Summary of Changes1
Important User Information2
Environment and Enclosure3
Preventing Electrostatic Discharge3
Overview4
Catalog Number Explanation6
Install the Module6
Set the Network Address6
Mount the Module7
Product Dimensions8
Connect the I/O, Network and Auxiliary Cables to the Module10
Configure the Module14
Interpret LED Indicators16
Specifications19
Summary of Changes
This publication contains the following new or updated information. This list includes substantive updates only and is not
intended to reflect all changes.
Top icPa ge
Removed catalog number 1732E-16CFGM12P5QCWR to be
included in 1732E-IN009 publication
Corrected on component selection guide and system tools link14
Module specifications updated, refer to change bars for details19
Module certification updated22
Changed to new templatethroughout
1
ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect Installation Instructions
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety
Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from
your local Rockwell Automation sales office or online at rok.auto/literature
between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also
because of the wide variety of uses for solid- state equipment, all persons responsible for applying this equipment must
satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from
the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables
and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WAR N IN G : Identifies information about practices or circumstances that can cause an
explosion in a hazardous environment, which may lead to personal injury or death, property
damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to
personal injury or death, property damage, or economic loss. Attentions help you identify a
hazard, avoid a hazard and recognize the consequences.
SHOCK HAZARD: Label s may be on o r inside th e equipmen t (for exam ple, drive o r motor) to
alert people that dangerous voltage may be present.
) describes some important differences
BURN HAZARD: Labels may be on or inside the equipment (for example, drive or motor) to
alert people that surfaces may reach dangerous temperatures.
IMPORTANT
Identifies information that is critical for successful application and understanding of the
product.
2Rockwell Automation Publication 1732E-IN010D-EN-E - August 2020
ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect Installation Instructions
Environment and Enclosure
ATTENTION: This equipment is intended for use in overvoltage Category II applications (as defined
in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
ATTENTION: This equipment is considered Group 1, Class A industrial equipment according to IEC/
CISPR 11. Without appropriate precautions, there may be difficulties with ele ctromagnetic
compatibility in residential and other environments due to conducted and radiated disturbances.
ATTENTION: This equipment is supplied as enclosed equipment. It should not require additional
system enclosure when used in locations consistent with the enclosure type ratings stated in the
Specifications section of this publication. Subsequent sections of this publication may contain
additional information regarding specific enclosure type rati ngs, beyond what this product
provides, that are required to comply with certain product safety certifications.
ATTENTION: In addition to this publication, see:
• Industrial Automation Wiring and Grounding Guidelines, Rockwell Automation publication
1770-4.1
, for additional installation requirements.
• NEMA Standard 250 and IEC 60529, as applicable, for explanations of the degrees of protection
provided by different types of enclosure.
Preventing Electrostatic Discharge
ATTENTION: This equipment is sensitive to electrostatic discharge, which can cause internal
damage and affect normal operation. Follow these guidelines when you handle this equipment:
• Touch a grounded object to discharge potential static.
• Wear an approved grounding wriststrap.
• Do not touch connectors or pins on component boards.
• Do not touch circuit components inside the equipment.
• Use a static-safe workstation, if available.
• Store the equipment in appropriate static-safe packaging when not in use.
Rockwell Automation Publication 1732E-IN010D-EN-E - August 20203
ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect Installation Instructions
Additional Resources
ResourceDescription
ArmorBlock 2-Port EtherNet with Diagnostics and
QuickConnect Wiring Diagrams, publication 17 32E-WD004
Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1
If you would like a manual, you can:
• download a free electronic version from the Internet rok.auto/literature
• purchase a printed manual by contacting your local Allen-Bradley® distributor or Rockwell Automation
representative
Detailed description of how to wire your 1732E12X4M12QCDR or 1732E-12X4M12P5QCDR module.
Detailed description of how to wire your 1732E16CFGM12QCWR module.
Detailed description of how to wire your 1732E16CFGM12QCR or 1732E-16CFGM12P5QCR module.
Detailed explanation on how to set up and use
QuickConnect ArmorBlock modules.
More information on proper wiring and grounding
techniques.
Overview
The 1732E-12X4M12QCDR, 1732E-12X4M12P5QCDR, 1732E-16CFGM12QCR, 1732E-16CFGM12P5QCR, 1732E-16CFGM12QCWR
ArmorBlock® are I/O modules that communicate via Eth erNet/IP™. The sealed IP65, IP66, IP67, and IP69K housing of these
modules requires no enclosure. The I/O modules have dual Ethernet ports and use an e mbedded Ethernet switch.
The modules have Auxiliary power In and Out connectors. There is no need to house these modules in a secondar y
enclosure. The I/O modules support the QuickConnect feature, onboard nonvolatile memory for storing block-specific
data such as Tool ID and counter value, and provide basic distributed I/O functionality.
4Rockwell Automation Publication 1732E-IN010D-EN-E - August 2020
Module Identification
LINK 1
LINK 2
MOD
NET
PORT 1
PORT 2
AUX POWER
45758
1732E-16CFGM12QCWR shown
LED status indicators
Functio n earth
(2)
EtherNet/IP D-code M12
connector
EtherNet/IP D-code M12
connector
Node address
switches
M12 style
I/O connectors
Mini-style auxiliary
power in
Mini-style auxiliary
power out
M12 style I/O
connectors
Protective earth
(1)
ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect Installation Instructions
(1) Protective Earth is provided for the grounding of field devices and is internally connected to each Pin 5 of the
M12 I/O connectors. See
I/O Connectors on page 10.
(2) Functional Earth grounds the I/O block’s EtherNet/IP communication circuitry which is designed to mitigate the
effect of noise on the network. See
Rockwell Automation Publication 1732E-IN010D-EN-E - August 20205
EtherNet/IP Connector on page 12.
ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect Installation Instructions
Catalog Number Explanation
Refer to the table for a description of the module catalog numbers.
Catalog NumberDescription
1732E-12X4M12QCDR
1732E-12X4M12P5QCDR
1732E-16CFGM12QCR
1732E-16CFGM12P5QCR
1732E-16CFGM12QCWR
Diagnostic 12-input/4 output 24V DC digital I/O
dual-port Ethernet module with QuickConnect
Diagnostic 12-input/4 output 24V DC digital I/O
dual-port Ethernet module with QuickConnect
16 channel 24V DC self-configurable digital I/O
dual-port Ethernet module with QuickConnect
16 channel 24V DC self-configurable digital I/O
dual-port Ethernet module with QuickConnect
16 channel 24V DC self-configurable digital I/O
dual-port Ethernet metal WeldBlock module with
QuickConnect
Network
Connector
Dual D-code M12
Dual D-code M12
Dual D-code M12
Dual D-code M12
Dual D-code M12
Auxiliary
Power
Dual 4-pin
mini
Dual 5-pin
mini
Dual 4-pin
mini
Dual 5-pin
mini
Dual 4-pin
mini
Install the Module
To install the module:
• Set the network address
•Mount the module
• Connect the I/O, Network and Auxiliary cables to the module.
Set the Network Address
The I/O block ships with the rotary switches set to 999 and DHCP enabled.
To change the network address, you can do one of the following:
• adjust the switch on the front of the module.
• use a Dynamic Host Configuration Protocol (DHCP) server, such as Rockwell Automation® BootP/DHCP.
• retrieve the IP address from nonvolatile memory.
The I/O block reads the switches first to determine if the switches are set to a valid number. To set the network address:
1. Rotate the three (3) switches on the front of the module using a small blade screwdriver.
2. Line up the small notch on the switch with the number setting you wish to use.
Valid settings range from 001…254.
3. Cycle power.
6Rockwell Automation Publication 1732E-IN010D-EN-E - August 2020
ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect Installation Instructions
Example shows default node
address set at 163.
45759
Set Network Address
When the switches are set to a valid number, the I/O block’s IP address is 192.168.1.xxx (where xxx represents the number
set on the switches). The I/O block’s subnet mask is 255.255.255.0 and the gateway address is set to 0.0.0.0. When the I/O
block uses the network address set on the switches, the I/O block does not have a host name assigned to it or use any
Domain Name Server.
If the switches are set to an invalid number (for example, 000 or a value greater than 254 excluding 888), the I/O block
checks to see if DHCP is enabled. If DHCP is enabl ed, the I/O block asks for an address from a DHCP server. The DHCP
server also assigns other Transport Control Protocol (TCP) parameters.
If DHCP is not enabled, the I/O block uses the IP address (along with other TCP configurable parameters) stored in
nonvolatile memory.
Mount the Module
Two sets of mounting holes are used to mount the module directly to a panel or machine. Mounting holes accommodate
#8 (M4) pan head screws. The torque specification is 1.13 Nm (10 in-lb).
Rockwell Automation Publication 1732E-IN010D-EN-E - August 20207
ArmorBlock 2-Port EtherNet/IP Modules with QuickConnect Installation Instructions
LINK 1 LINK 2
MOD
NET
AUX POWER
PORT 1PORT 2
45760
200 mm
(2.38 in.)
45 mm
28 mm
(7.87 in.)
189.6 mm
(7.46 in.)
60.4 mm
(1.77 in.)
(1.1 in.)
Front viewSide view
Product Dimensions
Refer to the mounting dimensions illustration to help you mount the module.Module Dimensions
8Rockwell Automation Publication 1732E-IN010D-EN-E - August 2020
Loading...
+ 16 hidden pages