Ronan X54-201L, X54-201SR Instructions And Operating Manual

Instructions
and
Operating Manual
SERIES X54-201L/SR
LOOP-POWERED
INDICATOR
Table of Contents
2.0 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
3.0 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
3.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
3.2 Span Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
3.3 Zero Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
3.4 Decimal Point Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
3.5 Linear or Square Root Function Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
4.0 Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
4.1 Linear Display, Model X54-201L . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
4.2 Square Root Display, Model X54-201SR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
5.0 Drawings
X54-201 Explosion Proof Assembly, X54C92 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
X54-201 Panel Mount Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
X54-201L/SR Installation Drawing Using I.S. Barriers or Explosion Proof Conduit . . . . . . . . . . . . . . . . . . . . . .7
Warranty
Ronan warrants equipment of its own manufacture to be free from defects in material and workmanship under normal conditions of use and service, and will repair or replace any component found to be defective, on its return, transportation charges prepaid, within one year of its original purchase. This warranty carries no liability, either expressed or implied, beyond our obligation to replace the unit which carries the warranty.
1
1.0 GENERAL DESCRIPTION
Ronan’s Models X54-201L and -201SR are 3½-digit loop powered indicators which display linear (-201L) and square root (-201SR) values of the associated loop current. The loop containing one of these indicators is barely effected as the indicators require less than 1 V to operate. These versatile modules allow the selection of a linear or square root display, zero value, span and decimal point through the placement of plug-in jumpers. Spans from 0.100 to 1999 and span zeros from –360 to +1300 are selected by the plug-in jumpers. The decimal point selector plug may be placed in any one of four positions which selects one, two or three digits to the right of the decimal point or in position 0 for no decimal point.
2.0 SPECIFICATIONS
Note: Specifications apply at 25ºC ± 2ºC unless
otherwise stated. Specifications subject to change without notice.
Input: 4-20 mA. Input Protection: Diode protected against
reverse polarity.
Voltage Drop: Less than 1 V. Span Selection: Spans from 0.100 to 1999 digits are
selected by DIP-switch settings accessible at the top board of the module. Refer to Table 3-1 on page 3.
Span Adjustment: Front-accessible, multi-turn potentiometer allows ± 20% adjustment of all ranges.
Zero-offset Selection: Offsets from –360 to +1300 digits are selected by DIP-switch settings accessible at the top board of the module. Refer to Table 3-2 on page 3.
Zero Adjust: Front accessible, multi-turn potentiometer allows ± 10% adjustment of selected span range.
Decimal Point Selection: Plug-in jumpers, accessible at the top board of the module, allow selection of the decimal point position. See section 3.5.
Accuracy:
Linear Display: ± 0.1% of span or ±1 digit. Square Root Display: ± 0.3% of span or ± 1 digit
(applies from 4.3 to 20 mA input). Operating Ambient Temperature Range: –10º to
+55ºC.
Temperature Coefficient:
Zero: ± 0.01% of Span/ºC, ± 0.01% of elevated zero value/ºC. Span: ± 0.015% of Span/ºC.
Display: 3½-digit LCD, black digits on a reflective background.
T erminals: Compression type for wire size up to #14 AWG.
Factory Mutual Approvals
-EXP2 Housing = Explosion Proof -Class I-III, Div. 1, Grps B-G and NEMA 4
-PM2 Housing = Div. 2 Applications -Class I, Div. 2, Grps A-D
CSAApprovals
-EXP2 Housing = Explosion Proof -Class I-II, Div. 1, Grps B-G
-PM2 Housing = Div. 2 Applications -Class I, Div. 2, Grps A-D
CENELEC Approvals
X54-201-MI (EXP housing)
X54-201-MX (EXP Housing)
X54-201 Approvals (_PM2 and _EXP2)
= Intrinsic Safe -Class I-III, Div, Div. 1, Grps A-G and NEMA 4 = Intrinsic Safe -Class I, Div.1, Grps A-D
= Intrinsic Safe -Class I-II, Div. 1, Grps A-G = Div. 2 Applications -Class I-II, Div. 2, Grps A-G
= Intrinsic Safe -Class I-II, Div. 1, Grps A-G
Intrinsic Safe -EEx ia IIC T4 (Tamb = 85°C)
Flame Proof -EEx d IIC T6
-EEx ia IIC T5
3.0 OPERATION
3.1 General
Model X54-201 is put into service by connecting it in series with 4-20 mA current loop. The connections are made to the two-position compression-type screw terminal mounted on the lower board and accessible from the top of the module. The loop indicator module needs to be removed from the enclosure in order to feed the wires past the bottom board and into the screw terminals. To remove the module from the explosion-proof enclosure:
A. Unscrew and remove the enclosure cap. B. Snap off the top plate of the module and insert
your index finger into cutout and remove the plate.
C. Loosen the two module captive mounting
screws until the module is free.
D. Remove the module from the enclosure and
fasten the input wiring to the screw terminals.
E. Connect the lead that returns back to the –
output of the power supply, either directly or through a two wire transmitter, to the – terminal of the X54-201. Connect the other wire to the + terminal. See Figure 3-1.
F. Re-install the module and enclosure cap. The Model X54-201 Loop Powered Indicator is normally shipped calibrated to ranges as specified by the purchaser. However, it is designed to allow easy reconfiguration in the field. The span is changed by changing the position of one or two of the SW1 switches -1 through -5. The span zero value is changed by changing the settings of SW2 switches -1 through -6 and SW1-6.
-
+
Figure 3-1: Wiring Diagram