Software Revision
5. Hardware Revision
6. Transmit Pwr. Lvl
7. Min Brdcst Updt Rt
1. Write Protect
2. Over The Air Upgrade
1. Network ID
2. Join To Network
3. Broadcast Info
1. Application
2. Sensor
1. Display Mode
2. Display Item
1. Meas Status Log
2. Primary Variable, PV
3. 2nd Variable, SV
4. 3rd Variable, TV
5. 4th Variable, QV
6. Configure Data Hist
1. Write Protect
2. Over The Air Upgrade
1. Electronics Temp
2. Elect Temp Status
3. Unit
4. Maximum
5. Minimum
1. Tag
2. Long Tag
3. Descriptor
4. Message
5. Date
6. Country
7. SI Unit Control
1. Power Mode
2. Power Source
1. Configure Alert 1
2. Mode
3. Variable
4. Direction
5. Limit
6. Band
1. Configure Alert 2
2. Mode
3. Variable
4. Direction
5. Limit
6. Band
1. Config Adv Brdcsg
2. Message 1 Content (*2)
3. Message 2 Content (*2)
4. Message 3 Content (*2)
(*1) Config Adv Brdcsg will be displayed if Advanced Broadcasting is enabled; same menus as under Configure - Manual Setup - Wireless - Broadcast Info.
(*2) Only visible if Bursting message is enabled.
1. Operation Mode
2. Sensor Output Delay
3. Media Density
1. Sensor Stabilization Time
2. Measurement Time
3. Allowable Change in Dry Fork Frequency
4. Sensor Fault Delay
1. Configure Alert 3
2. Mode
3. Variable
4. Direction
5. Limit
6. Band
1. Configure Alert 4
2. Mode
3. Variable
4. Direction
5. Limit
6. Band
A
See next page
2-4
1. Configure Message 1
2. Configure Message 2
3. Configure Message 3
4. Event Notification
5. Disable Advanced Broadcasting
A
1. Broadcast Configuration
2. Update Rate
1. Enable Burst Msg 1
2. Message 1 Content
3. First & Trigger Var (*3)
4. 2nd Variable (*3)
5. 3rd Variable (*3)
6. 4th Variable (*3)
7. 5th Variable (*4)
8. 6th Variable (*4)
9. 7th Variable (*4)
10. 8th Variable (*4)
1. Trigger Mode
2. Trigger Level (*3)
3. First & Trigger Var (*3)
4. Update Rate
5. Default Update Rate
1. Trigger Mode
2. Trigger Level (*3)
3. First & Trigger Var (*3)
4. Update Rate
5. Default Update Rate
1. Broadcast Configuration
2. Update Rate
1. Enable Burst Msg 2
2. Message 2 Content
3. First & Trigger Var (*3)
4. 2nd Variable (*3)
5. 3rd Variable (*3)
6. 4th Variable (*3)
7. 5th Variable (*4)
8. 6th Variable (*4)
9. 7th Variable (*4)
10. 8th Variable (*4)
1. Trigger Mode
2. Trigger Level (*3)
3. First & Trigger Var (*3)
4. Update Rate
5. Default Update Rate
1. Broadcast Configuration
2. Update Rate
1. Enable Burst Msg 3
2. Message 3 Content
3. First & Trigger Var (*3)
4. 2nd Variable (*3)
5. 3rd Variable (*3)
6. 4th Variable (*3)
7. 5th Variable (*4)
8. 6th Variable (*4)
9. 7th Variable (*4)
10. 8th Variable (*4)
(*3) Only visible if Message Content is “Selectable Process Variables/Status” or “Selectable Process Variables”.
(*4) Only visible if Message Content is “Selectable Process Variables/Status”.
1. Refresh Following Info
2. Failed
3. Maintenance
4. Advisory
5. Event Notification
From previous page
Reference Manual
00809-0100-4160, Rev AD January 2013
Field communicator menu tree continued...
Rosemount 2160
2-5
Rosemount 2160
Field communicator menu tree continued...
Reference Manual
00809-0100-4160, Rev AD
January 2013
1. Overview
2. Configure
3. Service Tools
(*1) Only visible when there is a history.
(*2) Only one option is visible and it is dependent on whether Factory Calibration or Site Calibration has been selected.
(*3) Only visible when data logging is enabled.
See Page 2-5
See Page 2-5
1. Alerts
2. Variables
3. Trends
4. Communications
5. Maintenance
6. Simulate
1. Refresh Alerts
2. No Active Alerts
3. History
1. PV – 1.0=Wet/0.0=Dry
2. PV Status
3. Sensor Frequency
4. Sensor Frequency Status
5. Electronics Temp
6. Electronics Temp Status
7. Supply Voltage
8. Supply Voltage Status
9. Last Update Time
1. Output State
2. Sensor Frequency
3. Electronics Temp
4. Supply Voltage
5. Data History
1. Join Status
2. Comm Status
3. Join Mode
4. Available Neighbors
5. Advertisements
6. Join Attempts
1. Diagnostics
2. Counters / Timers
3. Calibrate
4. Routine Maintenance
5. Reset / Restore
1. Output State
2. Sensor Frequency
3. Electronics Temperature
4. Supply Voltage
1. Clear Alert History
2. View Alert History (*1)
1. Device Variable
2. Variable Units
3. Sample Inteval
4. Time of First Value
5. Date of First Value
6. View Data History (*3)
7. Refresh (*3)
1. Sensor
2. Dry Fork Frequency / Switch Points
1. Counters
2. Timers
1. Sensor Calibration
2. Reset Sensor Calibration
3. Sensor Compensation
1. Locate Device
2. Install New Power Module
1. Device Reset
2. Load User Defaults
1. Sensor Frequency
2. Temperature Compensation
3. Uncompensated Frequency
4. Sensor State
5. Sensor Status
1. Dry Fork Frequency
2. Dry to Too Dry
3. Dry to Indeterminate
4. Wet to Indeterminate
5. Wet to Too Wet
6. Zero
1. Sensor Wet Count
2. Reset/Preset Wet Count
3. Calibration Count
4. Fault Control
5. Reset Fault Count
1. Time Since Output Change
2. Total Time Dry
3. Total Time Wet
1. Dry Fork Frequency
2. Sensor Frequency
3. Calibrate Dry Fork
4. Sensor Calibration Status
5. Calibration Count
1. Restore Factory Calibration
2. Restore Site Calibration
1. Calibration Temperature
2. Temperature Compensation
3. Process Temperature
(*2)
2-6
Reference Manual
00809-0100-4160, Rev AD January 2013
Rosemount 2160

DEVICE NETWORK CONFIGURATION

Join to Network To communicate with the Smart Wireless Gateway, and ultimately the
Fast Keys
2, 1, 2
Information System, the 2160 must be configured to communicate with the wireless network. This step is the wireless equivalent of connecting wires from a transmitter to the host system.
1. From the Home screen, select 2: Configure.
2. Select 1: Guided Setup.
3. Select 1: Join to Network.
Using AMS or a Field Communicator, enter the Network ID and Join Key so they match the Network ID and Join Key of the Gateway and the other devices in the network. If the Network ID and Join Key are not identical, the 2160 will not communicate with the network.
When using a Field Communicator, the Network ID can be configured by entering Fast Key sequence: 2, 2, 1, 1. The Join Key can also be configured using a Field Communicator with the Fast Key sequence: 2, 2, 1, 2.
NOTE
The Network ID and Join Key may be obtained from the
Setup>Network>Settings page on the Gateway’s web server.
Configure Update Rate The final device network configuration piece is the Update Rate which, by
Fast Keys
2, 2, 3
default, is 1 minute. It can be changed at commissioning, or at any time, by using AMS or the Gateway’s web server. The Update Rate should be between 1 second and 60 minutes.
1. From the Home screen, select 2: Configure.
2. Select 1: Guided Setup.
3. Select 3: Configure Update Rate.
Operation Mode To view or cha nge th e op er ation mode:
Fast Keys
2, 2, 2, 1, 1
1. From the Home screen, select 2: Configure.
2. Select 2: Manual Setup.
3. Select 2: Operation.
4. Select 1: Application.
5. Select 1: Operation Mode.
The default operating mode is Normal Mode. Other options are Enhanced Operation Mode (Fault=Wet) or Enhanced Operation Mode (Fault=Dry).
Remove Black Power Module
After the bench top and network device configuration is completed, you can remove the Black Power Module and replace the housing cover. The Black Power Module should be inserted only when the device is ready to be installed.
Use caution when handling the Black Power Module. The Black Power Module may be damaged if dropped from heights in excess of 20 ft. (6,1 m).
When the device is installed, re-insert the Black Power Module and close the housing cover securely. Always ensure a proper seal but do not over tighten.
2-7
Rosemount 2160
Reference Manual
00809-0100-4160, Rev AD
January 2013

REVIEW CONFIGURATION DATA

Review Device Identification Information
Fast Keys
1, 6, 1, 3
The following is a list of factory default configurations that can be viewed by using the Field Communicator or AMS. Follow the steps below to review the level switch configuration information.
NOTE
Information and procedures in this section that make use of Field Communicator fast key sequences and AMS assume that the 2160 and communication equipment are connected, powered, and operating correctly.
To view device identification information:
1. From the Home screen, select 1: Overview.
2. Select 6: Device Information.
3. Select 1: Identification.
4. Select 3: Device.
5. Select from the corresponding number to view each field:
1 Device Image 2 Tag 3 Long Tag
4 Model 5 Serial Number 6 Device ID 7Date 8 Descriptor
9 Message 10 Model Number I 11 Model Number II
Review Radio Information
Fast Keys
1, 6, 3
NOTE
Other device information can also be found at Fast Key sequence 2, 2, 7.
To view radio information:
1. From the Home screen, select 1: Overview.
2. Select 6: Device Information.
3. Select 3: Radio.
4. Select from the corresponding number to view each field:
1 Manufacturer
2 Device Type
3 Device Revision
4 Software Revision
5 Hardware Revision
6 Transmit Power Level
7 Minimum Broadcast Update Rate
2-8
Reference Manual
00809-0100-4160, Rev AD January 2013
Rosemount 2160

CHECK OUTPUT Before performing other level switch operations, ensure the 2160 is oper ating

properly by checking the process variables.
Variables To view the Variables menu:
Fast Keys
3, 2
1. From the Home screen, select 3: Service Tools.
2. Select 2: Variables.
The variable menu displays the following process var iab le s:
PVlevel switch output state of 0.0 (Dry) or 1.0 (Wet)
PV Status – valid or fault status (see “Troubleshooting” on page 6-2)
Sensor Frequencythe frequency of the vibrating fork
Sensor Frequency Status – valid or fault status
Electronics Temp – the temperature inside the 2160 housing
Electronics Temp Status – valid or fault status
Supply Voltage – the input voltage to the level switch
Supply Volt Status – valid or fault status
Last Update Time – elapsed time since the last data update
BASIC SETUP Temperature Units The Unit setting allows the Electronics Temperature process variable to be
Fast Keys
2, 2, 6
displayed in Farenheit (°F) or Celsius (°C). To view the electronics temperature menu:
1. From the Home screen, select 2: Configure.
2. Select 2: Manual Setup.
3. Select 6: Device Temperature.
The electronics temperature menu displays the following:
Electronics Temp – the live electronics temperature measurement
Electronics Temp Status – valid or fault status
Unitchange/view measurement units for Electronics Temperature
Maximumview the highest measured electronics temperature
Minimumview the lowest measured electronics temperature
Operation Mode The 2160 has three operation modes (see Table A-2 on page A-3):
Fast Keys
2, 2, 2, 1, 1
Standard – Default operation mode for no sensor fault detection
Enhanced (Fault=WET) – Output is forced to Wet when fault detected
Enhanced (Fault=DRY) – Output is forced to Dry when fault detected
To change or view the operation mode:
1. From the Home screen, select 2: Configure.
2. Select 2: Manual Setup.
3. Select 2: Operation.
4. Select 1: Application.
5. Select 1: Operation Mode.
2-9
Reference Manual
00809-0100-4160, Rev AD
Rosemount 2160
January 2013
Sensor Output Delay When the 2160 detects a change in process conditions from wet-to-dry or
Fast Keys
2, 2, 2, 1, 2
dry-to-wet, the Sensor Output Delay parameter causes a delay of up to 3600 seconds before a new process condition is indicated in the process variables.
If, for example, there are waves in a tank, then the 2160 may intermittently detect a change in process conditions. The sensor output delay ensures that the 2160 fork is dry or wet for a period before switching.
Depending on the application, a suitable delay can prevent const ant switching of the output state.
NOTE
The delay re-starts each time a change in process conditions is detected.
To change or view the sensor output delay:
1. From the Home screen, select 2: Configure.
2. Select 2: Manual Setup.
3. Select 2: Operation.
4. Select 1: Application.
5. Select 2: Sensor Output Delay.
Media Density The frequency of the vibrating fork sensor can be affected by the process
Fast Keys
2, 2, 2, 1, 3
liquid density. Use Media Density to select one of the following options:
Normal – Select when the liquid specific gravity is between 0.7 and 2.0
Low – Select when the liquid specific gravity is less than 0.7
High – Select when the liquid specific gravity is greater than 2.0
NOTE
If the liquid specific gravity is unknown, keep the default setting of Normal.
Write Protect The 2160 has a software write protect security feature.
Fast Keys
2, 2, 5, 1
The change or view write protect security settings:
1. From the Home screen, select 2: Configure.
2. Select 2: Manual Setup.
3. Select 5: Security.
4. Select 1: Write Protect.
Data Logging Data logging records previous measurement values.
Fast Keys
2, 2, 4, 6
To enable or disable the logging:
1. From the Home screen, select 2: Configure.
2. Select 2: Manual Setup.
3. Select 4: Data Logging.
4. Select 6: Configure Data Hist.
2-10
Follow on-screen instructions to enable or disable the logging.
Reference Manual
00809-0100-4160, Rev AD January 2013

LCD DISPLAY

Rosemount 2160
LCD Display Configuration
Fast Keys
2, 1, 4
The LCD display indicates output and abbreviated diagnostic messages.
NOTE
Use Rosemount Wireless LCD Part Number: 00753-9004-0002.
The LCD display features a four-line display and a bar graph. The first line of five characters displays the output description, the second line of seven digits displays the actual value, the third line of six characters displays engineering units, and the fourth line displays “Error” when there is an alarm condition. The LCD display can also display diagnostic messages. The bar graph represents the network connectivity status.
See “LCD Screen Messages” on page 5-3 for more information on LCD messages.
To change or view LCD display options:
1. From the Home screen, select 2: Configure.
2. Select 1: Guided Setup.
3. Select 4: Configure Device Display.
Alternatively, to manually change or view LCD display options:
1. From the Home screen, select 2: Configure.
2. Select 2: Manual Setup.
3. Select 3: Display.
4. Follow the on-screen instructions to configure Display Mode and Display Item parameters.
2-11
Reference Manual
Deadband
Assigned Value
Alert Set Point
Alert “OFF” Alert “ON” Alert “OFF”
Units of Measurement
Time
Deadband
Assigned Value
Alert Set Point
Alert “OFF” Alert “ON” Alert “OFF”
Units of Measurement
Time
00809-0100-4160, Rev AD
Rosemount 2160
January 2013
DETAILED SETUP Configure Alerts Alerts can be configured to output a HART message when a configured data
Fast Keys
2, 1, 5
point is exceeded. A process alert is transmitted continuously if a set point for a process variable is exceeded and the alert mode is enabled.
An alert is displayed on a Field Communicator, AMS status screen, or in the error section of the optional LCD display. The alert is reset when the assigned value (process variable) returns within its normal range.
Example 1: Rising Alert
Example 2: Falling Alert
To change or view the process alerts:
1. From the Home screen, select 2: Configure.
2. Select 1: Guided Setup.
3. Select 5: Configure Alerts.
4. Follow the on-screen instructions to configure up to four alerts (Alert 1,
Each alert requires the following information:
To view active or previous alerts:
1. From the Home screen, select 3: Service Tools.
2. Select 1: Alerts.
3. Select Refresh Alerts to repor t new alerts since the last update,
Alert 2, Alert 3, and Alert 4).
•Mode Disabled (default) or enabled alert
Variable – Select Output State, Sensor Frequency,
Electronics Temperature, or Supply Voltage
Direction Rising or falling alert
Limit Alert set point (in same units as the variable)
Dead Band Hysteresis data point (in same units as the variable)
for transition from deadband zone to new alert state
Active Alerts to view active alerts, or History to view previous alerts.
2-12
Loading...
+ 70 hidden pages