ISO 9001
REGISTERED
RTD Transmitters - Field Configuration Options - High Density DIN Rail Packaging
X54-3302 Dual Channel Universal RTD Transmitter
♦ High Density Dual Channel Packaging
♦ Field Configurable Options Including:
four (4) RTD types, seven (7) standard input spans
with selectable zero offsets (for non-linearized ranges only)
♦ Full Input/Output/Power and Channel Isolation
♦ Front Panel Power/Sensor Fail LED Indicator
♦ Front Access to Zero and Span Adjustments
♦ Standard 35 mm DIN Rail Mounting
DESCRIPTION: The X54-3302 is a dual channel RTD transmit-
ter powered by 24 vdc. Features include: two piece plug-in connectors
for easy wiring and maintenance; Power/Sensor Fail LEDs; field configurable ranges and RTD types; optional linearized outputs; full 1000
vac isolation; and front panel access to ZERO and SPAN adjustments.
RFI protection, wide operating temperature, and high accuracy are
standard features. Custom inputs, outputs, scaling and linearization are
available from the factory.
SPECIFICATIONS:
Input:
RTD sensor types: 100 ohm platinum, 120 ohm nickel,
10 ohm copper.
(linearized outputs available for Platinum or Nickel only)
Input Impedance:
> 100 K ohms.
Outputs: 4-20 mA or 0-20 mA into 650 ohm loads
1-5 V, 0-5 V with 250 ohm output impedance.
Span Adjustment:
Front-accessible, multi-turn, infinite resolution potentiometer
permits minimum +/- 5% adjustment.
Zero Adjustment:
Front-accessible, multi-turn, infinite resolution potentiometer
permits minimum +/- 5% adjustment
Sensor Failure Response:
Red front-panel LED indication with upscale drive standard.
Calibrated Accuracy:
+/- 0.1% of span (linearization errors additional on large
span applications, consult factory )
Isolation:
1,000 vac between channels, input and output.
Input and output circuits isolated by transformers.
Specifications apply at 23 +/- 2°C (74 +/- 2°F) unless otherwise specified, and are subject to change without notice,
Common Mode Rejection:
> 120 dB, DC at 60 Hz.
Common Mode Voltage:
1000 volts peak AC maximum without damage.
Ambient Temperature Coefficient:
Ambient temperature range: 32 to 158
Gain: < +/- 0.01 % /
Zero: < +/- 0.01 % /
Ambient Temperature Range:
Operating: -20 to 158 F (-25 to 70
Storage: -40 to 158 F (-40 to 70
Power Supply Range:
18 to 30 vdc (Max. current draw = 190 madc @ 24 vdc)
Radio Frequency Effects:
< 0.4 mV (referred to input) + 0.2% of span (referred to output) when exposed to 5W transmitter with frequency range
20-460 MHz at a distance of 1 m.
Calibration:
Typically, factory calibrated to customer specified ranges.
Customer configurable for non-linearized applications.
Terminals:
High temperature polyester type, wire size 12 AWG max., 10
A max., 300 V max.
A Family of
Products!!!
Transmitters
Alarm Trips
I/I Isolators
°F (0 to 70°C).
°F.
°F.
°C).
°C).
Page 1 of 2
Ronan Engineering Company
Ph: 800-327-6626 Fax: 818-992-6435 E-mail: sales@ronan.com Web: www.ronan.com
Rev. 0
X54-3302 Dual Channel Universal RTD Transmitter (continued)
TERMINAL ARRANGEMENT:
Outputs
Ch1
Ch2
18-30 vdc
Power
Input
*
1.) Plug-in connector design simplifies installation and mainte-
2.) Use up to 12 awg wiring.
3.) When inserted, case back cover provides a mechanical cover
J2*
J2* J1*
+
1
-
2
NC
3
+
4
-
5
6
NC
1
+
2
-
3
GND
J5*
nance.
for connector screws (as required by European standards).
3-wire RTD
1
2
3
4
5
6
Inputs
Ch1
Ch2
MECHANICAL DETAIL:
2.47”
62.7mm
DIN Rail
2.23”
54.6mm
C
L
0.850”
21.6mm
5.80”
147.3mm
ORDERING INFORMATION:
X54-3302-(I) (II) (III)-(I) (II) (III)
Channel #2
Channel #1
I = RTD type (100 = 100 ohm Platinum 0.00385)
( 1 2 0 = 1 2 0 o h m N i c k e l )
( 1 0 = 1 0 o h m C o p p e r @ 0 ° C )
( 9 = 10 ohm Copper @ 25°C)
II = Standard Range code (A - G) or
specify special range; e.g. 0-450°F linearized = (0/450°F)
III = Output (B = 4-20mA; H = 0-20mA; D = 1-5vdc; F = 0-5vdc)
Example: Standard Ranges 0-500°F linearized
X 5 4 - 3 3 0 2 - 1 0 0 E B - 1 0 0 E B
Example: Special Range 0-450°F linearized
X54-3302-100L(0/450°F)B—100L(0/450°F)B
Accessories:
D2-35X7.5 35 mm X 7.5 mm “U” style DIN rail, sold per foot
STANDARD INPUT RANGES:
Code
A -40 to +40 -40 to +4 100, 120
B -40 to +104 -40 to +40 100, 120
C 32 to +100 0 to +38 100, 120,
D 32 to +212 0 to +100 100, 120,
E 0 to +500 -18 to +260 100, 120
F 32 to +932 0 to +500 100
G 0 to +1500 -18 to +815 100
Above ranges are standard offerings for fastest deliv-
ery, and they are linearized for Platinum and Nickel
RTDs only. Contact Ronan for price and delivery of
non-standard ranges with or without linearization.
These transmitters can be configured in the field or
pre-configured at the factory to the customer’s spe-
cific RTD type and temperature range. Factory con-
figuration is only necessary if linearization is re-
quired. Only the Platinum and Nickel RTDs have
ºF
the linearized output option.
ºC
Sensor
Types
10, 9
10, 9
Page 2 of 2
Ronan Engineering Company
Ph: 800-327-6626 Fax: 818-992-6435 E-mail: sales@ronan.com Web: www.ronan.com