POINT I/O and ArmorPOINT I/O DeviceLogix Modules User Manual
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize
themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to
be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use
or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software
described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is
prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may
lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or
economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may
be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach
dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc
Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements
for safe work practices and for Personal Protective Equipment (PPE).
2Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Rockwell Automation Publication 1734-UM015B-EN-E - May 20205
Table of Contents
Notes:
6Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Summary of Changes
This manual contains new and updated information. Changes throughout this
revision are marked by change bars, as shown to the right of this paragraph.
New and Updated
Information
This table contains the additions made to this revision.
TopicPage
Updated version and revision information13, 84
Changed Function Block category to Compute/Math67
Added Down Counter type in Timer/Counter category instruction
types
Updated Timer/Counter Category information 70
Removed Square Root (SQR) and Power (XPY) in the Compute
Category
Updated Logic Execution Time table74
New Appendix section for Write Enable Flag Feature113
69
71
Rockwell Automation Publication 1734-UM015B-EN-E - May 20207
Summary of Changes
Notes:
8Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Preface
Purpose of This Manual
This manual describes how to install, configure, and troubleshoot your
POINT I/O™ DeviceLogix™ and ArmorPOINT® I/O DeviceLogix
modules.
POINT I/O and ArmorPOINT I/O modules can be used in EtherNet/IP™,
DeviceNet®, and ControlNet® systems. As such, you may need to refer to
other publications in addition to this one.
When using POINT I/O DeviceLogix modules with a communication
adapter, use this manual in conjunction with the user manual for the adapter
you are using as shown in the table.
POINT I/O DeviceLogix modules are not compatible with the PROFIBUS
adapter.
When using ArmorPOINT I/O DeviceLogix modules with a communication
adapter, use this manual in conjunction with the user manual for the adapter
you are using as shown in the table.
ArmorPOINT I/O DeviceLogix modules are not compatible with the
PROFIBUS adapter.
The modules in this manual are DeviceNet-ready. Each module can exist on
the DeviceNet network as one of the following:
• An individual node
• With an adapter (catalog number 1734-ADN or 1734-ADNX) as a
single node
For applications using these modules in a network with a 1734-PDN
DeviceNet Communication Interface, or a 1734D-xx POINTBlock I/O
module, this user manual is the primary documentation.
Rockwell Automation Publication 1734-UM015B-EN-E - May 20209
Preface
Who Should Use This
Manual
This manual is intended for qualified personnel. You should know how to do
the following:
• Use RSNetWorx™ software or similar configuration software to se
and calib
•
Download and use electronic data sheet (EDS) files.
rate these module
s.
In addition, you should be familiar with RSLogix 5000® and CIP™ Network
terminology. If you do not, refer to your
software documentation or online
help before attempting to use these modules.
Related Publications
Refer to this table for a list of related POINT I/O products and
documentation. The publications are available atrok.auto/literature. For
specification and safety certification information, refer to the installation
instructions.
Resource Description
POINT I/O DeviceLogix Module
POINT I/O Module with 8 Configurable 24V DC Points and DeviceLogix
Installation Instructions, publication 1734-IN039
Communication Devices
ControlNet Adapter Installation Instructions, publication 1734-IN582Provides installation information about 1734-ACNR adapters.
ControlNet Adapter User Manual, publication 1734-UM008
DeviceNet Communication Interface Module Installation Instructions,
publication 1734-IN057
DeviceNet Adapter Installation Instructions, publication 1734-IN026Provides installation information about 1734-ADN and 1734-ADNX
DeviceNet Adapter User Manual, publication 1734-UM002
RSNetWorx for DeviceNet Getting Results Guide, publication DRNET-
GR001
EtherNet/IP Adapter Installation Instructions, publication 1734-IN590Provides installation information about 1734-AENT adapters.
EtherNet/IP Adapter User Manual, publication 1734-UM011
Power Supplies, Wiring Base Assemblies, Miscellaneous
Field Potential Distributor Installation Instructions, publication 1734-IN059Provides installation information about 1734-FPD distributors.
POINT I/O 24V DC Expansion Power Supply Installation Instructions,
publication 1734-IN058
POINT I/O 120/240V AC Expansion Power Supply Installation Instructions,
publication 1734-IN017
POINT I/O Common Terminal Module Installation Instructions, publication
1734-IN024
POINT I/O Voltage Terminal Module Installation Instructions, publication
1734-IN024
Provides installation information and wiring diagrams for 1734-8CFGDLX
modules.
Describes how to use 1734-ACNR adapters.
Provides installation information about 1734-PDN modules.
adapters.
Describes how to use 1734-ADN and 1734-ADNX adapters.
Describes how to install and navigate the RSNetWorx for DeviceNet
software.
Describes how to use 1734-AENT adapters.
Provides installation information about 1734-EP24DC power supplies.
Provides installation information about 1734-EPAC power supplies.
Provides installation information about 1734-CTM modules.
Provides installation information about 1734-VTM modules.
t up
10Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Resource Description
POINT I/O Wiring Base Assembly Installation Instructions, publication
1734-IN511
POINT I/O Wiring Base Assembly Installation Instructions, publication
1734-IN013
POINT I/O One-piece Wiring Base Assembly Installation Instructions,
publication 1734-IN028
Provides installation information about 1734-TB and 1734-TBS assemblies.
Provides installation information about 1734-TB3 and 1734-TB3S
assemblies.
Provides installation information about 1734-TOP, 1734-TOPS, 1734-TOP3,
and 1734-TOP3S assemblies.
Refer to this table for a list of related ArmorPOINT I/O products and
documentation. The publications are available atrok.auto/literature. For
specification and safety certification information, refer to the installation
instructions.
ArmorPOINT I/O DeviceNet Adapter User Manual, publication 1738-UM001 Describes how to use 1738-ADN and 1738-ADNX adapters.
ArmorPOINT EtherNet/IP Adapter, Series A Installation Instructions,
publication 1738-IN017
ArmorPOINT I/O 2-Port EtherNet/IP Adapter, Series A Installation
Instructions, publication 1738-IN028
Power Supplies, Wiring Base Assemblies, Miscellaneous
ArmorPOINT I/O Field Potential Distributor, Series A Installation
Instructions, publication 1738-IN019
ArmorPOINT I/O 24V DC Expansion Power Supply, Series A Installation
Instructions, publication 1738-IN020
Provides wiring diagrams for 1738-8CFGDLXM8, 1738-8CFGDLXM12, and
1738-8CFGDLXM23.
Provides installation information about 1738-8CFGDLXM8, 17388CFGDLXM12, and 1738-8CFGDLXM23.
Provides installation information about 1738-ACNR adapters.
Provides installation information about 1738-ADN and 1738-ADNX
adapters.
Provides installation information about 1738-AENT adapters.
Provides installation information about 1738-AENTR adapters.
Provides installation information about 1738-FPD distributors.
Provides installation information about 1738-EP24DC power supplies.
Preface
Rockwell Automation Publication 1734-UM015B-EN-E - May 202011
Preface
Notes:
12Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Introduction
Chapter
1
About This Chapter
About the Modules
This chapter introduces POINT I/O and ArmorPOINT I/O configurable
modules with DeviceLogix capability.
•About the Modules
• Quick Start - Prepare the Modules to work on DeviceNet
• Quick Start - Prepare the Modules to work on EtherNet/IP and
ControlNet
The POINT I/O and ArmorPOINT I/O modules work with EtherNet/IP,
DeviceNet, and ControlNet network adapters. Each module has eight 24V DC
I/O points that self-configure to be inputs or outputs. Inputs are IEC Type 3
and outputs are self-protecting 0.5 A outputs.
The firmware in these modules uses Version 3 (1738-8CFGDLXM8,
1738-8CFGDLXM12, 1738-8CFGDLXM23) and Version 7
(1734-8CFGDLX) of the DeviceLogix master library. The modules can
execute 144 DeviceLogix function blocks in 3 ms. Smaller programs that
contain fewer than 40 function blocks can be executed in 1 ms.
Each module produces 20 bytes of data including I/O state (8 bits), eight
user-defined bits, and eight user-defined words of analog data to be consumed
by processors or other DeviceLogix modules. Each module consumes 20 bytes
of data to set the I/O state (8 bits), eight user-defined control bits, and eight
user-defined words of analog data. It is also possible to consume the data from
up to eight other peers.
This table lists 1734 and 1738 configurable I/O modules with DeviceLogix.
Module DescriptionCat. No.
POINT I/O module with 8 configurable 24V DC I/O points
and DeviceLogix capabilities
ArmorPOINT I/O module with 8 configurable 24V DC M8
connectors and DeviceLogix
ArmorPOINT I/O module with 8 configurable 24V DC M12
connectors and DeviceLogix
ArmorPOINT I/O module with 1 configurable 24V DC M23
connector and DeviceLogix
Rockwell Automation Publication 1734-UM015B-EN-E - May 202013
1734-8CFGDLX
1738-8CFGDLXM8
1738-8CFGDLXM12
1738-8CFGDLXM23
Introduction
1734-8CFGDLX
This module is an 8-point 24V DC I/O module with eight self-configuring
points and DeviceLogix capabilities. Each of the I/O points can be either a
DC input or output. The module supports removal and insertion under power,
auto-address, and auto-baud in compliance with the POINTBus™ backplane.
1738-8CFGDLXM8, 1738-8CFGDLXM12, and 1738-8CFGDLXM23
The ArmorPOINT I/O family consists of modular I/O modules. The sealed
IP67 housing of these modules requires no enclosure. Environmental
requirements other than IP67 may require an additional appropriate housing.
I/O connectors are sealed M8 (Pico™), M12 (micro) or M23 styles. The
mounting base ships with the module.
Modes of Usage
The module can be used in one of the following modes:
• as a standard POINT I/O module,
• in a standalone DeviceLogix program where it controls its own I/O, and
• in network applications with or without the peer exchange of data.
Standard POINT I/O Module
The module can simply be used as an 8-point configurable POINT I/O
module. It uses ODVA pre-defined Produce and Consume assemblies. Default
settings help to facilitate quick setup right out-of-the-box. It is CIP network
independent and it can run on DeviceNet, EtherNet/IP or ControlNet when
used in conjunction with an adapter.
14Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Introduction
Stand Alone DeviceLogix
If DeviceLogix is enabled (programmed), then the module becomes the owner
of its outputs. The DeviceLogix program reads inputs and controls the
onboard outputs.
• The produced assembly may be shared with a controller if a connection
exists.
• As the owner of its local outputs, the module may run without an
external controller.
An external controller, which is the owner of the connection to the module,
can influence the module’s logic via a consume assembly – both digital and
analog data. Configuration of the module is performed via RSNetWorx for
DeviceNet. When used on ControlNet or EtherNet/IP, the tool bridges
through the adapter to directly communicate with the DeviceLogix module on
the POINT I/O backplane.
Peer Enabled POINT I/O
The POINT I/O DeviceLogix module can “listen in” on data connections to
other POINT I/O modules on the backplane. This data can be used in the
DeviceLogix program to control the outputs. It can consume data from eight
different peers. The data from each peer can be up to 24 bytes long. The data
can be digital, analog (16-bit), or a mixture. The module supports the “Auto
Produce” parameter to produce I/O data automatically without the need for a
master. It will also produce and consume network data. Configuration of peer
data is performed via RSNetWorx.
See Chapter 6, Configuring POINT I/O and ArmorPOINT I/O DeviceLogix
modules using RSNetWorx for DeviceNet.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202015
Introduction
Mount the Module
For POINT I/O, see Chapter 2
.
For ArmorPOINT I/O, see Chapter 3
.
Wire the Module
For POINT I/O, see Chapter 2
.
For ArmorPOINT I/O, see Chapter 3
.
Configure DeviceNet Network and
Scanner
See Chapter 4
.
Configure the Module using
RSNetWorx for DeviceNet
See Chapter 6
.
Write the DeviceLogix Program
See Chapter 7
.
Quick Start - Prepare the
Modules to work on
DeviceNet
16Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Quick Start - Prepare the
Mount the Module
For POINT I/O, see Chapter 2
.
For ArmorPOINT I/O, see Chapter 3
.
Wire the Module
For POINT I/O, see Chapter 2
.
For ArmorPOINT I/O, see Chapter 3
.
Add Module to RSLogix 5000
See Chapter 5
.
Write the DeviceLogix Program in
RSNetWorx for DeviceNet
See Chapter 7
.
Modules to work on
EtherNet/IP and ControlNet
Introduction
Rockwell Automation Publication 1734-UM015B-EN-E - May 202017
Introduction
Notes:
18Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Chapter
ATTENTION
2
Install POINT I/O DeviceLogix Modules
If you are using ArmorPOINT I/O modules
(1738-8CFGDLXM8/M12/M23), go to Chapter 3, Install ArmorPOINT I/O
DeviceLogix Modules.
About This Chapter
Read this chapter for installation and wiring information including how to
complete the following:
• Install the Mounting Base Assembly
• Install an I/O Module
• Install the Removable Terminal Block
• Remove a 1734-TB or 1734-TBS Base
• Wire the Modules
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2
industrial environment, in overvoltage Category II applications
(as defined in IEC publication 60664-1), at altitudes up to 2000 m
(6561 ft) without derating.
This equipment is considered Group 1, Class A industrial
equipment according to IEC/CISPR 11. Without appropriate
precautions, there may be potential difficulties ensuring
electromagnetic compatibility in other environments due to
conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be
mounted within an enclosure that is suitably designed for those
specific environmental conditions that will be present and
appropriately designed to prevent personal injury resulting from
accessibility to live parts. The interior of the enclosure must be
accessible only by the use of a tool. Subsequent sections of this
publication may contain additional information regarding specific
enclosure type ratings that are required to comply with certain
product safety certifications.
See NEMA Standards 250 and IEC 60529, as applicable, for
explanations of the degrees of protection provided by different
types of enclosure. Also, see the appropriate sections in this
publication, as well as the Allen-Bradley publication 1770-4.1
(Industrial Automation Wiring and Grounding Guidelines), for
additional installation requirements pertaining to this equipment.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202019
Install POINT I/O DeviceLogix Modules
ATTENTION
WARNING
ATTENTION
POINT I/O is grounded through the DIN rail to chassis ground.
Use zinc-plated, yellow-chromated steel DIN rail to assure proper
grounding. The use of DIN rail materials (for example, aluminum
or plastic) that can corrode, oxidize, or are poor conductors, can
result in improper or intermittent grounding.
Secure DIN rail to mounting surface approximately every 200 mm
(7.8 in.).
EXPLOSION HAZARD
• Do not disconnect equipment unless power has been
removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment
unless power has been removed or the area is known to
be nonhazardous. Secure any external connections that
mate to this equipment by using screws, sliding latches,
threaded connectors, or other means provided with this
product.
• Substitution of components may impair suitability for
Class I, Division 2.
• If this product contains batteries, they must only be
changed in an area known to be nonhazardous.
Prevent Electrostatic Discharge
This equipment is sensitive to electrostatic discharge, which can
cause internal damage and affect normal operation. Follow these
guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging
when not in use.
20Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Install POINT I/O DeviceLogix Modules
Module
Status
Network
Status
NODE:
0
1
2
3
4
5
6
7
Mechanical
Keying (orange)
Module Wiring
Diagram
Module Locking
Mechanism
Insertable I/O
Module
Mounting Base
Removable Terminal
Block (RTB)
DIN Rail Locking
Screw (orange)
Slide-in Writable
Label
Interlocking Side
Pieces
44713
RTB Removal
Handle
44714
1734-TOP or
1734-TOPS
One-piece
Terminal Base
with Screw or
Spring Clamp
Insertable
I/O Module
Slide-in
Writable Label
Handle
Module Locking
Mechanism
Interlocking
Side Pieces
DIN Rail Locking
Screw (orange)
Module Wiring
Diagram
Mechanical
Keying (orange)
Install the Mounting Base
Assembly
The 1734-8CFGDLX is compatible with 1734-TB, 1734-TBS, 1734-TOP, and
1734-TOPS wiring bases.
The 1734-TB or 1734-TBS wiring base assembly consists of a 1734-MB
mounting base and a 1734-RTB or 1734-RTBS removable terminal
block (RTB).
1734-TB or 1734-TBS wiring base
The 1734-TOP and 1734-TOPS are one-piece terminal bases.
1734-TOP or 1734-TOPS wiring base
Rockwell Automation Publication 1734-UM015B-EN-E - May 202021
Install POINT I/O DeviceLogix Modules
44858
Removable Terminal
Block (RTB)
Mounting Base
31586
To install the mounting base assembly on the DIN rail, proceed as follows.
1. If you are using the 1734-TB or 1734-TBS mounting base, attach the
RTB to the mounting base.
Otherwise, skip to step 2.
2. Position the mounting base (wiring base assembly) vertically above the
installed units, for example, adapter, power supply, or existing module.
3. Slide the mounting base down, allowing the interlocking side pieces to
engage the adjacent module, power supply, or adapter.
4. Press firmly to seat the mounting base on the DIN rail until the base
snaps into place.
22Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
5. Use a small-bladed screwdriver to rotate the DIN-rail locking screw to
the horizontal position.
This locks the assembly to the DIN rail.
Install POINT I/O DeviceLogix Modules
WARNING
Notch
Position 1 is shown.
44710
44966
Install an I/O Module
Install the module before or after base installation. Make sure that the
mounting base is correctly keyed before installing the module into the
mounting base. In addition, make sure the mounting base locking screw is
positioned horizontally referenced to the base.
When you insert or remove the module while backplane power is
on, an electrical arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is removed
or the area is nonhazardous before proceeding.
1. Use a bladed screwdriver to rotate the keyswitch on the mounting base
clockwise until the number required for the type of module aligns with
the notch in the base.
ModuleKeyswitch Position
1734-8CFGDLX1
2. Make certain the DIN-rail locking screw is in the horizontal position,
noting that you cannot insert the module if the locking mechanism is
unlocked.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202023
Install POINT I/O DeviceLogix Modules
2
4V
D
C
Source
Ou
tput
Module
S
t
atus
N
etw
ork
St
a
t
us
17
3
4
O
B
4
E
0
1
2
3
N
ODE:
44967
44859
Handle
Module
3. Insert the module straight down into the mounting base and press to
secure.
4. Secure the module with the RTB removal handle (for 1734-TB or
1734-TBS bases) or handle (for 1734-TOP or 1734-TOPS bases).
24Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Install POINT I/O DeviceLogix Modules
WARNING
44968
Install the Removable
Terminal Block
A removable terminal block (RTB) is supplied with your mounting base
assembly.
To remove, pull up on the RTB handle. This lets you remove and replace the
base when necessary without removing any of the wiring.
To reinsert the RTB, proceed as follows.
When you connect or disconnect the RTB with field-side power
applied, an electrical arc can occur. This could cause an
explosion in hazardous location installations. Be sure to remove
power or that the area is nonhazardous before proceeding.
1. Insert the RTB end opposite the handle into the base unit.
This end has a curved section that engages with the mounting base.
2. Rotate the terminal block into the mounting base until it locks itself in
place.
3. If an I/O module is installed, snap the RTB handle into place on the
module.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202025
Install POINT I/O DeviceLogix Modules
WARNING
44969
Remove a 1734-TB or
1734-TBS Base
To remove a 1734-TB or 1734-TBS mounting base, do the following.
When you insert or remove the module while backplane power
is on, an electrical arc can occur. This could cause an explosion
in hazardous location installations. Be sure to remove power or
that the area is nonhazardous before proceeding.
1. Unlatch the RTB handle on the I/O module.
2. Pull on the RTB handle to remove the RTB.
3. Press the module lock on the top of the I/O module and pull the I/O
module out of the base.
4. Remove the I/O module to the right of the base you are removing,
noting that the interlocking portion of the base sits under the adjacent
module.
5. Use a small-bladed screwdriver to rotate the orange DIN-rail locking
screw on the mounting base to a vertical position.
6. This unlocks the mounting base from the DIN rail.
7. Lift the mounting base straight up to remove.
26Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Install POINT I/O DeviceLogix Modules
WARNING
Remove a 1734-TOP or
1734-TOPS Base
To remove a wiring base from the DIN rail, you must remove the module
installed to the right of the base.
If you connect or disconnect wiring while the field-side power
is on, an electrical arc can occur. This could cause an explosion
in hazardous location installations.
Be sure that power is removed or the area is nonhazardous
before proceeding.
1. Squeeze the module locking mechanism of the module to the right of
the base, pulling up to remove the module.
2. Use a small-bladed screwdriver to rotate the orange DIN-rail locking
screw on the mounting base to a vertical position.
This unlocks the mounting base from the DIN rail.
3. Slide the base up to release it from its mating units.
Rockwell Automation Publication 1734-UM015B-EN-E - May 202027
Install POINT I/O DeviceLogix Modules
7
1
3
0
2
Module
Status
Network
Status
Device
Logix
Status
1734
8CFGDLX
1
3
0
2
5
7
4
6
NODE:
44758
Module Status
Network Status
I/O 0I/O 1
I/O 2I/O 3
I/O 4I/O 5
I/O 6I/O 7
Status of I/O 0
Status of I/O 1
Status of I/O 2
Status of I/O 3
Note that voltage and current to the module is applied through the adapter,
the 1734-FPD module, or the 1734-EP24DC module. V = 10…28.8 V DC.
Status of I/O 4
Status of I/O 5
Status of I/O 6
Status of I/O 7
DeviceLogix Status
Prox
I/O 0
Load
Prox
Prox
Prox
Load
Load
Load
I/O 2
I/O 4
I/O 6
I/O 1
I/O 3
I/O 5
I/O 7
V CC
If a connection to Common or the Supply Voltage is required for two- or
three-wire devices, then a 1734-CTM or 1734-VTM can be used.
Each I/O point is either Input or Output.
44687
Wire the Modules
This section provides wiring instructions for the modules.
1734-8CFGDLX I/O Module
28Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
1734-8CFGDLX Wiring Diagram
Prox
Prox
Prox
Prox
I/O 0
I/O 2
I/O 4
I/O 6
I/O 1
I/O 3
I/O 5
I/O 7
Load
Load
Load
Load
Install POINT I/O DeviceLogix Modules
ChannelTerminal Number
I/OCommonVoltage
00
External
(1)
11
22
33
44
55
66
77
10/28.8 V DC is supplied through the internal power bus.
(1)
Common connections require an external connection, such as a 1734-CTM module.
(2)
Supply Voltage Connections require an external connection such as a 1734-VTM module.
External
(2)
System and Power Considerations
There are no power terminals on the POINT I/O DeviceLogix module. The
module gets its power from the Field Power Bus of the back plane. Depending
on your system and network topology, power can be applied through one of
the following:
• 1734-PDN (DeviceNet adapter)
• 1734-ADN or 1734-ADNX (DeviceNet adapter)
• 1734-ACNR (ControlNet adapter)
• 1734-AENT or 1734-AENTR (EtherNet/IP adapter)
• 1734-EP24DC (Expansion power supply)
• 1734-FPD (Field power distribution)
Rockwell Automation Publication 1734-UM015B-EN-E - May 202029
Install POINT I/O DeviceLogix Modules
1734adn4
Adapter
Status
DeviceNet
Status
POINTBus
Status
I
E
2
C
O
E
2
C
I
B
2
O
B
2
E
ADN
I
B
2
O
B
2
E
O
B
4
E
EP24DC
0 1 0 1
0 1
0 1
0 1
24V DC supply
1734-EP24DC
1734-ADN
12V DC
Status
Power
Power
DeviceNet
System
DeviceNet
Power
Power
0 1 0 1 0 1
1734
VTM
1734-VTM
1734-CTM
Voltage Out
Voltage Out
Voltage Out
Voltage Out
Voltage Out
Voltage Out
Voltage Out
Voltage Out
Common
Common
Common
Common
Common
Common
Common
Common
43929
Voltage Out = 0…7
Common = 0…7
Example of Logical Partitioning
Similarly, field power and common (return) can be terminated in the POINT
I/O system by using the following modules:
• 1734-VTM (Voltage termination module)
• 1734-CTM (Common termination module)
1734
CTM
30Rockwell Automation Publication 1734-UM015B-EN-E - May 2020
Loading...
+ 90 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.