PowerFlex 750-Series Products with TotalFORCE Control
Catalog Numbers 20G, 20J
Important User Information
Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are
required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may
be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from
the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous
environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
IMPORTANTIdentifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
10Rockwell Automation Publication 750-TG100B-EN-P - June 2019
Preface
This manual provides a recommended preventative maintenance schedule, major
component test and hardware replacement procedures, and schematic diagrams
for PowerFlex® 750-Series products with TotalFORCE™ control.
It is highly recommended that you obtain a copy of the PowerFlex Drives with
TotalFORCE Control Programming Manual, publication 750-PM100
Programming Manual contains fault, alarm, and programming information that
can help you troubleshoot drive errors and determine if repairs are necessary.
This manual is intended for qualified service personnel responsible for PowerFlex
750-Series products repairs. You must have previous experience with, and an
understanding of, electrical terminology, procedures, required equipment,
equipment protection procedures and methods, and safety precautions. See
safety-related practices that are contained in publication NFPA 70E, Standard for
Electrical Safety in the Work Place.
. The
Summary of Changes
Additional Resources
This manual contains new ad updated information
Top icPag e
Updated the steps to Remove Power from the System to include information for frames 5, 6, and 7.15
Updated the Recommended Preventative Maintenance schedules to include the following
information:
• Components and preventative maintenance parameters for frames 5, 6, and 7
• Preventative maintenance parameters for frames 13…15 components
Updated the Component Inspection and Test Procedures chapter to include information for frames 5,
6, and 7.
Added Chapter 4
Added Chapter 5 for frame 6 product parts replacement.75
Added Chapter 6 for frame 7 product parts replacement.97
Added procedures for frames 5, 6, and 7 to the Start Up After Repairs chapter.291
Added schematic diagrams for frames 5, 6, and 7 products.299
for frame 5 product parts replacement.55
27
45
These documents contain additional information concerning related products
from Rockwell Automation.
ResourceDescription
AC Drives Common Bus Application Techniques, publication
750-AT004
Drives in Common Bus Configurations with PowerFlex
755TM Bus Supplies Application Techniques, publication
Provides basic information to properly wire and ground
common bus PWM AC drives.
Provides basic information to properly wire and ground
the following products in common bus applications:
• PowerFlex 755TM drive system for common bus
solutions
• PowerFlex 750-Series AC and DC input drives
• Kinetix® 5700 servo drives
Provides guidance on how to tune Flux Vector position
and velocity loops, filters, and other features to achieve
the level of performance that is required for a given
application. This publication is intended for novice
drives users and users with advanced skills.
Rockwell Automation Publication 750-TG100B-EN-P - June 201911
Preface
ResourceDescription
PowerFlex 750-Series Products with TotalFORCE Control
Installation Instructions, publication 750-IN100
PowerFlex 755TM AC Precharge Modules Unpacking and
Lifting Instructions, publication 750-IN102
PowerFlex 755TM DC Precharge Modules Unpacking and
Lifting Instructions, publication 750-IN103
PowerFlex 755TM Power and Filter Modules Unpacking and
Lifting Instructions, publication 750-IN104
PowerFlex 750-Series Service Cart and DCPC Module Lift
Installation Instructions, publication 750-IN105
PowerFlex 755TM Power and Filter Module Storage
Hardware Installation Instructions, publication 750-IN106
PowerFlex 755T Module Service Ramp Instructions,
publication 750-IN108
PowerFlex 750-Series I/O, Feedback, and Power Option
Modules Installation, publication 750-IN111
PowerFlex 755T Frames 5 and 6 Conduit Box and Ground
Plate Kits, Installation Instructions, publication 750-IN112
Provides the basic steps to install PowerFlex 755TL
drives, PowerFlex 755TR drives, and PowerFlex 755TM
bus supplies.
These publications provide detailed information on:
• Component weights
• Precautions and recommendations
• Hardware attachment points
• Lifting the component out of the packaging
Provides detailed set-up and operating instructions for
the module service car t and lift extension option.
Provides detailed installation and usage instructions for
this hardware a ccessory.
Provides detailed usage instructions for the module
service ramp.
Provides instructions to install and wire 750-Series
option modules.
Provides installation instructions for the field-installed
frame 5 and 6 conduit box and ground plate option kits.
Provides installation instructions for the field-installed
frame 5 and 6 marine discharge option kits.
Provides detailed information on:
• I/O, control, and feedback options
• Parameters and programming
• Faults, alarms, and troubleshooting
Provides detailed setup and programming instructions
for common applications.
Provides detailed information on:
• Drive and bus supply specifications
• Option specifications
• Fuse and circuit breaker ratings
These publications provide detailed information on
installation, set-up, and operation of the 750-Series
safety option modules.
Provides basic information on enclosure systems,
considerations to help protect against environmental
contaminants, and power and grounding
considerations for installing Pulse Width Modulated
(PWM) AC drives.
Provides basic information to properly wire and ground
PWM AC drives.
Provides general guidelines for installing a Rockwell
Automation industrial system.
Provides general guidelines for the application,
installation, and maintenance of solid-state control.
Provides declarations of conformity, certificates, and
other certification details.
12Rockwell Automation Publication 750-TG100B-EN-P - June 2019
.
Chapter 1
Before You Begin Tests, Maintenance, or Repairs
Top icPa ge
Product Ad visories14
Remove Power from the System15
Commonly Used Tools22
Hardware Instal lation Diagrams23
Fastener Torque Sequences24
Read the information in this chapter before you begin tests, maintenance, or
repairs on drive components.
IMPORTANTOnce the product is connected to a power supply, always verify that system
power is not present before performing any work on the product. See safetyrelated practices that are contained in publication NFPA 70E, Standard for
Electrical Safety in the Work Place.
Rockwell Automation Publication 750-TG100B-EN-P - June 201913
Chapter 1Be fo re You B eg in Tes ts , M ai nt en an ce , or Re pa ir s
Product Advisories
Read the following precautions before you begin to test components, perform
maintenance, or repair the drive.
Qualified Personnel
ATT EN TI ON : Only qualified personnel familiar with PowerFlex® 755T products
and associated machinery should plan or implement the installation, start-up
and subsequent maintenance of the system. Failure to comply can result in
personal injury and/or equipment damage.
Personal Safety
ATT EN TI ON : To avoid an electric shock hazard, verify that the voltage on the
bus capacitors has discharged before servicing.
Frames 5 and 6: Measure the DC bus voltage at the power terminal block by
measuring between the +DC and –DC terminals. Also, measure between the +DC
terminal and the chassis, and between the –DC terminal and the chassis. The
voltage must be zero for all three measurements. See Frames 5 and 6 in the
Remove Power from the System section on page 15
Frames 7…15: Measure the DC bus voltage by measuring between the +DC and
–DC testpoint sockets on the front of the power module. Also measure between
the +DC testpoint and chassis GND, and the –DC testpoint and chassis GND. See
Frames 7…15 in the Remove Power from the System section on page 17
locations.
for locations.
for
ATT EN TI ON : Potentially fatal voltages can result from improper usage of an
oscilloscope and other test equipment. The oscilloscope chassis can be at a
potentially fatal voltage if not properly grounded. If an oscilloscope is used to
measure high-voltage waveforms, use only a dual channel oscilloscope in the
differential mode with X 100 probes. It is recommended that the oscilloscope is
used in the A minus B Quasi-differential mode and the oscilloscope chassis is
grounded to an earth ground.
Product Safety
ATT EN TI ON : This drive contains ESD (Electrostatic Discharge) sensitive parts
and assemblies. Static control precautions are required when you install, test,
service, or repair this assembly. Component damage can result if ESD control
procedures are not followed.
Class 1 Light-emitting Diode Product
ATT EN TI ON : Hazard of permanent eye damage exists when using optical
transmission equipment. This product emits intense light and invisible
radiation. Do not look into module ports or fiber-optic cable connectors.
14Rockwell Automation Publication 750-TG100B-EN-P - June 2019
Before You Begin Tests, Maintenance, or RepairsChapter 1
Remove Power from the
System
Follow the appropriate procedures to remove power from the dive system.
Instructions for frames 7…15 begin on page 17
.
Frames 5 and 6
The following procedures must be followed before attempting to service any part
of a frame 5 and 6 drive or frame 6 bus supply.
WARNING: Remove power before you remove or make cable connections.
When you remove or insert a cable connector with power applied, an electric
arc can occur. An electric arc can cause personal injury or property damage in
theses ways:
• An electric arc can send an erroneous signal to system field devices, which can
cause unintended machine motion
• An electric arc can cause an explosion in a hazardous environment
Electric arcs cause excessive wear to contacts on both the module and its mating
connector. Worn contacts can create electrical resistance.
1. Turn off and lockout all input power, including any external power
sources.
2. Wait 15 minutes.
3. For frame 5 drives, if the conduit box is present, remove the M6 x 12 mm
torx screw that secures the conduit box cover to the chassis and remove the
cover.
4. For frame 6 drives or bus supplies, complete these steps:
a. Remove the cover. See Remove the Cover from the Chassis on page 76
b. If the conduit box is present, loosen the four M6 captive torx screws
that secure the cover to the conduit box and remove the cover.
5. Measure the AC input and DC bus voltage to verify that there is no
voltage present (see Figure 1
on page 16
• Measure the AC input terminals R/L1, S/L2, and T/L3, L to L and L
to chassis GND (PE).
• Measure the DC output terminals DC+ and DC–, DC+ to DC–,
DC+ to chassis GND (PE), and DC– to chassis GND (PE).
for terminal identification):
on page 16 for terminal locations and Ta b l e 1
.
Rockwell Automation Publication 750-TG100B-EN-P - June 201915
Chapter 1Be fo re You B eg in Tes ts , M ai nt en an ce , or Re pa ir s
21543
Frame 5 (Shown with Cover Removed for Clarity Only)Frame 6
12345
Figure 1 - Frame 5 and 6 Drives
Table 1 - Frame 5 and 6 Terminal Identification
ItemNameDescriptionItemNameDescription
1PE grounding studTermination point to chassis ground for AC line
2R/L1, S/L2, T/L3AC line input power terminals5PE grounding studTermination point to chassis ground for motor shield
3DC+, DC– DC bus terminals———
16Rockwell Automation Publication 750-TG100B-EN-P - June 2019
shield
4U/T1, V/T2, W/T3AC output motor terminals
Before You Begin Tests, Maintenance, or RepairsChapter 1
Frames 7…15
The following procedures must be followed before attempting to service any part
of the drive system.
WARNING: Remove power before you remove or make cable connections.
When you remove or insert a cable connector with power applied, an electric
arc can occur. An electric arc can cause personal injury or property damage in
theses ways:
• An electric arc can send an erroneous signal to system field devices, which can
cause unintended machine motion
• An electric arc can cause an explosion in a hazardous environment
Electric arcs cause excessive wear to contacts on both the module and its mating
connector. Worn contacts can create electrical resistance.
1. Turn off and lockout all input power, including any external power sources
(such as an Active Front End or other DC power source).
ATT EN TI ON : To avoid an electric shock hazard when servicing the drive, a
means for lockout/tagout of the external, single-phase 120/240V power source
and, if present, external 120V uninterruptible power supply source, must be
provided.
2. If present, turn off and lockout any external, single-phase 120/240V power
source.
3. For regenerative drives and bus supplies, complete steps a…e.
a. On the input bay, turn the AC precharge disconnect switch to the
“Off ” position.
b. Wait 15 minutes.
c. Open the enclosure door.
d. Close and lock the hasp on the circuit breaker.
e. Lock the fused disconnect switch.
Rockwell Automation Publication 750-TG100B-EN-P - June 201917
Chapter 1Be fo re You B eg in Tes ts , M ai nt en an ce , or Re pa ir s
Frame 9, IP21 UL Type 1 Input Bay Shown
4. For common bus inverters with DC precharge, complete steps a…e:
a. Turn the DC precharge disconnect switch to the “Off” position.
a. Wait 15 minutes.
b. Open the enclosure door.
c. Close and lock the hasp on the molded case switch.
d. Lock the fused disconnect switch.
e. If a control bay is used, turn the selector switch to the “Off” position
and lock the switch.
ATT EN TI ON : To avoid an electric shock hazard, verify that there is no AC input
and DC bus voltage before servicing by taking these measurements:
• Verify that there is no AC input voltage present using the R/L1, S/L2, and T/L3
test point sockets in the input bay by measuring L to L and L to GND.
• Verify that there is no AC input voltage present using the R, S, and T testpoint
sockets in the input bay by measuring L to L and L to GND.
• Verify that there is no DC bus voltage present using the +DC to –DC testpoints
in the input bay by measuring +DC to –DC, +DC to GND, and –DC to GND.
5. For regenerative drives and bus supplies, measure the AC input and DC
bus voltage at the following testpoint sockets in the input bay to verify that
there is no voltage present:
• Using the circuit breaker output (CB1 SEC) testpoints R/L1, S/L2,
and T/L3, measure L to L and L to chassis GND.
• By using the fused disconnect output (FD1 SEC) testpoints R, S, and
T, measure L to L and L to chassis GND.
• By using the DC bus testpoints +DC and –DC, measure +DC to
–DC, +DC to chassis GND, and –DC to chassis GND.
18Rockwell Automation Publication 750-TG100B-EN-P - June 2019
Before You Begin Tests, Maintenance, or RepairsChapter 1
Frames 8…15 Power Module
ATT EN TI ON : To avoid an electric shock hazard, verify that the voltage on the
bus capacitors has discharged completely before servicing. Verify that there
is no DC bus voltage present using the +DC to –DC testpoints on all power
modules by measuring +DC to –DC, +DC to GND, and –DC to GND.
6. For common bus inverters, by using the DC bus testpoints +DC and
–DC on the front of the power modules, measure the DC bus voltage of
all power modules and verify that there is no voltage present on the bus
capacitors. Measure +DC to –DC, +DC to chassis GND, and –DC to
chassis GND.
Rockwell Automation Publication 750-TG100B-EN-P - June 201919
Chapter 1Be fo re You B eg in Tes ts , M ai nt en an ce , or Re pa ir s
AC Precharge Circuit Breaker
Frame 10 Input Bay ShownAC Precharge Circuit Breaker
7. Measure the 240V AC control voltage at the appropriate terminals:
• For frame 7 drives and bus supplies, measure terminals L and N on
terminal block TB3.
• For frames 8…15 drives and bus supplies, in the input bay, measure
terminals L and N on terminal block TB2.
20Rockwell Automation Publication 750-TG100B-EN-P - June 2019
Before You Begin Tests, Maintenance, or RepairsChapter 1
• For control bays, measure terminal L at FH2-2 and terminal N at
terminal block TB4.
Rockwell Automation Publication 750-TG100B-EN-P - June 201921
Chapter 1Be fo re You B eg in Tes ts , M ai nt en an ce , or Re pa ir s
Commonly Used Tools
Ta b l e 2 includes the tools that are needed for test measurements, basic
maintenance, and service repairs.
IMPORTANT Care must be taken to be sure that tools and/or hardware components do not
fall into open drive assemblies. Do not energize the drive unless all loose tools
and/or hardware components have been removed from the drive assemblies
and enclosure.
Table 2 - Service Tools
Tool DescriptionDetails
Allen socket wrench3 mm
Box wrench7 mm, 8 mm, 10 mm, 13 mm, 15 mm, 17 mm, 19 mm, 22 mm
Crimp toolsFor cable terminals 1.5...240
Current clamp1000 A (AC, rms), signal output
ESD-protected place of workWork surface, Floor cover, seat, and ground connections
Flat-nose screwdriver3 mm (0.12 in.), 5 mm (0.19 in.), 6.4 mm (0.25 in.)
Torx, star, or hexalobular screw
driver/bit
Hexagonal socket wrench2.5 mm, 7 mm, 8 mm, 10 mm, 12 mm, 13 mm, 17 mm, 18 mm
Insulation tester1000V DC
Level–
Lift strap5/16 in. J-hook style, 24 in. long, 1000 lb. Minimum
Multi-meterDigital multi-meter, capable of AC and DC voltage, continuity, resistance,
Nose pliers–
OscilloscopePortable, digitizing, dual channel scope, with isolation
Phillips screwdriver/bit#1, #2
Module service cartThe optional module service cart (20-750-MCART1) is recommended to handle
Module storage hardwareModule storage hardware (20-750-MINV-ATIP) helps to stabilize power and filter
Torque wrench1...12 N
Torque wrench6...50 N
Wire c utter–
#15, #20, #25, #30, #40, #45
capacitance measurements, and forward diode bias tests. Fluke model 87 III or
equivalent.
and transport power and filter modules.
modules during temporary storage after removal.
•m (8.8…106 lb•in)
•m (53…443 lb•in)
Software Tools
Connected Components Workbench™ software is an application that can be used
to upload and download parameter configuration and monitor system
parameters. Connected Components Workbench version 10.xx or later is
required for use with PowerFlex 755T products.
22Rockwell Automation Publication 750-TG100B-EN-P - June 2019
Before You Begin Tests, Maintenance, or RepairsChapter 1
Fastener Type
Flat-head screw
Hexagonal bolt
Hexagonal nut or standoff
Hexagonal screw
Tor x s cre w
Phillips screw
Pozid riv scre w
Slotted tor x screw
Sequence
Number
1
M4 x 10 mm
T20 or F - 6.4 mm (0.25 in.)
4.8 N
•m (42 lb•in)
Tool Type and Size
FFlat-nose screwdriver
PxPhillips screwdriver/bit and size
PZxPozidriv screwdriver/bit and size
TxxTorx screwdriver/bit and size
xx mm Hexagonal socket wrench
Final Assembly Torque
Fastener Size
Hardware Installation
Diagrams
The disassembly illustrations throughout this manual contain diagrams (as
shown here) that identify the following: corresponding sequence number (if
necessary), type of fastener, fastener size, tool type and size, and final assembly
torque.
Rockwell Automation Publication 750-TG100B-EN-P - June 201923
Chapter 1Be fo re You B eg in Tes ts , M ai nt en an ce , or Re pa ir s
1
2
Initial Sequence
1
2
12
Final Sequence
1
2
3
4
34
Initial Sequence
1
2
1
234
Final Sequence
Fastener Torque Sequences
The following illustrates initial and final tightening sequences for components
that are fastened to a heat sink by using two, four, and six screws. Initial torque is
1/3 (33%) of final torque, except six-point mountings, which require 0.7 N
(6 lb
Drive components do not contain these labels.
Figure 2 - Two-point Mounting
ATT EN TI ON : When mounting components to a drive heat sink, component
fastener torque sequences and tolerances are crucial to component-to-heat sink
heat dissipation.
Components can be damaged if initial tightening procedure is not performed to
specification.
•m
•in) initial torque. The numeric illustration labels are for your assistance.
Figure 3 - Four-point Mounting
24Rockwell Automation Publication 750-TG100B-EN-P - June 2019
Figure 4 - Six-point Mounting
642
351
34
Initial Sequence
1265
Final Sequence
341265
Do not exceed 0.7 N•m (6 lb•in) on initial torque of all six screws.
Before You Begin Tests, Maintenance, or RepairsChapter 1
Rockwell Automation Publication 750-TG100B-EN-P - June 201925
Chapter 1Be fo re You B eg in Tes ts , M ai nt en an ce , or Re pa ir s
Notes:
26Rockwell Automation Publication 750-TG100B-EN-P - June 2019
Chapter 2
Preventative Maintenance
Top icPag e
Recommended Preventative Maintenance27
Predictive Maintenance28
Schedule Codes Explanation28
Shock Events41
Maintenance of Industrial Control Equipment42
This chapter provides information on preventative maintenance for components
that can affect the life and operational characteristics of PowerFlex® 750-Series
products with TotalFORCE® Control.
Recommended
Preventative Maintenance
Rockwell Automation recognizes that following a defined maintenance schedule
delivers the maximum product availability. By strictly following the maintenance
schedule of tasks that is provided for your operating environment, you can expect
the highest possible uptime. A maintenance schedule is provided for each of these
environments:
• Ta b l e 3
• Ta b l e 4
• Ta b l e 5
IMPORTANT Duty cycle and load profile can greatly affect the reliability of PowerFlex
Recommended Maintenance Schedule for Normal Operation on
page 29
ambient temperature is less than or equal to 40 °C (104 °F).
Operation on page 33
environment where the ambient temperature is above 41 °C (106 °F).
Operation on page 37
reactivity level greater than 1000 angstroms per 30 days exposure. No
condensation allowed. Maximum allowable humidity is 60% in the
presence of corrosive gases. See ISA-71.04-2013 for details on how to
measure reactivity levels on copper and silver test coupons.
. Normal operation is defined as an environment where the
Recommended Maintenance Schedule for High Temperature
. High temperature operation is defined as an
Recommended Maintenance Schedule for Harsh Environment
. Harsh environment is defined as a copper or silver
750-Series Products with TotalFORCE Control.
Rockwell Automation Publication 750-TG100B-EN-P - June 201927
Chapter 2Preventative Maintenance
An annual preventative maintenance program includes the following primary
tasks:
• A visual inspection of all components accessible from the front of the
Module
• Resistance checks on the power components
• Power-supply voltage level checks
• General cleaning and maintenance
• Tightness checks on all accessible power connections
Predictive Maintenance
Schedule Codes
Explanation
See Chapter 3 - Component Inspection and Test Procedures on page 45
for
additional information on how to perform inspections and tests.
PowerFlex 750-Series Products with TotalFORCE Control contain algorithms
for predictive maintenance that are used to improve the “uptime” of machines,
processes, and facilities. These algorithms monitor the lifespan of certain
components and display the calculated value in specific parameters. These
algorithms can be used to alert personnel when the components are nearing the
end of their lifespan so the components can be replaced before they fail. The
shaded rows in Ta b l e 3
…Ta b l e 5 on pages 29…37, respectively, identify the
components with predictive maintenance parameters. Use the predictive
maintenance parameters to determine a replacement schedule for the applicable
components. See Predictive Maintenance in the PowerFlex 750-Series Products
with TotalFORCE Control Reference Manual, publication 750-RM100
, for
more information.
IMPORTANT Failure to address predictive maintenance alarms can cause unexpected
downtime or premature product failure.
The codes that are listed in this table are used to identify the task that is
associated with the components that are identified in the tables on pages 29
CodeTaskDescription
IInspectInspect the component for signs of excessive accumulation of dust, dirt, or external
damage. For example, inspect the filters/fan inlet screens for debris that can block
the airflow path.
CCleanClean the components that can be reused, specifically the door-mounted air filters
and fan inlet screens.
MMaintainThis type of maintenance task can include an inductance test of line reactors/DC
links, or a full test of an isolation transformer, and so on.
RReplaceThis component has reached its mean operational life. Replace the component to
decrease the chance of failure. It is likely that components can exceed the designed
life in the drive, but component life is dependent on many factors such as usage and
heat.
Use the predictive maintenance parameters to determine a replacement schedule for
components in shaded table rows.
RvReviewA discussion with Rockwell Automation personnel is recommended to help
determine whether any of the enhancements/changes made to the drive hardware
and control could benefit the application.
…37.
28Rockwell Automation Publication 750-TG100B-EN-P - June 2019
Preventative MaintenanceChapter 2
RR
IIIIIIIIIIIIIIIIIIII
Maintenance
Parameters
Grease Power Stabs -
Frames 8… 15 onlyRBalance Resistors -
Frames 8… 15 only
Power Mod ules,
Years >01234567891011121314151617181920
Table 3 - Recommended Maintenance Schedule for Normal Operation
Module/ActivityComponentPredictive
Frames 7…15
340, 440, 540, 640,
740, 840, 940, 1040
Port 12 /14: 143, 243,
343, 443, 543, 643,
743, 843, 943, 1043
(cat. no. SK-RM-INVBRn-F8M)
IGBTsPort 12 /14: 140, 240,
Bus Capacitors (cat. no.
SK-RM-ICP1-xnnnxnnn)
Power Laye r Interf ace Circuit Board
(cat. no. SK-RM-PLI1-F7,
SK-RM-PLI1-F8)RPower Interface Circuit Board
(cat. no. SK-RM-PIBn-xnnnxnnn,
SK-RM-PIB4-xnnnxnnn)RGate Driver Circuit Board -
Frames 8… 15 onlyRHeat Sink Fan (cat. no.
Port 12 /14: 136, 236,
336, 436, 536, 636,
736, 836, 936, 1036
IGBTsPort 12 /14: 140
Power Feedbac k Circuit B oard
SK-RM-INVFAN1-F8,
SK-RM-MFAN-F7)
(cat. no. SK-RM-PFB-F5-F6)RFan Power Supply Circuit Board
Power Components,
Frames 5 and 6
(cat.no. SK-RM-PSB1-F5-F6)RStirring Fan - Frames 5 and 6 (cat.
Port 14: 128IIIIIIIIIIIIIIIIIIII
no.
SK-RM-MFAN1-F5,
SK-RM-MFAN1-F6)
IIIIIIIIIIIIIIIIIIII
Port 14: 136
Heat Sink Fan (cat. no.
SK-RM-HSFAN1-F5,
SK-RM-HSFAN1-F6)
Rockwell Automation Publication 750-TG100B-EN-P - June 201929
Chapter 2Preventative Maintenance
RR
R
RR
IIIIIIIIIIIIIIIIIIII
Port 14: 1250, 1450,
1550, 1650, 1750,
Maintenance
Parameters
Grease Power Stabs -
Frames 8… 15 onlyRCapacitors
LCL Filter Modules,
Years >01234567891011121314151617181920
Table 3 - Recommended Maintenance Schedule for Normal Operation (Continued)