2.0DATA FORMAT AND PROTOCOL..........................................................................................................................3
2.1D
2.2S
2.3P
ATA TRANSMISSION FORMAT .....................................................................................................................................3
EST ERROR LED (RED) ..............................................................................................................................................6
RANSMIT ERROR LED (RED)......................................................................................................................................6
TATUS/RUN LED (GREEN)..........................................................................................................................................6
TO SW3-8.........................................................................................................................................................9
X120-FCPS2424 POWER SUPPLY ............................................................................................................................................5
X120-FCPS12524 P
X120-FCPS125125 P
X120-FCPS24125 P
X120-LPS-24 P
X120-LPS-48 P
X120-LPS-115 P
X120-LPS-125 P
SPECIFICATIONS - MODEL X120 MULTIPLEXER/TERMINATION UNIT
Features
• Monitors up t o 48 switching devices
• Reliable high-speed event transmission
• Interfaces with most plant computers and the Ronan Model X110 Serial Input Visual Annunciator
• Internal relay for self-test and power supply status
• Digital filtering to assure accurate monitoring of status changes
• Up to 32 units may be series connected to monitor up to 1,536 total inputs
• Considerable savings in cable costs by the use of serial transmission
General Description
The Ronan Model X120 Multiplexer/Termination Unit is designed to continuously monitor up to 48 field contacts and/or
solid state switching devices. Any input status change is converted to serial data which can be transferred to a plant computer
or serial input display device, like Ronan’s Model X110 visual annunciator. The input signals are monitored using optoisolated input circuits to provide isolation between input signal voltages and the Model X120 logic circuits. The 48 inputs are
sequentially scanned on a continuous basis.
Input status changes are digitally filtered for a 16 millisecond period before being transmitted over the high speed serial line.
Self-test and watchdog timer circuits, in addition to power supply monitor circuits, are displayed by means of LED indicators.
Loss of a power supply voltage will de-energize the self-test relay.
Up to 32 Model X120 units can be daisy-chained to form a single serial output which monitors the status of up to 1,536 field
contacts or solid state switching devices.
Each Model X120 unit receives 5 VDC power to operate its internal logic. An isolated 125 VDC or 24 VDC voltage source
can be used to power the field contacts. The isolated power source, along with digital filtering, assures maximum noise
immunity for system operation.
Power Requireme nts:Isolated: 0.5 A @ 24 VDC plus 0.25 A @ 24 or 125 VDC
Non-isolated: 0.75 A @ 24 VDC
Capacity: 48 inputs
Protocol: Ronan Proprietary
Data Transmission:
TypeDistance (Feet)Rate (Baud)
RS422/48540002400
40004800
40009600
200019200
Universal Data Format: per point status change
# Symbol: Start of data string
2 Digits:Termination assembly ID
2 Digits:Point ID
1 Character: O=Open, C=Closed, F=False Alarm (ignore message)
ODH Character: End of data string
Ronan Proprietary Data Format: Contact Factory
Page 1 of 12
Output Relay:
• Normally energized, SPST 2 A @ 24 VDC
• Monitors internal logic, all power supplies and optional ground detection
Minimum Sustained Data Transfer Ra te:190 events per second (at 19.2 K baud using Ronan proprietary protocol)
Specifications subject to change without notice.
1.0MULTIPLEXER CONTROLLER MODULE X120-1000
The primary function of the controller board is to gather “event” data from 48 input channels and relay the
collected information to the Model X110 via RS422/485. This is done by continuous scanning of each of the eight
inputs with U7 (1-OF-8 DECODER/DEMULTIPLEXER). There are 8 outputs from U7 (CS0, CS1, CS2, CS3,
CS4, CS5, CS6, CS7) which are used to scan all the channels and to read the status of SW2 and SW3. The function
and the logical address of each output is shown in Figure 1.
IDENT.LOGIC ADDRESSFUNCTION
CS08000HREADING DATA FROM CH. 1-8
CS18001HREADING DATA FROM CH. 9-16
CS28002HREADING DATA FROM CH. 17-24
CS38003HREADING DATA FROM CH. 25-32
CS48004HREADING DATA FROM CH. 32-40
CS58005HREADING DATA FROM CH. 41-48
CS68006HREADING DATA FROM SW2 è 1-8
CS78007HREADING DATA FROM SW3 è 1-8
Figure 1
Each time the controller board scans all the input channels, it stores all the data in the internal memory and makes
filter calculations (refer to filtering section for more information). After filter processing, all the status changes of
inputs are transferred to the transmit buffer and ready to be transmitted. If the old status change of any input has
not been transmitted from the transmit buffer before the status of the same input changes, the controller board
would not register the new status change of that input channel. Therefore the old status of input channels would
not be lost before being transmitted to the X110 system.
Page 2 of 12
2.0DATA FORMAT AND PROTOCOL
All the data from the X120 is transmitted serially via RS232 (P1) to a terminal/printer and RS422/485 (P2) to
X110.
2.1Data Transmission Format
Baudrate=1200 / 9600
Number of data bits=7
Number of stop bits=1
Parity=Even
2.2Status Format
Six bytes of data would be transmitted each time the status of any input channel changes. The formats of
these data bytes are shown below:
2.3Protocol
The protocol between X120 and X110 is RONAN proprietary and is done to make sure that any status
data transmitted from the X120 would be received by the X110 properly. Each time the X120 transmits a
status change of an input, it will wait for approximately 250ms to receive an ACK (Ctr F) from the X110
which means that the X110 received the data without any error. If after 250ms the ACK is not received,
the same status would be transmitted again up to three times. After the third time, the transmit error LED
would be illuminated and the horn relay would be activated before sending the next status change.
Note:When an ACK is received by the X120, the transmit error LED would be turned off (if it was
on) and the horn relay would be deactivated.
3.0SPECIAL FUNCTIONS
Along with its event collecting/transmitting tasks, the controller board performs a number of secondary tasks that
are explained in different sections.
3.1Filtering
Page 3 of 12
Before reporting the occurrence of an “event”, the controller board’s program makes “software filter”
calculation. Recall, that a change in the status of a contact must be seen for a specified duration of time
equal to the “time constant value”) before an event is actually declared. The filter calculations are made to
determine when the proper duration of time has expired. The “time constant value” is set to 16ms for all the
input channels.
3.2Input Channel Test
The controller board tests all the 48 input channels of the multiplexer for alarm and return to normal
conditions (only if SW2-7 is set to the ON position) each time it is reset. The test error LED would be
illuminated and the horn relay would be made active if any of the 48 input channels failed to test. This test
is done by using two relays K1 and K2. The K1 relay is used to disconnect the field contact power to all the
inputs. The K2 relay is used to test all the input channels by connecting and disconnecting the field contact
voltage to all the channels and checking all the outputs for proper function. The test error flag would be set
on each channel that was bad and they will be reported before the alarm summary (refer to ALARM
SUMMARY section for more information) with the following format:
The BAD channel report is very useful for troubleshooting input boards. By connecting a terminal to RS232 (P1)
port, all the bad channels (if there is any) would be displayed before the alarm summary each time the X120 is
reset.
Note:The input channel test is valid only if all 48 inputs are set for dry co ntact (B&C jumpers installed).
3.3Alarm Summary
To update all the annunciator windows with the current status of inputs, Alarm Summary of all the input
channels (open or closed) would be reported if the X120 is reset. To clear all the annunciator windows
before alarm summary, the following data would be sent:
Note:All the data is sent with even parity.
Page 4 of 12
After clearing all the windows, all the bad input channels would be reported (if there is any) only if SW2-7 was set
to the ON position. The alarm summary would be reported next, followed by this data:
4.0CONFIGURATIONS
The X120 multiplexers can be connected to the X110 system in two different ways (parallel & serial) and J2, J3,
J4, J5 burg jumpers have to be set differently for each X120 in different configurations.
4.1Parallel Configuration
Only one X120 is connected to the X110(s) in this configuration and J2, J3, J4 and J5 burg jumpers are
used (installed).
4.2Serial Configuration
Two to thirty-two X120s can be connected together serially in this configuration. Only J2 & J3 on the
first X120 and J4 & J5 on the last X120 are installed. J2, J3, J4 and J5 should not be installed on any
X120 between first and last.
Figure 2 shows how the X120s are connected serially.
Page 5 of 12
5.0LED INDICATIONS
There are three LEDs on the controller board that indicate the status of the X120s and communication between
X120s and X110s. The operations of these LEDs are explained in the following sections.
5.1Test Error LED (Red)
Refer to section 3.2.
5.2Transmit Error LED (Red)
Refer to section 2.3.
5.3Status/Run LED (Green)
The run/status LED indicates the connection between all the X120 multiplexers. All the run/status LEDs
should be flashing synchronously if connections between all the X120s are okay. The flashing rate
depends on the number of X120 multiplexers connected together and decreases by connecting more
X120(s) in the chain.
Note 1: If any of the X120 multiplexers is transmitting events, the run/status LEDs stop flashing
during the transmission time and stay on or off depending on its state which transmission
started.
Page 6 of 12
Note 2: Make sure that all the burg jumpers (J2, J3, J4, J5) are installed properly.
6.0JUMPER SETTINGS
6.1J2, J3, J4, J5
Refer to section 4.0.
6.2J6 Jumper
The DS1232 (U9) provides a watchdog timer function by forcing RST and RST signals to the active state
when the ST input is not simulated for a predetermined time. The time period is set by the TD input to
be 150 ms with TD connected to ground (J6-2&3 installed), 600 ms with TD left unconnected (J6 not
installed), and 1.2 seconds with TD connected to Vcc (J6-1&2 installed).
6.3J7 Jumper
This jumper is for setting the horn relay contact to normally open or normally closed. The horn relay is
normally energized. To set the horn relay output contact, install (J7-1&2) for normally open and (J7-2&3)
for normally closed.
The factory setting is (J6-1&2 installed)
The factory setting is normally open (J7 -1&2 installed)
6.4J8, J9 Jumpers
These jumpers are to enable/disable the data transmission to test port (P1). P1 port is used for testing the
X120 boards and can be connected to any terminal with the RS232 port to display the ASCII data
transmitted by the X120 to the X110.
Install J8 & J9 to enable and remove J8 & J9 to disable the data transmission from the X120 to RS232 test
port P1.
Note:The J8 & J9 are installed only on the master controller board to test the system.
6.5J10, J11 Jumpers
These jumpers are to enable/disable the data reception from RS232 test port (P1) and they are used only
for testing the system.
The factory setting (J8&J9 installed)
The factory setting is (J10&J11 installed)
Note:If you install J10 & J11 for testing the system, disconnect the cable between the X120 and
X110.
Page 7 of 12
6.6J12, J13 Jumpers
Installing a burg jumper on J12 will place in service a 112 ohm line-to-line terminator across the receiver
line (RXD, RXD RTN). If the system is subject to extremely noisy environments, it would be better to
terminate only the receiver side of the communication line by line-to-ground termination on each side of
the receiver line (RXC, RXD RTN). Installing burg jumpers on both J12 and J13 will terminate each side
of the receiver line through 56 ohm to ground .
6.7J14, J15 Jumpers
Installing a burg jumper on J14 will place in service a 112 ohm line-to-line terminator across the receiver
line (TXC, TXC RTN). Installing burg jumpers on both J14 and J15 will terminate each side of the
transmitter line through 56 ohm to gro und.
7.0SWITCH SETTINGS
Position 1 to 5 of SW2 are for setting the MUX numbers and they are set as follows: