Ronan X11SN User Manual

Instructions
and
Operating Manual
SERIES X11SN
WINDOW ANNUNCIATOR
SYSTEMS
TABLE OF CONTENTS
1.0 General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3.0 Expansion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
4.0 Auxiliary Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
5.0 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
6.0 Power Up and Test Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
6.1 Wiring Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
7.0 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
7.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
7.2 Nonoperating Alarm System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
7.3 Step-by-step Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
8.0 Alarm Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
8.1 Integral/Push-button Flasher Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
8.2 Alarm Sequence/Display Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
8.3 Output Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
9.0 Standard Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
9.1 A, Automatic Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
9.2 M, Manual Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
9.3 F3A, Automatic Reset First Out with First Out Flashing and Reset Push Button . . . . . . . . . . . . . . 11
9.4 R, Ringback
(Ronan ID RD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
9.5 F2A, Automatic Reset First Out with No Subsequent Alarm Flashing
(Ronan ID FS) . . . . . . . . . . . . 12
9.6 F2M, Manual Reset First Out with No Subsequent Alarm Flashing
(Ronan ID FSM) . . . . . . . . . . . . 12
10.0 Dimension and Wiring Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
10.1 Monalarm Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
10.2 Binalarm Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
10.3 Trialarm Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
10.4 Quadalarm Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
10.5 Standard Rear Terminal Arrangements and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
10.6 Rear Terminal Arrangements and Wiring for 125 Vdc Field Contact . . . . . . . . . . . . . . . . . . . . . . . 18
10.7 Rear Terminal Arrangements and Wiring for Transistor Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
10.8 Rear Terminal Arrangements and Wiring for Opto-coupled Input . . . . . . . . . . . . . . . . . . . . . . . . . 20
THREE-YEAR WARRANTY: Ronan warrants equipment of its own manufacture to be free from defects in material
and workmanship, under normal conditions of use and service, and will repair or replace any component found to be defective, on its return, transportation charges prepaid, within three (3) years of its original purchase. This warranty carries no liability, either expressed or implied, beyond our obligations to replace the unit which carries the warranty.
1

1.0 GENERAL DESCRIPTION

The Ronan Series X11SN Window Annunciator Systems feature Monalarm, Binalarm, Trialarm and Quadalarm displays within Ronan’s standard 3.5 inch (89 mm) by 3.5 inch (89 mm) mechanical cabi­net modules. The single plug-in module construction contains single or multipoint alarm circuitry with maximum noise immunity and reliability. The most popular ISA sequences, A, M, F2A, F2M, F3A, and R are readily available. For other special sequences, consult factory. For higher noise im­munity and specific field contact time applications, a programmable field contact time delay board is an available option. Normally open/normally closed field contact logic for each individual channel is jumper switch-selectable on the single-board design. A sys­tem common trouble alarm (CTA) may be utilized for remote group alarms. The system's CTA and re­flash transistor outputs may be connected directly or via interface relays to provide inputs to remote annunciators.

2.0 SPECIFICATIONS

System Voltage:
Logic, Lamps: 24 Vdc ± 20%. Field Contact Options: 24 Vdc Dry Contact, 48, 125,
250 Vdc ± 20% live input or opto-isolated 115, 240 Vac two-wire input (H and N).
Temperature Range:
Storage: -40 to 85°C (-40 to +185°F). Operating: -40 to +60°C (-40 to +140°F).
Consult factory for extended ranges.
Power Sources:
External Power Supplies or Inverters Available for:
120 Vac ± 20%, 60 Hz; 240 Vac ± 20%, 50/60 Hz; Converter 24, 48 or 125 Vdc ± 20%.
Power Requirements: To specify the correct power supply, count the number of alarm modules to be powered from the supply. Calculate the total require­ments with the following equation:
Total Watts = No. of Modules x (Display Factor F + F Aux.)
F Aux.
Model F Lamps F LEDs Relay Adder
X11SN (1000 Series) 5.3 W 7.1 W 1 W X11SN (2000 Series) 9.3 W 7.1 W 2 W X11SN (3000 Series) 13.3 W 5.6 W 3 W X11SN (4000 Series) 9.3 W 7.1 W 4 W
Inputs: 24 Vdc dry contact, 48, 125, 250 Vdc ± 20% live input or opto-isolated 115, 240 Vac two­wire input (H and N).
Outputs:
Lamp Outputs: Fast flash, slow flash, steady on, intermittent fast flash.
Alarm: Single audible. Auxiliary Relay: Field selectable Form Aor B. Contact Rating: 2A @ 28 Vdc, General Purpose or
Hermetically Sealed.
Common Trouble Alarm: Output follows FC NDE. Reflash Option: Output on rear terminal block
point F4.
Response Time: 20 msec nominal. Surge Withstand Capability (SWC):
All Logic Tested to: ANSI/IEEE C37.90-1989.
Controls: Integral or Remote Silence, Acknow­ledge, Reset, and Test: Momentary push button, single pole, normally open.
System Size:
Multiple of Cabinet Module: 3.5 inch (89 mm) x 3.5 inch (89 mm). See dimensional information draw­ings for detailed dimensions.
System Weight Per Cabinet Module: 2 lbs. (909 grams) not including power supply.

3.0 EXPANSION

The Series X11SN Window Annunciator Systems are built for expandability. This allows field expan­sion of the Monalarm System to either Binalarm, Trialarm or Quadalarm, and the Binalarm to Trialarm or Quadalarm, by simply replacing the alarm/lamp modules and the appropriate bezels. CAUTION: The last position of each chassis can not be more than two alarm positions due to the flasher, so it will only expand to Binalarm.

4.0 AUXILIARY CONTACTS

The auxiliary contact outputs may be purchased ini­tially or added later in the field. The single, dual, triple or quad relay circuit module plugs in from the front of the system. The receiving multipin printed circuit connector and the terminals for the contact outputs are furnished with the system. Each relay follows the selected alarm board auxiliary behavior and provides a selectable Form A or B type contact. The relays are available in General Purpose or Hermetically Sealed models.
2

5.0 MOUNTING

A. The annunciator is shipped with all of the alarm/
lamp modules, auxiliary contact module(s) and flasher module(s) installed in the cabinet, as specified by purchase order.
B. External horn relay(s), reflash relay, common
alarm relay, relay sockets, horns, bells, push but­tons and power supply are packed separately.
C. Install the alarm cabinet from the front of the
panel.
1. Position the cabinet in the cutout so that the cabinet rests on the front extruded trim, see detail A, Figure 1. Make sure that the front rim is firmly against the panel, both top and bot­tom.
2. From the rear view of the panel, insert the two halves of the clamp assembly (one half threaded and the other half unthreaded) in the groove of the front trim, see detail C below.
3. Slide the clamps together until both holes align, see detail B below.
4. Insert the jack screw and tighten to secure the cabinet in the panel. Install all the clamps the same way and be sure to tighten evenly.
5. Tighten up the lock nuts on each jack screw.
3
Clamp Assembly
Flasher Module
Alarm Lamp Module
Auxiliary
Contact Module
Bezel
Rear Cover
Detail A
Detail B
Figure 1: X11SN Assembly Drawing
Detail C
D. Systems purchased with NEMA12 or NEMA4
Doors require mounting of the door before Step C1. After removal of the mounting clamp assem­blies, the system can be inserted through the open door, sandwiching the door between the panel and the system’s extruded trim (gasket is furnished with door). Continue with Steps C1 through C5. Note: The panel cutout is the same as specified in standard flush mounted alarm systems.
E. Mount all external relays, horns and/or bells,
push buttons and power supply on the panel or in the rear of the annunciator cabinet, where possible.
F. Wire system’s inputs and support equipment as
shown under System’s Support Wiring.
Before turning on power read Power Up and Test Procedure.
CAUTION

6.0 POWER UP AND TEST PROCEDURE

It is important to review all external equipment, including the alarm system, before turning on power and proceeding with testing. Before installing, verify that each component meets the area and environment standard required by the National Electrical Code. Particular attention must be paid to reviewing push buttons, horn relays, horns and bells, to see that they meet the right classification of the electrical code.

6.1 Wiring Inspection

6.1.1 Alarm Inputs. Each active alarm input
must be wired to customer’s sensing device that provides an opening or closing on alarm condition. The terminals on the alarm system for each alarm input are marked 1 and are supplied via a pull-up resistor on each alarm module point. This resistor is used in the V+ source to each field contact to reduce the effect of large transients entering the alarm chassis. Each alarm input module is provided with a separate terminal 1. However, it is common practice to run one common wire from terminal 1 to many field contacts to reduce the number of field wires required. When using common wiring, it is important to jumper together terminal 1 of the respective alarm cabinet modules to provide the correct amount of current source to the field contact.
The return wire from the field contact is wired to terminal 2 for each respective alarm mod­ule. Since the alarm system provides the power to the field contacts, it is important to verify that no other voltage source appears on either terminal 1 or terminal 2.
Note: On alarm systems where the alarm inputs are supplied from transistor switch out­puts, the V- of both systems has to be com­mon. If the system under test has this fea­ture, it must be verified by reviewing the elec­trical drawing, particularly the alarm module schematic.
In general, the solid state alarm system is a floating system. The V+ and V- should be verified as ungrounded.
6.1.2 Push-button Wiring. Verify that the push-button wires are correctly wired to all of the push buttons, including the push-button contacts. Refer to pages 13 through 20 for outlined dimensions and rear terminal
4
arrangements. Insure that normally open con­tacts are used. For example, if the wrong con­tacts (normally closed) are used, this is the same as having the operator pushing the push button continuously, which obviously will dras­tically affect the operation of the alarm system. Alarm systems using multiple alarm cabinets may use a common set of push buttons to con­trol the total system. A detailed check for prop­er installation is recommended, including diode type isolation, if specified on the electrical drawings.
6.1.3 Horn and Bell Wiring. Terminals H1, H2, and CA use short circuit protected drivers to drive associated relays and horns. The sug­gested minimum turn-on current of con­nected elements should be greater than 10 mA. The maximum horn current should not exceed 500 mA. If electronic horns are used, the horns can be directly connected to the audible output terminals (H1, H2). Systems using the conventional AC or DC horns and bells, must use a horn relay with suitable con­tact rating. On multiple alarm cabinet systems where individual power input is preferred, a horn relay must be used with each cabinet to maintain electrical isolation.
6.1.4 Power Supply. Verify the correct polarity of connection to the alarm systems. In the larg­er system, it is important to verify the wire sizes of the power leads to the alarm cabinets. To protect the larger alarm chassis, it is com­mon to provide more than one input to the cab­inet in which each section is provided with a separate filter, fuse and supply input terminals. In systems with multiple supply input, it is nec­essary for the customer to make V- connec­tions common.
6.1.5 Normally Open/Normally Closed Field Contacts.All alarm modules are equipped for
operation with normally open or normally closed field contacts. This is accomplished by using a jumper switch on each alarm module, identified as NO and NC for the normally open and normally closed position respectively. When the complete system is in operation, the field contact that opens with an alarm condition is termed a “normally closed” alarm input; con­versely, the field contact that closes with an alarm condition is termed a “normally open” alarm input.
6.1.6 Power Up. Carefully inspect the hookup wiring to insure conformity with the furnished schematic. Pay particular attention to power source polarity and verify that terminal 3 is
CAUTION
connected common for first alert sequence groups. Now remove the alarm modules one at a time and determine whether or not the normally closed/normally open switch is in the proper position and reinsert the card firmly, seating it in the connector. Power may now be applied to the system.
Upon power application, the flasher module within the system will automatically initiate a reset cycle. The system should then be in a quiescent state with the horn(s) off and no lamps flashing. Some lamps may, however, be on if their associated field contacts are in an abnormal condition.
Depression of TEST should cause all extin­guished lamps to come on flashing and the audible alarm to sound. From this point, refer to the particular Sequence Charts to obtain normal system operation. When testing an in­stalled system, be alert to the possibility that an actual alarm may initiate during the test procedure and appear to give conflicting results.

7.0 TROUBLESHOOTING

7.1 General

Simple attention to the obvious can often solve what appears to be a problem in the system.
A.Burned out, broken, or improperly seated
bulbs will not light.
B.Alarm modules not properly seated in their
connector will prevent alarm point(s) from functioning.
C.Alarm point pull-up resistors could be
burned providing no voltage at terminal 1.

7.2 Nonoperating Alarm System

A.Verify that the power source is operating
and that the V+ to V- voltage on the rear terminals is in the range of 18 V to 28 V. (Below 18 V, operation may prove erratic.) Be sure to verify polarity.
B.If the power supply fuse blows each time
power is applied:
1. Check the Power Supply Parts List for proper fuse size.
2. Remove Alarm System from the supply and try again. If fuse holds, double
5
check polarity and reconnect. If fuse still blows, remove all alarm modules and flasher and try again. If the fuse blows at this point, the problem has been isolated to a short in the internal wiring.
C. If power remains on, but any or all push but-
tons (SILENCE, TEST, RESET, ACKNOWL­EDGE) do not appear to function:
1. Verify proper wiring by measuring the voltage at terminal T, A, S and/or R as applicable. Voltage measurements are taken with respect to the V- terminal and should in all cases be zero volts with the button released and V+ (20-28 Vdc) with the button depressed.
2. If the problem persists, the Flasher Module is suspect. Replace the Flasher Module and try again.
3. Be alert to the possibility that a single board can, under unique conditions, cause what appears to be a system mal­function. The following is a typical exam­ple:
a) If a large group of F3A points comes
on fast flashing rather than intermit­tent flashing during TEST, one board can be sending a signal to all of the others. Afailure of the flasher or the test circuit is not necessarily indicat­ed.
b) In the above case, remove Alarm
Modules sequentially and repeat test­ing until the trouble clears.
c) As a general rule, common sense in
isolating the trouble will prevail. If one or more alarm boards appear to be malfunctioning, remove them from the system entirely before continuing. Fill their positions with boards from the upper left or lower right of the system so as to concentrate known good modules, and then proceed with diag­nostic and analysis of the remainder. Working with several scattered diverse problems simultaneously is nearly always self-defeating.
d)Refer to the section on Step-by-step
Procedures for further information.
6

7.3 Step-by-step Procedures

A. Check the system voltage and verify polar-
ity of supply input voltage and that the sys­tem voltage lines are not grounded.
B. Isolate all external devices except the input
power connections.
C. Unseat all alarm/lamp modules except the
No. 1 alarm module. At this point the only items plugged into the alarm chassis are one alarm module and flasher horn driver module. Jumper the push-button input ter­minals on the master module to simulate the correct connections for operations of the alarm system (since only normally open push-button contacts are used for all push­button functions, no connections will be made for normal operation).
D. Connect a simulating set of devices to
replace the field contact as shown on the electrical schematics on terminals 1 and 2.
E. Using the simulated field contacts and fol-
owing the test procedure instructions, check the sequence operation of the annunciator.
F. If the first alarm module does not operate
correctly, replace the flasher module to eliminate the possibility of a faulty flasher module. Once established that the flasher is functional, the fault will probably lie in one of the following areas:
1. A faulty alarm/lamp module.
2. No +24 Vdc at terminal 1.
3. Chassis wiring fault such as a short or cold solder joint.
G.After checking for proper operation of termi-
nal 1 output, remove the No. 1 alarm mod­ule and insert the No. 2 alarm module in the No. 1 chassis position. If the No. 2 alarm module operates correctly, this indi­cates that the No. 1 alarm module is faulty. Should the No. 2 alarm module not func­tion in the No. 1 chassis position, the fault lies in the chassis wiring.
H. If the failure is isolated in the chassis
wiring, remove each alarm input terminal plate and inspect for foreign objects which might cause a short. Review for any dam­aged wiring or broken connections to the printed circuit board connector. Finally, if the above procedure does not produce a solution to the fault, a thorough review of all solder joints is recommended.
I. Should No. 1 alarm function correctly, con-
tinue with the same procedure for checking all alarm/lamps modules by seating each module and using a simulating field contact switch at each alarm point. After the testing, should all the alarm/lamp modules function correctly, it must be assumed that the entire alarm system and modules are not faulty.
At this point, the error is now confined to the external wiring, possible push button or external equipment miswiring, or a short in the field contact wiring.
J. To avoid further damage to new alarm mod-
ules, do not place another alarm module into an alarm position that has produced cir­cuit board trace failures. Adetailed review of the trace failure will determine the reason for the failure. In most cases, damage can be the result of high voltage inputs or short­ing in the chassis.

8.0 ALARM MODULES

8.1 Integral/Push-button Flasher Modules
The X11SN System can operate with either an integral flasher or push-button flasher module. These flasher modules function to provide slow and fast flashing signals and filter the push­button signals to a V- active mode for the alarm cards. The integral flasher is identified by a red handle. The push-button flasher mod­ule is identified by the membrane switch and MAINTENANCE and POWER LED indication. The flasher module has the following specific field selectable options:
A.Slave or master flashing module control. B.ISA options 2 and/or 3. C. Normally energized/deenergized common
trouble alarm output. D. Time selectable auto-silence on Horn 1. E.Normally open/closed contact on mainte-
nance required relay. F. Normally open/closed contacts on alarm
point auxiliary relays (integral modules
only).
Slave (S) or Master (M) Flashing module is controlled by slide switch SW1. In the M posi­tion, the flasher will provide slow and fast flashing rates for all synchronized chassis. Chassis flashing is synchronized by connect­ing similar rear terminals F1, F2, and V-.
7
These terminals are located in the rear, lower left corner of the chassis. There can only be one master flasher in any synchronized chain. All other system flashers must be placed in the S position. Single system flashers must be placed in the M position for proper alarm sequence operation.
ISA option 2 provides an interlock to require operation of the silence push button before alarms can be acknowledged. This control is located at the selectable header location ISA2. In position 2, ISA option 2 is enabled. Otherwise, the system can be acknowledged at any time with ISA2 in the nonlabeled posi­tion. Push-button flasher modules that do not have a silence push button are permanently configured in the nonlabeled position.
ISA option 3 provides an interlock to require operation of the acknowledge push button before alarms can be reset by the reset push button. This interlock control is located at the selectable header location ISA3. In position 3, ISA option 3 is enabled. The nonlabeled posi­tion will allow system reset at anytime.
Common Trouble Alarm operation is deter­mined by the group alarm bus/CTA. This bus feeds the flasher as an input and is available to the user as an active low output at rear ter­minal CA. This terminal is located in the rear, lower left corner of the chassis. This output can be controlled as normally energized/deen­ergized at header location CTA.
In the NO position, the CA output will follow the alarm card CTA designation. For example, an alarm that follows the the field contacts NDE (normally deenergized) will provide an active V- output at CAwhen any field contact is abnormal and the flasher CTA selection is NO. The user could configure this particular system as normally energized CA following field contacts by putting the CTA switch in the NC position.
Users who elect to have the automatic horn silence option on Horn 1 configure the horn time at header locations TADJ (time adjust­ment) and TRNG (time range). The available horn time ranges are 1 and 10 minutes. These ranges are selected at the TRNG header in the respective 1 and 10 positions. Half-time and full time is selected at header location TADJ in the respective L (low) and H(high) positions. For example; 30 second Horn 1 auto-silence is selected by placing TRNG in position 1 and TADJ in position L.
The other available configurations are shown in the table below.
Horn 1
TRNG TADJ Auto Silence
1 L 30 sec.
1 H 1 min.
10 L 5 min. 10 H 10 min.
All flashers have a maintenance required relay that energizes on flasher failure or when 24 volts is applied at terminal block F3 in the rear, lower left corner of the chassis. Flasher failure occurs when either the fast or slow flash signals are not available to the alarm card bus. The relay contact is available to the user on terminals F5 and F6. The Normally open or closed status can be selected on the flasher card at the header selector switch MAIN as NO and NC respectively. Push-but­ton flashers have an additional red MAINTE­NANCE front panel LED that can additionally follow the CTA or AL2 bus. This LED behavior is permanently selected during initial order­ing. The green POWER LED indicates when 24 volts is applied to system power.
Systems that occupy the flasher cabinet with alarm points can specify up to two auxiliary relays on the integral flasher card. Header selector switches (RLYA, RLYB) are also on the flasher card to determine the normally open or closed status.

8.2 Alarm Sequence/Display Module

The module X11SN is offered in two separate sequences as described in ANSI/ISAS18.1­1979 (R1985). On PCB X11-1013C and X11­1020, the operating sequence is selected as labeled at respective headers SEQA-SEQD. On the programmable version (PCB X11­1019B), the sequence selection is made at slide switch SEQ. Switches 1-4 are connect­ed for field contacts FCA-FCD respectively.
J5 and J6 of PCB X11-1019B are used when the field contact selectable time delay board is ordered. The time delay selects 1 of 32 dif­ferent time responses using switch TIME. Each field contact can bypass this selection using switch BYPASS. BYPASS switch posi­tions 1-4 correspond to field contacts FCA­FCD respectively and will have the nominal 20 ms. response when selected. Otherwise,
Bypass Switch Selection
Channel A(1) and Channel C(3) in ON position by­passes the time selected by TIME. The FC response for Channel Aand Channel C will be 20 ms. nominal. Channel B(2) and Channel D(4) in off position selects the field contact response selected by TIME, in this case, 3.0 seconds.
Time Switch Selection
The table below shows that with switches 2 and 3 in the ON position and 1, 4, and 5 in the OFF position,
3.0 seconds is selected for field contact response.
Detail A: Time Board Operation Example.
the field contact response will be the time selected by switch TIME. See Figure 2, Detail A for a time board operation example.
Dual horn selection is offered as an option to choose the active horn bus HORN1 and HORN2. This option should be used when the user needs to separate module groups by activating different horns. On PCBs X11­1013C and X11-1020, the horn selection is made at headers HORNA-HORND. These refer to associated field contacts FCA-FCD. The programmable version uses a slide switch labeled HORN. The OFF position selects HORN1 and the ON position selects HORN2. Switches 1-4 are connected for field contacts FCA-FCD respectively.
Although ordering auxiliary relay boards is not mandatory, the X11SN system is designed so that auxiliary relay behavior must be selected. The basic options available choose between Normally Energized/Deenergized following the field contact or alarm cycle behavior. The spe­cific options available can be consulted in the X11SN sales brochure. When selectable auxil­iary behavior is chosen, an on board selector switch is located at SW1 on PCBs X11-1013C and X11-1020. PCB X11-1019B uses selector switch AUX. See specific sequence charts for specific auxiliary relay behavior. NOTE: Unless otherwise specified, the standard auxil­iary relay option is normally non-energized fol­low field contact.
PCB X11-1019B (programmable) has an addi­tional header J7 and slideswitch GEN. The header J7 is used for parallel port program­ming of the device located at U6. This header should remain unconnected and without any additional connected shunts during normal cir­cuit operation. The slideswitch GEN is provid­ed when unusual or non-standard circuit per­formance or configuration is necessary. Normally, most assemblies do not populate slideswitch GEN. See Figure 3 (see page 9), Details B and C for header and switch loca­tions of PCB X11-1019B.
The combination display/alarm module con­tains a single, dual, triple, or quad alarm chan­nel circuit with the appropriate lamp display constructed as a single plug-in module. The modules are removable from the front of the system without the interference to the remain­ing channels of the
8
Figure 2: X11-1024 PCB Switch Locations.
Switch Time Time Switch Time Time
12345 Delay 12345 Delay
00000 50 msec. 00001 45 sec. 10000 100 msec. 10001 1 min.
01000 300 msec. 01001 90 sec.
11000 0.5 sec. 11001 2 min.
00100 1.0 sec. 00101 3 min. 10100 2.0 sec. 10101 4 min.
01100 3.0 sec. 01101 5 min. 11100 4.0 sec. 11101 6 min.
00010 5.0 sec. 00011 7 min. 10010 6.0 sec. 10011 8 min.
01010 7.0 sec. 01011 9 min.
11010 8.0 sec. 11011 10 min. 00110 9.0 sec. 00111 15 min.
10110 10.0 sec. 10111 30 min. 01110 15.0 sec. 01111 45 min.
1111 0 30.0 sec. 11111 60 min.
system. The window display areas are con­tained within Ronan’s standard colored­bezels, allowing multiline engraving on sin­gle or sandwich lenses. The alarm logic may interface with a normally open or normally closed field contact. The field contacts are interrogated by the system’s 24 Vdc logic supply, or optionally, with 125 Vdc from a dual output power supply, if so specified. In addition, the module’s input circuit is designed to accept a logic voltage without external components.
9
C30
C29
R46
R30
R31
C21
J4
J5
C2
R6
Z1
R7Z2
C5
R4
D1
C3
R8 C6 R9 R10
COMPONENT SIDE
C9 C10
NO
NO
NO
NO
FCA
NC
FCB
NC
FCC
NC
FCD
NC
C16
R29
R69
R66
R56
R64
C24
C20
C15
C7
R14
R26
J3
B
A
J1
R43
R24
R12
R12
C1
R2
Z3
Z4
Z7
Z8
J2
Z16
Z15
Z14
Z13
Z12
Z11
Z10
Z9
U6
R80
R81
VR1
J7
R76
U11
J6
Q8
Q6
Q5
Q4
Q3
Q2
Q1
C23
D3
D4
D5
D6 D7
D8 D9
D10
D2
R20
R19 C11
Q7
U7
C44
C45
R84
U12
U8
Q9
GEN
AUX
HORN
SEQ
C33
C32
C34 C35
D14
R73
R74
R75
U10
C28
R62
R51
R52
R34 R35 R36
C17 R37 R38
Z5
Z6
R53
R54
R21
R39
C13
C18
C14
C19
R22
R40
R23
R55
PBA PBB PBC PBD
C12
C4
R18
R63
R83
R82
R77
L5
L7
L6
L4
L3
L1
L2
L8
D13
D12
D11
U9
U13
U14
C31
R79
R78
R72
U4
C22
R61
R58
C26
R15
R11
R1
R27
R16
R28
R44
R67 R68
R57
R25
R13
R41
R42
R65
R45
U5
U1
C8
C25
R60
R59
R71
R70
C36
C37
C38
C39
C40
C41
C42
C43
C27
R49
R32
R48
R47
R50
R33
R3
R17
R5
U2
U3
Figure 3: X11-1019B PCB Switch Locations.
SEQ Switch Selection
Channel A(1) and Channel B(2) in ON position selects M Sequence. Channel C(3) and Channel D(4) in OFF position selects ASequence.
Horn Switch Selection (Optional)
Channel A(1) and Channel C(3) in OFF position selects Horn1. Channel B(2) and Channel D(4) in ON position selects Horn2.
FCA
NC
NO
NO
NO
NO
FCB
NC
FCC
NC
FCD
NC
Field Contact Switch Selection
FCA and FCB set in the positions shown select Normally Open Field Contacts. FCC and FCD set in the positions shown, select Normally Closed Field Contacts.
Detail C: Field Contact Switch Selection Example.
Detail B: Example X11SN4MA0122* Card Switch Selection.
Sequence “M” Manual Reset or “A” Automatic Reset.
* See X11SN Window Annunciator Systems sales brochure for
* alarm card assembly numbers.
ON
1
SEQ
2
GEN
3
4
AUX
HORN
ON
1
2
3
4

9.2 M, Manual Reset

1. Acknowledge, reset and test push buttons.
2. Alarm audible device.
3. Lock-in momentary alarms until acknowledged.
4. The audible device is silenced and flashing stops when acknowledged.
5. Manual reset of acknowledged alarm indications after process conditions return to normal.
6. Operational test.

8.3 Output Features

The X11SN System provides the following fea­tures on the terminal located in the lower, left, rear terminal plate.
8.3.1 Common Trouble Alarm. This output is
at terminal CA and follows the field contacts A 24 Vdc relay wired between CA and V+ will energize whenever a point is abnormal (in alarm) and the relay will stay energized until all points in the system return to normal.
8.3.2 Reflash. This output is at terminal F4
and follows the field contacts. A 24 Vdc relay wired between F4 and V+ will energize when­ever a point is abnormal (in alarm). If a sec­ond point goes abnormal (in alarm) while the first point is still abnormal, the reflash module briefly returns to normal then goes abnormal until all points return to normal.
8.3.3 Auxiliary Contact Module. The auxiliary
contact module is available with a single, dual, triple or quad relay circuit, accommodating the
window density selected. The modules plug in from the front of the system and may be pur­chased initially or added later in the field. The terminals for the contact outputs are furnished as part of the system. Each relay provides a selec­table Form A or B type contact with a rating of 2 A at 28 Vdc. Relays are available in either Hermetically Sealed or General Purpose types.
Normally open (Type A) or normally closed (Type B) contact is available for each alarm point at their respective rear terminal block terminals 5 and 6. The normal operation (NO/ NC) can be changed on the auxiliary contact module at head­ers marked AUX1, AUX2, AUX3, or AUX4.
8.3.4 Transistor Output
Terminal 4 (TO) of each alarm I/O terminal strip provides an open collector output (pulling to -V) programmable for various system functions. A typical application is to drive an auxiliary relay following the field contact or lamp logic.
10

9.0 STANDARD SEQUENCES (For other special sequences consult factory)

9.1 A, Automatic Reset

1. Acknowledge and test push buttons.
2. Alarm audible device.
3. Lock-in of momentary alarms until
acknowledged.
4. The audible device is silenced and
flashing stops when acknowledged.
5. Automatic reset of acknowledged
alarm indications when process conditions return to normal.
6. Operational test.
PROCESS
PROCESS
PROCESS
PROCESS
PROCESS
ABNORMAL OR NORMAL
NORMAL
ABNORMAL
ABNORMAL OR NORMAL
ABNORMAL OR NORMAL
FIRST OUT
RESET
FIRST ABNORMAL
RETURN TO
NORMAL
FIRST OUT RESET
WHILE NORMAL
SUB ALARM
NORMAL
SUB ACKNOWLEDGED
FIRST OUT RESET
WHILE ABNORMAL
FIRST ACKNOWLEDGED
SLOW FLASHING
FIRST ALARM
ACKNOWLEDGE WHILE NORMAL
SUBSEQUENT
ABNORMAL
ACKNOWLEDGE
WHILE
ABNORMAL
FAST FLASH
OFF
ON
INTERMITTENT FLASHING
SEQUENCE
SEQUENCE
SEQUENCE
SEQUENCE
SEQUENCE
VISUAL
VISUAL
VISUAL
VISUAL
VISUAL
AUDIBLE
AUDIBLE
AUDIBLE
AUDIBLE
AUDIBLE
AUDIBLE
SILENT
SILENT
SILENT
ACKNOWLEDGE
AUDIBLE
SEQUENCE DIAGRAM
9.3 F3A, Automatic Reset First Out with First Out Flashing and Reset Push Button
1. Acknowledge, first-out reset and test push buttons.
2. Alarm audible device.
3. Lock-in of momentary alarms until acknowledged.
4. First-out flashing different from subsequent flashing.
5. First-out reset push button to change the first out visual indication to be the same as subsequent visual indications.
6. Automatic reset of acknow­ledge alarm indications when process conditions return to normal.
7. Operational test.

9.4 R, Ringback (Ronan ID RD)

1. Acknowledge, reset, and test push buttons.
2. Alarm and ringback audible devices.
3. Lock-in of momentary alarms until acknowledged.
4. The audible device is silenced and fast flashing stops when acknowledged.
5. Ringback visual and audible indications when process conditions return to normal.
6. Manual reset of ringback indications.
7. Operational test.
11
9.0 SEQUENCES (CONT.)
PROCESS
PROCESS
PROCESS
PROCESS
ABNORMAL
NORMAL
NORMAL
ABNORMAL OR NORMAL
RESET
TO ABNORMAL
RETURN
TO NORMAL
RETURN TO ABNORMAL
ACKNOWLEDGE
WHILE ABNORMAL
ACKNOWLEDGE WHILE NORMAL
ACKNOWLEDGED
RINGBACK
NORMAL
ALARM
ON
SLOW FLASHING
OFF
FAST FLASHING
RINGBACK AUDIBLE
RINGBACK AUDIBLE
RINGBACK AUDIBLE
RINGBACK AUDIBLE
ALARM AUDIBLE
ALARM AUDIBLE
ALARM AUDIBLE
ALARM AUDIBLE
SEQUENCE
SEQUENCE
SEQUENCE
SEQUENCE
VISUAL
VISUAL
VISUAL
VISUAL
SILENT
SILENT
SILENT
AUDIBLE
SILENT
AUDIBLE
SILENT
SILENT
SEQUENCE DIAGRAM
PROCESS
PROCESS
PROCESS PROCESS
NORMAL
ABNORMAL OR NORMAL
ABNORMAL OR NORMAL
ABNORMAL OR NORMAL
SUBSEQUENT TO ABNORMAL
ACKNOWLEDGE
WHILE NORMAL
SUBSEQUENT ALARM
ACKNOWLEDGE WHILE ABNORMAL
NORMAL
ACKNOWLEDGED
FIRST ALARM
ACKNOWLEDGE
(FIRST OUT RESET)
FIRST TO
ABNORMAL
RETURN TO
NORMAL
ON
OFF
ON
SLOW FLASHING
SEQUENCE
SEQUENCE
SEQUENCE SEQUENCE
VISUAL
VISUAL
VISUAL VISUAL
AUDIBLE
AUDIBLE
AUDIBLE AUDIBLE
AUDIBLE
SILENT
SILENT AUDIBLE
SEQUENCE DIAGRAM
9.5 F2A, Automatic Reset First Out with No Subsequent Alarm Flashing
(Ronan ID FS)
1. Acknowledge, reset, and test push
buttons.
2. Alarm audible device.
3. Lock-in of momentary alarms until
acknowledged.
4. Flashing indication for first alarm only.
New subsequent alarms have the same visual indication as acknow­ledged alarms.
5. First out indication is reset when
acknowledged.
6. Automatic reset of acknowledged
alarm indications when process conditions return to normal.
7. Operational test.
9.6 F2M, Manual Reset First Out with
No Subsequent Alarm Flashing
(Ronan ID FSM)
1. Acknowledge, reset, and test push buttons.
2. Alarm audible device.
3. Lock-in of momentary alarms until acknowledged.
4. Flashing indication for first alarm only. New subsequent alarms have the same visual indication as acknow­ledged alarms.
5. First out indication is reset when acknowledged.
6. Manual reset of acknowledged alarm indications after process conditions return to normal.
7. Operational test.
12
9.0 SEQUENCES (CONT.)
PROCESS
PROCESS
PROCESS PROCESS
NORMAL
ABNORMAL OR NORMAL
ABNORMAL OR NORMAL
ABNORMAL OR NORMAL
SUBSEQUENT TO ABNORMAL
SUBSEQUENT ALARM
ACKNOWLEDGE
NORMAL
ACKNOWLEDGED
FIRST ALARM
ACKNOWLEDGE
(FIRST OUT RESET)
FIRST TO
ABNORMAL
RESET WHILE
NORMAL
ON
OFF
ON
SLOW FLASHING
SEQUENCE
SEQUENCE
SEQUENCE SEQUENCE
VISUAL
VISUAL
VISUAL VISUAL
AUDIBLE
AUDIBLE
AUDIBLE AUDIBLE
AUDIBLE
SILENT
SILENT AUDIBLE
SEQUENCE DIAGRAM

10.1Monalarm Dimensional Drawings

13
A Overall
A Overall
B Cutout
B Cutout
2.75” (69.85 mm) High x
3.00” (76.20 mm) Wide Alarm Window
Optional Push-button Flasher Module or Front Accessible Flasher Module
14.12(358.78 mm)
0.56(14.22 mm)
2.00 (50.80 mm)
Removable Rear Cover with Captive Fasteners
A
0.75(19.05 mm) Conduit Knock-out
Flush-mount - Front View X11SN-1000 & X11SNLR-1000
Relay Rack-mount - Front and Side View X11SNRR-1000
Flush-mount - Side View X11SN-1000
Flush-mount - Side View X11SNLR-1000
11.75(298.45 mm)
0.56(14.22 mm) Max. Panel Thickness
Field Wiring Terminal
Rear Cover Removed
Fuse
A
Less Rear
Detail A
19.00(482.60 mm) Overall
A
Overall
17.75(450.85 mm) Rack Opening
2.75(69.85 mm) High x 3.00(76.20 mm) Wide Alarm Window
11.75(298.45 mm)
Fuse
Field Contact Terminals
No. of Windows A Overall B Cutout
High or Wide Inches mm Inches mm
1 5.00 127.00 4.38 111.25 2 8.50 215.90 7.88 200.15 3 12.00 304.80 11.38 289.05 4 15.50 393.70 14.88 377.95 5 19.00 482.60 18.38 466.85 6 22.50 571.50 21.88 555.75 7 26.00 660.40 25.38 644.65 8 29.50 749.30 28.88 733.55
9 33.00 838.20 32.50 825.50 10 36.50 927.10 36.00 914.40 11 40.00 1016.00 39.50 1003.30 12 43.50 1104.90 43.00 1092.20
Number of Number of A Overall
Windows High Windows Wide Inches mm
1* 5** 3.50 88.90 2* 5** 7.00 177.80 3* 5** 10.50 266.70 4* 5** 14.00 355.60
**Not limited to 2 high.
**Limited to 5 wide only. 19.00” (482.60) mm rack. Also available 6 wide. 24.00” (609.60 mm) rack.
A
A
10.2Dualarm Dimensional Drawings
19.00(482.60 mm) Overall
A
Overall
17.75(450.85 mm) Rack Opening
1.44(35.56 mm) High x 3.00(76.20 mm) Wide Alarm Window
Flush-mount - Front View X11SN-2000 & X11SNLR-2000
Relay Rack-mount - Front and Side View X11SNRR-2000
Flush-mount - Side View X11SN-2000
Flush-mount - Side View X11SNLR-2000
11.75(298.45 mm)
0.56(14.22 mm) Max. Panel Thickness
Field Wiring Terminal
Rear Cover Removed
Fuse
A
Less Rear
Detail A
11.75(298.45 mm)
Fuse
Field Contact Terminals
No. of Windows A Overall B Cutout
High Wide Inches mm Inches mm
2 6 5.00 127.00 4.38 111.25 4 2 8.50 215.90 7.88 200.15 6 3 12.00 304.80 11.38 289.05
8 4 15.50 393.70 14.88 377.95 10 5 19.00 482.60 18.38 466.85 12 6 22.50 571.50 21.88 555.75 14 7 26.00 660.40 25.38 644.65 16 8 29.50 749.30 28.88 733.55 18 9 33.00 838.20 32.50 825.50 20 10 36.50 927.10 36.00 914.40 22 11 40.00 1016.00 39.50 1003.30 24 12 43.50 1104.90 43.00 1092.20
Number of Number of A Overall
Windows High Windows Wide Inches mm
1* 5** 3.50 88.90 2* 5** 7.00 177.80 3* 5** 10.50 266.70 4* 5** 14.00 355.60
**Not limited to 2 high.
**Limited to 5 wide only. 19.00” (482.60) mm rack. Also available 6 wide. 24.00” (609.60 mm) rack.
A Overall
A Overall
B Cutout
B Cutout
1.44(69.85 mm) High x
3.00(76.20 mm) Wide Alarm Window
Optional Push-button Flasher Module or Front Accessible Flasher Module
14
A B
A
B
14.12(358.78 mm)
0.56(14.22 mm) Max. Panel Thickness
A
2.00 (50.80 mm)
Removable Rear Cover with Captive Fasteners
0.75(19.05 mm) Conduit Knock-out
10.3 Trilarm Dimensional Drawings
15
A Overall
A Overall
B Cutout
B Cutout
.86(69.85 mm) High x
3.00(76.20 mm) Wide Alarm Window
Optional Push-button Flasher Module or Front Accessible Flasher Module
14.12(358.78 mm)
0.56(14.22 mm)
2.00 (50.80 mm)
Removable Rear Cover with Captive Fasteners
A
0.75(19.05 mm) Conduit Knock-out
Flush-mount - Front View X11SN-3000 & X11SNLR-3000
Relay Rack-mount - Front and Side View X11SNRR-3000
Flush-mount - Side View X11SN-3000
Flush-mount - Side View X11SNLR-3000
11.75(298.45 mm)
0.56(14.22 mm) Max. Panel Thickness
Field Wiring Terminal
Rear Cover Removed
Fuse
A
Less Rear
Detail A
19.00(482.60 mm) Overall
A
Overall
17.75(450.85 mm) Rack Opening
.86(21.84 mm) High x 3.00(76.20 mm) Wide Alarm Window
11.75(298.45 mm)
Fuse
Field Contact Terminals
No. of Windows A Overall B Cutout
High Wide Inches mm Inches mm
3 1 5.00 127.00 4.38 111.25 6 2 8.50 215.90 7.88 200.15
9 3 12.00 304.80 11.38 289.05 12 4 15.50 393.70 14.88 377.95 15 5 19.00 482.60 18.38 466.85 18 6 22.50 571.50 21.88 555.75 21 7 26.00 660.40 25.38 644.65 24 8 29.50 749.30 28.88 733.55 27 9 33.00 838.20 32.50 825.50 30 10 36.50 927.10 36.00 914.40 33 11 40.00 1016.00 39.50 1003.30 36 12 43.50 1104.90 43.00 1092.20
Number of Number of A Overall
Windows High Windows Wide Inches mm
1* 5** 3.50 88.90 2* 5** 7.00 177.80 3* 5** 10.50 266.70 4* 5** 14.00 355.60
**Not limited to 2 high.
**Limited to 5 wide only. 19.00” (482.60) mm rack. Also available 6 wide. 24.00” (609.60 mm) rack.
A
B C
A
B C

10.4 Quadalarm Dimensional Drawings

16
A Overall
A Overall
B Cutout
B Cutout
1.44(35.56 mm) High x
1.44(35.56 mm) Wide Alarm Window
Optional Push-button Flasher Module or Front Accessible Flasher Module
14.12(358.78 mm)
0.56(14.22 mm)
2.00 (50.80 mm)
Removable Rear Cover with Captive Fasteners
A
0.75(19.05 mm) Conduit Knock-out
Flush-mount - Front View X11SN-4000 & X11SNLR-4000
Relay Rack-mount - Front and Side View X11SNRR-4000
Flush-mount - Side View X11SN-4000
Flush-mount - Side View X11SNLR-4000
11.75(298.45 mm)
0.56(14.22 mm) Max. Panel Thickness
Field Wiring Terminal
Rear Cover Removed
Fuse
A
Less Rear
Detail A
19.00(482.60 mm) Overall
A
Overall
17.75(450.85 mm) Rack Opening
1.44(35.56 mm) High x 1.44(35.56 mm) Wide Alarm Window
11.75(298.45 mm)
Fuse
Field Contact Terminals
No. of Windows A Overall B Cutout
High or Wide Inches mm Inches mm
2 5.00 127.00 4.38 111.25 4 8.50 215.90 7.88 200.15 6 12.00 304.80 11.38 289.05
8 15.50 393.70 14.88 377.95 10 19.00 482.60 18.38 466.85 12 22.50 571.50 21.88 555.75 14 26.00 660.40 25.38 644.65 16 29.50 749.30 28.88 733.55 18 33.00 838.20 32.50 825.50 20 36.50 927.10 36.00 914.40 22 40.00 1016.00 39.50 1003.30 24 43.50 1104.90 43.00 1092.20
Number of Number of A Overall
Windows High Windows Wide Inches mm
1* 5** 3.50 88.90 2* 5** 7.00 177.80 3* 5** 10.50 266.70 4* 5** 14.00 355.60
**Not limited to 2 high.
**Limited to 5 wide only. 19.00” (482.60) mm rack. Also available 6 wide. 24.00” (609.60 mm) rack.
A
B
C
D
A
B
C
D
17
10.5 Standard Rear Terminal Arrangements and Wiring - 24 Vdc
Monalarm X11SN-1000
Binalarm X11SN-2000
Trialarm X11SN-3000
Quadalarm X11SN-4000
AB
ABAB
1
2
3
G
CA
V-V
+
V
+
V
+
24 Vdc Input
Electronic
Horn
AC Horn
Horn 1 Relay
Ack
Silence
Test
Reset
Horn 2 Relay
7
7
72
3
1
31
2 2
K1
K2
K1 or K2
Common
Trouble
K3
K3
V
+
V-
DETAIL A
DETAIL B
DETAIL C
FUSE
Typical Field Contact Wiring For All Alarm Positions
*
*
*
*
T
S
A
R H1 H2
AB
AB
C
C
AB
1
2
3
G
CA
V-V
+
V
+
V
+
24 Vdc Input
Electronic
Horn
AC Horn
Horn 1 Relay
Ack
Silence
Test
Reset
Horn 2 Relay
7
7
72
3
1
31
2 2
K1 K2
K1 or K2
Common
Trouble
K3
K3
V
+
V-
DETAIL A
DETAIL B
DETAIL C
FUSE
Typical Field Contact Wiring For All Alarm Positions
*
*
*
*
T
S
A R
H1
H2
AB
AB
C
C
D
ADB
1
2
3
G
CA
V-V
+
V
+
V
+
24 Vdc Input
Electronic
Horn
AC Horn
Horn 1 Relay
Ack
Silence
Test
Reset
Horn 2Relay
7
7
72
3
1
31
2 2
K1 K2
K1 or K2
Common
Trouble
K3
K3
V
+
V-
DETAIL A
DETAIL B
DETAIL C
FUSE
Typical Field Contact Wiring For All Alarm Positions
*
*
*
*
T
S
A
R H1 H2
Detail A
1. (F1, F2) flasher sync. connect for multi chassis applications.
2. (F3) apply +24 Vdc to activate maintenance required LED and relay.
3. (F5/F6) maintenance required relay contact output.
4. In last position (3) of Trialarm and Quadalarm units, the flasher occu­pies positions “C” and “D”, there­fore, only positions “A” and “B” are available.
Notes:
Detail B
5. (ME) Used to form first alert groups.
6. Auxiliary output NO/NC selectable.
7. (TO) Transistor Output.
Detail C
8. (CA) common trouble alarm transis­tor driver output.
Flasher Sync
for Multichassis
Applications
Reflash Output or
Lamp Inhibit +24Vdc
Maintenance
Required Dry Contact
F1 F2
24 Vdc Input to Activate
F3
Maintenance
F4
Required Relay and LED
F5 F6
V+
CA
V+
To Push-button
Wiring
Common
Trouble
2
7
K3
3
1
K3
18

10.6 Rear Terminal Arrangements and Wiring for 125 Vdc Field Contact

Monalarm X11SN-1000
Binalarm X11SN-2000
Trialarm X11SN-3000
Quadalarm X11SN-4000
A
A
B
B
A
B
1
2
3
G
CA
V-V
+
V
+
V
+
24 Vdc
Input
125 Vdc
Field
Contact
Input
Electronic
Horn
AC Horn
Horn 1 Relay
Ack
Silence
Test
Reset
Horn 2 Relay
7
7
72
3
1
31
2 2
K1 K2
K1 or K2
+
Common
Trouble
K3
K3
V
+
V-
-
DETAIL A
DETAIL B
DETAIL C
FUSE
Typical Field Contact Wiring For All Alarm Positions
*
*
*
*
T S A R
H1
H2
A
A
B
C
C
B
A
B
1
2
3
G
CA
V-V
+
V
+
V
+
24 Vdc
Input
125 Vdc
Field
Contact
Input
Electronic
Horn
AC Horn
Horn 1 Relay
Ack
Silence
Test
Reset
Horn 2 Relay
7
7
72
3
1
31
2 2
K1 K2
K1 or K2
+
Common
Trouble
K3
K3
V
+
V-
-
DETAIL A
DETAIL B
DETAIL C
FUSE
Typical Field Contact Wiring For All Alarm Positions
*
*
*
*
T S A
R H1 H2
A
A
B
C
CD
D
B
A
B
1
2
3
G
CA
V-V
+
V
+
V
+
24 Vdc
Input
125 Vdc
Field
Contact
Input
Electronic
Horn
AC Horn
Horn 1 Relay
Ack
Silence
Test
Reset
Horn 2 Relay
7
7
72
3
1
31
2 2
K1 K2
K1 or K2
+
Common
Trouble
K3
K3
V
+
V-
-
DETAIL A
DETAIL B
DETAIL C
FUSE
Typical Field Contact Wiring For All Alarm Positions
*
*
*
*
T S A R
H1
H2
Detail A
1. (F1, F2) flasher sync. connect for multi chassis applications.
2. (F3) apply +24 Vdc to activate maintenance required LED and relay.
3. (F5/F6) maintenance required relay contact output.
4. In last position (3) of Trialarm and Quadalarm units, the flasher occu­pies positions “C” and “D”, there­fore, only positions “A” and “B” are available.
Notes:
Detail B
5. (ME) Used to form first alert groups.
6. Auxiliary output NO/NC selectable.
7. (TO) Transistor Output.
Detail C
8. (CA) common trouble alarm transis-
tor driver output.
Flasher Sync
for Multichassis
Applications
Reflash Output or
Lamp Inhibit +24Vdc
Maintenance
Required Dry Contact
F1 F2
24 Vdc Input to Activate
F3
Maintenance
F4
Required Relay and LED
F5 F6
V+
CA
V+
To Push-button
Wiring
Common
Trouble
2
7
K3
3
1
K3
10.7 Rear Terminal Arrangements and Wiring for Transistor Input
Binalarm X11SN-2000
Trialarm X11SN-3000
Quadalarm X11SN-4000
Detail A
1. (F1, F2) flasher sync. connect for multi chassis applications.
2. (F3) apply +24 Vdc to activate maintenance required LED and relay.
3. (F5/F6) maintenance required relay contact output.
4. In last position (3) of Trialarm and Quadalarm units, the flasher occu­pies positions “C” and “D”, there­fore, only positions “A” and “B” are available.
Notes:
Detail B
5. (ME) Used to form first alert groups.
6. Auxiliary output NO/NC selectable.
7. (TO) Transistor Output.
Detail C
8. (CA) common trouble alarm transis­tor driver output.
19
DETAIL A
2 2
K1
K2
T S A R
7
H1
H2
7 31
Common
Trouble
CA
Test
Silence
Ack
Reset
Horn 1 Relay
Horn 2 Relay
AC Horn
Electronic
Horn
K1 or K2
+
V
72
K3
3
1
K3
+
V
DETAIL C
DETAIL B,Typical for
All Alarm Positions
G
+
V-V
3
24 Vdc Input
FUSE
V-
+
V
Flasher Sync
for Multichassis
Applications
Reflash Output or
Lamp Inhibit +24Vdc
Maintenance
Required Dry Contact
F1 F2
24 Vdc Input to Activate
F3
Maintenance
F4
Required Relay and LED
F5 F6
BA
2
1
DETAIL A
2 2
K1 K2
T S A R
7
H1
H2
7 31
Common
Trouble
CA
72
1
V+V
K3
K3
+
3
Test
Silence
Ack
Reset
Horn 1 Relay
Horn 2 Relay
AC Horn
Electronic
Horn
K1 or K2
DETAIL A
2 2
K1 K2
T S A R
7
H1
H2
7 31
Common
Trouble
CA
72
1
K3
+
+
V
V
K3
3
Test
Silence
Ack
Reset
Horn 1 Relay
Horn 2 Relay
AC Horn
Electronic
Horn
K1 or K2
DETAIL B,Typical for
3
DETAIL C
24 Vdc Input
DETAIL B,Typical for
3
DETAIL C
24 Vdc Input
All Alarm Positions
G
+
V-V
FUSE
2
V-
+
V
All Alarm Positions
G
+
V-V
FUSE
2
V-
+
V
CB A
1
DCBA
1
V+
CA
V+
To Push-button
Wiring
Common
Trouble
2
7
K3
3
1
K3
20
10.8 Rear Terminal Arrangements and Wiring for Opto-coupled Input 115 Vac, 24 Vdc, 48 Vdc, 125 Vdc
Monalarm X11SN-1000
Binalarm X11SN-2000
Trialarm X11SN-3000
Quadalarm X11SN-4000
AB
A
AB
B
1
2
3
G
CA
V-V
+
V
+
V
+
24 Vdc Input
Electronic
Horn
AC Horn
Horn 1 Relay
Ack
Silence
Test
Reset
Horn 2 Relay
7
7
72
3
1
31
2 2
K1
K2
K1 or K2
Common
Trouble
K3
K3
V
+
V-
DETAIL A
DETAIL C
DETAIL B
FUSE
Typical Field Contact NO or NC
+++
+
++
*
*
*
*
Input Voltage
T S A
R H1 H2
ABC
A
ABB
C
T
S
A R
H1
1
2
3
H2
G
CA
V-V
+
V
+
V
+
24 Vdc Input
Electronic
Horn
AC Horn
Horn 1 Relay
Ack
Silence
Test
Reset
Horn 2 Relay
7
7
72
3
1
31
2 2
K1 K2
K1 or K2
Common
Trouble
K3
K3
V
+
V-
DETAIL A
DETAIL C
DETAIL B
FUSE
Typical Field Contact NO or NC
++
+
+
+
+
++
*
*
*
*
Input Voltage
ABC
ADD
ABB
C
T
S A R
H1
1
2
3
H2
G
CA
V-V
+
V
+
V
+
24 Vdc Input
Electronic
Horn
AC Horn
Horn 1 Relay
Ack
Silence
Test
Reset
Horn 2 Relay
7
7
72
3
1
31
2 2
K1 K2
K1 or K2
Common
Trouble
K3
K3
V
+
V-
DETAIL A
DETAIL B
DETAIL C
FUSE
Typical Field Contact NO or NC
++
+
+
+
+++++
*
*
*
*
Input Voltage
Detail A
1. (F1, F2) flasher sync. connect for multi chassis applications.
2. (F3) apply +24 Vdc to activate maintenance required LED and relay.
3. (F5/F6) maintenance required relay contact output.
4. In last position (3) of Trialarm and Quadalarm units, the flasher occu­pies positions “C” and “D”, there­fore, only positions “A” and “B” are available.
Notes:
Detail B
5. (ME) Used to form first alert groups.
6. Auxiliary output NO/NC selectable.
7. (TO) Transistor Output
Detail C
8. (CA) common trouble alarm transis­tor driver output.
Flasher Sync
for Multichassis
Applications
Reflash Output or
Lamp Inhibit +24 Vdc
Maintenance
Required Dry Contact
F1
F2
24 Vdc Input to Activate
F3
Maintenance
F4
Required Relay and LED
F5 F6
V+
CA
V+
To Push-button
Wiring
Common
Trouble
2
7
K3
3
1
K3
X11SN FLASHER
SWITCH/JUMPER OPTIONS
DRAWING NUMBER
X11C387
REV
0
21
RONAN ENGINEERING RONAN ENGINEERING RONAN ENGINEERING COMPANY LIMITED U.K. LIMITED .
21200 Oxnard Street 1 Tilley Road 32 Bermondsey Road Woodland Hills Crowther Industrial Estate Toronto, Ontario California 91367 U.S.A. Washington, Tyne and Wear Canada M4B 1Z5 (800) 327-6626 • FAX (818) 992-6435 United Kingdom, NE38 OAE (416) 752-0310 • FAX (416) 752-8072 E-Mail: info@ronan.com (191) 416-1689 • FAX (191) 416-5856 Web Site: http//www.ronan.com
X11SNI&O / Rev. 2 Printed in U.S.A.
Loading...