Rockwell Automation 1747-DCM, D17476.8 User Manual

Allen-Bradley
Direct Communication
User
Module
(Cat. No. 1747-DCM)
Manual

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment. “Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls” (Publication SGI-1.1) describes some important differences between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will the Allen-Bradley Company be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, the Allen-Bradley Company cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Allen-Bradley Company with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of the Allen-Bradley Company is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
!
damage, or economic loss.
Attentions help you:
identify a hazard
avoid the hazard
recognize the consequences
Important: Identifies information that is especially important for successful
application and understanding of the product.
PLC, PLC-2, PLC-3, and PLC-5 are registered trademarks of Allen-Bradley Company, Inc. SLC, SLC 500, Dataliner, PanelView, RediPANEL, PLC-5/11, PLC-5/15, PLC-5/20, PLC-5/12, PLC-5/25, PLC-5/30, PLC-5/40, PLC-5/60 are trademarks of Allen-Bradley Company, Inc. IBM is a registered trademark of International Business Machines, Incorporated.

Summary of Changes

Summary of Changes
The information below summarizes the changes to this manual since the last printing as 1747-NM007–September 1993.
To help you find new information and updated information in this release of the manual, we have included change bars as shown to the right of this paragraph.

New Information

The table below lists sections that document new features and additional information about existing features, and shows where to find this new information.
For This New Information See
Related documentation updated preface Quick Start for Experienced Users chapter 2 Default DIP switch settings chapter 4 CE certification chapter 5, appendix A DCM clear on fault DIP switch chapter 6
T
able of Contents
Direct Communication Module User Manual
Preface
Who
Should Use this Manual
Purpose
Terms Common Allen-Bradley
of this Manual Contents Related
Local
Technical Product Assistance P–5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Your Questions or Comments on this Manual P–5. . . . . . . . . . . . . . . . . . . . .
of this Manual
Documentation
and Abbreviations
Techniques Used in this Manual
Support
Product Support
P–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
P–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
P–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
P–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
P–4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
P–5. . . . . . . . . . . . . . . . . . . . . . . . . .
P–5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
P–5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Overview
Quick Start for Experienced Users
Addressing
Chapter 1
Hardware Overview 1–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System Overview 1–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
What
Is a Remote I/O Adapter?
Extended
Scanner Image Division 1–4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Scanner
Data Exchange Between RIO Scanners and the DCM 1–6. . . . . . . . . . . . . . . . .
What
Node Capability
Image Division Configuration Example
Is the Status W
ord? 1–6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 2
Required Tools and Equipment
Procedures 2–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 3
Addressing
PLC/Scanner Addresses 3–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SLC Addresses 3–3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I/O
Image
Ladder Logic Instructions
Image T
PLC to DCM/SLC 3–4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DCM/SLC
Mapping
ables 3–4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
to PLC
1–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1–4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1–5. . . . . . . . . . . . . . . . . . .
2–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3–4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3–5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module Configuration
Chapter 4
DIP Switches 4–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DIP
Switch 1 Settings Starting Rack
DIP
Rack
Last Rack (SW2-4) 4–6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Clear Data
I/O Group Number (SW1-7 and SW1-8)
Address (SW1-1 through SW1-6)
Switch 2 Settings
Size (SW2-5 and SW2-6))
On Fault (SW2-3)
Rate (SW2-1 and SW2-2)
4–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4–2. . . . . . . . . . . . . . . . . . .
4–3. . . . . . . . . . . . . . . . . . . . . . . . .
4–6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4–6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4–7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4–7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
i
T
able of Contents
Direct Communication Module User Manual
Installation and Wiring
Programming
Chapter 5
Compliance
EMC Directive 5–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DCM
Installation 5–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removal 5–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Network
to European Union Directives
Installation
Wiring
Chapter 6
Overview 6–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Programming Examples 6–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Physical Physical Physical
Physical
Status Words 6–5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RIO DCM/SLC
Applications Using I/O Status W
RIO
DCM/SLC
RIO
Input into PLC – Physical Output from SLC Input into SLC – Physical Output from PLC Input into Both PLC and SLC (Logical AND) –
Physical Output from SLC 6–3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Input into First SLC – Physical Output from Second SLC
Scanner Input Status W
Output Status W
Scanner Status W
Using
the Program/T
Output Status W
Using
the Data Invalid Bit
Using
the User Status Flag Bit
Scanner Input Status and DCM/SLC Output Status
Using
the Logical OR Bit
ord Examination (Decimal) 6–5. . . . . . . . . . . . .
ord Examination (Octal) 6–6. . . . . . . . . . . . . . . .
ord Bits
ord 6–7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
est/Fault Mode Bit
ord 6–7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5–1. . . . . . . . . . . . . . . . . . . . . . . . . .
5–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5–3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6–2. . . . . . . . . . . . . . . .
6–3. . . . . . . . . . . . . . . .
6–4. . . . . .
6–7. . . . . . . . . . . . . . . . . . . . . . . . . . . .
6–7. . . . . . . . . . . . . . . . . . . . . . .
6–7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6–8. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6–10. . . . . . . . . . . . .
6–10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting
Application Examples
ii
Chapter 7
DCM
Status Indicators Troubleshooting
Troubleshooting Using the COMM LED (Green) 7–2. . . . . . . . . . . . . . . . . . . . . .
Using the F
AULT LED (Red) 7–1. . . . . . . . . . . . . . . . . . . . . . . .
Chapter 8
Basic Example 8–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1747-SN DIP System System Image Program
Supplementary Example 8–4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Module DIP System Image
Module Configuration
Switch Settings
Configuration for Rack 1 Configuration for Rack 2
T
able Configuration
Listing
Configuration
Switch Settings
Configuration
T
able Configuration
7–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8–3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8–3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8–4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8–5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8–5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8–5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
T
able of Contents
Direct Communication Module User Manual
Specifications
DCM Addressing Worksheet
Program Program
Listing for 5/01 Listing for PLC5/15
Appendix A
Electrical Environmental Network Throughput
Specifications
Specifications
Specifications
T
iming A–2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Appendix B
Directions B–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Addressing Review B–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PLC Addresses B–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
SLC Addresses B–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8–6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8–9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A–1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
iii

Preface

Preface
Read this preface to familiarize yourself with the rest of the manual. This preface covers the following topics:
who should use this manual
the purpose of this manual
terms and abbreviations
conventions used in this manual
Allen–Bradley support

Who Should Use this Manual

Purpose of this Manual

Use this manual if you are responsible for designing, installing, programming, or troubleshooting control systems that use Allen–Bradley small logic controllers.
You should have a basic understanding of SLC 500t products. You should understand programmable controllers and be able to interpret the ladder logic instructions required to control your application. If you do not, contact your local Allen–Bradley representative for information on available training courses before using this product. If using Advanced Programming
Software (APS), we recommend that you review The APS Quick Start for New Users, Publication 9399-APSQS.
This manual is a reference guide for the Direct Communication Module (DCM). It describes the procedures you use to address, configure and program the DCM for application with PLCs and SLCs.
P–1
Preface
Contents of this Manual
Chapter Title Content
Describes the purpose, background, and scope of
Preface
1 Overview
this manual. Also specifies the audience for whom this manual is intended.
Provides a hardware and system overview including physical features, system communication, scanner
image division and communications flow. 2 3 Addressing Explains slot numbering and image mapping.
4 Module Configuration Provides DIP switch setting information. 5 Installation and Wiring
6 Programming
7 Troubleshooting Describes troubleshooting using front panel LEDs. 8 Application Examples
Appendix A Specifications
Appendix B DCM Addressing Worksheet
Quick Start
for Experienced Users
Serves as a Quick Start Guide for using the DCM.
Provides installation procedures and a wiring
diagram.
Shows how to program ladder logic in the PLCr
and the SLC 500, including an examination of
special programming instructions that affect system
response. Also examines the status word and its
applications.
Provides and examines both basic and
supplementary applications.
Provides module and system specifications and
discusses throughput.
Helps you to work out the image table configuration
for DCMs in your system.
P–2
Preface
Related Documentation
The following documents contain additional information concerning Allen–Bradley SLCt and PLC products. To obtain a copy, contact your local Allen–Bradley office or distributor.
For Read This Document
An overview of the SLC 500 family of products SLC 500 System Overview 1747-2.30 A description on how to install and use your Fixed SLC 500
programmable controller A description on how to install and use your Modular SLC 500
programmable controller A reference manual that contains information regarding the use of
the PLC–5r programmable controller A procedural manual for technical personnel who use APS to
develop control applications A reference manual that contains status file data, and instruction
set information for the SLC 500 processors and MicroLogix 1000 controllers.
Information regarding the use of the 1747–SN SLC RIO scanner Remote I/O Scanner User Manual 1747-6.6 An introduction to APS for first–time users, containing basic
concepts but focusing on simple tasks and exercises, and allowing the reader to begin programming in the shortest time possible
A training and quick reference guide to APS
A common procedures guide to APS. A procedural and reference manual for technical personnel who
use an HHT to develop control applications An introduction to HHT for first–time users, containing basic
concepts but focusing on simple tasks and exercises, and allowing the reader to begin programming in the shortest time possible
An article on wire sizes and types for grounding electrical equipment
A complete listing of current Allen–Bradley documentation, including ordering instructions. Also indicates whether the documents are available on CD–ROM or in multi–languages.
A glossary of industrial automation terms and abbreviations Allen–Bradley Industrial Automation Glossary AG-7.1
Installation & Operation Manual for Fixed Hardware Style Programmable Controllers
Installation & Operation Manual for Modular Hardware Style Programmable Controllers
PLC–5 Reference Instruction Set 1785-6.1 Rockwell Software Advanced Programming
Software (APS) User Manual SLC 500t and MicroLogix 1000t Instruction Set
Reference Manual
Quick Start for New Users 9399-APSQS
SLC 500 Software Programmer’s Quick Reference Guideavailable on PASSPORT at a list price of $50.00
SLC 500 Common Procedures Guideavailable on PASSPORT at a list price of $50.00
Allen–Bradley Hand–Held Terminal User Manual 1747-NP002
Getting Started Guide for HHT 1747-NM009
National Electrical Code
Allen–Bradley Publication Index SD499
Document
Number
1747-6.21
1747-6.2
9399-APSUM
1747-6.15
ABT-1747-TSG001
ABT-1747-TSJ50
Published by the National Fire Protection Association of Boston, MA.
P–3
Preface

Terms and Abbreviations

The following terms and abbreviations are specific to this product. For a complete listing of Allen–Bradley terminology, refer to the Allen–Bradley Industrial Automation Glossary, Publication Number ICCG–7.1.
Adapter – Any physical device that is a slave on the RIO link. Adapter Image – The portion of scanner image assigned to an individual
adapter. You configure the adapter image by assigning it a starting logical rack number, starting logical group number and the number of logical groups it uses. In the case of the DCM, this is referred to as the DCM image.
DCM – Refers to the Direct Communication Module. Distributed Control/Controller – Refers to a control system that employs a
number of different hardware controllers/processors, each designed to perform a different subtask on behalf of an overall program or process. In a single processor (non–distributed) system, each task would be done by the single processor controlling the process. In a distributed system, each task is targeted to the specific processor required to perform its needs. Since all processors run simultaneously and independently, the time required to perform each task of the overall process is reduced in comparison to a single processor system. Therefore, overall program or process performance is typically better.
Inhibit – A function by which the scanner stops communicating with a logical device. The logical device will consider itself inhibited if it does not receive communications from the scanner within a certain period of time.
Logical Device Logical Group – A logical group consists of one input and one output word
within a logical rack. A word consists of 16 bits, each bit represents one terminal on a discrete I/O module. Also referred to as an I/O Group.
Logical Rack – A fixed section of the scanner image comprised of eight input words and eight output words. Also referred to as a rack.
Logical Slot – A logical slot consists of one input and one output byte within a logical group. A byte consists of 8 bits, each bit represents one terminal on a discrete I/O module.
Physical Device – The number of devices that the supervisory processor/ scanner will support.
PLC Chassis – A physical PLC (Programmable Logic Controller) rack that houses PLC processors and 1771 I/O modules.
– Any portion of a logical rack assigned to a single adapter.
P–4
Preface
Rack Size – The logical rack size of the DCM image. RIO Link – (Remote Input/Output) Refers to an Allen–Bradley
communication system supporting high–speed serial transfer of Remote I/O (RIO) control information.
Scanner – The communication master on the RIO link. Scanner Image – The data table area within the scanner, used to exchange
I/O information between the scanner and all the adapters on the RIO link. The scanner image is a portion of the SLC or PLC processor image.
Slave – In a communication link, a station that cannot initiate communication.
SLC Chassis – A physical SLC (Small Logic Controller) rack that houses SLC processors and 1746 and 1747 I/O modules.
Slot – The physical location in any chassis used to insert I/O (or specialty) modules.

Common Techniques Used in this Manual

Supervisory Control/Controller – A control system whereby a host (supervisory) controller/processor monitors and intermittently adjusts control parameters, as necessary, of one or several lower level processors while the lower level processor(s) performs the control task continuously in real time.
The following conventions are used throughout this manual:
Bulleted lists such as this one provide information, not procedural steps.
Numbered lists provide sequential steps or hierarchical information.
Italic type is used for emphasis.
P–5
Preface

Allen–Bradley Support

Allen–Bradley offers support services worldwide, with over 75 Sales/Support Offices, 512 authorized Distributors and 260 authorized Systems Integrators located throughout the United States alone, plus Allen–Bradley representatives in every major country in the world.
Local Product Support
Contact your local Allen–Bradley representative for:
sales and order support
product technical training
warranty support
support service agreements
Technical Product Assistance
If you need to contact Allen–Bradley for technical assistance, please review the information in the Troubleshooting chapter first. Then call your local Allen–Bradley representative.
Your Questions or Comments on this Manual
If you find a problem with this manual, please notify us of it on the enclosed Publication Problem Report.
If you have any suggestions for how this manual could be made more useful to you, please contact us at the address below:
Allen–Bradley Company, Inc. Automation Group Technical Communication, Dept. 602V, T122 P.O. Box 2086 Milwaukee, WI 53201–2086
P–6
Chapter
are Overvie
1
Overview
This chapter provides a hardware and system overview including physical features and connectivity illustrations. It also explains data exchange between processors and discusses rack size. Topics include:

hardware overview

system overview
scanner image division
communications flow
Hardw
w
FAULT LED
(Red)
COMM LED
(Green)
Door Label
Front Label
RIO Link Connector
Cable Tie Slots
The Direct Communication Module, Catalog Number 1747–DCM, is used to connect an SLC 500 Fixed Programmable Controller with expansion chassis or any SLC 500 Modular Programmable Controller to a supervisory Allen–Bradley Programmable Controller via the RIO Link, thereby providing a distributed processing system. The DCM occupies one slot in any SLC 500 chassis.
Self–Locking Tab
Side Label
DIP Switches
DCM FAULT COMM
CONFIGURATION
RACK ADDR
RACK SIZE
1/4 1/2 3/4 1
FIRST I/O GROUP 0 2 4 6
DATA RATE (K B/S)
57.6 115.2 230.4
LINE 1 _______ SHIELD ______ LINE 2 _______
SW1
SW2
1747–DCM
I/O
GROUP
(LSB)
RACK
ADDRESS
2345678
(MSB)
1
O
N
X X
RACK
SIZE
LAST
RACK
CLR ON FL
T
2345678
DATA RATE
1
O
N
2345678 1
2345678 1
SW1 SW2
SERIAL NO.
SW 1
I/O
GROUP
(LSB)
RACK ADDR
(MSB)
SW 2
RACK SIZE
LAST
CLR ON FL
MADE IN USA
DATA RATE
CAT
MODULE
X X
RACK
T
DIRECT COMMUNICATION
SLC 500
8 7 6 5 4 3 2 1
8 7 6 5 4 3 2 1
Self–Locking Tab
Hardware Features
Hardware
Function
FAULT LED Displays operating status COMM LED Displays communication status Front, Side and Door Labels Provide module configuration information RIO Link Connector Provides physical connection to RIO network Cable Tie Slots Secure and route wiring from module DIP Switches Establish configuration parameters for the module Self–Locking Tabs Secure module in chassis slot
1–1
Chapter 1
stem Overvie
Overview
Sy
w
Supervisory PLC or SLC
The Direct Communication Module is an SLC 500 family Remote I/O (RIO) adapter. It allows supervisory processors, such as PLC–5s, and distributed SLC–500 processors residing on an Allen–Bradley RIO Communication Link to transfer data between each other. The DCM appears as an RIO adapter to:
a PLC processor with integral RIO scanner on the RIO Communication
Link
an RIO scanner, Catalog Number 1771–SN or 1747–SN, on the RIO
Communication Link
RIO
Scanner
PanelViewt
(adapter)
Distributed SLCs with DCMs (adapters)
RIO Communication Link
DCM 1
DCM 2
DCM 3
DCM modules are connected in a daisy–chain configuration using Belden 9463 cable.
What Is a Remote I/O Adapter?
A remote I/O adapter (RIO adapter) is any module that acts as a slave to an RIO scanner, the master on the RIO link. The DCM is an RIO adapter.
All RIO scanners have defined physical and logical specifications. Physical specifications are the maximum number of adapters that can be connected to the scanner. (See Extended Node Capability on page 1–4.) Logical specifications are the maximum number of logical racks the scanner can address, the ways logical racks can be assigned, and the ability of the scanner to perform block transfers. Refer to the appropriate scanner manual for details concerning physical and logical specifications.
The DCM can physically reside on the RIO link with any other adapter. The following table lists the adapters available for use with an RIO link.
1–2
Chapter 1
Overview
Compatible
Number
1785-LT/x PLC-5/15 Yes In adapter mode 1785-LT2 PLC-5/25 Yes In adapter mode 1785-LT3 PLC-5/12 Yes In adapter mode 1785-L30x PLC-5/30 Yes In adapter mode 1785-L40x PLC-5/40 Yes In adapter mode 1785-L60x PLC-5/60 Yes In adapter mode 1771-ASC Remote I/O Adapter Module No
1771-ASB Remote I/O Adapter Module
1771-AM1
1771-AM2
1784-F30D 1771-RIO Remote I/O Interface Module No
Catalog
Adapters
Device
1-Slot I/O Chassis with Integral Power Supply and Adapter
2-Slot I/O Chassis with Integral Power Supply and Adapter
Plant Floor Terminal Remote I/O Expansion Module
Extended
Node
Capability
Series B and
C only
Yes
Yes
Yes
Comments
Series A, B, and C
1771-JAB Single Point I/O Adapter Module Yes 1771-DCM Direct Communication Module No 1778-ASB Remote I/O Adapter Module Yes 1747-ASB Remote I/O Adapter Module Yes
2706-xxxx 2705-xxx
2711-xx PanelView Terminal Yes 1336-RIO
1395-NA
1747-ASB
DL40 Datalinert RediPANELt
Remote I/O Adapter for 1336 AC Industrial Drives
Remote I/O Adapter for 1395 DC Industrial Drives
SLC 500 Remote I/O Adapter Module
Yes Yes
Yes
Yes
Yes
Must be catalog number 2706-ExxxxxB1.
1–3
Chapter 1
canner Image
on
Overview
Extended Node Capability
Both scanners and adapters can have extended node capability. Extended node capability allows you to have up to 32 adapters on the RIO link using an 82 Ohm termination resistor at both ends of the RIO link for all baud rates.
Extended node capability can only be used if the scanner and all adapters on the RIO link have extended node capability. The DCM has extended node
capability.
S
Divisi
The scanner allows each adapter to use a fixed amount (user defined) of its input and output image.
The scanner image is divided into logical racks and further divided into logical groups. A full logical rack consists of eight input and eight output image words. A logical group consists of one input and one output word in a logical rack. Each logical group is assigned a number from 0–7. The number of racks available for data and I/O transfer depends on the scanner you are using.
Local I/O
Logical Rack 0
Remote I/O
(Scanner
Image)
Processor I/O Image Scanner I/O Image Adapter
Logical Rack 1
Logical
Rack 2
Logical Rack 3
Logical Group 0
Logical
Group 7
Image
1–4
The scanner image also contains the image of each adapter on the RIO link. The adapter is assigned a portion of the scanner image, which is referred to as the adapter image.
Chapter 1
Overview
Scanner Image Division Configuration Example
The example presented here can help you configure your RIO architecture. Refer to it as necessary.
The following figure shows how a portion of a scanner’s input image table might be configured. An output image table would be identically configured.
Logical
0
Rack
Logical
1
Rack
Logical
Rack 2
Decimal Bit Number
Octal Bit Number
Rack 0 Group 0
Rack 0 Group 1
Rack 0 Group 2
Rack 0 Group 3
Rack 0 Group 4
Rack 0 Group 5
Rack 0 Group 6
Rack 0 Group 7
Rack 1 Group 0
Rack 1 Group 1
Rack 1 Group 2
Rack 1 Group 3
Rack 1 Group 4
Rack 1 Group 5
Rack 1 Group 6
Rack 1 Group 7
Rack 2 Group 0
Rack 2 Group 1
Rack 2 Group 2
Rack 2 Group 3
Rack 2 Group 4
Rack 2 Group 5
Rack 2 Group 6
Rack 2 Group 7
Word 0
Word 1
Word 2
Word 3
Word 4
Word 5
Word 6
Word 7
Word 8
Word 9
Word 10
Word 11
Word 12
Word 13
Word 14
Word 15
Word 16
Word 17
Word 18
Word 19
Word 20
Word 21
Word 22
Word 23
0123456789101112131415 012345671011121314151617
Device
(Full logical rack)
1
Device 2
(3/4 logical rack)
Device 3
(1/4 logical rack)
Device
Device
4
5
(1/2 logical rack)
(1/2 logical rack)
Important: The configured image size of a DCM cannot cross logical rack
boundaries; it cannot use a portion of rack 0 and a portion of rack 1.
1–5
Chapter 1
Overview

Data Exchange Between RIO Scanners and the DCM

Processor Scan
Supervisory PLC or SLC
Information is transferred between the RIO scanner and the DCM every RIO scan. RIO transmissions are asynchronous to the processor scans.
Important: The DCM provides word integrity on all words transferred via
the SLC backplane.
The DCM communicates with supervisory PLC or SLC controllers through RIO scanners, as if they were addressing a logical rack. However, the DCM does not scan the I/O in its local I/O chassis, rather it passes the supervisory data to the distributed SLC processor.
In the DCM, outputs from the SLC output image table are inputs to the supervisory processor input image table. Likewise, outputs from the supervisory processor output image table are inputs to the SLC input image table.
The diagram that follows depicts the communications flow between an RIO scanner and the DCM.
Distributed Processor Scan
SLC Distributed
Scanner
RIO Scan
Processor
DCM
I/O Module
I/O Module
Outputs from PLC, Input Data to DCM
SLC Expansion
Chassis
Outputs from Modules
Output Device
Inputs to PLC, Output Data from DCM
SLC Chassis
Inputs to Modules
Input Device
What Is the Status Word?
The first word of the DCM input and output image is the status word. The status word indicates the status of communication and data between the RIO scanner and the DCM. For more information on status words and their applications, see chapter 6, Programming.
1–6
Chapter
2
Quick Start for Experienced Users
This chapter helps you to get started using the Direct Communication Module (DCM). We base the procedures here on the assumption that you have a basic understanding of SLC 500 products.
You must:
understand electronic process control
be able to interpret the ladder logic instructions for generating the
electronic signals that control your application
Because it is a start-up guide for experienced users, this chapter does not contain detailed explanations about the procedures listed. It does, however, reference other chapters in this book where you can get more detailed information. It also references other documentation that may be helpful if you are unfamiliar with programming techniques or system installation requirements.

Required Tools and Equipment

If you have any questions, or are unfamiliar with the terms used or concepts presented in the procedural steps, always read the referenced chapters and other recommended documentation before trying to apply the information.
This chapter:
tells you what tools and equipment you need
lists preliminary considerations
describes when to address, configure and program the module
explains how to install and wire the module
discusses system power-up procedures
Have the following tools and equipment ready:
medium blade screwdriver
(2) 1/2 watt terminating resistors (See chapter 5, Installation and Wiring,
for correct size.)
programming equipment (All programming examples shown in this
manual demonstrate the use of Allen-Bradley’s Advanced Programming Software [APS] for personal computers.)
2–1
Chapter 2
Quick Start for Experienced Users

Procedures

Check
1.
the contents of the shipping box.
Unpack the module making sure that the contents include:
Direct Communication Module (Catalog Number 1747-DCM)
removable connector (factory-installed on module)
cable tie
user manual (Catalog Number 1747-NM007)
If the contents are incomplete, call your local Allen-Bradley representative for assistance.
2.
2.
Select
a scanner
.
To begin configuration of your RIO system, you should know three things:
which scanner is compatible with your PLC/SLC controller. Use the table below to select a
scanner that is compatible with your processor. The DCM is compatible with all RIO scanners.
Catalog Number
1747-SN
1771-SN 1772-SD, -SD2
➂➃
1775-S4A, -S4B, -S5 1775-SR, -SR5 1785-L11B 1785-LT/x 1785-L20B 1785-LT2 1785-L30x 1785-L40x 1785-L60x 5250-RS 6008-SI 6008-SV
➀➄
➀➄
➀ ➀ ➀
SLC Remote I/O Scanner Sub I/O scanner for Mini–PLC-2r and PLC-5 families Remote scanner/distribution panel for PLC-2 family I/O scanner-programmer interface module for PLC-3r family Remote scanner/distribution panel for PLC-3/10 family PLC 5/11t (in scanner mode)
PLC 5/15 (in scanner mode) PLC 5/20t (in scanner mode) PLC 5/25 (in scanner mode) PLC 5/30t (in scanner mode) PLC 5/40t (in scanner mode) PLC 5/60t (in scanner mode) Remote scanner for PLC 5/250 IBMr PC I/O Scanner Module VMEbus I/O Scanner Module
6008-SQH1, -SQH2 Q-bus I/O Scanner Module
Description
Reference
Reference
The manual for
the scanner you
select
2–2
Extended
Revision D or later
Rev
Extended node capability not available with Series A.
node capability
. 3 or later
.
Rev.
3 or later
PLC 5/25 Series A Revision D or later have partial rack addressing. Earlier versions are limited to 7 devices.
.PLC 5/15 Series B Revision H or later have partial rack addressing. Earlier versions are limited to 3 devices.
.
.
Chapter 2
Quick Start for Experienced Users
the maximum number of physical devices and logical racks your scanner supports.
the logical rack size of each DCM. This depends on how many I/O data words you need to transfer. The first word
is always the status word. The table below shows the number of data words transferred relative to the rack size.
If you configure the DCM as:
1/4 Rack
1/2 Rack
3/4 Rack
Full Rack
3.
Select DCM addressing. (A configuration worksheet is included in appendix B to assist you in DCM image table addressing.)
Choose
4.
Configure your system by setting the DIP switches.
5.
the type of slot addressing you will use.
Configure
Insert
the 1747-DCM module into the chassis.
1 data word (16 bits of I/O
3 data words (48 bits of I/O
5 data words (80 bits of I/O
7 data words (112 bits of I/O
the module using the DIP switches.
Then: Including the Status Word
data) are transferred.
data) are transferred.
data) are transferred.
data) are transferred.
Total transfer = 2 words
Total transfer = 4 words
Total transfer = 6 words
Total transfer = 8 words
Reference
Chapter 3
(Addressing)
Appendix B
(DCM Worksheet)
Reference
Chapter 4
(Module
Configuration)
Reference
ATTENTION: Never install, remove, or wire modules with power applied to the chassis or
!
devices wired to the module.
SLC/DCM power requirements to ensure your SLC power supply has adequate reserve power
Review Make sure system power is off; then insert the DCM into your 1746 chassis. In this example
procedure, local slot 1 is selected.
Module Release
Card Guide
. . .
Cable Tie
Chapter 5
(Installation and
Wiring)
.
2–3
Chapter 2
Usin
xtende
8
apabilit
1
1
xtende
e
Quick Start for Experienced Users
To wire the network, a 1/2 watt terminating resistor must be attached across line 1 and line 2 of the connectors at each end (scanner and last physical device) of the network. The size of the resistor depends on the baud rate and extended node capability, as shown below:
Baud Rate
g E
Node C
Not Using E
d Nod
Capability
6.
Define the application requirements. Write and enter the ladder logic program.
7.
Power up your system by performing standard start-up procedures as indicated in your processor manual. No special start-up procedures are required when using the DCM module.
57.6K baud 3048 meters (10,000 feet)
d
115.2K baud 1524 meters (5,000 feet)
y
230.4K baud
57.6K baud 3048 meters (10,000 feet)
115.2K baud 1524 meters (5,000 feet)
230.4K baud 762 meters (2,500 feet)
Enter
Go
through the system start-up procedure.
Maximum Cable Distance
(Belden 9463)
762 meters (2,500 feet)
your ladder program.
Resistor Size
2W 1/2 Watt
Brown–Green–Brown–Gold
50W 1/2 Watt
50W 1/2 Watt
Brown–Green–Brown–Gold 82W 1/2 Watt
Gray–Red–Black–Gold
Reference
Chapter 6
(Programming)
Chapter 8
(Application
Examples)
Reference
2–4
Loading...
+ 56 hidden pages