Rockwell Automation Library of Process Objects: PowerFlex
753 Drive (P_PF753)
Version 3.5
IMPORTANT
This manual applies to the Rockwell Automation Library of Process Objects version 3.5 or earlier.
For Rockwell Automation Library of Process Objects version 5.0, see
• PROCES-RM200
For Rockwell Automation Library of Process Objects version 4.0 or later, use the following manuals:
• PROCES-RM013 contains logic instructions
• PROCES-RM014 contains display elements
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, and Rockwell Automation are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Automation Publication SYSLIB-RM044D-EN-P - February 20173
Table of Contents
Notes:
4Rockwell Automation Publication SYSLIB-RM044D-EN-P - February 2017
Preface
Software Compatibility and
Content Revisions
Additional Resources
Table 1 - Summary of Changes
TopicPage
Visualization Files: Global Objects (.ggfx) - Process Diagnostic Objects10
For the latest compatible software information and to download the Rockwell
Automation® Library or Process Objects, see the Product Compatibility and
Download Center at
For general library considerations, see Rockwell Automation Library of Process
Objects, publication
PROCES-RM002.
These documents contain additional information concerning related products
from Rockwell Automation.
ResourceDescription
PlantPAx® Distributed Control System Selection Guide,
publication
PlantPAx Distributed Control System Reference Manual,
publication
Rockwell Automation Library of Process Objects,
publication
FactoryTalk® View Machine Edition User Manual,
publication
FactoryTalk View Site Edition User Manual,
publication
PowerFlex
publication 750-TD001
PowerFlex 750-series AC Drives Installation Instructions,
publication
PowerFlex 750-series AC Drives Programming Manual,
publication
Safe Speed Monitor Option Module for PowerFlex 750-series
AC Drives Safety Reference Manual, publication
PowerFlex 750-series AC Drives Reference Manual,
publication
Rockwell Automation Library of Process Objects: Common
Alarm Block (P_Alarm) Reference Manual,
publication
PROCES-SG001
PROCES-RM001
PROCES-RM002
VIEWME-UM004
VIEWSE-UM006
® 750-series Technical Data,
750-IN001
750-PM001
750-RM001
750-RM002
SYSLIB-RM002
Provides information to assist with equipment
procurement for your PlantPAx system.
Provides characterized recommendations for
implementing your PlantPAx system.
Provides general considerations for the PlantPAx system
library of process objects.
Provides details on how to use this software package for
creating an automation application.
Provides details on how to use this software package for
developing and running human-machine interface
(HMI) applications that can involve multiple users and
servers, distributed over a network.
Shows the specifications and certifications for the
PowerFlex 750-series AC drives.
Explains the steps for mechanical installation and for
connecting incoming power, the motor, and basic I/O to
the PowerFlex 750-series Adjustable Frequency
AC drives.
Provides basic information to install, start up, and
troubleshoot PowerFlex 750-series Adjustable
Frequency AC Drives.
Explains how PowerFlex 750-series drives can be used
in Safety Integrity Level (SIL) CL3, Performance Level
[PL e], or Category (CAT) 4 applications.
Provides details on the operation, parameters
descriptions, and programming for PowerFlex
750-series AC drives.
Details how to monitor an input condition to raise an
alarm. Information includes acknowledging, resetting,
inhibiting, and disabling an alarm. Generally the
P_Alarm faceplate is accessible from the Alarms tab.
Rockwell Automation Publication SYSLIB-RM044D-EN-P - February 20175
Preface
ResourceDescription
Rockwell Automation Library of Process Objects: Interlocks
with First Out and Bypass (P_Intlk) Reference Manual,
publication SYSLIB-RM004
Rockwell Automation Library of Process Objects: Common
Mode Block (P_Mode) Reference Manual,
publication
Rockwell Automation Library of Process Objects: Permissives
with Bypass (P_Perm) Reference Manual,
publication
Rockwell Automation Library of Process Objects: Restart
Inhibit for Large Motor (P_ResInh) Reference Manual,
publication
Rockwell Automation Library of Process Objects: Run Time
and Starts (P_RunTime) Reference Manual,
publication
SYSLIB-RM005
SYSLIB-RM007
SYSLIB-RM009
SYSLIB-RM010
Explains how to collect (sum up) the interlock
conditions that stop or de-energize a running or
energized piece of equipment or prevent it from
starting or being energized.
Explains how to choose the Mode (owner) of an
instruction or control strategy. The Mode instruction is
usually embedded within other instructions to extend
their functionality.
Details how to collect permissive conditions to start a
piece of equipment.
Explains how to protect a large motor from damage
caused by repeated starts.
Explains how to accumulate the total run time and
count of starts for a motor or other equipment.
You can view or download publications at
http:/www.rockwellautomation.com/literature/. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.
6Rockwell Automation Publication SYSLIB-RM044D-EN-P - February 2017
Add-On Instruction
PowerFlex 753 Drive (P_PF753)
The P_PF753 (PowerFlex 753 Drive) object is used to operate one variable-speed
motor by using a PowerFlex 753 AC variable frequency drive in various modes,
and monitoring for fault conditions. The global objects and following faceplate
are examples of the graphical interface tools for this Add-On Instruction.
Faceplate
Global Objects
Guidelines
Use this instruction when you need to operate a motor connected to a
PowerFlex 753 variable frequency AC drive that is communicating with the
controller over an EtherNet/IP network.
This instruction is designed to work with the PowerFlex 753 drive and a
20-COMM-E EtherNet communication module.
Do not use this instruction in these situations:
• You need to operate a single-speed motor (running and stopped only). Use
the P_Motor instruction instead.
• You need to operate a two-speed motor (fast, slow, and stopped only). Use
the P_Motor2Spd instruction instead.
• You need to operate a simple reversing motor (forward, reverse, and
stopped only). Use the P_MotorRev instruction instead.
• You need to operate a motor with multiple discrete speeds. You need
specific logic for this motor. The P_PF753 instruction is designed for
motors with continuously variable (analog) speed, not multiple discrete
speed selections. You can use the P_D4SD or P_nPos instruction for
motors with multiple discrete speeds.
Rockwell Automation Publication SYSLIB-RM044D-EN-P - February 20177
PowerFlex 753 Drive (P_PF753)
• If your PowerFlex 753 drive uses the 20-750-ENETR EtherNet interface,
use the P_PF755 instruction instead. The PowerFlex 753 drive with the
20-750-ENETR interface uses the same interface data structures as the
PowerFlex 755 drive, giving you more data.
• If you are using a drive other than the PowerFlex 523, 525, 753, or 755,
drive, use the P_VSD (generic variable-speed drive) instruction instead.
Functional Description
The P_PF753 instruction provides the following capabilities:
• Ownership of the drive through the standard P_Mode Add-On
Instruction and modes.
• Ability to start and stop the drive and motor, control the drive speed (via
speed reference), and monitor the drive run status and speed feedback to
verify the drive is running or stopped. Provides alarms and drive shutdown
for Fail to Start and Fail to Stop if the feedback does not follow the
commanded state within a configured amount of time.
• Reading from the drive, the instruction displays drive faults, drive alarms,
conditions that inhibit starting the drive, drive predictive maintenance
data, and general drive status data.
• Ability to read a fault code from the drive and provide descriptive text of
fault codes.
• Indication of Accelerating, Decelerating, At Speed, Warning, or Alarm
status as received from the drive.
• Optional capability to support reversing drives, with commands for
forward and reverse rotation, and display of actual rotation direction.
• Input and alarm for a drive fault condition and an output to send a drive
fault reset to the drive. Provides a configurable time to pulse the drive fault
reset output when a reset command is received.
• Permissives (bypassable and non-bypassable), which are conditions that let
a drive start, and Interlocks (bypassable and non-bypassable), which are
conditions that stop the drive as well as prevent starting. Provides an alarm
when an Interlock stops the drive. Provides maintenance personnel the
capability to bypass the bypassable Permissives and Interlocks.
• Maintenance personnel have the capability to disable (soft lock out) the
drive. This capability is not a substitute for hard lockout/tagout (LOTO)
procedures.
• Monitor an I/O fault input, and alarm on an I/O fault. The I/O fault
condition can optionally de-energize the outputs to the drive, requiring
a reset.
• In Override mode, provides an override state input that determines if the
override is to run or stop the drive (default = stop), and, if the drive is to
run, an override speed reference and direction.
8Rockwell Automation Publication SYSLIB-RM044D-EN-P - February 2017
PowerFlex 753 Drive (P_PF753)
• Provides simulation capability. Outputs to the drive are kept de-energized,
but the object can be manipulated as if a working drive were present,
including a basic ramp-up of speed feedback value on starting and rampdown on stopping. The simulated ramp-up-to-speed time is configurable.
This capability is often used for activities such as system testing and
operator training.
Required Files
Add-On Instructions are reusable code objects that contain encapsulated logic
that can streamline implementing your system. This lets you create your own
instruction set for programming logic as a supplement to the instruction set
provided natively in the ControlLogix® firmware. An Add-On Instruction is
defined once in each controller project, and can be instantiated multiple times in
your application code as needed.
Controller File
The P_PF753_3_5-00_RUNG.L5X rung import must be imported into the
controller project to be used in the controller configuration. The service release
number (boldfaced) can change as service revisions are created.
Visualization Files
This Add-On Instruction has associated visualization files that provide a
common user interface. These files can be downloaded from the Product
Compatibility and Download Center at
The visualization file dependencies require Process Library content imports to
occur in a specific order as reflected in the following tables:
• Images
• Global Objects
• Standard Displays
• HMI Tags
• Macros
Images are external graphic files that can be used in displays. They must be
imported for FactoryTalk View to make use of them.
When PNG files are imported, they are renamed by FactoryTalk View with
a .bmp file extension, but retain a .png format.
Table 2 - Visualization Files: Images (.png)
FactoryTalk View SE SoftwareFactoryTalk View ME SoftwareDescription
All .png files in the images folderAll .png files in the images folderThese are the common icons used in the global objects and
Rockwell Automation Publication SYSLIB-RM044D-EN-P - February 20179
standard displays for all Process Objects.
PowerFlex 753 Drive (P_PF753)
The Global Object files (.ggfx file type) in the following table are Process Library
display elements that are created once and referenced multiple times on multiple
displays in an application. When changes are made to a Global Object, all
instances in the application are automatically updated.
Table 3 - Visualization Files: Global Objects (.ggfx)
FactoryTalk View SE SoftwareFactoryTalk View ME SoftwareDescription
(RA-BAS) Common Faceplate Objects(RA-BAS-ME) Common Faceplate ObjectsGlobal objects used on process object faceplates.
(RA-BAS) P_VSD Graphics Library(RA-BAS-ME) P_VSD Graphics LibraryDrive global object device symbols used to build
(RA-BAS) Process Alarm Objects(RA-BAS-ME) Process Alarm ObjectsGlobal objects used for managing alarms on process
(RA-BAS) Process Diagnostic Objects(RA-BAS-ME) Process Diagnostic ObjectsDiagnostic global objects used on process object
(RA-BAS) Process Faceplate Motor Objects(RA-BAS-ME) Process Faceplate Motor ObjectsMotor global objects used on process object faceplates.
(RA-BAS) Process Help Objects(RA-BAS-ME) Process Help ObjectsGlobal objects used for all process objects help displays.
(RA-BAS) Process Interlock Objects(RA-BAS-ME) Process Interlock ObjectsGlobal objects used for managing interlocks and
(RA-BAS) Process Mode Objects(RA-BAS-ME) Process Mode ObjectsGlobal objects used for managing modes on process
process graphics.
object faceplates.
faceplates.
permissives on process object faceplates.
object faceplates.
The Standard Display files (.gfx file type) in the following table are the Process
Library displays that you see at runtime.
Table 4 - Visualization Files: Standard Displays (.gfx)
FactoryTalk View SE SoftwareFactoryTalk View ME SoftwareDescription
(RA-BAS) Common-AnalogEditN/AFaceplate used for analog input data entry. The FactoryTalk
(RA-BAS) P_Alarm-Faceplate(RA-BAS-ME) P_Alarm-FaceplateThe faceplate that is used for managing alarms for
(RA-BAS) P_Alarm-Help(RA-BAS-ME) P_Alarm-HelpAlarm Help information that is accessed from the
(RA-BAS) P_Mode-Config(RA-BAS-ME) P_Mode-ConfigThe Configuration Display used to configure the
(RA-BAS) P_Mode-Help(RA-BAS-ME) P_Mode-HelpMode Help information that is accessed from the
(RA-BAS) P_PF753-Faceplate(RA-BAS-ME) P_PF753-FaceplateThe faceplate that is used for the object
(RA-BAS) P_PF753-Quick(RA-BAS-ME) P_PF753-QuickThe Quick display that is used for the object
RunTime faceplate display that is used for the object
Use this file if your object has an associated P_RunTime
object and you enable navigation to the P_RunTime
faceplate from the object faceplate.
(RA-BAS) Process Interlock Family-Help(RA-BAS-ME) Process Interlock Family-HelpOptional
Interlock/permissives help display that is used for
the object
Use this file if you use the P_Intlk or P_Perm faceplate.
HMI Tags are created in a FactoryTalk View ME application to support tab
switching on Process Library faceplates. The HMI tags may be imported via the
comma-separated values file (.csv file type) in the following table.
Table 5 - Visualization Files: HMI Tags (.csv)
PowerFlex 753 Drive (P_PF753)
FactoryTalk View SE SoftwareFactoryTalk View ME SoftwareDescription
N/AFTVME_PlantPAxLib_Tags_3_5_xx.csv
Controller Code
where xx = the service release number.
This section describes the parameter references for this Add-On Instruction.
These tags must be imported into the
FactoryTalk View ME project to support switching tabs on
any Process Object faceplate.
PowerFlex 753 Drive InOut Structure
InOut parameters are used to link the Add-On Instruction to external tags that
contain necessary data for the instruction to operate. These external tags must be
of the data type shown.
Table 7 - P_PF753 Drive InOut Parameters
Tag NameData TypeDescription
InpP_PF753_InpCommon part of PowerFlex 753 input assembly.
OutP_PF753_OutCommon part of PowerFlex 753 output assembly.
Ref_FaultCodeListP_DescList[*]Array tag containing list of fault codes (DINT) and their descriptions (STRING_40).
Rockwell Automation Publication SYSLIB-RM044D-EN-P - February 201711
PowerFlex 753 Drive (P_PF753)
The figure below shows the drive fault table tags that are in each template.
To display fault descriptions for the PowerFlex 753 drive, you must enter the
name of the Fault Code List (first column) in the P_PF753 Ref_FaultCodeList
parameter.
Each fault code list has preset codes and descriptions that provide humanreadable descriptions of drive fault conditions.
For a complete list of fault codes for the PowerFlex 753 Drive, refer to the
PowerFlex 750 Series AC Drivers Programming Manual,
publication
12Rockwell Automation Publication SYSLIB-RM044D-EN-P - February 2017
750-PM001.
Table 8 - P_PF753 Drive Input Parameters
PowerFlex 753 Drive (P_PF753)
PowerFlex 753 Drive Input Structure
Input parameters include the following:
• Input data elements (Inp_) are typically used to connect field inputs from
I/O modules or signals from other objects.
• Configuration data elements (Cfg_) are used to set configurable
capabilities and features of the instruction.
• Command data elements (PCmd_, OCmd_, MCmd_) are used by
program logic, operators, and maintenance personnel to request
instruction actions.
• Setting data elements (PSet_, OSet_, MSet_) are used by program logic,
operators, and maintenance personnel to establish runtime setpoints,
thresholds, and so forth. Set_ data elements (without a leading P, O, or M)
establish runtime settings regardless of role or mode.
Input ParameterData
Type
EnableInBOOL1Ladder Diagram:
Inp_FwdPermOKBOOL11 = Permissives OK, drive can start Forward.
Inp_FwdNBPermOKBOOL11 = Non-Bypassable Permissives OK, drive can start Forward.
Inp_RevPermOKBOOL11 = Permissives OK, drive can start Reverse.
Inp_RevNBPermOKBOOL11 = Non-bypassable Permissives OK, motor can start Reverse.
Inp_IntlkOKBOOL11 = Interlocks OK, drive can start/run.
Inp_NBIntlkOKBOOL11 = Non-bypassable Interlocks OK, drive can start/run.
Inp_IOFaultBOOL0Input communication status:
Inp_SimBOOL0Simulation input. When set to 1, the instruction keeps outputs de-energized
Inp_HandBOOL01 = Request to acquire Hand mode
Inp_OvrdBOOLMode.Inp_Ovrd01 = Request to Acquire Override mode
Inp_OvrdCmdSINT0Override mode command:
Inp_OvrdSpeedREAL0.0Value to set Speed Reference in Override mode (SpeedRef engineering units).
Inp_ResetBOOL01 = Reset drive fault conditions and latched Alarms.
Alias ForDefaultDescription
If the rung-in condition is true, the instruction’s Logic routine executes. If the
rung-in condition is false, the instruction’s EnableInFalse routine executes.
Function Block Diagram:
If true, or not connected, the instruction’s Logic routine executes. If the parameter
is exposed as a pin and wired, and the pin is false, the instruction’s EnableInFalse
routine executes.
Structured Text:
No effect. The instruction’s Logic routine executes.
0 = OK,
1 = fail
(zero) and simulates a working drive. When set to 0, the instruction operates the
drive normally.
0 = Release Hand mode
0 = Release Override mode
0 = None
1 = Stop
2 = Start Fwd
3 = Start Rev
Rockwell Automation Publication SYSLIB-RM044D-EN-P - February 201713
PowerFlex 753 Drive (P_PF753)
Table 8 - P_PF753 Drive Input Parameters
Input ParameterData
Type
Cfg_HasReverseBOOL01 = Drive can be run reverse.
Cfg_HasJogBOOL01 = Drive Jog Command enabled/visible.
Cfg_AllowLocalBOOL01 = Allow Local Start/Stop without alarm.
Cfg_HasFwdPermObjBOOL01 = Tells HMI a forward permissive object (for example, P_Perm) is used for
Cfg_HasRevPermObjBOOL01 = Tells HMI a reverse permissive object (for example, P_Perm) is used for
Cfg_HasIntlkObjBOOL01 = Tells HMI an interlock object (for example, P_Intlk) is used for Inp_IntlkOK
Cfg_HasResInhObjBOOL01 = Tells HMI a restart inhibit object (for example, P_ResInh) is connected and
Cfg_HasRunTimeObjBOOL01 = Tells HMI a runtime object (for example, P_RunTime) is connected and
Cfg_SetTrackBOOL1This parameter is used to set up bumpless behavior of setting parameters when
Cfg_PCmdClearBOOLMode.Cfg_PCmdClear1When this parameter is 1, program commands are cleared once they are acted
Cfg_ProgDefaultBOOLMode.Cfg_ProgDefault0This parameter defines the default mode. When this parameter is 1, the mode
Alias ForDefaultDescription
0 = Forward only.
0 = Drive Jog Command not allowed.
0 = Start/Stop from HMI/program only.
Inp_FwdPermOK and navigation to the permissive object’s faceplate is enabled.
IMPORTANT: The name of the Forward Permissive object in the controller must
be this object's name with the suffix ‘_FwdPerm.’ For example, if your P_PF753
object has the name ’PF753123’, then its Forward Permissive object must be
named ‘PF753123_FwdPerm’.
Inp_RevPermOK and navigation to the permissive object’s faceplate is enabled.
IMPORTANT: The name of the Reverse Permissive object in the controller must
be this object's name with the suffix ‘_RevPerm’. For example, if your P_PF753
object has the name ’PF753123’, then its Reverse Permissive object must be
named ‘PF753123_RevPerm’.
and navigation to the interlock object’s faceplate is enabled.
IMPORTANT: The name of the Interlock object in the controller must be this
object's name with the suffix ‘_Intlk’. For example, if your P_PF753 object has the
name ’PF753123’, then its Interlock object must be named ‘PF753123_Intlk’.
navigation to the restart inhibit object’s faceplate is enabled.
IMPORTANT: The name of the Restart Inhibit object in the controller must be this
object's name with the suffix ‘_ResInh’. For example, if your P_PF753 object has
the name ’PF753123’, then its Restar t Inhibit object must be named
‘PF753123_ResInh’.
navigation to the runtime object’s faceplate is enabled.
IMPORTANT: The name of the runtime object in the controller must be this
object's name with the suffix ‘_RunTime’. For example, if your P_PF753 object
has the name ‘PF753123’, then its runtime object must be named
‘PF753123_RunTime’.
switching modes. When this parameter is 1, in Program mode the operator
settings track the program settings; in Operator mode the program settings track
the operator settings; and the simulation inputs match the output values
(transitions are bumpless).
When this parameter is 0, the operator settings and program settings are not
modified by this instruction. In this case, when the mode is changed, the effective
value of the setting can change depending on the program-set and operator-set
values.
upon. When set to 0, program commands remain set until cleared by the
application program logic.
IMPORTANT: Clearing this parameter online can cause unintended program
command execution.
defaults to Program if no mode is being requested. When this parameter is 0, the
mode defaults to Operator if no mode is being requested.
IMPORTANT: Changing this parameter online can cause unintended mode
changes.
14Rockwell Automation Publication SYSLIB-RM044D-EN-P - February 2017
Table 8 - P_PF753 Drive Input Parameters
PowerFlex 753 Drive (P_PF753)
Input ParameterData
Type
Cfg_OperStopPrioBOOL01 = OCmd_Stop has priority, accepted any time. If OCmd_Stop stops the drive in
Cfg_OCmdResetsBOOL01 = New Operator drive command resets fault. If OCmd_Stop stops the drive in a
Cfg_ShedOnFailToStartBOOL11 = Stop motor and alarm on Fail to Start.
Cfg_ShedOnIOFaultBOOL11 = Stop motor and alarm on I/O Fault.
Cfg_SimScaleEUBOOL01 = In simulation, scale Speed Ref engineering units to Speed feedback
Cfg_SimScaleRawBOOL01 = In simulation, scale Speed Ref engineering units to raw, then raw to Speed
Cfg_HasFailToStartAlmBOOLFailToStart.Cfg_Exists0These parameters determine whether the corresponding alarm exists and is
Cfg_HasFailToStopAlmFailToStop.Cfg_Exists
Cfg_HasIntlkTripAlmIntlkTrip.Cfg_Exists
Cfg_HasDriveFaultAlmDriveFault.Cfg_Exists
Cfg_HasIOFaultAlmIOFault.Cfg_Exists
Cfg_FailToStartResetReqdBOOLFailToStart.Cfg_ResetReqd0These parameters determine whether a reset is required to clear the alarm status.
Cfg_FailToStopResetReqdFailToStop.Cfg_ResetReqd
Cfg_IntlkTripResetReqdIntlkTrip.Cfg_ResetReqd
Cfg_DriveFaultResetReqdDriveFault.Cfg_ResetReqd
Cfg_IOFaultResetReqdIOFault.Cfg_ResetReqd
Cfg_FailToStartAckReqdBOOLFailToStart.Cfg_AckReqd1These parameters determine whether an acknowledgement is required for an
Cfg_FailToStopAckReqdFailToStop.Cfg_AckReqd
Cfg_IntlkTripAckReqdIntlkTrip.Cfg_AckReqd
Cfg_DriveFaultAckReqdDriveFault.Cfg_AckReqd
Cfg_IOFaultAckReqdIOFault.Cfg_AckReqd
Alias ForDefaultDescription
a mode other than Maintenance or Operator, a reset is required to start.
0 = OCmd_Stop only in Operator or Maintenance mode.
mode other than Maintenance or Operator, a reset is required to start.
0 = Reset required to clear fault.
0 = Always use Permissive/ Interlock.
0 = Alarm only on Fail to Start.
IMPORTANT: If a condition is configured to shed the device to the Stopped state
on a fault, a reset is required to clear the shed fault to command the drive to a
state other than Stopped.
0 = Alarm only on I/O Fault.
IMPORTANT: If a condition is configured to shed the device to the Stopped state
on a fault, a reset is required to clear the shed fault to command the drive to a
state other than Stopped.
engineering units.
feedback engineering units.
evaluated or if the alarm does not exist and is not used. When these parameters
are 1, the corresponding alarm exists.
When these parameters are 1, the alarm is latched ON when the alarm occurs.
After the alarm condition returns to normal, a reset is required to clear the alarm
status (for example, OCmd_Reset, Inp_Reset, or Drivefault.OCmd_Reset are
required to clear Alm_DriveFault alarm after the alarm is set and the value
returns to normal). When these parameters are 0, no reset is required and the
alarm status is cleared when the alarm condition returns to normal.
IMPORTANT: If the reset clears the alarm, it also acknowledges the alarm.
alarm. When these parameters are 1, the acknowledge (ack) bit is cleared when
the alarm occurs. An acknowledge command (for example, PCmd_FailAck or
Fail.OCmd_Ack) is required to acknowledge the alarm. When set to 0, the
Acknowledge bit is set when an alarm occurs indicating an acknowledged alarm
and no acknowledge command is required.
Rockwell Automation Publication SYSLIB-RM044D-EN-P - February 201715
PowerFlex 753 Drive (P_PF753)
Table 8 - P_PF753 Drive Input Parameters
Input ParameterData
Type
Cfg_FailToStartSeverityINTFailToStart.Cfg_Severity1000These parameters determine the severity of each alarm. This drives the color and
Cfg_FailToStopSeverityFailToStop.Cfg_Severity
Cfg_IntlkTripSeverityIntlkTrip.Cfg_Severity250
Cfg_DriveFaultSeverityDriveFault.Cfg_Severity1000
Cfg_IOFaultSeverityIOFault.Cfg_Severity
Cfg_MinSpdRefREAL0.0Minimum Speed Reference in engineering units (for limiting).
Cfg_MaxSpdRefREAL60.0Maximum Speed Reference in engineering units (for limiting).
Cfg_SpeedRefRawMinDINT0Speed Reference Minimum in Drive (raw) Units (for scaling).
Cfg_SpeedRefRawMaxDINT60000Speed Reference Maximum in Drive (raw) Units (for scaling).
Cfg_SpeedRefEUMinREAL0.0Speed Reference Minimum in Engineering Units (for scaling).
Cfg_SpeedRefEUMaxREAL60.0Speed Reference Maximum in Engineering Units (for scaling).
Cfg_SpeedFdbkRawMinDINT0Speed Feedback Minimum in Drive (raw) Units (for scaling).
Cfg_SpeedFdbkRawMaxDINT60000Speed Feedback Maximum in Drive (raw) Units (for scaling).
Cfg_SpeedFdbkEUMinREAL0.0Speed Feedback Minimum in Engineering Units (for scaling).
Cfg_SpeedFdbkEUMaxREAL60.0Speed Feedback Maximum in Engineering Units (for scaling).
Cfg_SimRampTDINT10Time to ramp speed feedback when in Simulation (seconds).
Cfg_FailToStartTDINT15Time after Start to get Run Feedback before Fault (seconds).
Cfg_FailToStopTDINT15Time after Stop to drop Run Feedback before Fault (seconds).
Cfg_ResetPulseTDINT2Time to pulse Out_Reset to clear drive fault (seconds).
Cfg_MaxJogTREAL0.0Maximum jog time (seconds, 0 = unlimited).
Cfg_OperKeepSINT2#0000_0000Operator keeps control in Program mode:
Cfg_ProgKeepSINT2#0000_0000Program keeps control in Operator mode:
PSet_SpeedRefREAL0.0Program Setting of Speed Reference (engineering units).
PSet_OwnerDINT0Program Owner Request ID (non-zero) or Release (zero).
OSet_SpeedRefREAL0.0Operator Setting of Speed Reference (engineering units).
PCmd_StartBOOL0When Cfg_PCmdClear is 1:
PCmd_Stop
Alias ForDefaultDescription
symbol that are used to indicate alarm status on the faceplate and global object.
The following are valid values:
1…250 = Low
251…500 = Medium
501…750 = High
751…1000 = Urgent
IMPORTANT: For FactoryTalk View software version 7.0, these severity
parameters drive the indication only on the global object and faceplate. The
Alarms and Events definition of severity drives the color and symbol that is used
on the alarm banner and alarm summary as well as the value returned by
FactoryTalk Alarms and Events display commands.
Bit .0 = Reference,
Bit .1 = Start/Stop,
Bit .2 = Forward/Reverse
Bit .0 = Reference,
Bit .1 = Start/Stop,
Bit .2 = Forward/Reverse
• Set PCmd_Start to 1 to start the drive
• Set PCmd_Stop to 1 to stop the drive
• These parameters are reset automatically
When Cfg_PCmdClear is 0:
• Set PCmd_Start to 1 to start the drive
• Set PCmd_Start to 0 to stop the drive
• PCmd_Stop is not used
• These parameters do not reset automatically
16Rockwell Automation Publication SYSLIB-RM044D-EN-P - February 2017
Table 8 - P_PF753 Drive Input Parameters
PowerFlex 753 Drive (P_PF753)
Input ParameterData
Type
PCmd_FwdBOOL0When Cfg_PCmdClear is 1:
PCmd_Rev
PCmd_AcqBOOLMode.PCmd_Acq0When Cfg_PCmdClear is 1:
PCmd_RelMode.PCmd_Rel
PCmd_LockBOOLMode.PCmd_Lock0When Cfg_PCmdClear is 1:
PCmd_UnlockMode.PCmd_Unlock
PCmd_ResetBOOL0• Set PCmd_Reset to 1 to reset all alarms requiring reset
PCmd_FailToStartAckBOOLFailToStart.PCmd_Ack0• Set PCmd_<Alarm>Ack to 1 to Acknowledge alarm
PCmd_FailToStopAckFailToStop.PCmd_Ack
PCmd_IntlkTripAckIntlkTrip.PCmd_Ack
PCmd_DriveFaultAckDriveFault.PCmd_Ack
PCmd_IOFaultAckIOFault.PCmd_Ack
PCmd_FailToStartSuppressBOOLFailToStart.PCmd_Suppress0When Cfg_PCmdClear is 1:
• Set PCmd_Fwd to 1 to select the forward direction
• Set PCmd_Rev to 1 to select the reverse direction
• These parameters are reset automatically
When Cfg_PCmdClear is 0:
• Set PCmd_Rev to 0 to select the forward direction
• Set PCmd_Rev to 1 to select the reverse direction
• PCmd_Fwd is not used
• These parameters do not reset automatically
• Set PCmd_Acq to 1 to Acquire
• Set PCmd_Rel to 1 to Release
• These parameters reset automatically
When Cfg_PCmdClear is 0:
• Set PCmd_Acq to 1 to Acquire
• Set PCmd_Acq to 0 to Release
• PCmd_Rel is not used
• These parameters do not reset automatically
• Set PCmd_Lock to 1 to Lock
• Set PCmd_Unlock to 1 to Unlock
• These parameters reset automatically
When Cfg_PCmdClear is 0:
• Set PCmd_Lock to 1 to Lock
• Set PCmd_Lock to 0 to Unlock
• PCmd_Unlock is not used
• These parameters do not reset automatically
• This parameter is always reset automatically
• The parameter is reset automatically
• Set PCmd_<Alarm>Suppress to 1 to suppress alarm
• Set PCmd_<Alarm>Unsuppress to 1 to unsuppress alarm
• These parameters reset automatically
When Cfg_PCmdClear is 0:
• Set PCmd_<Alarm>Suppress to 1 to suppress alarm
• Set PCmd_<Alarm>Suppress to 0 to unsuppress alarm
• PCmd_<Alarm>Unsuppress is not used
• These parameters do not reset automatically
Rockwell Automation Publication SYSLIB-RM044D-EN-P - February 201717
PowerFlex 753 Drive (P_PF753)
Table 8 - P_PF753 Drive Input Parameters
Input ParameterData
Type
PCmd_FailToStartUnshelveBOOLFailToStart.PCmd_Unshelve0• Set PCmd_<Alarm>Unshelve to 1 to Unshelve alarm
PCmd_FailToStopUnshelveFailToStop.PCmd_Unshelve
PCmd_IntlkTripUnshelveIntlkTrip.PCmd_Unshelve
PCmd_DriveFaultUnshelveDriveFault.PCmd_Unshelve
PCmd_IOFaultUnshelveIOFault.PCmd_Unshelve
OCmd_StartBOOL0Operator command to start drive.
OCmd_StopBOOL0Operator command to stop drive.
OCmd_JogBOOL0Operator command to jog drive (not cleared by instruction if Cfg_MaxJogT = 0).
OCmd_FwdBOOL0Operator command to set direction to Forward.
OCmd_RevBOOL0Operator command to set direction to Reverse.
OCmd_BypassBOOL0Operator command to bypass all bypassable interlocks and permissives.
OCmd_CheckBOOL0Operator command to check (not bypass) all interlocks and permissives.
MCmd_DisableBOOL0Maintenance command to disable drive.
MCmd_EnableBOOL0Maintenance command to enable (allow to run) drive.
MCmd_AcqBOOLMode.MCmd_Acq0Maintenance command to acquire ownership (Operator/Program/Override to
MCmd_RelBOOLMode.MCmd_Rel0Maintenance command to release ownership (Maintenance to Operator/
OCmd_AcqLockBOOLMode.OCmd_AcqLock0Operator command to acquire (Program to Operator)/lock ownership.
OCmd_UnlockBOOLMode.OCmd_UnlockRel0Operator command to unlock/release (Operator to Program) ownership.
OCmd_ResetBOOL0Operator command to reset all alarms requiring reset and trigger a drive reset if
OCmd_ResetAckAllBOOL0Operator command to acknowledge and reset all alarms and latched Shed
Alias ForDefaultDescription
• The parameter is reset automatically
Maintenance).
Program/Override).
the drive is faulted.
conditions.
18Rockwell Automation Publication SYSLIB-RM044D-EN-P - February 2017
Table 9 - P_PF753 Drive Output Parameters
PowerFlex 753 Drive (P_PF753)
PowerFlex 753 Drive Output Structure
Output parameters include the following:
• Output data elements (Out_) are the primary outputs of the instruction,
typically used by hardware output modules; however, they can be used by
other application logic.
• Value data elements (Val_) are numeric outputs of the instruction for use
by the HMI. Values can also be used by other application logic or software
packages.
• Source and Quality data elements (SrcQ_) are outputs of the instruction
used by the HMI to indicate PV source and quality.
• Status data elements (Sts_) are bit outputs of the instruction for use by the
HMI. Status bits can also be used by other application logic.
• Error data elements (Err_) are outputs of the instruction that indicate a
particular configuration error. If any Err_ bit is set then the Sts_Err
configuration error summary status is set and the Invalid Configuration
indicator is displayed on the HMI.
• Not Ready data elements (Nrdy_) are bit outputs of the instruction for use
by the HMI for displaying the Device Not Ready indicator.
• Alarm data elements (Alm_) are outputs of the instruction that indicate a
particular alarm has occurred.
• Acknowledge data elements (Ack_) are outputs of the instruction that
indicate the corresponding alarm has been acknowledged.
• Ready data elements (Rdy_) are bit outputs of the instruction used by the
HMI to enable or disable Command buttons and Setting entry fields.
Output ParameterData TypeAlias ForDescription
EnableOutBOOLEnable Output: The EnableOut signal is not manipulated by this instruction. Its output state
Val_SpeedRefREALSpeed Reference (target) to drive.
Val_SpeedFdbkREALSpeed Feedback (actual) from drive.
1 = I/O live and assumed good quality
2 = No feedback configured, assumed good quality
TEST 8 = Device simulated
9 = Device loopback simulation
10 = Manually entered value
UNCERTAIN 16 = Live input, off-specification
17 = Value substituted at device/bus
18 = Value substituted by maintenance (Has and not Use)
19 = Shed, using last good value
20 = Shed, using replacement value
BAD 32 = Signal failure (out-of-range, NaN, invalid combination)
33 = I/O channel fault
34 = I/O module fault
35 = Bad I/O configuration (for example, scaling parameters)