Rockwell Automation Allen-Bradley PowerFlex 6000 Commissioning Manual

Page 1
Commissioning Manual

PowerFlex 6000 Medium Voltage Variable Frequency Drive Commissioning Manual

Publication 6000-IN007B-EN-P
Page 2

Important User Information

IMPORTANT
Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws, and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, Rockwell Automation, PowerFlex, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Page 3

Table of Contents

Preface
Introduction
Preparation and Inspection (For IEC)
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Who Should Use This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
What Is Not in This Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Required Supplemental Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Dimensional Drawings and Electrical Drawings. . . . . . . . . . . . . . . . . . . 7
Shipping, Handling, and Installation Manual . . . . . . . . . . . . . . . . . . . . . 8
General Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Chapter 1
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Documentation and Application Review. . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Review all Rockwell Automation Supplied Documentation . . . . . . 12
Pre-commissioning Customer Meeting. . . . . . . . . . . . . . . . . . . . . . . . . 13
Review Drive Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Chapter 2
Gather Required Tools and Test Equipment . . . . . . . . . . . . . . . . . . . . . . . 15
Lockout and Tagout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Inspect Drive Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Functional Assessment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Interconnection Review . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Installation Review . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Mechanical Installation Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Electrical Installation Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Power Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Drive Megger Check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Isolate the Power and Control Circuits. . . . . . . . . . . . . . . . . . . . . . . . . 23
Connect the Insulation Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Final Steps before Equipment is Ready for Energization . . . . . . . . . . . . . 29
Seal the Cabinet Plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Preparation and Inspection (For UL)
Chapter 3
Gather Required Tools and Test Equipment . . . . . . . . . . . . . . . . . . . . . . . 31
Lockout and Tagout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Inspect Drive Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Functional Assessment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Interconnection Review . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Installation Review . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Mechanical Installation Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Electrical Installation Inspection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Power Cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 3
Page 4
Table of Contents
Drive Megger Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Isolate the Power and Control Circuits . . . . . . . . . . . . . . . . . . . . . . . . . 39
Connect the Insulation Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Final Steps before Equipment is Ready for Energization . . . . . . . . . . . . . 46
Seal the Cabinet Plates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Chapter 4
Commissioning
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Control System Check Setup. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Simulate Closed Input Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . 48
Energize Control Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Control System Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Verify Factory Default Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Set P Parameters to Enable Testing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Verify Settings for Low-Voltage Testing . . . . . . . . . . . . . . . . . . . . . . . . 58
Verify Operation of Frequency Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
Verify Operation to Set Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Simulate Warnings and Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Verify E-Stop Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Verify Switching from Local Control to Remote Control . . . . . . . . 73
Verify Operation of Input/Output and Bypass Isolation Switches
(Manual Bypass). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Verify Operation of Input/Output and Bypass Contactors
(Automatic Bypass) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Verify Operation of DCS Input and Output Signals . . . . . . . . . . . . . 83
Restore P Parameter Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Set Date and Time Zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Access T Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Change Time/Date/Regional Settings. . . . . . . . . . . . . . . . . . . . . . . . . . 87
Chapter 5
No-load Test
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
No-load Test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Energize Drive Control Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Configure P and T Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Change Parameters T11...T13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Close Isolation Switches in Bypass Cabinet . . . . . . . . . . . . . . . . . . . . 102
Close Input Circuit Breaker . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Check Cooling Fan Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Operate Motor by HMI. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Load Test of Drive System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Appendix A
Torque Requirements
4 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Torque Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Page 5
Appendix B
Table of Contents
Single Line Diagrams
Special Function Parameter Settings
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Appendix C
Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
System Setting Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Number of Power Modules Per Phase . . . . . . . . . . . . . . . . . . . . . . . . . 117
Switch Control Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Rated/Maximum Output Frequency. . . . . . . . . . . . . . . . . . . . . . . . . . 118
Motor Parameter Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Hall Effect Current Sensor Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Analog Output Display Parameter Setting . . . . . . . . . . . . . . . . . . . . . 119
Restore Factory Setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Speed Command Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Set Frequency Command Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Set Frequency Correction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Frequency Command Deadband Upper Limit . . . . . . . . . . . . . . . . . 120
Frequency Amplitude Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Frequency Skip. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Speed Reference Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
V/F Curve Setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Set Maximum Modulation Index and Limit Output Voltage
Amplitude . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Set Flux Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 122
Analog Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Stop Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Flying Start Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Restart the Drive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Index
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 5
Page 6
Table of Contents
Notes:
6 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 7

Preface

Introduction

Who Should Use This Manual

What Is Not in This Manual

This document provides procedural information for commissioning PowerFlex® 6000 medium voltage drives with version 4.001 firmware.
This manual is intended for Rockwell Automation Field Service Engineers with Medium Voltage Drive factory training and field experience commissioning medium voltage solid-state variable speed drive equipment.
WARNING: This document is for internal use only (for Rockwell CSM/field support Engineers). DO NOT disclose this document to customers or any non­Rockwell Automation employee. Disclosure of sensitive information in this document may cause dire consequences to the drive.
This manual is generic and does not include project-specific or drive-specific information. Contact the Start-up Project Manager for required project-specific or drive-specific information such as:
Dimensional Drawings and Electrical Drawings generated for the customer’s order.
Spare parts lists compiled for the customer’s order.
Drive-specific technical specifications.
Pre-commissioning Checklist
PLC program for standard, integral PLC

Required Supplemental Information

Dimensional Drawings and Electrical Drawings
Thoroughly review the project-specific Dimensional Drawings (DDs) and Electrical Drawings (EDs) to understand the specific drive system being commissioned, before performing any mechanical or electrical work.
Within these drawings is detailed information which is important to understand for the commissioning and installation of the equipment.
Table 1 - Electrical Drawings
Contactor Locations (electrically)
Drive Topology
General Notes
Minimum Power Cable Insulation Ratings
Component Designations
Customer Power and Control Wiring Locations (electrically)
Control and Medium Voltage Power Ratings
Fuse Locations (electrically)
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 7
Page 8
Preface
Table 2 - Dimensional Drawings
Control and Medium Voltage Power Ratings
Drive Options
Motor Ratings
Drive Power Component Selection Ratings
If the drawings require changes to suit the installation and application of the system, fax or e-mail the marked up drawings to the Start-up Project Manager.
Shipping, Handling, and Installation Manual
Review publication 6000-IN006_-EN-P, PowerFlex 6000 Medium Voltage Variable Frequency Drive Shipping, Handling, and Installation manual.
The customer/contractor has the option to perform the electrical interconnection work between cabinet shipping splits, as shown in this manual, or contract Rockwell Automation to perform this work. This will be reflected in the Services Purchase Order and the pre-commissioning checklist. Verify that the documentation matches the actual scope of work done by the customer/ contractor. You will be required to either perform this interconnection work immediately prior to the commissioning process or to verify the work was done correctly by the contractor. It is very important to confirm the alignment of the paperwork with the actual scope of work.
It is also extremely important to understand the contractor’s basic scope of work, preceding the commissioning process. Part of the overall commissioning process is to ensure this work has been done correctly. If this work has not been done properly, this must be brought to the attention of the customer immediately. Do not proceed with commissioning until this issue is resolved.
Additional required information about the PowerFlex 6000 can be downloaded from http:/www.rockwellautomation.com/literature/
6000-IN006_-EN-P
: PowerFlex 6000 Medium Voltage Variable
.
Frequency Drive Shipping, Handling, and Installation Instructions
6000-UM002_-EN-P
: PowerFlex 6000 Medium Voltage Variable
Frequency Drive User Manual (operating the HMI, full parameter listing)
You must review these publications thoroughly before beginning the commissioning process. They contain supplemental information that will aid in the commissioning process.
8 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 9
Preface

General Precautions

Additional Resources

ATT EN TI ON : This drive contains ESD (Electrostatic Discharge) sensitive parts
and assemblies. Static control precautions are required when installing, testing, servicing or repairing this assembly. Component damage may result if ESD control procedures are not followed. If you are not familiar with static control procedures, reference Allen-Bradley publication 8000-4.5.2, “Guarding Against Electrostatic Damage” or any other applicable ESD protection handbook.
ATT EN TI ON : An incorrectly applied or installed drive can result in component damage or a reduction in product life. Wiring or application errors, such as, undersizing the motor, incorrect or inadequate AC supply, or excessive ambient temperatures may result in malfunction of the system.
ATT EN TI ON : Only personnel familiar with the PowerFlex 6000 Adjustable Speed Drive (ASD) and associated machinery should plan or implement the installation, start-up and subsequent maintenance of the system. Failure to comply may result in personal injury and/or equipment damage.
These documents contain additional information concerning related products from Rockwell Automation.
Resource Description
Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
Product Certifications website, http://www.ab.com
Provides general guidelines for installing a Rockwell Automation industrial system.
Provides declarations of conformity, certificates, and other certification details.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 9
Page 10
Preface
Notes:
10 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 11
Introduction
Chapter 1

Overview

Information contained in this chapter will assist in commissioning a PowerFlex 6000 medium voltage AC drive.
Review the information contained in this chapter prior to commissioning the drive and use it as a reference while the drive commissioning is performed.
WARNING: Perform the commissioning checks illustrated in the sequence that they have been presented. Failure to do so may result in equipment failure, personal injury, or death.
Prior to commissioning, the following work will have been performed by the customer or the customer’s electrical contractor:
Connect External Cabling and Wiring
Connect System Ground Cable
Megger Test of Power Cables
Connect Incoming Line and Outgoing Motor Power Cables
Connec t Control Powe r Wiring
Connec t Extern al Control S ignal Wiri ng
Connect Electrical Safety Interlock Control Signal Wiring Circuit to Input Circuit Breaker
Connect Internal Cabling and Wiring
Connect Isolation Transformer Secondar y Power Cables to Power Modules
Connect Motor Cables and Voltage Sensing Board Cables to U, V, and W Output Phase Buses
Connect LV Control and Fan Wiring Bundles
Connect Ground Bus Splices
(1)
(1)
(2)
(1) If an optional bypass unit is supplied, the system ground cable, incoming line power cables, and outgoing motor power cables are
connected to the bypass unit.
(2) Interconnection of power cables and low voltage control wiring bundles, between separately shipped cabinets, can be done by the
contractor or Rockwell Automation. The commissioning quote from Rockwell Automation reflects this and will contain two options: a) the base quote, reflecting the power cable and control wiring interconnection work being done by the contractor b) the optional quote adder, reflecting the additional time and cost for Rockwell Automation to perform the power cable and control wiring interconnection work immediately prior to the commissioning process.
This work will be reviewed during the pre-commissioning customer meeting and validated during the commissioning process; see Installaion Review on page 21
page 37
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 11
.
or
Page 12
Chapter 1 Introduction
Lockout
and Tagout
Functio nal
Assessment
Interconnection
Review
Installation
Review
Control
System Ch eck
(LV Only)
No-load Test
of Drive System
(MV)
Load Test o f
Drive System
(MV)

Documentation and Application Review

Preparation and Inspection
Review
Rockwell
Automation
Supplied
Documentation
Pre-commissioning
Customer Meeting
Gather
Required Tools
and Test
Equipme nt
Review Drive
Application
Commissioning
Inspect Drive Components
Meggering
Final Review
and Preparation
Process Flowcharts
Documentation and Application Review
Review all Rockwell Automation Supplied Documentation
Each drive is shipped with the technical publications required to assist in commissioning and troubleshooting the drive. Request copies or revisions of these documents from the Start-up Project Manager. However, you will have received e-copies of this information prior to commissioning by the Start-up Project Manager.
Before commissioning the drive, ensure you have the following resources:
Project-specific Electrical Drawings and Dimensional Drawings
PowerFlex 6000 Medium Voltage Variable Frequency Drive Shipping,
): provides
Handling, and Installation Manual 6000-IN006_-EN-P procedural information for physically unloading, moving, and installing equipment
PowerFlex 6000 Medium Voltage Variable Frequency Drive Commissioning Manual (6000-IN007_-EN-P
): required procedures and
checklists for Rockwell Automation Field Service Engineers.
PowerFlex 6000 Medium Voltage Variable Frequency Drive User Manual (6000-UM002_-EN-P interface, and maintenance tasks
): instructions for daily recurring drive usage, HMI
12 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 13
Introduction Chapter 1
PLC Program: The PLC I/O processes control signals within the drive and I/O signals to and from the customer’s control system and input circuit breaker. The PLC program is standardized. However, it may be customized to address specific customer requirements by Rockwell Automation during the Application Engineering phase of order execution.
Pre-commissioning Customer Meeting
Before commissioning the drive, it is recommended to schedule a meeting with the customer.
1. Discuss the activities and documentation needed to review the drive application
2. Review the start-up activities and timelines
3. Review the Pre-commissioning Checklist (see 6000-IN006_-EN-P)
4. Review the drive application
Review Drive Application
To ensure trouble-free commissioning , it is necessary for all personnel involved in the start-up to familiarize themselves with the drive and actual application. Service on the equipment should not be performed without a clear understanding of how the equipment has been designed to function and how the equipment has been applied.
Before commissioning the drive, inspect the process that the drive is intended to control. This identifies how the equipment is designed to suit the application, and any potential hazards. Determine what measures must be taken to ensure that commissioning the equipment does not expose anyone to hazardous situations or damage to the equipment. Verify that the load is not turning due to the process, as a freewheeling motor can generate voltage that will be back-fed to the equipment being serviced. Take all actions necessary to ensure that motor regeneration into the drive does not occur while the equipment is being started up or being serviced.
Review Electrical System One-line Diagram
Identify all relevant equipment Tag Identification names and numbers. Study the system for sources of power and parallel paths of medium voltage power. Retain a copy of the one-line diagram for commissioning the drive. If applicable, send a copy of the one-line diagram to the Start-up Project Manager to be archived and used for future customer assistance.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 13
Page 14
Chapter 1 Introduction
On-site Verification of Electrical System One-line Diagram
ATT EN TI ON : Make sure the medium voltage input circuit breaker feeding the drive is locked out and tagged out. Make sure the LV circuit breaker feeding control power to the drive is locked out and tagged out. Make sure the drive is de-energized before conducting the drive inspection process.
Once all documentation has been reviewed, an on-site inspection of the drive is required. Identify the physical locations of the connections to the drive using Tag Identification names or numbers from the one-line diagram and Rockwell Automation Electrical Drawings.
All customer power and control wiring required for the drive line-up installation has been identified on the Rockwell Automation Electrical Drawings by a dashed line.
Installation of all external power cabling and control wiring interfacing with the drive is completed by the customer or their electrical contractor. Verify that this wiring is installed correctly and meets electrical voltage and current capacity requirements. Trace the power cables point-to-point from the input circuit breaker to the drive, and from the drive to the motor using the Electrical Drawings as a reference for proper drive power cable termination locations. Any discrepancy between the physical installation and the Electrical Drawings of the following items should be reviewed prior to commissioning the drive:
Medium voltage power cabling in from the input circuit breaker to drive
Medium voltage power cabling out from drive to motor
Low Voltage control power cables from LV MCC or circuit breaker to
drive
Ground connection from system ground to drive
Control signal wires and communication cables from remote DCS/PLC
or other remote device to drive
Electrical safety interlock/control wiring from the drive to the input
circuit breaker
ATT EN TI ON : Do not change wiring or remove terminal wiring.
14 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 15
Preparation and Inspection (For IEC)
Chapter 2

Gather Required Tools and Test Equipment

Hand Tools
Metric wrenches and sockets
To r qu e w re nc h
Assortment of screw drivers
Wire stripper/cutter
Electrical Equipment
High voltage gloves – 17 kV insulation rating (minimum)
Anti-static strap
Live-line tool (Hot stick)
5 kV Insulation Tester
Test Equipment
600V (1000V rating) digital multimeter with assorted clip leads
Computer Requirements and Software
Laptop computer
USB cable
PLC program
CCW software

Lockout and Tagout

SHOCK HAZARD: Servicing energized industrial control equipment can be
dangerous. Severe injury or death can result from electrical shock, burn, or unintended actuation of control equipment. Hazardous voltages may exist in the cabinet even with the input circuit breaker in the off position. Required practice is to disconnect and lock out control equipment from power sources, and confirm discharge of stored energy in capacitors. If it is necessary to work in the vicinity of energized equipment, the safety related work practices outlined in Electrical Safety requirements for Employee Work places must be followed. Before attempting any work, verify the system has been locked out and tested to have no potential.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 15
Page 16
Chapter 2 Preparation and Inspection (For IEC)
IMPORTANT
Lockout and tagout the input circuit breaker before opening the doors to the drive system cabinets. After the cabinet doors are opened, immediately test the incoming and outgoing power cables and any components connected to medium voltage with a live-line tool (hot stick) while wearing high voltage gloves. Pay special attention to any capacitors connected to medium voltage that can retain a charge for a period of time. Only after the equipment has been verified as isolated and de-energized can subsequent work be performed. Even though the input to the drive may be open, it is still possible for hazardous voltage to be present.
Refer to local safety guidelines for detailed procedures on how to safely isolate the equipment from hazards.
Safety Test
Complete every point included in this section prior to continuing with the drive commissioning, to ensure that the commissioning continues in an environment safe to all those involved in servicing the drive. Ensure that commissioning of this drive is performed in accordance with local safety standards.

Inspect Drive Components

After performing the lockout and tagout procedure (see page 15), open all of the cabinet doors. Inspect each component for signs of shipping damage (see Ta b l e 3
on page 18). An initial inspection would have been done by the customer when
the equipment was received. However, this would have been done from the front only and was just looking for obvious signs of damage (see publication 6000-
IN006_-EN-P). Record the part number and description of any damaged
components and immediately contact the Start-up Project Manager to order replacement components, if required.
ATT EN TI ON : Verify the equipment against any damage. Do not install a damaged drive.
Verify that all components are securely affixed to the cabinet.
Most components will be easily visible on the doors or from the front of the cabinets after the doors are opened. Some components are best viewed from the rear of the cabinet.
For rear inspection, remove top and bottom rear access plates from the drive and bypass cabinet (if supplied). See publication 6000-IN006_-EN-P.
The Inspect Drive Components Checklist (see page 18) mentions the principal base components supplied in the drive and bypass units. It is not comprehensive, as customer-required options may be supplied and three different bypass configurations are available.
Perform the shipping damage inspection for all components mounted in the drive cabinets and specific bypass unit cabinet (if supplied).
16 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 17
Preparation and Inspection (For IEC) Chapter 2

Functional Assessment

After the components are visually inspected to identify any shipping damage, a thorough functional assessment should be performed (see Table 4 on page 19 The main purpose of this assessment is to ensure that all movable parts and assemblies operate properly, connect properly, and components are wired properly and securely.
The Functional Assessment procedure can be combined with the “Inspect Drive Components” checklist on page 18
Descriptions of the Power Cable Connections to be inspected and torqued to specifications are in the Interconnection Review and Installation Review sections.
.
).
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 17
Page 18
Chapter 2 Preparation and Inspection (For IEC)
Door:
Pilot lights
Push buttons
Selector switches
HMI
Interface board (on the back of the LV door)
Panel:
DIN rail mounted components
UPS
Fiber optic cables
PLC
Control U nit
UPS connections
Fixed Mounted Power Module Configuration:
Door:
Power Module retaining tabs
Transformer Temperature monitor
Check for debris
Output Bus Supports
Fuse Mounting Supports
Drawout Power Module Configuration:
Fan control c ircuit breaker s
LV Cabinet components
Cabinet:
Transformer Plastic Baffle
Support frame
Power Modules
(1)
Outgoing Motor Power Cable standoffs on
Cabinet Sidesheet
Verify orientation relative to barrier plates
Fixed Mounted Power Module:
Heat sink
Drawout Power Module:
Power In/Power Out connections
(1)
Inspect nomex wrap
Verify windings from core are undamaged
Outgoing Motor Power Cable Terminal
– Check for debris in top of core
Insulators on transformer
Voltage Sensing Board
Incoming Line Power Cable Terminal Insulators
on transformer
Motor Cable Braces
Fixed Mounted Power Module Configuration:
Transformer Secondary Windings (2 sets)
Fixed Mounted Power Module Configuration:
Transformer Secondary Windings (1)
Inspect nomex wrap
Verify windings from core are undamaged
Check for debris in top of core
Inspect nomex wrap
Verify windings from core are undamaged
Drawout Power Module Configuration:
Transformer Secondary Windings (3)
Check for debris in top of core
Door:
Pilot Lights
Voltage Indicator Relay
Cabinet:
Insulators
Switch assemblies
Vacuum contactors
Bypass Cabinet (if supplied) Isolation Transformer Cabinet Power Module Cabinet Low Voltag e Control Cabinet
Table 3 - Inspect Drive Components Checklist (IEC)
Mechanical linkages
Front
Rear
18 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
(1) Motor Cable terminations could be on the transformer structure or cabinet sidesheet, depending on the power rating.
Page 19
Preparation and Inspection (For IEC) Chapter 2
Check connec tion of all fiber optic cables
Check connec tion of HMI interface board
Control Unit
HECS (2)
HMI
Check plug connectors
Test switch contacts wired back to terminal
Door Interlock Limit Switches (2)
and terminal blocks
– Tug test all wires on door, panel, and relays
Low Voltage wires
blocks in LV panel with ohmmeter
Power Modules fiber optic cables
Check all connections
Verify operation
Circuit Breakers and Contactors
Test each fuse with multimeter
Power Modules Fuses
components
– Check connec tions from all attached
Vertical Ground Bus
Door Grounding Straps
Low Voltage Door

devices
Verify operation of all operator interface
Check connections
AC/DC Power Sup plies
Door Grounding Straps
Check connection
UPS
Check electrical connection
Top Mounted Cooling Fans
Table 4 - Functional Assessment Checklist (IEC)
Transformer Secondary Cables
Bypass Cabinet (if supplied) Isolation Transformer Cabinet Power Module Cabinet Low Voltage Control Cabinet
Electrical Door Interlock
Verify cables are properly fed through the
Verify proper operation of auxiliary contacts
glanding plate and are undamaged
with an ohmmeter
to the board are secure
– Verify the primar y and secondary connections
Voltage Sensing Board cables
– Verify proper operation with an ohmmeter
Isolation switch auxiliary contacts
Isolation switches
terminal blocks in LV panel with ohmmeter
– Test auxiliary switch contacts wired back to
Door Interlock Limit Switches
Verify proper operation
Outer jaws must securely contact the center
Verify wires are intact and properly inserted
Temperature Sensing Wires (3 places)
stab in the closed position
– Check all connections per Electrical Drawings
Secondary Wiring and Low Voltage Fuses
Front
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 19
Bottom-mounted Auxiliary Fan power from
Isolation Transformer Auxiliary Winding
Door Grounding Straps
– Check connections
Door Grounding Straps
– Tug test on all cable connections
Transformer Temperature Protection Relay
– Check electrical connection
Auxiliary Cooling Fans (3)
glanding plate are undamaged
– Verify cables are properly fed through the
Transformer Secondary Cables
– Check braided copper connections
Surge Arrestors
– Verify connection
Tap Changer
– Pe rform tug tes t
Voltage Sensing Relay Cables
– Check electrical connection
Top Mounted Cooling Fans
– Verify phasing and torque
Line and Load side power cables
Top Ground Bus
Rear
structure
– Assembly must be affixed properly to
Fan H ousi ngs
Verify braided connections
Check electrical connection
Auxiliary Cooling Fans (3)
Page 20
Chapter 2 Preparation and Inspection (For IEC)
IMPORTANT

Interconnection Review

Table 5 - Interconnection Review Checklist (IEC)
Bypass Cabinet (if supplied) Isolation Transformer Cabinet Power Module Cabinet Low Voltage Control Cabinet
Verify the braided ground connection to adjacent cabinet(s) is properly installed
Review the braided ground connection to adjacent cabinet
Verify line and load power cables from Isolation Transformer
Front Inspection
Rear Inspection
Cabinet are properly connected Verify all control wires per
Electrical Drawing
The interconnection checklist summarizes the required items to review to validate the reconnection of power, ground, and control cables between cabinets within the drive system, that were disconnected for shipment. Power and control cables that pass from one cabinet to another are bundled in the appropriate cabinet. These cables are connected for system test at the factory but disconnected and coiled up for shipment. If this interconnection work was done by the contractor, use this checklist to review and ensure the work was done correctly. If the interconnection work was not done by the contractor, the scope of work required to be performed is described in 6000-IN006_-EN-P
.
.
Check torque on all power and ground cable connections per specifications listed in Torque Requirements
Verify the braided ground connection to adjacent cabinet(s) is properly installed
Review all isolation transformer secondary wiring from Power Module cabinet (2 sets)
Verify that the shields of all of the system’s connecting wires are properly grounded
Verify all control wires per Electrical Drawing
– Cables are run in LV cable
sections along front and back of cabinet
Fixed Mounted Power Module:
Verify all isolation transformer secondary windings from Power Module Cabinet are properly connected (1 set)
Drawout Power Module:
Verify all isolation transformer secondary windings from Power Module Cabinet are properly connected (3 sets)
Verify all power supply cables for main cooling fans for Isolation Transformer Cabinet are properly connected(3 sets)
Verify the braided ground connection to adjacent cabinet(s) is properly installed
Verify that the shields of all of the system’s connecting wires are properly grounded
Review load power cable connection from Isolation Tra nsf orm er C abi net
Verify Voltage Sensing Board power cables from Isolation Transformer Cabinet are properly installed
on page 109.
Verify control signal wiring bundles from LV Control cabinet to LV panel in Isolation Transformer cabinet and LV panel in the Bypass Cabinet (if supplied) are routed correctly
20 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 21
Preparation and Inspection (For IEC) Chapter 2

Installation Review

Prior to commencing the commissioning of the drive, verify the equipment was properly installed. Identifying errors in the drive installation prior to commencing the commissioning as opposed to mid-way through the commissioning process will greatly reduce the amount of time required to commission the drive. Verify the drive and all associated equipment have the system power grounding cable installed. Refer to 6000-IN006_-EN-P
to review the contractor’s drive installation responsibilities and understand the scope of the work you will be reviewing.
Mechanical Installation Inspection
Sequence Task Reference Document
1 Verify line up positioning Dimensional Drawings
2 Verify cabinets are bolted together correctly 6000-IN006_-EN-P
3 Verify cabinets are affixed to the floor properly Dimensional Drawings,
6000-IN006_-EN-P
4 Verify fans are installed correctly 6000-IN006_-EN-P
5 Verify power modules are installed correctly 6000-IN006_-EN-P
6 Review duct installation (if applicable) 6000-IN006_-EN-P
7 Verify the cable trenches meet design requirements 6000-IN006_-EN-P
8 Verify required cabinet clearances 6000-IN006_-EN-P
9 Verify there are no scratches or damage to the cabinet body N/A
10 Verify the top cover of the isolation transformer cabinet is securely
mounted
6000-IN006_-EN-P
Refer to project-specific EDs to review all electrical connections to external input and output devices.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 21
Page 22
Chapter 2 Preparation and Inspection (For IEC)
Electrical Installation Inspection
Sequence Task Reference
Document
1 Verify that medium voltage cables are separated at least 30 cm from the control cables
2 Verify that all secondary control wiring use shielded cables
3 Verify that input and output medium voltage cables specifications meet the stated
insulation requirements
4 Verify that input and output medium voltage cables have attached nameplates
5 Verify the diameter of control power cables comply with the drawings Electrical
6 Verify that the electrical safety circuit wiring between the input circuit breaker and the drive
7 Verify the wiring between the DCS and the drive is shielded and only the end the drive side is
8 Verify that the user-provided ground cable is ≥50 mm
9 Verify the isolation transformer’s primary input voltage matches the system primary voltage
10 Verify that the customer motor specifications match the drive voltage and current
11 Verify that the isolation transformer’s input si de wiring is correct Electrical
12 Verify that the motor output side wiring is correct Electrical
13 Verify all external control wiring is terminated correctly and to the proper terminal blocks Electrical
14 Verify torque on incoming line power cable and outgoing motor powe r cable terminations Electrical
is shielded and only the end at the drive side is grounded
grounded
2
capabilities
Electrical Drawings
Drawings
Drawings
Drawings
Drawings
Drawings
Power Cabling
Trace the power cabling from termination point to termination point while examining the cable and its routing for mechanical damage, sharp bend radiuses and sources of induced noise and heat. The power cabling must be is sufficiently braced to contain the cabling in the event of a ground fault. Color coding is used to indicate the phase orientation of the drive.
Table 6 - Color Coding
Color Incoming Line Side Outgoing Motor Side
Black L11 (A Phase) Line Cable Terminal U Phase:
Brown L12 (B Phase) Line Cable Terminal V Phase:
Grey L13 (C Phase) Line Cable Terminal W Phase:
Power Module Bus
VSB Input Cable
Motor Cable Termination
Motor Cable Connection to Power Module Bus
Power Module Bus
VSB Input Cable
Motor Cable Termination
Motor Cable Connection to Power Module Bus
Power Module Bus
VSB Input Cable
Motor Cable Termination
Motor Cable Connection to Power Module Bus
22 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 23
Preparation and Inspection (For IEC) Chapter 2
Incoming Line and Outgoing Motor cables must be routed separately to prevent cable insulation damage.
All cables must be terminated on each end and sufficiently torqued.
All customer power cables must be Hi-Potted or Meggered and read a sufficient insulation value. Review Hi-Pot or megger test report from the customer.
Control Wiring
Identify all customer-required control wiring detailed on the Electrical Drawings and locate it within the terminal blocks. Verify the cable insulation is not tightened in a terminal connection. All connections must have proper continuity.
Inspect the control cable routing to ensure that DC control wiring and AC control wiring are separated from each other. Routing them together in the same bundle or cabling product may result in unwanted noise being induced in the drive control. In the overhead cable tray provided at the front of the drive, the AC control, DC control and fiber optic cables must be separate. These cables may also be from the bottom.

Drive Megger Check

Control wiring must be routed separately from power cabling.
Inspect for additional control not shown on the Electrical Drawings. Determine its purpose, mark the changes on the electrical diagram and send the prints to the Start-up Project Manager for future reference.
Perform a tug test on all control cables to ensure that they are securely fastened, and check each plug and connector to ensure it is properly seated in its socket.
Isolate the Power and Control Circuits
ATT EN TI ON : Verify the grounding cable connection is secure.
Disconnect the low voltage power before the megger test. Short circuit the 3 input cables and 3 output cables on one point.
1. Isolate and lock out the drive system from any high voltage source.
Disconnect any incoming power sources, medium voltage sources should be isolated and locked out and all control power sources should be turned off at their respective circuit breaker(s).
Verify with a potential indicator that power sources have been disconnected, and that the control power in the drive is de-energized.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 23
Page 24
Chapter 2 Preparation and Inspection (For IEC)
VSB Board Cable connected to Transformer Cabinet
Keep the plug at least
100 mm away from
Temperature Monitor plug
2. Disconnect four 380V AC cables (a, b, c, and o cables) from the bottom of the Isolation Transformer.
Figure 1 - 380V AC Bottom-mounted Auxiliary Fan Input Cables (IEC)
3. Disconnect the Voltage Sensing Board Output Cable. Keep the plug at least 100 mm away from the Voltage Sensing Board.
Figure 2 - Voltage Sensing Board Output Connection Cable (IEC)
4. Disconnect the Isolation Transformer Temperature Monitor. Keep the plug at least 100 mm away from the connection point on the Monitor.
Figure 3 - Isolation Transformer Temperature Monitor (IEC)
24 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 25
Preparation and Inspection (For IEC) Chapter 2
Miniature Circuit Breakers
Top Main Cooling Fan Cir cuit Brea kers
Miniature Circuit Breakers
5. Switch the miniature circuit breakers in the LV Cabinet off.
Figure 4 - Control Switches (IEC)
6. Switch the miniature circuit breakers in the Isolation Transformer Cabinet LV Control panel off. Switch the Top Main Cooling Fan circuit breakers off.
Figure 5 - Control Switches (IEC)
7. Remove two star connection cables (the cabling that goes through the HECS) and connect them to the output connections of any two power modules within a phase.
Figure 6 - Star Connection Cable
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 25
Page 26
Chapter 2 Preparation and Inspection (For IEC)
Control Cable
HECS
(located at the top of the
power unit cabinet)
Control Board Power Cables
HMI Power Cable
8. Disconnect the control cable of HECS.
Figure 7 - Hall Effect Current Sensor
9. Disconnect the HMI and Control Board power cables.
Figure 8 - Back of HMI
26 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 27
Preparation and Inspection (For IEC) Chapter 2
Analog Interface Board location on Control Unit
Control Unit terminals
10. Remove the Analog Interface board and disconnect all of the terminals from the Control Unit.
Figure 9 - Back of Control Unit
Connect the Insulation Meter
1. Connect the red wire from the insulation meter to the U Phase and the black wire to the grounding bus.
ATTENTION: Verify the drive and any connected equipment is clear of personnel and tools prior to commencing the Megger test. Barricade off any open or exposed conductors. Conduct a walk-around inspection before commencing the test.
2. Use jumper wires to make the connections as shown in Figure 10
.
The jumper wires must be rated for greater than 5 kV or must maintain sufficient clearance to any metal surface.
3. If the Megger has a lower voltage setting (normally 500V or 1000V), apply that voltage for 5 seconds as a precursor for the higher voltage rating. This may limit the damage if there is a problem. If the reading is very high, apply the test voltage per Figure 10
.
4. Perform a Megger test with the insulation meter voltage set according to the voltages shown in Ta b l e 7
for 1 minute and record the result.
The test should produce a reading greater than the minimum values listed below. If the test results produced a value lower than these values start segmenting the drive system down into smaller components and repeat the test on each segment to identify the source of the ground fault.
ATTENTION: Discharge the Megger prior to disconnecting it from the equipment.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 27
Page 28
Chapter 2 Preparation and Inspection (For IEC)
Ground Bus Bar
Insulation Meter
Outgoing Motor Power
Cable Connections
Incoming Line Power Cable Connections
5. Disconnect the Insulation Meter and jumpers installed in steps 1 and 2.
6. Reconnect all wires, cables, and connections in reverse order of removal.
Figure 10 - Connected Insulation Meter (IEC)
Table 7 - Insulation Test Voltage Values
Drive Rated Voltage U1 Insulation Resistance Test Direct Voltage (V)
1000<U1≤5000 2500
5000<U1 5000
Typical of Drive Minimum Megger Value
Entire Drive 1 kM Ohm
28 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 29
Preparation and Inspection (For IEC) Chapter 2
IMPORTANT
Apply silicone as
shown by bold lines
Apply silicone as
shown by bold lines

Final Steps before Equipment is Ready for Energization

1. Review interior of all cabinets for foreign material that might have been left behind during the installation process. Ensure no tools, hardware, or wiring debris remain in the drive system cabinets. Clear any metal shavings that may result from any drilling activities.
2. If any internal barriers were removed during the commissioning process, ensure they are reinstalled.
Seal the Cabinet Plates
Once the back plates have been reattached, the seams along the plates must be sealed with silicone. Where the silicone is applied is dependent on the cabinet configuration (Fixed-mounted or Drawout Power Module).
Use the approved silicone that is shipped with the drive.
Figure 11 - Silicone Locations on Fixed-mounted Power Module Configuration
Figure 12 - Silicone Locations on Drawout Power Module Configuration
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 29
Page 30
Chapter 2 Preparation and Inspection (For IEC)
Notes:
30 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 31
Preparation and Inspection (For UL)
Chapter 3

Gather Required Tools and Test Equipment

Hand Tools
Metric wrenches and sockets
To r qu e w re nc h
Assortment of screw drivers
Wire stripper/cutter
Electrical Equipment
High voltage gloves – 17 kV insulation rating (minimum)
Anti-static strap
Live-line tool (Hot stick)
5 kV Insulation Tester
Test Equipment
600V (1000V rating) digital multimeter with assorted clip leads
Computer Requirements and Software
Laptop computer
USB cable
PLC program
CCW software

Lockout and Tagout

SHOCK HAZARD: Servicing energized industrial control equipment can be
dangerous. Severe injury or death can result from electrical shock, burn, or unintended actuation of control equipment. Hazardous voltages may exist in the cabinet even with the input circuit breaker in the off position. Required practice is to disconnect and lock out control equipment from power sources, and confirm discharge of stored energy in capacitors. If it is necessary to work in the vicinity of energized equipment, the safety related work practices outlined in Electrical Safety requirements for Employee Work places must be followed. Before attempting any work, verify the system has been locked out and tested to have no potential.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 31
Page 32
Chapter 3 Preparation and Inspection (For UL)
IMPORTANT
Lockout and tagout the input circuit breaker before opening the doors to the drive system cabinets. After the cabinet doors are opened, immediately test the incoming and outgoing power cables and any components connected to medium voltage with a live-line tool (hot stick) while wearing high voltage gloves. Pay special attention to any capacitors connected to medium voltage that can retain a charge for a period of time. Only after the equipment has been verified as isolated and de-energized can subsequent work be performed. Even though the input to the drive may be open, it is still possible for hazardous voltage to be present.
Refer to local safety guidelines for detailed procedures on how to safely isolate the equipment from hazards.
Safety Test
Complete every point included in this section prior to continuing with the drive commissioning, to ensure that the commissioning continues in an environment safe to all those involved in servicing the drive. Ensure that commissioning of this drive is performed in accordance with local safety standards.

Inspect Drive Components

After performing the lockout and tagout procedure (see page 31), open all of the cabinet doors. Inspect each component for signs of shipping damage (see Ta b l e 8
on page 34). An initial inspection would have been done by the customer when
the equipment was received. However, this would have been done from the front only and was just looking for obvious signs of damage (see publication 6000-
IN006_-EN-P). Record the part number and description of any damaged
components and immediately contact the Start-up Project Manager to order replacement components, if required.
ATT EN TI ON : Verify the equipment against any damage. Do not install a damaged drive.
Verify that all components are securely affixed to the cabinet.
Most components will be easily visible on the doors or from the front of the cabinets after the doors are opened. Some components are best viewed from the rear of the cabinet.
For rear inspection, remove top and bottom rear access plates from the drive and bypass cabinet (if supplied). See publication 6000-IN006_-EN-P.
The Inspect Drive Components Checklist (see page 34) mentions the principal base components supplied in the drive and bypass units. It is not comprehensive, as customer-required options may be supplied and three different bypass configurations are available.
Perform the shipping damage inspection for all components mounted in the drive cabinets and specific bypass unit cabinet (if supplied).
32 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 33
Preparation and Inspection (For UL) Chapter 3

Functional Assessment

After the components are visually inspected to identify any shipping damage, a thorough functional assessment should be performed (see Table 9 on page 35 The main purpose of this assessment is to ensure that all movable parts and assemblies operate properly, connect properly, and components are wired properly and securely.
The Functional Assessment procedure can be combined with the “Inspect Drive Components” checklist on page 34
Descriptions of the Power Cable Connections to be inspected and torqued to specifications are in the Interconnection Review and Installation Review sections.
.
).
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 33
Page 34
Chapter 3 Preparation and Inspection (For UL)
Door:
Fixed Mounted Power Module Configuration:
Pilot lights
Power Module retaining tabs
Push buttons
Selector switches
HMI
Interface board (on the back of the LV door)
Check for debris
Output Bus Supports
Fuse Mounting Supports
Voltage Sensing Board
Panel:
DIN rail mounted components
UPS
Fiber optic cables
PLC
Control U nit
UPS connections
Verify orientation relative to barrier plates
Drawout Power Module Configuration:
Support frame
Power Modules
(1)
(1)
Fixed Mounted Power Module:
Heat sink
Table 8 - Inspect Drive Components Checklist (UL)
Door:
Transformer Temperature monitor
LV Cabinet components
Cabinet:
Transformer Plastic Baffle
Outgoing Motor Power Cable standoffs on
Cabinet Sidesheet
Outgoing Motor Power Cable Terminal
Insulators on transformer
Incoming Line Power Cable Terminal Insulators
on transformer
Motor Cable Braces
Door:
Pilot Lights
Voltage Indicator Relay
Cabinet:
Insulators
Switch assemblies
Vacuum contactors
Bypass Cabinet (if supplied) Isolation Transformer Cabinet Power Module Cabinet Low Voltag e Control Cabinet
Mechanical linkages
Front
Fan control c ircuit breaker s
Fixed Mounted Power Module Configuration:
Inspect nomex wrap
Verify windings from core are undamaged
Transformer Secondary Windings (2 sets)
Check for debris in top of core
Fixed Mounted Power Module Configuration:
Transformer Secondary Windings (1)
Inspect nomex wrap
Rear
Verify windings from core are undamaged
Check for debris in top of core
(1) Motor Cable terminations could be on the transformer structure or cabinet sidesheet, depending on the power rating.
34 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 35
Preparation and Inspection (For UL) Chapter 3
Check connec tion of all fiber optic cables
Check connec tion of HMI interface board
Check plug connectors
HMI
Test switch contacts wired back to terminal
Mechanical Interlock (2)
Control Unit
HECS (2)
and terminal blocks
– Tug test all wires on door, panel, and relays
Low Voltage wires
blocks in LV panel with ohmmeter
Power Modules fiber optic cables
Check all connections
Verify operation
Circuit Breakers and Contactors
Test each fuse with multimeter
Power Modules Fuses
components
– Check connec tions from all attached
Vertical Ground Bus
– Verify the primary and secon dary connections
Door Grounding Straps
Voltage Sensing Board cables
devices
– Verify operation of all operator interface
Low Volta ge Door
to the board are secure
Door Grounding Straps

Check connection
UPS
Check electrical connection
Top Mounted Cooling Fans
Check connections
AC/DC Power Sup plies
Table 9 - Functional Assessment Checklist (UL)
Transformer Secondary Cables
Bypass Cabinet (if supplied) Isolation Transformer Cabinet Power Module Cabinet Low Voltage Control Cabinet
Electrical Door Interlock
Verify cables are properly fed through the
Verify proper operation of auxiliary contacts
glanding plate and are undamaged
with an ohmmeter
terminal blocks in LV panel with ohmmeter
– Test auxiliary switch contacts wired back to
Mechanical Interlock
– Verify proper operation with an ohmmeter
Isolation switch auxiliary contacts
– Verify wires are intact and properly inserted
Temperature Sensing Wires (3 places)
Verify proper operation
Outer jaws must securely contact the center
Isolation switches
Tug test on all cable connections
Door Grounding Straps
Transformer Temperature Protection Relay
stab in the closed position
– Check all connections per Electrical Drawings
Secondary Wiring and Low Voltage Fuses
Door Grounding Straps
Front
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 35
glanding plate are undamaged
– Verify cables are properly fed through the
Transformer Secondary Cables
– Check braided copper connections
Surge Arrestors
– Verify connection
Line and Load side power cables
– Check electrical connection
Top Mounted Cooling Fans
– Verify phasing and torque
Top Ground Bus
Rear
Tap Changer
Pe rform tug tes t
Voltage Sensing Relay Cables
structure
– Assembly must be affixed properly to
Fan H ousi ngs
Verify braided connections
Page 36
Chapter 3 Preparation and Inspection (For UL)
IMPORTANT

Interconnection Review

Table 10 - Interconnection Review Checklist (UL)
Bypass Cabinet (if supplied) Isolation Transformer Cabinet Power Module Cabinet Low Voltage Control Cabinet
Verify the braided ground connection to adjacent cabinet(s) is properly installed
Review the braided ground connection to adjacent cabinet
Verify line and load power cables from Isolation Transformer Cabinet are properly connected
Front Inspection
Verify all control wires per Electrical Drawing
The interconnection checklist summarizes the required items to review to validate the reconnection of power, ground, and control cables between cabinets within the drive system, that were disconnected for shipment. Power and control cables that pass from one cabinet to another are bundled in the appropriate cabinet. These cables are connected for system test at the factory but disconnected and coiled up for shipment. If this interconnection work was done by the contractor, use this checklist to review and ensure the work was done correctly. If the interconnection work was not done by the contractor, the scope of work required to be performed is described in 6000-IN006_-EN-P
.
.
Check torque on all power and ground cable connections per specifications listed in Torque Requirements
Verify the braided ground connection to adjacent cabinet(s) is properly installed
Review all isolation transformer secondary wiring from Power Module cabinet (2 sets)
Verify that the shields of all of the system’s connecting wires are properly grounded
Verify all control wires per Electrical Drawing
– Cables are run in LV cable
sections along front and back of cabinet
Verify the braided ground connection to adjacent cabinet(s) is properly installed
Verify that the shields of all of the system’s connecting wires are properly grounded
Review load power cable connection from Isolation Tra nsf orm er C abi net
Verify Voltage Sensing Board power cables from Power Module Cabinet are properly installed
Verify that the two plugs from the LV Control Cabinet and Isolation Transformer Cabinet are properly installed
on page 109.
Verify control signal wiring bundles from LV Control cabinet to LV panel in Isolation Transformer cabinet and LV panel in the Bypass Cabinet (if supplied) are routed correctly
36 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 37
Preparation and Inspection (For UL) Chapter 3

Installation Review

Prior to commencing the commissioning of the drive, verify the equipment was properly installed. Identifying errors in the drive installation prior to commencing the commissioning as opposed to mid-way through the commissioning process will greatly reduce the amount of time required to commission the drive. Verify the drive and all associated equipment have the system power grounding cable installed. Refer to 6000-IN006_-EN-P
to review the contractor’s drive installation responsibilities and understand the scope of the work you will be reviewing.
Mechanical Installation Inspection
Sequence Task Reference Document
1 Verify line up positioning Dimensional Drawings
2 Verify cabinets are bolted together correctly 6000-IN006_-EN-P
3 Verify cabinets are affixed to the floor properly Dimensional Drawings,
6000-IN006_-EN-P
4 Verify fans are installed correctly 6000-IN006_-EN-P
5 Verify power modules are installed correctly 6000-IN006_-EN-P
6 Review duct installation (if applicable) 6000-IN006_-EN-P
7 Verify the cable trenches meet design requirements 6000-IN006_-EN-P
8 Verify required cabinet clearances 6000-IN006_-EN-P
9 Verify there are no scratches or damage to the cabinet body N/A
10 Verify the top cover of the isolation transformer cabinet is securely
mounted
6000-IN006_-EN-P
Refer to project-specific EDs to review all electrical connections to external input and output devices.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 37
Page 38
Chapter 3 Preparation and Inspection (For UL)
Electrical Installation Inspection
Sequence Task Reference
Document
1 Verify that medium voltage cables are separated at least 30 cm from the control cables
2 Verify that all secondary control wiring use shielded cables
3 Verify that input and output medium voltage cables specifications meet the stated
insulation requirements
4 Verify that input and output medium voltage cables have attached nameplates
5 Verify the diameter of control power cables comply with the drawings Electrical
6 Verify that the electrical safety circuit wiring between the input circuit breaker and the drive
7 Verify the wiring between the DCS and the drive is shielded and only the end the drive side is
8 Verify that the user-provided ground cable is ≥50 mm
9 Verify the isolation transformer’s primary input voltage matches the system primary voltage
10 Verify that the customer motor specifications match the drive voltage and current
11 Verify that the isolation transformer’s input si de wiring is correct Electrical
12 Verify that the motor output side wiring is correct Electrical
13 Verify all external control wiring is terminated correctly and to the proper terminal blocks Electrical
14 Verify torque on incoming line power cable and outgoing motor powe r cable terminations Electrical
is shielded and only the end at the drive side is grounded
grounded
2
capabilities
Electrical Drawings
Drawings
Drawings
Drawings
Drawings
Drawings
Power Cabling
Trace the power cabling from termination point to termination point while examining the cable and its routing for mechanical damage, sharp bend radiuses and sources of induced noise and heat. The power cabling must be is sufficiently braced to contain the cabling in the event of a ground fault. Color coding is used to indicate the phase orientation of the drive.
Table 11 - Color Coding (UL)
Color Incoming Line Side Outgoing Motor Side
Black L1 (A Phase) Line Cable Terminal U Phase:
Red L2 (B Phase) Line Cable Terminal V Phase:
Blue L3 (C Phase) Line Cable Terminal W Phase:
Power Module Bus
VSB Input Cable
Motor Cable Termination
Motor Cable Connection to Power Module Bus
Power Module Bus
VSB Input Cable
Motor Cable Termination
Motor Cable Connection to Power Module Bus
Power Module Bus
VSB Input Cable
Motor Cable Termination
Motor Cable Connection to Power Module Bus
38 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 39
Preparation and Inspection (For UL) Chapter 3
Incoming Line and Outgoing Motor cables must be routed separately to prevent cable insulation damage.
All cables must be terminated on each end and sufficiently torqued.
All customer power cables must be Hi-Potted or Meggered and read a sufficient insulation value. Review Hi-Pot or megger test report from the customer.
Control Wiring
Identify all customer-required control wiring detailed on the Electrical Drawings and locate it within the terminal blocks. Verify the cable insulation is not tightened in a terminal connection. All connections must have proper continuity.
Inspect the control cable routing to ensure that DC control wiring and AC control wiring are separated from each other. Routing them together in the same bundle or cabling product may result in unwanted noise being induced in the drive control. In the overhead cable tray provided at the front of the drive, the AC control, DC control and fiber optic cables must be separate. These cables may also be from the bottom.

Drive Megger Check

Control wiring must be routed separately from power cabling.
Inspect for additional control not shown on the Electrical Drawings. Determine its purpose, mark the changes on the electrical diagram and send the prints to the Start-up Project Manager for future reference.
Perform a tug test on all control cables to ensure that they are securely fastened, and check each plug and connector to ensure it is properly seated in its socket.
Isolate the Power and Control Circuits
ATT EN TI ON : Verify the grounding cable connection is secure.
Disconnect the low voltage power before the megger test. Short circuit the 3 input cables and 3 output cables on one point.
1. Isolate and lock out the drive system from any high voltage source.
Disconnect any incoming power sources, medium voltage sources should be isolated and locked out and all control power sources should be turned off at their respective circuit breaker(s).
Verify with a potential indicator that power sources have been disconnected, and that the control power in the drive is de-energized.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 39
Page 40
Chapter 3 Preparation and Inspection (For UL)
VSB Board Cable connected to
Transformer Cabinet
2. Disconnect four 380V AC cables (a, b, c, and o cables) from the bottom of the Isolation Transformer.
Figure 13 - 380V AC Bottom-mounted Auxiliary Fan Input Cables (UL)
3. Disconnect the Voltage Sensing Board Output Cable. Keep the plug at least 100 mm away from the Voltage Sensing Board.
Figure 14 - Voltage Sensing Board Output Connection Cable (UL)
4. Disconnect the Isolation Transformer Temperature Monitor. Keep the plug at least 100 mm away from the connection point on the Monitor.
Figure 15 - Isolation Transformer Temperature Monitor (UL)
40 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 41
Preparation and Inspection (For UL) Chapter 3
Miniature Circuit Breakers
Miniature Circuit Breakers
Top Main Cooling
Fan Cir cuit Bre akers
5. Switch the miniature circuit breakers in the LV Cabinet off.
Figure 16 - Control Switches (UL)
6. Switch the miniature circuit breakers in the Isolation Transformer Cabinet LV Control panel off. Switch the Top Main Cooling Fan circuit breakers off.
Figure 17 - Control Switches (UL)
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 41
Page 42
Chapter 3 Preparation and Inspection (For UL)
Control Cable
HECS (located on the right side of the power unit cabinet
7. Remove two star connection cables (the cabling that goes through the HECS) and connect them to the output connections of any two power modules within a phase.
Figure 18 - Star Connection Cable (UL)
8. Disconnect the control cable of HECS.
Figure 19 - Hall Effect Current Sensor (UL)
42 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 43
Preparation and Inspection (For UL) Chapter 3
Control Board Power Cables
HMI Power Cable
Analog Interface Board location on Control Unit
Control Unit terminals
9. Disconnect the HMI and Control Board power cables.
Figure 20 - Back of HMI
10. Remove the Analog Interface board and disconnect all of the terminals from the Control Unit.
Figure 21 - Back of Control Unit
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 43
Page 44
Chapter 3 Preparation and Inspection (For UL)
Connect the Insulation Meter
1. Connect the red wire from the insulation meter to the U Phase and the black wire to the grounding bus.
ATTENTION: Verify the drive and any connected equipment is clear of personnel and tools prior to commencing the Megger test. Barricade off any open or exposed conductors. Conduct a walk-around inspection before commencing the test.
2. Use jumper wires to make the connections as shown in Figure 22
.
The jumper wires must be rated for greater than 5 kV or must maintain sufficient clearance to any metal surface.
3. If the Megger has a lower voltage setting (normally 500V or 1000V), apply that voltage for 5 seconds as a precursor for the higher voltage rating. This may limit the damage if there is a problem. If the reading is very high, apply the test voltage per Figure 22
.
4. Perform a Megger test with the insulation meter voltage set according to the voltages shown in Ta b l e 1 2
for 1 minute and record the result.
The test should produce a reading greater than the minimum values listed below. If the test results produced a value lower than these values start segmenting the drive system down into smaller components and repeat the test on each segment to identify the source of the ground fault.
ATTENTION: Discharge the Megger prior to disconnecting it from the equipment.
44 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 45
Preparation and Inspection (For UL) Chapter 3
Ground Bus Bar
Insulation Meter
Incoming Line Power
Cable Connections
5. Disconnect the Insulation Meter and jumpers installed in steps 1 and 2.
6. Reconnect all wires, cables, and connections in reverse order of removal.
Figure 22 - Connected Insulation Meter (UL)
Table 12 - Insulation Test Voltage Values
Drive Rated Voltage U1 Insulation Resistance Test Direct Voltage (V)
1000<U1≤5000 2500
5000<U1 5000
Typical of Drive Minimum Megger Value
Entire Drive 1 kM Ohm
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 45
Page 46
Chapter 3 Preparation and Inspection (For UL)
IMPORTANT
Apply silicone as
shown by bold lines

Final Steps before Equipment is Ready for Energization

1. Review interior of all cabinets for foreign material that might have been left behind during the installation process. Ensure no tools, hardware, or wiring debris remain in the drive system cabinets. Clear any metal shavings that may result from any drilling activities.
2. If any internal barriers were removed during the commissioning process, ensure they are reinstalled.
Seal the Cabinet Plates
Once the back plates have been reattached, the seams along the plates must be sealed with silicone. Where the silicone is applied is dependent on the cabinet configuration (Fixed-mounted or Drawout Power Module).
Use the approved silicone that is shipped with the drive.
Figure 23 - Silicone Locations on Fixed-mounted Power Module Configuration
46 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 47
Commissioning
Chapter 4

Introduction

ATT EN TI ON : The Control System Check requires LV Control power only. The
Input Circuit Breaker must remain locked out and tagged out for this procedure.
A number of activities are required before the Control System Check can be performed.
Procedure Page
Simulate Closed Input Circuit Breaker
Energize Control Ci rcuit 48
48
The complete Control System Check requires the following procedures to be performed.
Procedure Page
Verify Factory Default Settings 52
Set P Parameters to Enable Testing 55
Verify Settings for Low-Voltage Testing 58
Verify Operation of Frequency Steps 63
Verify Operation to Set Frequency 65
Simulate Warnings and Faults 65
Verify E-Stop Functionality 72
Verify Switching from Local Control to Remote Control 73
Verify Operation of Input/Output and Bypass Isolation Switches (Manual Bypass)
Verify Operation of Input/Output and Bypass Contactors (Automatic Bypass)
Verify Operation of DCS Input and Output Signals 83
Restore P Parameter Settings 84
(1)
(1)
74
77
(1) Only required if a bypass configuration is supplied.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 47
Page 48
Chapter 4 Commissioning
IMPORTANT
Control Power Transformer
UPS
REAR
FRONT

Control System Check Setup

Simulate Closed Input Circuit Breaker
The “normal” operating mode is for the input circuit breaker to be closed. Install a temporary jumper (X1-117, X1-119) in the LV Control Cabinet to simulate operating the system in “normal” mode (input circuit breaker closed) to allow the Control System Check process to proceed.
Refer to Electrical Drawings.
Energize Control Circuit
Before beginning this process, ensure that the customer's control power supply breaker is closed and control power is available.
Control power voltage used in the control circuit is nominally 220V and referred to in the example. The control circuit can directly accommodate other widely used voltages of 230V and 240V also. If 110V or 120V is the control power voltage supplied by the customer, a control power transformer is supplied in the LV control cabinet to step up the customer supplied control power to 220V (Figure 24
Q1 (CB1), Q2 (CB2), Q3 (CB3), Q5 (CB5), and Q6 (CB6) miniature circuit breaker designations are located in the LV Control Cabinet (Figure 25 (CB4) and Q7 (CB7) miniature circuit breaker designations are located in the LV Control panel of the Isolation Transformer Cabinet (Figure 26 Electrical Drawings.
). This must be specified at time of order.
). The Q4
). Refer to the
Test points indicated in the instructions are at the circuit breaker terminals, not at the terminal blocks.
Circuit breaker device designation labels (Q1 (CB1), Q2 (CB2), etc.) are affixed to the device mounting surfaces.
Figure 24 - UPS and CPT Mounting Plate (Top View)
48 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 49
Figure 25 - LV Control Cabinet
135
246
Q1
(CB1)Q2(CB2)
Q3
(CB3)
Q6
(CB6)
Q5
(CB5)
Q7Q4
For IE C For UL
Commissioning Chapter 4
Figure 26 - LV Panel in the Isolation Transformer Cabinet
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 49
Page 50
Chapter 4 Commissioning
Table 13 - Energize Control Circuit Sequence (For IEC)
Item Before Closing Breaker After Closing Breaker Comments
Close Breaker Q1
Verify that the input voltage at the Q1 circuit breaker is AC220V (1 is L, 3 is N). Verify output is not shorted (2 and 4). Verify OPEN state (5 and 6).
Verify that the output voltage is AC220V (2 is L, 4 is N). Verify CLOSED state (5 and 6).
Q1 connects customer-supplied control power to the control circuit (UPS).
Start UPS (Press ON button)
Close Breaker Q2
Close Breaker Q3
Close Breaker Q4
Close Breaker Q5
Close Breaker Q6
Close Breaker Q7
Before pressing the ON button, withdraw the Type I UPS power plug from the power receptacle (XS2). Verify that the input voltage of the XS2 receptacle is AC220V. Verify that the PE connection of the XS2 receptacle is properly grounded. Plug the UPS into the receptacle. Press and hold the ON button for 3 seconds to turn on the UPS (all status lights on the UPS will be green).
Verify that the input voltage at the Q2 circuit breaker is AC220V (1 is L, 3 is N). Ignore if done in “Start UPS” step. Verify output is not shorted (2 and 4).
Verify that the input voltage at the Q3 circuit breaker is AC220V (1 is L, 3 is N). Ignore if done in “Start UPS” step. Verify output is not shorted (2 and 4). Verify OPEN state (5 and 6).
Control power is fed from the isolation transformer tertiary winding for the Q4 circuit breaker, therefore not present for this test. A two pole breaker is supplied for lower power drives (220V powered auxiliary fans). A three pole breaker is supplied for higher power drives (380V power auxiliary fans). Verify open status (1 and 2) and output not shorted (2 and 4).
Control power is fed from the isolation transformer tertiary winding for the Q5 circuit breaker, therefore not present for this test. Verify open status (1 and 2) and output not shorted (2 and 4).
Verify that the input voltage at the Q6 circuit breaker is AC220V (1 is L, 3 is N). Verify output is not shorted (2 and 4).
Verify that the input voltage at the Q7 circuit breaker is AC220V (1 is L, 3 is N). Verify output is not shorted (2 and 4).
Verify that UPS operates normally and that the UPS output is AC220V. The output of the UPS is connected to the input of Q2 and Q3. The UPS output voltage can be checked at the input of Q2 or Q3 (1 is L, 3 is N).
Verify that the input voltage of power supplies is AC220V (L-N). Refer to Figure 27 PLC, HMI, and Control Unit power up.
Verify that the output voltage is AC220V (2 is L, 4 is N). Verify CLOSED state (5 and 6). Verify that the PLC I/O status lights and control relay red indicating lights illuminate.
Verify closed status (1 and 2). Q4 connects control power from isolation
Verify closed status (1 and 2). Q5 connects back-up control power from
Verify that the output voltage is AC220V (2 is L, 4 is N). Verify that the LV Door pilot lights illuminate.
Verify that the output voltage is AC220V (2 is L, 4 is N). Verify that the Isolation Transformer temperature monitor powers up.
. Verify that the
UPS feeds control power to the circuits supplied by the Q2 and Q3 circuit breakers.
Q2 connects control power directly to AC/DC power supplies (G1, G2, and G3), PLC, HMI, and Control Unit
Q3 connects control power to PLC I/O and control relays.
transformer tertiary winding to bottom­mounted auxiliary fans (6).
isolation transformer tertiary winding to switch to the control circuit (UPS) if the main (customer­supplied) control power is lost.
Q6 connects control power to door mounted pilot lights and spare relays for DCS.
Q7 connects control power to isolation transformer temperature monitor
ATT EN TI ON : The following should be opened successively when the control power is switched off: Q5, Q4, Q3, Q2 and UPS; opening Q1 is not necessary when the control power is not disconnected.
Table 14 - Energize Control Circuit Sequence (For UL)
Item Before Closing Breaker After Closing Breaker Comments
Close Breaker CB1
Start UPS (Press ON button)
Close Breaker CB2
50 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Verify that the input voltage at the CB1 circuit breaker is AC220V (1 is L, 3 is N). Verify output is not shorted (2 and 4). Verify OPEN state (5 and 6).
Before pressing the ON button, withdraw the Type I UPS power plug from the power receptacle (XS2). Verify that the input voltage of the XS2 receptacle is AC220V. Verify that the PE connection of the XS2 receptacle is properly grounded. Plug the UPS into the receptacle. Press and hold the ON button for 3 seconds to turn on the UPS (all status lights on the UPS will be green).
Verify that the input voltage at the CB2 circuit breaker is AC220V (1 is L, 3 is N). Ignore if done in “Start UPS” step. Verify output is not shorted (2 and 4).
Verify that the output voltage is AC220V (2 is L, 4 is N). Verify CLOSED state (5 and 6).
Verify that UPS operates normally and that the UPS output is AC220V. The output of the UPS is connected to the input of CB2 and CB3. The UPS output voltage can be checked at the input of CB2 or Q3 (1 is L, 3 is N).
Verify that the input voltage of power supplies is AC220V (L-N). Refer to Figure 27 PLC, HMI, and Control Unit power up.
. Verify that the
CB1 connects customer-supplied control power to the control circuit (U PS).
UPS feeds control power to the circuits supplied by the CB2 and CB3 circuit breakers.
CB2 connects control power directly to AC/DC power supplies (G1, G2, and G3), PLC, HMI, and Control Unit
Page 51
Table 14 - Energize Control Circuit Sequence (For UL)
N
N
L
L
Close Breaker CB3
Close Breaker CB5
Verify that the input voltage at the CB3 circuit breaker is AC220V (1 is L, 3 is N). Ignore if done in “Start UPS” step. Verify output is not shorted (2 and 4). Verify OPEN state (5 and 6).
Control power is fed from the isolation transformer tertiary winding for the CB5 circuit breaker, therefore not present for this test. Verify open status (1 and 2) and output not shorted (2 and 4).
Commissioning Chapter 4
Verify that the output voltage is AC220V (2 is L, 4 is N). Verify CLOSED state (5 and 6). Verify that the PLC I/O status lights and control relay red indicating lights illuminate.
Verify closed status (1 and 2). CB5 connects back-up control power from
CB3 connects control power to PLC I/O and control re lays.
isolation transformer tertiary winding to switch to the control circuit (UPS) if the main (customer­supplied) control power is lost.
Close Breaker CB6
Close Breaker CB7
Verify that the input voltage at the CB6 circuit breaker is AC220V (1 is L, 3 is N). Verify output is not shorted (2 and 4).
Verify that the input voltage at the CB7 circuit breaker is AC220V (1 is L, 3 is N). Verify output is not shorted (2 and 4).
Figure 27 - AC/DC Power Supplies
Verify that the output voltage is AC220V (2 is L, 4 is N). Verify that the LV Door pilot lights illuminate.
Verify that the output voltage is AC220V (2 is L, 4 is N). Verify that the Isolation Transformer temperature monitor powers up.
CB6 connects control power to door mounted pilot lights and spare relays for DCS.
CB7 connects control power to isolation transformer temperature monitor
ATT EN TI ON : The following should be opened successively when the control power is switched off: CB5, CB3, CB2 and UPS; opening CB1 is not necessary when the control power is not disconnected.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 51
Page 52
Chapter 4 Commissioning
IMPORTANT
TIP

Control System Check

Verify Factory Default Settings
Confirm Language, Bypass Mode, and Local Operation
The default Language setting and bypass mode are set before shipment.
You can change the language but cannot change the bypass mode, as this is set at the factory to match the shipped drive configuration.
1. Press in the System Parameter Settings
interface screen.
2. In the Languages
3. Press to accept and proceed to the Main Interface
Screen.
Detailed information about the HMI screens is included in publication
6000-UM002_-EN-P,
Drive User Manual.
dialog box, select the language you want and press
.
PowerFlex 6000 Medium Voltage Variable Frequency
52 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 53
Commissioning Chapter 4
No Bypass Cabinet
Manual Bypass Cabinet
4. Press and confirm the Bypass Configuration matches one of the five Input Supply graphics.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 53
Page 54
Chapter 4 Commissioning
Automatic Bypass Cabinet
Note the Contactor Operation selection appears when Automatic Bypass is selected
Manual Bypass Two Cabinets
Automatic Bypass Two Cabinets
Note the Contactor Operation selection appears when Automatic Bypass is selected
5. Und er Control Owner Selection, press .
54 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 55
Commissioning Chapter 4
The Select Local Control? dialog box appears.
6. Select to confirm Local Control, and press to
return to the Main Interface Screen.
Set P Parameters to Enable Testing
There are two specific “P” parameters that must be changed to allow the Control System Check to proceed.
This section is password protected and the setup login process must be completed before making any changes.
Access Setup Settings
1. Press from the Main Interface Screen.
2. Press under Parameter Access Level
.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 55
Page 56
Chapter 4 Commissioning
TIP
IMPORTANT
The Setup Login dialog box appears. Press .
3. Enter the User and Password details.
Press and enter “setup”. Press when finished.
Press to enter the password. Press when finished.
The password will be sent by the Project Start-up Manager.
4. Press to login.
The Current User will now display Setup, indicating appropriate access has been granted.
5. Once logged in, press to proceed.
If the login information was incorrect, you will be prompted to login again.
Set P Parameters
Once the appropriate access has been granted, you can now select and change parameters.
For the simulation tests, you only need to change two parameters: P007 and P224.
56 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 57
Commissioning Chapter 4
TIP
1. Press in the Setup Parameter Type.
2. Press the P007 parameter input field.
WARNING: Do NOT press . This will reset all factory-set parameters.
When the “P” Parameter number is pressed (e.g. P007), the description appears in the information box at the bottom of the screen.
.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 57
Page 58
Chapter 4 Commissioning
IMPORTANT
3. Press “0” on the keypad dialog and press .
Parameter 007 will now show a value of “0”.
4. Repeat steps 2 and 3 to change Parameter 224 to “120”.
Verify Settings for Low-Voltage Testing
The following settings are for low-voltage testing only.
Before performing high-voltage testing, the “Power Loss” setting must be restored to the unshielded state.
1. Press from the Main Interface Screen.
2. Press under Parameter Access Level
The R&D Login dialog box appears. Press .
.
58 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 59
Commissioning Chapter 4
IMPORTANT
3. Enter the User and Password details.
Press and enter “RD”. Press when finished.
Press and enter “668”. Press when finished.
4. Press to login.
The Current User will now display RD, indicating appropriate access has been granted.
5. Once logged in, press to proceed.
If the login information was incorrect, you will be prompted to login again.
Set P Parameters
Once the appropriate access has been granted, you can now select and change parameters.
1. Press under P Parameter Settings
.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 59
Page 60
Chapter 4 Commissioning
2. Press “499” on the keypad dialog and press .
will now show a value of “499”.
3. Press and enter “1”. Press when finished.
4. Press . The should display “1.00”.
5. Press to view the Fault Masks screen.
60 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 61
Commissioning Chapter 4
For IEC Standard
6. Press and . The buttons should change
to and respectively.
.
WARNING: Before performing the high-voltage test, press
to change back to and keep current blocked because there is no hardware detection in IEC)
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 61
Page 62
Chapter 4 Commissioning
IMPORTANT
For UL Standard
7. Press to change the button to .
.
8. Press to return to P Parameter Settings and continue with low-voltage testing.
After the end of the simulation tests, the “Power Loss” setting must be restored to the unshielded state.
9. Press to exit P Parameter Settings, and . Press
to confirm Setup has logged out.
10. Press to return to the Main Interface Screen.
62 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 63
Commissioning Chapter 4
TIP
TIP
Verify Operation of Frequency Steps
There are two parts to this procedure, increasing the frequency in set increments and increasing the frequency to a specific rated frequency.
During the Control System Check procedure, an “Abnormal Output Voltage Warning” will appear, as the procedure is done without MV and the Control System is expecting an output voltage. Ignore this warning for this procedure.
Increase Frequency by Step
1. From the Main Interface Screen, press the Set Frequency: input field.
2. In the Set Freq: dialog box, enter a value of “10” and press .
Press to confirm.
The Set Frequency and Actual Frequency occasionally will not show the exact integral value selected, due to internal data conversion in the HMI program.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 63
Page 64
Chapter 4 Commissioning
IMPORTANT
TIP
3. Press , and press in the Start Drive? dialog box to confirm operation.
When the drive is 0.5 Hz, the “Connect” light will be illuminated. When the speed of the drive surpasses 0.5 Hz, the “Connect” and “Running” lights will be red. The “Warning” light will illuminate when the Actual Frequency increases above 10.00 Hz. This is an internal function for testing purposes only.
4. When the Actual Frequency reaches 10 Hz, press .
Press in the Accel Speed by Step? dialog box.
T Parameter T09 determines the value of the frequency step change. The default is 1. Refer to Access T Parameters
on page 86.
The Set Frequency and Actual Frequency are now 11 Hz.
64 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 65
Commissioning Chapter 4
5. Press and press in the Decel Speed by Step? dialog box.
The actual frequency will decrease by 1 Hz.
Verify Operation to Set Frequency
1. Press the Set Frequency: input field and enter “50” in the Set Freq: dialog
box and press .
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 65
Page 66
Chapter 4 Commissioning
2. Press to accept and begin the simulation.
Actual Frequency: will show the frequency increasing to 50 Hz.
3. Once the actual frequency has reached the set frequency, press
and press in the Stop Drive? dialog to confirm
action.
The actual frequency will decrease to 0 Hz.
66 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 67
Commissioning Chapter 4
Simulate Warnings and Faults
This section describes how to simulate warnings and faults, and how to clear or reset the alarm. Warning codes begin with a W prefix, and fault codes begin with a F prefix.
Alarm Self-clearing Requires Reset
Transformer Overtemperature Warning YES
Transformer Overtemperature Trip YES
Transformer Cabinet Main Cooling Fan Fault YES
Power Module Cabinet Main Cooling Fan Fault YES
Cabinet Door Open Warning
Left Isolation Transformer Cabinet DoorRight Isolation Transformer Cabinet DoorLeft Power Module/LV Cabinet DoorRight Power Module/LV Cabinet DoorBypass Cabinet Door (if applicable)
The Set Frequency: field will already have 50 Hz shown from the previous exercise in the Set Freq: dialog box.
YES
1. Press , and press in the Start Drive? dialog box.
Simulate the Transformer Overtemperature Warning
1. Start the drive, then open the door of the Control cabinet.
2. In the control cabinet, remove the wire from terminal block 419. This
triggers the transformer overtemperature warning alarm.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 67
Page 68
Chapter 4 Commissioning
3. Press to view alarm record.
.
4. Replace the wire for terminal block 419 and tighten properly to remove the warning.
Simulate Transformer Overtemperature Trip
1. Start the drive, then open the door of the Control cabinet.
2. In the Control cabinet, remove the wire from terminal block 418. This
triggers the transformer overtemperature trip alarm.
3. Press to view the alarm record.
4. Replace the wire for terminal block 418 and tighten properly to remove the
trip message.
5. Press to return to the Main Interface Screen.
68 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 69
Commissioning Chapter 4
TIP
6. Press , and press to confirm the operation in the Reset Drive? dialog box.
Wait until the Ready status indicator is red before starting another simulation.
Simulate a Transformer Cabinet Main Cooling Fan Fault
1. Set the frequency to 10 Hz and start the drive.
2. Open the LV door of the Isolation Transformer cabinet.
The circuit breakers for the main cooling fans for the entire drive are located here.
3. Turn the first motor control circuit breaker (Q10 for IEC and CB10 for UL), controlling the Isolation Transformer Cabinet Main Cooling Fans (one per fan), to the OFF position.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 69
Page 70
Chapter 4 Commissioning
TIP
4. Press to confirm the Transformer Cabinet Main Cooling Fan Fault.
5. After the fault is reported, the drive is in a fault stop state.
6. Turn the first (Q10 for IEC and CB10 for UL) circuit breaker to the ON
position, to remove the fault.
7. Press to return to the Main Interface Screen.
Simulate a Power Module Cabinet Main Cooling Fan Fault
1. Set the frequency to 10 Hz and start the drive.
2. Open the LV door of the Isolation Transformer cabinet.
From left to right on the DIN rail in the LV cabinet, the main cooling fan circuit breakers are located first for the Isolation Transformer cabinet then the Power Module cabinet.
Almost all drive configurations will have a maximum of three main cooling fans for the Isolation Transformer Cabinet. Therefore, the main cooling fan circuit breaker designations of Q10, Q11, and Q12 are reserved for the Isolation Transformer Main Cooling Fans. Power Module Cabinet Main Cooling Fan circuit breaker designations begin at Q13.
Refer to the appendix in 6000-IN006_-EN-P cabinet location, or look at the fans on the top plate of the drive.
3. Turn the applicable motor control circuit breaker (Q13 for IEC and CB13 for UL), controlling the Power Module Main Cooling Fans (one per fan), to the OFF position.
to determine the number of main cooling fans in each
70 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 71
Commissioning Chapter 4
4. Press and confirm the Power Module Cabinet Fan Fault.
5. After the fault is reported, the drive is in a fault stop state.
6. Turn the (Q13 for IEC and CB13 for UL) circuit breaker to the ON
position, to remove the fault.
7. Press to return to the Main Interface Screen.
Simulate Cabinet Door Open Warning
1. Open the left Isolation Transformer Cabinet door.
2. Press to confirm the Cabinet Door Open Warning.
The drive will shut off.
3. Close the left Isolation Transformer Cabinet to remove the warning.
4. Repeat this procedure using the:
Right Isolation Transformer Cabinet door
Left Power Module/LV Cabinet door
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 71
Page 72
Chapter 4 Commissioning
Right Power Module/LV Cabinet door
Bypass Cabinet door (if applicable)
5. Press to return to the Main Interface Screen.
6. Press to remove the fault. Press to confirm operation in the Reset Drive? dialog.
Verify E-Stop Functionality
1. Press on the Main Interface Screen to start the drive.
2. Push the E-stop button on the front of the LV Control cabinet.
3. Press and confirm the E-stop Trip fault.
4. Twist to pull out the E-stop button on the front of the LV Control cabinet.
72 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 73
Commissioning Chapter 4
5. Press to return to the Main Interface Screen.
6. Press to remove the fault. Press to confirm operation in the Reset Drive? dialog.
Verify Switching from Local Control to Remote Control
Depending on whether the drive has an automatic or manual Bypass or no Bypass configuration, the Operation Interface screen will be different.
1. Press from the Main Interface Screen.
2. Press in the Control Owner Selection
.
3. Press in the Select Remote Control? dialog.
4. Press to return to the Main Interface Screen and confirm Remote status indicator light is on.
5. Press from the Main Interface Screen.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 73
Page 74
Chapter 4 Commissioning
6. Und er Control Owner Selection, press .
7. Select to confirm selection in the Select Local Control? dialog,
and press to return to the Main Interface Screen and confirm the Local status indicator is on.
Verify Operation of Input/Output and Bypass Isolation Switches (Manual Bypass)
Input/Output Isolation Switches
1. Press from the Main Interface screen.
74 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 75
Commissioning Chapter 4
2. Open the Bypass cabinet door, and close QS2 and QS3.
Verify the Input and Output contactors are closed on the HMI.
3. Close the customer-supplied input circuit breaker by installing a temporary jumper wire (X-117, X-119).
Verify the input circuit breaker is closed.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 75
Page 76
Chapter 4 Commissioning
Bypass Isolation Switches
1. Press from the Main Interface screen.
2. Open the Bypass cabinet door, and close QS1.
Verify the bypass isolation switch is closed on the HMI.
76 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 77
Commissioning Chapter 4
IMPORTANT
3. Close the customer-supplied input circuit breaker by installing a temporary jumper wire (X-117, X-119).
Verify the input circuit breaker is closed.
Verify Operation of Input/Output and Bypass Contactors (Automatic Bypass)
Input/Output Drive Contactors
Turn the 3-position on the selector switch on the front of the LV Cabinet to the Drive position.
1. Press from the Main Interface screen.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 77
Page 78
Chapter 4 Commissioning
2. Close the customer-supplied input circuit breaker by installing a temporary jumper wire (X-117, X-119).
Verify the input circuit breaker is closed.
3. Press under Contactor Operation confirm.
, and press to
78 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 79
Verify the input and output drive contactors are closed.
Commissioning Chapter 4
4. Press under Contactor Operation confirm.
.
, and press to
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 79
Page 80
Chapter 4 Commissioning
IMPORTANT
5. Verify the input and output drive contactors are open.
Bypass Contactors
Turn the 3-position on the selector switch on the front of the LV Cabinet to the Bypass position.
1. Press from the Main Interface screen.
.
80 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 81
Commissioning Chapter 4
2. Press under Contactor Operation, and press to confirm.
.
Verify the bypass contactor is closed.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 81
Page 82
Chapter 4 Commissioning
3. Press under Contactor Operation, and press to confirm.
.
Verify the bypass contactor is open.
82 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 83
Commissioning Chapter 4
Verify Operation of DCS Input and Output Signals
Figure 28 - Status Indicators
Table 15 - Drive to DCS
Signal Name Terminal Number HMI Status Terminal Open Terminal Closed
MVPRE-Closed CB 901-902 Allowed Red Grey
MV CLOSING 903-904 MVClosd Red Grey
Warning 905-906 Warning Red Grey
Fault 907-908 Warning Red Grey
Drive running 909-910 Running/Connect Red Grey
Drive STOP 911-912 Running/Connect Red Grey
READY 913-914 Ready Red Grey
DCS control 915-916 Remote Red Grey
Local Grey Red
Table 16 - 4-20 mA
Output Current 925-926 Motor Cu rrent 0-Rated Current
Output Frequency 927-928 Actual Frequency 0-Rated Frequency
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 83
Page 84
Chapter 4 Commissioning
When the two terminals specified are shorted, verify the result shown in the third column occurs.
Table 17 - DCS to Drive
Signal Name Terminal Number Function
Fault Reset 412-401 Reset System
DCS Start 449-401 Start Drive
DCS Stop 450-401 Stop Drive
E-stop 1101-1101 E-stop Drive
Frequency Set 931-402 Set Drive Frequency
Restore P Parameter Settings
1. Press , and press under Parameter Access Level.
The Setup Login dialog box appears. Press .
2. Enter the User and Password details.
Press to enter user details. Press when finished.
Press to enter password details. Press when finished.
84 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 85
Commissioning Chapter 4
3. Press to login.
4. Press , and press .
WARNING: Do NOT press Reset. This will reset all factory-set parameters.
5. Press the P007 parameter field to enter the number of power cells per
phase, and press .
6. Press the P224 parameter field .
7. Change the value from 120 to 80. Press , and press .
8. Press to exit P Parameter Settings
, to confirm
Setup has logged out, and to return to the Main Interface Screen.
WARNING: Remove the temporary jumper (X1-117, X1-119) in the LV Control Cabinet, which was installed to enable the Control System Test.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 85
Page 86
Chapter 4 Commissioning
TIP

Set Date and Time Zone

To access the Date and Time Zone settings, you must exit the PowerFlex 6000 HMI to Windows CE.
Access T Parameters
1. Press from the Main Interface Screen.
2. Press under Parameter Access Level.
The Setup Login dialog box appears. Press .
3. Enter the User and Password details.
4. Press to login.
5. Once logged in, press .
6. Press in the Setup Parameter Type
7. Press the T10 parameter input field. Enter “555” and press .
8. Press and to confirm.
.
It will take 3...5 minutes to shutdown.
86 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 87
Commissioning Chapter 4
IMPORTANT
Change Time/Date/Regional Settings
Enter the Time Zone settings before changing the date and time.
1. In Windows ME, press Ter mi na l S et tin gs [F 4] .
2. Press the Down Arrow to choose Time/Date/Regional Settings, and press Enter.
3. Choose Time zone and press Enter.
4. Scroll up or down and select the desired time zone.
a. Press Daylight Savings [F1] b. Select the Ye s radio button, and press Close [F8].
5. Press OK [F7].
6. Choose Date and press Enter.
a. Press Yea r [ F1 ], Month [F2], and Day [F3] to set the correct date. b. Press OK [F7].
7. Choose Time and press Enter. a. Press Hour [F1], Minute [F2], and Seconds [F3] to set the correct
time.
b. Press OK [F7].
8. Press Close [F8] twice, Reset [F7], and Yes [ F7 ] to restart the HMI.
9. Select language and bypass mode in the System Parameters Settings
interface.
10. Press to accept and proceed to the Main Interface Screen.
Verify the date and time is updated under Version Info.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 87
Page 88
Chapter 4 Commissioning
Notes:
88 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 89

No-load Test

Chapter 5

Introduction

No-load Test
ATT EN TI ON : Medium Voltage is required for parts of this test. Close and lock all
medium voltage doors on the PowerFlex 6000 and Bypass Cabinet (if supplied) prior to removing Lockout and Tagout provisions and closing the input circuit breaker. All safety related work practices outlined in Electrical Safety requirements for Employee Work places must be followed when removing the input circuit breaker from the locked out, tagged out state.
The No-load Test consists of the following procedures and must be performed in the sequence shown.
Sequence Procedure Page
1 Energize Drive Control Circuit 90
LV
2 Configure P and T Parameters 90
Only
3 Close Isolation Switches in Bypass Cabinet
4 Close Input Circuit Breaker
MV
5 Check Cooling Fan Operation 103
6 Operate Motor by HMI 104
(1) This procedure is performed only if an optional bypass configuration is supplied.
(1)
102
103
WARNING: These procedures must be performed in the order they are listed here. Failure to do so may result in personal injury or death, property damage, or economic loss.
ATT EN TI ON : Isolation switches in bypass cabinets can only be opened or closed when the Input Circuit Breaker is in the open position. Isolation Switches must not be operated when the Input Circuit Breaker is closed.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 89
Page 90
Chapter 5 No-load Test
TIP
Energize Drive Control Circuit
The “Energize Control Circuit” process is already described on page 48. For the “Energize Drive Control Circuit” procedure, repeat the process in the same sequence, without the requirements of taking voltage measurements.
1. Close circuit breaker Q1 (CB1).
2. Start UPS. Press and hold the ON button for approximately 3 seconds.
3. Close circuit breakers Q2 (CB2), Q3 (CB3), Q5 (CB5), and Q6 (CB6) in
the LV Control Panel.
4. Close circuit breakers Q4 (CB4) and Q7 (CB7) in the Isolation Tra ns fo rm er Ca bi ne t LV P an e l .
Configure P and T Parameters
See Set P Parameters to Enable Testing on page 55 for information on how to access and change parameters.
Set the P parameters as shown in Ta b l e 1 8 , and T parameters as shown in
Ta b l e 1 9
.
This table outlines the specific parameters that must be checked and/or modified. Parameters that must be modified are outlined in the Instruction column. All other parameters listed must be verified. For special functions or actions which are not listed here, but are commonly performed while commissioning a drive, see Special Function Parameter Settings
Table 18 - Setup and R&D P Parameters
Parameter Number
P004 Command Source
P005 Restore Factory Settings
P007 Nu mber of Power Cells Per P hase 0 9 9 ON
P008 Motor Rotation Direction Under Local Control
P009 Motor Rotation Direction Command Selection:
P010 Power Cell Fault Mask 0 32767 32767 ON
P017 Number Of Motor Pole Pairs 0 100 2 OFF
P019 Encoder Resolution 0 4096 1024 OFF
Description Min. Max. Default Modify
020OFF
0 = Communication Port 1 = Digital Input 2 = EtherNet/IP
0500OFF
30 = Restore Setup Level 40 = Restore User Level 50 = Restore R&D Level
011OFF
0 = Reverse 1 = Forward
010OFF
0 = Local Control 1 = DCS
on page 117.
Root
90 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 91
Table 18 - Setup and R&D P Parameters (Continued)
No-load Test Chapter 5
Parameter Number
P020 Mask Bit For System Fault 0 32767 32767 ON
P021 Mask Bit For System Warning 0 32767 32767 ON
P022 Mask Bit For Logic Fault A 0 32767 32767 ON
P023 Mask Bit For Logic Fault B 0 32767 32767 ON
P024 Stop Method
P025 Flux Reduction Enable
P026 Power Angle Threshold For Flux Reduction 0 180 0 ON
P027 Time For Flux Reducing 0 32767 5000 ON
P028 Flux Reduction Ratio 0 100 70 ON
P029 Power Angle Threshold For Flux Restore 0 180 0 ON
P030 Powercell Fault Trip Signal Mask Register 0 32767 32767 OFF
P031 System Fault Trip Signal Mask Register 0 32767 32767 OFF
P032 Logic Fault A Trip Signal Mask Register 0 32767 32767 OFF
P033 Logic Fault B Trip Signal Mask Register 0 32767 32767 OFF
P034 Current Stability Loop Filter Time 0 32767 63 ON
P035 Current Stability Loop Output Scaling Factor 0 100 20 ON
P036 Current Stability Loop Output Upper Limit 0 100 10 ON
P037 Current Stability Loop Output Lower Limit -100 100 -10 ON
P038 Current Stability Loop Enable
P039 Current Stability Loop Enable Frequency Range Upper
P040 Safe Start Condition
P087 Switch Frequency Setting Enable Code
P088 Switch Frequency Setting
P089 Skip Frequency Enable
P090 Skip Frequency 1 Lower Limit 0 75 0 ON
P091 Skip Frequency 1 Upper Limit 0 75 0 ON
P092 Skip Frequency 2 Lower Limit 0 75 0 ON
P093 Skip Frequency 2 Upper Limit 0 75 0 ON
P113 Flying Start-Initial Output Voltage 0 100 5 ON
Description Min. Max. Default Modify
Root
010ON
0 = Ramp Dow 1 = Coast Stop
010ON
0 = Disable 1 = Enable
011ON
0 = Disable 1 = Enable
0 100 40 ON
Limit
011OFF
0 = Zero Frequency Command Required 1 = Frequency Command Allowed
010OFF
0 = Disable 1 = Enable
010OFF
0 = 600 Hz 1 = 1200 Hz
010ON
0 = Disable 1 = Enable
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 91
Page 92
Chapter 5 No-load Test
Table 18 - Setup and R&D P Parameters (Continued)
Parameter Number
P114 Flying Start-Current Comparison Delay For Motor Speed
P115 Flying Start-Current Threshold For Successful Motor
P198 HECS Rated Current 0 5000 0 ON
P199 Motor Rated Current 0 5000 0 ON
P200 Ia Motor Current Memory Address 0 500 13 ON
P201 Motor Ia Scaling Correction Factor 0.00 199.99 100.00 ON
P202 Ib Motor Current Memory Address 0 500 14 ON
P203 Motor Ib Scaling Correction Factor 0.00 199.99 100.00 ON
P204 Motor Uab Voltage Address 0 500 11 ON
P205 Motor Uab Voltage Scaling Factor Correction 0.00 199.99 199.99 ON
P206 Motor Uac Voltage Scaling Factor Correction 0.00 199.99 199.99 ON
P208 Phase Over Current Enable Frequency Range Upper Limit 0 100 10 ON
P209 Phase Over Current Filter Time 0 32767 5 ON
P210 Phase Over Current Threshold 0 199.99 180 ON
P211 Filter Time For Abnormal Output Voltage 0 32767 1000 ON
P212 Filter Time For Output Short-Circuit 0 32767 10 ON
P213 Output Short-Circuit Fault Threshold 0 199.99 180 ON
P214 Over Current Low/High Speed Region Boundary 0 100 5 ON
P215 Filter Time For Output Over Current 0.0 3276.7 20.0 ON
P216 High-Frequency Output Over Current Threshold 0.00 199.99 120.00 ON
P217 Low-Frequency Output Over Current Threshold 0.00 199.99 70.00 ON
P218 Filter Time For Motor Over Temperature 0.0 3276.7 600.0 ON
P219 Motor Over Temperature Warning Threshold 0.00 199.99 110.00 ON
P220 Motor Over Temperature Fault Threshold 0.00 199.99 120.00 ON
P221 Filter Time For Output Over Voltage 0 32767 100 ON
P222 Output Over Voltage Fault Threshold 0.00 199.99 130.00 ON
P223 Output Voltage Deviation Warning Threshold 0.00 199.99 60.00 ON
P224 Output Voltage Deviation Fault Threshold 0.00 199.99 80.00 ON
P225 Motor Over Temperature Warning Cancellation
P226 Output Voltage Abnormality Warning Cancellation
P227 Ground Fault Detection Scaling Correction Factor 0.00 199.99 100.00 ON
P228 Filter Time For Ground Fault 0 32767 1000 ON
P229 Ground Fault Warning Threshold 0.00 199.99 20.00 ON
P230 Ground Fault Trip Threshold 0.00 199.99 60.00 ON
P231 Filter Time For Overspeed Fault (Upper Limit) 0 32767 100 ON
P232 Filter Time For Overspeed Fault (Lower Limit) 0 32767 100 ON
Description Min. Max. Default Modify
0 5000 1000 ON
Search
01005ON
Speed Search
0.00 199.99 100.00 ON
Temperature
0.00 199.99 50.00 ON
Threshol d
Root
92 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 93
Table 18 - Setup and R&D P Parameters (Continued)
No-load Test Chapter 5
Parameter Number
P233 Threshold Of Over-Speed Fault At Lower Frequency Limit 0.00 199.99 20.00 ON
P234 Threshold Of Over-Speed Fault At Upper Frequency Limit 0.00 199.99 20.00 ON
P235 Frequency Deviation Warning Cancellation Threshold 0.00 199.99 0.99 ON
P236 Frequency Deviation Warning Threshold 0.00 199.99 6.00 ON
P237 Frequency Deviation Warning Delay 0 32767 8 ON
P238 Motor Stall Fault Threshold 0.00 199.99 10.00 ON
P239 Motor Stall Fault Delay 0 32767 6000 ON
P240 Transformer Over Temperature Fault Delay 0 32767 5000 ON
P241 Transformer Over Temperature Warning Delay 0 32767 5000 ON
P247 Software Interlock
P250 Input Contactor/Circuit Breaker Close Delay 0 10000 5000 ON
P251 Frequency Command-Low Frequenc y Region Boundary 0.0 100.0 0.5 ON
P252 Motor In Stopping Condition Threshold 0 100 1 ON
P253 Motor Coast Stop Time 0 10000 10 ON
P256 Ground Fault Warning Cancellation Threshold 0.00 199.99 10.00 ON
P257 Motor Stall Warning Cancellation Threshold 0.00 199.99 2.98 ON
P259 Frequency Command Analog Offset -100.00 199.99 0.00 ON
P260 Frequency Command Analog Scaling Factor 0.00 199.99 100.00 ON
P261 Frequency Command Analog Minimum 0.00 199.99 0.49 ON
P262 Frequency Command Source Selection
P263 Power Loss Restart Enable
P264 Power Loss Allowable Time 0.00 3599.96 59.63 OFF
P265 Power Loss Time Max Limit 0.00 3599.96 299.82 OFF
P268 Flux Control Signal Filter Time 0.00 13499.96999.97 ON
Description Min. Max. Default Modify
Root
011ON
0 = Enable 1 = Disable
010OFF
0 = Digital 1 = Analog
010OFF
0 = Disable 1 = Enable
P269 System Derating Control Signal Filter Time 0.00 13499.96999.97 ON
P270 Delayed Lockout Time Of Stop Operation 0 5000 2000 ON
P271 Flux Delay 0 5000 50 ON
P272 Flux Control Regulation Time 0.96 999.97 0.96 ON
P273 Flux Control Regulation Control Enable
0 = Disable 1 = Enable
P275 Flux Control Regulation Acceleration Threshold 100.00 199.99 100.00 ON
P276 Derating Control No-Load Modulation Index 50 100 80 ON
P277 Derating Control Full-Load Modulation Index 50.00 199.99 81.99 ON
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 93
011ON
Page 94
Chapter 5 No-load Test
Table 18 - Setup and R&D P Parameters (Continued)
Parameter Number
P278 Derating Control Enable Threshold 50.00 199.99 100.00 ON
P279 Derating Control Output Filter Time 9.95 1999.94 9.95 ON
P280 Low Voltage Ride Through Recovery Voltage Boost
P281 Low Voltage Ride Through Min Time Interval 0.00 1000.00 9.97 ON
P282 Low Voltage Ride Through Min Frequenc y Limit 5 100 20 OFF
P283 Low Voltage Ride Through Enable
P284 Low Voltage Ride Through Min Time Limit 20.02 13663.0139.62 OFF
P285 Low Voltage Ride Through Max Time Limit 20.02 13663.0199.66 OFF
P286 Low Voltage Ride Through Recovery Frequency
P287 Low Voltage Ride Through Recovery Time 145.95 13663.011499.95 OFF
P288 Low Voltage Ride Through System Delay Correction
P289 Low Voltage Ride Through Motor Speed Estimation Filter
P290 Voltage Loop Enable
P291 Voltage Loop Enable Min Frequency 0 100 20 OFF
P292 Voltage Loop Proportional Coefficient 99.98 1999.94 899.96 ON
P293 Voltage Loop Integral Coefficient 0.00 99.98 19.96 ON
P294 Voltage Loop Positive Incremental Error Limit 20.02 1000.00 49.99 ON
P295 Voltage Loop Negative Incremental Error Limit 20.02 1000.00 99.98 ON
P296 Reserved 49.99 1000.00 0.00 ON
P297 Voltage Loop Voltage Reference 125.00 1200.12 1000.00 ON
P298 Voltage Loop Current Filter Time 0.00 1999.94 9.95 ON
P299 Voltage Loop Voltage Filter Time 0.00 1999.94 2.99 ON
P300 Digital Output #0 Memory Address 0 500 99 ON
P301 Digital Output #0 Logic
P302 Digital Output #0 Bit Selection 0 15 0 ON
P303 Digital Output #0 Delay 0 32767 0 ON
P304 Digital Output #1 Memory Address 0 500 99 ON
P305 Digital Output #1 Logic
P306 Digital Output #1 Bit Selection 0 15 1 ON
P307 Digital Output #1 Delay 0 32767 0 ON
Description Min. Max. Default Modify
Root
0 100 10 ON
Coefficient
010ON
0 = Disable 1 = Enable
-200.00 199.99 0.00 OFF
Compensation Factor
0.00 10000.002199.97 ON
Fac tor
0.98 1000.00 9.95 OFF
Time
010OFF
0 = Disable 1 = Enable
010ON
0 = Non-Inverting 1 = Inverting
010ON
0 = Non-Inverting 1 = Inverting
94 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 95
Table 18 - Setup and R&D P Parameters (Continued)
No-load Test Chapter 5
Parameter Number
P308 Digital Output #2 Memory Address 0 500 99 ON
P309 Digital Output #2 Logic
P310 Digital Output #2 Bit Selection 0 15 2 ON
P311 Digital Output #2 Delay 0 32767 0 ON
P312 Digital Output #3 Memory Address 0 500 99 ON
P313 Digital Output #3 Logic
P314 Digital Output #3 Bit Selection 0 15 3 ON
P315 Digital Output #3 Delay 0 32767 0 ON
P316 Digital Output #4 Memory Address 0 500 99 ON
P317 Digital Output #4 Logic
P318 Digital Output #4 Bit Selection 0 15 4 ON
P319 Digital Output #4 Delay 0 32767 0 ON
P320 Digital Output #5 Memory Address 0 500 99 ON
P321 Digital Output #5 Logic
P322 Digital Output #5 Bit Selection 0 15 5 ON
P323 Digital Output #5 Delay 0 32767 0 ON
P324 Digital Output #6 Memory Address 0 500 99 ON
P325 Digital Output #6 Logic
P326 Digital Output #6 Bit Selection 0 15 6 ON
P327 Digital Output #6 Delay 0 32767 0 ON
P328 Digital Output #7 Memory Address 0 500 99 ON
P329 Digital Output #7 Logic
P330 Digital Output #7 Bit Selection 0 15 7 ON
P331 Digital Output #7 Delay 0 32767 0 ON
P332 Analog Output #1 Memory Address 0 500 252 ON
P333 Analog Output #1 Filter Time 0 32767 1000 ON
P334 Analog Output #1 Offset -100 100 0 ON
P335 Analog Output #1 Scaling Factor 0.00 199.99 100.00 ON
P336 Analog Output #2 Memory Address 0 500 206 ON
P337 Analog Output #2 Filter Time 0 32767 1000 ON
P338 Analog Output #2 Offset -100 100 0 ON
Description Min. Max. Default Modify
Root
010ON
0 = Non-Inverting 1 = Inverting
010ON
0 = Non-Inverting 1 = Inverting\
010ON
0 = Non-Inverting 1 = Inverting
010ON
0 = Non-Inverting 1 = Inverting
010ON
0 = Non-Inverting 1 = Inverting
010ON
0 = Non-Inverting 1 = Inverting
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 95
Page 96
Chapter 5 No-load Test
Table 18 - Setup and R&D P Parameters (Continued)
Parameter Number
P339 Analog Output #2 Scaling Factor 0.00 199.99 100.00 ON
P340 Analog Output #3 Memory Address 0 500 0 ON
P341 Analog Output #3 Filter Time 0 32767 1000 ON
P342 Analog Output #3 Offset -100 100 0 ON
P343 Analog Output #3 Scaling Factor 0.00 199.99 100.00 ON
P344 Analog Output #4 Memory Address 0 500 0 ON
P345 Analog Output #4 Filter Time 0 32767 1000 ON
P346 Analog Output #4 Offset -100 100 0 ON
P347 Analog Output #4 Scaling Factor 0.00 199.99 100.00 ON
P351 Rated Frequency HMI Display Filter Time 0 32767 100 ON
P352 Rated Frequency HMI Display Integer Part 0 75 50 ON
P353 Rated Frequency HMI Display Decimal Par t 0 1000 0 ON
P354 Motor Voltage HMI Display Filter Time 0 32767 2000 ON
P355 Motor Voltage HMI Display Integer Part 0 16384 10000 ON
P356 Motor Voltage HMI Display Decimal Part 0 1000 0 ON
P357 Actual Frequency HMI Display Filter Time 0 32767 100 ON
P358 Actual Frequency HMI Display Integer Part 0 75 50 ON
P359 Actual Frequency HMI Display Decimal Part 0 1000 0 ON
P360 Motor Current HMI Display Filter Time 0 32767 2000 ON
P361 Motor Current HMI Display Integer Par t 0 5000 0 ON
P362 Motor Current HMI Display Decimal Par t 0 1000 0 ON
P371 Rated Frequency HMI Display Address 0 500 221 ON
P372 Motor Voltage HMI Display Address 0 500 119 ON
P373 Actual Frequency HMI Display Address 0 500 252 ON
P374 Motor Current HMI Display Address 0 500 118 ON
P375 Frequency At First Point for 5 Point VF 0 10 1 OFF
P376 Amplitude At First Point for 5 Point VF 0 3 1 OFF
P377 Frequency At Second Point for 5 Point VF 0 100 20 OFF
P378 Amplitude At Second Point for 5 Point VF 0 100 10 OFF
P379 Frequency At Third Point for 5 Point VF 0 100 40 OFF
P380 Amplitude At Third Point for 5 Point VF 0 100 27 OFF
P381 Frequency At Fourth Point for 5 Point VF 0 100 60 OFF
P382 Amplitude At Fourth Point for 5 Point VF 0 100 45 OFF
P383 Frequency At Fifth Point for 5 Point VF 0 100 80 OFF
P384 Amplitude At Fifth Point for 5 Point VF 0 100 70 OFF
P385 Deceleration Process Enable
P386 Deceleration Time 1 0 3276 150 ON
Description Min. Max. Default Modify
Root
010OFF
0 = Disable 1 = Enable
96 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 97
Table 18 - Setup and R&D P Parameters (Continued)
No-load Test Chapter 5
Parameter Number
P387 Deceleration Frequency 1 0 75 30 ON
P388 Deceleration Time 2 0 3276 80 ON
P389 Deceleration Frequency 2 0 75 20 ON
P390 Deceleration Time 3 0 3276 80 ON
P391 Deceleration Frequency 3 0 75 10 ON
P392 Deceleration Time 4 0 3276 100 ON
P399 Deceleration Time 0 3276 400 ON
P401 Acceleration Time 0 3276 200 ON
P402 Acceleration Ramp Transition Time 0 3276 3 ON
P403 Acceleration Time Unit
P405 Deceleration Ramp Transition Time 0 3276 3 ON
P406 Deceleration Time Unit
P409 Amplification Coefficient Of Error Terms 0.00 199.99 100.00 ON
P411 Over Speed Upper Limit Reference 0 100 100 ON
P412 Over Speed Lower Limit Reference 0 100 0 ON
P413 Frequency Command Lower Limit -16384 16384 0 ON
P414 Frequency Command Deadband Upper Limit 0.00 100.00 0.49 ON
P415 Frequency Command Upper Limit -16384 16384 16384 ON
P416 Flying Start Mode
P417 Flying Start Motor Speed Search Timeout 0 1000 50 ON
P438 Current Limitation Enable Frequency Range Lower Limit 0 100 10 ON
P439 Current Limitation Upper Offset 0 10 3 ON
P440 Current Limitation Lower Offset 0 10 3 ON
P441 Current Limitation Threshold 0 130 100 ON
P451 Low Speed Voltage Compensation 0.00 3.00 0.99 OFF
P452 Low Speed Voltage Compensation Frequency Threshold 0 100 20 ON
P453 V/F Curve
P454 Flux Time (s) 0.0 10.0 0.5 OFF
P455 Modulation Index 0.00 110.00 87.99 ON
P456 Motor Voltage Upper Limit 0.00 110.00 87.99 ON
P457 Flying Start Voltage Recovery Time (Low Speed Region) 0.00 163.84 5.00 ON
Description Min. Max. Default Modify
00.10.1ON
1000 = 0.01 s 10000 = 0.1s
00.10.1ON
1000 = 0.01 s 10000 = 0.1s
030ON
0 = Disable 1 = Set Frequency 2 = Stop Frequency Plus 5 Hz 3 = Rated Frequency
0 = Linear 1 = Parabolic Curve 2 = Predefined Cur ve #1 3 = Predefined Cur ve #2 4 = 5 Point VF
04 (R&D)
3 (Setup)
1OFF
Root
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 97
Page 98
Chapter 5 No-load Test
Table 18 - Setup and R&D P Parameters (Continued)
Parameter Number
Description Min. Max. Default Modify
Root
P458 Coefficient A 0 100 40 OFF
P459 Flying Star t Voltage Recovery Time (High Spe ed Region) 0 163.84 5 ON
P460 Rated Output Frequency 0 75 50 OFF
P461 Restart Enable
010ON
0 = Disable 1 = Enable
P462 Fault Reset Timeout 0 120 120 ON
P463 Flying Start Low/High Speed Regions Boundary 0 100 16 ON
P465 Power Cell Fault Auto Reset Delay 0 10 4 ON
P466 Maximum Output Frequency 0 75 50 OFF
P467 Over Speed Enable
010OFF
0 = Disable 1 = Enable
P470 Version Compatibility Enable
011OFF
0 = Disable 1 = Enable
P497 Major Rev # Of DSP Main Firmware —— —— 0 Cannot
Modify
P498 Minor Rev # Of DSP Main Firmware —— —— 2 Cannot
Modify
P499 Display Fault Masks Button
010ON
0 = Disable 1 = Enable
P500 Display DSP Variables 0 1 0 ON
There are no specific T parameters to modify when commissioning a drive. Verify the values and only modify per customer specifications.
Table 19 - Setup and R&D T Parameters
Parameter Number
T01 Fault-To-Bypass
T02 Fault-To-Bypass Delay (0...5s) 3 Yes 16-bit Unsigned Integer
T03 Fault-To-Bypass Delay When Starting the Motor
T04 Fault-To-Bypass Minimum Frequency
T07 Local Frequency Command Selection
T08 Remote Frequency Command Selection
T09 Frequency Step For Accel or Decel 1 Yes 16-bit Unsigned Integer
Description Default
Value
0 Yes B oolean 0 = Disable 1 = Enable
60 Yes 16-bit Unsigned Integer (0...60s)
5 Yes 32-bit Float
0...Rated Frequency (Hz)
0 Yes B oolean 0 = Digital 1 = Analog
1 Yes 16-bit Unsigned Integer 1 = Analog 2 = 4-Step Speed 4 = Communication Port
Modify Root
Data Type
98 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Page 99
Table 19 - Setup and R&D T Parameters (Continued)
No-load Test Chapter 5
Parameter Number
T10 Exit To Configuration Mode Password 555 No 16-bit Unsigned Integer
T11 Automatic Bypass-To-Drive or
T12 PID Parameter Settings
T13 4-Step Variable Speed (available only when T8 = 2)
T14 One-Drive-Two-Motor Mode, QS Enable
T15 Bypass Mode Selection (0...4) 0 Operation Button
T16 When Disconnected between
Description Default
Value
0 Operation Button
Drive-To-Bypass Selection
Bypass-To -Drive Yes
Drive-To-Bypass Yes
P 0.01 Yes 32-bit Float
I 0.01 Yes 32-bit Float
D 0 Yes 32-bit Float
D Gain 0 Yes 32-bit Float
Speed 1 10 Yes 32-bit Float
Speed 2 20 Yes 32-bit Float
Speed 3 30 Yes 32-bit Float
Speed 4 40 Yes 32-bit Float
1 Yes B oolean 0 = No 1 = Yes
No Bypass Yes
Manual Bypass, One-Drive-One-Motor Yes
Auto Bypass, One-Drive-One-Motor Yes
Manual Bypass, One-Drive-Two-Motor Yes
Auto Bypass, One-Drive-Two-Motor Yes
1 Yes 16-bit Unsigned Integer 0 = Stop 1 = Keep Current Frequency 2 = Keep T13, Speed 1 3 = Keep T13, Speed 2 4 = Keep T13, Speed 3 5 = Keep T13, Speed 4
Modify Root
Data Type
ATT EN TI ON : If you enter a value that is greater than the allowed range for the
parameter, the input field will turn red.
Rockwell Automation Publication 6000-IN007B-EN-P - March 2016 99
Page 100
Chapter 5 No-load Test
Change Parameters T11...T13
Parameter T11
To change Parameter T11:
1. Press the T11 Parameter input field.
2. In the Operation Mode dialog, press or .
3. If you select , the:
drive must be set to Local Control
position switch must be set to Drive
bypass contactor must be ON
drive must not be running.
4. If you select , the:
drive must be set to Local Control
100 Rockwell Automation Publication 6000-IN007B-EN-P - March 2016
Loading...