Rosemount 2088, 2090P, and 2090F
Pressure Transmitters
with 4-20 mA HART and 1-5 Vdc Low Power Protocol
www.rosemount.com
Reference Manual
NOTICE
00809-0100-4690, Rev FC
June 2011
Rosemount 2088 and 2090
Rosemount 2088, 2090F, and
2090P Pressure Transmitters
Read this manual before working with the product. For personal and system safety, and for
optimum product performance, make sure you thoroughly understand the contents before
installing, using, or maintaining this product.
For technical assistance, contacts are listed below:
Customer Central
Technical support, quoting, and order-related questions.
United States - 1-800-999-9307 (7:00 am to 7:00 pm CST)
Asia Pacific- 65 777 8211
Europe/ Middle East/ Africa - 49 (8153) 9390
North American Response Center
Equipment service needs.
1-800-654-7768 (24 hours—includes Canada)
Outside of these areas, contact your local Emerson Process Management representative.
The products described in this document are NOT designed for nuclear-qualified
applications. Using non-nuclear qualified products in applications that require
nuclear-qualified hardware or products may cause inaccurate readings.
For information on Rosemount nuclear-qualified products, contact your local Emerson
Process Management Sales Representative.
USING THIS MANUALThe sections in this manual provide information on installing, operating, and
maintaining Rosemount 2088, 2090F, and 2090P pressure transmitters with
®
HART
protocol. The sections are organized as follows:
•Section 2: Installation contains mechanical and electrical installation
instructions.
•Section 3: Configuration provides instruction on commissioning and
operating Rosemount 2088, 2090F, and 2090P transmitters.
Information on software functions, configuration parameters, and online
variables is also included.
•Section 4: Operation and Maintenance contains operation and
maintenance techniques.
•Section 5: Troubleshooting provides troubleshooting techniques for
the most common operating information.
•Appendix A: Reference Data supplies reference and specification
data, as well as ordering information.
•Appendix B: Approval Information contains intrinsic safety approval
information, European ATEX directive information, and approval
drawings.
•Appendix C: Glossary
SERVICE SUPPORTTo expedite the return process outside of the United States, contact the
nearest Emerson Process Management representative.
Within the United States, call the Emerson Process Management Instrument
and Valves Response Center using the 1-800-654-RSMT (7768) toll-free
number. This center, available 24 hours a day, will assist you with any needed
information or materials.
www.rosemount.com
Reference Manual
00809-0100-4690, Rev FC
Rosemount 2088 and 2090
The center will ask for product model and serial numbers and will provide a
Return Material Authorization (RMA) number. The center will also ask for the
process material to which the product was last exposed.
Individuals who handle products exposed to a hazardous substance can avoid injury if they
are informed of and understand the hazard. If the product being returned was exposed to a
hazardous substance as defined by OSHA, a copy of the required Material Safety Data Sheet
(MSDS) for each hazardous substance identified must be included with the returned goods.
Emerson Process Management Instrument and Valves Response Center
representatives will explain the additional information and procedures
necessary to return goods exposed to hazardous substances.
June 2011
MODELS COVEREDThe following Rosemount Pressure Transmitters are covered by this manual:
Rosemount 2088 Pressure Transmitter
2088G - Gage Pressure Transmitter
Measures gage pressure up to 4000 psi (275,8 bar)
PRODUCT
RECYCLING/DISPOSAL
2088A - Absolute Pressure Transmitter
Measures absolute pressure up to 4000 psi (275,8 bar)
Rosemount 2090F Hygienic Pressure Transmitter
2090FG - Gage Pressure Transmitter
Measures gage pressure up to 300 psi (20,7 bar)
2090FA - Absolute Pressure Transmitter
Measures absolute pressure up to 300 psi (20,7 bar)
Rosemount 2090P Pulp & Paper Pressure Transmitter
2090PG - Gage Pressure Transmitter
Measures gage pressure up to 300 psi (20,7 bar)
2090PA - Absolute Pressure Transmitter
Measures absolute pressure up to 300 psi (20,7 bar)
Recycling of equipment and packaging should be taken into consideration
and disposed of in accordance with local and national legislation/regulations.
OVERVIEWThe information in this section covers installation considerations for the
Rosemount 2088, 2090F, and 2090P transmitters with HART protocols. A
Quick Installation Guide (document number 00825-0100-4690) is shipped
with every transmitter to describe basic pipe-fitting and wiring procedures for
initial installation.
Field Communicator and AMS Device Manager instructions are given to
perform configuration functions. For convenience, Field Communicator fast
key sequences are labeled “Fast Keys” for each software function below the
appropriate headings.
SAFETY MESSAGESInstructions and procedures in this section may require special precautions to
ensure the safety of the personnel performing the operations. Information that
raises potential safety issues is indicated by a warning symbol ( ). Refer to
the following safety messages before performing an operation preceded by
this symbol.
www.rosemount.com
Rosemount 2088 and 2090
Warnings
Explosions could result in death or serious injury:
Installation of this transmitter in an explosive environment must be in accordance with
the appropriate local, national, and international standards, codes, and practices.
Please review the approvals section of the reference manual for any restrictions
associated with a safe installation.
• Before connecting a Field Communicator in an explosive atmosphere, ensure
the instruments in the loop are installed in accordance with intrinsically safe or
non-incendive field wiring practices.
• In an Explosion-Proof/Flameproof installation, do not remove the transmitter
covers when power is applied to the unit.
Process leaks may cause harm or result in death.
• Install and tighten process connectors before applying pressure.
Electrical shock can result in death or serious injury.
• Avoid contact with the leads and terminals. High voltage that may be present
on leads can cause electrical shock.
Conduit/Cable Entries.
• Unless marked, the conduit/cable entries in the transmitter housing use a
1
compatible thread form when closing these entries.
Reference Manual
00809-0100-4690, Rev FC
June 2011
/2-14 NPT thread form. Only use plugs, adapters, glands, or conduit with a
Electrical shock can result in death or serious injury.
• Avoid contact with the leads and terminals.
Process leaks could result in death or serious injury.
• Install and tighten all four flange bolts before applying pressure.
• Do not attempt to loosen or remove flange bolts while the transmitter is
in service.
Replacement equipment or spare parts not approved by Emerson Process
Management for use as spare parts could reduce the pressure retaining
capabilities of the transmitter and may render the instrument dangerous.
• Use only bolts supplied or sold by Emerson Process Management as spare
parts.
• Refer to page A-7 for a complete list of spare parts.
Use appropriately rated sanitary clamps and gaskets during installation of the 2090F.
The maximum working pressure of the clamp and gasket must be greater than or
equal to the working pressure range of the transmitter. Failure to use proper clamps
and gaskets can cause process leaks and can result in death or serious injury.
2-2
Reference Manual
00809-0100-4690, Rev FC
June 2011
Rosemount 2088 and 2090
GENERAL
CONSIDERATIONS
MECHANICAL
CONSIDERATIONS
ENVIRONMENTAL
CONSIDERATIONS
Measurement accuracy depends on proper installation of the transmitter and
impulse piping. Mount the transmitter close to the process and use a
minimum of impulse piping to achieve the best accuracy. Also, consider the
need for easy access, personnel safety, practical field calibration, and a
suitable transmitter environment. Install the transmitter to minimize vibration,
shock, and temperature fluctuation.
IMPORTANT
Install the enclosed pipe plug (found in the box) in unused conduit opening
with a minimum of five threads engaged to comply with explosion-proof
requirements.
For material compatibility considerations, see document number
00816-0100-3045 on www.emersonprocess.com/rosemount.
NOTE
For steam service or for applications with process temperatures greater than
the limits of the transmitter, do not blow down impulse piping through the
transmitter. Flush lines with the blocking valves closed and refill lines with
water before resuming measurement.
Best practice is to mount the transmitter in an environment that has minimal
ambient temperature change. The transmitter electronics temperature
operating limits are -40 to 185 °F (-40 to 85 °C). Refer to Appendix A:
Reference Data which lists the sensing element operating limits. Mount the
transmitter so that it is not susceptible to vibration and mechanical shock and
does not have external contact with corrosive materials.
2-3
Rosemount 2088 and 2090
START HERE
Bench
Calibration?
Field Install
No
Set Units
(page 3-8)
Set Range
Points
(page 3-9)
Set Output
Type
(page 3-8)
Set Damping
(page 3-11)
Verify
Apply Pressure
Yes
Within
Specifications
?
Yes
No
Refer to
Section 4:
Operation and
Maintenance
Configure
Security and
Alarm
(page 2-15)
Mount
Transmitter
(page 2-5)
Wire Transmitter
(page 2-18)
Power
Transmitter
(page 2-18)
Check Process
Connection
Trim Transmitter
for Mounting
Effects
(page 2-5)
Done
Review
Transmitter
Configuration
(page 3-4)
Confirm
Transmitter
Configuration
(page 3-4)
Configure
HART INSTALLATION
FLOWCHART
Figure 2-1. HART Installation Flowchart
Reference Manual
00809-0100-4690, Rev FC
June 2011
2-4
Reference Manual
00809-0100-4690, Rev FC
June 2011
INSTALLATION
PROCEDURES
Mount the TransmitterRosemount 2088
The Rosemount 2088 Transmitter weighs approximately 2.44 lb. (1,11 kg). In
many cases, its compact size and light weight makes it possible to mount the
2088 directly to the impulse line without using an additional mounting bracket.
When this is not desirable, mount directly to a wall, panel, or two-inch pipe
using the optional mounting bracket (see Figure 2-3).
The 2088 offers several process connections. Use your plant-approved
thread sealant to ensure a leak-proof connection.
Rosemount 2090P
The Rosemount 2090P is designed to be mounted directly to the process pipe
using a weld spud (see Figure 2-7). Mount the transmitter using an existing
weld spud or install a new one using the instructions on page 2-11.
Rosemount 2090F
Rosemount 2088 and 2090
The Rosemount 2090F is designed to be mounted directly to the process pipe
using a standard sanitary fitting (see Figure 2-8). The transmitter is available
with either a 1
NOTE
Most transmitters are calibrated in the horizontal position. Mounting the
transmitter in any other position will shift the zero point to the equivalent
amount of liquid head pressure caused by the varied mounting position. To
reset zero point, refer to “Sensor Trim” on page 4-8.
Terminal Side of Electronics Housing
Mount the transmitter so the terminal side is accessible. Clearance of 0.75-in.
(19 mm) is required for cover removal. Use a conduit plug on the unused side
of the conduit opening.
Circuit Side of Electronics Housing
Provide 0.75 in. (19 mm) of clearance for units without an LCD display.
Provide 3 in. (76 mm) of clearance for units installed with an LCD display.
Cover Installation
Always ensure a proper seal by installing the electronics housing covers so
that metal contacts metal. Use Rosemount supplied o-rings.
Mounting Brackets
1
/2- or 2-inch Tri-Clamp® connection.
Rosemount 2088/2090 Transmitters may be panel-mounted or pipe-mounted
through an optional mounting bracket. See Figure 2-3 on page 2-8 for
dimensional and mounting configurations.
2-5
Rosemount 2088 and 2090
*M20 1.5 Female and G
1
/2 Female (PF 1/2) also available as options.
†
DIN 16288 G
1
/2 Male, RC 1/2 Female (PT 1/2), and M20 1.5 Male also available.
2 ½–14 NPT*
Conduit
Connection
Terminal
Connections
5.1 (130)
Optional Display Cover
Transmitter Circuitry
Certifications Tag
2 ¼–20 UNC-2B
Mounting Holes
½–14 NPT
Female† Process Connection
4.3 (110) Max.
3.9 (100)
0.75 (20)
Clearance for
Cover Removal
4.7
(120)
5.75
(146)
Rosemount 2088
2.38
(60)
5.1 (130)
Optional Display Cover
Transmitter Circuitry
Terminal
Connections
M44 1.25
Weld Spud
2
1
/4–20 UNC–2BX
Depth 0.60
Mounting Holes
0.82
(21)
Certification Tag
4.3 (110)
Rosemount 2090P (11/2-in.) Flush Mount
Vessel Wall
NOTE: Dimensions are in. (mm).
Weld Spud
4.7
(120)
5.1(130)
Typical
3.9 (100)
Dimensional Drawings
Figure 2-2. Transmitter Dimensional Drawings
Reference Manual
00809-0100-4690, Rev FC
June 2011
2-6
Reference Manual
Nameplate
3.9
(100)
2X
1
/4–20 UNC–2BX 0.60 Deep
Mounting Bracket Holes
4.7 (140)
Terminal
Connections
Transmitter Circuitry Side
Optional Display Cover
5.1 (130)
Weld Spud
1.0 (25.4)
Vessel Wall
4.3 (110)
1.05 (26.6)
1.32 (33,4)
5.75 (146)
3X
5
/16–18 UNC
Mounting Holes for
Rotational Mounting
0.7 (17,8)
O-ring (Viton
®
standard)
External Zero/Span (under Nameplate)
1.03 (26.2)
Rosemount 2090P (1-in. Flush Mount)
11/2 or 2-in. Tri-Clamp Connection
2
1
/4–20 UNC–2BX 0.60
Deep Mounting Holes
4.7
(120)
3.9 (100)
*M20 1.5 Female also available.
NOTE: Dimensions are in inches (millimeters).
Optional Display
Cover
Transmitter Circuitry Side
Terminal
Connections
5.0 (125)
4.3 (110)
Certifications Tag
Rosemount 2090F
00809-0100-4690, Rev FC
June 2011
Rosemount 2088 and 2090
2-7
Rosemount 2088 and 2090
2-inch U-Bolt
for Pipe Mounting
NOTE
Dimensions are in. (mm).
1.30 (33)
2.81 (71)
PIPE MOUNTING
PANEL MOUNTING
Mounting bracket ordering code B4, and optional block and bleed valve.
5
/16 × 1½ Bolts
for Panel Mounting
(not supplied)
5
/16× 1½ Bolts
for Panel Mounting
(not supplied)
3.9 (100)
5.0 (125)
4.3 (110)
6.0 (150)
2.5
(63)
3.6
(90)
5.0
(139)
1.25 (32)
HEX
3.0 (80)
3.9
(100)
6.2
(160)
2.8
(70)
4.75 (120)
7.0 (175)
Figure 2-3. Transmitter
Mounting Configurations with
Optional Bracket.
Reference Manual
00809-0100-4690, Rev FC
June 2011
2-8
Reference Manual
00809-0100-4690, Rev FC
June 2011
Rosemount 2088 and 2090
Impulse PipingThe piping between the process and the transmitter must accurately transfer
the pressure to obtain accurate measurements. There are six possible
sources of impulse piping error: pressure transfer, leaks, friction loss
(particularly if purging is used), trapped gas in a liquid line, liquid in a gas line,
and density variations between the legs.
The best location for the transmitter in relation to the process pipe is
dependent on the process. Use the following guidelines to determine
transmitter location and placement of impulse piping:
•Keep impulse piping as short as possible.
•For liquid service, slope the impulse piping at least 1 in./foot (8 cm/m)
upward from the transmitter toward the process connection.
•For gas service, slope the impulse piping at least 1 in./foot (8 cm/m)
downward from the transmitter toward the process connection.
•Avoid high points in liquid lines and low points in gas lines.
•Make sure both impulse legs are the same temperature.
•Use impulse piping large enough to avoid friction effects and blockage.
•Vent all gas from liquid piping legs.
•When using a sealing fluid, fill both piping legs to the same level.
•When purging, make the purge connection close to the process taps
and purge through equal lengths of the same size pipe. Avoid purging
through the transmitter.
•Keep corrosive or hot (above 250 °F [121 °C]) process material out of
direct contact with the sensor module and flanges.
•Prevent sediment deposits in the impulse piping.
•Maintain equal leg of head pressure on both legs of the impulse piping.
•Avoid conditions that might allow process fluid to freeze within the
process flange.
Mounting Requirements
Impulse piping configurations depend on specific measurement conditions.
Refer to Figure 2-4 for examples of the following mounting configurations:
Liquid Flow Measurement
•Place taps to the side of the line to prevent sediment deposits on the
process isolators.
•Mount the transmitter beside or below the taps so gases vent into the
process line.
•Mount drain/vent valve upward to allow gases to vent.
Gas Flow Measurement
•Place taps in the top or side of the line.
•Mount the transmitter beside or above the taps so to drain liquid into
the process line.
2-9
Rosemount 2088 and 2090
GAS
SERVICE
STEAM SERVICE
LIQUID SERVICE
Steam Flow Measurement
•Place taps to the side of the line.
•Mount the transmitter below the taps to ensure that impulse piping will
remain filled with condensate.
•In steam service above 250 °F (121 °C), fill impulse lines with water to
prevent steam from contacting the transmitter directly and to ensure
accurate measurement start-up.
NOTE
For steam or other elevated temperature services, it is important that
temperatures at the process connection do not exceed the transmitter’s
process temperature limit, which is 250 °F (121 °C).
Figure 2-4. Installation
Examples
Reference Manual
00809-0100-4690, Rev FC
June 2011
2-10
Reference Manual
00809-0100-4690, Rev FC
June 2011
Process ConnectionsRosemount 2090P
Installing the Rosemount 2090P transmitter involves attaching a weld spud to
the tapped process vessel, attaching the transmitter to the weld spud, and
making electrical connections. If you intend to use an existing weld spud,
proceed to the transmitter section of this installation procedure (page 2-12).
NOTE
The Rosemount 2090P isolating diaphragm can be mounted flush with the
inside diameter of any vessel larger than three inches in diameter.
Installation of the weld spud should be performed by a skilled welder using a TIG welder.
Improper installation may result in weld spud distortion.
Weld Spud
Rosemount 2088 and 2090
1.Using the appropriate size hole saw, cut a hole in the process vessel
to accept the weld spud. The diameter for a weld spud with heat
isolator groove is 2.37 in. (60 mm); when compatible with 1-in. PMC
process connection style spud, diameter is 1.32 in. (33,4 mm). The
hole should produce a tight, uniform fit when coupled with the weld
spud.
2.Bevel the edge of the vessel hole to accept filler material (see Figure
2-5).
3.Remove the weld spud from the transmitter and remove the PTFE
gasket from the weld spud.
Excessive heat will distort the weld spud. Weld in sections, as shown in Figure 2-5,
cooling each section with a wet cloth. Allow adequate cooling between passes.
To reduce the chances of distorting the weld spud (for 1.5-in. connection), use a heat
sink—Rosemount Part Number 02088-0196-0005.
4.Position the weld spud in the vessel hole, place heat sink and tack
spud in place using the welding sequence shown in Figure 2-5. Cool
each section with a wet cloth before proceeding to the next section.
5.Weld the spud in place using 0.030 to 0.045 in. (0,762 to 1,143 mm)
stainless steel rod as filler in the bevelled area. Using between 100
and 125 amps., adjust the amperage for 0.080 in. (2,032 mm)
penetration.
®
2-11
Rosemount 2088 and 2090
Transmitter
1.After the weld spud has cooled, remove the heat sink and install the
PTFE gasket into the weld spud. Ensure that the gasket is properly
positioned within the weld spud; improper placement could cause a
process leak (see Figure 2-6).
2.Position the transmitter into the spud and begin to engage the
threads. Rotate the transmitter prior to seating the threads completely
to enable access to the housing compartments, the conduit entry, and
the LCD Display.
3.Hand tighten the transmitter using the knurled retaining ring, then
snug an additional
IMPORTA NT
Do not over-tighten the retaining ring. A spanner wrench hole is located on the
knurled portion of the retaining ring to assist in transmitter removal if it is
over-tightened.
00809-0100-4690, Rev FC
1
/8 turn with adjustable pliers.
Reference Manual
June 2011
2-12
Reference Manual
PREPARING THE VESSEL HOLE
4
6
8
1
3
5
7
2
Process
Vessel
Bevelled
Edge
Weld Spud
100–125 Amps
recommended
308L SST
2.37 (60)
Code “C” in Model Structure or
P/N 02088-0195-0005
WELDING SEQUENCE
Heat Isolation
Grooves
PTFE Gasket
Nameplate
2 ¼–20
UNC–2BX
Depth 0.60
Mounting
Holes
Bevelled Edge
Vessel
Wall
Weld Spud
DETAIL OF WELD SPUD
Vessel Wall
100–125 Amps
recommended
Weld Spud
00809-0100-4690, Rev FC
June 2011
Figure 2-5. PTFE Installing the Weld Spud.
Figure 2-6. PTFE Gasket Placement.
Rosemount 2088 and 2090
Figure 2-7. Rosemount 2090P Mounting Configuration Using a Weld Spud.
2-13
Rosemount 2088 and 2090
Nameplate
1.5- or 2-in.
Tri-Clamp
Connection
1.1 (28)
Typical
User Supplied
Gasket and
Clamp
B
A
DETAIL OF SANITARY
CONNECTION
Standard Sanitary Clamp Models
Clamp Model
psi @ 70 °F
(kPa @ 21 °C)
psi @ 250 °F
(kPa @ 121 °C)
Recommended
Torque
13 MHHM 1.5-inch
13 MHHM 2-inch
450 (3 103)
500 (3 448)
250 (1 724)
250 (1 724)
25 in-lb. (2.8 N•m)
13 MHHS 1.5-inch
13 MHHS 2-inch
600 (4 138)
550 (3 793)
300 (2 069)
275 (1 896)
25 in-lb. (2.8 N•m)
13 MHP 1.5-inch
13 MHP 2-inch
1500 (10 345)
1000 (6 896)
1200 (8 276)
800 (5 517)
20 ft-lb (27 N•m)
CONNECTION SIZE
* Dimensions are in inches (millimeters)
Connection
Size*
AB
1.50 (38)1.99 (50)1.71 (43)
2.00 (51)2.52 (64)2.22 (56)
Mounting
Hole
Rosemount 2090F
The Rosemount 2090F hygienic pressure transmitter is designed to be
installed directly to a sanitary fitting. The transmitter is available with either a
1
/2- or 2-in. clamp connection.
1
When installing the transmitter to the sanitary fitting, it is important to use the
proper sanitary clamp and gasket (user-supplied). Check the clamp and
gasket specifications before installing. Refer to Standard Sanitary Clamp Models in Figure 2-8 for a list of standard sanitary clamps, their respective
maximum pressure ranges, and the recommended torque to be applied when
mounting.
Figure 2-8. Rosemount 2090F Mounting Configuration Using a Sanitary Fitting.
Reference Manual
00809-0100-4690, Rev FC
June 2011
2-14
Reference Manual
Electronics
Housing
Process
Connection
00809-0100-4690, Rev FC
June 2011
Do not apply torque directly to the electronics housing. Rotation between the electronics housing and the
process connection can damage the electronics. To avoid damage, apply torque only to the hex-shaped
process connection. Use a backup wrench on Process Connection when installing an adapter.
CONFIGURE SECURITY
AND ALARM
Rosemount 2088 and 2090
Write Protect
There are three security methods in the Rosemount 2088/2090 transmitter:
1.Security Jumper: prevents all writes to transmitter configuration.
2.Local Keys (Local Zero and Span) Software Lock Out: prevents
changes to transmitter range points via local zero and span
adjustment keys. With local keys security enabled, changes to
configuration are possible via HART.
3.Physical removal of Local Keys (Local Zero and Span) Magnetic
Buttons: removes ability to use local keys to make transmitter range
point adjustments. With removing local keys, changes to
configuration are possible via HART.
You can prevent changes to the transmitter configuration data with the write
protect jumper. Security is controlled by the security (write protect) jumper
located on the electronics board or LCD display. Position the jumper on the
transmitter circuit board in the “ON” position to prevent accidental or
deliberate change of configuration data.
If the transmitter write protection is in the “ON” position, the transmitter will not
accept any “writes” to its memory. Configuration changes, such as digital trim
and reranging, cannot take place when the transmitter security is on.
2-15
Rosemount 2088 and 2090
NOTE
If either the alarm or security jumper is dislodged or removed from its position,
the transmitter reverts to default alarm or security settings of: Alarm: Output
high; Security: Off
Configuring Transmitter Security and Alarm Jumper Procedure
To reposition the jumpers, follow the procedure described below.
1.Do not remove the transmitter covers in explosive atmospheres when
the circuit is live. If the transmitter is live, set the loop to manual and
remove power.
2.Remove the housing cover opposite the field terminal side. Do not
remove the transmitter covers in explosive atmospheres when the
circuit is live.
3.Reposition the jumpers as desired.
• Figure 2-9 shows the jumper positions for the 4-20 mA HART
Transmitter and 1-5 Vdc Low Power Transmitter.
4.Reattach the transmitter cover. Always ensure a proper seal by
installing the electronics housing covers so that metal contacts metal
to meet explosion-proof requirements.
Reference Manual
00809-0100-4690, Rev FC
June 2011
2-16
Reference Manual
Security
Alarm
Alarm
Security
Alarm
Security
Alarm
Security
00809-0100-4690, Rev FC
June 2011
Rosemount 2088 and 2090
Figure 2-9. Transmitter Alarm
and Security Jumper Locations
Without LCD DisplayLow Power without LCD Display
With LCD DisplayLow Power with LCD Display
.
Without a display installed
The failure mode alarm jumper is located on the front side of the electronics
module just inside the electronics housing cover and is labeled ALARM (See
Figure 2-9). Do not remove the transmitter cover in explosive atmospheres
when the circuit is alive. Both covers must be fully engaged to meet
explosion-proof requirements.
With a display installed
The failure mode alarm jumper is located on the LCD faceplate in the
electronics module side of the transmitter housing and is labeled ALARM
(See Figure 2-9). Do not remove the transmitter cover in explosive
atmospheres when the circuit is alive. Both covers must be fully engaged to
meet explosion proof requirements.
2-17
Rosemount 2088 and 2090
Voltage (Vdc)
Load (Ohms)
Operating
Region
1387
1000
500
0
10.52030
42.4
Reference Manual
00809-0100-4690, Rev FC
June 2011
ELECTRICAL
CONSIDERATIONS
The wiring terminations on the Rosemount 2088/2090 are located in the side
of the transmitter housing marked “FIELD TERMINALS.” Access to these
terminations is required during installation and may be necessary during
periodic calibration of the transmitter.
NOTE
Make sure all electrical installation is in accordance with national and local
code requirements.
Power SupplyThe dc power supply should provide power to the transmitter with less than
one percent ripple. The total loop resistance load is the sum of the resistance
of the signal wires and the resistance load of the controller, indicator, and
other pieces of equipment in the loop. Note that the resistance of intrinsic
safety barriers, if used, must be included. Figure 2-10 shows the transmitter
power supply load limitations.
Figure 2-10. Load Limitation
Maximum Loop Resistance = 43.5 * (Power Supply Voltage – 10.5)
The Field communicator requires a minimum loop resistance of 250
for communication.
Power Supply for 1-5 Vdc HART Low Power
Low power transmitters operates on 6-14 Vdc. The dc power supply should
provide power with less than two percent ripple. The V
load should be 100
out
kor greater.
2-18
Reference Manual
00809-0100-4690, Rev FC
June 2011
Wiring
Rosemount 2088 and 2090
Do not connect the power signal wiring to the test terminals. Voltage may burn out
the reverse-polarity protection diode in the test connection.
NOTE
Use shielded twisted pairs to yield best results. To ensure proper
communication, use 24 AWG or larger wire, and do not exceed 5000 feet
(1500 meters).
All power to the transmitter is supplied over the signal wiring. Signal wiring
need not be shielded, but use twisted pairs for best results. Do not run
unshielded signal wiring in conduit or open trays with power wiring, or near
heavy electrical equipment. For high EMI/RFI environments, shielded twisted
pair cable should be used. To power the transmitter, connect the positive
power lead to the terminal marked “PWR/COMM+” and the negative power
lead to the terminal marked “–” (see Figure 2-11). Tighten the terminal screws
to ensure that proper contact is made. Avoid contact with the leads and the
terminals. No additional power wiring is required for transmitters with “S”
output. For “N” output code transmitters, connect positive signal lead to “test
+” and negative signal lead to terminal marked “-.”
To connect test equipment for monitoring the output of the Rosemount
2088/2090 transmitter during maintenance procedures, connect one lead to
the terminal labeled “TEST+” and the other lead to the terminal labeled “–”
(see Figure 2-11). Avoid contact with the leads and the terminals.
Signal wiring may be grounded at any one point on the measurement loop, or
it may be left ungrounded. The negative side of the power supply is a
recommended grounding point. The transmitter case may be grounded or left
ungrounded.
Conduit connections at the transmitter should be sealed to prevent moisture
accumulating in the field terminal side of the transmitter housing. Also, install
wiring with a drip loop with the bottom of the drip loop lower than the conduit
connection of the transmitter housing.
2-19
Rosemount 2088 and 2090
Positive
Negative
Test
Power
Supply
RL250
Power
Supply
Voltmeter
Figure 2-11. Rosemount 2088/2090 Transmitter Signal Wiring Terminals
Figure 2-12. 4-20 mA HART Transmitter Wiring Diagram
Reference Manual
00809-0100-4690, Rev FC
June 2011
Figure 2-13. 1-5 mA Vdc HART Low Power Transmitter Wiring
2-20
Loading...
+ 80 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.