Rosemount 2090P, 2090F Operating Manual

Page 1
Reference Manual
00809-0100-4690, Rev FC June 2011
Rosemount 2088, 2090P, and 2090F Pressure Transmitters
with 4-20 mA HART and 1-5 Vdc Low Power Protocol
www.rosemount.com
Page 2
Page 3
Reference Manual
NOTICE
Rosemount 2088 and 2090
Rosemount 2088, 2090F, and 2090P Pressure Transmitters
Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product.
For technical assistance, contacts are listed below:
Customer Central
Technical support, quoting, and order-related questions.
United States - 1-800-999-9307 (7:00 am to 7:00 pm CST)
Asia Pacific- 65 777 8211
Europe/ Middle East/ Africa - 49 (8153) 9390
North American Response Center
Equipment service needs.
1-800-654-7768 (24 hours—includes Canada)
Outside of these areas, contact your local Emerson Process Management representative.
The products described in this document are NOT designed for nuclear-qualified applications. Using non-nuclear qualified products in applications that require nuclear-qualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact your local Emerson Process Management Sales Representative.
www.rosemount.com
Page 4
Page 5
Reference Manual
00809-0100-4690, Rev FC June 2011

Table of Contents

Rosemount 2088 and 2090
SECTION 1 Introduction
SECTION 2 Installation
Using this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Service Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
Models Covered. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Rosemount 2088 Pressure Transmitter . . . . . . . . . . . . . . . . . . 1-2
Rosemount 2090F Hygienic Pressure Transmitter . . . . . . . . . . 1-2
Rosemount 2090P Pulp & Paper Pressure Transmitter . . . . . . 1-2
Product Recycling/Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1
General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Mechanical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Environmental Considerations. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
HART Installation Flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Rosemount 2088 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Rosemount 2090P. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Rosemount 2090F. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Terminal Side of Electronics Housing . . . . . . . . . . . . . . . . . . . . 2-5
Circuit Side of Electronics Housing . . . . . . . . . . . . . . . . . . . . . . 2-5
Cover Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Mounting Brackets. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Rosemount 2088 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Rosemount 2090P (1
Mounting Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Rosemount 2090P. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
Weld Spud. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
Transmitter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
Rosemount 2090F. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-14
Configure Security and Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
Write Protect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-15
Configuring Transmitter Security and Alarm Jumper . . . . . . . 2-16
Without a display installed. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-17
With a display installed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-17
Electrical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-18
Power Supply for 1-5 Vdc HART Low Power . . . . . . . . . . . . . 2-18
Signal Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-21
Transmitter Case. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-21
Hazardous Locations Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . 2-21
1
/2-in.) Flush Mount . . . . . . . . . . . . . . . . . 2-6
TOC-1
Page 6
Rosemount 2088 and 2090
Reference Manual
00809-0100-4690, Rev FC
June 2011
SECTION 3 Configuration
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Configuration Data Review . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
AMS Device Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Field Communicator Menu Tree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
Fast key Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7
Check Output. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Method 1: Rerange with a Field Communicator
or AMS Device Manager . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Method 2: Rerange Using the Communicator
and a Pressure Source or Process Pressure . . . . . . . . . . . . . . 3-9
Method 3: Rerange Using the Local Zero and Span Buttons
and a Pressure Source or Process Pressure . . . . . . . . . . . . . 3-10
Disabling the Zero and Span Adjustments . . . . . . . . . . . . . . . 3-10
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
LCD Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-11
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
AMS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
Detailed Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-14
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-15
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
Diagnostics and Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-16
Multidrop Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-17
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-18
TOC-2
Page 7
Reference Manual
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090
SECTION 4 Operation and Maintenance
SECTION 5 Troubleshooting
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Calibration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2
Sample Calculation For A Standard 2088. . . . . . . . . . . . . . . . . 4-4
Analog Output Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
AMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
AMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
AMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Sensor Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
AMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9
AMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
Field Communicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
AMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1
Diagnostic Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Error . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
FAIL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
FAIL MODULE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
FAIL ELECT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
FAIL CONFIG . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
PRESS LIMIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
CURR FIXED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
CURR SATURD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
LOOP TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
XMTR INFO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
ZERO PASS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
ZERO FAIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
SPAN PASS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
LOCAL DSBLD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
WRITE PROTECT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
Field Communicator Diagnostics . . . . . . . . . . . . . . . . . . . . . . . 5-5
Disassembly Procedures. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
Reassembly Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9
TOC-3
Page 8
Rosemount 2088 and 2090
Reference Manual
00809-0100-4690, Rev FC
June 2011
APPENDIX A Reference Data
Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Reference Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Ambient Temperature Effect . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Stability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Vibration Effect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Power Supply Effect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Mounting Position Effect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
RFI Effect . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Transient Protection (Option Code T1) . . . . . . . . . . . . . . . . . . . A-2
IEEE 587 Category B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
IEEE 472 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Functional Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Ranges for Rosemount 2088 . . . . . . . . . . . . . . . . . . . . . . . . . . A-3
Ranges for Rosemount 2090F . . . . . . . . . . . . . . . . . . . . . . . . . A-3
Ranges for Rosemount 2090P . . . . . . . . . . . . . . . . . . . . . . . . . A-3
Load Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3
Zero Elevation and Suppression . . . . . . . . . . . . . . . . . . . . . . . . A-4
Overpressure Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-4
Temperature Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-4
Humidity Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5
Volumetric Displacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5
Failure Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5
Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5
Electrical Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5
Process Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5
Process Wetted Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5
Non-wetted Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6
Accessory Block and Bleed Valve (S5 Option) . . . . . . . . . . . . . A-6
Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-7
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-10
APPENDIX B Approval Information
APPENDIX C Glossary
TOC-4
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
ATEX Directive (94/9/EC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
European Pressure Equipment Directive (PED) (97/23/EC) . . . B-1
Electro Magnetic Compatibility (EMC) (2004/108/EC) . . . . . . . B-1
North American Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
European Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2
Japanese Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-3
Australian Certifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-4
Page 9
Reference Manual
Rosemount 2088 and 2090

Section 1 Introduction

Using this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1
Service Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-1
Models Covered . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 1-2

USING THIS MANUAL The sections in this manual provide information on installing, operating, and

maintaining Rosemount 2088, 2090F, and 2090P pressure transmitters with
®
HART
protocol. The sections are organized as follows:
Section 2: Installation contains mechanical and electrical installation
instructions.
Section 3: Configuration provides instruction on commissioning and
operating Rosemount 2088, 2090F, and 2090P transmitters.
Information on software functions, configuration parameters, and online
variables is also included.
Section 4: Operation and Maintenance contains operation and
maintenance techniques.
Section 5: Troubleshooting provides troubleshooting techniques for
the most common operating information.
Appendix A: Reference Data supplies reference and specification
data, as well as ordering information.
Appendix B: Approval Information contains intrinsic safety approval
information, European ATEX directive information, and approval
drawings.
Appendix C: Glossary

SERVICE SUPPORT To expedite the return process outside of the United States, contact the

nearest Emerson Process Management representative.
Within the United States, call the Emerson Process Management Instrument and Valves Response Center using the 1-800-654-RSMT (7768) toll-free number. This center, available 24 hours a day, will assist you with any needed information or materials.
www.rosemount.com
Page 10
Reference Manual
00809-0100-4690, Rev FC
Rosemount 2088 and 2090
The center will ask for product model and serial numbers and will provide a Return Material Authorization (RMA) number. The center will also ask for the process material to which the product was last exposed.
Individuals who handle products exposed to a hazardous substance can avoid injury if they are informed of and understand the hazard. If the product being returned was exposed to a hazardous substance as defined by OSHA, a copy of the required Material Safety Data Sheet (MSDS) for each hazardous substance identified must be included with the returned goods.
Emerson Process Management Instrument and Valves Response Center representatives will explain the additional information and procedures necessary to return goods exposed to hazardous substances.
June 2011

MODELS COVERED The following Rosemount Pressure Transmitters are covered by this manual:

Rosemount 2088 Pressure Transmitter
2088G - Gage Pressure Transmitter
Measures gage pressure up to 4000 psi (275,8 bar)

PRODUCT RECYCLING/DISPOSAL

2088A - Absolute Pressure Transmitter
Measures absolute pressure up to 4000 psi (275,8 bar)
Rosemount 2090F Hygienic Pressure Transmitter
2090FG - Gage Pressure Transmitter
Measures gage pressure up to 300 psi (20,7 bar)
2090FA - Absolute Pressure Transmitter
Measures absolute pressure up to 300 psi (20,7 bar)
Rosemount 2090P Pulp & Paper Pressure Transmitter
2090PG - Gage Pressure Transmitter
Measures gage pressure up to 300 psi (20,7 bar)
2090PA - Absolute Pressure Transmitter
Measures absolute pressure up to 300 psi (20,7 bar)
Recycling of equipment and packaging should be taken into consideration and disposed of in accordance with local and national legislation/regulations.
1-2
Page 11
Reference Manual
Rosemount 2088 and 2090

Section 2 Installation

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-1
General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-3
Mechanical Considerations . . . . . . . . . . . . . . . . . . . . . . . .page 2-3
Environmental Considerations . . . . . . . . . . . . . . . . . . . . . page 2-3
HART Installation Flowchart . . . . . . . . . . . . . . . . . . . . . . .page 2-4
Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-5
Configure Security and Alarm . . . . . . . . . . . . . . . . . . . . . . page 2-15
Electrical Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . page 2-18
Hazardous Locations Certifications . . . . . . . . . . . . . . . . .page 2-21

OVERVIEW The information in this section covers installation considerations for the

Rosemount 2088, 2090F, and 2090P transmitters with HART protocols. A Quick Installation Guide (document number 00825-0100-4690) is shipped with every transmitter to describe basic pipe-fitting and wiring procedures for initial installation.
Field Communicator and AMS Device Manager instructions are given to perform configuration functions. For convenience, Field Communicator fast key sequences are labeled “Fast Keys” for each software function below the appropriate headings.

SAFETY MESSAGES Instructions and procedures in this section may require special precautions to

ensure the safety of the personnel performing the operations. Information that raises potential safety issues is indicated by a warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.
www.rosemount.com
Page 12
Rosemount 2088 and 2090
Warnings
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the approvals section of the reference manual for any restrictions associated with a safe installation.
• Before connecting a Field Communicator in an explosive atmosphere, ensure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
• In an Explosion-Proof/Flameproof installation, do not remove the transmitter covers when power is applied to the unit.
Process leaks may cause harm or result in death.
• Install and tighten process connectors before applying pressure.
Electrical shock can result in death or serious injury.
• Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
Conduit/Cable Entries.
• Unless marked, the conduit/cable entries in the transmitter housing use a
1
compatible thread form when closing these entries.
Reference Manual
00809-0100-4690, Rev FC
June 2011
/2-14 NPT thread form. Only use plugs, adapters, glands, or conduit with a
Electrical shock can result in death or serious injury.
• Avoid contact with the leads and terminals.
Process leaks could result in death or serious injury.
• Install and tighten all four flange bolts before applying pressure.
• Do not attempt to loosen or remove flange bolts while the transmitter is in service.
Replacement equipment or spare parts not approved by Emerson Process Management for use as spare parts could reduce the pressure retaining capabilities of the transmitter and may render the instrument dangerous.
• Use only bolts supplied or sold by Emerson Process Management as spare parts.
• Refer to page A-7 for a complete list of spare parts.
Use appropriately rated sanitary clamps and gaskets during installation of the 2090F. The maximum working pressure of the clamp and gasket must be greater than or equal to the working pressure range of the transmitter. Failure to use proper clamps and gaskets can cause process leaks and can result in death or serious injury.
2-2
Page 13
Reference Manual
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090

GENERAL CONSIDERATIONS

MECHANICAL CONSIDERATIONS

ENVIRONMENTAL CONSIDERATIONS

Measurement accuracy depends on proper installation of the transmitter and impulse piping. Mount the transmitter close to the process and use a minimum of impulse piping to achieve the best accuracy. Also, consider the need for easy access, personnel safety, practical field calibration, and a suitable transmitter environment. Install the transmitter to minimize vibration, shock, and temperature fluctuation.
IMPORTANT
Install the enclosed pipe plug (found in the box) in unused conduit opening with a minimum of five threads engaged to comply with explosion-proof requirements.
For material compatibility considerations, see document number 00816-0100-3045 on www.emersonprocess.com/rosemount.
NOTE
For steam service or for applications with process temperatures greater than the limits of the transmitter, do not blow down impulse piping through the transmitter. Flush lines with the blocking valves closed and refill lines with water before resuming measurement.
Best practice is to mount the transmitter in an environment that has minimal ambient temperature change. The transmitter electronics temperature operating limits are -40 to 185 °F (-40 to 85 °C). Refer to Appendix A: Reference Data which lists the sensing element operating limits. Mount the transmitter so that it is not susceptible to vibration and mechanical shock and does not have external contact with corrosive materials.
2-3
Page 14
Rosemount 2088 and 2090
START HERE
Bench
Calibration?
Field Install
No
Set Units
(page 3-8)
Set Range
Points
(page 3-9)
Set Output
Type
(page 3-8)
Set Damping
(page 3-11)
Verify
Apply Pressure
Yes
Within
Specifications
?
Yes
No
Refer to
Section 4:
Operation and
Maintenance
Configure
Security and
Alarm
(page 2-15)
Mount
Transmitter
(page 2-5)
Wire Transmitter
(page 2-18)
Power Transmitter (page 2-18)
Check Process
Connection
Trim Transmitter
for Mounting
Effects
(page 2-5)
Done
Review
Transmitter
Configuration
(page 3-4)
Confirm
Transmitter
Configuration
(page 3-4)
Configure

HART INSTALLATION FLOWCHART

Figure 2-1. HART Installation Flowchart
Reference Manual
00809-0100-4690, Rev FC
June 2011
2-4
Page 15
Reference Manual
00809-0100-4690, Rev FC June 2011

INSTALLATION PROCEDURES

Mount the Transmitter Rosemount 2088
The Rosemount 2088 Transmitter weighs approximately 2.44 lb. (1,11 kg). In many cases, its compact size and light weight makes it possible to mount the 2088 directly to the impulse line without using an additional mounting bracket. When this is not desirable, mount directly to a wall, panel, or two-inch pipe using the optional mounting bracket (see Figure 2-3).
The 2088 offers several process connections. Use your plant-approved thread sealant to ensure a leak-proof connection.
Rosemount 2090P
The Rosemount 2090P is designed to be mounted directly to the process pipe using a weld spud (see Figure 2-7). Mount the transmitter using an existing weld spud or install a new one using the instructions on page 2-11.
Rosemount 2090F
Rosemount 2088 and 2090
The Rosemount 2090F is designed to be mounted directly to the process pipe using a standard sanitary fitting (see Figure 2-8). The transmitter is available with either a 1
NOTE
Most transmitters are calibrated in the horizontal position. Mounting the transmitter in any other position will shift the zero point to the equivalent amount of liquid head pressure caused by the varied mounting position. To reset zero point, refer to “Sensor Trim” on page 4-8.
Terminal Side of Electronics Housing
Mount the transmitter so the terminal side is accessible. Clearance of 0.75-in. (19 mm) is required for cover removal. Use a conduit plug on the unused side of the conduit opening.
Circuit Side of Electronics Housing
Provide 0.75 in. (19 mm) of clearance for units without an LCD display. Provide 3 in. (76 mm) of clearance for units installed with an LCD display.
Cover Installation
Always ensure a proper seal by installing the electronics housing covers so that metal contacts metal. Use Rosemount supplied o-rings.
Mounting Brackets
1
/2- or 2-inch Tri-Clamp® connection.
Rosemount 2088/2090 Transmitters may be panel-mounted or pipe-mounted through an optional mounting bracket. See Figure 2-3 on page 2-8 for dimensional and mounting configurations.
2-5
Page 16
Rosemount 2088 and 2090
* M20 1.5 Female and G
1
/2 Female (PF 1/2) also available as options.
DIN 16288 G
1
/2 Male, RC 1/2 Female (PT 1/2), and M20  1.5 Male also available.
2 ½–14 NPT*
Conduit
Connection
Terminal
Connections
5.1 (130) Optional Display Cover
Transmitter Circuitry
Certifications Tag
2 ¼–20 UNC-2B
Mounting Holes
½–14 NPT
Female† Process Connection
4.3 (110) Max.
3.9 (100)
0.75 (20)
Clearance for
Cover Removal
4.7
(120)
5.75
(146)
Rosemount 2088
2.38 (60)
5.1 (130) Optional Display Cover
Transmitter Circuitry
Terminal
Connections
M44 1.25
Weld Spud
2
1
/4–20 UNC–2BX
Depth 0.60
Mounting Holes
0.82 (21)
Certification Tag
4.3 (110)
Rosemount 2090P (11/2-in.) Flush Mount
Vessel Wall
NOTE: Dimensions are in. (mm).
Weld Spud
4.7
(120)
5.1(130) Typical
3.9 (100)
Dimensional Drawings
Figure 2-2. Transmitter Dimensional Drawings
Reference Manual
00809-0100-4690, Rev FC
June 2011
2-6
Page 17
Reference Manual
Nameplate
3.9
(100)
2X
1
/4–20 UNC–2BX 0.60 Deep
Mounting Bracket Holes
4.7 (140)
Terminal
Connections
Transmitter Circuitry Side
Optional Display Cover
5.1 (130)
Weld Spud
1.0 (25.4)
Vessel Wall
4.3 (110)
1.05 (26.6)
1.32 (33,4)
5.75 (146)
3X
5
/16–18 UNC
Mounting Holes for
Rotational Mounting
0.7 (17,8)
O-ring (Viton
®
standard)
External Zero/Span (under Nameplate)
1.03 (26.2)
Rosemount 2090P (1-in. Flush Mount)
11/2 or 2-in. Tri-Clamp Connection
2
1
/4–20 UNC–2BX 0.60
Deep Mounting Holes
4.7
(120)
3.9 (100)
* M20 1.5 Female also available.
NOTE: Dimensions are in inches (millimeters).
Optional Display Cover
Transmitter Circuitry Side
Terminal
Connections
5.0 (125)
4.3 (110)
Certifications Tag
Rosemount 2090F
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090
2-7
Page 18
Rosemount 2088 and 2090
2-inch U-Bolt
for Pipe Mounting
NOTE Dimensions are in. (mm).
1.30 (33)
2.81 (71)
PIPE MOUNTING
PANEL MOUNTING
Mounting bracket ordering code B4, and optional block and bleed valve.
5
/16 × 1½ Bolts
for Panel Mounting
(not supplied)
5
/16× 1½ Bolts
for Panel Mounting
(not supplied)
3.9 (100)
5.0 (125)
4.3 (110)
6.0 (150)
2.5
(63)
3.6
(90)
5.0
(139)
1.25 (32) HEX
3.0 (80)
3.9
(100)
6.2
(160)
2.8
(70)
4.75 (120)
7.0 (175)
Figure 2-3. Transmitter Mounting Configurations with Optional Bracket.
Reference Manual
00809-0100-4690, Rev FC
June 2011
2-8
Page 19
Reference Manual
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090
Impulse Piping The piping between the process and the transmitter must accurately transfer
the pressure to obtain accurate measurements. There are six possible sources of impulse piping error: pressure transfer, leaks, friction loss (particularly if purging is used), trapped gas in a liquid line, liquid in a gas line, and density variations between the legs.
The best location for the transmitter in relation to the process pipe is dependent on the process. Use the following guidelines to determine transmitter location and placement of impulse piping:
Keep impulse piping as short as possible.
For liquid service, slope the impulse piping at least 1 in./foot (8 cm/m) upward from the transmitter toward the process connection.
For gas service, slope the impulse piping at least 1 in./foot (8 cm/m) downward from the transmitter toward the process connection.
Avoid high points in liquid lines and low points in gas lines.
Make sure both impulse legs are the same temperature.
Use impulse piping large enough to avoid friction effects and blockage.
Vent all gas from liquid piping legs.
When using a sealing fluid, fill both piping legs to the same level.
When purging, make the purge connection close to the process taps and purge through equal lengths of the same size pipe. Avoid purging through the transmitter.
Keep corrosive or hot (above 250 °F [121 °C]) process material out of direct contact with the sensor module and flanges.
Prevent sediment deposits in the impulse piping.
Maintain equal leg of head pressure on both legs of the impulse piping.
Avoid conditions that might allow process fluid to freeze within the process flange.
Mounting Requirements
Impulse piping configurations depend on specific measurement conditions. Refer to Figure 2-4 for examples of the following mounting configurations:
Liquid Flow Measurement
Place taps to the side of the line to prevent sediment deposits on the process isolators.
Mount the transmitter beside or below the taps so gases vent into the process line.
Mount drain/vent valve upward to allow gases to vent.
Gas Flow Measurement
Place taps in the top or side of the line.
Mount the transmitter beside or above the taps so to drain liquid into the process line.
2-9
Page 20
Rosemount 2088 and 2090
GAS
SERVICE
STEAM SERVICE
LIQUID SERVICE
Steam Flow Measurement
Place taps to the side of the line.
Mount the transmitter below the taps to ensure that impulse piping will remain filled with condensate.
In steam service above 250 °F (121 °C), fill impulse lines with water to prevent steam from contacting the transmitter directly and to ensure accurate measurement start-up.
NOTE
For steam or other elevated temperature services, it is important that temperatures at the process connection do not exceed the transmitter’s process temperature limit, which is 250 °F (121 °C).
Figure 2-4. Installation Examples
Reference Manual
00809-0100-4690, Rev FC
June 2011
2-10
Page 21
Reference Manual
00809-0100-4690, Rev FC June 2011
Process Connections Rosemount 2090P
Installing the Rosemount 2090P transmitter involves attaching a weld spud to the tapped process vessel, attaching the transmitter to the weld spud, and making electrical connections. If you intend to use an existing weld spud, proceed to the transmitter section of this installation procedure (page 2-12).
NOTE
The Rosemount 2090P isolating diaphragm can be mounted flush with the inside diameter of any vessel larger than three inches in diameter.
Installation of the weld spud should be performed by a skilled welder using a TIG welder. Improper installation may result in weld spud distortion.
Weld Spud
Rosemount 2088 and 2090
1. Using the appropriate size hole saw, cut a hole in the process vessel
to accept the weld spud. The diameter for a weld spud with heat isolator groove is 2.37 in. (60 mm); when compatible with 1-in. PMC
process connection style spud, diameter is 1.32 in. (33,4 mm). The hole should produce a tight, uniform fit when coupled with the weld spud.
2. Bevel the edge of the vessel hole to accept filler material (see Figure
2-5).
3. Remove the weld spud from the transmitter and remove the PTFE
gasket from the weld spud.
Excessive heat will distort the weld spud. Weld in sections, as shown in Figure 2-5, cooling each section with a wet cloth. Allow adequate cooling between passes.
To reduce the chances of distorting the weld spud (for 1.5-in. connection), use a heat sink—Rosemount Part Number 02088-0196-0005.
4. Position the weld spud in the vessel hole, place heat sink and tack
spud in place using the welding sequence shown in Figure 2-5. Cool each section with a wet cloth before proceeding to the next section.
5. Weld the spud in place using 0.030 to 0.045 in. (0,762 to 1,143 mm)
stainless steel rod as filler in the bevelled area. Using between 100 and 125 amps., adjust the amperage for 0.080 in. (2,032 mm) penetration.
®
2-11
Page 22
Rosemount 2088 and 2090
Transmitter
1. After the weld spud has cooled, remove the heat sink and install the
PTFE gasket into the weld spud. Ensure that the gasket is properly positioned within the weld spud; improper placement could cause a process leak (see Figure 2-6).
2. Position the transmitter into the spud and begin to engage the
threads. Rotate the transmitter prior to seating the threads completely to enable access to the housing compartments, the conduit entry, and the LCD Display.
3. Hand tighten the transmitter using the knurled retaining ring, then
snug an additional
IMPORTA NT
Do not over-tighten the retaining ring. A spanner wrench hole is located on the knurled portion of the retaining ring to assist in transmitter removal if it is over-tightened.
00809-0100-4690, Rev FC
1
/8 turn with adjustable pliers.
Reference Manual
June 2011
2-12
Page 23
Reference Manual
PREPARING THE VESSEL HOLE
4
6
8
1
3
5
7
2
Process Vessel
Bevelled Edge
Weld Spud
100–125 Amps
recommended
308L SST
2.37 (60)
Code “C” in Model Structure or
P/N 02088-0195-0005
WELDING SEQUENCE
Heat Isolation
Grooves
PTFE Gasket
Nameplate
2 ¼–20
UNC–2BX
Depth 0.60
Mounting
Holes
Bevelled Edge
Vessel Wall
Weld Spud
DETAIL OF WELD SPUD
Vessel Wall
100–125 Amps
recommended
Weld Spud
00809-0100-4690, Rev FC June 2011
Figure 2-5. PTFE Installing the Weld Spud.
Figure 2-6. PTFE Gasket Placement.
Rosemount 2088 and 2090
Figure 2-7. Rosemount 2090P Mounting Configuration Using a Weld Spud.
2-13
Page 24
Rosemount 2088 and 2090
Nameplate
1.5- or 2-in. Tri-Clamp
Connection
1.1 (28) Typical
User Supplied Gasket and Clamp
B
A
DETAIL OF SANITARY
CONNECTION
Standard Sanitary Clamp Models
Clamp Model
psi @ 70 °F
(kPa @ 21 °C)
psi @ 250 °F
(kPa @ 121 °C)
Recommended
Torque
13 MHHM 1.5-inch 13 MHHM 2-inch
450 (3 103) 500 (3 448)
250 (1 724) 250 (1 724)
25 in-lb. (2.8 N•m)
13 MHHS 1.5-inch 13 MHHS 2-inch
600 (4 138) 550 (3 793)
300 (2 069) 275 (1 896)
25 in-lb. (2.8 N•m)
13 MHP 1.5-inch 13 MHP 2-inch
1500 (10 345)
1000 (6 896)
1200 (8 276)
800 (5 517)
20 ft-lb (27 N•m)
CONNECTION SIZE
* Dimensions are in inches (millimeters)
Connection
Size*
A B
1.50 (38) 1.99 (50) 1.71 (43)
2.00 (51) 2.52 (64) 2.22 (56)
Mounting
Hole
Rosemount 2090F
The Rosemount 2090F hygienic pressure transmitter is designed to be installed directly to a sanitary fitting. The transmitter is available with either a
1
/2- or 2-in. clamp connection.
1
When installing the transmitter to the sanitary fitting, it is important to use the proper sanitary clamp and gasket (user-supplied). Check the clamp and
gasket specifications before installing. Refer to Standard Sanitary Clamp Models in Figure 2-8 for a list of standard sanitary clamps, their respective
maximum pressure ranges, and the recommended torque to be applied when mounting.
Figure 2-8. Rosemount 2090F Mounting Configuration Using a Sanitary Fitting.
Reference Manual
00809-0100-4690, Rev FC
June 2011
2-14
Page 25
Reference Manual
Electronics
Housing
Process
Connection
00809-0100-4690, Rev FC June 2011
Do not apply torque directly to the electronics housing. Rotation between the electronics housing and the process connection can damage the electronics. To avoid damage, apply torque only to the hex-shaped process connection. Use a backup wrench on Process Connection when installing an adapter.

CONFIGURE SECURITY AND ALARM

Rosemount 2088 and 2090
Write Protect
There are three security methods in the Rosemount 2088/2090 transmitter:
1. Security Jumper: prevents all writes to transmitter configuration.
2. Local Keys (Local Zero and Span) Software Lock Out: prevents changes to transmitter range points via local zero and span adjustment keys. With local keys security enabled, changes to configuration are possible via HART.
3. Physical removal of Local Keys (Local Zero and Span) Magnetic Buttons: removes ability to use local keys to make transmitter range point adjustments. With removing local keys, changes to configuration are possible via HART.
You can prevent changes to the transmitter configuration data with the write protect jumper. Security is controlled by the security (write protect) jumper located on the electronics board or LCD display. Position the jumper on the transmitter circuit board in the “ON” position to prevent accidental or deliberate change of configuration data.
If the transmitter write protection is in the “ON” position, the transmitter will not accept any “writes” to its memory. Configuration changes, such as digital trim and reranging, cannot take place when the transmitter security is on.
2-15
Page 26
Rosemount 2088 and 2090
NOTE
If either the alarm or security jumper is dislodged or removed from its position, the transmitter reverts to default alarm or security settings of: Alarm: Output high; Security: Off
Configuring Transmitter Security and Alarm Jumper Procedure
To reposition the jumpers, follow the procedure described below.
1. Do not remove the transmitter covers in explosive atmospheres when the circuit is live. If the transmitter is live, set the loop to manual and remove power.
2. Remove the housing cover opposite the field terminal side. Do not remove the transmitter covers in explosive atmospheres when the circuit is live.
3. Reposition the jumpers as desired.
• Figure 2-9 shows the jumper positions for the 4-20 mA HART
Transmitter and 1-5 Vdc Low Power Transmitter.
4. Reattach the transmitter cover. Always ensure a proper seal by installing the electronics housing covers so that metal contacts metal to meet explosion-proof requirements.
Reference Manual
00809-0100-4690, Rev FC
June 2011
2-16
Page 27
Reference Manual
Security
Alarm
Alarm
Security
Alarm
Security
Alarm
Security
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090
Figure 2-9. Transmitter Alarm and Security Jumper Locations
Without LCD Display Low Power without LCD Display
With LCD Display Low Power with LCD Display
.
Without a display installed
The failure mode alarm jumper is located on the front side of the electronics module just inside the electronics housing cover and is labeled ALARM (See Figure 2-9). Do not remove the transmitter cover in explosive atmospheres when the circuit is alive. Both covers must be fully engaged to meet explosion-proof requirements.
With a display installed
The failure mode alarm jumper is located on the LCD faceplate in the electronics module side of the transmitter housing and is labeled ALARM (See Figure 2-9). Do not remove the transmitter cover in explosive atmospheres when the circuit is alive. Both covers must be fully engaged to meet explosion proof requirements.
2-17
Page 28
Rosemount 2088 and 2090
Voltage (Vdc)
Load (Ohms)
Operating
Region
1387
1000
500
0
10.5 20 30
42.4
Reference Manual
00809-0100-4690, Rev FC
June 2011

ELECTRICAL CONSIDERATIONS

The wiring terminations on the Rosemount 2088/2090 are located in the side of the transmitter housing marked “FIELD TERMINALS.” Access to these terminations is required during installation and may be necessary during periodic calibration of the transmitter.
NOTE
Make sure all electrical installation is in accordance with national and local code requirements.
Power Supply The dc power supply should provide power to the transmitter with less than
one percent ripple. The total loop resistance load is the sum of the resistance of the signal wires and the resistance load of the controller, indicator, and other pieces of equipment in the loop. Note that the resistance of intrinsic safety barriers, if used, must be included. Figure 2-10 shows the transmitter power supply load limitations.
Figure 2-10. Load Limitation
Maximum Loop Resistance = 43.5 * (Power Supply Voltage – 10.5)
The Field communicator requires a minimum loop resistance of 250
for communication.
Power Supply for 1-5 Vdc HART Low Power
Low power transmitters operates on 6-14 Vdc. The dc power supply should provide power with less than two percent ripple. The V
load should be 100
out
kor greater.
2-18
Page 29
Reference Manual
00809-0100-4690, Rev FC June 2011
Wiring
Rosemount 2088 and 2090
Do not connect the power signal wiring to the test terminals. Voltage may burn out the reverse-polarity protection diode in the test connection.
NOTE
Use shielded twisted pairs to yield best results. To ensure proper communication, use 24 AWG or larger wire, and do not exceed 5000 feet (1500 meters).
All power to the transmitter is supplied over the signal wiring. Signal wiring need not be shielded, but use twisted pairs for best results. Do not run unshielded signal wiring in conduit or open trays with power wiring, or near heavy electrical equipment. For high EMI/RFI environments, shielded twisted pair cable should be used. To power the transmitter, connect the positive power lead to the terminal marked “PWR/COMM+” and the negative power lead to the terminal marked “–” (see Figure 2-11). Tighten the terminal screws to ensure that proper contact is made. Avoid contact with the leads and the terminals. No additional power wiring is required for transmitters with “S” output. For “N” output code transmitters, connect positive signal lead to “test +” and negative signal lead to terminal marked “-.”
To connect test equipment for monitoring the output of the Rosemount 2088/2090 transmitter during maintenance procedures, connect one lead to the terminal labeled “TEST+” and the other lead to the terminal labeled “–” (see Figure 2-11). Avoid contact with the leads and the terminals.
Signal wiring may be grounded at any one point on the measurement loop, or it may be left ungrounded. The negative side of the power supply is a recommended grounding point. The transmitter case may be grounded or left ungrounded.
Conduit connections at the transmitter should be sealed to prevent moisture accumulating in the field terminal side of the transmitter housing. Also, install wiring with a drip loop with the bottom of the drip loop lower than the conduit connection of the transmitter housing.
2-19
Page 30
Rosemount 2088 and 2090
Positive
Negative
Test
Power Supply
RL250
Power Supply
Voltmeter
Figure 2-11. Rosemount 2088/2090 Transmitter Signal Wiring Terminals
Figure 2-12. 4-20 mA HART Transmitter Wiring Diagram
Reference Manual
00809-0100-4690, Rev FC
June 2011
Figure 2-13. 1-5 mA Vdc HART Low Power Transmitter Wiring
2-20
Page 31
Reference Manual
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090
T ransient Protection Terminal Block
The transmitter will withstand electrical transients of the energy level usually encountered in static discharges or induced switching transients. However, high-energy transients, such as those induced in wiring from nearby lightning strikes, can damage the transmitter.
The transient protection terminal block can be ordered as an installed option (Option Code T1 in the transmitter model number) or as a spare part to retrofit existing 2088 transmitters in the field. See “Spare Parts” on page A-7 for spare part numbers.
NOTE
The transient protection terminal block does not provide transient protection unless the transmitter case is properly grounded. Use the guidelines to ground the transmitter case.
Do not run the transient protection ground wire with signal wiring as the ground wire may carry excessive current if a lightning strike occurs.
Grounding Use the following techniques to properly ground the transmitter signal wiring
and case:
Signal Wiring
Do not run signal wiring in conduit or open trays with power wiring or near heavy electrical equipment. It is important that the instrument cable shield be:
Trimmed close and insulated from touching the transmitter housing
Connected to the next shield if cable is routed through a junction box
Connected to a good earth ground at the power supply end

HAZARDOUS LOCATIONS CERTIFICATIONS

For 4-20 mA HART output, the signal wiring may be grounded at any one point on the signal loop or may be left ungrounded. The negative terminal of the power supply is a recommended grounding point.
For 1-5 Vdc HART Low Power output, the power wires may be grounded at only one point or left ungrounded. The negative terminal of the power supply is a recommended grounding point.
Transmitter Case
Always ground the transmitter case in accordance with national and local electrical codes. The most effective transmitter case grounding method is a direct connection to earth ground with minimal impedance. Methods for grounding the transmitter case include:
Internal Ground Connection: The Internal Ground Connection screw
is inside the FIELD TERMINALS side of the electronics housing. This screw is identified by a ground symbol ( ). The ground connection screw is standard on all Rosemount 2088 transmitters.
Individual transmitters are clearly marked with a tag indicating the approvals they carry. Transmitters must be installed in accordance with all applicable codes and standards to maintain these certified ratings. Refer to “Hazardous Locations Certifications” on page B-1 for information on these approvals.
2-21
Page 32
Rosemount 2088 and 2090
Reference Manual
00809-0100-4690, Rev FC
June 2011
2-22
Page 33
Reference Manual
Rosemount 2088 and 2090

Section 3 Configuration

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-1
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-2
Configuration Data Review . . . . . . . . . . . . . . . . . . . . . . . . page 3-4
Field Communicator Menu Tree . . . . . . . . . . . . . . . . . . . .page 3-5
Fast Key Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-7
Check Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-8
Basic Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-8
LCD Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-11
Detailed Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 3-14
Diagnostics and Service . . . . . . . . . . . . . . . . . . . . . . . . . . page 3-16
Multidrop Communication . . . . . . . . . . . . . . . . . . . . . . . . .page 3-17

OVERVIEW This section contains information on commissioning and tasks that should be

performed on the bench prior to installation.
Field Communicator and AMS Device Manager instructions are given to perform configuration functions. For convenience, Field Communicator fast key sequences are labeled “Fast Keys” for each software function below the appropriate headings.

SAFETY MESSAGES Procedures and instructions in this section may require special precautions to

ensure the safety of the personnel performing the operations. Information that raises potential safety issues is indicated by a warning symbol. Refer to the following safety messages before performing an operation preceded by this symbol.
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the approvals section of the 2051 reference manual for any restrictions associated with a safe installation.
• Before connecting a Field Communicator in an explosive atmosphere, ensure
the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
• In an Explosion-Proof/Flameproof installation, do not remove the transmitter
covers when power is applied to the unit.
Process leaks may cause harm or result in death.
• Install and tighten process connectors before applying pressure.
Electrical shock can result in death or serious injury.
• Avoid contact with the leads and terminals. High voltage that may be present
on leads can cause electrical shock.
www.rosemount.com
Page 34
Reference Manual
00809-0100-4690, Rev FC
Rosemount 2088 and 2090
June 2011

COMMISSIONING Commissioning consists of testing the transmitter and verifying transmitter

configuration data. The Rosemount 2088/2090 can be commissioned either before or after installation. Commissioning the transmitter on the bench before installation using a Field Communicator or AMS Device Manager ensures that all transmitter components are in working order.
To commission on the bench, required equipment includes a power supply, a milliamp meter, and a Field Communicator or AMS Device Manager. Wire equipment as shown in Figure 3-1 and Figure 3-2. To ensure successful communication, a resistance of at least 250 ohms must be present between the Field Communicator loop connection and the power supply. Connect the Field Communicator leads to the terminals labeled “COMM” on the terminal block. Set all transmitter hardware adjustments during commissioning to avoid exposing the transmitter electronics to the plant environment after installation.
When using a Field Communicator, any configuration changes made must be sent to the transmitter by using the “Send” key. AMS Device Manager configuration changes are implemented when the “Apply” button is clicked.
Setting the Loop to Manual
Whenever sending or requesting data that would disrupt the loop or change the output of the transmitter, set the process application loop to manual. The Field Communicator or AMS Device Manager will prompt you to set the loop to manual when necessary. Acknowledging this prompt does not set the loop to manual. The prompt is only a reminder; set the loop to manual as a separate operation.
Wiring Diagrams Connect the equipment as shown in Figure 3-1 for 4-20 mA HART or
Figure 3-2 for 1-5 Vdc HART Low Power. To ensure successful communication, a resistance of at least 250 ohms must be present between the Field Communicator loop connection and the power supply. The Field Communicator or AMS Device Manager may be connected at “COMM” on the transmitter terminal block or across the resistor. Connecting across the “TEST” terminals will prevent successful communication for the 4-20 mA HART output.
Turn on the Field Communicator by pressing the ON/OFF key or log into AMS Device Manager. The Field Communicator or AMS Device Manager will search for a HART-compatible device and indicate when the connection is made. If the Field Communicator or AMS Device Manager fail to connect, it indicates that no device was found. If this occurs, refer to Section 5: Troubleshooting.
3-2
Page 35
Reference Manual
Power Supply
RL250
Power Supply
Voltmeter
00809-0100-4690, Rev FC June 2011
Figure 3-1. 4-20 mA HART Transmitter Wiring Diagram
Figure 3-2. 1-5 Vdc HART Low Power Transmitter Wiring
Rosemount 2088 and 2090
3-3
Page 36
Rosemount 2088 and 2090
Reference Manual
00809-0100-4690, Rev FC
June 2011

CONFIGURATION DATA REVIEW

NOTE
Information and procedures in this section that make use of Field Communicator fast key sequences and AMS Device Manager assume that the transmitter and communication equipment are connected, powered, and operating correctly.
The following is a list of factory default configurations. These can be reviewed by using the Field Communicator or AMS Device Manager
Field Communicator
4-20 mA Fast Keys
1, 5
Enter the fast key sequence to view the configuration data.
Ta g Range Date Descriptor Message Minimum and Maximum Sensor Limits Minimum Span Units 4 and 20 mA points Output (linear or sq. root) Damping Alarm Setting (high, low) Security Setting (on, off) Local Zero/Span Keys (enabled,
Integral Display Sensor Fill Isolator Material Flange (type, material) O-Ring Material Drain/Vent Remote Seal (type, fill fluid, isolator material,
number) Address Sensor S/N
disabled)
Transmitter S/N
AMS Device Manager
Right click on the device and select “Configuration Properties” from the menu. Select the tabs to review the transmitter configuration data.
3-4
Page 37
Reference Manual
Pressure Percent Range Analog Output
1 Tag
2 Unit
3 RANGE VALUES
4 DEVICE INFO
5 Damp
6 DISPLAY
OPTIONS
1 Self test 2 Status
1 Keypad Input 2 Apply Values
1 Loop Test 2 Digital-to-Analog Trim 3 Scaled D/A Trim 4 AO Alarm Type
1 Poll Address 2 Number of Req.
Pream. 3 Burst Mode 4 Burst Option
1 Digital-to-Analog Trim 2 Scaled D/A Trim
1 Zero Trim 2 Lower Sensor Trim 3 Upper Sensor Trim 4 Sensor T rim Cal Type 5 Sensor Trim Points
1 Date 2 Descriptor 3 Message 4 Write Protect
1 Keypad Input 2 Apply Values
1 Pressure 2 Percent Range
1 Keypad Input 2 Apply Values
1 Pressure 2 Percent Range 3 Analog Output
1 FIELD DEVICE INFO 2 SENSOR INFO
3 Self Test 4 DIAPHRAGM
SEALS INFO
1 DEVICE SETUP 2 PV 3 AO 4 LRV 5 URV
PROCESS
VARIABLES
DIAGNOSTICS AND SERVICE
BASIC SETUP
DETAILED
SETUP
REVIEW
1 TEST DEVICE
2 Loop Test
3 CALIBRATION
1 RERANGE
2 ANALOG
OUTPUT TRIM
3 SENSOR TRIM
1 Pressure 2 % Range
1 PROCESS
VARIABLES
2 SENSOR
TRIM
3 Unit
Online Menu
1 PRESSURE
SNSR
1 SENSORS
2 SIGNAL
CONDITION
3 OUTPUT
CONDITION
4 DEVICE
INFORMATION
1 Tag 2 Date 3 Descriptor 4 Message 5 Model 6 Write Protect 7 Local Keys 8 REVISION #s 9 Final Assy #
Device ID Distributor
1 Measurement Type
2 Isolator Material
3 Fill Type
4 Proc. Conn. Type
5 Proc. Conn.
Material
1 Display Type 2 CUSTOM
DISPLAY SETUP
1 PROCESS
VARIABLES
2 RANGE VALUES 3 Unit
4 Damp
1 PROCESS
VARIABLES
2 ANALOG
OUTPUT
3 HART OUTPUT
4 METER
OPTIONS
1 Diaph. Seal Type 2 Diaph. Seal Fill
Fluid
3 Diaph. Seal
Material
1 Display Type 2 CUSTOM
DISPLAY SETUP
3 Custom Display
Value
1 Select Dec. Pt. Pos. 2 CM Upper Value 3 CM Lower V alue 4 CM Units
1 Univ. Rev. 2 Fld. Dev.
Rev.
3 S/W Rev.
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090

FIELD COMMUNICATOR MENU TREE

Figure 3-3. Rosemount 2088/2090 HART menu tree for 4-20 mA HART
3-5
Page 38
Rosemount 2088 and 2090
1 DEVICE
SETUP
2PV
3AO
4LRV
5URV
1 PROCESS
VAR IAB LE
2 DIAGNOSTICS
AND SERVICE
3 BASIC SETUP
4 DETAILED
SETUP
5Review
1 Pressure
2 Percent Range
3 Analog Output
4 Sensor
Temperature
1 TEST DEVICE
2 Loop Test
3CALIBRATION
1Self Test
2Status
1RERANGE
2TRIM ANALOG
OUTPUT
3SENSOR TRIM
1SENSORS
2SIGNAL
CONDITION
3OUTPUT
CONDITION
4DEVICE
INFORMATION
1 Keypad Input
2 Apply Values
1 Digital-to-Analog Trim
2 Scaled D/A Trim
1 Zero Trim
2 Lower Sensor Trim
3 Upper Sensor Trim
4 Sensor Trim Points
1 Keypad Input
2 Apply Values
1Date
2Descriptor
3 Message
4 Write Protect
5 Meter Type
1Tag
2Unit
3 RANGE VALUES
4 DEVICE INFO
5 Transfer Function
6Damp
1 PRESSURE
SENSOR
2 TEMP SENSOR
1 Sensor Temp 2 Sensor Temp Unit
1 PROCESS VARIABLE
2 SENSOR SERVICE
3Unit
1Pressure 2% Range 3Sensor Temp
1 SENSOR
TRIM
1Zero Trim 2 Lower
Sensor Trim
3 Upper
Sensor Trim
4 Sensor Trim
Points
1 PROCESS
VARIABLE
2RANGE
VAL UES 3Unit
4Transfer Func
5Damp
1 PROCESS
VARIABLES
2ANALOG
OUTPUT
3 AO Alarm Type
4 HART OUTPUT
1FIELD DEVICE
INFO
2SENSOR INFO 3 Meter Type
4Self Test
1 Pressure 2 % Range 3 Snsr Temp
1Keypad Input
2 Apply Values
1 Pressure
2 % Range
3 Analog Output
4 Sensor Temp
1 Loop Test
2 Digital-to-Analog Trim
3 Scaled D/A Trim
4 AO Alarm Type
1 Poll Address
2 Nos. of Req. Pream.
3 Burst Mode
4 Burst Option
1 Measurement Type
2 Mod. Config. Type
3 Isolator Material
4 Fill Fluid
5 Flange Type
6 Proc. Conn. Material
7 Flange Material
8 Drain/Vent Material
9 # of Diaphr. Seals
Diaphr. Seal Type
Diaphr. Material
1Tag
2Date
3 Descriptor
4 Message
5 Model
6 Write Protect
7 Local Keys
8REVISION #S 9Final Assy #
Device ID
Distributor
1Univ. Rev.
2 Fid. Dev. Rev.
3S/W Rev.
Figure 3-4. Rosemount 2088 HART Menu Tree for 1-5 Vdc Low Power
Reference Manual
00809-0100-4690, Rev FC
June 2011
3-6
Page 39
Reference Manual
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090

FAST KEY SEQUENCE

Table 3-1. HART Fast Key Sequences for the Rosemount 2088/2090.
A check () indicates the basic configuration parameters. At minimum, these parameters should be verified as part of the configuration and startup procedure
Function HART Fast Key Sequence
Analog Output Alarm 1, 4, 3, 2, 4 Burst Mode Control 1, 4, 3, 3, 3 Burst Option 1, 4, 3, 3, 4 Calibration 1, 2, 3
Damping 1, 3, 5
Date 1, 3, 4, 1 Descriptor 1, 3, 4, 2 Digital To Analog Trim (4–20 mA Output) 1, 2, 3, 2, 1 Disable Local Span/Zero Adjustment 1, 4, 4, 1, 7 Field Device Info 1, 4, 4, 1 Keypad Input 1, 2, 3, 1, 1 Loop Test 1, 2, 2 Lower Range Value 4, 1 Lower Sensor Trim 1, 2, 3, 3, 2 Message 1, 3, 4, 3 Meter Type 1, 3, 6, 1 Number of Requested Preambles 1, 4, 3, 3, 2 Output Trim 1, 2, 3, 2 Percent Range 1, 1, 2 Poll Address 1, 4, 3, 3, 1
Range Values 1, 3, 3
Rerange 1, 2, 3, 1 Scaled D/A Trim (4–20 mA Output) 1, 2, 3, 2, 2 Self Test (Transmitter) 1, 2, 1, 1 Sensor Info 1, 4, 4, 2 Sensor Trim (Full Trim) 1, 2, 3, 3 Sensor Trim Points 1, 2, 3, 3, 5 Status 1, 2, 1, 2
Ta g 1, 3, 1
Transmitter Security (Write Protect) 1, 3, 4, 4
Units (Process Variable) 1, 3, 2
Upper Range Value 5, 2 Upper Sensor Trim 1, 2, 3, 3, 3 Zero Trim 1, 2, 3, 3, 1
3-7
Page 40
Reference Manual
00809-0100-4690, Rev FC
Rosemount 2088 and 2090
June 2011

CHECK OUTPUT Before performing other transmitter on-line operations, review the digital

output parameters to ensure that the transmitter is operating properly and is configured to the appropriate process variables.
Process Variables
The process variables for the Rosemount 2088/2090 provide the transmitter
output, and are continuously updated. The Process Variables menu displays
the following process variables:
Pressure
Percent Range
Analog Output
Field Communicator
4-20 mA Fast Keys
1, 1

BASIC SETUP From the Basic Setup menu you can configure the transmitter for certain

basic variables. In many cases, all of these variables are pre-configured at the factory. Configuration may be required if your transmitter is not configured or if the configuration variables need revision.
Tag The Tag variable is the easiest way to identify and distinguish between
transmitters in multi-transmitter environments. Use this variable to label transmitters electronically according to the requirements of your application. The tag you define is automatically displayed when a Field Communicator establishes contact with the transmitter at power-up. The tag may be up to eight characters long and has no impact on the primary variable readings of the transmitter.
Field Communicator
4-20 mA Fast Keys
1, 3, 1
Set Units The Unit command sets the desired primary variable units. Set the transmitter
output to one of the following engineering units:
inH20 g/cm inHg kg/cm ftH20 Pa mmH20 kPa psi torr bar atm mbar mmH20 @ 4 °C nH2O @ 4 °C
Field Communicator
4-20 mA Fast Keys
2
2
1, 3, 2
3-8
NOTE
After changing units, press SEND so the microprocessor will recalculate the associated variables (4–20 mA points, for example). The Rosemount 2088/2090 recalculates all variables that depend on units. After the transmitter recalculates the variables, you may change any of the remaining parameters.
Page 41
Reference Manual
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090
Rerange The Range Values command sets each of the lower and upper range analog
values (4 and 20 mA points and 1 and 5 Vdc points) to a pressure. The lower range point represents 0% of range and the upper range limit represents 100% of range. Setting the range values to the limits of expected readings maximizes transmitter performance; the transmitter is most accurate when operated within the expected pressure ranges for your application. In practice, you may reset the transmitter range values as often as necessary to reflect changing process conditions.
NOTE
Transmitters are shipped from Emerson Process Management fully calibrated per request or by the factory default of full scale (zero to upper range limit).
NOTE
Regardless of the range points, the Rosemount 2088/2090 will measure and report all readings within the digital limits of the sensor. For example, if the 4 and 20 mA points are set to 0 and 10 inH pressure of 25 inH percent of span reading.
0, it digitally outputs the 25 inH20 reading and a 250
2
0, and the transmitter detects a
2
You may use one of three methods to rerange the transmitter. Each method is unique; examine all three closely before deciding which method to use.
Method 1: Rerange with a Field Communicator or AMS Device Manager
This is the easiest and most popular way to rerange the transmitter. This method changes the values of the analog 4 and 20 mA points (1 and 5 Vdc points) independently without a pressure input. This means that when you change either the 4 or 20 mA setting, you also change the span.
To rerange using only the communicator enter the fast-key sequence above,
select 1 Keypad input, and follow the on-line instructions or enter the values
directly from the HOME screen.
Field Communicator
4-20 mA Fast Keys
Method 2: Rerange Using the Communicator and a Pressure Source or Process Pressure
Reranging using the communicator and a pressure source or process pressure is a way of reranging the transmitter when specific 4 and 20 mA points (1 and 5 Vdc points) are not known.
NOTE
The span is maintained when the 4 mA point (1 Vdc point) is set. The span changes when the 20 mA point (5 Vdc point) is set. If the lower range point is set to a value that causes the upper range point to exceed the sensor limit, the upper range point is automatically set to the sensor limit, and the span is adjusted accordingly.
1, 3, 3
To rerange using the communicator and a pressure source or process
pressure, enter the fast-key sequence above, select 2 Apply values, and
follow the on-line instructions.
3-9
Page 42
Rosemount 2088 and 2090
Span and Zero Adjustment Buttons
Method 3: Rerange Using the Local Zero and Span Buttons and a Pressure Source or Process Pressure
The Rosemount 2088/2090 is equipped with local zero and span adjustment buttons. The buttons are located on the top of the transmitter beneath the certifications label. Use the zero and span adjustments to set the 4 and 20 mA output points.
To rerange the transmitter using the span and zero buttons, perform the following procedure.
1. Loosen the screw holding the nameplate on top of the transmitter housing and rotate the nameplate to expose the zero and span buttons (see Figure 3-5).
2. Using a pressure source with an accuracy three to ten times the desired calibrated accuracy, apply a pressure equivalent to the lower range value.
3. To set the 4 mA point, press and hold the zero button for at least two seconds, then verify that the output is 4 mA. If a display is installed, it will display ZERO PASS.
4. Apply a pressure equivalent to the upper range value.
5. To set the 20 mA point, press and hold the span button for at least two seconds, then verify that the output is 20 mA. If a display is installed, it will display SPAN PASS.
Reference Manual
00809-0100-4690, Rev FC
June 2011
Figure 3-5. Local Zero and Span Adjustments
NOTE
If the transmitter security jumper is in the “ON” position, or if the local zero and span adjustments are disabled through the software, you will not be able to make adjustments to the zero and span using the local buttons. Refer to Figure 2-9 on page 2-17 for the proper placement of the transmitter security jumper.
Disabling the Zero and Span Adjustments
After you rerange the transmitter using the span and zero adjustments, you may wish to disable the adjustments to prevent further reranging. To disable the span and zero adjustments, activate the transmitter security jumper.
3-10
Page 43
Reference Manual
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090
Damping The Damping command changes the response time of the transmitter to
smooth variations in output readings caused by rapid changes in input. Determine the appropriate damping setting based on the necessary response time, signal stability, and other requirements of the loop dynamics of your system. The default damping value is 0.50 seconds and can be reset in fixed increments of 0.05, 0.10, 0.20, 0.40, 0.80, 1.60, 3.20, 6.40, 12.8, or 25.6 seconds.
Field Communicator
4-20 mA Fast Keys
1, 3, 5

LCD DISPLAY The LCD display connects directly to the interface board which maintains

direct access to the signal terminals. The display indicates output and abbreviated diagnostic messages. A display cover is provided to accommodate the display.
For 4-20 mA HART output, the LCD display features a two-line display. The first line of five characters displays the actual measured value. The second line of six characters displays the engineering units. The LCD can also display diagnostic messages. Refer to Figure 3-6.
Figure 3-6. LCD Display
4-20 mA HART 1-5 Vdc HART Low Power
For 1-5 Vdc HART Low Power output, the LCD display features a single-line display with four characters that display the actual value. The LCD can also display diagnostic messages. Refer to Figure 3-6.
3-11
Page 44
Rosemount 2088 and 2090
See “Safety Messages” on page 3-1 for complete warning information.
Reference Manual
00809-0100-4690, Rev FC
June 2011
LCD Display Configuration for 4-20 mA HART only
The factory default is Percent of Range (M5 option) or Engineering Units (M7 option). The LCD Display Configuration command allows customization of the LCD display to suit application requirements. The LCD display will alternate between the selected items:
Eng. Units only Alternate Eng. Units & % of Range
% of Range only Alternate Eng. Units & Custom Display
Custom Display only Alternate % of Range & Custom Display
Field Communicator
4-20 mA Fast Keys
To change the standard default to one of the above options, follow these steps:
1. From the communicators main menu select (1) Device Setup (3) Basic Setup, (7) Meter Options.
2. Select (1) Meter Type. Using the up or down arrows scroll up or down until the desired display has been highlighted. Press ENTER, SEND, and HOME.
AMS
Right click on the device and select “Configuration Properties” from the menu.
1. In the “Local Display” tab, locate the “Meter Type” area. Select the
desired options to suit your application needs, click Apply.
2. An “Apply Parameter Modification” screen appears. Enter desired
information and click OK.
3. After carefully reading the warning provided, select OK.
1, 3, 7
Custom Display Configuration 4-20 mA HART only
The user-configurable scale is a feature that enables the LCD display to display flow, level, or custom pressure units. With this feature you can define the decimal point position, the upper range value, the lower range value, the engineering units, and the transfer function.The display can be configured using a Field Communicator or AMS.
The user-configurable scale feature can define:
decimal point position
upper range values
lower range values
engineering units
transfer function
To configure the display with a Field Communicator, perform the following procedure:
1. Change the Meter Type to “Custom Meter” by using the Fast Key sequence under “LCD Display Configuration for 4-20 mA HART only” on page 3-12.
2. Next, from the ONLINE screen, Select 1 Device Setup, 3 Basic
Setup, 7 Meter Options, 2 Meter Options, 2 Custom Meter Setup.
3-12
Page 45
Reference Manual
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090
To specify decimal point position:
a. Select 1 Sel dec pt pos. Choose the decimal point representation
that will provide the most accurate output for your application. For example, when outputting between 0 and 75 GPM, choose
XX.XXX or use the decimal point examples below:
XXXXX XXXX.X XXX.XX XX.XXX X.XXXX
NOTE:
Make sure the selection has been sent and the decimal point has changed before proceeding to the next step.
b. SEND
3. To specify a custom upper range value:
a. Select 2 CM Upper Value. Type the value that you want the
transmitter to read at the 20 mA point.
b. SEND
4. To specify a custom lower range value:
a. Select 3 CM Lower Value. Type the value that you want the
transmitter to read at the 4 mA point.
b. SEND
5. To define custom units:
a. Select 4 CM Units. Enter the custom units (five characters
maximum) that you want the display to display.
b. SEND
6. To choose the transmitter transfer function for the display:
a. Select 5 CM xfer fnct. Enter the transmitter transfer function for the
display. Select sq root to display flow units. The custom meter
transfer function is independent of the analog output transfer function.
7. Select SEND to upload the configuration to the transmitter.
3-13
Page 46
Rosemount 2088 and 2090

DETAILED SETUP

Reference Manual
00809-0100-4690, Rev FC
June 2011
Failure Mode Alarm and Saturation
Table 3-2. 4-20 mA HART Alarm and Saturation Values
Table 3-3. NAMUR-Compliant Alarm and Saturation Values
As part of normal operation, the Rosemount 2088/2090 Pressure Transmitter continuously monitors its own operation. This automatic diagnostic routine is a timed series of checks repeated continuously. If the diagnostic routine detects a failure in the transmitter, the transmitter drives its output either below or above specific values depending on the position of the failure mode jumper or switch.
The values to which transmitters drive their output in failure mode depend on
whether they are factory-configured to standard or NAMUR-compliant
operation. The values for each are as follows:
Level 4–20 mA Saturation 4–20 mA Alarm
Low 3.9 mA 3.75 mA
High 20.8 mA 21.75 mA
Level 4–20 mA Saturation 4–20 mA Alarm
Low 3.8 mA 3.6 mA
High 20.5 mA 22.5 mA
Table 3-4. 1-5 Vdc HART Low-Power Alarm and Saturation Values
Level 1–5 V Saturation 1–5 V Alarm
Low 0.97 V 0.95 V
High 5.20 V 5.4 V
To determine the failure mode configuration of your transmitter, review the failure mode options using a Field Communicator.
NOTE
The failure mode configuration, whether standard or NAMUR-compliant, is configured at the factory and can not be changed in the field.
3-14
Page 47
Reference Manual
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090
Burst Mode Burst Mode sets the transmitter to maintain digital contact with a Digital
Control System that has custom software to support burst mode. When the Rosemount 2088 transmitter is configured for burst mode, it provides faster digital communication from the transmitter to the control system by eliminating the time required for the control system to request information from the transmitter.
Burst mode is compatible with use of the analog signal. Because HART
protocol features simultaneous digital and analog data transmission, the analog value can drive other equipment in the loop while the control system is receiving the digital information. Burst mode applies only to the transmission of dynamic data (pressure and temperature in engineering units, pressure in percent of range, and/or analog output in mA), and does not affect the way other transmitter data is accessed.
Field Communicator
4-20 mA Fast Keys
Access to information other than dynamic transmitter data is obtained through the normal poll/response method of HART communication. A Field Communicator or the control system may request any of the information that is normally available while the transmitter is in burst mode. Between each message sent by the transmitter, a short pause allows the Field Communicator or a control system to initiate a request. The transmitter will receive the request, process the response message, and then continue “bursting” the data approximately three times per second.
1, 4, 3, 3, 3
®
Alarm and Saturation Levels for Burst Mode
Alarm and Saturation Values for Multidrop Mode
Transmitters set to burst mode handle saturation and alarm conditions differently.
Alarm Conditions:
Analog output switches to alarm value
Primary variable is burst with a status bit set
Percent of range follows primary variable
Temperature is burst with a status bit set
Saturation:
Analog output switches to saturation value
Primary variable is burst normally
Temperature is burst normally
Transmitters set to multidrop mode handle saturation and alarm conditions differently.
Alarm Conditions:
Primary variable is sent with a status bit set
Percent of range follows primary variable
Temperature is sent with a status bit set
Saturation:
Primary variable is sent normally
Temperature is sent normally
3-15
Page 48
Reference Manual
00809-0100-4690, Rev FC
Rosemount 2088 and 2090
June 2011
Alarm Level Verification If the transmitter electronics board, sensor module, or LCD display is repaired
or replaced, verify the transmitter alarm level before returning the transmitter to service. This feature is also useful in testing the reaction of the control system to a transmitter in an alarm state. To verify the transmitter alarm values, perform a loop test and set the transmitter output to the alarm value.
Save, Recall, or Clone Configuration Data
Data that was entered off-line can be stored in the communicator memory and downloaded to other transmitters later. Data also can be copied from a transmitter in order to be sent to other transmitters in a process known as “cloning.” This is especially useful if you work with a large number of transmitters that require the same configuration data.
Field Communicator
4-20 mA Fast Keys
left arrow, 3 (note)

DIAGNOSTICS AND SERVICE

Test Device The Test Device command initiates a more extensive diagnostic routine than
that performed continuously by the transmitter. The transmitter test routine can identify an electronics failure. If the transmitter test detects a problem, the communicator displays messages to indicate the source of the problem.
Field Communicator
4-20 mA Fast Keys
1, 2, 1, 1
Loop Test The Loop Test command verifies the output of the transmitter, the integrity of
the loop, and the operations of any recorders or similar devices installed in the loop. To initiate a loop test, perform the following procedure:
Field Communicator
4-20 mA Fast Keys
1, 2, 2
3-16
1. Connect a reference meter to the transmitter. To do so, either connect the meter to the test terminals on the transmitter terminal block, or shunt the power to the transmitter through the meter at some point in the loop.
2. From the HOME screen, Select 1 Device Setup, 2 Diagnostics and Service, 2 Loop Test, to prepare to perform a loop test.
3. Select “OK” after you set the control loop to manual. The communicator displays the loop test menu.
4. Select a discreet milliamp level for the transmitter to output. At the
“Choose analog output” prompt, select 1 4mA, 2 20mA, or select 3 other to manually input a value between 4 and 20 mA.
5. Check the current meter installed in the test loop to verify that it reads the value you commanded the transmitter to output. If the readings do not match, the transmitter requires an output trim or the current meter is malfunctioning.
After completing the test procedure, the display returns to the loop test screen and allows you to choose another output value.
Page 49
Reference Manual
HART
Modem
Power
Supply
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090

MULTIDROP COMMUNICATION

Figure 3-7. Typical Multidrop Network.
Multidropping transmitters refers to the connection of several transmitters to a single communications transmission line. Communication between the host and the transmitters takes place digitally with the analog output of the transmitters deactivated. Many of the Rosemount transmitters can be multidropped. With the HART communications protocol, up to 15 transmitters can be connected on a single twisted pair of wires or over leased phone lines. Note that Burst Mode Operation is not compatible with multidrop communications.
The application of a multidrop installation requires consideration of the update rate necessary from each transmitter, the combination of transmitter models, and the length of the transmission line. Multidrop installations are not recommended where intrinsic safety is a requirement. Communication with the transmitters can be accomplished with commercially available HART modems and a host implementing the HART protocol. Each transmitter is identified by a unique address (1-15) and responds to the commands defined in the HART protocol.
Figure 3-7 shows a typical multidrop network. This figure is not intended as an installation diagram. Contact Rosemount product support with specific requirements for multidrop applications.
HART-based communicators can test, configure, and format a multidropped transmitter the same way as a transmitter in a standard point-to-point installation.
NOTE
The transmitter is set to address 0 at the factory, allowing it to operate in the standard point-to-point manner with a 4–20 mA output signal. To activate multidrop communication, you must change the transmitter address to a number from 1 to 15. This change deactivates the 4–20 mA analog output, locking it to 4 mA. It also disables the failure mode alarm signal, which is controlled by the upscale/downscale jumper position.
3-17
Page 50
Rosemount 2088 and 2090
Reference Manual
00809-0100-4690, Rev FC
June 2011
Changing a Transmitter Address
Communicating with a Multidropped Transmitter
Polling a Multidropped Loop
To change the address of a multidropped transmitter, follow these fast key sequences. To activate multidrop communication, the transmitter address must be changed to a number from 1 to 15.
Field Communicator
4-20 mA Fast Keys
To communicate with a multidropped transmitter for the purpose of testing, configuring, or formatting.
Field Communicator
4-20 mA Fast Keys
Polling a multidropped loop determines the model, address, and number of transmitters on the given loop.
Field Communicator
4-20 mA Fast Keys
1, 4, 3, 3, 1
1, 4, 3, 3, 2
Left Arrow, 4, 1, 1
3-18
Page 51
Reference Manual
Rosemount 2088 and 2090

Section 4 Operation and Maintenance

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-1
Calibration Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-2
Analog Output Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-5
Sensor Trim . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4-8

OVERVIEW This section contains information on calibrating and diagnostics messages on

the Rosemount 2088/2090 Pressure Transmitters.
Field Communicator and AMS instructions are given to perform configuration functions. For convenience, Field Communicator fast key sequences are labeled “Fast Keys” for each software function below the appropriate headings.

SAFETY MESSAGES Procedures and instructions in this section may require special precautions to

ensure the safety of the personnel performing the operations. Information that raises potential safety issues is indicated by a warning symbol ( ). Refer to the following safety messages before performing an operation preceded by this symbol.
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the approvals section of the reference manual for any restrictions associated with a safe installation.
• Before connecting a Field Communicator in an explosive atmosphere, ensure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
• In an Explosion-Proof/Flameproof installation, do not remove the transmitter covers when power is applied to the unit.
Process leaks may cause harm or result in death.
• Install and tighten process connectors before applying pressure.
Electrical shock can result in death or serious injury.
Avoid contact with the leads and terminals. High voltage that may be present on leads can
cause electrical shock.
www.rosemount.com
Page 52
Rosemount 2088 and 2090
Reference Manual
00809-0100-4690, Rev FC
June 2011

CALIBRATION OVERVIEW

Calibration is defined as the process required to optimize transmitter accuracy over a specific range by adjusting the factory sensor characterization curve located in the microprocessor. Possible procedures are:
• Reranging: Setting the lower and upper range points (4 and 20 mA or 1 and 5 Vdc) points at required pressures. Reranging does not change the factory sensor characterization curve. Refer to page 3-9.
• Analog Output Trim: Adjusts the transmitter’s analog characterization curve to match the plant standard of the control loop. There are two types of digital-to-analog output trims. Refer to page 4-5.
Digital-to-Analog Output Trim on 4-20 mA HART output (page 4-5)
Digital-to-Analog Output Trim on 4-20 mA HART output Using Other
Scale (page 4-6)
• Sensor Trim: Adjusts the position of the factory sensor characterization curve due to a change in the sensor characteristics over time or a change in test equipment. Trimming has two steps, zero and sensor trims. Refer to page 4-8.
Zero Trim (page 4-9)
Sensor Trim (page 4-9)
Figure 4-1 Illustrates the Rosemount 2088/2090 data flow. This data flow can be summarized in four major steps:
1. A change in pressure is measured by a change in the sensor output
(Sensor Signal).
2. The sensor signal is converted to a digital format that can be
understood by the microprocessor (Analog-to-Digital Signal Conversion).
3. Corrections are performed in the microprocessor to obtain a digital
representation of the process input (Digital PV).
4. The Digital PV is converted to an analog value
(Digital-to-Analog Signal Conversion).
4-2
Page 53
Reference Manual
Transmitter Electronics Module
Microprocessor
Digital PV
Sensor
Input Device
Output Device
20.00 mA
2088s:PT-4763
1 Device Setup
Online 2PV100.00 inH2O
3AO20.00 mA 4LRV0.00 inH2O 5URV100.00 inH2O
Transmitter Ranged 0 to 100 inH2O
Input
Pressure
Sensor
Signal
Analog Output
Field
Communicator
NOTE
Value on PV line should equal the input pressure. Value on AO line should equal the output device reading.
00809-0100-4690, Rev FC June 2011
Figure 4-1. Transmitter Data Flow with Calibration Options
Rosemount 2088 and 2090
Determining Calibration Frequency
NOTE
The 2088/2090 has been carefully calibrated at the factory. Trimming adjusts the position of the factory characterization curve. It is possible to degrade performance of the transmitter if any trim is done improperly or with inaccurate equipment.
Calibration frequency can vary greatly depending on the application, performance requirements, and process conditions. Use the following procedure to determine calibration frequency that meets the needs of your application.
1. Determine the performance required for your application.
2. Determine the operating conditions.
3. Calculate the Total Probable Error (TPE).
4. Calculate the stability per month.
5. Calculate the calibration frequency.
4-3
Page 54
Rosemount 2088 and 2090
ReferenceAccuracy
2
TemperatureEffect
2
StaticPressureEffect
2
++
0.15% URL 0.15% of span+per 50 F 0.3% of span=
Stability 0.100 URL% of span for 1 year 0.0083% of span per month==
Cal. Freq.
Req. Performance TPE
Stability per Month
---------------------------------------------------------------------- -
0.5% 0.316%
0.0083%
--------------------------------------------- 22 m o n t h s===
Sample Calculation For A Standard 2088
Step 1: Determine the performance required for your application.
Required Performance: 0.50% of span
Step 2: Determine the operating conditions.
Transmitter: 2088G, Range 1 [URL=30 psi (2,1 bar)]
Calibrated Span: 30 psi (2,1 bar)
Ambient Temperature Change: ± 50 °F (28 °C)
Step 3: Calculate total probable error (TPE).
TPE = = 0.316% of span
Where:
Reference Accuracy = ± 0.10% of span
Ambient Temperature Effect =
Reference Manual
00809-0100-4690, Rev FC
June 2011
Choosing a Trim Procedure
Step 4: Calculate the stability per month.
Step 5: Calculate calibration frequency.
To decide which trim procedure to use, you must first determine whether the analog-to-digital section or the digital-to-analog section of the transmitter electronics need calibration. Refer to Figure 4-1 and perform the following procedure:
1. Connect a pressure source, a Field Communicator or AMS, and a digital
readout device to the transmitter.
2. Establish communication between the transmitter and the Field
Communicator.
3. Apply pressure equal to the upper range point pressure.
4. Compare the applied pressure to the pressure process variable valve on
the Process Variables menu on the Field Communicator or the Process Variables screen in AMS. For instructions on how to access process variables, see page 3-8 of Section 3: Configuration.
a. If the pressure reading does not match the applied pressure (with
high-accuracy test equipment), perform a sensor trim. See “Sensor Trim Overview” on page 4-8 to determine which trim to perform.
5. Compare the Analog Output (AO) line, on the Field Communicator or
AMS, to the digital readout device.
4-4
If the AO reading does not match the digital readout device (with high-accuracy test equipment), perform an analog output trim. See “Analog Output Trim” on page 4-5.
Page 55
Reference Manual
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090

ANALOG OUTPUT TRIM The Analog Output Trim commands allow you to adjust the transmitter’s

current output at the 4 and 20 mA (1 and 5 Vdc) points to match the plant standards. This command adjusts the digital to analog signal conversion.
Figure 4-2. Output Trim
Digital-to-Analog Trim Field Communicator
4-20 mA Fast Keys
To perform a digital-to-analog trim with a Field Communicator, perform the following procedure.
1. From the HOME screen, enter the fast key sequence “Digital-to-Analog
Trim.” Select OK after setting the control loop to manual, see “Setting the
Loop to Manual” on page 3-2.
2. a. For 4-20 mA HART output, connect a reference meter to the
transmitter by either connecting the meter to the test terminals on the terminal block, or shunting transmitter power through the meter at some point in the loop. b. For 1-5 Vdc Low Power HART output, connect a reference meter to the V
3. Select OK after connecting the reference meter.
4. Select OK at the SETTING FLD DEV OUTPUT TO 4 MA (1 Vdc)
prompt. The transmitter outputs 4.0 mA.
5. Record the actual value from the reference meter, and enter it at the
ENTER METER VALUE prompt. The Field Communicator prompts you
to verify whether or not the output value equals the value on the reference meter.
6. Select 1: Yes, if the reference meter value equals the transmitter output
value, or 2: No, if it does not.
7. Select OK at the SETTING FLD DEV OUTPUT TO 20 MA (5 Vdc)
prompt, and repeat Steps 5 and 6 until the reference meter value equals the transmitter output value.
8. Select OK after the control loop is returned to automatic control.
terminal.
out
a. If 1 is selected: Yes, proceed to Step 7.
b. If 2 is selected: No, repeat Step 5.
1, 2, 3, 2, 1
4-5
Page 56
Rosemount 2088 and 2090
AMS
Right click on the device and select “Calibrate,” then “D/A Trim” from the
.
menu
1. Click Next after setting the control loop to manual.
2. Click Next after connecting the reference meter.
3. Click Next at the “Setting fld dev output to 4 mA (1 Vdc)” screen.
4. Record the actual value from the reference meter, and enter it at the
“Enter meter value” screen and click Next.
5. Select Yes, if the reference meter value equals the transmitter output
value or No, if it does not. Click Next.
a. If Yes is selected, proceed to Step 6.
b. If No is selected, repeat Step 4.
6. Click Next at the “Setting fld dev output to 20 mA (5 Vdc)” screen.
7. Repeat Step 4 - Step 5 until the reference meter equals the transmitter
output value.
8. Select Next to acknowledge the loop can be returned to automatic
control.
9. Select Finish to acknowledge the method is complete.
Reference Manual
00809-0100-4690, Rev FC
June 2011
Digital-to-Analog Trim Using Other Scale
The Scaled D/A Trim command matches the 4 and 20 mA (1 and 5 Vdc) points to a user selectable reference scale other than 4 and 20 mA (for example, 2 to 10 volts if measuring across a 500 ohm load, or 0 to 100 percent if measuring from a Distributed Control System (DCS)). To perform a scaled D/A trim, connect an accurate reference meter to the transmitter and trim the output signal to scale, as outlined in the Output Trim procedure.
NOTE
Use a precision resistor for optimum accuracy. If you add a resistor to the loop, ensure that the power supply is sufficient to power the transmitter to a 20 mA output with additional loop resistance. Refer to “Power Supply” on page 2-18.
4-6
Page 57
Reference Manual
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090
Field Communicator
4-20 mA Fast Keys
AMS
Right click on the device and select “Calibrate,” then “Scaled D/A trim” from the menu
1. Click Next after setting the control loop to manual.
2. Select Change to change scale, click Next.
3. Enter Set scale-Lo output value, click Next.
4. Enter Set scale-Hi output value, click Next.
5. Click Next to proceed with Trim.
6. Click Next after connecting the reference meter.
7. Click Next at the “Setting fld dev output to 4 mA” screen.
8. Record the actual value from the reference meter, enter it at the “Enter
9. Select Yes, if the reference meter value equals the transmitter output
10. Click Next at the “Setting fld dev output to 20 mA” screen.
11. Repeat Step 8 - Step 9 until the reference meter equals the transmitter
12. Select Next to acknowledge the loop can be returned to automatic
13. Select Finish to acknowledge the method is complete.
.
meter value” screen, and click Next.
value or No, if it does not. Click Next.
a. If Yes is selected, proceed to Step 10.
b. If No is selected, repeat Step 8.
output value.
control.
1, 2, 3, 2, 2
Recall Factory Trim— Analog Output
The Recall Factory Trim—Analog Output command allows the restoration of the as-shipped factory settings of the analog output trim. This command can be useful for recovering from an inadvertent trim, incorrect Plant Standard, or faulty meter. This command is only available with 4-20 mA output.
Field Communicator
4-20 mA Fast Keys
AMS
Right click on the device and select “Calibrate,” then “Recall Factory Trim” from the menu
1. Click Next after setting the control loop to manual.
2. Select “Analog output trim” under “Trim to recall” and click Next.
3. Click Next to acknowledge restoration of trim values is complete.
4. Select Next to acknowledge the loop can be returned to automatic
control.
5. Select Finish to acknowledge the method is complete.
.
1, 2, 3, 4, 2
4-7
Page 58
Reference Manual
00809-0100-4690, Rev FC
Rosemount 2088 and 2090
June 2011
SENSOR TRIM Sensor Trim Overview Trim the sensor using either sensor or zero trim functions. Trim functions vary
in complexity and are application-dependent. Both trim functions alter the transmitter’s interpretation of the input signal.
Zero trim is a single-point offset adjustment. It is useful for compensating for
mounting position effects and is most effective when performed with the transmitter installed in its final mounting position. Since this correction maintains the slope of the characterization curve, it should not be used in place of a sensor trim over the full sensor range.
When performing a zero trim, ensure that the equalizing valve is open and all wet legs are filled to the correct levels.
NOTE Do not perform a zero trim on Rosemount 2088/2090 Absolute pressure transmitters. Zero trim is zero based, and absolute pressure transmitters
reference absolute zero. To correct mounting position effects on an Absolute Pressure Transmitter, perform a low trim within the sensor trim function. The low trim function provides an offset correction similar to the zero trim function, but it does not require zero-based input.
Figure 4-3. Sensor Trim

Sensor trim is a two-point sensor calibration where two end-point pressures

are applied, and all output is linearized between them. Always adjust the low trim value first to establish the correct offset. Adjustment of the high trim value provides a slope correction to the characterization curve based on the low trim value. The trim values allow you to optimize performance over your specified measuring range at the calibration temperature.
4-8
Page 59
Reference Manual
00809-0100-4690, Rev FC June 2011
Zero Trim NOTE
The transmitter must be within three percent of true zero (zero-based) in order to calibrate with zero trim function.
Field Communicator
Rosemount 2088 and 2090
4-20 mA Fast Keys
Calibrate the sensor with a Field Communicator using the zero trim function as follows:
1. Vent the transmitter and attach a Field Communicator to the
2. From the HOME screen, follow the fast key sequence “Zero Trim.”
3. Follow the commands provided by the Field Communicator to complete
AMS
Right click on the device and select “Calibrate,” then “Zero trim” from the menu
1. Click Next after setting the control loop to manual.
2. Click Next to acknowledge warning.
3. Click Next after applying appropriate pressure to sensor.
4. Select Next to acknowledge the loop can be returned to automatic
5. Select Finish to acknowledge the method is complete.
Sensor Trim NOTE
Use a pressure input source that is at least three times more accurate than the transmitter, and allow the input pressure to stabilize for ten seconds before entering any values.
1, 2, 3, 3, 1
measurement loop.
the zero trim adjustment.
.
control.
Field Communicator
4-20 mA Fast Keys
To calibrate the sensor with a Field Communicator using the sensor trim function, perform the following procedure:
1. Assemble and power the entire calibration system including a
transmitter, Field Communicator, power supply, pressure input source, and readout device.
2. From the HOME screen, enter the fast key sequence under “Sensor
Trim.”
3. Select 2: Lower sensor trim. The lower sensor trim value should be the
sensor trim point that is closest to zero.
Examples:
Calibration: 0 to 100 inH
Calibration: -100 to 0 inH
Calibration: -100 to 100 inH
upper trim = -100 or 100
1, 2, 3, 3
O - lower trim = 0, upper trim = 100
2
O - lower trim = 0, upper trim = -100
2
O - lower trim = -100 or 100,
2
4-9
Page 60
Rosemount 2088 and 2090
NOTE
Select pressure input values so that lower and upper values are equal to or outside the 4 and 20 mA (1 and 5 Vdc) points. Do not attempt to obtain reverse output by reversing the high and low points. This can be done by going to “Rerange” on page 3-9 of Section 3: Configuration. The transmitter allows approximately five percent deviation.
4. Follow the commands provided by the Field Communicator to complete
the adjustment of the lower value.
5. Repeat the procedure for the upper value, replacing 2: Lower sensor trim
with 3: Upper sensor trim in Step 3.
AMS
Right click on the device and select “Calibrate,” then “Sensor trim” from the
.
menu
1. Select “Lower sensor trim.” The lower sensor trim value should be the
sensor trim point that is closest to zero.
2. Click Next after setting the control loop to manual.
3. Click Next after applying appropriate pressure to sensor.
4. Select Next to acknowledge the loop can be returned to automatic
control.
5. Select Finish to acknowledge the method is complete.
6. Right click on the device and select “Calibrate.” Select “Sensor trim” from
the menu
7. Select “Upper sensor trim” and repeat steps 2-5.
Reference Manual
00809-0100-4690, Rev FC
June 2011
.
Recall Factory Trim— Sensor Trim
The Recall Factory Trim—Sensor Trim command allows the restoration of the as-shipped factory settings of the sensor trim. This command can be useful for recovering from an inadvertent zero trim of an absolute pressure unit or inaccurate pressure source. This command is only available with 4-20 mA output.
Field Communicator
4-20 mA Fast Keys
AMS
Right click on the device and select “Calibrate,” then “Recall Factory Trim” from the menu
1. Click Next after setting the control loop to manual.
2. Select “Sensor trim” under “Trim to recall” and click Next.
3. Click Next to acknowledge restoration of trim values is complete.
4. Select Next to acknowledge the loop can be returned to automatic
control.
5. Select Finish to acknowledge the method is complete.
.
1, 2, 3, 4, 1
4-10
Page 61
Reference Manual
Rosemount 2088 and 2090

Section 5 Troubleshooting

Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-1
Safety Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-1
Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-1
Diagnostic Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-3
Disassembly Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . page 5-8
Reassembly Procedures . . . . . . . . . . . . . . . . . . . . . . . . . .page 5-9

OVERVIEW Table 5-1 provides summarized maintenance and troubleshooting suggestions for

the most common operating problems.
If you suspect malfunction despite the absence of any diagnostic messages on the Field Communicator display, consider using Table 5-1 on page 5-2 to identify any potential problem.

SAFETY MESSAGES Procedures and instructions in this section may require special precautions to

ensure the safety of the personnel performing the operations. Information that raises potential safety issues is indicated by a warning ( ). Refer to the following safety messages before performing an operation preceded by this symbol.

WARNINGS

Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the approvals section of the reference manual for any restrictions associated with a safe installation.
• Before connecting a Field Communicator in an explosive atmosphere, ensure the instruments in the loop are installed in accordance with intrinsically safe or non-incendive field wiring practices.
• In an Explosion-Proof/Flameproof installation, do not remove the transmitter covers when power is applied to the unit.
Process leaks may cause harm or result in death.
• Install and tighten process connectors before applying pressure.
Electrical shock can result in death or serious injury.
• Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock.
www.rosemount.com
Page 62
Reference Manual
00809-0100-4690, Rev FC
Rosemount 2088 and 2090
Table 5-1. Rosemount 2088/2090Troubleshooting for 4-20 mA output.
Symptom Corrective Actions
Transmitter milliamp reading is zero Verify power is applied to signal terminals
Check power wires for reversed polarity
Verify terminal voltage is 10.5 to 42.4 Vdc
Check for open diode across test terminal
Transmitter Not Communicating with Field Communicator
Transmitter milliamp reading is low or high Verify applied pressure
Transmitter will not respond to changes in applied pressure
Digital Pressure Variable reading is low or high Check test equipment (verify accuracy)
Digital Pressure Variable reading is erratic Check application for faulty equipment in pressure line
Milliamp reading is erratic Verify power source to transmitter has adequate voltage and current
Verify the output is between 4 and 20 mA or saturation levels
Verify terminal voltage is 10.5 to 42.4 Vdc
Verify clean DC Power to transmitter (Max AC noise 0.2 volts peak to peak)
Check loop resistance, 250 minimum (PS voltage -transmitter voltage/loop current)
Have Field Communicator poll for all addresses
Verify 4 and 20 mA range points
Verify output is not in alarm condition
Verify if 4 – 20 mA output trim is required
Check test equipment
Check impulse piping or manifold for blockage
Verify the transmitter is not in multidrop mode
Verify applied pressure is between the 4 and 20 mA set points
Verify output is not in alarm condition
Verify transmitter is not in Loop Test mode
Check impulse piping for blockage or low fill in wet leg
Verify transmitter is calibrated properly
Verify pressure calculations for application
Verify transmitter is not reacting directly to equipment turning on/off
Verify damping is set properly for application
Check for external electrical interference
Verify transmitter is properly grounded
Verify shield for twisted pair is only grounded at one end
June 2011
5-2
Page 63
Reference Manual
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090

DIAGNOSTIC MESSAGES

In addition to the output, the LCD displays abbreviated operation, error, and warning messages for troubleshooting the transmitter. Messages appear according to their priority, with normal operating messages appearing last. To determine the cause of a message, use a Field Communicator to further interrogate the transmitter. A description of each LCD diagnostic message follows.
Error
Error messages appear on the LCD display to inform you of serious problems affecting the operation of the transmitter. The display displays an error message until the error condition is corrected, and the analog output is driven to the specified alarm level. No other transmitter information is displayed during an alarm condition.
FAIL
The transmitter CPU board and the sensor module are incompatible.
FAIL MODULE
The sensor module is disconnected or is malfunctioning. Verify that the sensor module ribbon cable is connected to the back of the electronics board. If the ribbon cable is not disconnected, there is a problem within the sensor module. Possible sources of problems include:
Pressure or temperature updates are not being received in the sensor module.
A non-volatile memory fault that will affect transmitter operation has been detected in the module by the memory verification routine.
FAIL ELECT
The transmitter electronics module is malfunctioning. Possible causes include:
Internal fault
A non-volatile memory fault that will affect transmitter operation has been detected in the module by the memory verification routine
Neither problem is repairable; the electronics board must be replaced.
FAIL CONFIG
A non-volatile memory fault has been detected in the transmitter memory by the memory verification routine. The memory fault is in a location that could affect transmitter operation, and is user-accessible. To correct this problem, use a Field Communicator to interrogate and reconfigure the appropriate portion of the transmitter memory.
Warnings
Warnings appear on the LCD display to alert you of user-repairable problems with the transmitter, or current transmitter operations. Warnings appear alternately with other transmitter information until the warning condition is corrected or the transmitter completes the operation that triggered the warning message.
5-3
Page 64
Rosemount 2088 and 2090
PRESS LIMIT
The process variable read by the transmitter is outside of sensor range limits.
CURR FIXED
The transmitter is in multidrop mode. The analog output is not tracking pressure changes.
CURR SATURD
The pressure read by the module is outside of the specified range, and the analog output has been driven to saturation levels (see “Transient Protection Terminal Block” on page 2-21).
LOOP TEST
A loop test is in progress. During a loop test or 4–20 mA trim, the analog output is set to a fixed value. The display alternates between the current selected in milliamps and “LOOP TEST.”
XMTR INFO
A non-volatile memory fault has been detected in the transmitter memory by the memory verification routine. The memory fault is in a location containing transmitter information. To correct this problem, use a Field Communicator to interrogate and reconfigure the appropriate portion of the transmitter memory. This warning does not affect the transmitter operation.
Reference Manual
00809-0100-4690, Rev FC
June 2011
Operation
Normal operation messages appear on the LCD display to confirm actions or inform you of transmitter status. Operation messages are displayed with other transmitter information, and warrant no action to correct or alter the transmitter settings.
ZERO PASS
The zero value, set with the local zero adjustment button, has been accepted by the transmitter, and the output should change to 4 mA.
ZERO FAIL
The zero value, set with the local zero adjustment button, exceeds the maximum rangedown allowed for a particular range, or the pressure sensed by the transmitter exceeds the sensor limits.
SPAN PASS
The span value, set with the local span adjustment button, has been accepted by the transmitter and the output should change to 20 mA.
LOCAL DSBLD
This message appears during reranging with the integral zero and span buttons and indicates that the transmitter local zero and span adjustments have been disabled. The adjustments may have been disabled by the transmitter security jumper on the transmitter circuit board or through software commands from the Field Communicator. Refer to “Transient Protection Terminal Block” on page 2-21 for information on the position of the security jumper, and for information on the software lockout.
5-4
Page 65
Reference Manual
00809-0100-4690, Rev FC June 2011
Table 5-2. Field Communicator Messages
Rosemount 2088 and 2090
WRITE PROTECT
The write protect (SECURITY) jumper is set to disable changes to the transmitter configuration data. Refer to “Transient Protection Terminal Block” on page 2-21 for more information on the security jumper.
Field Communicator Diagnostics
Table 5-2 is a list of messages used by the Field Communicator (HC) and their corresponding descriptions.
Variable parameters within the text of a message are indicated with
<variable parameter>.
Reference to the name of another message is identified by
[another message].
Message Description
1k snsr EEPROM error-factory ON
1k snsr EEPROM error-user-no out ON
1k snsr EEPROM error-user ON 4k micro EEPROM error-factory ON 4k micro EEPROM error-user-no out ON
4k micro EEPROM error-user ON
4k snsr EEPROM error-factory ON 4k snsr EEPROM error-user ON Add item for ALL device types or only for this ONE device type.
Command Not Implemented The connected device does not support this function. Communication Error The communicator and the device are not communicating
Configuration memory not compatible with connected device
CPU board not initialized ON The electronics board is not initialized.
CPU EEPROM write failure ON Message sent to electronics board from HART signal
Device Busy The connected device is busy performing another task. Device Disconnected The device failed to respond to a command. Check all
Device write protected Device is in write-protect mode. Data can not be written.
Replace the transmitter
Use the Field Communicator to reset the following parameters: remote seal isolator, remote seal fill fluid, flange material, o-ring material, transmitter type, remote seal type, flange type, meter type, number of remote seals. Perform a full trim to recalibrate the transmitter.
Replace the electronics board.
Use the Field Communicator to reset the message field.
Use the Field Communicator to reset the following parameters: units, range values, damping, analog output, transfer function, tag, scaled meter values. Perform a D/A trim to ensure that the error is corrected. Replace the transmitter.
Use the Field Communicator to reset the temperature units and the calibration type. Asks the user whether the hot key item being added should be added for all device types or only for the type of device that is connected.
correctly. Check all connections between the Field Communicator and the device and resend the information.
The configuration stored in memory is incompatible with the device to which a transfer has been requested.
Replace the electronics board.
failed. Replace the electronics board.
connections between the Field Communicator and the device and resend the command.
5-5
Page 66
Rosemount 2088 and 2090
Message Description
Device write protected. Do you still want to shut off? Display value of variable on hotkey menu?
Download data from configuration memory to device
Exceed field width Indicates that the field width for the current arithmetic
Exceed precision Indicates that the precision for the current arithmetic
Ignore next 50 occurrences of status? Illegal character An invalid character for the variable type was entered. Illegal date The day portion of the date is invalid.
Illegal month The month portion of the date is invalid. Illegal year The year portion of the date is invalid. Incompatible CPU board and module ON Incomplete exponent The exponent of a scientific notation floating point
Incomplete field The value entered is not complete for the variable type. Looking for a device Polling for multidropped devices at addresses 1–15. Local buttons operator error ON Illegal pressure applied during zero or span operation.
Mark as read only variable on hotkey menu?
Module EEPROM write failure ON No device configuration in configuration memory No Device Found Poll of address zero fails to find a device, or poll of all
No hotkey menu available for this device. No pressure updates ON No pressure updates being received from the sensor
No offline devices available. There are no device descriptions available to be used to
No simulation devices available. There are no device descriptions available to simulate a
No temperature updates ON No temperature updates being received from the sensor
No UPLOAD_VARIABLES in ddl for this device
No Valid Items The selected menu or edit display contains no valid items. OFF KEY DISABLED Appears when the user attempts to turn the HC off before
Online device disconnected with unsent data. RETRY or OK to lose data.
Reference Manual
00809-0100-4690, Rev FC
June 2011
Device is in write-protect mode. Press YES to turn the Field communicator off and lose the unsent data.
Asks whether the value of the variable should be displayed adjacent to its label on the hotkey menu if the item being added to the hotkey menu is a variable.
Press the SEND softkey to transfer information from the communicator memory to the device.
variable exceeds the device-specified description edit format.
variable exceeds the device-specified description edit format. Select YES to ignore the next 50 occurrences of device status, or select no to display every occurrence.
Upgrade the electronics board or the sensor module to the current revision.
variable is incomplete.
Repeat the process after verifying the correct pressures. Asks whether the user should be allowed to edit the variable from the hotkey menu if the item being added to the hotkey menu is a variable. Message sent to the module from the HART signal failed. Replace the transmitter. There is no configuration saved in memory available to re-configure off-line or transfer to a device.
addresses fails to find a device if auto-poll is enabled. There is no menu named “hotkey” defined in the device description for this device.
module. Verify that the sensor module ribbon cable is attached correctly. Or replace the transmitter.
configure a device offline.
device.
module. Verify that the sensor module ribbon cable is attached correctly. Or replace the transmitter. There is no menu named “upload_variables” defined in the device description for this device. This menu is required for offline configuration.
sending modified data or before completing a method. There is unsent data for a previously connected device. Press RETRY to send data, or press OK to disconnect and lose unsent data.
5-6
Page 67
Reference Manual
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090
Message Description
Out of memory for hotkey configuration. Delete unnecessary items. Overwrite existing configuration memory
Press OK... Press the OK softkey. This message usually appears after
Restore device value? The edited value that was sent to a device was not
ROM checksum error ON Checksum of transmitter software has detected a fault.
Save data from device to configuration memory Saving data to configuration memory. Sending data to device. Data is being transferred from configuration memory to a
Sensor board not initialized ON The sensor module electronics board is not initialized.
There are write only variables which have not been edited. Please edit them. There is unsent data. Send it before shutting off? Too few data bytes received Command returns fewer data bytes than expected as
Transmitter Fault Device returns a command response indicating a fault
Units for <variable label> has changed. Unit must be sent before editing, or invalid data will be sent. Unsent data to online device. SEND or LOSE data
Upgrade 475 software to access XMTR function. Continue with old description?
Use up/down arrows to change contrast. Press DONE when done. Value out of range The user-entered value is either not within the range for
<message> occurred reading/writing <variable label>
<variable label> has an unknown value. Unit must be sent before editing, or invalid data will be sent.
There is no more memory available to store additional hotkey items. Unnecessary items should be deleted to make space available. Requests permission to overwrite existing configuration either by a device-to-memory transfer or by an offline configuration. User answers using the softkeys.
an error message from the application or as a result of HART communications.
properly implemented. Restoring the device value returns the variable to its original value.
Replace the electronics board. Prompts user to press SAVE softkey to initiate a device-to-memory transfer. Data is being transferred from a device to configuration memory.
device.
Replace the transmitter. There are write-only variables which have not been set by the user. These variables should be set or invalid values may be sent to the device. Press YES to send unsent data and turn the HC off. Press NO to turn the HC off and lose the unsent data.
determined by the device description.
with the connected device. The engineering units for this variable have been edited. Send engineering units to the device before editing this
variable.
There is unsent data for a previously connected device which must be sent or thrown away before connecting to another device. The communicator does not contain the most recent 2051 Device Descriptors (DDs). Select YES to communicate using the existing DDs. Select NO to abort communication. Gives direction to change the contrast of the HC display.
the given type and size of variable or not within the min/max specified by the device.
Either a read/write command indicates too few data bytes received, transmitter fault, invalid response code, invalid response command, invalid reply data field, or failed pre­or post-read method; or a response code of any class other than SUCCESS is returned reading a particular variable.
A variable related to this variable has been edited. Send related variable to the device before editing this variable.
5-7
Page 68
Rosemount 2088 and 2090
See “Safety Messages” on page 5-1 for complete warning information.
Reference Manual
00809-0100-4690, Rev FC
June 2011

DISASSEMBLY PROCEDURES

Do not remove the instrument cover in explosive atmospheres when the circuit is live.
Remove from Service Follow these steps:
Follow all plant safety rules and procedures.
Isolate and vent the process from the transmitter before removing the transmitter from service.
Remove all electrical leads and disconnect conduit.
Remove the transmitter from the process connection.
The Rosemount 2088 transmitter is attached to the process by a
single hex nut process connection. Loosen the hex nut to separate the transmitter from the process. Do not wrench on neck of transmitter.
Do not scratch, puncture, or depress the isolating diaphragms.
Clean isolating diaphragms with a soft rag and a mild cleaning solution and rinse with clear water.
Remove Terminal Block Electrical connections are located on the terminal block in the compartment
labeled “FIELD TERMINALS.”
1. Remove the housing cover from the field terminal side.
2. Loosen the two small screws located on the assembly in the 9 o’clock and 3 o’clock positions.
3. Pull the entire terminal block out to remove it.
Remove the Electronics Board
The transmitter electronics board is located in the compartment opposite the terminal side. To remove the electronics board perform the following procedure:
1. Remove the housing cover opposite the field terminal side.
2. If you are disassembling a transmitter with an LCD display, loosen the two captive screws that are visible on the right and left side of the meter display.
3. Loosen the two captive screws that anchor the board to the housing. The electronics board is electrostatically sensitive; observe handling precautions for static-sensitive components. Use caution when removing the LCD as there is an electronic pin connector that interfaces between the LCD and electronics board. The two screws anchor the LCD display to the electronics board and the electronics board to the housing.
4. Using the two captive screws, slowly pull the electronics board out of the housing. The sensor module ribbon cable holds the electronics board to the housing. Disengage the ribbon cable by pushing the connector release.
5-8
Page 69
Reference Manual
See “Safety Messages” on page 5-1 for complete warning information.
00809-0100-4690, Rev FC June 2011

REASSEMBLY PROCEDURES

Rosemount 2088 and 2090
Attach the Electronics Board
1. Remove the cable connector from its position inside of the internal black cap and attach it to the electronics board.
2. Using the two captive screws as handles, insert the electronics board into the housing. Make sure the posts from the electronics housing properly engage the receptacles on the electronics board. Do not force. The electronics board should slide gently on the connections.
3. Tighten the captive mounting screws.
4. Replace the electronics housing cover. The transmitter covers must be engaged metal-to-metal to ensure a proper seal and to meet Explosion-Proof requirements.
Install the Terminal Block 1. Gently slide the terminal block into place, making sure the two posts from
the electronics housing properly engage the receptacles on the terminal block.
2. Tighten the captive screws.
3. Replace the electronics housing cover. The transmitter covers must be fully engaged to meet Explosion-Proof requirements.
5-9
Page 70
Rosemount 2088 and 2090
Reference Manual
00809-0100-4690, Rev FC
June 2011
5-10
Page 71
Reference Manual
Rosemount 2088 and 2090

Appendix A Reference Data

Performance Specifications . . . . . . . . . . . . . . . . . . . . . . . page A-1
Functional Specifications . . . . . . . . . . . . . . . . . . . . . . . . . page A-2
Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-5
Spare Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page A-7
Ordering Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page A-10

PERFORMANCE SPECIFICATIONS

Conformance To Specification (±3 (Sigma))
For zero based spans, reference conditions, silicone fill fluid, SST materials, digital trim values range points. Applies to 4-20 mA HART output only unless otherwise noted.
Technology leadership, advanced manufacturing techniques, and statistical process control ensure specification conformance to at least ±3.
Reference Accuracy
2088
±0.10% of calibrated span. Includes combined effects of linearity, hysteresis, and repeatability.
+/-0.075% of calibrated span (high accuracy option P8)
2090
+/- 0.20% of calibrated span. Includes combined effects of linearity, hysteresis, and repeatability.
+/- 0.10% of calibrated span (high accuracy option P8)
Ambient Temperature Effect
2088
Expressed as a total effect per 50 °F (28 °C). Total effect includes zero and span effects.
+/- (0.15% URL + 0.15% of span) from -40 to 185 °F (-40 to 85 °C)
www.rosemount.com
2090
Expressed as a total effect per 100 °F (56 °C).
± (0.3% URL + 0.3% of span) from –40 to 185 °F (–40 to 85 °C).
Stability
±0.10% of upper range limit for 12 months.
Page 72
Rosemount 2088 and 2090
Vibration Effect
Less than ±0.1% of upper range limit when subjected to vibration of: peak to peak constant displacement of 4 mm (5–15 Hz) and constant acceleration of 2 g (15–150 Hz) and 1 g (150–2000 Hz).
Power Supply Effect
Less than 0.01% of calibrated span per volt.
Mounting Position Effect
Zero shift of up to 1.2 inH effect.
RFI Effect
Less than ±0.25% of upper range limit from 20–1000 MHz at 30 V/m with leads in conduit. Less than ±0.25% of upper range limit at 10 V/m with unshielded twisted pair (no conduit).
Trans ient Protection (Option Code T1) IEEE 587 Category B
6 kV Crest (1.2  50 s) 3 kA Crest (8  20 s) 6 kV Crest (0.5 s by 100 kHz)
Reference Manual
00809-0100-4690, Rev FC
June 2011
O (3 0.3 kPa), which can be calibrated out. No span
2

FUNCTIONAL SPECIFICATIONS

IEEE 472
SWC 2.5 kV Crest,1 MHz waveform
General Specifications
Tested to IEC 801-3.
Service
Rosemount 2088
Liquid, gas, and vapor applications.
Rosemount 2090P
Liquid, gas, vapor, and high-viscosity applications.
Rosemount 2090F
Liquid, gas, vapor, and hygienic applications.
Rangedown
20 to 1
A-2
Page 73
Reference Manual
Load (ohms)
Operating
Region
Voltage (Vdc)
Max. Loop Resistance = 43.5 (Power Supply Voltage – 10.5)
1387
1000
500
0
10.5
20 30
42.4
The Field communicator requires a minimum loop resistance of 250
for communication.
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090
Ranges for Rosemount 2088
Range Minimum Span URL/Max.span/Sensor Limit
1 1.5 psi (103 mbar) 30 psi (2,1 bar)
2 7.5 psi (517 mbar) 150 psi (10,3 bar)
3 40 psi (2,76 bar) 800 psi (55,2 bar)
4 200 psi (13,8 bar) 4000 psi (275,8 bar)
Ranges for Rosemount 2090F
Range Minimum Span URL/Max.span/Sensor Limit
1 1.5 psi (103 mbar) 30 psi (2,1 bar)
2 7.5 psi (517 mbar) 150 psi (10,3 bar)
3 40 psi (2,76 bar) 300 psi (20,7 bar)
Ranges for Rosemount 2090P
Range Minimum Span URL/Max.span/Sensor Limit
1 1.5 psi (103 mbar) 30 psi (2,1 bar)
2 7.5 psi (517 mbar) 150 psi (10,3 bar)
3 40 psi (2,76 bar) 300 psi (20,7 bar)
Protocols 4–20 mA HART (Output Code S)
Output
Two-wire 4–20 mA, user-selectable for linear or square root output. Digital process variable superimposed on 4–20 mA signal, available to any host
that conforms to the HART protocol.
Power Supply
External power supply required. Standard transmitter operates on 10.5 to
42.4 Vdc with no load.
Turn-On Time
Performance within specifications less than 2.0 seconds after power is applied to the transmitter.
Load Limitations
Maximum loop resistance is determined by the power supply voltage, as described by:
A-3
Page 74
Rosemount 2088 and 2090
1-5 Vdc HART Low Power (Output Code N)
Output
Three wire 1–5 Vdc output, user-selectable for linear or square root output. Digital process variable superimposed on voltage signal, available to any
host conforming to the HART protocol.
Power Supply
External power supply required. Standard transmitter operates on 9 to 28 Vdc with no load.
Power Consumption
3.0 mA, 27–84 mW
Output Load
100 k or greater
Turn-On Time
Performance within specifications less than 2.0 seconds after power is applied to the transmitter.
Reference Manual
00809-0100-4690, Rev FC
June 2011
Zero Elevation and Suppression
Zero can be suppressed between atmosphere for gage transmitters, or 0 psia for absolute transmitters, and upper range limit, provided the calibrated span is equal to or greater than the minimum span, and the upper range value does not exceed the upper range limit. Vacuum calibrations are allowed on the Rosemount 2088G, 2090FG, and 2090PG transmitters.
Overpressure Limits
Range 1: 120 psig max. All other ranges: twice the upper range limit.
Temperature Limits
Process
Rosemount 2088 Silicone fill sensor: –40 to 250 °F (–40 to 121 °C).
Inert fill sensor: –22 to 250 °F (–30 to 121 °C).
Rosemount 2090P –4 to 250 °F (–20 to 121 °C).
Rosemount 2090F –4 to 284 °F (–20 to 140 °C).
Process temperatures above 185 °F (85 °C) require derating the ambient limits by a 1.5:1 ratio. For example, for process temperature of 195 °F (91 °C), new ambient temperature limit is equal to 170 °F (77 °C). This can be determined as follows: (195 °F - 185 °F) x 1.5 = 15 °F, 185 °F - 15 °F = 170 °F
Ambient
Rosemount 2088 –40 to 185 °F (–40 to 85 °C).
–4 to 175 °F (–20 to 80 °C) with LCD display.
(1)
A-4
Rosemount 2090P –4 to 185 °F (–20 to 85 °C).
Rosemount 2090F –4 to 185 °F (–20 to 85 °C).
Page 75
Reference Manual
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090
Storage
Rosemount 2088 –50 to 230 °F (–46 to 110 °C).
–40 to 185 °F (–40 to 85 °C) with LCD display.
Rosemount 2090P –50 to 185 °F (–45 to 85 °C).
Rosemount 2090F –22 to 185 °F (–30 to 85 °C).
(1) LCD display may not be readable and LCD updates will be slower at temperatures below -4 °F (-20 °C).
Humidity Limits
0–100% relative humidity.
Volumetric Displacement
Less than 0.00042 cm
Failure Mode
If self-diagnostics detect a sensor or microprocessor failure, the analog signal is driven either high or low to alert the user. High or low failure mode is user-selectable with a jumper on the transmitter. The values to which the transmitter drives its output in failure mode depend on whether it is
factory-configured to standard or NAMUR-compliant operation. The values
for each are as follows:
3
.
(1)

PHYSICAL SPECIFICATIONS

Standard Operation Output Code Linear Output Fail High Fail Low
S 3.9 I 20.8 I 21.75 mA I 3.75 mA N 0.97 V 5.2 V 5.4 V V 0.95 V N with Code C2 0.78 V 3.44 V 4.0 V V 0.77 V
NAMUR-Compliant Operation
Output Code S 3.8  I  20.5 I 22.5 mA I  3.6 mA
Linear Output Fail High Fail Low
Electrical Connection
Rosemount 2088
1
/2–14 NPT, M20 x 1.5 or G 1/2 female (PF 1/2 female) conduit entry.
Rosemount 2090
1
/2–14 NPT or M20 x 1.5 conduit entry
Process Connection
Rosemount 2088
1
/2–14 NPT female, DIN 16288 G 1/2 male, RC 1/2 female (PT 1/2 female),
M20 x1.5 male.
Rosemount 2090P
M44 x 1.25 male, compatible with a 1-in. PMC
®
process connection.
Rosemount 2090F
1
/2-inch or 2-inch Tri-Clamp Connection
1
Process Wetted Parts
Isolating Diaphragm
A-5
Page 76
Rosemount 2088 and 2090
Rosemount 2088 316L stainless steel or Alloy C-276. Rosemount 2090P 316L stainless steel. Rosemount 2090F 316L stainless steel.
Process Connector
Rosemount 2088 316L stainless steel or Alloy C-276. Rosemount 2090P 316L stainless steel.
Rosemount 2090F 316L stainless steel.
Non-wetted Parts
Electronics Housing
Low-copper aluminum, NEMA 4X, IP65, IP67, CSA enclosure Type 4X.
Paint
Polyurethane.
Cover O-rings
Buna-N.
Fill Fluid
Rosemount 2088 Silicone or inert fill Rosemount 2090P Silicone Rosemount 2090F Neobee M20
Weight
Rosemount 2088 Approximately 2.44 lb. (1,11 kg). Rosemount 2090P Approximately 2.96 lb. (1,34 kg). Rosemount 2090F Approximately 2.74 lb. (1,24 kg).
Reference Manual
00809-0100-4690, Rev FC
June 2011
TFE process connector gasket.
Accessory Block and Bleed Valve (S5 Option)
For information on Rosemount 306 Integral Manifold (pre-assembled to transmitter and leak checked), refer to Product Data Sheet 00813-0100-4733.
A-6
Page 77
Reference Manual
4
3
2
7
8
Figure A-1. Replacement Parts for the Rosemount 2088.
6
5
LCD Display Cover Assembly includes LCD Cover and O-ring
1
2
1
00809-0100-4690, Rev FC June 2011

SPARE PARTS .

Rosemount 2088 and 2090
Item No. Part Description Part Number Spares Category
Transmitters (Output Code S)
1, 2
6 LCD Display Cover Assembly 03031-0193-0002 B
2 Cover O-rings 03031-0232-0001 B
3 3
4
5, 6
5
7 Local Zero and Span Kit 3031-0293-0002 A
8 8
(1) One spare part is recommended for every 25 transmitters in category A, and one spare part for every 50 transmitters in
category B.
Electronics Cover (with O-ring) 03031-0292-0001
Electronics Board Kits S Output (4–20 mA/Digital HART Protocol) S Output (NAMUR Compliant Operation)
Optional Mounting Bracket (with 2-inch U-Bolt for Pipe Mounting) 02088-0071-0001
LCD Display Kit with Cover LCD Display Kit without Cover
Standard Terminal Block Transient Protection Block
(1)
02088-0306-0002 02088-0306-0003
03031-0193-0101 03031-0193-0103
03031-0332-0011 03031-0332-0012
A A
A
B B
A-7
Page 78
Rosemount 2088 and 2090
LCD Display Cover Assembly includes LCD Cover and O-ring
9
10
11
Item No. Part Description Part Number
1,2
Transmitters (Output Code S) Electronics Cover (with O-ring) 03031-0292-0001
10 LCD Display Cover Assembly 03031-0193-0002
2 Cover O-rings 03031-0232-0001
3 3
Electronics Boards S Output (4–20 mA/Digital HART Protocol) S Output (NAMUR Compliant Operation)
02088-0306-0002 02088-0306-0003
4
Optional Mounting Bracket (with 2-inch U-Bolt for Pipe Mounting) 02088-0071-0001
9, 10
9
LCD Display Kit with Cover LCD Display Kit without Cover
03031-0193-0101 03031-0193-0103
8 Calibration Adapter 02088-0197-0001
5 PTFE Gaskets (package of 12) 02088-0078-0001
6 7
316 SST Weld Spud with Heat Isolator Groove 316 SST Plug/Heat Sink
02088-0295-0003 02088-0196-0001
11 11
Standard Terminal Block Transient Terminal Block
03031-0332-0011 03031-0332-0012
1-in. Flush Mount Weld Spud 02088-0285-0001
1-in. Flush Mount Calibration Adapter 02088-0198-0002
1
1
/2-in. Threaded Weld Spud Kit 02088-0295-0003
8
4
1
2
3
5
6
7
Figure A-2. Replacement Parts for the Rosemount 2090P.
Reference Manual
00809-0100-4690, Rev FC
June 2011
A-8
Page 79
Reference Manual
LCD Display Cover Assembly includes LCD Cover and O-ring
4
5
NOTE: Sanitary clamp and gasket to be supplied by user.
Item No. Part Description Part Number
1
Transmitters (Output Code S) Electronics Cover (with O-ring) 03031-0292-0001
5 LCD Display Cover Assembly 03031-0193-0002
2 O-rings 03031-0232-0001
3 3
Electronics Boards S Output (4–20 mA/Digital HART Protocol) S Output (NAMUR Compliant Operation)
02088-0306-0002 02088-0306-0003
7
Optional Mounting Bracket (with 2-inch U-Bolt for Pipe Mounting) 02088-0071-0001
4, 5
4
LCD Display Kit with Cover LCD Display Kit without Cover
03031-0193-0101 03031-0193-0103
6 6
Calibration Adapter, 1
1
/2 inch
Calibration Adapter, 2 inch
02088-0197-0011 02088-0197-0012
8 8
Standard Terminal Block Transient Terminal Block
03031-0332-0011 03031-0332-0012
6
1
2
3
7
8
00809-0100-4690, Rev FC June 2011
Figure A-3. Replacement Parts for the Rosemount 2090F.
Rosemount 2088 and 2090
A-9
Page 80
Reference Manual
00809-0100-4690, Rev FC
Rosemount 2088 and 2090
June 2011

ORDERING INFORMATION

Table A-1. Rosemount 2088 Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
Model Product description
2088 Pressure Transmitter
Transmitter Type
Standard Standard
A Absolute
G Gage
Pressure Ranges
Standard Standard
2088G 2088A
1 -14.7 to 30 psi /(-1,01 to 2,1 bar) 0 to 30 psi (0 to 2,1 bar) 2 -14.7 to 150 psi (-1,01 to 10,3 bar) 0 to 150 psi (0 to 10,3 bar) 3 -14.7 to 800 psi (-1,01 to 55,2 bar) 0 to 800 psi (0 to 55,2 bar) 4 -14.7 to 4,000 psi(-1,01 to 275,8 bar) 0 to 4,000 psi (0 to 275,8 bar)
Transmitter Output
Standard Standard
S 4–20 mA dc/Digital HART® Protocol N 1-5 Vdc Low Power/ Digital HART protocol
Materials of Construction
Standard Standard
Process connection Isolating diaphragm Fill Fluid
(1)
22 33
Expanded
2B
Process Connection
Standard Standard
A ½–14 NPT Female
B
(2)(3)
D
Expanded
(2)(3)
C
Conduit Entry
Standard Standard
1 ½–14 NPT
2
Expanded
4
316L SST 316L SST Silicone
(1)
Alloy C-276 Alloy C-276 Silicone
(1)
316L SST 316L SST Inert
(2)
DIN 16288 G ½ Male M20 1.5 Male
RC ½ Female (PT ½ Female)
(2)
M20 1.5 Female
(2)
G ½ Female (PF ½ Female)
Options (Include with selected model number)
Diaphragm seal assemblies
Standard Standard
(4)(5)
S1
Display and Interface Options
Standard Standard
M5 LCD display, configured for percent of range M7 LCD display, configured for engineering units
A-10
Assemble to one Rosemount 1199 diaphragm seal
Page 81
Reference Manual
00809-0100-4690, Rev FC June 2011
Table A-1. Rosemount 2088 Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
Mounting Brackets
Standard Standard
B4 SST mounting bracket with SST Bolts
Product Certifications
Standard Standard
C6 CSA Explosion-Proof, Intrinsically Safe, and non-Incendive E2 INMETRO Flameproof E3 China Flameproof
(2)(6)
E4
E5 FM Explosion-Proof, Dust Ignition-proof E7 IECEx Flameproof
ED ATEX Flameproof
I1
I2 INMETRO Intrinsic Safety I3 China Intrinsic Safety I5 FM Intrinsically safe, Division 2
I7 SAA Intrinsic Safety K1 ATEX Flameproof, Intrinsic Safety, Type n, Dust K5 FM Explosion-Proof, Dust Ignition-proof, Intrinsically Safe, Division 2
K6
K7 SAA Intrinsic Safety and Type n; IECEx Flameproof and Dust
KB FM and CSA Explosion-proof, Dust Ignition-proof, Intrinsically Safe, Division 2
KH
N1
N3 China Type n N7 SAA Type n
ND
NK IECEx Dust
Shipboard Approvals
Standard Standard
SBS American Bureau of Shipping (ABS) Type Approval SBV Bureau Veritas (BV) Type Approval SDN Det Norske Veritas (DNV) Type Approval
SLL Lloyd's Register (LR) Type Approval
Pressure Testing Expanded
P1 Hydrostatic testing
Terminal Block
Standard Standard
T1 Transient protection
Special Cleaning Expanded
P2 Cleaning for special service
Calibration Certificate
Standard Standard
Q4 Calibration certificate
Quality Traceability Certification
Standard Standard
Q8 Material Traceability Certification per EN 10204 3.1B
TIIS Flameproof
(2)
ATEX Intrinsic Safety
(2)
ATEX and CSA Explosion-Proof, Dust Ignition-proof, Intrinsically Safe, Division 2
(2)
FM Approvals and ATEX Explosion-Proof and Intrinsically Safe
(2)
ATEX Type n
(2)
ATE X D ust
Rosemount 2088 and 2090
A-11
Page 82
Reference Manual
00809-0100-4690, Rev FC
Rosemount 2088 and 2090
Table A-1. Rosemount 2088 Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
Digital Signal
Standard Standard
(2)
C4
CN
Configuration
Standard Standard
C9 Software configuration
Manifold Assemblies
Standard Standard
S5
Calibration Accuracy
Standard Standard
P8
Water Approval
Standard Standard
DW
Low Output for Low Power Expanded
C2 0.8 - 3.2 Vdc output with HART protocol, Output code N only.
Surface Finish
Standard Standard
Q16 Surface finish certification for sanitary remote seals
Toolkit Total System Performance Reports
Standard Standard
QZ Remote Seal System Performance Calculation Report
Typical Model Number: 2088 G 2 S 22 A 1 B4 M5
(1) Materials of Construction comply with recommendations per NACE MR0175/ISO 15156 for sour oil field production environments. Environmental limits
apply to certain materials. Consult latest standard for details. Selected mat erials also conform to NACE MR0103 for sour refining environments. (2) Not available with low-power Output code N. (3) Not available with (4) Use (5) “Assemble-to” items are specified separately and require a completed model number. (6) Only available with Conduit Thread code 4. (7) Available with Output code S, stainless steel isolators, and silicone fill. (8) Requires Materials of Construction code 22 with Proc ess Connection code A.
NAMUR alarm and saturation levels, high alarm
(2)
NAMUR alarm and saturation levels, low alarm
(4)(5)
Assemble to Rosemount 306 integral manifold
(7)
0.075% accuracy to 10:1 turndown
(8)
NSF drinking water approval
1
/2 - 14 NPT Female Process Connection code A.
Alloy C-276, Materials of Construction code 33.
June 2011
A-12
Page 83
Reference Manual
00809-0100-4690, Rev FC June 2011
Table A-2. Rosemount 2090P Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
Model Product Description
2090P Pulp & Paper Pressure Transmitter
Transmitter Type Standard Standard
A Absolute G Gage
Pressure Ranges
Range
Standard Standard
1 0–30 psi (0–2.1 bar) 2 0–150 psi (0–10.3 bar) 3 0–300 psi (0–20.7 bar)
Output Standard Standard
S 4–20 mA dc/Digital HART Protocol
Material of Construction
Process Connection Isolating Diaphragm Fill Fluid
Standard Standard
22 316L SST 316L SST Silicone
Process Connection Standard Standard
A 1 1/2-in. Threaded, No Weld Spud, 1 1/2-in. PTFE Gasket C 1 1/2-in. Threaded, 316L SST Weld Spud with Stress Isolation and PTFE Gasket D 1-in. Flush Mount G 1-in. Flush Mount with weld-on nipple
Conduit Entry Standard Standard
1
1 2 M20 1.5
/2–14 NPT
Rosemount 2088 and 2090
Options (Include with selected model number)
Digital Display Standard Standard
M5 LCD display, configured for percent of range M7 LCD display, configured for engineering units
Mounting Brackets Standard Standard
B4 SST mounting bracket with SST Bolts
Product Certifications Standard Standard
E5 FM Explosion-Proof, Dust Ignition-proof
ED ATEX Flameproof
I5 FM Intrinsically safe, Division2
K5 FM Explosion-Proof, Dust Ignition-proof, Intrinsically Safe, Division 2
I1 ATEX Intrinsic Safety N1 ATEX Type n C6 CSA Explosion-Proof, Intrinsically Safe, and Non-incendive
KB FM and CSA Explosion-Proof, Dust Ignition-proof, Intrinsically Safe, Division 2 KH FM Approvals and ATEX Explosion-Proof and Intrinsically Safe ND ATEX Dust
A-13
Page 84
Reference Manual
00809-0100-4690, Rev FC
Rosemount 2088 and 2090
Table A-2. Rosemount 2090P Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
NK IECEx Dust
K7 SAA Flameproof, Dust Ignition-proof, Intrinsic Safety, Type n; IECEx Flameproof and Dust K1 ATEX Flameproof, Intrinsic Safety, Type n, Dust K6 CSA and ATEX Explosion-Proof and Intrinsically Safe Approvals
I3 China Intrinsic Safety E3 China Flameproof
Terminal Blocks Standard Standard
T1 Transient Protection
Special Certificate Standard Standard
Q4 Calibration Certificate
Alarm Limit Standard Standard
C4 NAMUR alarm and saturation levels, high alarm
CN NAMUR alarm and saturation levels, low alarm
Wetted O-ring Material Standard Standard
W2 Buna-N W3 Ethylene-Propylene
Special Procedures Expanded
P2 Cleaning for Special Service
Calibration Accuracy Standard Standard
P8 0.1% Accuracy to 10:1 Turndown
P Specials Standard Standard
PXXXX Special that needs to be created
Typical Model Number: 2090PG 2 S 22 A 1
June 2011
A-14
Page 85
Reference Manual
00809-0100-4690, Rev FC June 2011
Table A-3. Rosemount 2090F Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
Model Product Description
2090F Hygienic Pressure Transmitter
Transmitter Type Standard Standard
A Absolute G Gage
Pressure Ranges
Range
Standard Standard
1 0–30 psi (0–2 bar) 2 0–150 psi (0–10.3 bar) 3 0–300 psi (0–20.7 bar)
Output Standard Standard
S 4–20 mA dc/Digital HART Protocol
Material of Construction
Process Connection Isolating Diaphragm Oil Fill
Standard Standard
2D 316L SST 316L SST Neobee
Code Process Connection
Standard Standard
E 1
F 2–in. Tri-Clamp Connection
Conduit Entry Standard Standard
1 2 M20 1.5
1
/2–in. Tri-Clamp Connection
1
/2–14 NPT
Rosemount 2088 and 2090
Options (Include with selected model number)
Digital Display Standard Standard
M5 LCD display, configured for percent of range M7 LCD display, configured for engineering units
Mounting Brackets Standard Standard
B4 SST mounting bracket with SST Bolts
Product Certifications Standard Standard
E5 FM Explosion-Proof, Dust Ignition-proof
ED ATEX Flameproof
I5 FM Intrinsically safe, Division2 K5 FM Explosion-Proof, Dust Ignition-proof, Intrinsically Safe, Division 2
I1 ATEX Intrinsic Safety N1 ATEX Type n C6 CSA Explosion-Proof, Intrinsically Safe, and Non-incendive
KB FM and CSA Explosion-Proof, Dust Ignition-proof, Intrinsically Safe, Division 2 KH FM Approvals and ATEX Explosion-Proof and Intrinsically Safe ND ATEX Dust NK IECEx Dust
K7 SAA Flameproof, Dust Ignition-proof, Intrinsic Safety, Type n; IECEx Flameproof and Dust
A-15
Page 86
Reference Manual
00809-0100-4690, Rev FC
Rosemount 2088 and 2090
Table A-3. Rosemount 2090F Ordering Information
The Standard offering represents the most common options. The starred options () should be selected for best delivery.
__The Expanded offering is manufactured after receipt of order and is subject to additional delivery lead time.
K1 ATEX Flameproof, Intrinsic Safety, Type n, Dust K6 CSA and ATEX Explosion-Proof and Intrinsically Safe Approvals
I3 China Intrinsic Safety E3 China Flameproof
Terminal Blocks Standard Standard
T1 Transient Protection
Special Certificate Standard Standard
Q4 Calibration Certificate
Alarm Limit Standard Standard
C4 NAMUR alarm and saturation levels, high alarm
CN NAMUR alarm and saturation levels, low alarm
Wetted O-ring Material Standard Standard
W2 Buna-N W3 Ethylene-Propylene
Special Procedures Expanded
P2 Cleaning for Special Service
Calibration Accuracy Standard Standard
P8 0.1% Accuracy to 10:1 Turndown
P Specials Standard Standard
PXXXX Special that needs to be created
Typical Model Number: 2090FG 2 S 2D E 1
June 2011
A-16
Page 87
Reference Manual
Rosemount 2088 and 2090

Appendix B Approval Information

OVERVIEW This Appendix contains information on approved manufacturing locations,

European directive information. Ordinary Location certification, Hazardous Locations Certifications and approval drawings.
Approved Manufacturing Locations
European Directive Information
Hazardous Locations Certifications
Rosemount Inc. — Chanhassen, Minnesota USA Emerson Process Management GmbH & Co. — Wessling, Germany Emerson Process Management Asia Pacific Private Limited — Singapore Beijing Rosemount Far East Instrument Co., LTD — Beijing, China
The EC declaration of conformity for all applicable European directives for this product can be found on the Rosemount website at www.rosemount.com. A hard copy may be obtained by contacting our local sales office.
ATEX Directive (94/9/EC)
Emerson Process Management complies with the ATEX Directive.
European Pressure Equipment Directiv e (PED ) (9 7/ 23 /EC)
2088/2090 Pressure Transmitters
— Sound Engineering Practice
Electro Magnetic Compatibility (EMC) (2004/108/EC)
All Model 2088/2090 Pressure Transmitter: EN 61326-1:2006
North American Certifications
Factory Mutual (FM) E5 Explosion-proof for Class I, Division 1, Groups B, C, and D.
Dust-Ignition-Proof for Class II, Division 1, Groups E, F, G, Class III, Division 1, indoor and outdoor (NEMA 4X) hazardous locations; factory sealed. Temperature Class T5 Ta = 85 °C.
I5 Intrinsically safe for use in Class I, Division 1, Groups A, B, C, D; Class II,
Division 1, Groups E, F, and G; and Class III, Division 1 when connected in accordance with Rosemount drawing 02088-1018. Non-incendive for Class I, Division 2, Groups A, B, C, and D. Temperature Class T4 Ta = 85 °C; indoor and outdoor (NEMA 4X) hazardous locations. For input parameters see control drawing 02088-1018.
www.rosemount.com
Canadian Standards Association (CSA)
2088 CSA hazardous approved transmitters are certified per ANSI/ISA
12.27.01-2003.
Page 88
Rosemount 2088 and 2090
C6 Explosion-proof for Class I, Division 1, Groups B, C, and D.
Dust-Ignition-Proof for Class II, Division 1, Groups E, F, G, Class III, indoor and outdoor hazardous locations. CSA enclosure Type 4X; factory sealed. Suitable for Class I, Division 2, Groups A, B, C, and D. 2088 is Single Seal.
Intrinsically Safe for Class I, Division 1, Groups A, B, C, and D. Temp. Code T3C. Intrinsically safe when connected with approved barriers in accordance with Rosemount drawing 02088-1024. 2088 is Single Seal. For input parameters see control drawing 02088-1024.
European Certifications I1 BASEEFA ATEX Intrinsic Safety
Certificate No.: BAS00ATEX1166X II 1 G Ex ia IIC T5 (–55 °C  T Ex ia IIC T4 (–55 °C  T
1180
Table B-1. Input Parameters
Loop/Power
Ui = 30 Vdc Ii = 200 mA Pi = 0.9 W Ci = 0.012 F
40 °C)
amb
70 °C)
amb
Reference Manual
00809-0100-4690, Rev FC
June 2011
Special Conditions for Safe Use (x):
When the optional transient protection terminal block is installed, the apparatus is not capable of withstanding a 500 V r.m.s. test to case. This must be taken into account on any installation in which it is used, for example by assuring that the supply to the apparatus is galvanically isolated.
N1 BASEEFA ATEX Type n
Certification No.: BAS00ATEX3167X II 3 G Ex nA nL IIC T5 (-40 °C  T
= 50 Vdc max
U
i
amb
70 °C)
Special Conditions for Safe Use (x):
When the optional transient protection terminal block is installed, the apparatus is not capable of withstanding a 500 V r.m.s. test to case. This must be taken into account on any installation in which it is used, for example, by assuring that the supply to the apparatus is galvanically isolated.
ND BASEEFA ATEX Dust
Certificate No.: BAS01ATEX1427X II 1 D Ex tD A20 T105°C (-20 °C  T
amb
85 °C)
IP66
1180
Vmax = 36 Vdc
B-2
Page 89
Reference Manual
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090
Special Conditions for Safe Use (x):
1. The user must ensure that the maximum rated voltage and current (36 volts, 24 mA, D.C.) are not exceeded. All connections to other apparatus or associated apparatus shall have control over this voltage and current equivalent to a category “ib” circuit according to EN50020.
2. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.
3. Unused cable entries must be filled with suitable blanking plugs which maintain the ingress protection of the enclosure to at least IP66.
4. Cable entries and blanking plugs must be suitable for the ambient range of the apparatus and capable of withstanding a 7J impact test.
5. The 2088/2090 sensor module must be securely screwed in place to maintain the ingress protection of the enclosure.
ED KEMA ATEX Flameproof
Certification No.: KEMA97ATEX2378X II 1/2 G Ex d IIC T6 (-40 °C  T
T4 (-40 °C  T
1180 Vmax = 36 Vdc (with Output Code S) Vmax = 14 Vdc (with Output Code N)
80 °C)
amb
40 °C)
amb
Special Conditions for Safe Use (x):
1. The cable and conduit entry devices shall be of a certified flameproof type Ex d, suitable for the conditions of use and correctly installed.
2. With the use of conduit entries a sealing device shall be provided immediately on the entrance thereto.
3. Unused apertures shall be closed with suitable Ex d certified blanking elements.
4. Suitable heat-resisting cables shall be used when the ambient temperature at the cable or conduit entries exceed 65 ˚C.
5. This device contains a thin wall diaphragm. Installation, maintenance, and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer's instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
6. For information on the dimensions of the flameproof joints the manufacturer shall be contacted.
Japanese Certifications E4 TIIS Flameproof
Ex d IIC T6 (T
= 85 °C)
amb
B-3
Page 90
Rosemount 2088 and 2090
Certificate Description
TC15874 2088 with Alloy C-276 wetted parts (with display) TC15873 2088 with Alloy C-276 wetted parts (no display) TC15872 2088 with SST wetted parts (with display) TC15871 2088 with SST wetted parts (no display)
Australian Certifications I7 SAA Intrinsic Safety
Certification No.: AUS Ex 1249X
Ex ia IIC T4 (T
Ex ia IIC T5 (T
IP66
When connected per Rosemount drawing 03031-1026
amb
amb
Reference Manual
00809-0100-4690, Rev FC
June 2011
= 70 °C)
= 40 °C)
Table B-2. Input Parameters
Loop/Power
U
= 30 V
max
I
= 200 mA
max
P
= 0.9 W
max
Ci = 0.01 F Li = 10 H
Special Conditions for Safe Use (X):
Observe barrier/entity parameters during installation. A passive current limited power source must be used. The power source must be such that Po (Uo * Io)/4. For modules using transient protection in the terminal assembly (T1 transient protection models), the apparatus enclosure is to be electrically bonded to the protective earth. The conductor used for the connection shall be equivalent to a copper conductor of 4mm cross-sectional area.
N7 SAA Type n (Non-Sparking)
Certificate No.: AUS Ex 1249X
Ex n IIC T4 (T
Ex n IIC T5 (T
= 70 °C)
amb
= 40 °C)
amb
IP66
Special Conditions for Safe Use (X):
Where the equipment is installed such that there is an unused conduit entry, it must be sealed with a suitable blanking plug to maintain the IP66 degree of protection. Any blanking plug used with the equipment shall be of a type which requires the use of a tool to effect its removal. Voltage source shall not exceed 60 Vac or 75 Vdc.
NK IECEx Dust Ignition Proof
IECEx Certificate number: IECEx KEM 06.0021X
Ex tD A22 IP66 T90°C (-20 °C  T
80 °C)
amb
Vmax = 55 Vdc
Ii = 23 mA
2
minimum
B-4
Page 91
Reference Manual
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm. Installation, maintenance, and use shall take into account the environmental conditions to which the diaphragm will be subjected. The manufacturer’s instructions for installation and maintenance shall be followed in detail to assure safety during its expected lifetime.
2. Cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.
3. Unused cable entries must be used which maintain the ingress protection of the enclosure to at least IP66.
4. Cable entries and blanking plugs must be suitable for the ambient range of the apparatus and capable of withstanding a 7J impact.
5. The 2088/2090 sensor module must be securely screwed in place to maintain the ingress protection of the enclosure.
E7 KEMA IECEx Flameproof
Certification No.: IECEx KEM 06.0021X
Ex d IIC T4 (-40 °C  T
1180
Vmax = 36 Vdc (with Output Code S)
Vmax = 14 Vdc (with Output Code N)
80 °C)
amb
Brazil Certifications I2 INMETRO Intrinsic Safety
Certification No.: CEPEL-Ex-063/97-1X BR-Ex ia IIC T5/T4
Special Conditions for Safe Use (X):
Only the sensor piezo-resistive can be installed in Zone 0. The transmitter must be installed in Zone 1 or 2.
E2 INMETRO Flameproof
Certification No.: CEPEL-Ex-076/97-1 BR-Ex d IIC T6/T5
China Certifications I3 China (NEPSI) Intrinsic Safety
NEPSI Certificate No. (2088 manufactured in Chanhassen, MN): GYJ111063X NEPSI Certificate No. (2088 manufactured in Beijing, China): GYJ071129
NEPSI Certificate No. (2088 manufactured in Singapore): GYJ111063X NEPSI Certificate No. (2090 Manufactured in Beijing, China): GYJ071131 2090 RTC & SMMC Certificate No. GYJ111065X Ex ia IIC T4
B-5
Page 92
Rosemount 2088 and 2090
Special Conditions for Safe Use
1. Symbol “X” is used to denote specific conditions of use:
• This apparatus is not capable of withstanding the 500 V r.m.s. insulation test required by Clause 6.4.12 of GB3836.4-2000.
2. The ambient temperature range is:
3. Intrinsically safe parameters:
Maximum
input voltage:
4. The pressure transmitter should be used with Ex-certified linear associated apparatus to establish explosion protection system that can be used in explosive gas atmospheres. Wiring and terminals should comply with the instruction manual of the pressure transmitter and associated apparatus.
5. The cable between the pressure transmitter and associated apparatus should be insulated, shielded cable. The cable shield must be grounded in a non-hazardous area.
6. End users are not permitted to change internal components. Contact the manufacturer to avoid damaging the pressure transmitter.
7. During installation, use, and maintenance of the pressure transmitter, observe the following standards:
Reference Manual
00809-0100-4690, Rev FC
T Code Ambient Temperature
T5 -55°C Ta 40 °C T4 -55°C Ta 70 °C
Maximum
(V)
U
i
30 200 0.9 112 0
input current:
(mA)
I
i
Maximum
input power:
(W)
P
i
Maximum Internal Parameters
Ci(nF) Li (mH)
June 2011
a. GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus used in explosive gas atmospheres”
b. GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)”
c. GB3836.16-2006 “Electrical apparatus for explosive gas atmospheres Part 16: Inspection and maintenance of electrical installation (other than mines)”
d. GB50257-1996 “Code for construction and acceptance of electric device for explosion atmospheres and fire hazard electrical equipment installation engineering”
B-6
Page 93
Reference Manual
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090
E3 China (NEPSI) Flameproof
NEPSI Certificate No. (2088 manufactured in Chanhassen, MN):
GYJ111062
NEPSI Certificate No. (2088 manufactured in Beijing, China):
GYJ071128 NEPSI Certificate No. (2090 manufactured in Beijing, China): GYJ071130 2090 RTC & SMMC Certificate No. GYJ111065X
NEPSI Certificate No. (2088 manufactured in Singapore): GYJ111062
Ex d IIB+H2 T4/T5
Special Conditions for Safe Use
1. The ambient temperature range is:
T Code Ambient Temperature
T6 -20°C Ta 40 °C T4 -20°C Ta 80 °C
2. The earth connection facility on the enclosure should be connected reliably.
3. During installation in a hazardous location, use cable glands, conduits, and blanking plugs that are certified by state-appointed inspection bodies with Ex d IIC type protection.
4. During installation, use, and maintenance in explosive gas atmospheres, observe the warning, “Do not open when energized.”
5. During installation, there should be no mixture harm to flameproof housing.
6. End users are not permitted to change internal components. Contact the manufacturer to avoid damaging the pressure transmitter.
7. Maintenance should be done in non-hazardous locations.
8. During installation, use, and maintenance of the pressure transmitter, observe the following standards:
a. GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus used in explosive gas atmospheres”
b. GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)”
c. GB3836.16-2006 “Electrical apparatus for explosive gas atmospheres Part 16: Inspection and maintenance of electrical installation (other than mines)”
d. GB50257-1996 “Code for construction and acceptance of electric device for explosion atmospheres and fire hazard electrical equipment installation engineering”
B-7
Page 94
Rosemount 2088 and 2090
N3 China Type n Non - Sparking
NEPSI Cert No. (2088 manufactured in Beijing, China): GYJ101126X
Ex nA nL IIC T5
Special Conditions for Safe Use (x)
1. Symbol “X” is used to denote specific conditions of use: The apparatus is not capable of withstanding the 500 V test to earth for one minute. This must be taken into consideration during installation.
2. The ambient temperature range of the device is: -40 °C Ta 70 °C.
3. Minimum input voltage is 50 V.
4. Metal cable glands, conduit, or blanking plugs, certified by NEPSI with Ex e or Ex n protection type should be used on external connections and redundant cable entries.
5. Maintenance should be done in non-hazardous locations.
6. End users are not permitted to change any internal components.
7. During installation, use, and maintenance of the pressure transmitter, observe the following standards:
Reference Manual
00809-0100-4690, Rev FC
June 2011
a. GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus used in explosive gas atmosphere”
b. GB3836.15-2000 “Electrical apparatus for explosive gas atmospheres Part 15: Electrical installations in hazardous area (other than mines)”
c. GB3836.16-2006 “Electrical apparatus for explosive gas atmospheres Part 16: Inspection and maintenance of electrical installation (other than mines)”
d. GB50257-1996 “Code for construction and acceptance of electric device for explosion atmospheres and fire hazard electrical equipment installation engineering”
Combinations of Certifications
Stainless steel certification tag is provided when optional approval is specified. Once a device labeled with multiple approval types is installed, it should not be reinstalled using any other approval types. Permanently mark the approval label to distinguish it from unused approval types.
KB K5 and C6 combination KH K5, ED, and I1 combination K5 E5 and I5 combination K6 C6, I1, and ED combination K7 I7, N7, E7, and NK combination K1 I1, N1, ED, and ND combination
B-8
Page 95
Reference Manual
00809-0100-4690, Rev FC June 2011
Figure B-1. F.M. Intrinsically Safe Approvals for Rosemount 2088 and 2090
Rosemount 2088 and 2090
B-9
Page 96
Rosemount 2088 and 2090
Reference Manual
00809-0100-4690, Rev FC
June 2011
B-10
Page 97
Reference Manual
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090
B-11
Page 98
Rosemount 2088 and 2090
Reference Manual
00809-0100-4690, Rev FC
June 2011
B-12
Page 99
Reference Manual
00809-0100-4690, Rev FC June 2011
Rosemount 2088 and 2090
B-13
Page 100
Rosemount 2088 and 2090
Reference Manual
00809-0100-4690, Rev FC
June 2011
B-14
Loading...