Rockwell Automation Allen-Bradley PowerFlex 750 Series, PowerFlex 755TL, PowerFlex 755TM, PowerFlex 755TR Service Manual

Hardware Service Manual
Original Instructions
PowerFlex 750-Series Products with TotalFORCE Control
Catalog Numbers 20G, 20J
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANT Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Before You Begin Tests, Maintenance, or Repairs

Table of Contents

Preface
Summary of Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Chapter 1
Product Advisories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Qualified Personnel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Personal Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Product Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Class 1 Light-emitting Diode Product . . . . . . . . . . . . . . . . . . . . . . 14
Remove Power from the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Frames 5 and 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Frames 7…15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Commonly Used Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Software Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Hardware Installation Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Fastener Torque Sequences . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Chapter 2
Preventative Maintenance Recommended Preventative Maintenance. . . . . . . . . . . . . . . . . . . . . . . 27
Predictive Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Schedule Codes Explanation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Shock Events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Maintenance of Industrial Control Equipment . . . . . . . . . . . . . . . . . . 42
Solid-state Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Chapter 3
Component Inspection and Test Procedures
Component Inspection and Maintenance . . . . . . . . . . . . . . . . . . . . . . . 45
Forward and Reverse Biased IGBT/Diode Tests . . . . . . . . . . . . . . . . . 47
AC Input Link Fuses Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
DC Link Fuse Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Component Fuse Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Chapter 4
Frame 5 Components Frame 5 Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Remove the Cover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Remove the Cover from the Chassis. . . . . . . . . . . . . . . . . . . . . . . . . 56
Install the Cover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Main Control Circuit Board Replacement . . . . . . . . . . . . . . . . . . . . . . 57
Remove the Main Control Circuit Board. . . . . . . . . . . . . . . . . . . . 57
Install the Main Control Circuit Board . . . . . . . . . . . . . . . . . . . . . 60
Stirring Fan Assembly Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Remove the Stirring Fan Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Install the Stirring Fan Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Rockwell Automation Publication 750-TG100B-EN-P - June 2019 3
Table of Contents
Heatsink Fan Assembly Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
Remove the Heatsink Fan Assembly . . . . . . . . . . . . . . . . . . . . . . . . 62
Install the Heatsink Fan Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Fan Power Supply Circuit Board Replacement. . . . . . . . . . . . . . . . . . . 64
Remove the Fan Power Supply Circuit Board . . . . . . . . . . . . . . . . 64
Install the Fan Power Supply Circuit Board. . . . . . . . . . . . . . . . . . 65
Potential Earth (PE) Jumper Replacement . . . . . . . . . . . . . . . . . . . . . . 66
Remove the PE Jumper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Install the PE Jumper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Power Feedback Circuit Board and Bracket Replacement. . . . . . . . . 67
Remove the Power Feedback Circuit Board and Bracket . . . . . . 67
Install the Power Feedback Circuit Board and Bracket. . . . . . . . 70
LCL Filter Capacitor Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Remove the LCL Filter Capacitor. . . . . . . . . . . . . . . . . . . . . . . . . . . 71
Install the LCL Filter Capacitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Chapter 5
Frame 6 Components Frame 6 Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Remove the Cover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Remove the Cover from the Chassis. . . . . . . . . . . . . . . . . . . . . . . . . 76
Install the Cover. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Main Control Circuit Board Replacement . . . . . . . . . . . . . . . . . . . . . . 77
Remove the Main Control Circuit Board. . . . . . . . . . . . . . . . . . . . 77
Install the Main Control Circuit Board . . . . . . . . . . . . . . . . . . . . . 80
Stirring Fan Assembly Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Remove the Stirring Fan Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Install the Stirring Fan Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Heatsink Fan Assembly Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Remove the Heatsink Fan Assembly . . . . . . . . . . . . . . . . . . . . . . . . 82
Install the Heatsink Fan Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . 83
DR and PE-A (EMC & MOV) Jumper Replacement. . . . . . . . . . . . . 83
Remove the DR and PE-A (EMC & MOV) Jumper . . . . . . . . . . 83
Install the DR and PE-A (EMC & MOV) Jumper. . . . . . . . . . . . 84
Fan Power Supply Circuit Board Replacement. . . . . . . . . . . . . . . . . . . 84
Remove the Fan Power Supply Circuit Board . . . . . . . . . . . . . . . . 84
Install the Fan Power Supply Circuit Board. . . . . . . . . . . . . . . . . . 86
Power Feedback Circuit Board and Bracket Replacement. . . . . . . . . 87
Remove the Power Feedback Circuit Board and Bracket . . . . . . 87
Install the Power Feedback Circuit Board and Bracket. . . . . . . . 90
LCL Filter Capacitor Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Remove the LCL Filter Capacitor. . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Install the LCL Filter Capacitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
4 Rockwell Automation Publication 750-TG100B-EN-P - June 2019
Table of Contents
Chapter 6
Frame 7 Components Frame 7 Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
IP54 Exhaust Vent Filters Replacement . . . . . . . . . . . . . . . . . . . . . . . . . 98
IP54, 800 mm Wide Door Vent Filters Replacement . . . . . . . . . . . . . 98
IP21, 800 mm Wide Door Vent Filter Replacement. . . . . . . . . . . . . . 98
Control Pod Cover Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Remove the Control Pod Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Install the Control Pod Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Control Pod Fan Assembly Replacement. . . . . . . . . . . . . . . . . . . . . . . . 99
Remove the Control Pod Fan Assembly . . . . . . . . . . . . . . . . . . . . . 99
Install the Control Pod Fan Assembly . . . . . . . . . . . . . . . . . . . . . . 100
Main Control Circuit Board Replacement . . . . . . . . . . . . . . . . . . . . . 101
Remove the Main Control Circuit Board. . . . . . . . . . . . . . . . . . . 101
Install the Main Control Circuit Board . . . . . . . . . . . . . . . . . . . . 103
Control Pod Assembly Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Remove the Control Pod Assembly . . . . . . . . . . . . . . . . . . . . . . . . 104
Install the Control Pod Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . 108
Power/Filter Module Heatsink Fan Assembly Replacement. . . . . . 109
Remove the Power/Filter Module Fan Assembly . . . . . . . . . . . . 109
Install the Power/Filter Module Fan Assembly. . . . . . . . . . . . . . 110
Remove the Protective Guard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Remove the Protective Guard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Install the Protective Guard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Control Transformer Fuses (FH4) Replacement. . . . . . . . . . . . . . . . 112
Remove the Control Transformer Fuses. . . . . . . . . . . . . . . . . . . . 112
Install the Control Transformer Fuses. . . . . . . . . . . . . . . . . . . . . . 112
Power Module Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Remove the Power Module from the Enclosure . . . . . . . . . . . . . 113
Install the Power Module in the Enclosure. . . . . . . . . . . . . . . . . . 120
Power Layer Interface Circuit Board Replacement . . . . . . . . . . . . . . 120
Remove the Power Layer Interface Circuit Board. . . . . . . . . . . . 120
Install the Power Layer Interface Circuit Board . . . . . . . . . . . . . 123
Power Interface Circuit Board Replacement . . . . . . . . . . . . . . . . . . . . 124
Remove the Power Interface Circuit Board . . . . . . . . . . . . . . . . . 124
Install the Power Interface Circuit Board . . . . . . . . . . . . . . . . . . . 126
LCL Filter Module Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 127
Remove the LCL Filter Module from the Enclosure . . . . . . . . . 127
Install the LCL Filter Module in the Enclosure. . . . . . . . . . . . . . 131
Current Sense Circuit Board Replacement . . . . . . . . . . . . . . . . . . . . . 132
Remove the Current Sense Circuit Board. . . . . . . . . . . . . . . . . . . 132
Install the Current Sense Circuit Board . . . . . . . . . . . . . . . . . . . . 137
Rockwell Automation Publication 750-TG100B-EN-P - June 2019 5
Table of Contents
Chapter 7
Control Bay and Control Pod Components
Control Bay and Control Pod Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
IP21/IP54 Roof Vent Filter Replacement . . . . . . . . . . . . . . . . . . . . . . 142
Remove the IP21/IP54 Roof Vent Filter . . . . . . . . . . . . . . . . . . . 142
Install the IP21/IP54 Roof Vent Filter . . . . . . . . . . . . . . . . . . . . . 143
IP54/IP21 Roof Vent Fan Replacement. . . . . . . . . . . . . . . . . . . . . . . . 143
Remove the IP21/IP54 Roof Vent Fan . . . . . . . . . . . . . . . . . . . . . 143
Install the IP21/IP54 Roof Vent Fan. . . . . . . . . . . . . . . . . . . . . . . 144
IP21/IP54 Door Vent Filter Replacement. . . . . . . . . . . . . . . . . . . . . . 145
Remove the IP21/IP54 Door Vent Filter . . . . . . . . . . . . . . . . . . . 145
Install the IP21/IP54 Door Vent Filter. . . . . . . . . . . . . . . . . . . . . 145
Control Pod Cover Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Remove the Control Pod Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . 146
Install the Control Pod Cover . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Fiber Transceiver Circuit Board Replacement . . . . . . . . . . . . . . . . . . 148
Remove the Fiber Transceiver Circuit Board. . . . . . . . . . . . . . . . 148
Install the Fiber Transceiver Circuit Board . . . . . . . . . . . . . . . . . 151
Main Control Circuit Board Replacement . . . . . . . . . . . . . . . . . . . . . 152
Remove the Main Control Circuit Board. . . . . . . . . . . . . . . . . . . 152
Install the Main Control Circuit Board . . . . . . . . . . . . . . . . . . . . 154
Backplane Circuit Board Replacement . . . . . . . . . . . . . . . . . . . . . . . . . 155
Remove the Backplane Circuit Board . . . . . . . . . . . . . . . . . . . . . . 155
Install the Backplane Circuit Board . . . . . . . . . . . . . . . . . . . . . . . . 156
Fiber-optic Interface Circuit Board Replacement . . . . . . . . . . . . . . . 157
Remove the Fiber-optic Interface Circuit Board. . . . . . . . . . . . . 157
Install the Fiber-optic Interface Circuit Board . . . . . . . . . . . . . . 164
Control Pod Fan Assembly Replacement. . . . . . . . . . . . . . . . . . . . . . . 164
Remove the Control Pod Fan Assembly . . . . . . . . . . . . . . . . . . . . 164
Install the Control Pod Fan Assembly . . . . . . . . . . . . . . . . . . . . . . 166
Control Pod Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Remove the Control Pod. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Install the Control Pod . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 171
Chapter 8
Input Bay Components Input Bay Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 173
IP21/IP54 Roof Vent Filter Replacement . . . . . . . . . . . . . . . . . . . . . . 179
IP54/IP21 Roof Vent Fan Replacement. . . . . . . . . . . . . . . . . . . . . . . . 179
IP54/IP21, 400/600 mm Wide Door Vent Filters Replacement. . 179
Remove the IP54/IP21, 400/600 mm Wide Door Vent
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
Install the IP54/IP21, 400/600 mm Wide Door Vent
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
IP54, 800/1000 mm Wide Door Vent Filters Replacement . . . . . . 180
Remove the IP54, 800/1000 mm Wide Door Vent Filters . . . 180
Install the IP54, 800/1000 mm Wide Door Vent Filters . . . . . 181
6 Rockwell Automation Publication 750-TG100B-EN-P - June 2019
Table of Contents
IP21, 800/1000 mm Wide Door Vent Filter Replacement. . . . . . . 181
Remove the IP21, 800/1000 mm Wide Door Vent Filter . . . . 181
Install the IP21, 800/1000 mm Wide Door Vent Filter . . . . . . 182
IP54/IP21, 1000 mm Wide Door Vent Fan Replacement . . . . . . . 182
Remove the IP54/IP21, 1000 mm Wide Door Vent Fan. . . . . 182
Install the IP21/IP54, 1000 mm Wide Door Vent Fan . . . . . . 183
Guard Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
Remove the Guards. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
Install the Guards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
AC Precharge Control Circuit Board Replacement . . . . . . . . . . . . . 186
Remove the AC Precharge Control Circuit Board. . . . . . . . . . . 186
Install the AC Precharge Control Circuit Board . . . . . . . . . . . . 189
AC Precharge Time Delay Relay Replacement . . . . . . . . . . . . . . . . . . 189
Remove the AC Precharge Time Delay Relay . . . . . . . . . . . . . . . 189
Install the AC Precharge Time Delay Relay . . . . . . . . . . . . . . . . . 190
AC Precharge TVSS Module Replacement . . . . . . . . . . . . . . . . . . . . . 190
Remove the AC Precharge TVSS Module . . . . . . . . . . . . . . . . . . 190
Install the AC Precharge TVSS Module . . . . . . . . . . . . . . . . . . . . 192
AC Precharge Control Circuit Board Fuses (FH1) Replacement . 192
Remove the AC Precharge Control Circuit Board Fuses . . . . . 192
Install the AC Precharge Control Board Fuses . . . . . . . . . . . . . . 193
240V Power Distribution Fuse (FH2) Replacement. . . . . . . . . . . . . 194
Remove the 240V Power Distribution Fuse. . . . . . . . . . . . . . . . . 194
Install the 240V Power Distribution Fuse . . . . . . . . . . . . . . . . . . 195
Roof Fan 240V Control Power Fuse (FH3) Replacement. . . . . . . . 195
Remove the Roof Fan 240V Control Power Fuse. . . . . . . . . . . . 195
Install the Roof Fan 240V Control Power Fuse . . . . . . . . . . . . . 196
Control Transformer Fuses (FH4…FH7) Replacement. . . . . . . . . . 197
Remove the Control Transformer Fuses. . . . . . . . . . . . . . . . . . . . 197
Install the Control Transformer Fuses. . . . . . . . . . . . . . . . . . . . . . 198
AC Precharge Fused Disconnect (FD1) Fuses Replacement. . . . . . 199
Remove the AC Precharge Fused Disconnect Fuses. . . . . . . . . . 199
Install the AC Precharge Fused Disconnect Fuses . . . . . . . . . . . 200
Control Transformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
Chapter 9
Power Bay Components Power Bay Kits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
IP54 Exhaust Vent Filters Replacement . . . . . . . . . . . . . . . . . . . . . . . . 211
Remove the IP54 Exhaust Vent Filters . . . . . . . . . . . . . . . . . . . . . 211
Install the IP54 Exhaust Vent Filters . . . . . . . . . . . . . . . . . . . . . . . 211
IP54 Exhaust Fan Fuse Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . 212
Remove the IP54 Exhaust Fan Fuse . . . . . . . . . . . . . . . . . . . . . . . . 212
Install the IP54 Exhaust Fan Fuse . . . . . . . . . . . . . . . . . . . . . . . . . . 213
IP54 Exhaust Fan Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
Remove the IP54 Exhaust Fan . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 214
Install the IP54 Exhaust Fan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 219
Rockwell Automation Publication 750-TG100B-EN-P - June 2019 7
Table of Contents
IP54, 400/600 mm Wide Door Vent Filters Replacement . . . . . . . 220
Remove the IP54, 400/600 mm Wide Door Vent Filters. . . . . 220
Install the IP54, 400/600 mm Wide Door Vent Filters . . . . . . 220
IP21 400/600 mm Wide Door Vent Filter Replacement. . . . . . . . . 221
Remove the IP21, 400/600 mm Wide Door Vent Filter . . . . . 221
Install the IP21, 400/600 mm Wide Door Vent Filter . . . . . . . 222
IP54, 800 mm Wide Door Vent Filters Replacement . . . . . . . . . . . . 222
IP21, 800 mm Wide Door Vent Filter Replacement. . . . . . . . . . . . . 222
DC Precharge Module Disconnect Handle and Shaft
Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
Remove the DC Precharge Module Disconnect Handle
and Shaft . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
Install the DC Precharge Module Disconnect Handle
and Shaft . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224
DC Precharge Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 224
Remove the DC Precharge Module from the Enclosure . . . . . . 224
Install the DC Precharge Module in the Enclosure . . . . . . . . . . 228
DC Precharge Circuit Board Replacement . . . . . . . . . . . . . . . . . . . . . 229
Remove the DC Precharge Circuit Board. . . . . . . . . . . . . . . . . . . 229
Install the DC Precharge Circuit Board . . . . . . . . . . . . . . . . . . . . 232
DC Precharge Fuses Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
Remove the DC Precharge Fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . 233
Install the DC Precharge Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
Guard Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Remove the Guard. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Install the Guard . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Power Module Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
Remove the Power Module from the Enclosure . . . . . . . . . . . . . 236
Install the Power Module in the Enclosure. . . . . . . . . . . . . . . . . . 241
DC Link Fuses Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
Remove the DC Link Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 242
Install the DC Link Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 243
Power Module PE-B1 Power Jumper Replacement. . . . . . . . . . . . . . 243
Remove the Power Module PE-B1 Power Jumper . . . . . . . . . . . 243
Install the Power Module PE-B1 Power Jumper . . . . . . . . . . . . . 244
Circuit Board Tray Removal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
Remove the Circuit Board Tray. . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
Install the Circuit Board Tray . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
Power Layer Interface Circuit Board Replacement . . . . . . . . . . . . . . 249
Remove the Power Layer Interface Circuit Board. . . . . . . . . . . . 249
Install the Power Layer Interface Circuit Board . . . . . . . . . . . . . 250
Power Interface Circuit Board Replacement . . . . . . . . . . . . . . . . . . . . 250
Remove the Power Interface Circuit Board . . . . . . . . . . . . . . . . . 251
Install the Power Interface Circuit Board
. . . . . . . . . . . . . . . . . . . 252
Balance Resistors Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
Remove the Balance Resistors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
Install the Balance Resistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 254
8 Rockwell Automation Publication 750-TG100B-EN-P - June 2019
Table of Contents
Current Sensors Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
Remove the Current Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
Install the Current Sensors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256
LCL Filter Module Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
Remove the LCL Filter Module from the Enclosure . . . . . . . . . 257
Install the LCL Filter Module in the Enclosure. . . . . . . . . . . . . . 262
AC Input Link Fuses Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262
Remove the AC Input Link Fuses. . . . . . . . . . . . . . . . . . . . . . . . . . 263
Install the AC Input Link Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . 264
LCL Filter Capacitor Assembly Replacement. . . . . . . . . . . . . . . . . . . 264
Remove the LCL Filter Capacitor Assembly . . . . . . . . . . . . . . . . 264
Install the LCL Filter Capacitor Assembly. . . . . . . . . . . . . . . . . . 267
AC Common Mode Filter Circuit Board Replacement. . . . . . . . . . 268
Remove the AC Common Mode Filter Circuit Board . . . . . . . 268
Install the AC Common Mode Circuit Board. . . . . . . . . . . . . . . 270
Current Sense Circuit Board Replacement . . . . . . . . . . . . . . . . . . . . . 270
Remove the Current Sense Circuit Board. . . . . . . . . . . . . . . . . . . 271
Install the Current Sense Circuit Board . . . . . . . . . . . . . . . . . . . . 274
Power/LCL Filter Module Heatsink Fan Fuse Replacement . . . . . 275
Remove the Power/LCL Filter Module Heatsink Fan Fuse. . . 275
Install the Power/LCL Filter Module Heatsink Fan Fuse . . . . 276
Power/LCL Filter Module Heatsink Fan Assembly
Replacement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276
Remove the Power or LCL Filter Module Heatsink Fan
Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 276
Install the Power or LCL Filter Module Heatsink Fan
Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 277
Torque Accuracy Module Replacement . . . . . . . . . . . . . . . . . . . . . . . . 277
Remove the Torque Accuracy Module . . . . . . . . . . . . . . . . . . . . . 277
Install the Torque Accuracy Module . . . . . . . . . . . . . . . . . . . . . . . 279
DC Bus Conditioner Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . 279
Remove the DC Bus Conditioner. . . . . . . . . . . . . . . . . . . . . . . . . . 279
Install the DC Bus Conditioner . . . . . . . . . . . . . . . . . . . . . . . . . . . 282
Wire Entry/Exit Bay Components
Chapter 10
Wire Entry/Exit Bay Kits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 283
IP54/IP21, 400 mm Wide Door Vent Filters Replacement . . . . . . 285
IP54/IP21, 800 mm Wide Door Vent Filters Replacement . . . . . . 285
IP54/IP21, 400/800 mm Wide Door Vent Fan and Filter
Assembly Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 285
Remove the IP54/IP21, 400/800 mm Wide Door Vent Fan
and Filter Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 285
Install the IP54/IP21, 400/800 mm Wide Door Vent Fan
and Filter Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 286
Thermal Switch Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 287
Remove the Thermal Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 287
Install the Thermal Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 289
Rockwell Automation Publication 750-TG100B-EN-P - June 2019 9
Table of Contents
Chapter 11
Start Up After Repairs Before You Apply Power to the Drive. . . . . . . . . . . . . . . . . . . . . . . . . . 291
Frames 5 and 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 292
Frames 7…15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 294
No-load DC Bus Voltage and Output Current Measurements . . . 298
Appendix A
System Schematics List of Schematic Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 299
Index
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 345
10 Rockwell Automation Publication 750-TG100B-EN-P - June 2019

Preface

This manual provides a recommended preventative maintenance schedule, major component test and hardware replacement procedures, and schematic diagrams for PowerFlex® 750-Series products with TotalFORCE™ control.
It is highly recommended that you obtain a copy of the PowerFlex Drives with TotalFORCE Control Programming Manual, publication 750-PM100 Programming Manual contains fault, alarm, and programming information that can help you troubleshoot drive errors and determine if repairs are necessary.
This manual is intended for qualified service personnel responsible for PowerFlex 750-Series products repairs. You must have previous experience with, and an understanding of, electrical terminology, procedures, required equipment, equipment protection procedures and methods, and safety precautions. See safety-related practices that are contained in publication NFPA 70E, Standard for Electrical Safety in the Work Place.
. The

Summary of Changes

Additional Resources

This manual contains new ad updated information
Top ic Pag e
Updated the steps to Remove Power from the System to include information for frames 5, 6, and 7. 15
Updated the Recommended Preventative Maintenance schedules to include the following information:
• Components and preventative maintenance parameters for frames 5, 6, and 7
• Preventative maintenance parameters for frames 13…15 components
Updated the Component Inspection and Test Procedures chapter to include information for frames 5, 6, and 7.
Added Chapter 4
Added Chapter 5 for frame 6 product parts replacement. 75
Added Chapter 6 for frame 7 product parts replacement. 97
Added procedures for frames 5, 6, and 7 to the Start Up After Repairs chapter. 291
Added schematic diagrams for frames 5, 6, and 7 products. 299
for frame 5 product parts replacement. 55
27
45
These documents contain additional information concerning related products from Rockwell Automation.
Resource Description
AC Drives Common Bus Application Techniques, publication
750-AT004
Drives in Common Bus Configurations with PowerFlex 755TM Bus Supplies Application Techniques, publication
DRIVES-AT005
PowerFlex 755T Flux Vector Tuning, publication 750-AT006
Provides basic information to properly wire and ground common bus PWM AC drives.
Provides basic information to properly wire and ground the following products in common bus applications:
• PowerFlex 755TM drive system for common bus solutions
• PowerFlex 750-Series AC and DC input drives
• Kinetix® 5700 servo drives
Provides guidance on how to tune Flux Vector position and velocity loops, filters, and other features to achieve the level of performance that is required for a given application. This publication is intended for novice drives users and users with advanced skills.
Rockwell Automation Publication 750-TG100B-EN-P - June 2019 11
Preface
Resource Description
PowerFlex 750-Series Products with TotalFORCE Control Installation Instructions, publication 750-IN100
PowerFlex 755TM AC Precharge Modules Unpacking and Lifting Instructions, publication 750-IN102
PowerFlex 755TM DC Precharge Modules Unpacking and Lifting Instructions, publication 750-IN103
PowerFlex 755TM Power and Filter Modules Unpacking and Lifting Instructions, publication 750-IN104
PowerFlex 750-Series Service Cart and DCPC Module Lift Installation Instructions, publication 750-IN105
PowerFlex 755TM Power and Filter Module Storage Hardware Installation Instructions, publication 750-IN106
PowerFlex 755T Module Service Ramp Instructions, publication 750-IN108
PowerFlex 750-Series I/O, Feedback, and Power Option Modules Installation, publication 750-IN111
PowerFlex 755T Frames 5 and 6 Conduit Box and Ground Plate Kits, Installation Instructions, publication 750-IN112
PowerFlex 755T Frames 5 and 6 Marine Discharge Kits, Installation Instructions, publication 750-IN114
PowerFlex Drives with TotalFORCE Control Programming Manual, publication 750-PM100
PowerFlex 750-Series Products with TotalFORCE Control Reference Manual, publication 750-RM100
PowerFlex 750-Series Products with TotalFORCE Control Technical Data, publication 750-TD100
PowerFlex 750-Series Safe Speed Monitor Option Module Safety Reference Manual, publication 750-RM001
PowerFlex 750-Series Safe Torque Off Option Module User Manual, publication 750-UM002
PowerFlex 750-Series ATEX Option Module User Manual, publication 750-UM003
Industry Installation Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-AT003
Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives, publication DRIVES-IN001
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control, publication SGI-1.1
Product Certifications website, http://
www.rockwellautomation.com/global/certification/ overview.page
Provides the basic steps to install PowerFlex 755TL drives, PowerFlex 755TR drives, and PowerFlex 755TM bus supplies.
These publications provide detailed information on:
• Component weights
• Precautions and recommendations
• Hardware attachment points
• Lifting the component out of the packaging
Provides detailed set-up and operating instructions for the module service car t and lift extension option.
Provides detailed installation and usage instructions for this hardware a ccessory.
Provides detailed usage instructions for the module service ramp.
Provides instructions to install and wire 750-Series option modules.
Provides installation instructions for the field-installed frame 5 and 6 conduit box and ground plate option kits.
Provides installation instructions for the field-installed frame 5 and 6 marine discharge option kits.
Provides detailed information on:
• I/O, control, and feedback options
• Parameters and programming
• Faults, alarms, and troubleshooting
Provides detailed setup and programming instructions for common applications.
Provides detailed information on:
• Drive and bus supply specifications
• Option specifications
• Fuse and circuit breaker ratings
These publications provide detailed information on installation, set-up, and operation of the 750-Series safety option modules.
Provides basic information on enclosure systems, considerations to help protect against environmental contaminants, and power and grounding considerations for installing Pulse Width Modulated (PWM) AC drives.
Provides basic information to properly wire and ground PWM AC drives.
Provides general guidelines for installing a Rockwell Automation industrial system.
Provides general guidelines for the application, installation, and maintenance of solid-state control.
Provides declarations of conformity, certificates, and other certification details.
You can view or download publications at
http://www.rockwellautomation.com/global/literature-library/overview.page
12 Rockwell Automation Publication 750-TG100B-EN-P - June 2019
.
Chapter 1
Before You Begin Tests, Maintenance, or Repairs
Top ic Pa ge
Product Ad visories 14
Remove Power from the System 15
Commonly Used Tools 22
Hardware Instal lation Diagrams 23
Fastener Torque Sequences 24
Read the information in this chapter before you begin tests, maintenance, or repairs on drive components.
IMPORTANT Once the product is connected to a power supply, always verify that system
power is not present before performing any work on the product. See safety­related practices that are contained in publication NFPA 70E, Standard for Electrical Safety in the Work Place.
Rockwell Automation Publication 750-TG100B-EN-P - June 2019 13
Chapter 1 Be fo re You B eg in Tes ts , M ai nt en an ce , or Re pa ir s

Product Advisories

Read the following precautions before you begin to test components, perform maintenance, or repair the drive.

Qualified Personnel

ATT EN TI ON : Only qualified personnel familiar with PowerFlex® 755T products
and associated machinery should plan or implement the installation, start-up and subsequent maintenance of the system. Failure to comply can result in personal injury and/or equipment damage.

Personal Safety

ATT EN TI ON : To avoid an electric shock hazard, verify that the voltage on the
bus capacitors has discharged before servicing.
Frames 5 and 6: Measure the DC bus voltage at the power terminal block by measuring between the +DC and –DC terminals. Also, measure between the +DC terminal and the chassis, and between the –DC terminal and the chassis. The voltage must be zero for all three measurements. See Frames 5 and 6 in the Remove Power from the System section on page 15
Frames 7…15: Measure the DC bus voltage by measuring between the +DC and –DC testpoint sockets on the front of the power module. Also measure between the +DC testpoint and chassis GND, and the –DC testpoint and chassis GND. See Frames 7…15 in the Remove Power from the System section on page 17 locations.
for locations.
for
ATT EN TI ON : Potentially fatal voltages can result from improper usage of an oscilloscope and other test equipment. The oscilloscope chassis can be at a potentially fatal voltage if not properly grounded. If an oscilloscope is used to measure high-voltage waveforms, use only a dual channel oscilloscope in the differential mode with X 100 probes. It is recommended that the oscilloscope is used in the A minus B Quasi-differential mode and the oscilloscope chassis is grounded to an earth ground.

Product Safety

ATT EN TI ON : This drive contains ESD (Electrostatic Discharge) sensitive parts
and assemblies. Static control precautions are required when you install, test, service, or repair this assembly. Component damage can result if ESD control procedures are not followed.

Class 1 Light-emitting Diode Product

ATT EN TI ON : Hazard of permanent eye damage exists when using optical
transmission equipment. This product emits intense light and invisible radiation. Do not look into module ports or fiber-optic cable connectors.
14 Rockwell Automation Publication 750-TG100B-EN-P - June 2019
Before You Begin Tests, Maintenance, or Repairs Chapter 1

Remove Power from the System

Follow the appropriate procedures to remove power from the dive system. Instructions for frames 7…15 begin on page 17
.

Frames 5 and 6

The following procedures must be followed before attempting to service any part of a frame 5 and 6 drive or frame 6 bus supply.
WARNING: Remove power before you remove or make cable connections. When you remove or insert a cable connector with power applied, an electric arc can occur. An electric arc can cause personal injury or property damage in theses ways:
• An electric arc can send an erroneous signal to system field devices, which can cause unintended machine motion
• An electric arc can cause an explosion in a hazardous environment
Electric arcs cause excessive wear to contacts on both the module and its mating connector. Worn contacts can create electrical resistance.
1. Turn off and lockout all input power, including any external power sources.
2. Wait 15 minutes.
3. For frame 5 drives, if the conduit box is present, remove the M6 x 12 mm
torx screw that secures the conduit box cover to the chassis and remove the cover.
4. For frame 6 drives or bus supplies, complete these steps: a. Remove the cover. See Remove the Cover from the Chassis on page 76 b. If the conduit box is present, loosen the four M6 captive torx screws
that secure the cover to the conduit box and remove the cover.
5. Measure the AC input and DC bus voltage to verify that there is no voltage present (see Figure 1 on page 16
• Measure the AC input terminals R/L1, S/L2, and T/L3, L to L and L
to chassis GND (PE).
• Measure the DC output terminals DC+ and DC–, DC+ to DC–,
DC+ to chassis GND (PE), and DC– to chassis GND (PE).
for terminal identification):
on page 16 for terminal locations and Ta b l e 1
.
Rockwell Automation Publication 750-TG100B-EN-P - June 2019 15
Chapter 1 Be fo re You B eg in Tes ts , M ai nt en an ce , or Re pa ir s
21 543
Frame 5 (Shown with Cover Removed for Clarity Only) Frame 6
1 2 3 4 5
Figure 1 - Frame 5 and 6 Drives
Table 1 - Frame 5 and 6 Terminal Identification
Item Name Description Item Name Description
1 PE grounding stud Termination point to chassis ground for AC line
2 R/L1, S/L2, T/L3 AC line input power terminals 5 PE grounding stud Termination point to chassis ground for motor shield
3 DC+, DC– DC bus terminals
16 Rockwell Automation Publication 750-TG100B-EN-P - June 2019
shield
4 U/T1, V/T2, W/T3 AC output motor terminals
Before You Begin Tests, Maintenance, or Repairs Chapter 1

Frames 7…15

The following procedures must be followed before attempting to service any part of the drive system.
WARNING: Remove power before you remove or make cable connections. When you remove or insert a cable connector with power applied, an electric arc can occur. An electric arc can cause personal injury or property damage in theses ways:
• An electric arc can send an erroneous signal to system field devices, which can cause unintended machine motion
• An electric arc can cause an explosion in a hazardous environment
Electric arcs cause excessive wear to contacts on both the module and its mating connector. Worn contacts can create electrical resistance.
1. Turn off and lockout all input power, including any external power sources (such as an Active Front End or other DC power source).
ATT EN TI ON : To avoid an electric shock hazard when servicing the drive, a means for lockout/tagout of the external, single-phase 120/240V power source and, if present, external 120V uninterruptible power supply source, must be provided.
2. If present, turn off and lockout any external, single-phase 120/240V power source.
3. For regenerative drives and bus supplies, complete steps a…e. a. On the input bay, turn the AC precharge disconnect switch to the
“Off ” position. b. Wait 15 minutes. c. Open the enclosure door. d. Close and lock the hasp on the circuit breaker. e. Lock the fused disconnect switch.
Rockwell Automation Publication 750-TG100B-EN-P - June 2019 17
Chapter 1 Be fo re You B eg in Tes ts , M ai nt en an ce , or Re pa ir s
Frame 9, IP21 UL Type 1 Input Bay Shown
4. For common bus inverters with DC precharge, complete steps a…e: a. Turn the DC precharge disconnect switch to the “Off” position. a. Wait 15 minutes. b. Open the enclosure door. c. Close and lock the hasp on the molded case switch. d. Lock the fused disconnect switch. e. If a control bay is used, turn the selector switch to the “Off” position
and lock the switch.
ATT EN TI ON : To avoid an electric shock hazard, verify that there is no AC input and DC bus voltage before servicing by taking these measurements:
• Verify that there is no AC input voltage present using the R/L1, S/L2, and T/L3 test point sockets in the input bay by measuring L to L and L to GND.
• Verify that there is no AC input voltage present using the R, S, and T testpoint sockets in the input bay by measuring L to L and L to GND.
• Verify that there is no DC bus voltage present using the +DC to –DC testpoints in the input bay by measuring +DC to –DC, +DC to GND, and –DC to GND.
5. For regenerative drives and bus supplies, measure the AC input and DC bus voltage at the following testpoint sockets in the input bay to verify that there is no voltage present:
• Using the circuit breaker output (CB1 SEC) testpoints R/L1, S/L2,
and T/L3, measure L to L and L to chassis GND.
• By using the fused disconnect output (FD1 SEC) testpoints R, S, and
T, measure L to L and L to chassis GND.
• By using the DC bus testpoints +DC and –DC, measure +DC to
–DC, +DC to chassis GND, and –DC to chassis GND.
18 Rockwell Automation Publication 750-TG100B-EN-P - June 2019
Before You Begin Tests, Maintenance, or Repairs Chapter 1
Frames 8…15 Power Module
ATT EN TI ON : To avoid an electric shock hazard, verify that the voltage on the bus capacitors has discharged completely before servicing. Verify that there is no DC bus voltage present using the +DC to –DC testpoints on all power modules by measuring +DC to –DC, +DC to GND, and –DC to GND.
6. For common bus inverters, by using the DC bus testpoints +DC and –DC on the front of the power modules, measure the DC bus voltage of all power modules and verify that there is no voltage present on the bus capacitors. Measure +DC to –DC, +DC to chassis GND, and –DC to chassis GND.
Rockwell Automation Publication 750-TG100B-EN-P - June 2019 19
Chapter 1 Be fo re You B eg in Tes ts , M ai nt en an ce , or Re pa ir s
AC Precharge Circuit Breaker
Frame 10 Input Bay Shown AC Precharge Circuit Breaker
7. Measure the 240V AC control voltage at the appropriate terminals:
• For frame 7 drives and bus supplies, measure terminals L and N on
terminal block TB3.
• For frames 8…15 drives and bus supplies, in the input bay, measure
terminals L and N on terminal block TB2.
20 Rockwell Automation Publication 750-TG100B-EN-P - June 2019
Before You Begin Tests, Maintenance, or Repairs Chapter 1
• For control bays, measure terminal L at FH2-2 and terminal N at
terminal block TB4.
Rockwell Automation Publication 750-TG100B-EN-P - June 2019 21
Chapter 1 Be fo re You B eg in Tes ts , M ai nt en an ce , or Re pa ir s

Commonly Used Tools

Ta b l e 2 includes the tools that are needed for test measurements, basic
maintenance, and service repairs.
IMPORTANT Care must be taken to be sure that tools and/or hardware components do not
fall into open drive assemblies. Do not energize the drive unless all loose tools and/or hardware components have been removed from the drive assemblies and enclosure.
Table 2 - Service Tools
Tool Description Details
Allen socket wrench 3 mm
Box wrench 7 mm, 8 mm, 10 mm, 13 mm, 15 mm, 17 mm, 19 mm, 22 mm
Crimp tools For cable terminals 1.5...240
Current clamp 1000 A (AC, rms), signal output
ESD-protected place of work Work surface, Floor cover, seat, and ground connections
ESD-protective clothing Wrist wrap, shoes, overall clothing (coat)
Flash light
Flat-nose screwdriver 3 mm (0.12 in.), 5 mm (0.19 in.), 6.4 mm (0.25 in.)
Torx, star, or hexalobular screw driver/bit
Hexagonal socket wrench 2.5 mm, 7 mm, 8 mm, 10 mm, 12 mm, 13 mm, 17 mm, 18 mm
Insulation tester 1000V DC
Level
Lift strap 5/16 in. J-hook style, 24 in. long, 1000 lb. Minimum
Multi-meter Digital multi-meter, capable of AC and DC voltage, continuity, resistance,
Nose pliers
Oscilloscope Portable, digitizing, dual channel scope, with isolation
Phillips screwdriver/bit #1, #2
Module service cart The optional module service cart (20-750-MCART1) is recommended to handle
Module storage hardware Module storage hardware (20-750-MINV-ATIP) helps to stabilize power and filter
Torque wrench 1...12 N
Torque wrench 6...50 N
Wire c utter
#15, #20, #25, #30, #40, #45
capacitance measurements, and forward diode bias tests. Fluke model 87 III or equivalent.
and transport power and filter modules.
modules during temporary storage after removal.
m (8.8…106 lbin)
m (53…443 lbin)

Software Tools

Connected Components Workbench™ software is an application that can be used to upload and download parameter configuration and monitor system parameters. Connected Components Workbench version 10.xx or later is required for use with PowerFlex 755T products.
22 Rockwell Automation Publication 750-TG100B-EN-P - June 2019
Before You Begin Tests, Maintenance, or Repairs Chapter 1
Fastener Type
Flat-head screw
Hexagonal bolt
Hexagonal nut or standoff
Hexagonal screw
Tor x s cre w
Phillips screw
Pozid riv scre w
Slotted tor x screw
Sequence Number
1
M4 x 10 mm T20 or F - 6.4 mm (0.25 in.)
4.8 N
m (42 lbin)
Tool Type and Size
FFlat-nose screwdriver Px Phillips screwdriver/bit and size PZx Pozidriv screwdriver/bit and size Txx Torx screwdriver/bit and size xx mm Hexagonal socket wrench
Final Assembly Torque
Fastener Size

Hardware Installation Diagrams

The disassembly illustrations throughout this manual contain diagrams (as shown here) that identify the following: corresponding sequence number (if necessary), type of fastener, fastener size, tool type and size, and final assembly torque.
Rockwell Automation Publication 750-TG100B-EN-P - June 2019 23
Chapter 1 Be fo re You B eg in Tes ts , M ai nt en an ce , or Re pa ir s
1
2
Initial Sequence
1
2
12
Final Sequence
1
2
3
4
3 4
Initial Sequence
1
2
1
234
Final Sequence

Fastener Torque Sequences

The following illustrates initial and final tightening sequences for components that are fastened to a heat sink by using two, four, and six screws. Initial torque is 1/3 (33%) of final torque, except six-point mountings, which require 0.7 N (6 lb Drive components do not contain these labels.
Figure 2 - Two-point Mounting
ATT EN TI ON : When mounting components to a drive heat sink, component
fastener torque sequences and tolerances are crucial to component-to-heat sink heat dissipation.
Components can be damaged if initial tightening procedure is not performed to specification.
m
in) initial torque. The numeric illustration labels are for your assistance.
Figure 3 - Four-point Mounting
24 Rockwell Automation Publication 750-TG100B-EN-P - June 2019
Figure 4 - Six-point Mounting
6 42
3 51
3 4
Initial Sequence
1 2 65
Final Sequence
3 41 2 65
Do not exceed 0.7 Nm (6 lbin) on initial torque of all six screws.
Before You Begin Tests, Maintenance, or Repairs Chapter 1
Rockwell Automation Publication 750-TG100B-EN-P - June 2019 25
Chapter 1 Be fo re You B eg in Tes ts , M ai nt en an ce , or Re pa ir s
Notes:
26 Rockwell Automation Publication 750-TG100B-EN-P - June 2019
Chapter 2
Preventative Maintenance
Top ic Pag e
Recommended Preventative Maintenance 27
Predictive Maintenance 28
Schedule Codes Explanation 28
Shock Events 41
Maintenance of Industrial Control Equipment 42
This chapter provides information on preventative maintenance for components that can affect the life and operational characteristics of PowerFlex® 750-Series products with TotalFORCE® Control.

Recommended Preventative Maintenance

Rockwell Automation recognizes that following a defined maintenance schedule delivers the maximum product availability. By strictly following the maintenance schedule of tasks that is provided for your operating environment, you can expect the highest possible uptime. A maintenance schedule is provided for each of these environments:
Ta b l e 3
Ta b l e 4
Ta b l e 5
IMPORTANT Duty cycle and load profile can greatly affect the reliability of PowerFlex
Recommended Maintenance Schedule for Normal Operation on page 29 ambient temperature is less than or equal to 40 °C (104 °F).
Operation on page 33 environment where the ambient temperature is above 41 °C (106 °F).
Operation on page 37 reactivity level greater than 1000 angstroms per 30 days exposure. No condensation allowed. Maximum allowable humidity is 60% in the presence of corrosive gases. See ISA-71.04-2013 for details on how to measure reactivity levels on copper and silver test coupons.
. Normal operation is defined as an environment where the
Recommended Maintenance Schedule for High Temperature
. High temperature operation is defined as an
Recommended Maintenance Schedule for Harsh Environment
. Harsh environment is defined as a copper or silver
750-Series Products with TotalFORCE Control.
Rockwell Automation Publication 750-TG100B-EN-P - June 2019 27
Chapter 2 Preventative Maintenance
An annual preventative maintenance program includes the following primary tasks:
• A visual inspection of all components accessible from the front of the Module
• Resistance checks on the power components
• Power-supply voltage level checks
• General cleaning and maintenance
• Tightness checks on all accessible power connections

Predictive Maintenance

Schedule Codes Explanation

See Chapter 3 - Component Inspection and Test Procedures on page 45
for
additional information on how to perform inspections and tests.
PowerFlex 750-Series Products with TotalFORCE Control contain algorithms for predictive maintenance that are used to improve the “uptime” of machines, processes, and facilities. These algorithms monitor the lifespan of certain components and display the calculated value in specific parameters. These algorithms can be used to alert personnel when the components are nearing the end of their lifespan so the components can be replaced before they fail. The shaded rows in Ta b l e 3
Ta b l e 5 on pages 2937, respectively, identify the components with predictive maintenance parameters. Use the predictive maintenance parameters to determine a replacement schedule for the applicable components. See Predictive Maintenance in the PowerFlex 750-Series Products with TotalFORCE Control Reference Manual, publication 750-RM100
, for
more information.
IMPORTANT Failure to address predictive maintenance alarms can cause unexpected
downtime or premature product failure.
The codes that are listed in this table are used to identify the task that is associated with the components that are identified in the tables on pages 29
Code Task Description
I Inspect Inspect the component for signs of excessive accumulation of dust, dirt, or external
damage. For example, inspect the filters/fan inlet screens for debris that can block the airflow path.
C Clean Clean the components that can be reused, specifically the door-mounted air filters
and fan inlet screens.
M Maintain This type of maintenance task can include an inductance test of line reactors/DC
links, or a full test of an isolation transformer, and so on.
R Replace This component has reached its mean operational life. Replace the component to
decrease the chance of failure. It is likely that components can exceed the designed life in the drive, but component life is dependent on many factors such as usage and heat.
Use the predictive maintenance parameters to determine a replacement schedule for components in shaded table rows.
Rv Review A discussion with Rockwell Automation personnel is recommended to help
determine whether any of the enhancements/changes made to the drive hardware and control could benefit the application.
37.
28 Rockwell Automation Publication 750-TG100B-EN-P - June 2019
Preventative Maintenance Chapter 2
RR
I I I I I I I I I I I I I I I I I I I I
Maintenance
Parameters
Grease Power Stabs -
Frames 8… 15 onlyRBalance Resistors -
Frames 8… 15 only
Power Mod ules,
Years > 01234567891011121314151617181920
Table 3 - Recommended Maintenance Schedule for Normal Operation
Module/Activity Component Predictive
Frames 7…15
340, 440, 540, 640,
740, 840, 940, 1040
Port 12 /14: 143, 243,
343, 443, 543, 643,
743, 843, 943, 1043
(cat. no. SK-RM-INVBRn-F8M)
IGBTs Port 12 /14: 140, 240,
Bus Capacitors (cat. no.
SK-RM-ICP1-xnnnxnnn)
Power Laye r Interf ace Circuit Board
(cat. no. SK-RM-PLI1-F7,
SK-RM-PLI1-F8)RPower Interface Circuit Board
(cat. no. SK-RM-PIBn-xnnnxnnn,
SK-RM-PIB4-xnnnxnnn)RGate Driver Circuit Board -
Frames 8… 15 onlyRHeat Sink Fan (cat. no.
Port 12 /14: 136, 236,
336, 436, 536, 636,
736, 836, 936, 1036
IGBTs Port 12 /14: 140
Power Feedbac k Circuit B oard
SK-RM-INVFAN1-F8,
SK-RM-MFAN-F7)
(cat. no. SK-RM-PFB-F5-F6)RFan Power Supply Circuit Board
Power Components,
Frames 5 and 6
(cat.no. SK-RM-PSB1-F5-F6)RStirring Fan - Frames 5 and 6 (cat.
Port 14: 128 I I I I I I I I I I I I I I I I I I I I
no.
SK-RM-MFAN1-F5,
SK-RM-MFAN1-F6)
I I I I I I I I I I I I I I I I I I I I
Port 14: 136
Heat Sink Fan (cat. no.
SK-RM-HSFAN1-F5,
SK-RM-HSFAN1-F6)
Rockwell Automation Publication 750-TG100B-EN-P - June 2019 29
Chapter 2 Preventative Maintenance
R R
R
RR
I I I I I I I I I I I I I I I I I I I I
Port 14: 1250, 1450,
1550, 1650, 1750,
Maintenance
Parameters
Grease Power Stabs -
Frames 8… 15 onlyRCapacitors
LCL Filter Modules,
Years > 01234567891011121314151617181920
Table 3 - Recommended Maintenance Schedule for Normal Operation (Continued)
Module/Activity Component Predictive
Frames 7…15
1850, 1950, 2150
(cat. no. SK-RM-LCLCPn-F8M)
Current Sense Circuit Board
(cat. no. SK-RM-CSB1-nnn,
SK-RM-CSB-F7)RAC Common Mode Filter Board -
Frames 8… 15 only
(cat. no. SK-RM-EMCFB1)
Port 14: 1246, 1346,
Heat Sink Fan (cat. no.
1546, 1646, 1746,
SK-RM-INVFAN1-F8,
1846, 1946, 2146
Port 14: 1250 R R
SK-RM-MFAN-F7)
LCL Filter Capacitor (cat. no.
SK-RM-LCLCP4-F5,
SK-RM-LCLCP6-F5,
SK-RM-LCLCP4-F6,
SK-RM-LCLCP6-F6)
Main Circuit Breaker (CB1) Port 14: 1143, 1153
Time Delay Relay (cat. no.
20-750-MACPC-TDR)
AC Precharge Circuit Board (c at. no.
20-750-MACPC1-xx,
LCL Fi lter
Components, Frames
5 and 6
AC Precharge Module,
20-750-MACPC1-xx-F7M)RPrecharge Contactor (M1) Port 14: 1146, 1156
Frames 7…15
Grease Power Stabs R
DC Precharge Module,
DC Prech arge Circuit B oard
Frames 8…15
(cat. no. SK-RM-DCPC1-xx)RMolded Case Switch (CB1) Port 12: 145, 245, 345,
445, 545, 645, 745,
845, 945, 1045
30 Rockwell Automation Publication 750-TG100B-EN-P - June 2019
Loading...
+ 322 hidden pages