Ronan X11SN User Manual

Instructions
and
Operating Manual
SERIES X11SN
WINDOW ANNUNCIATOR
SYSTEMS
TABLE OF CONTENTS
1.0 General Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
3.0 Expansion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
4.0 Auxiliary Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
5.0 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
6.0 Power Up and Test Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
6.1 Wiring Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
7.0 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
7.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
7.2 Nonoperating Alarm System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
7.3 Step-by-step Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
8.0 Alarm Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
8.1 Integral/Push-button Flasher Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
8.2 Alarm Sequence/Display Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
8.3 Output Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
9.0 Standard Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
9.1 A, Automatic Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
9.2 M, Manual Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
9.3 F3A, Automatic Reset First Out with First Out Flashing and Reset Push Button . . . . . . . . . . . . . . 11
9.4 R, Ringback
(Ronan ID RD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
9.5 F2A, Automatic Reset First Out with No Subsequent Alarm Flashing
(Ronan ID FS) . . . . . . . . . . . . 12
9.6 F2M, Manual Reset First Out with No Subsequent Alarm Flashing
(Ronan ID FSM) . . . . . . . . . . . . 12
10.0 Dimension and Wiring Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
10.1 Monalarm Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
10.2 Binalarm Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
10.3 Trialarm Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
10.4 Quadalarm Dimensional Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
10.5 Standard Rear Terminal Arrangements and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
10.6 Rear Terminal Arrangements and Wiring for 125 Vdc Field Contact . . . . . . . . . . . . . . . . . . . . . . . 18
10.7 Rear Terminal Arrangements and Wiring for Transistor Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
10.8 Rear Terminal Arrangements and Wiring for Opto-coupled Input . . . . . . . . . . . . . . . . . . . . . . . . . 20
THREE-YEAR WARRANTY: Ronan warrants equipment of its own manufacture to be free from defects in material
and workmanship, under normal conditions of use and service, and will repair or replace any component found to be defective, on its return, transportation charges prepaid, within three (3) years of its original purchase. This warranty carries no liability, either expressed or implied, beyond our obligations to replace the unit which carries the warranty.
1

1.0 GENERAL DESCRIPTION

The Ronan Series X11SN Window Annunciator Systems feature Monalarm, Binalarm, Trialarm and Quadalarm displays within Ronan’s standard 3.5 inch (89 mm) by 3.5 inch (89 mm) mechanical cabi­net modules. The single plug-in module construction contains single or multipoint alarm circuitry with maximum noise immunity and reliability. The most popular ISA sequences, A, M, F2A, F2M, F3A, and R are readily available. For other special sequences, consult factory. For higher noise im­munity and specific field contact time applications, a programmable field contact time delay board is an available option. Normally open/normally closed field contact logic for each individual channel is jumper switch-selectable on the single-board design. A sys­tem common trouble alarm (CTA) may be utilized for remote group alarms. The system's CTA and re­flash transistor outputs may be connected directly or via interface relays to provide inputs to remote annunciators.

2.0 SPECIFICATIONS

System Voltage:
Logic, Lamps: 24 Vdc ± 20%. Field Contact Options: 24 Vdc Dry Contact, 48, 125,
250 Vdc ± 20% live input or opto-isolated 115, 240 Vac two-wire input (H and N).
Temperature Range:
Storage: -40 to 85°C (-40 to +185°F). Operating: -40 to +60°C (-40 to +140°F).
Consult factory for extended ranges.
Power Sources:
External Power Supplies or Inverters Available for:
120 Vac ± 20%, 60 Hz; 240 Vac ± 20%, 50/60 Hz; Converter 24, 48 or 125 Vdc ± 20%.
Power Requirements: To specify the correct power supply, count the number of alarm modules to be powered from the supply. Calculate the total require­ments with the following equation:
Total Watts = No. of Modules x (Display Factor F + F Aux.)
F Aux.
Model F Lamps F LEDs Relay Adder
X11SN (1000 Series) 5.3 W 7.1 W 1 W X11SN (2000 Series) 9.3 W 7.1 W 2 W X11SN (3000 Series) 13.3 W 5.6 W 3 W X11SN (4000 Series) 9.3 W 7.1 W 4 W
Inputs: 24 Vdc dry contact, 48, 125, 250 Vdc ± 20% live input or opto-isolated 115, 240 Vac two­wire input (H and N).
Outputs:
Lamp Outputs: Fast flash, slow flash, steady on, intermittent fast flash.
Alarm: Single audible. Auxiliary Relay: Field selectable Form Aor B. Contact Rating: 2A @ 28 Vdc, General Purpose or
Hermetically Sealed.
Common Trouble Alarm: Output follows FC NDE. Reflash Option: Output on rear terminal block
point F4.
Response Time: 20 msec nominal. Surge Withstand Capability (SWC):
All Logic Tested to: ANSI/IEEE C37.90-1989.
Controls: Integral or Remote Silence, Acknow­ledge, Reset, and Test: Momentary push button, single pole, normally open.
System Size:
Multiple of Cabinet Module: 3.5 inch (89 mm) x 3.5 inch (89 mm). See dimensional information draw­ings for detailed dimensions.
System Weight Per Cabinet Module: 2 lbs. (909 grams) not including power supply.

3.0 EXPANSION

The Series X11SN Window Annunciator Systems are built for expandability. This allows field expan­sion of the Monalarm System to either Binalarm, Trialarm or Quadalarm, and the Binalarm to Trialarm or Quadalarm, by simply replacing the alarm/lamp modules and the appropriate bezels. CAUTION: The last position of each chassis can not be more than two alarm positions due to the flasher, so it will only expand to Binalarm.

4.0 AUXILIARY CONTACTS

The auxiliary contact outputs may be purchased ini­tially or added later in the field. The single, dual, triple or quad relay circuit module plugs in from the front of the system. The receiving multipin printed circuit connector and the terminals for the contact outputs are furnished with the system. Each relay follows the selected alarm board auxiliary behavior and provides a selectable Form A or B type contact. The relays are available in General Purpose or Hermetically Sealed models.
2

5.0 MOUNTING

A. The annunciator is shipped with all of the alarm/
lamp modules, auxiliary contact module(s) and flasher module(s) installed in the cabinet, as specified by purchase order.
B. External horn relay(s), reflash relay, common
alarm relay, relay sockets, horns, bells, push but­tons and power supply are packed separately.
C. Install the alarm cabinet from the front of the
panel.
1. Position the cabinet in the cutout so that the cabinet rests on the front extruded trim, see detail A, Figure 1. Make sure that the front rim is firmly against the panel, both top and bot­tom.
2. From the rear view of the panel, insert the two halves of the clamp assembly (one half threaded and the other half unthreaded) in the groove of the front trim, see detail C below.
3. Slide the clamps together until both holes align, see detail B below.
4. Insert the jack screw and tighten to secure the cabinet in the panel. Install all the clamps the same way and be sure to tighten evenly.
5. Tighten up the lock nuts on each jack screw.
3
Clamp Assembly
Flasher Module
Alarm Lamp Module
Auxiliary
Contact Module
Bezel
Rear Cover
Detail A
Detail B
Figure 1: X11SN Assembly Drawing
Detail C
D. Systems purchased with NEMA12 or NEMA4
Doors require mounting of the door before Step C1. After removal of the mounting clamp assem­blies, the system can be inserted through the open door, sandwiching the door between the panel and the system’s extruded trim (gasket is furnished with door). Continue with Steps C1 through C5. Note: The panel cutout is the same as specified in standard flush mounted alarm systems.
E. Mount all external relays, horns and/or bells,
push buttons and power supply on the panel or in the rear of the annunciator cabinet, where possible.
F. Wire system’s inputs and support equipment as
shown under System’s Support Wiring.
Before turning on power read Power Up and Test Procedure.
CAUTION

6.0 POWER UP AND TEST PROCEDURE

It is important to review all external equipment, including the alarm system, before turning on power and proceeding with testing. Before installing, verify that each component meets the area and environment standard required by the National Electrical Code. Particular attention must be paid to reviewing push buttons, horn relays, horns and bells, to see that they meet the right classification of the electrical code.

6.1 Wiring Inspection

6.1.1 Alarm Inputs. Each active alarm input
must be wired to customer’s sensing device that provides an opening or closing on alarm condition. The terminals on the alarm system for each alarm input are marked 1 and are supplied via a pull-up resistor on each alarm module point. This resistor is used in the V+ source to each field contact to reduce the effect of large transients entering the alarm chassis. Each alarm input module is provided with a separate terminal 1. However, it is common practice to run one common wire from terminal 1 to many field contacts to reduce the number of field wires required. When using common wiring, it is important to jumper together terminal 1 of the respective alarm cabinet modules to provide the correct amount of current source to the field contact.
The return wire from the field contact is wired to terminal 2 for each respective alarm mod­ule. Since the alarm system provides the power to the field contacts, it is important to verify that no other voltage source appears on either terminal 1 or terminal 2.
Note: On alarm systems where the alarm inputs are supplied from transistor switch out­puts, the V- of both systems has to be com­mon. If the system under test has this fea­ture, it must be verified by reviewing the elec­trical drawing, particularly the alarm module schematic.
In general, the solid state alarm system is a floating system. The V+ and V- should be verified as ungrounded.
6.1.2 Push-button Wiring. Verify that the push-button wires are correctly wired to all of the push buttons, including the push-button contacts. Refer to pages 13 through 20 for outlined dimensions and rear terminal
4
arrangements. Insure that normally open con­tacts are used. For example, if the wrong con­tacts (normally closed) are used, this is the same as having the operator pushing the push button continuously, which obviously will dras­tically affect the operation of the alarm system. Alarm systems using multiple alarm cabinets may use a common set of push buttons to con­trol the total system. A detailed check for prop­er installation is recommended, including diode type isolation, if specified on the electrical drawings.
6.1.3 Horn and Bell Wiring. Terminals H1, H2, and CA use short circuit protected drivers to drive associated relays and horns. The sug­gested minimum turn-on current of con­nected elements should be greater than 10 mA. The maximum horn current should not exceed 500 mA. If electronic horns are used, the horns can be directly connected to the audible output terminals (H1, H2). Systems using the conventional AC or DC horns and bells, must use a horn relay with suitable con­tact rating. On multiple alarm cabinet systems where individual power input is preferred, a horn relay must be used with each cabinet to maintain electrical isolation.
6.1.4 Power Supply. Verify the correct polarity of connection to the alarm systems. In the larg­er system, it is important to verify the wire sizes of the power leads to the alarm cabinets. To protect the larger alarm chassis, it is com­mon to provide more than one input to the cab­inet in which each section is provided with a separate filter, fuse and supply input terminals. In systems with multiple supply input, it is nec­essary for the customer to make V- connec­tions common.
6.1.5 Normally Open/Normally Closed Field Contacts.All alarm modules are equipped for
operation with normally open or normally closed field contacts. This is accomplished by using a jumper switch on each alarm module, identified as NO and NC for the normally open and normally closed position respectively. When the complete system is in operation, the field contact that opens with an alarm condition is termed a “normally closed” alarm input; con­versely, the field contact that closes with an alarm condition is termed a “normally open” alarm input.
6.1.6 Power Up. Carefully inspect the hookup wiring to insure conformity with the furnished schematic. Pay particular attention to power source polarity and verify that terminal 3 is
CAUTION
connected common for first alert sequence groups. Now remove the alarm modules one at a time and determine whether or not the normally closed/normally open switch is in the proper position and reinsert the card firmly, seating it in the connector. Power may now be applied to the system.
Upon power application, the flasher module within the system will automatically initiate a reset cycle. The system should then be in a quiescent state with the horn(s) off and no lamps flashing. Some lamps may, however, be on if their associated field contacts are in an abnormal condition.
Depression of TEST should cause all extin­guished lamps to come on flashing and the audible alarm to sound. From this point, refer to the particular Sequence Charts to obtain normal system operation. When testing an in­stalled system, be alert to the possibility that an actual alarm may initiate during the test procedure and appear to give conflicting results.

7.0 TROUBLESHOOTING

7.1 General

Simple attention to the obvious can often solve what appears to be a problem in the system.
A.Burned out, broken, or improperly seated
bulbs will not light.
B.Alarm modules not properly seated in their
connector will prevent alarm point(s) from functioning.
C.Alarm point pull-up resistors could be
burned providing no voltage at terminal 1.

7.2 Nonoperating Alarm System

A.Verify that the power source is operating
and that the V+ to V- voltage on the rear terminals is in the range of 18 V to 28 V. (Below 18 V, operation may prove erratic.) Be sure to verify polarity.
B.If the power supply fuse blows each time
power is applied:
1. Check the Power Supply Parts List for proper fuse size.
2. Remove Alarm System from the supply and try again. If fuse holds, double
5
check polarity and reconnect. If fuse still blows, remove all alarm modules and flasher and try again. If the fuse blows at this point, the problem has been isolated to a short in the internal wiring.
C. If power remains on, but any or all push but-
tons (SILENCE, TEST, RESET, ACKNOWL­EDGE) do not appear to function:
1. Verify proper wiring by measuring the voltage at terminal T, A, S and/or R as applicable. Voltage measurements are taken with respect to the V- terminal and should in all cases be zero volts with the button released and V+ (20-28 Vdc) with the button depressed.
2. If the problem persists, the Flasher Module is suspect. Replace the Flasher Module and try again.
3. Be alert to the possibility that a single board can, under unique conditions, cause what appears to be a system mal­function. The following is a typical exam­ple:
a) If a large group of F3A points comes
on fast flashing rather than intermit­tent flashing during TEST, one board can be sending a signal to all of the others. Afailure of the flasher or the test circuit is not necessarily indicat­ed.
b) In the above case, remove Alarm
Modules sequentially and repeat test­ing until the trouble clears.
c) As a general rule, common sense in
isolating the trouble will prevail. If one or more alarm boards appear to be malfunctioning, remove them from the system entirely before continuing. Fill their positions with boards from the upper left or lower right of the system so as to concentrate known good modules, and then proceed with diag­nostic and analysis of the remainder. Working with several scattered diverse problems simultaneously is nearly always self-defeating.
d)Refer to the section on Step-by-step
Procedures for further information.
6

7.3 Step-by-step Procedures

A. Check the system voltage and verify polar-
ity of supply input voltage and that the sys­tem voltage lines are not grounded.
B. Isolate all external devices except the input
power connections.
C. Unseat all alarm/lamp modules except the
No. 1 alarm module. At this point the only items plugged into the alarm chassis are one alarm module and flasher horn driver module. Jumper the push-button input ter­minals on the master module to simulate the correct connections for operations of the alarm system (since only normally open push-button contacts are used for all push­button functions, no connections will be made for normal operation).
D. Connect a simulating set of devices to
replace the field contact as shown on the electrical schematics on terminals 1 and 2.
E. Using the simulated field contacts and fol-
owing the test procedure instructions, check the sequence operation of the annunciator.
F. If the first alarm module does not operate
correctly, replace the flasher module to eliminate the possibility of a faulty flasher module. Once established that the flasher is functional, the fault will probably lie in one of the following areas:
1. A faulty alarm/lamp module.
2. No +24 Vdc at terminal 1.
3. Chassis wiring fault such as a short or cold solder joint.
G.After checking for proper operation of termi-
nal 1 output, remove the No. 1 alarm mod­ule and insert the No. 2 alarm module in the No. 1 chassis position. If the No. 2 alarm module operates correctly, this indi­cates that the No. 1 alarm module is faulty. Should the No. 2 alarm module not func­tion in the No. 1 chassis position, the fault lies in the chassis wiring.
H. If the failure is isolated in the chassis
wiring, remove each alarm input terminal plate and inspect for foreign objects which might cause a short. Review for any dam­aged wiring or broken connections to the printed circuit board connector. Finally, if the above procedure does not produce a solution to the fault, a thorough review of all solder joints is recommended.
I. Should No. 1 alarm function correctly, con-
tinue with the same procedure for checking all alarm/lamps modules by seating each module and using a simulating field contact switch at each alarm point. After the testing, should all the alarm/lamp modules function correctly, it must be assumed that the entire alarm system and modules are not faulty.
At this point, the error is now confined to the external wiring, possible push button or external equipment miswiring, or a short in the field contact wiring.
J. To avoid further damage to new alarm mod-
ules, do not place another alarm module into an alarm position that has produced cir­cuit board trace failures. Adetailed review of the trace failure will determine the reason for the failure. In most cases, damage can be the result of high voltage inputs or short­ing in the chassis.

8.0 ALARM MODULES

8.1 Integral/Push-button Flasher Modules
The X11SN System can operate with either an integral flasher or push-button flasher module. These flasher modules function to provide slow and fast flashing signals and filter the push­button signals to a V- active mode for the alarm cards. The integral flasher is identified by a red handle. The push-button flasher mod­ule is identified by the membrane switch and MAINTENANCE and POWER LED indication. The flasher module has the following specific field selectable options:
A.Slave or master flashing module control. B.ISA options 2 and/or 3. C. Normally energized/deenergized common
trouble alarm output. D. Time selectable auto-silence on Horn 1. E.Normally open/closed contact on mainte-
nance required relay. F. Normally open/closed contacts on alarm
point auxiliary relays (integral modules
only).
Slave (S) or Master (M) Flashing module is controlled by slide switch SW1. In the M posi­tion, the flasher will provide slow and fast flashing rates for all synchronized chassis. Chassis flashing is synchronized by connect­ing similar rear terminals F1, F2, and V-.
Loading...
+ 16 hidden pages