Catalog Numbers 1794-IJ2, 1794-IJ2K, 1794-IJ2XT
User Manual
Page 2
Important User Information
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application,
Installation and Maintenance of Solid State Controls (publication SGI-1.1
http://literature.rockwellautomation.com
) describes some important differences between solid state equipment and hard-wired electromechanical
devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this
equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this
equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated
with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and
diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this
manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from your local Rockwell Automation sales office or online at
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may
lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to: personal injury or death, property damage, or
economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Labels may be on or inside the equipment, such as a drive or motor, to alert people that dangerous voltage may be present.
Labels may be on or inside the equipment, such as a drive or motor, to alert people that surfaces may reach dangerous
temperatures.
Allen-Bradley, Rockwell Automation, FLEX I/O, RSLinx, RSLogix 5000 and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Page 3
Summary of Changes
This manual contains new and updated information. Changes throughout this
revision are marked by change bars, as shown to the right of this paragraph.
New and Updated
Information
This table contains the changes made to this revision.
TopicPage
Inclusion of two catalogs, 1794-IJ2K and 1794-IJ2XT1
The first chapter has been updated with the following topics:
1
•The FLEX System
•Type of Modules
•The FLEX I/O Module in a Logix Control System
The wiring illustration for terminal base units has been updated.20
The following topics have been added:
•Configure Your FLEX I/O Module with RSLogix 5000
29
(Chapter 3)
•Troubleshoot the Module (Chapter 5)
•Electronic Data Sheet (EDS) Files
The Specifications topic (Appendix A) has been updated to include
specifications for 1794-IJ2K, and 1794-IJ2XT.
"Program Your Module" is now moved to the appendices section. It was
previously Chapter 3 in the last revision.
Read this preface to familiarize yourself with the rest of the manual. It provides
information concerning:
• who should use this manual
• the purpose of this manual
• related documentation
• conventions used in this manual
• terminology used in this manual
Who Should Use This
Manual
Purpose of the Manual
We assume that you have previously used an Allen-Bradley programmable
controller, that you are familiar with its features, and that you are familiar with
the terminology we use. If not, read the user manual for your processor before
reading this manual.
This manual is a reference guide for the 1794 Frequency Input Modules. It
describes the procedures for installing, configuring and troubleshooting your
module.
For information onSee
Overview of the Frequency Input ModuleChapter 1
Install Your FLEX I/O Frequency Input ModuleChapter 2
Configure Your FLEX I/O Module with RSLogix 5000 SoftwareChapter 3
Read and Write Configuration Maps for the FLEX I/O ModuleChapter 4
Troubleshoot the ModuleChapter 4
SpecificationsAppendix A
Electronic Data Sheet (EDS) FilesAppendix B
SchematicsAppendix C
Program Your Module with PLC ProcessorsAppendix D
About the Vocabulary
ixPublication 1794-6.5.11 - September 2011
In this manual, we refer to:
• the frequency input module as the “input module”
• the Programmable Controller as the “controller”
Page 8
x Preface
Related Documentation
The following documents contain additional information concerning Rockwell
Automation products. To obtain a copy, contact your local
Rockwell Automation office or distributor.
FLEX I/O Input, Output and Input/Output Analog Modules
Installation Instructions, publication 1794-IN100
FLEX I/O Analog Module User Manual,
publication 1794-6.5.2
FLEX I/O Isolated Analog Output Module Installation
Instructions, publication 1794-IN037
Publication 1794-6.5.11 - September 2011
x xxxxxxxxxxxxx
x xxxxxxxxxxxxx
x xxxxxxxxxxxxx
x xxxxxxxxxxxxx
xxxxxxx
x xxxxxxxxxxxxx
Information on how to install the Flex I/O Digital DC Sourcing Output Modules
(Catalog No. 1794-OB8, 1794-OB8EP, 1794-OB16, 1794-OB16P, 1794-OB32P).
Information on how to install the Flex I/O Input/ Output Modules
(Catalog No. 1794-IB16XOB16P, 1794-IB10XOB6).
Information on how to install the Flex I/O 8 Output Relay Modules
(Catalog No. 1794-OW8, 1794-OW8K, 1794-OW8XT).
Information on how to install the FLEX I/O Input, Output and Input/Output
Analog Modules (Catalog No. 1794-IE8, 1794-IE4XOE2, 1794-OE4, 1794-IE8K,
1794-OE4K).
Information on how to install the FLEX I/O Analog Modules
(Catalog No. 794-OE4, 1794-IE8, 1794-IE12, 1794-OE12, 1794-IE4XOE2,
1794-IE8XOE4, 1794-IE4XOE2XT, 1794-IE8XT, 1794-OE4XT).
Information on how to install the FLEX I/O Isolated Analog Output Module
(Catalog No. 1794-OF4I).
Information on how to install the FLEX I/O 4 Isolated Input Module
(Catalog No. 1794-IF4I).
Information on how to install the FLEX I/O 2 In/2 Out Isolated Analog Combo
Module (Catalog No. 1794-IF2XOF2I).
Information on how to use the FLEX I/O Isolated Analog Modules
(Catalog No. 1794-IF4I, 1794-OF4I, 1794-IF2XOF2I, 1794-IF4IXT, 1794-IF4ICFXT,
1794-OF4IXT, 1794-IF2XOF2IXT).
Information on how to install the FLEX I/O 8 Thermocouple Input Modules
(Catalog No. 1794-IT8, 1794-IR8).
Information on how to use the FLEX I/O 8 Input RTD Module
(Catalog No. 1794-IR8).
Information on how to use the Thermocouple and Millivolt Input Module
(Catalog No. 1794-IT8).
Information on how to install the Thermocouple/Millivolt Input Modules
(Catalog No. 1794-IRT8, 1794-IRT8K, 1794-IRT8XT).
Information on how to install the 2-Input Frequency Module
(Catalog No. 1794-IJ2, 1794-IJ2K, 1794-IJ2XT).
Information on how to use the FLEX I/O Thermocouple, RTD, mV Input Module
(Catalog No. 1794-IRT8, 1794-IRT8K, and 1794-IRT8XT).
Information on how to install the 24V FLEX I/O 2 Channel Incremental Encoder
Module (Catalog No. 1794-ID2).
FLEX Integra Analog Module User Manual,
publication 1793-6.5.1
Information on how to install the FLEX Integra Analog Module (Catalog No.
1793-IE2X0E1,1793-IE2XOE1S, 1793-IE4, 1793-IE4S, 1793-OE2, 1793-OE2S).
Information on how to install the 24V DC FLEX I/O 4-Channel Module
(Catalog No. 1794-IP4).
Information on how to install the Very High Speed Counter Module
(Catalog No. 1794-VHSC).
Information on how to install the FLEX I/O 48V DC Input and Output Modules
(Catalog No. 1794-IC16, 1794-OC16).
Information on how to install the FLEX I/O AC Input Modules
(Catalog No. 1794-IA8, 1794-IA8I, 1794-IA16).
Information on how to install the FLEX I/O Digital AC Output Modules
(Catalog No. 1794-OA8, 1794-OA8K, 1794-OA8I, 1794-OA16).
Information on how to install the FLEX I/O 220V AC Input and Output Modules
(Catalog No. 1794-IM8, 1794-OM8).
Information on how to install the FLEX I/O Terminal Base Units
(Catalog No. 1794-TB2, 1794-TB3, 1794-TB3K, 1794-TB3S, 1794-TB32,
1794-TB3G, 1794-TB3GK, 1794-TB3GS, 1794-TB3T, 1794-TB3TS, 1794-TBN,
1794-TBNK, 1794-TBNF).
Information on how to install the Interconnect Cable
(Catalog No. 1794-CE1, 1794-CE3).
Publication 1794-6.5.11 - September 2011
Page 10
xii Preface
ResourceDescription
FLEX I/O DC Power Supply Installation Instructions,
publication 1794-IN069
Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1
The following conventions are used throughout this manual:
• Bulleted lists such as this one provide information, not procedural steps.
• Numbered lists provide sequential steps or hierarchical information.
• Italic type is used for emphasis.
Information on how to install the FLEX I/O DC Power Supply
(Catalog No. 1794-PS13, 1794-PS3).
In-depth information on grounding and wiring Allen-Bradley programmable
controllers.
A glossary of industrial automation terms and abbreviations.
Publication 1794-6.5.11 - September 2011
Page 11
Chapter
I/O moduleTerminal base
1794-IRT8
Adapter
2
+
2
+
45568
1
Overview of the Frequency Input Module
Overview
The FLEX System
This chapter provides a description of the application and capabilities of the
1794 FLEX I/O Frequency Input module. It also explains the general
algorithm for calculating frequency.
TopicPage
The FLEX System1
Type of Modules2
Usage of the Frequency Input Module2
The FLEX I/O Module in a Logix Control System3
Typical Applications5
Input Capabilities6
Output Capabilities7
How Frequency Is Calculated8
Chapter Summary12
FLEX I/O is a small, modular I/O system for distributed applications that
performs all of the functions of rack-based I/O. The FLEX system contains
the following components shown below:
• Adapter – transfers read and write configuration data to and from the
I/O module
• terminal base – contains a terminal strip to terminate wiring for two- or
three-wire devices
1Publication 1794-6.5.11 - September 2011
Page 12
2 Overview of the Frequency Input Module
• I/O module – contains the bus interface and circuitry needed to
perform specific functions related to your application
The 1794 FLEX system consists of an adapter module, terminal base unit,
DIN rail, power supply, and adapter cabling components. You can use up to 8
terminal bases per adapter module.
For detailed instructions to set up and install your module, refer to the topic,
Install Your FLEX I/O Frequency Input Module, on page 13.
Type of Modules
The FLEX I/O Frequency Input modules refer to the following catalogs.
Catalog No.VoltageInputsOutputs Description
1794-IJ224V DC22Digital – 2-pt 24V DC input frequency
module
1794-IJ2K24V DC22Digital – 2-pt 24V DC input frequency
module, conformally coated.
1794-IJ2XT24V DC22Digital – 2-pt 24V DC input frequency
module for extended temperature.
The frequency input module is an intelligent I/O module designed to perform
high-speed frequency algorithms. The module provides:
• 2 Frequency Inputs,
• 2 Gate Inputs and
•2 Outputs.
The Frequency Inputs can accept frequencies up to 32,767 Hz and it accepts
and returns binary data.
Usage of the Frequency
Input Module
Publication 1794-6.5.11 - September 2011
The FLEX I/O Frequency Input module is essentially a tachometer with the
capability of reporting frequency, acceleration, and direction. Outputs are
activated by alarms. Input devices range from magnetic pickup to flowmeters,
to incremental encoders to proximity detectors. This intelligent I/O module is
designed to perform high-speed frequency algorithms.
Power to the module is supplied from an external power supply. All power for
input devices (24V DC) is supplied by the I/O module. Outputs are used to
set alarms depending on the input conditions.
The module measures frequency over a user-specified time interval. A
frequency calculation can start before the time interval has elapsed, if a
user-specified number of frequency input pulses have occurred.
Page 13
Overview of the Frequency Input Module 3
500/50 mV
50 mV
Select
24V IEC 1+
24V IEC 1+
Magnetic
500/50 mV
Magnetic
Gate input
Frequency input
CRISP
Bus interface
Output 0
Output 1
Inter-processor
communication,
uP system 0/1
From
uP system 1
Data To/From FlexBus
Invert
Y/N
Invert
Y/N
Processing
Counter
Frequency / count data
uP system 0
Output control
Input control
Direction data
IEC 1+/Contact
Input
VORTEX
Vortex
3Vin 6Vin 24V power
IEC 1+/Contact
Input
50 mV
Select
GND
GND
Inputs
Module
FlexBus
24V Power
24Vpower
45388
The primary use of the module is accurate, high-speed frequency
measurement. A high-speed internal clock is synchronized with the frequency
input to count over a user-selected sampling time or a user-defined number of
frequency input pulses.
All power for input devices (4 devices, 24 V DC @ 15 mA max) is supplied by
the I/O module.
The FLEX I/O Module in a
Logix Control System
The frequency input module performs high-speed frequency and/or scaling
calculation operations for various industrial applications. The module
interfaces with a FLEX I/O family adapter which then communicates with a
programmable controller processor that has block-transfer capability and
external I/O devices.
The adapter transfers data to the module (block transfer write) and from the
module (block transfer read) using BTW and BTR instructions in your ladder
diagram program. These instructions let the adapter read input values and
status from the module, and let you write output values and configure the
module mode of operation. The following illustration describes the
communication process.
Publication 1794-6.5.11 - September 2011
Page 14
4 Overview of the Frequency Input Module
FREQ
GATE
OK
0
FREQUENCY INPUT 2 CHANNEL
1
1794-IJ2
F0F
FREQ
GATE
1
F1
F
OUT
0
OUT
1
45339
The adapter transfers your configuration data
to the module using a BTW.
1
FlexBus
Your ladder program instructs the
adapter to perform a BTR of the
values and stores them in a
data table.
4
The adapter module determines that the
transfer was made without error and
input values are within specified range.
5
Your ladder program can use and/or
transmit the data (if valid) before it is
overwritten by the transfer of new data in
a subsequent transfer.
6
Your ladder program performs BTWs to
the module when you power it up, and
any time you wish to reconfigure the
module.
7
External devices
transmit frequency
signals to the module.
2
The module converts
frequency signals into
integer format and stores
these values until the
adapter requests their
transfer.
Typical Communication between a FLEX I/O Module and an Adapter
Publication 1794-6.5.11 - September 2011
Page 15
Overview of the Frequency Input Module 5
Bridge
PanelView Station
Ethernet
PC running
controller and
Rockwell Automation
configuration software
1794 Adapter
1794 FLEX I/O module
FLEX System
45567
ATTENTION
A broader view of how the FLEX I/O module interfaces with the different
elements in a Logix system is shown in the sample illustration below.
Typical Applications
In this example, the FLEX I/O module communicates with the controller
through the adapter. The controller can produce and consume tags. It can
initiate MSG instructions that send and receive data or configure devices.
Configuration of devices and the network is done through the personal
computer running the controller and configuration software.
To learn about the steps to configure your FLEX I/O module, see Configure
Your FLEX I/O Module with RSLogix 5000 Software on page 29.
.
The following publications provide more information about
EtherNet/IP, and ControlNet modules in a Logix5000 system:
•EtherNet/IP Modules in Logix5000 Control Systems,
publication E
NET-UM001
•ControlNet Modules in Logix5000 Control Systems,
publication CNET-UM001
You can use the frequency input modules in power management, automotive,
food and beverage, and oil and gas industries for various flow and/or turbine
metering applications. Some sample applications include:
• turbine shaft speed monitoring
• automotive paint booths
• brewery flow monitoring
• petrochemical flow and custody transfer
Publication 1794-6.5.11 - September 2011
Page 16
6 Overview of the Frequency Input Module
Channel 0
Channel 1
Frequency Input (F0)
Gate Input (G0)
Frequency Input (F1)
Gate Input (G1)
Frequency Input (F0-F1) – you connect
your input device to this input (ac, proximity
sensors switch, magnetic, vortex )
Gate Input (G0-G1) – you connect your
input device to this input (ac, proximity
sensors switch, magnetic, vortex )
used to determine direction – CW or CCW
2 input channels
FREQ
GATE
OK
0
FREQUENCY INPUT 2 CHANNEL
1
1794-IJ2
Allen-Bradley
F0F
FREQGATE
1F1 F
OUT
0
OUT
1
45557
Input Capabilities
The frequency module has 2 input channels (mode dependent). Each of the 2
input channels may accept these input signals:
• magnetic pickup – 500 mV…28V AC peak (optional 50 mV…28V AC
peak for increased signal sensitivity)
• proximity probe inputs
– compatible with Bently Nevada 3300 – 5 mm (0.197 in.) and 8 mm
(0.315 in.) – proximity transducer systems
– provides 1 isolated 24V DC power supply (2 channels rated at 30 mA
each) to power external devices
– vortex flowmeter – 6V and 3V
You configure the 2 input channels for your specific application(s). Each input
channel has two input selections:
Publication 1794-6.5.11 - September 2011
Page 17
Modes of Operation
Overview of the Frequency Input Module 7
Selecting the Modes of Operation
You configure the frequency input module for these modes of operation:
ModeUse this mode toIndicators /
Alarms
Frequency and
% Full Scale
Frequency and Acceleration•Monitor the frequency of an input with high
•Monitor the frequency of an input with high
accuracy (for example, shaft)
•Monitor the percentage of full scale frequency
•Operate frequency alarm (% full scale)
•Scale the frequency
•Monitor the direction of shaft rotation
•Wire-off alarm with DC devices
•Missing pulse alarm
accuracy (for example, shaft)
•Monitor the acceleration (rate of speed change)
•Operate acceleration alarm (rate of change)
•Scale the frequency
•Monitor the direction of shaft rotation
•Wire-off alarm with DC devices
•Missing pulse alarm
x
x
x
x
x
x
Scaler /
Values
x
x
Output Capabilities
The frequency input module has 2 assignable outputs. These outputs are
designed for applications that require fast response. The outputs:
• are current sourcing at 10…31.2V DC (1 A maximum per output)
• are electrically fused (current limited to 3 A)
• can be assigned to the associated input channel with user-selectable
frequency and acceleration values
• are isolated – this lets you use two separate external power supplies if
desired (one for output 0 and one for output 1)
Implementing Application Features
You can use the module to implement programmable application features that
are usually initiated by your controller processor. This frees up the controller
Publication 1794-6.5.11 - September 2011
Page 18
8 Overview of the Frequency Input Module
processor to do other tasks and helps increase the overall throughput of your
controller system.
Application Features
FeatureModePurposeAlarm is ON when
Frequency alarmFrequency alarm
selected
Acceleration alarmAcceleration alarm
selected
Scaling% full scale and
acceleration
Activate alarm when calculated or scaled
frequency is higher than user-specified
frequency value.
Activate acceleration alarm when
acceleration is greater than user-specified
acceleration value.
Multiply and/or divide frequency by scalarFrequency > User-specified scaled
Frequency > user-specified value
| Acceleration | > user-specified value
frequency value
How Frequency Is
Calculated
The following paragraphs explain the operation of the frequency input module
algorithm and its modifying parameters.
Frequency Calculation
Frequency is determined by a general algorithm which can be modified by
user-defined parameters. In its simplest form, the algorithm employs the
user-defined Minimum Sampling Time to set a window in which to count
pulses to determine the frequency. At least two pulses are required within the
sample window. Frequency is determined by storing the time the first pulse
occurred and then continually storing and updating the time of subsequent
pulses, along with the number of pulses encountered. When the window
expires, the frequency is calculated and the procedure repeats. The sequence
and formula for determining frequency are shown below.
Publication 1794-6.5.11 - September 2011
Page 19
Overview of the Frequency Input Module 9
Missing pulse alarm would be
reported after 2 s, if no pulse occurs
Frequency reported
at end sampling time
Pulses counted
T2 - T1
pulses counted
First pulse in window,
T1 time stored
Last pulse in windowT2, update as each
pulse occurs
Minimum sampling time
Frequency input
pulses
45340
=
45341
Frequency reported at
first pulse in extended Time
2 - 1
T2 - T1
=
Missing pulse alarm is reported after 2 s, if no pulse occurs
Minimum
sampling timeFrequency input
pulses
2 = pulses counted
First pulse in window,
T1 time stored
First pulse after
window extended,
T2 time stored
Sampling time
extended to 2 s
Normal Mode Frequency Determination, at Least Two Pulses
in Sampling Time
If only one pulse occurs within the sampling window, when the sample time
has expired, the window is extended to 2 s to allow for a second pulse to occur.
As soon as a second pulse occurs, the frequency is calculated and the
procedures starts over. If no second pulse is detected, zero frequency is
reported and a Missing Pulse Alarm is generated. The following figure depicts
this scenario.
Normal Mode, Only One Pulse in Sampling Time,
Sampling Time Extended
Publication 1794-6.5.11 - September 2011
Page 20
10 Overview of the Frequency Input Module
Frequency reported at
number of pulses to
terminate reached
=
Pulses to terminate - 1
T2 - T1
Missing pulse alarm would be reported after 2 seconds, if no pulse occurs
pulses to terminate
Minimum sampling time
Frequency input
pulses
First pulse in window,
T1 time stored
T2, update as each
pulse occurs
Number of pulses to
terminate reached
45342
Termination on Number of Pulses
The normal mode is designed to provide wide bandwidth. However, it requires
the full 2 seconds to report a missing pulse. Another user parameter, Number
of Pulses to Terminate Sampling, is provided for scenarios where many pulses
are expected within the sampling window, such that early determination of
frequency is possible.
During normal operation, there is a sufficient number of pulses to prevent the
module from entering the 2-second extension mode. Once the user-defined
number of pulses is reached within the sampling window, the frequency is
immediately reported.
If the sampling window has been extended to 2 seconds while waiting for a
second pulse to occur, a situation which can occur during system startup, the
module does not wait for the number of pulses to be reached. Instead, as soon
as a second pulse occurs, the frequency is calculated based on the time
between the 2 pulses, and the procedure starts over.
Termination on Number of Pulses
Missing Pulse Multiplier
Publication 1794-6.5.11 - September 2011
The last user parameter which is provided to modify the frequency algorithm
is the Missing Pulse Multiplier. In this case, the user can set the number of
Minimum Frequency Sampling Time windows allowed to extend the time to
capture a second pulse, before reporting a Missing Pulse Alarm. The intent
with this parameter is to allow a tradeoff of the bandwidth available with the
response time to report a missing pulse. This mechanism is shown in the
following figure.
Page 21
Overview of the Frequency Input Module 11
Missing pulse multiplier
Frequency reported at
first pulse in extended
time
2 - 1
T2 - T1
=
Missing pulse alarm would be reported after last window, if no pulse occurs
Extended windows added one at time, until
pulse occurs or multiplied windows exceeded
Minimum sampling time
2 = pulses counted
Possible extended window
Frequency input
pulses
First pulse in window,
T1 time stored
First pulse in an extended
window, T2 time stored
45343
Direction Detection
Direction detection is accomplished by using the Frequency input, Gate input,
and two sensors. The module expects to see a Low to High transition on the
Frequency input, followed by a Low to High transition on the Gate input. This
assumes both input polarity select bits are the same selection.
This corresponds to clockwise rotation. See illustration, Direction Detection –
Principle of Operation, on page 12. If a Low to High transition occurs on the
Gate input, followed by one on the Frequency input, the rotation is
counterclockwise.
Publication 1794-6.5.11 - September 2011
Page 22
12 Overview of the Frequency Input Module
45344
Direction Detection – Principle of Operation
Clockwise rotation
Chapter Summary
M
2 x M
Sensor 0
Sensor 1
Gate input
IJ2 module
Sensor 0 (F)
Sensor 1 (G)
Sensor 0 (F)
Sensor 1 (G)
Frequency input
Clockwise
Rotation
Counter
Clockwise
Rotation
In this chapter, you learned about the frequency input module, block transfer
communication, and details of how the module functions.
Publication 1794-6.5.11 - September 2011
Page 23
Chapter
ATTENTION
2
Install Your FLEX I/O Frequency Input Module
Overview
This chapter provides you with pre-installation requirements and instructions
on how to install your FLEX I/O Frequency Input modules.
TopicPage
Before You Install Your Module13
Power Requirements13
Install the Module14
Mount on a DIN Rail14
Mount on a Panel or Wall16
Mount the Frequency Input Module on the Terminal Base Unit18
Wiring Information20
Connect Wiring to the FLEX I/O Frequency Input Module21
Connecting Wiring Using a 1794-TB3G, 1794-TB3GK or 1794-TB3GS
Terminal Base Unit
Resolution and Accuracy24
Examples of Wiring to a 1794-TB3G Terminal Base Unit27
Chapter Summary27
22
Before You Install
Before installing your frequency input module in the FLEX I/O system, you
need to:
Your Module
• calculate the power requirements of all modules in each FLEX I/O
system, and
• position the keyswitch on the terminal base.
This FLEX I/O module does not receive primary operational power
from the backplane. 24V DC power must be applied to your module
before installation. If power is not applied, the module position may
appear to the adapter as an empty slot in your chassis.
Power Requirements
13Publication 1794-6.5.11 - September 2011
The wiring of the terminal base unit is determined by the current draw
through the terminal base. Make certain that the current draw does not
exceed 10 A.
Page 24
14 Install Your FLEX I/O Frequency Input Module
ATTENTION
ATTENTION
ATTENTION
Total current draw through the terminal base unit is limited to 10 A.
Separate power connections may be necessary.
The frequency input module requires 30 mA at 5V DC from the FlexBus
backplane.
Methods of wiring the terminal base units are shown in the illustration below.
Do not daisychain power or ground from the terminal base unit to any
AC or DC digital module terminal base unit.
Install the Module
Installation of the frequency input module consists of:
• mounting the terminal base unit
• installing the module into the terminal base unit
• installing the connecting wiring to the terminal base unit
Mount on a DIN Rail
Do not remove or replace a terminal base unit when power is applied.
Interruption of the FlexBus can result in unintended operation or
machine motion.
Install the Terminal Base Unit
1. Remove the cover plug in the male connector of the unit to which you
are connecting this terminal base unit.
Publication 1794-6.5.11 - September 2011
Page 25
Install Your FLEX I/O Frequency Input Module 15
1
2
3
4
6
7
7
8
9
0
2
+
2
+
45319
2
+
2
+
45320
2. Check to make sure that the 16 pins in the male connector on the
adjacent device are straight and in line so that the mating female
connector on this terminal base unit will mate correctly.
Make certain that the female FlexBus connector is fully retracted into
the base unit.
3. Position the terminal base at a slight angle and hooked over the top of
the 35 x 7.5 mm DIN rail A (Allen Bradley part number 199-DR1;
46277-3).
4. Slide the terminal base over tight against the adapter, or proceeding
terminal base. Make sure the hook on the terminal base slides under the
edge of the adapter, or proceeding terminal base, and the FlexBus
connector is fully retracted.
5. Rotate the terminal base onto the DIN rail with the top of the rail
hooked under the lip on the rear of the terminal base.
Use caution to make sure that the female FlexBus connector does not
strike any of the pins in the mating male connector.
Publication 1794-6.5.11 - September 2011
Page 26
16 Install Your FLEX I/O Frequency Input Module
2
+
2
+
45321
2
+
2
+
45322
6. Press down on the terminal base unit to lock the terminal base on the
DIN rail. If the terminal base does not lock into place, use a screwdriver
or similar device to open the locking tab, press down on the terminal
base until flush with the DIN rail and release the locking tab to lock the
base in place.
Gently push the FlexBus connector into the side of the adapter, or
proceeding terminal base to complete the backplane connection.
Publication 1794-6.5.11 - September 2011
For specific wiring information, refer to the installation instructions for
the module you are installing in this terminal base unit.
7. Repeat the above steps to install the next terminal base unit.
Ensure that the cover of the FlexBus connector on the last terminal
base unit is in place.
Mount on a Panel or Wall
Installation of a FLEX I/O system on a wall or panel consists of:
• laying out the drilling points on the wall or panel.
• drilling the pilot holes for the mounting screws.
• mounting the adapter mounting plate.
Page 27
Install Your FLEX I/O Frequency Input Module 17
1
2
3
4
45323
Millimeters
(inches)
45327
• installing the terminal base units and securing them to the wall or panel.
Use the mounting kit Cat. No. 1794-NM1 for panel or wall mounting.
1794-NM1 Mounting Kit
35.5
(1.4)
0
9
1
8
7
6
2
2
+
+
7
2
3
4
DescriptionDescription
1Mounting plate for adapter3Terminal base unit (not included)
2#6 Self-tapping screws4Adapter module (not included)
To install the mounting plate on a wall or panel:
1. Lay out the required points on the wall or panel as shown in the drilling
dimension drawing.
Drilling Dimensions for Panel or Wall Mounting
58.5
(2.3)
35.5
(1.4)
Millimeters
35.5
(1.4)
(Inches)
21 (0.83)
58.5
(2.3)
35.5
(1.4)
Publication 1794-6.5.11 - September 2011
Page 28
18 Install Your FLEX I/O Frequency Input Module
IMPORTANT
2. Drill the necessary holes for the #6 self-tapping mounting screws.
3. Mount the mounting plate for the adapter module using two #6
self-tapping screws – 18 screws are included for mounting up to 8
modules and the adapter.
Make certain that the mounting plate is properly grounded to
the panel. Refer to Industrial Automation Wiring and Grounding
Guidelines, publication 1770-4.1
.
4. Hold the adapter at a slight angle and engage the top of the mounting
plate in the indention on the rear of the adapter module.
5. Press the adapter down flush with the panel until the locking lever locks.
6. Position the terminal base unit up against the adapter and push the
female bus connector into the adapter.
7. Secure to the wall with two #6 self-tapping screws.
8. Repeat for each remaining terminal base unit.
Mount the Frequency Input Module on the Terminal Base Unit
The Frequency Input module mounts on a 1794-TB3G or 1794-TB3GS
terminal base unit.
1. Rotate keyswitch (3) on terminal base unit (4) clockwise to position 1 as
required for the module.
Do not change the position of the keyswitch after wiring the terminal
base unit.
Publication 1794-6.5.11 - September 2011
Page 29
Install Your FLEX I/O Frequency Input Module 19
1
2
3
4
5
6
7
8
Label here or under here
40231
ATTENTION
DescriptionDescription
1FlexBus connector5Base unit
2Latching mechanism6Alignment groove
3Keyswitch7Alignment bar
4Cap plug8Module
2. Make certain the FlexBus connector (1) is pushed all the way to the left
to connect with the neighboring terminal base or adapter.
You cannot install the module unless the connector is fully extended.
3. Make sure the pins on the bottom of the module are straight so they will
align properly with the connector in the terminal base unit.
If you remove or insert the module while the backplane power is on,
an electrical arc can occur. This could cause an explosion in hazardous
location installations. Be sure that power is removed or the area is
nonhazardous before proceeding.
4. Position the module (8) with its alignment bar (7) aligned with the
groove (6) on the terminal base.
5. Press firmly and evenly to seat the module in the terminal base unit.
The module is seated when the latching mechanism is locked into the
module.
6. Remove cap plug and attach another terminal base unit to the right of
this terminal base unit if required.
Make sure the last terminal base has the cap plug in place.
Publication 1794-6.5.11 - September 2011
Page 30
20 Install Your FLEX I/O Frequency Input Module
IMPORTANT
Daisy-chaining
Individual
Combination
24V DC
24V DC
24V DC
24V DC
24V DC
24V DC
Frequency input
module
Digital input
module
Frequency input
module
Analog
module
Digital output
module
Digital input
module
Frequency input
module
Analog
module
Frequency input
module
Frequency input
module
Frequency Input
module
Frequency input
module
45556
Wiring when total current draw is 10 A.
Wiring when total current draw is greater than 10 A.
Total current draw through any base must not be greater than 10 A.
The adapter is capable of addressing eight modules. Do not exceed a
maximum of eight terminal base units in your system.
Wiring Information
This section provides essential wiring information for the 1794-TB3G,
1794-TB3GK, and 1794-TB3GS terminal base units. It also includes
instructions for connecting wiring to the FLEX I/O module.
34 and 50 = 24V DC
35 and 51 = common
16 and 33 = chassis
40…45 = chassis ground
35 and 51 = common
34 and 50 = 24V DC
16 and 33 = chassis ground
40…45 = chassis ground
45328
Take note of the following considerations when wiring your
terminal base units:
•AIl modules must be frequency or analog modules for the
daisychain configuration.
•Use the individual type of configuration for any "noisy" DC
digital I/O modules in your system.
•All modules powered by the same power supply must be
frequency or analog modules for the combination type of
configuration.
Wire the Terminal Base Units
Wiring the FLEX I/O Frequency Input module is done using the 1794-TB3G,
1794-TB3GK or the 1794-TB3GS terminal base unit.
1794-TB3G, 1794-TB3GK and 1794-TB3GS Wiring Connections
Connect Wiring to the FLEX I/O Frequency Input Module
Wiring to the Frequency Input module is made through the terminal base unit
on which the module mounts.
The module is compatible with the 1794-TB3G, 1794-TB3GK and
1794-TB3GS terminal base units.
Publication 1794-6.5.11 - September 2011
Page 32
22 Install Your FLEX I/O Frequency Input Module
ATTENTION
ATTENTION
ATTENTION
ATTENTION
Connecting Wiring Using a 1794-TB3G, 1794-TB3GK or
1794-TB3GS Terminal Base Unit
1. Connect individual signal wiring to numbered terminals on the 0…15
row (A) and 17…32 row (B) on the terminal base unit as indicated in
the table below.
2. Connect output signal and supply wiring to the numbered terminals on
rows B and C, as shown in the figure, 1794-TB3G, 1794-TB3GK and
1794-TB3GS Wiring Connections, on page 21.
3. Terminate shields to terminals 16 or 33 on row B, or 40…45 on row C.
4. Connect +24V DC to terminal 34 on the 34…51 row (C), and 24V
common to terminal 35 on the 34…51 row (C).
To reduce susceptibility to noise, power frequency modules and digital
modules from separate power supplies. Do not exceed a length of
10 m (33 ft) for DC power cabling.
5. If daisychaining the +24V DC power to the next 1794-TB3G or
1794-TB3GS base unit, connect a jumper from terminal 50 (+24V) on
this base unit to terminal 34 and from terminal 51 (24V DC common)
to terminal 35 on the next 1794-TB3G or 1794-TB3GS base unit.
Use extreme care when connecting wiring to an adjacent terminal
base unit. Wiring for the 1794-TB3G and 1794-TB3GS terminal base
units is different from other 1794 terminal base units.
Do not daisychain power or ground from the 1794-TB3G or
1794-TB3GS terminal base unit to any AC or DC digital module
terminal base unit.
24V DC power must be applied to your module before operation. If
power is not applied, the module position will appear to the adapter as
an empty slot in your chassis. If the adapter does not recognize your
module after installation is completed, cycle power to the adapter.
Publication 1794-6.5.11 - September 2011
Page 33
Install Your FLEX I/O Frequency Input Module 23
ATTENTION
Wiring Connections for the Frequency Input Module
RET
(5)
Channel 1 Terminals
(7)
Power Input
Channel 0 Terminals
Types of InputsPower Input
Frequency
24V DC IEC1+ Proximity
24V DC Contact Switch
(1) (2)
(3)
500mV AC Magnetic Pickup
50mV AC Magnetic Pickup
7638912
7638912
(6)
7
(4)
75381012
53 8 1012
6V AC Vortex213131412
3V AC Vortex203131512
Gate
24V DC IEC1+ Proximity
24V DC Contact Switch
(1) (2)
(3)
242320252629
242320252629
500mV AC Magnetic Pickup242220252729
(4)
50mV AC Magnetic Pickup
(1)
As defined by standard IEC 1131-2.
(2)
RET not used on 2-wire devices.
(3)
Add external resistor from 24V to F or G for wire-off detection (0.4 mA) – (≈ 50 KΩ ).
(4)
Add a jumper between 50 mV and RET (Frequency – channel 0 = 3…4; channel 1 = 11…12)
(Gate – channel 0 = 21…20; channel 1 = 28…29).
(5)
Connect cable shields to GND terminals.
(6)
24V terminal may not be used on 2-wire magnetic devices.
(7)
All 4 RET terminals (ch 0 and 1, Freq, Gate) are internally connected together.
242220252729
RET
(5)
(7)
GND
(5)
Total current draw through the terminal base unit is limited to 10 A.
Separate power connections to the terminal base unit may be
necessary.
Publication 1794-6.5.11 - September 2011
Page 34
24 Install Your FLEX I/O Frequency Input Module
+24V DC = Terminals C-34 and C-50
COM = C-35 and C-51
Chassis Ground = Terminals B-16, B-33, C-38, C-40…45, and C-47
NC = No connection
For daisychaining:
Supply in – C-34 (+) and C-35 (-)
Supply out – C-50 (+) and C-51 (-)
45346
Connections for Terminal Base 1794-TB3G shown
0123456789101112131415
24V
3V6V 24V
171819202122232425 2627282930313233
16
Out 0
Out 0
Ret
3536373839404142434445464748495051
34
RET 50
Pwr
Channel 0 Frequency InputChannel 1 Frequency Input
Channel 0 Gate InputChannel 1 Gate Input
mV
Sel
mV
Sel
500/50
mV
500/50
50
mV
Pwr
24V
Pwr
24V
Pwr
24V
Pwr
500/50mV50
500/50mV50
mV
Sel
mV
Sel
RETFF
Pwr
3V6V24V
Out 1
Out 1RETGGRET
Ret
Chassis GndChassis Gnd
+V COM+V COM
24V DC
Supply In
Sply 0
Channel 0 Output SupplyChannel 1 Output Supply
Gnd
Sply 0
Ret
6 Chassis Ground
for Shields
Sply 1
Gnd
Sply 1
Ret
24V DC
Supply Out
Output Alarm Connections
Output Alarm
Channel 0 Terminals
(1)
Channel 1 Terminals
(1)
Connections
Supply+Supply
RET
Out +Out
RET
Supply+Supply
RET
Out +Out
SupplyC-37C-39C-46C-48
OutputB-17B-18B-31B-32
(1)
Connect cable shields to GND connections.
RET
Resolution and Accuracy
Publication 1794-6.5.11 - September 2011
1 Hz or 0.1 Hz (depending on frequency range bit setting), or + accuracy
specification listed below, whichever is greater.
Important: When using a channel
for 50 mV sensor, jumper the
50/500 mV pin to the appropriate
RET.
Magnetic
Input
Device
4041
3
3
42
14
12
12
13
45
6V Vortex Flowmeter
42
38
16
39
External
Power Supply #1
10-31.2V DC @ 1A
+
-
+
-
LOAD 0
9
Power
In
8
44
24V DC Contact Switch
Add external resistor
from 24V to F or G for
wire-off detection.
3
6V Vortex
Flowmeter
+
-
+
-
45347
Examples of Wiring to a 1794-TB3G Terminal Base Unit
Chapter Summary
This chapter provided you with instructions on how to install the input
module in an existing programmable controller system and how to wire to a
terminal base unit.
Publication 1794-6.5.11 - September 2011
Page 38
28 Install Your FLEX I/O Frequency Input Module
Notes:
Publication 1794-6.5.11 - September 2011
Page 39
Chapter
ATTENTION
Configure Your FLEX I/O Module with
RSLogix 5000 Software
3
Overview
This chapter describes how to configure the 1794-IJ2 module for the
ControlLogix and CompactLogix system. The module can communicate
through different networks such as ControlNet, Ethernet, Profibus, among
others. In the examples below, the Ethernet adapter is used for
communication between the Logix processor and the FLEX I/O bus.
If using an SLC controller with ControlNet, refer to the
associated I/O scanner documentation.
If using a PLC 5 controller, refer to the PLC 5 controller
documentation for ControlNet configuration information.
You need to follow these series of steps to fully configure your FLEX I/O
module in the RSLogix 5000 software.
1. Add and configure the new local bridge module, such as 1756-ENBT, to
your project. This user manual assumes you have already properly
configured this module. Refer to the associated documentation.
2. Add and configure the new adapter module, such as a FLEX I/O
EtherNet Adapter (1794-AENT). This user manual assumes you have
already properly configured this module. Refer to the associated
documentation.
3. Add and configure your FLEX I/O module. See the steps provided
below.
4. Download the configuration to the controller.
Add and Configure the
To be able to add your FLEX I/O Frequency Input module, you should have
already added and configured your Ethernet bridge and adapter.
FLEX I/O Module
29Publication 1794-6.5.11 - September 2011
Page 40
30 Configure Your FLEX I/O Module with RSLogix 5000 Software
Right-click the local communication module.
Select New Module.
1. Select New Module for the I/O Configuration.
2. The Select Module dialog appears.
Publication 1794-6.5.11 - September 2011
Select the FLEX I/O module from the Specialty module type. Click OK
3. The New Module dialog appears.
Page 41
Configure Your FLEX I/O Module with RSLogix 5000 Software 31
Complete the following fields and click OK.
•Name
•Description
• Comm Format
• Electronic Keying
4. On the Connection tab, specify a value for the Requested Packet
Interval(RPI).
5. On the Fault Action tab, specify the following:
•Fault Mode
• Communication Fault Behavior
Publication 1794-6.5.11 - September 2011
Page 42
32 Configure Your FLEX I/O Module with RSLogix 5000 Software
6. On the Configuration tab, specify the following:
• Channel
• Frequency or Acceleration
If you choose Frequency, go to step 8. Go to step 9 if you choose
Acceleration.
7. For Frequency mode, specify the following:
• Maximum Frequency
• Frequency Range
• Minimum Frequency Sample Time
8. For Acceleration mode, specify the following:
• Maximum Frequency
• Frequency Range
• Minimum Frequency Sample Time
• Acceleration Calculation Time
9. Click the Alarms tab and specify the following:
• Missing Pulse Multiplier
• Missing Pulse Delay Multiplier
• Pulses to Terminate Sampling
• Wire-off/Missing Pulse Fault Select Mode
Publication 1794-6.5.11 - September 2011
10. Click OK on the Module Properties dialog after you have configured the
different parameters.
The following options are available for each parameter on the Configuration
and Alarms tabs of the Module Properties dialog.
Page 43
Configure Your FLEX I/O Module with RSLogix 5000 Software 33
Configuration Parameters
Module PropertyConfiguration Options
Maximum Frequency0 Hz (default)
Frequency Range1…32767
1.0…3276.7
Minimum Frequency Sample Time2…100
Acceleration Calculation TimeRolling Average
8
16
32
Missing Pulse MultiplierNone
2
8
32
Pulses to Terminate SamplingMinimum Frequency Sample Time
2
4
8
16
32
Wire-off/Missing Pulse Fault Select
Mode
Disabled
Alarm Only
Alarm/Maximum Frequency
Alarm/Minimum Frequency
Chapter Summary
You should now see the 1794-IJ2 module added to your
I/O Configuration tree.
To be able to check if your configured parameters are acceptable and the
configuration is successful, you need to go online.
Refer to the RSLogix 5000 Online Help for detailed descriptions of the
configuration parameters.
This chapter provided instructions and required parameters for setting up your
FLEX I/O module on an EtherNet/IP network.
Publication 1794-6.5.11 - September 2011
Page 44
34 Configure Your FLEX I/O Module with RSLogix 5000 Software
Notes:
Publication 1794-6.5.11 - September 2011
Page 45
Chapter
4
Read and Write Configuration Maps for the
FLEX I/O Module
Overview
Configure Your Frequency
Input Module
This chapter describes how to configure, read data from, and map data to your
Frequency Input module.
TopicPage
Configure Your Frequency Input Module35
Read Data From Your Module35
Map Data for the Module36
Frequency Input Module Image Table Mapping36
Chapter Summary49
The frequency module is configured using a group of data table words that are
transferred to the module using a block transfer write instruction.
The software features available for configuration are:
• frequency range
• number of pulses to sample
• sampling time
• safe states
• fault modes
• alarms
Configure your module for its intended operation by means of your
programming terminal and write block transfers.
During normal operation, the processor transfers from 1…8 words to the
module when you program a BTW instruction to the module address.
Read Data From Your
Module
35Publication 1794-6.5.11 - September 2011
Read programming transmits status and data from the frequency input module
to the processor data table in one I/O scan. The processor user program
initiates the request to transfer data from the frequency input module to the
processor.
Page 46
36 Read and Write Configuration Maps for the FLEX I/O Module
Module Image
I/O Image
Frequency Channel 0
% Full Scale or Acceleration Channel 0
Diagnostics
Input size
Output size
0...7 Words
1...6 Words
Frequency Channel 1
% Full Scale or Acceleration Channel 1
GS1F/A1WO1MPA
1
DIR
1
GS0F/A0WO0MPA
0
DIR
0
RRR
Reserved
FR
1
MPM
1
R
NOPTS
1
LF
FR
0
MPM
0
NOPTS
0
SSMCF
Minimum Freq or Absolute Value of Acceleration Channel 0
Frequency Scaling Divisor Channel 0
Frequency Scaling Multiplier Channel 0
F/A
AS0
WOFM
0
IS
UP0
MPDM
0
MFST
0
ACT 0
IFI
0
IGI
0
WOFF
0
WOFG
0
Minimum Freq or Absolute Value of Acceleration Channel 1
Frequency Scaling Divisor Channel 1
Frequency Scaling Multiplier Channel 1
F/A
AS1
WOFM
1
IS
UP1
MPDM
1
MFST
1
ACT 1
IFI
1
IGI
1
WOFF
1
WOFG
1
45351
Map Data for the Module
The following read and write words and bit/word descriptions describe the
information written to and read from the frequency input module. The
module uses up to 6 words of input data and up to 7 words of output data.
Each word is composed of 16 bits.
Ch 1
5ReservedDiagnostic Status
Where:R = Reserved
GS = Gate state
F/A = Frequency/Acceleration alarm
WO = Wire-off alarm
MPA = Missing pulse alarm
Bit/Word Definitions for Block Transfer Read Words
WordBitDefinition
Read
Word 0
Bit 00…15
(00…17)
Word 1Bit 00…15
(00…17)
Word 2Bit 00…15
(00…17)
Word 3Bit 00…15
(00…17)
Calculated value of frequency (channel 0) – frequency can be reported down to 1 or 1.0 Hz, depending on
the Frequency Range bit setting:
Below a 1 Hz value, 0 is reported
Below a 1.0 Hz value, 0.0 is reported.
Calculated frequency depends on Minimum Sampling Time and Missing Pulse Multiplier.
% of Full Scale or Acceleration (channel 0) – Value of the calculated frequency scaled by the Maximum
Frequency, or Calculated Value of Acceleration in Hz/s, depending on the state of the Frequency or
Acceleration Alarm Select bit.
Note: Percentage Full scale is calculated accurately up to a maximum of 3,276.7%. Beyond this maximum,
the value of 3,276.7% will be returned, and a Calculation Failure (9) will be set in the Diagnostic Status
byte.
Calculated value of Frequency (channel 1) – Frequency can be reported down to 1 or 1.0 Hz, depending on
the Frequency Range bit setting; below a 1 Hz value, 0 is reported; below a 1.0 Hz value, 0.0 is reported.
Calculated frequency depends on Minimum Sampling Time and Missing Pulse Multiplier.
Percentage of Full Scale or Acceleration (channel 1) – Value of the calculated Frequency scaled by the
Maximum Frequency, or Calculated Value of Acceleration in Hz/s, depending on the state of the Frequency
or Acceleration Alarm Select bit. Percentage full scale will be calculated accurately up to a maximum of
3,276.7%. Beyond this maximum, the value of 3,276.7% is returned, and a Calculation Failure (9) is set in
the Diagnostic Status byte.
Publication 1794-6.5.11 - September 2011
Page 48
38 Read and Write Configuration Maps for the FLEX I/O Module
Bit/Word Definitions for Block Transfer Read Words
WordBitDefinition
Word 4Bits 00Missing Pulse Alarm (channel 1) – Indicates that no Frequency input pulse has occurred within the period
determined by the Minimum Frequency Sampling Time and the Missing Pulse Multiplier. Primary control is
given to the Missing Pulse Multiplier to determine when this bit is set. However, if the Missing Pulse
Multiplier is set to 0, then the Minimum Frequency Sampling Time characteristics will determine when this
bit is set.
Bit 01Wire Off Fault Alarm (channel 1) – when set, indicates that 24V DC Input (IEC 1+ or Switch Contact with
shunt) Wire Off Detection has gone true for any of the Frequency or Gate inputs on a channel that has the
Wire Off Fault Select = 1.
Bit 02Frequency or Acceleration Alarm (channel 1) – Changes state from 0…1 if the calculated Frequency (actual
or scaled) exceeds the user programmed Maximum Frequency, or the absolute value of calculated
Acceleration/Deceleration exceeds the user programmed Maximum Acceleration Value.
The Frequency Alarm turns off when the Frequency drops below 95% of the Alarm Value.
The Acceleration Alarm turns off when the Acceleration drops below 90% of the Alarm Value.
Bit 03Gate Input State (channel 1) – Indicates if there is a valid signal on the gate input. This parameter is only
determined once every 0.5…2 s.
Bits 04…05Direction (channel 1) – Indicates the current Direction of Rotation, using both the Frequency and Gate
inputs. (Frequency leads Gate = Clockwise; Gate leads Frequency = CounterClockwise). Used for slow speed
detection from 1…1,500Hz. No or Stopped rotation can be determined by the state of the Missing Pulse
Alarm, when it is switched on. A missing Frequency Input generates a Missing Pulse Alarm, a missing Gate
Input only generates a No Sensor Present/Detected status (3).
Bits 06…07Not used
Bits 08 (10)Missing Pulse Alarm (channel 0) – Indicates that no frequency input pulse has occurred within the period
determined by the Minimum Frequency Sampling Time and the Missing Pulse Multiplier. Primary control is
given to the Missing Pulse Multiplier to determine when this bit is set. However, if the Missing Pulse
Multiplier is set to 0, then the Minimum Frequency Sampling Time characteristics determines when this bit
is set.
Bit 09 (11)Wire Off Fault Alarm (channel 0) – When set, indicates that 24V DC Input (IEC 1+ or Switch Contact with
shunt) Wire Off Detection has gone true for any of the Frequency or Gate inputs on a channel that has the
Wire Off Fault Select = 1.
Bit 10 (12)Frequency or Acceleration Alarm (channel 0) – Changes state from 0…1 if the calculated Frequency (actual
or scaled) exceeds the user programmed Maximum Frequency, or the absolute value of calculated
Acceleration/Deceleration exceeds the user programmed Maximum Acceleration Value.
The Frequency Alarm turns off when the Frequency drops below 95% of the Alarm Value.
The Acceleration Alarm turns off when the Acceleration drops below 90% of the Alarm Value.
Bit 11 (13)Gate Input State (channel 0) – Indicates if there is a valid signal on the gate input. This parameter is only
determined once every 0.5…2 s.
Bits 12…13
(14…15)
Direction (channel 0) – Indicates the current Direction of Rotation, using both the Frequency and Gate
inputs.
Frequency leads Gate = Clockwise
Gate leads Frequency = CounterClockwise
Used for slow speed detection from 1…1,500Hz. No or Stopped rotation can be determined by the state of
the Missing Pulse Alarm, when it is switched on. A missing Frequency Input generates a Missing Pulse
Alarm, a missing Gate Input only generates a No Sensor Present/Detected status (3).
Bits 14…15
Not used
(16…17)
Publication 1794-6.5.11 - September 2011
Page 49
Read and Write Configuration Maps for the FLEX I/O Module 39
Bit/Word Definitions for Block Transfer Read Words
WordBitDefinition
Word 5Bits 00…03Diagnostic Status – indicates the response from the module; a normal or non-normal
operating condition.
Bit03020100
00000 = Normal Operation (No Failure)
00011 = Calibration Failure
00102 = Configuration Failure
A Minimum Frequency Sample Time value other than 0…9
was selected.
00113 = Message Failure
01004 = Lead Break Detection Hardware Failure
01015 = Major Hardware Failure
01106 = EEPROM Failure
01117 = RAM Failure
10008 = ROM Failure
10019 = Calculation Failure
The actual Frequency is greater than 32,767 Hz. or 3,276.7 Hz.
(overange).
The scaled Frequency is greater than 32,767 Hz. or 3,276.7 Hz.
(overange).
The % Full Scale calculation (based on Maximum Frequency) is
> 3,276.7%.
1010…1111 10…15 = Not Used
Bits 04…15
Reserved
(04…17)
Block Transfer Write Word Assignments
(Octal Bit)17161514131211100706050403020100
Dec. Bit 15 14 13121110090807060504 03020100
0CFSSMFR
Ch 0
Number Of Pulses
To Terminate
Sampling Ch 0
MPM
Ch 0
RLFFR
Ch 1
Number Of Pulses To
Terminate Sampling
Ch 1
MPM
Ch 1
1Maximum Frequency 0…32,767 or 0.0…3,276.7 or Absolute Value of Acceleration 0…32,767 – Channel 0
2Frequency Scaling Divisor 0…255 Ch 0Frequency Scaling Multiplier 0…255 Ch 0
3WOFG
Ch 0
WOFF
Ch 0
IGI
Ch 0
IFI
Minimum Frequency
Ch 0
Sample Time Ch 0
ACT Ch 0F/A AS
Init
St Up
Ch 0
MPDM
Ch 0
WOFM
Ch 0
Ch 0
4Maximum Frequency 0…32,767 or 0.0…3,276.7 or Absolute Value of Acceleration 0…32,767 – Channel 1
Publication 1794-6.5.11 - September 2011
Page 50
40 Read and Write Configuration Maps for the FLEX I/O Module
Block Transfer Write Word Assignments
(Octal Bit)17161514131211100706050403020100
Dec. Bit 15 14 13121110090807060504 03020100
Bit/Word Definitions for the Block Transfer Write Words
WordBit
Definition
Write Word 0Bits 00…01Missing pulse multiplier bits (channel 1) – used to modify the Minimum Frequency
Sampling Time to allow the frequency bandwidth to be more closely adjusted to the
value needed to report the proper frequency and report a missing pulse more quickly.
Default = No multiplier; alarm generated immediately
Bit0100Missing Pulse Multiplier
00No Multiplier, normal mode with 2 s delay
01X2
10X8
11X32
Bits 02…04Number of pulses to terminate sampling (channel 1) – Lets you calculate Frequency
when a specified number of input pulses have occurred. This allows earlier reporting of
the frequency than the Minimum Frequency Sampling Time, when many input pulses are
occurring. Accurate frequency determination is possible without waiting for the full
Minimum Frequency Sampling Time to expire.
Default = Minimum frequency sampling time
Bit040302Number of pulses to terminate sampling
000Use minimum frequency sampling time
0012
0104
0118
10016
10132
11064
111128
Publication 1794-6.5.11 - September 2011
Page 51
Bit/Word Definitions for the Block Transfer Write Words
Read and Write Configuration Maps for the FLEX I/O Module 41
WordBit
Word 0
Bits 05Frequency range bits (channel 1) – Specifies the Frequency Range of the Frequency
(con’t.)
Bits 06Local fault mode selection – determines how the Module Safe State data is used to
control alarm outputs for bus communication and internal module faults.
Local Fault = Wire Off Fault or Missing Pulse Alarm.
0 = Safe states activated by bus communication only;
1 = Safe states activated by any failure (bus communication, internal module faults,
and so on.)
Default = 0, safe states activated by bus communication only
Missing pulse multiplier bits (channel 0) – used to modify the Minimum Frequency
Sampling Time to allow the frequency bandwidth to be more closely adjusted to the
value needed to report the proper frequency and report a missing pulse more quickly.
Default = No multiplier; alarm generated immediately
Bit09
Number of pulses to terminate sampling (channel 0) – Lets you calculate Frequency
when a specified number of input pulses have occurred. This allows earlier reporting of
the frequency than the Minimum Frequency Sampling Time, when many input pulses are
occurring. Accurate frequency determination is possible without waiting for the full
Minimum Frequency Sampling Time to expire.
Default = Minimum frequency sampling time.
Bit12
Number of pulses to terminate sampling
(14)11(13)10(12)
000Use minimum frequency sampling time
0012
0104
0118
10016
10132
11064
111128
Publication 1794-6.5.11 - September 2011
Page 52
42 Read and Write Configuration Maps for the FLEX I/O Module
Bit/Word Definitions for the Block Transfer Write Words
WordBit
Definition
Bit 13 (15)Frequency range bits (channel 0) – Specifies the Frequency Range of the Frequency
Bit 14 (16)Safe state mode bit – selection determines how module alarm outputs react to bus
communication and internal module faults
Local fault = Wire Off Fault or Missing Pulse Alarm
0 = Reset outputs
1 = Hold last state
Default = 0 (reset outputs)
Bit 15 (17)Communication fault – Signals that communication has been interrupted on the
network. The adapter signals that the module should execute its fault routine or go to
the Safe State and control any Alarm Outputs accordingly. During normal startup, this bit
must be set (1) by the user program to begin normal module operation of Alarm Outputs
(in effect, an output enable). When the adapter communication link is broken, the
adapter will reset this bit (0). Adapter dependent.
Default = 0
Word 1Bits 00…15
(00…17)
Maximum frequency or absolute value acceleration/deceleration (channel 0) – Specifies
the highest Frequency or absolute Acceleration/Deceleration value allowed on the
Frequency input. 0…32,767, 0.0…3,276.7 Hz. or 0…32,767 Hz/s depending on the
Frequency Range and Frequency/Acceleration Alarm Select bits.
Word 2Bits 00…07Frequency scaling multiplier (channel 0) – Specifies a multiplier to scale the incoming
Frequency value, 0…255.
Bits 08…15
(10…17)
Default = 0 – no scaling multiplication performed (x1)
Frequency scaling divisor (channel 0) – Specifies divisor to scale the incoming Frequency
value, 0…255.
Default = 0 – no scaling division performed (divided by 1)
Publication 1794-6.5.11 - September 2011
Page 53
Bit/Word Definitions for the Block Transfer Write Words
Read and Write Configuration Maps for the FLEX I/O Module 43
WordBit
Definition
Word 3Bits 00…01Wire-Off/Missing Pulse fault select mode (channel 0) – Sets the mode for 24V DC IEC 1+
Wire Off Input Detection and Missing Pulse Detection result for any input (Frequency or
Gate). The Maximum Frequency is determined by Frequency Range bit and the
Maximum Frequency value, and the Minimum Frequency is determined by Frequency
Range bit. The Wire Off detect time (in mode 1, 2, & 3) is 2 seconds maximum.
00Disabled
01Alarm only (frequency unchanged)
10Alarm and force frequency to maximum frequency value
(32767 or 3276.7 or maximum frequency value, 0).
11Alarm and force frequency to minimum frequency value (0 or 0.0).
Bits 02…03Missing pulse delay multiplier bits (channel 0) – Specifies the number of Missing Pulse
Alarms periods (Minimum Frequency Sampling Times) which is permitted before the
alarm is raised, if enabled. Used to defeat the Missing Pulse Alarm during a system
startup.
Default = 0 – No multiplier; alarm generated immediately (normal mode with 2 s
extension delay)
Bit0302Alarm periods before alarm generated
00No multiplier; alarm generated immediately (normal mode with 2 s
extension delay)
012 sample periods + 2 s delay before alarm
108 sample periods + 2 s delay before alarm
1132 sample periods + 2 s delay before alarm
Bit 04Frequency or Acceleration Alarm Select (channel 0) – Determines if the value in the
Maximum Frequency or Acceleration write word is a Frequency (actual or scaled) or
Acceleration Alarm value. If set to Frequency, Acceleration is not calculated.
0 = Frequency alarm
1 = Acceleration alarm
Default = 0 – frequency alarm
Bits 05…06Acceleration Calculation Time (channel 0) – Specifies the number of Frequency Sample
Times over which the module calculates acceleration.
Default = 0 – Rolling Average (previous 4 samples)
Bit0605Acceleration Calculation Time in Frequency Sample Times
00Rolling Average (previous 4 samples)
018
1016
1132
Bit 07Initiate Startup Select (channel 0) – Alerts a channel that if process start up is in
progress to defeat the missing pulse alarm for a time determined by the missing pulse
delay multiplier.
0 = Normal Run Mode;
1 = Startup Mode – defeat/delay Missing Pulse Alarm
Default = 0 – Normal Run Mode
Publication 1794-6.5.11 - September 2011
Page 54
44 Read and Write Configuration Maps for the FLEX I/O Module
Bit/Word Definitions for the Block Transfer Write Words
WordBit
Definition
Word 3Bit 07Minimum Frequency Sampling Time (channel 0) – Specifies the minimum time (in ms)
the module spends collecting pulses to determine the Frequency.
Bits 08…11
(10…13)
Bit11
(13)10(12)09(11)08(10)
Minimum Frequency Sampling Time (in ms)
0000 2
0001 4
0010 5
0011 10
0100 20
0101 50
0110100
0111200
1000500
10011000
1010…1111 not used – 2 ms default sample time used
Bit 12 (14)Invert Select – Frequency Input (channel 0) – Selects whether to invert the Frequency
input signal, if not using an Active High (24V = On) 24V DC IEC 1+ sensor or Normally
Open relay or switch contact on the 24V DC Frequency Input terminal. Allows
compatibility with an Active Low (0V = On) 24V DC IEC 1+ sensor or Normally Closed
relay contact on the 24V DC Frequency Input terminal.
Bit 13 (15)Invert Select – Gate Input (channel 0) – Selects whether to invert the Gate input signal,
if not using an Active High (24V = On) 24V DC IEC 1+ sensor or Normally Open relay or
switch contact on the 24V DC Gate Input terminal. Allows compatibility with an Active
Low (0V = On) 24V DC IEC 1+ sensor or Normally Closed relay contact on the 24V DC
Gate Input terminal.
Bit 14 (16)Wire Off Fault Select – Frequency Input (channel 0) – Selects whether to turn On or Off
the 24V DC Frequency input IEC 1+ hardware Wire Off (Lead Breakage) detection.
0 = Disable,
1 = Enable
Default: = 0 – Disable
Note: Customer devices must draw more than 0.4 mA in the On and Off State. To use
this feature with relays or switches, connect a shunt resistor (~ 50K) across the
contacts.
Bit 15 (17)Wire Off Fault Select – Gate Input (channel 0) – Selects whether to turn On or Off the
24V DC Gate input IEC 1+ hardware Wire Off (Lead Breakage) detection.
0 = Disable,
1 = Enable
Default = 0 – Disable
Note: Customer devices must draw more than.4 mA in the On and Off State. To use this
feature with relays or switches, connect a shunt resistor (~ 50K) across the contacts.
Publication 1794-6.5.11 - September 2011
Page 55
Bit/Word Definitions for the Block Transfer Write Words
Read and Write Configuration Maps for the FLEX I/O Module 45
WordBit
Word 4Bits 00…15
(00…17)
Definition
Maximum frequency or absolute value acceleration/deceleration (channel 1) – Specifies
the highest Frequency or absolute Acceleration/Deceleration value allowed on the
Frequency input. 0…32,767 Hz, 0.0…3,276.7 Hz. or 0…32,767 Hz/s depending on the
Frequency Range and Frequency/Acceleration Alarm Select bits.
Word 5Bits 00…07Frequency scaling multiplier (channel 1) – Specifies a multiplier to scale the incoming
Frequency value, 0…255.
Default = 0 – no scaling multiplication performed (x1)
Bits 08…15
(10…17)
Frequency scaling divisor (channel 1) – Specifies divisor to scale the incoming Frequency
value, 0…255.
Default = 0 – no scaling division performed (divided by 1)
Publication 1794-6.5.11 - September 2011
Page 56
46 Read and Write Configuration Maps for the FLEX I/O Module
Bit/Word Definitions for the Block Transfer Write Words
WordBit
Definition
Word 6Bits 00…01Wire-Off/Missing Pulse fault select (channel 1) – Sets the mode for 24V DC IEC 1+ Wire
Off Input Detection and Missing Pulse Detection result for any input (Frequency or Gate).
The Maximum Frequency is determined by Frequency Range bit and the Maximum
Frequency value, and the Minimum Frequency is determined by Frequency Range bit.
The Wire Off detect time (in mode 1, 2, and 3) is 2 seconds maximum.
Bit0100Channel wire-off or missing pulse fault mode
00Disabled
01Alarm only (frequency unchanged)
10Alarm and force frequency to maximum frequency value (32767 or
3276.7 or maximum frequency value, 0).
11Alarm and force frequency to minimum frequency value (0 or 0.0).
Bits 02…03Missing pulse delay multiplier bits (channel 1) – Specifies the number of Missing Pulse
Alarms periods (Minimum Frequency Sampling Times) which will be tolerated before the
alarm is actually generated, if enabled. (Used to defeat the Missing Pulse Alarm during
a system startup.)
Default = 0 – No multiplier; alarm generated immediately (normal mode with 2 s
extension delay)
Bit0302Alarm periods before alarm generated
00No multiplier; alarm generated immediately (normal mode with 2 s
extension delay)
012 sample periods + 2 s delay before alarm
108 sample periods + 2 s delay before alarm
1132 sample periods + 2 s delay before alarm
Bit 04Frequency or Acceleration Alarm Select (channel 1) – Determines if the value in the
Maximum Frequency or Acceleration write word is a Frequency (actual or scaled) or
Acceleration Alarm value. If set to Frequency, Acceleration is not calculated.
Bits 05…06Acceleration Calculation Time (channel 1) – Specifies the number of Frequency Sample
Publication 1794-6.5.11 - September 2011
0 = Frequency alarm
1 = Acceleration alarm
Default = 0 – frequency alarm
Times over which the module calculates acceleration.
Default = 0 – Rolling Average (previous 4 samples)
Bit0605Acceleration Calculation Time in Frequency Sample Times
00Rolling Average (previous 4 samples)
018
1016
1132
Page 57
Bit/Word Definitions for the Block Transfer Write Words
Read and Write Configuration Maps for the FLEX I/O Module 47
WordBit
Definition
Word 6Bit 07Initiate Startup Select (channel 1) – Alerts a channel that if process startup is in
progress to defeat the missing pulse alarm for a time determined by the missing pulse
delay multiplier.
0 = Normal run mode,
1 = Startup Mode – Defeat/delay Missing Pulse Alarm
Default = 0 – Normal run mode
Bits 08…11
(10…13)
Minimum Frequency Sampling Time (channel 1) – Specifies the minimum time (in ms)
the module will spend collecting pulses to determine the Frequency.
Bit11100908Minimum Frequency Sampling Time (in ms)
1010…1111 not used – 2 ms default sample time used
Bit 12 (14)Invert Select – Frequency Input (channel 1) – Selects whether to invert the Frequency
input signal, if not using an Active High (24V = On) 24V DC IEC 1+ sensor or Normally
Open relay or switch contact on the 24V DC Frequency Input terminal. Allows
compatibility with an Active Low (0V = On) 24V DC IEC 1+ sensor or Normally Closed
relay contact on the 24V DC Frequency Input terminal.
48 Read and Write Configuration Maps for the FLEX I/O Module
Bit/Word Definitions for the Block Transfer Write Words
WordBit
Definition
Word 6Bit 13 (15)Invert Select – Gate Input (channel 1) – Selects whether to invert the Gate input signal,
if not using an Active High (24V = On) 24V DC IEC 1+ sensor or “Normally Open” relay or
switch contact on the 24V DC Gate Input terminal. Allows compatibility with an Active
Low (0V = On) 24 V DC IEC 1+ sensor or “Normally Closed” relay contact on the 24V DC
Gate Input terminal.
Bit 14 (16)Wire Off Fault Select – Frequency Input (channel 1) – Selects whether to turn On or Off
the 24V DC Frequency input IEC 1+ hardware Wire Off (Lead Breakage) detection.
0 = Disable,
1 = Enable
Default: = 0 – Disable
Note: Customer devices must draw more than 0.4 mA in the On and Off State. To use
this feature with relays or switches, connect a shunt resistor (~ 50K) across the
contacts.
Bit 15 (17)Wire Off Fault Select – Gate Input (channel 1) – Selects whether to power On or Off the
24V DC Gate input IEC 1+ hardware Wire Off (Lead Breakage) detection.
0 = Disable,
1 = Enable
Default = 0 – Disable
Note: Customer devices must draw more than 4 mA in the On and Off State. To use this
feature with relays or switches, connect a shunt resistor (~ 50K) across the contacts.
Input Map
Bit 15141312111009080706050403020100
WordRead
0Frequency 0…32,767 or 0.0…3,276.7 Channel 0
1% Full Scale 0.0…3,276.7% Channel 0 or Acceleration -32,768…32,767 Channel 0
2Frequency 0…32,767 or 0.0…3,276.7 Channel 1
3% Full Scale 0.0…3,276.7% Channel 1 or Acceleration -32,768…32,767 Channel 1
4RRDirection
Ch 0
5ReservedDiagnostic Status
GS
F/A
Ch 0
Ch 0
Channel 0
WO
Ch 0
MPA
RRDirection
Ch 0
Ch 1
GS
Ch 1
ReservedDiagnostic Status
Channel 1
F/A
Ch 1
WO
Ch 1
MPA
Ch 1
6Reserved
Where:R = Reserved
GS = Gate state
F/A = Frequency/Acceleration alarm
WO = Wire-off alarm
MPA = Missing pulse alarm
Publication 1794-6.5.11 - September 2011
Page 59
Read and Write Configuration Maps for the FLEX I/O Module 49
Output Map
Dec 15 141312111009 08 07 060504 03020100
Oct 17 161514131211 10 07 060504 03020100
0CFSSMFR
1Maximum Frequency 0…32.767 or 0.0…3,276.7 - or -
Absolute Value of Acceleration - 0…32767 Channel 0
This chapter provided the user with data and instructions to configure and
map FLEX I/O Frequency Input module data.
Publication 1794-6.5.11 - September 2011
Page 60
50 Read and Write Configuration Maps for the FLEX I/O Module
Notes:
Publication 1794-6.5.11 - September 2011
Page 61
Troubleshoot the Module
Chapter
5
Overview
Status Indicators
This chapter provides a description of the different status indicators for the
frequency input module to help you troubleshoot.
TopicPage
Status Indicators35
Diagnostics36
Diagnostic Bits in Word 5 of the BTR File37
The module has indicators for the following:
• Frequency and Gate Inputs
• Frequency and Gate Wire-Off Faults
•Alarm Outputs
1794-IJ2
FREQUENCY INPUT 2 CHANNEL
1
FREQGATE
0
F0F
A = Input indicator
B = Insertable label for writing individual I/O assignments
C = Wire-off fault indicator
D = Output indicator
E = Power/status indicator – indicates power applied to module and status of module
FREQGATE
1F1F
ABC
OUT
D
0
OUT
OK
1
E
45348
When an input indicator (yellow) is lighted, it indicates that a valid signal
(active high or active low) is present at one of the input terminals.
When wire-off detection is enabled, and a wire-off fault is detected (24V DC
IEC 1+ input terminal only), a fault indicator (red) flashes at a rate of 1 Hz to
signal a fault condition. A wire-off fault signal is also sent to the backplane. A
flashing red fault indication means a valid wire-off condition for a 24V DC
IEC 1+ Input or a 24V DC contact switch input with a shunt resistor.
35Publication 1794-6.5.11 - September 2011
Page 62
36 Troubleshoot the Module
When an output indicator is yellow, the logic is driving an output alarm On.
After detecting a fault, the internal circuitry sets the output data to the
appropriate safe state, as defined by the module data table. Safe state control
may be adapter-dependent.
The input and output indicators are on the field side of the isolation path, and
display the logic state of the actual microcontroller input and output.
The status indicator initially powers up as solid green, indicating the power
supply is operating and internal diagnostic tests are being performed. After a
successful power up test, the indicator remains green. The indicator turns red
in about 1.5 s if there is an internal diagnostics error.
The module is operating correctly when the green OK indicator is on.
A red OK indicator shows that the module is in a Faulted condition, indicating
an internal error.
IndicatorConditionOperating Description
Input (0, 1)Off (Dark)Input Turned Off, Input Not Used, or
Wire Disconnected
Diagnostics
(Freq. or Gate)On (Yellow)Input Turned On
(Active High or Active Low if Inverted)
Fault (F)Off (Dark)Wire connected, normal operation or
detection disabled
(Freq. or Gate)On (Red
Flashing)
Output Alarm
(0, 1)
Status (OK)Off (Dark)24V Power Turned Off,
Off (Dark)Output alarm turned off
On (Yellow)Output alarm turned on (Logic Drive On)
Wire disconnected, fault condition
(for IEC1 + Proximity switch or switch contacts
with shunt resistor)
or 5V Logic Power Problem
The frequency input module returns diagnostics to the PLC processor in Word
5 of the BTR file. These diagnostics give you information on the status or
condition of the module.
Publication 1794-6.5.11 - September 2011
Page 63
Troubleshoot the Module 37
45375
See table, Diagnostic Bits in Word 5, for diagnostics
Diagnostic Bits in Word 5 of the BTR File
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
word 5
Diagnostic Bits in Word 5
Word 5Bits 00…03Diagnostic Status – indicates the response from the module; a normal or non-normal
operating condition.
Bit03020100Decimal equivalent and condition
00000 = Normal operation (no failure)
00011 = Calibration failure
00102 = Configuration failure – a Minimum Frequency
The actual frequency is greater than 32,767 Hz or
3,276.7 Hz (overrange).
The scaled Frequency is greater than 32,767 Hz or
3,276.7 Hz (overrange).
The % Full Scale calculation (based on Maximum
Frequency) is > 3,276.7%.
1010…1111 10…15 = Not used
This chapter explained how to interpret the status indicators of the frequency
input module and the internal diagnostics that indicates the condition of the
module.
Publication 1794-6.5.11 - September 2011
Page 64
38 Troubleshoot the Module
Notes:
Publication 1794-6.5.11 - September 2011
Page 65
Specifications
Appendix
A
What This Appendix
Contains
This appendix contains the frequency accuracy and general specifications of
the Frequency Input module (1794-IJ2, 1794-IJ2K, and 1794-IJ2XT).
Input Specifications
AttributeValue
Number of input channels2
Number of inputs per
channel
Input frequency, max32 kHz
Frequency value, max32,767 Hz or 3,276.7 Hz (dependent on range)
Input pulse width20 μs
Resolution and accuracySee table, Resolution and Accuracy
On-state voltage, min10V (24V IEC+1 proximity, encoder input or switch inputs)
On-state voltage, nom
(selected by terminal base
connections)
On-state voltage, maxLimited to isolated 24V DC power supply
2 – Frequency and Gate
(gate used to establish direction)
, on page 24
50 mV AC, 28V AC peak – Extended magnetic pickup
500 mV AC, 28V AC peak – Magnetic pickup
< 3V – Vortex flowmeter low range
> 6V – Vortex flowmeter high range
24V DC IEC+1 proximity or encoder input
24V DC Contact switch input
On-state current
min
nom
max
Off-state current<1.5mA into 24V DC IEC+ terminal
Off-state voltage, max5.0V DC on 24V DC IEC+1 terminal
Wire-off detection0.4 mA for proximity, encoder or contact switch with
Frequency input impedance>5 KΩ for 50 mV Extended magnetic pickup
Gate input impedance>5 KΩ for 50 mV Extended magnetic pickup
55Publication 1794-6.5.11 - September 2011
2.0 mA
9.0 mA
10.0 mA
50 kΩ shunt resistor
>5 KΩ for 500 mV Magnetic pickup
>10 KΩ for 3V Vortex flowmeter low range
>10 KΩ for 6V Vortex flowmeter high range
>2.5 KΩ for 24V DC IEC+1 proximity or encoder input
>2.5 KΩ for 24V DC Contact switch input
>5 KΩ for 500 mV Magnetic pickup
>2.5 KΩ for 24V DC IEC+1 proximity or encoder input
>2.5 KΩ for 24V DC Contact switch input
Page 66
56 Specifications
Output Specifications
(1)
AttributeValue
Number of outputs2 – isolated
Output voltage sourceCustomer supplied
Output voltage
min
nom
max
10V DC
24V DC
31.2V DC
On-state current, min1 mA per output
On-state current, max1.0 A per channel sourced out of module
Current Limited – All outputs can be On simultaneously
without derating
Surge current2 A for 50 ms, repeatable every 2 s
Off-state leakage, maxLess than 300 μA @ 31.2V DC
On-state voltage drop0.9V DC @ 1 A
Output controlOutputs individually assignable to:
Frequency, % Full scale or acceleration alarm
Output switching timeTriggered by frequency alarm or acceleration alarm
Turn on: Less than 0.5 ms
Turn off: Less than 1 ms
(1)
Meets IEC 1A 24V DC output specifications.
General Specifications
AttributeValue
Module locationCat. No. 1794-TB3G and 1794-TB3GS terminal base units
External DC power
Voltage range
Supply voltage, nom
Supply current
(Input for +5V logic and 24V DC/DC converters)
19.2…31.2V DC (includes 5% AC ripple)
24V DC
220 mA @ 19.2V DC
180 mA @ 24V DC
140 mA @ 31.2V DC
Isolated DC power
Voltage range
Supply voltage, nom
Supply current, max
Peak AC ripple, max
(Output to sensors and encoders)
21.6…26.4V DC
24V DC
0…60 mA @ 24V DC
(4 devices @ 15 mA = 60 mA)
100 mV
Dimensions (with module
installed in base) HxWxD
94 x 94 x 69 mm
(3.7 x 3.7 x 2.7 in.)
Isolation voltage50V (continuous), Basic Insulation Type
Type tested @ 1365V AC for 60 s, between field side
and system and individual channels
Processing time<4 ms
FlexBus current30 mA @ 5V DC
Publication 1794-6.5.11 - September 2011
Page 67
Specifications 57
General Specifications
AttributeValue
Power dissipation, max4.6W @ 31.2V DC
Thermal dissipation, max15.6 BTU/hr @ 31.2V DC
Indicators (field side driven,
2 yellow status indicators (Out 0, Out 1) – logic side
Keyswitch position1
Wire sizeDetermined by installed terminal base
Wiring category
(1)
2 – on signal ports
3 – on power ports
Wire typeShielded on signal ports
Terminal screw torqueDetermined by installed terminal base
Enclosure type ratingNone (open-style)
North American temp codeT4A
IEC temp codeT4
(1)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring
and Grounding Guidelines, publication 1770-4.1
4 kV contact discharges – 1794-IJ2 and 1794-IJ2K
6 kV contact discharges – 1794-IJ2XT
8 kV air discharges
EFT/B immunityIEC 61000-4-4:
±2 kV @ 5 kHz on power ports
±2 kV @ 5 kHz on shielded signal ports
Surge transient
immunity
IEC 61000-4-5:
±2 kV line-earth(CM) on shielded signal ports
Conducted RF immunityIEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from
150 kHz…80 MHz on shielded signal ports
Certifications
Certifications when
product is marked
Value
(1)
c-UL-usUL Listed Industrial Control Equipment, certified for US and
Canada. See UL File E65584.
UL Listed for Class I, Division 2 Group A,B,C,D Hazardous
Locations, certified for U.S. and Canada. See UL File E194810.
CSA
(1794-IJ2, 1794-IJ2K)
CSA Certified Process Control Equipment. See CSA File LR54689C.
CSA Certified Process Control Equipment for Class I, Division 2
Group A,B,C,D Hazardous Locations. See CSA File LR69960C.
CEEuropean Union 2004/108/EC EMC Directive, compliant with:
EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)
ExEuropean Union 94/9/EC ATEX Directive, compliant with:
EN 60079-15; Potentially Explosive Atmospheres, Protection "n"
(II 3 G Ex nA IIC T4 X)
EN 60079-0; General Requirements (Zone 2)
Publication 1794-6.5.11 - September 2011
TÜVTÜV Certified for Functional Safety:
up to and including SIL 2
(1)
See the Product Certification link at http://www.ab.com for Declaration of Conformity, Certificates, and other
certification details.
Page 69
Appendix
Electronic Data Sheet (EDS) Files
B
Overview
EDS provides the definition for a device's configurable parameters and public
interfaces to those parameters:
• Every type of configurable device has its own unique EDS.
• EDS is a simple text file that allows product-specific information to be
made available to third-party vendors.
This makes updating of configuration tools easier without having to constantly
revise the configuration software tool.
Beginning with the following revisions, EDS files are required for RSNetworx
for Devicenet and ControlNet, RSLinx, RSLogix5, and RSLogix 5000 to
recognize a device:
Most EDS files are installed with RSLinx, RSNetworx, and other RSI software
as long as you enable the option during installation.
There are instances where you will need to acquire and register EDS files on
your own even after all software is installed.
• If you go online with RSNetworx and it shows a device with a "?" mark
icon, a globe, or a message that says the device is unrecognized, this
means the EDS file for that device does not exist on your PC.
• If RSLinx can see a processor but going online, uploading or
downloading is not possible.
With ControlLogix modules the backplane does not show after expanding the
tree or ControlLogix modules in the backplane show up as a yellow question
mark without a red X sign.
An EDS file is also required if a bridge module such as a 1756-CNB or DNB
does not show the "+" sign to expand the tree to show its network.
59Publication 1794-6.5.11 - September 2011
Page 70
60 Electronic Data Sheet (EDS) Files
ATTENTION
To acquire EDS files for Rockwell Automation and Allen-Bradley devices, go
to Tools & Resources EDS Files at www.ab.com/networks/eds
. It allows you
to search for devices by the type of network and their catalog number.
•Make sure to match the major firmware revision of the device
as each major firmware revision is associated with a specific
EDS file.
•Download the EDS file and place it in any folder, except the
/Program Files/Rockwell Software/RSCommon/EDS folder
where your Rockwell Automation software is installed.
•Register EDS files with RSNetworx by selecting Tools EDS
Wizard.
•Select Register an EDS File, then click the Browse button on
the Next page to find your file.
EDS Installation
You can register EDS files with the EDS Hardware Installation tool.
1. In Windows, go to Rockwell Software → RSLinx Tools → EDS
Hardware Installation Tool.
2. Click Add to register an EDS file.
When an EDS file is registered, a copy of the file is made and placed in
the /RSCommon/EDS folder where your Rockwell Automation
software is installed and your Windows registry is updated. Once the
registration is complete you can move, copy, or delete the original files.
Publication 1794-6.5.11 - September 2011
Page 71
Schematics
Appendix
C
What This Appendix
Contains
Use this appendix to understand the internal logic of the FLEX I/O
Frequency Input module.
Follow the wiring practices described in Industrial Automation Wiring and
Grounding Guidelines for Noise Immunity, publication 1770-4.1
your I/O devices. This includes:
• routing conductors
• grounding practices
• use of shielded cables
•input circuits
The frequency input module input logic consists of:
• frequency input circuits
• gate input circuits
• Frequency Inputs
The frequency input circuit uses a comparator to determine when the input
voltage threshold is exceeded. When exceeded, it provides logic pulses internal
to the 1794 Frequency Input module. The circuit is designed to interface with
both active or passive sensor inputs by accepting any pulse output device (such
as vortex flowmeter, magnetic pickup or digital pickup).
, when wiring
Gate Inputs
Gate inputs are similar to frequency inputs and are used for determining
direction. There is one gate associated with each frequency input circuit (G0
corresponds to F0). The circuit is designed to interface with both active or
passive sensor inputs by accepting any pulse output device (such as magnetic
pickup or digital pickup).
61Publication 1794-6.5.11 - September 2011
Page 72
62 Schematics
IEC 1+ or
24V DC
Switch input
50/500 mV
Input
6V Vortex
input
3V Vortex
input
50 mV Select
jumper
Internal 500 mV
Ref. Voltage
Return
Lead breakage
Reference voltage
Isolated 24V power
Invert frequency
(Gate) input
Ex
Nor
Frequency lead break
(Gate lead break)
Frequency input
(Gate input)
(F and G,
15 mA each)
Frequency only, not on gate
2.15 KW2.15 KW
2.5 KW
100pF
24V
215 W
47 pF
100 pF
100 pF
825 W
8.25 KW
100 KW
46.4 KW
8.25 KW
5.11 KW
10 KW
100 pF
10 KW
100 pF
+
-
+
-
45354
Output Circuits
The Frequency Input module output logic consists of digital outputs.
Digital Outputs
The module output is comprised of an isolated power MOSFET. This device
operates in current sourcing mode, and is capable of delivering up to
1 A @ 10…31.2V DC.
Publication 1794-6.5.11 - September 2011
Page 73
Schematics 63
Customer supplied power, ranging from 10V…31.2V DC, is connected internally to the power output transistor.
When an output is turned on, current flows into the source, out of the drain, through the load connected to the
ground of the customer supply (customer return). Diode D6 protects the power output transistors from damage due
to inductive loads.
Output Q1 is a thermally protected FET and will turn off @ 3A, approximately. After an output goes into thermal
shutdown, you must fix the cause of the shutdown and toggle the outputs ON and OFF to reenergize the output.
RT1 protects D6 and Q1 if power supply polarity is reversed.
45355
24V DC from
terminal base
DC/DC
converter
Channel 0
current limit
Channel 1
current limit
Frequency 0
Gate 0
15 mA
15 mA
30 mA
max
Frequency 1
Gate 1
15 mA
15 mA
30 mA
max
To customer devices
The frequency input module isolated power supply consists
of 1 isolated 24V DC power supply that provides 2 current
limited outputs of 30 mA max (1 for each channel).
45356
.
Output channel
Supply
10 KW
3.83 KW
3.83 KW
D5
6.8V
Q1
s
Output
TEMPFET
Output 0
D6
RT1
Supply return
DC to DC Converters – 24V DC Power Supplies
Alarm
10-31.2V
R
load
1A max
DC
The module provides two 24V (±10%) power sources rated at 15 mA each.
Each power source can power one Bently Nevada 3300 – 5 mm (0.197 in.) or
8 mm (0.315 in.) – Proximity Transducer.
Publication 1794-6.5.11 - September 2011
Page 74
64 Schematics
Notes:
Publication 1794-6.5.11 - September 2011
Page 75
Appendix
D
Program Your Module with PLC Processors
Overview
Enter Block Transfer
Instructions
This Appendix serves as a reference to users of the PLC-* Family Processors
to program their modules.
To initiate communication between the frequency input module and your PLC
processor, you must enter block transfer instructions into your ladder logic
program. Use this chapter to enter the necessary block transfer instructions
into your ladder logic program.
The frequency input module communicates with the PLC processor through
bidirectional block transfers. This is the sequential operation of both read and
write block transfer instructions.
Before you configure the module, you need to enter block transfer instructions
into your ladder logic. The following example programs illustrate the minimum
programming required for communication to take place between the module
and a PLC processor. These programs can be modified to suit your application
requirements.
A configuration block transfer write (BTW) is initiated when the frequency
module is first powered up, and subsequently only when the programmer
wants to enable or disable features of the module. The configuration BTW sets
the bits which enable the programmable features of the module, such as scalars
and alarm values, and so on. Block transfer reads are performed to retrieve
information from the module.
Block transfer read (BTR) programming moves status and data from the
module to the processor data table. The processor user program initiates the
request to transfer data from the module to the processor. The transferred
words contain module status, channel status and input data from the module.
Your program should monitor status bits, block transfer read and block
transfer write activity.
65Publication 1794-6.5.11 - September 2011
Page 76
66 Program Your Module with PLC Processors
IMPORTANT
PLC-2 Family Processor
The 1794 Frequency I/O module is not recommended for use with PLC-2
family programmable controllers due to the number of digits needed for high
resolution.
The frequency input module functions with reduced
performance in PLC-2 systems. Because the module does not
support BCD and the PLC-2 processor is limited to values of
4095 (12 bit binary), many values returned in the BTR file may
not provide meaningful data to the PLC-2 processor.
PLC-3 Family Processor
Block transfer instructions with the PLC-3 processor use a control file and a
data file. The block transfer control file contains the data table section for
module location, the address of the block transfer data file and other related
data. The block transfer data file stores data that you want transferred to the
module (when programming a BTW) or from the module (when programming
a BTR).
The programming terminal prompts you to create a control file when a block
transfer instruction is being programmed. The same block transfer control file
is used for both the read and write instructions for your module. A different
block transfer control file is required for every module.
Publication 1794-6.5.11 - September 2011
Page 77
Program Your Module with PLC Processors 67
13
U
IJ2 BTR
Error Bit
B17:0
EN
BTR
BLOCK TRANSFER READ
Rack
Group
Slot
Data File
3
2
0
N18:101
Length
Control
0
B17:0
EN
BTW
BLOCK TRANSFER WRITE
Rack
Group
Slot
Data
3
2
0
N18:1
DN
Length
Control
0
B17:0
5
B17:0
B17:0
15
ER
DN
ER
Rung M:0
The IJ2 module is located in rack 3, I/O group 2, slot 0. The control file is a 10 word file
starting at B17:0 that is shared by the BTR/BTW. The data obtained by the PLC3 processor is
placed in memory starting at location N18:101, and with the default length of 0, is 7 words long.
IJ2 BTR
Done Bit
IJ2 BTR/BTW
Control Block
The IJ2 module is located in rack 3, I/O group 2, slot 0. The control file is a 10 word file
starting at B17:0 that is shared by the BTR/BTW. The data sent by the PLC-3 processor to the
IJ2 module is from PLC memory starting at N18:1, and with the default length of 0,
is 8 words long.
13
IJ2 BTR
Error Bit
B17:0
IJ2 BTW
Done Bit
IJ2 BTR/BTW
Control Block
3
B17:0
3
B17:0
U
IJ2 BTW
Error Bit
IJ2 BTW
Error Bit
PLC-3 Processor
Program Example
45563
PLC-5 Family Processor
Block transfer instructions with the PLC-5 processor use a control file and a
data file. The block transfer control file contains the data table section for
module location, the address of the block transfer data file and other related
data. The block transfer data file stores data that you want transferred to the
module (when programming a BTW) or from the module (when programming
a BTR).
The programming terminal prompts you to create a control file when a block
transfer instruction is being programmed. A different block transfer control
file is used for the read and write instructions for your module.
Publication 1794-6.5.11 - September 2011
Page 78
68 Program Your Module with PLC Processors
EN
BTR
BLOCK TRANSFER READ
Rack
Group
Slot
Control
01
2
0
N22:200
DN
Data File
Length
Continuous
N22:101
0
N
ER
ENBLOCK TRANSFER WRITE
Rack
Group
Slot
Control
01
2
0
N22:205
DN
Data File
Length
Continuous
N22:1
0
N
ER
N22:200
15
N22:200
15
N22:205
15
Rung 2:0
The IJ2 module is located in rack 1, I/O group 2, slot 0. The integer control file
starts at N22:200, is 5 words long and is compatible with all PLC-5 family members.
The data obtained by the PLC-5 processor from the IJ2 module is placed in memory
starting at N22:101, and with the default length of 0, is 7 words long. The length
can be any number between 0 and 7. In enhanced PLC-5 processors, the block transfer
data type may be used as a control file.
N22:205
15
Rung 2:1
The IJ2 module is located in rack 1, group 2, slot 0. The integer control file
starts at N22:205, is a 5 words long and is compatible will all PLC-5 family
members. The data sent by the PLC-5 processor to the IJ2 module starts at N22:1,
and with the default length of 0, is 8 words long. Valid BTW lengths can be any
number from 0 to 8. In enhanced PLC-5 processors, the block transfer data type
may be used as a control file.
IJ2 BTR
Enable Bit
IJ2 BTW
Enable Bit
IJ2 BTR
Control File
IJ2 BTR
Enable Bit
IJ2 BTW
Enable Bit
IJ2 BTW
Control File
PLC-5 Processor
Program Example
BTW
Enhanced PLC-5 processors include: PLC-5/11, -5/20, -5/3x, -5/4x, and -5/6x.
1
1
1
45564
PLC-5/250 Family Processor
Block transfer instructions with the PLC-5/250 processor use a control file
and a data file. The block transfer control file contains the data table section
for module location, the address of the block transfer data file and other
related data. The block transfer data file stores data that you want transferred
to the module (when programming a BTW) or from the module (when
programming a BTR).
The programming terminal automatically selects the control file based on rack,
group and module, and whether it is a read or write. A different block transfer
control file is used for the read and write instructions for your module. A
different block transfer control file is required for every module.
Publication 1794-6.5.11 - September 2011
Page 79
Program Your Module with PLC Processors 69
EN
BTR
BLOCK TRANSFER READ
Rack
Group
Slot
Control Block
14
1
0
BR141:0
DN
Data File
BT Length
Continuous
2BTD5:101
0
NO
ER
EN
BTW
BLOCK TRANSFER WRITE
Rack
Group
Slot
Control Block
14
1
0
BW141:0
DN
Data File
BT Length
Continuous
2BTD5:1
0
NO
ER
BR141:0
EN
BR141:0
EN
BW141:0
EN
Rung 1STEPO:1
The IJ2 module is located in rack 14, I/O group 1, slot 0. The data obtained by the PLC-5/250 processor from the
IJ2 module is placed in the data table starting at 2BTD5:101, and with the default length of 0, is 7 words long. The
length can be any number between 0 and 7.
BW141:0
EN
Rung 1STEPO:1
The IJ2 module is located in rack 14, I/O group 1, slot 0. The data sent to the IJ2 module from the PLC-5/250 processor
is from the data table starting at 2BTD5:1, and with a default length of 0, is 8 words long.
Valid BTW lengths can be any number between 0 and 8.
acceleration 38, 43
communication fault 42
definition 40
diagnostic 53
direction 38
fault 38
frequency alarm 46
frequency range 42, 46
frequency scaling 42, 45
gate input state 38
initiate startup 47
input polarity 11
invert select 47
missing pulse 40
missing pulse delay 46
pulse 38,
pulses
wire-off 43, 46
block transfer read (BTR)
bit definition 37
bits 37
decimal bit 36
gate state 37
octal bits 36
word assignments 36
block transfer write (BTW)
bit definition 40
communication fault 40
decimal bits 39
frequency range 40, 41
initiate startup 47
instructions 3
invert frequency 40
invert gate 40
local fault 40
safe state 42
wire-off 40
missing pulse multiplier 40
safe state mode 40
40
C
cable shields 23
cabling
length 22
power 22
Publication 1794-6.5.12 - September 2011
Page 82
72 Index
calibration
failure 39, 53
chassis 13, 21, 22
combination type 21
communication 3, 4, 40, 41, 63, 69
CompactLogix 29
configuration
alarms 35
block transfer write 35
failure 39, 53
fault action 32
fault modes 35
individual 21
module properties 33
number of pulses 35
1794-TB3G, 1794-TB3GS, 1794-TB3GK 21
frequency module 21
illustration 14, 20
methods 14
onnecting 22
terminal base 21
word definition 37, 40
write word 39, 35, 40
Z
zero frequency 9
Publication 1794-6.5.12 - September 2011
Page 86
76 Index
Notes:
Publication 1794-6.5.12 - September 2011
Page 87
Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products.
At http://www.rockwellautomation.com/support/
application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the
best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect
support programs. For more information, contact your local distributor or Rockwell Automation representative,
or visit http://www.rockwellautomation.com/support/
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual.
You can contact Customer Support for initial help in getting your product up and running.
United States or Canada1.440.646.3434
Outside United States or
Canada
Use the Worldwide Locator
your local Rockwell Automation representative.
, you can find technical manuals, a knowledge base of FAQs, technical and
.
at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility.
However, if your product is not functioning and needs to be returned, follow these procedures.
United StatesContact your distributor. You must provide a Customer Support case number (call the phone number above to obtain
Outside United StatesPlease contact your local Rockwell Automation representative for the return procedure.
one) to your distributor to complete the return process.
Documentation Feedback
Your comm en ts will help us serve your documentation needs better. If you have any suggestions on how to improve this document,
complete this form, publication RA-DU002
, available at http://www.rockwellautomation.com/literature/.