Rockwell Automation 700-HX User Manual

Multifunction Digital Timer
700-HX User Manual
Important User Information
ATTENTION
!
IMPORTANT
Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen-Bradley does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Rockwell Automation publication SGI-1.1, Safety Guidelines for the Application, Installation and Maintenance of Solid-State Control (available from your local Rockwell Automation sales office or Allen-Bradley distributor), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited.
Throughout this manual we use notes to make you aware of safety considerations:
Identifies information about practices or circumstances that can lead to personal injury or death, property damage or economic loss
Attention statements help you to:
identify a hazard
avoid a hazard
recognize the consequences
Identifies information that is critical for successful application and understanding of the product.
European Communities (EC) Directive Compliance
If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.
EMC Directive
This product is tested to meet the Council Directive 89/336/EC Electromagnetic Compatibility (EMC) by applying the following standards, in whole or in part, documented in a technical construction file:
This product is intended for use in an industrial environment.
Low Voltage Directive
EN 50081-2 EMC — Generic Emission Standard, Part 2 — Industrial Environment
EN 50082-2 EMC — Generic Immunity Standard, Part 2 — Industrial Environment
This product is tested to meet Council Directive 73/23/EEC Low Voltage, by applying the safety requirements of EN 61010-1 safety requirements for electrical equipment for measurement, control and laboratory use--Part 1 General Safety Requirements.
This equipment is classified as open equipment and must be mounted as instructed in an enclosure during operation to provide safety protection.
Preface
Manual Objectives
Who Should Use This Manual
Counter/Timer Mode Explanation
The purpose of this manual is to provide you with the additional information necessary to apply the 700-HX Multifunction Digital Timer. Described in this manual are methods for applying and troubleshooting this product.
This manual is intended for qualified personnel responsible for setting up and servicing these devices. You must have previous experience with and a basic understanding of wiring diagrams, configuration procedures, related equipment, and safety precautions.
In this manual we refer to the Timer Output Modes with the following designations:
A: Signal ON delay 1
A-1: Signal ON delay 2
A-2: Power ON delay 1
A-3: Power ON delay 2
B: Repeat Cycle 1
B-1: Repeat Cycle 2
D: Signal OFF delay
E: One Shot
F: Cumulative
Z: ON/OFF-duty adjustable repeat cycle
S: Stop Watch
toff: Flicker OFF start 1(Timer resets when power comes on)
ton: Flicker ON start 1 (Timer resets when power comes on)
toff-1: Flicker OFF start 2(Timer does not reset when power comes on)
ton-1: Flicker ON start 2 (Timer does not reset when power comes on)
Note: In this manual the 700-HX Multifunction Digital Timer will be referred to
as “700-HX.” For further information, please refer to the Industrial Controls Catalog or www.ab.com/catalogs.
1 Publication 700-UM002B-EN-D June 2010
Preface 2
Publication 700-UM002B-EN-D - June 2010
Product Overview
Chapter
1
Bill of Material
Basic Product Information
Cat. No. Input
Voltage
700-HX86SA17 100…240
V AC
12…24V
700-HX86SU24
DC 24V AC
Output Modes Timing Ranges Sockets Output Pins
A mode: Signal ON-Delay 1 A-1 mode: Signal ON-Delay 2 A-2 mode: Power ON-Delay 1 A-3 mode: Power On-Delay 2 B mode: Repeat Cycle 1 B-1 mode: Repeat Cycle 2 D mode: Signal OFF-delay E mode: One Shot F mode: Cumulative Z mode: On/Off duty adjustable repeat cycle S mode:stop watch toff: Flicker OFF start 1 ton: Flicker ON start 1 toff-1: Flicker OFF start 2 ton-1: Flicker ON start 2
Your 700-HX Multifunction Digital Timer product package includes the following items:
Item No. Description Quantity
700-HX Digital Timing Relay 1
6-Language Instruction Sheet 1
Rubber Gasket 1
0.000…9.999 s
0.000…99.99 s
0.000…999.9 s
0.000…9999 s
0.000…99 min. 59 s
0.000…999.9 min.
0.000…9999 min.
0.000…99 h 59 min.
0.000…999.9 h
0.000…9999 h
700-HN100 700-HN125
SPDT 8
1 Publication 700-UM002B-EN-D - June 2010
1-2 Product Overview
Accessories (Order Separately)
Cat. No. Description Pkg. Qty.
700-HN100 Screw Terminal Tube Base Sockets — Panel or DIN Rail
Mounting Guarded Terminal Construction 8-pin for use with Bulletin 700-HX timing relays. Order must be for 10 sockets or multiples of 10.
700-HN125 Screw Terminal Tube Base Sockets — Panel or DIN Rail
Mounting Open Style Construction 8-pin for use with Bulletin 700-HX timing relays. Order must be for 10 sockets or multiples of 10. No retainer clip required.
199-DR1 DIN Rail Mounting Pack
Standard 35 x 7.5 mm DIN Rail, 1 meter long, 10 rails per package. Order must be for 10 rails or multiples of 10.
700-HN108 Specialty Socket
8-pin backwired socket with solder terminals for use with Bulletin 700-HX timing relays. Order must be for 10 sockets or multiples of 10.
700-HN130 Frame Adapter
For flush or door mounting of all Bulletin 700-HR and -HX timers.
700-HN132 Protective Cover
Helps prevent tampering of timing and mode settings. Provides a degree of protection against water and dirt from entering the front of the relay. For use with all Bulletin 700-HRs and -HX timing relays.
700-N40 Pre-printed identification tags contains 10 sheets of
pre-printed and blank tags. Each sheet contains 13 sets of the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and 117 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
10
10
10
1
1
10
Publication 700-UM002B-EN-D - June 2010
700-N41 Blank identification tags— contains 10 sheets of blank
identification tags for customer specialized printing. Each sheet contains 546 blank tags. Tags are peel-off with sticky backing for easy placement on relays.
10
Product Features
Input circuit
Internal control circuit
Power supply circuit
(Basic insulation)
Display circuit
Key switch circuit
(See note.)
Output circuit
Chapter
2
Block diagram
Note: 700-HX86SA17: Basic insulation is provided
700-HX86SU24: Basic insulation is not provided
Inputs Start signal Stops timing in A-2 and A-3 (power ON delay)
modes. Starts and stops timing in S mode. Start timing in other modes.
Reset Resets present value. (In elapsed time mode, the
present value returns to 0; in remaining time mode, the present value returns to the set value.) Count inputs are not accepted and control output turns OFF while reset input is ON. Reset indicator is lit while reset input is ON.
Gate Inhibits timer operation.
Outputs Control output (OUT) Outputs take place according to designated
operating mode when timer reaches corresponding set value.
Gate capability not available.
1 Publication 700-UM002B-EN-D - June 2010
2-2 Product Features
0 12345
1,000
500
100
50
10
Switching operations ( 10
4
)
250V DC/30V cos =1
250V A C cos =0.4
Load current (A)
30V DC L/R=7 ms
Reference:A maximum current of 0.15 A can be switched at 125V DC (cosφ=1) and a maximum current of 0.1 A can be switched if L/R is 7 ms. In both cases, a life of 100,000 operations can be expected. The minimum applicable load is 10 mA at 5V DC (failure level: P).
120V AC
120V AC
Engineering Data (Reference Values)
Specifications
Electrical Ratings
Pilot Duty Rating NEMA B300 Rated supply voltage 100 to 240V AC, 24V AC/12 to 24V DC (50/60Hz) (permissible
ripple: 20%(p-p) max.) Operating voltage range 85%…110% of rated supply voltage Power consumption 100…240V AC
24V AC/12…24V DC
Inrush Current 100…240V AC
24V AC/12…24V DC
4.3 VA
3.4 VA/1.7 W
3 A
5 A
30 A
15 A Make 240V AC
3 A
1.5 A
Break 240V AC Hp at 120V AC 1/4 Hp Hp at 240V AC 1/3 Hp
Mechanical
Mounting method Flush mounting, surface mounting, DIN mounting Display 7-segment, negative transmissive LCD;
Present value (red, 12 mm high characters); Set value (green,
6 mm high characters) Digits 4 digits Timer Time ranges 0.000…9.999 s, 0.00…99.99 s, 0.0…999.9 s, 0…9999 s,
Timer modes Elapsed time (Up), remaining time (Down), selectable Output modes A, A-1, A-2, A-3, B, B-1, D, E, F, Z, S, toff, ton, toff-1, or ton-1
0 min. 0 s…99 min. 59 s, 0.0…999.9 min., 0 h 00 min.…99 h
59 min., 0.0 h…999.9 h, 0 h…9999 h
Publication 700-UM002B-EN-D - June 2010
Product Features 2-3
Electrical Ratings
Inputs Input signals Start, reset
Input method No-voltage input via:NPN transistor or switching of contact Start, reset Minimum input signal width: 1 or 20 ms (selectable) Power reset Minimum power-opening time: 0.5 s (Except for A-3, B-1, and
F mode) Control output SPDT contact output: 5 A at 250V AC, resistive load
(cosine=1)
Minimum applied load: 10 mA at 5V DC (failure level: P,
reference value) External Power Supply No Key Protect Yes Memory backup EEP-ROM (overwritten 100,000 times min.), which can store
data for 10 years min. Accuracy of Operating Time and Setting Error Power-ON start: +-0.01% +-50 ms max.*
* to be rated against set value
Signal start: +- 0.005 +-30 ms max. *
* to be rated against set value
Signal start at transistor output model: +- 0.005% +-3 ms
max.
If the set value is within the sensor waiting time
(250 ms max.)
The values are based on the set value. The value is applied for a minimum pulse width of 1 ms.
Characteristics
Insulation resistance 100 MΩ min. (at 500V DC) Dielectric strength 2000V AC, 50/60Hz for 1 min. between current-carrying terminals and
non-current-carrying metal parts (1000V AC for 24V AC/12 to 24V DC type), 1000V AC, 50/60 Hz for 1 min. between non-continuous contacts
Noise immunity '+-1.5 kV (between power terminals) for 100 to 240V AC, +-480V for 24V AC/12
to 24VDC, and +-600V (between input terminals), square-wave noise by noise simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Static immunity ±8 kV (malfunction), ±15 kV (destruction) Vibration resistance Malfunction 10…55 Hz with 0.35 mm single amplitude each in three directions for 10 min. Shock resistance Malfunction
Life expectancy Mechanical 10 million operations min.
Electrical 100,000 operations min. (5 A at 250V AC, resistive load)
EMC (EMI) EN61812-1
2
98 m/s
(approx. 10 G) each in three directions
Emission Enclosure: EN55011 Group1 class A Emission AC mains: EN55011 Group1 class A (EMS) EN61812-1 Immunity ESD: EN61000-4-2: 4 kV contact discharge (level2) 8 kV air discharge (level3) Immunity RF-interference: EN61000-4-3: 10 V/m
Publication 700-UM002B-EN-D - June 2010
2-4 Product Features
12mm 6mm
1
3
2
8
9
5
4
6
7
10 11
12
Display Section
1. Key Protect Indicator
(orange)
2. Control Output Indicator
(orange)
Front View
Character Size for Present Value Display
Character Size for Set Value Display
3. Reset Indicator
(orange)
Operation Key
Switches
8. Mode Key
(Changes modes and setting items)
9. Reset Key
(Resets present value and output)
10. Up Keys 1 to 4
11. Down Keys 1 to 4
12. Key-protect Switch
6. Set Value Display
(Sub-display)
(Character height: 6 mm, green)
7. Set Value 1, 2 Indicator
(green)
4. Present Value Display
(Main display)
(Character height: 12 mm, red
*
)
* Characters on models with screw terminals
5. Time Unit Indicators
(Color is same as present value display.) (If the time range is 0 min, 0 h, 0.0 h, or 0 h
0 min, these indicators flash to indicate timing operation.)
OFF
(Disabled)
ON
(Enabled)
(Default setting)
can be switched between red, green, and orange.
Approved standards UL508, CSA C22.2 No.14
Conforms to EN 61812-1 (Pollution degree 2/overvoltage category III) Conforms to VDE0106/P 100 (Finger Protection), conforms to NEMA output rating (N/F)
Enclosure ratings Panel surface:IP66 and NEMA Type 4X (indoors) Weight Approx. 100 g
An attached waterproof packing is necessary to ensure IP66 waterproofing between the
700-HX and installation pan.
Nomenclature
Publication 700-UM002B-EN-D - June 2010
Output ON count alarm set value
Output ON count monitor value
(9999 x 1000 times)
(0 x 1000 times)
Note: The monitor value is only displayed.
It cannot be set.
99990
~
(9999)(1)
99991
timr
timm
outm
otim
w
ss hs
1 ms20 ms
……
s
(A-1) (A-2) (A-3) (b-1)(b) )Z()S()F()E()d((A)
za-1a a-2 a-3 b b-1 d e f s
m
m
Key protect level
(KP-1) (KP-2) (KP-3) (KP-4) (KP-5) (KP-6) (KP-7)
kp-2
kp-1
kp-3 kp-4 kp-5 kp-6 kp-7
Set the key protect levelusing the keys.
Run mode
Power ON
Note: 1. If the mode is switched to the function setting mode during operation,
operation will continue.
2. Changes made to settings in function setting mode are enabled for the first time when the mode is changed to run mode. Also, when settings are changed, the timer is reset (time initial ized and output turned OFF).
For details on operations in run mode, refer to 3-10.
See note 1. See note 2.
3 s min. 3 s min.
Function setting mode
Timer mode
Output mode
Output time
Input signal width
Time range
0.01 s to 99.99 s (default setting)
0.1 s to 999.9 s
1 s to 9,999 s
0 min 01 s to 99 min 59 s
0.1 min to 999.9 min
1 min to 9,999 min
0 h 01 min to 99 h 59 min
Display
0.1 h to 999.9 h
Set Value
1 h to 9,999 h
Time Range List
0.001s to 9.999 s
Set the time range using the keys.
Set the timer mode using the keys.
Set the output mode using the keys.
Set each digit for the output time using the corresponding keys.
Press the mode button f or se veral seconds to display the Time Range setti ng screen.
(If the output time is set to 0.00,hold is displayed.) Displayed for modes A, A-1, A-2, A-3, B, and B-1 only.
Set value upper limit
Output on count alarm
set value
Output on count
monitor set value
Set the key protect level using the keys.
Functions
Settings For Advanced Functions
Chapter
3
1 Publication 700-UM002B-EN-D - June 2010
3-2 Functions
Explanations of Functions
Time Range (
Set the range to be timed in the range 0.000 s… 9,999 h. Use the operation keys if these settings are required.
Timer Mode (
Set either the elapsed time (UP) or remaining time (DOWN) mode.
Output Mode (
Set the output mode. The possible settings are A, A-1, A-2, A-3, B, B-1, D, E, F, Z and S. (For details on output mode operation, refer to “Timing Charts” on page 3-11.)
Output Time (
When using one-shot output, set the output time for one-shot output (0.01…
99.99 s). One-shot output can be used only if the selected output mode is A, A-1, A-2, B, or B-1. If the output time is set to 0.00, hold is displayed, and the output is held.
timr
timm
outm
otim
)
)
)
)
Input Signal Width (
Set the minimum signal input width (20 ms or 1 ms) for signal and reset inputs. The same setting is used for all external inputs (signal and reset). If contacts are used for the input signal, set the input signal width to 20 ms. Processing to eliminate chattering is performed for this setting.Set the key protect level.
Set Value Upper Limit (
Set the upper limit for the set value when it is set in Run Mode. The limit can be set to between 1 and 9999. This setting does not apply to the ON duty in Z mode.
Output ON Count Alarm Set Value (
Set the alarm value for the output ON count.The limit can be set to between 0 x 1000 times and 9999 x 1000 times. (The rightmost three digits will not be displayed.) If the total ON count of the output exceeds the alarm set value, e3 will be displayed on the Timer to indicate that the output ON count alarm value was exceeded.
iflt
sl-h
)
)
on-a
)
Publication 700-UM002B-EN-D - June 2010
Output ON Count Monitor Value (
The monitor value is only displayed. It cannot be set. The value will be between 0 x 1000 times and 9999 x 1000 times. (The rightmost three digits will not be displayed.)
on-c
)
Functions 3-3
ON
OFF
Key protect indicator
Note: Factory-set to OFF
(See note)
Key Protect Level (
kypt
)
When the key-protect switch in set to ON, it is possible to prevent setting errors by prohibiting the use of certain operation keys by specifying the key protect level (KP-1 to KP-7). The key protect indicator is lit while the key-protect switch is set to ON. Confirm the ON/OFF status of the key-protect switch after the 700-HX is mounted to the panel.
Level Meaning
KP-1 (default setting)
KP-2 Prohibits changing the mode to timer/repeat
KP-3 Prohibits changing the mode to timer/repeat
KP-4 Prohibits changing the mode to timer/repeat
KP-5 Prohibits changing the mode to timer/repeat
KP-6 Prohibits changing the mode to timer/repeat
KP-7 Prohibits changing the mode to timer/repeat
Prohibits changing the mode to timer/repeat cycle selection mode or function setting mode. The 700-HX can only be used in run mode.
cycle selection mode or function setting mode. The 700-HX can only be used in run mode. Also prohibits use of the reset key.
cycle selection mode or function setting mode. The 700-HX can only be used in run mode. Also prohibits use of the up and down keys.
cycle selection mode or function setting mode. The 700-HX can only be used in run mode. Also prohibits use of the reset, up and down keys.
cycle selection mode or function setting mode. The 700-HX can only be used in run mode. Also prohibits use of any operation keys.
cycle selection mode or function setting mode. The 700-HX can only be used in run mode. Also prohibits use of the mode key.
cycle selection mode or function setting mode. The 700-HX can only be used in run mode. Also prohibits use of mode and reset keys.
Publication 700-UM002B-EN-D - June 2010
3-4 Functions
Present value
Set value
Present value
ON duty ratio
Present value
Cycle time
When Output Mode Z Is Selected
Set each digit for the ON duty ratio using the corresponding keys. (The keys for the 4th digit cannot be used.)
Set each digit for the cycle time using the corresponding keys.
Set each digit for the set value using the corresponding keys.
When Output Mode Is Not Z
Operation in Run Mode
Present Value and Set Value
These items are displayed when the power is turned ON. The present value is displayed in the main display and the set value is displayed in the sub-display. The values displayed will be determined by the settings made for the time range and the timer mode in function setting mode.
Present Value and ON Duty Ratio (Output Mode = Z)
The present value is displayed in the main display and the ON duty ratio is displayed in the sub-display. “SET1” lights at the same time.
Set the ON duty ratio used in ON/OFF-duty adjustable Repeat Cycle (Z) as a percentage.
If a cycle time is set, cyclic control can be performed in ON/OFF-duty adjustable Repeat Cycle simply by changing the ON duty ratio.
Present Value and Cycle Time (Output Mode = Z)
The present value is displayed in the main display and the cycle time is displayed in the sub-display. “SET2” lights at the same time.
Publication 700-UM002B-EN-D - June 2010
Set the cycle time used in ON/OFF-duty adjustable Repeat Cycle (Z).
Functions 3-5
Elapsed cycle time
ON duty set as a percentage
Up/down keys used for analog adjustment of the ON duty
Cycle time
ON duty (%)
Output control
Close
Open
Opening/closing valve
Fully closedFully open
0%100%
ON duty
1
Power ON
Function selection
Hold down for 1s min.
Switch from timer operation to repeat cycle operation using the keys.
Timer/repeat cycle selection mode
Run mode
m
Operation (Repeat Cycle Function)
Switching from Timer to Repeat Cycle
The 700-HX is factory-set for timer operation. To switch to repeat cycle operation, use the procedure given below. For details, refer to page Appendix-2.
Publication 700-UM002B-EN-D - June 2010
3-6 Functions
Run mode
Power ON
Function setting mode
From next pageTo next page
(1 ms)(20 ms)
(PNP input)(NPN input)
(Red) (Green) (Orange) (Red-green) (Green-red) (Red-orange) (Orange-red) (Green-orange) (Orange-green)
(Instantaneous)(Time-limit)
3 s min.
*2
3 s min.
*1
shss
shss
(DOWN)(UP)
OFF time range
ON time range
Timer mode
ON/OFF start mode
Input signal width
NPN/PNP input
Display color
Instantaneous/ time-limit
( ) ( ) ( ) ( )
Display Set Value
Time Range List
0.01 s to 99.99 s (default setting)
0.1 s to 999.9 s
1 s to 9999 s
0 min 01 s to 99 min 59 s
0.1 min to
999.9 min
1 min to 9999 min
0 h 01 min to 99 h 59 min
0.1 h to 999.9 h
1 h to 9999 h
0.001 s to
9.999 s
Flicker
OFF start 1
Flicker
On Start 1
Flicker
OFF start 2
Flicker
On Start 2
20ms
up down
1ms
pnp
grn
2c1c1c
red org r-g g-r r-o o-r g-o o-g
npn
……
s
……
s
toff ton tof1 ton1
For details, refer to Time Range List.
For details, refer to Time Range List.
Function setting mode
Set the OFF time range using the keys.
Set the ON time range using the keys.
Set the timer mode using the keys.
Set the repeat cycle mode using the
Set the input signal width using the keys.
Set the NPN/PNP input mode using the keys.
Set the display color using the keys.
Set the function (instantaneous or time-limit operation) for the instantaneous output (output 1)
using the Keys.
*1. If the mode is switched to the function setting mode during operation, operation will continue. *2. Changes made to settings in function setting mode are enabled for the first time when the mode is changed to run mode.
Also, when settings are changed, the timer is reset (time initialized and output turned OFF).
.
keys.
Settings for Advanced Functions
Publication 700-UM002B-EN-D - June 2010
Functions 3-7
~
~
~
(KP-1) (KP-2) (KP-3) (KP-4) (KP-5) (KP-6) (KP-7)
(9999 x 1000 times)
(0 x 1000 times)
(9999 x 1000 times)
(0 x 1000 times)
(9999 x 1000 times)
(0 x 1000 times)
Note: The monitor value is only displayed. It cannot be set.
Note:
The monitor value is only displayed.
It cannot be set.
Note:
The monitor value is only displayed.
It cannot be set.
To previous
page
From previous
page
Function setting mode
Set the digits for the set value limit using the corresponding keys.
Set the key protect level using the keys.
Set value upper limit 1
Set the digits for the set value limit using the corresponding keys.
Set value upper limit 2
Key protect level
Output ON count alarm set value/ monitor value
Output ON count alarm set value
Output ON count monitor value
Instantaneous output 1 (OUT1) ON count alarm set value
Instantaneous output 2 (OUT2) ON count alarm set value
Instantaneous output 1 (OUT1) ON count monitor value
Instantaneous output 2 (OUT2) ON count monitor value
• Models without Instantaneous Contact Outputs
• Models with Instantaneous Contact Outputs
*1.
Set the digits for the output ON alarm set value using the corresponding
keys.
*1
(9999)(1)
99990
99990
99990
9999
kp-2
kp-1
kp-3 kp-4 kp-5 kp-6 kp-7
1
(9999)(1)
99991
Publication 700-UM002B-EN-D - June 2010
3-8 Functions
Explanation of Functions (Repeat Cycle Function)
OFF Time Range (
Set the time range for the OFF time in the range 0.000 s… 9,999 h. Use the operation keys if another type of setting is required.
ON Time Range (
Set the time range for the ON time in the range 0.000 s …9,999 h. Use the operation keys if another type of setting is required.
oftr
ontr
)
)
Timer Mode (timm)
Set either UP (incremental) or DOWN (decremental) timer mode. In UP mode, the elapsed time is displayed, and in DOWN mode, the remaining time is displayed.
ON/OFF Start Mode (totm)
Set the output mode. Set either Repeat Cycle OFF start or Repeat Cycle ON start. (For details on output mode operation, refer to 3-11.)
Input Signal Width (
iflt
) (Setting possible using DIP switch.)
Set the minimum signal input width (20 ms or 1 ms) for signal, reset, and gate inputs. The same setting is used for all external inputs (signal and rese ). If contacts are used for the input signal, set the input signal width to 20 ms. Processing to eliminate chattering is performed for this setting.
Key Protect Level (
Set the key protect level.
When the key-protect switch in set to ON, it is possible to prevent setting errors by prohibiting the use of certain operation keys by specifying the key protect level (KP-1 to KP-7). The key protect indicator is lit while the key-protect switch is set to ON. Confirm the ON/OFF status of the key-protect switch after the 700-HX is mounted to the panel.
kypt
)
Publication 700-UM002B-EN-D - June 2010
Functions 3-9
ON
OFF
Key protect indicator
Note: Factory-set to OFF
(See note)
Level Meaning
KP-1 (default setting)
Prohibits changing the mode to timer/repeat cycle selection mode or function setting mode. The 700-HX can only be used in run mode.
KP-2 Prohibits changing the mode to timer/repeat
cycle selection mode or function setting mode. The 700-HX can only be used in run mode. Also prohibits use of the reset key.
KP-3 Prohibits changing the mode to timer/repeat
cycle selection mode or function setting mode. The 700-HX can only be used in run mode. Also prohibits use of the up and down keys.
KP-4 Prohibits changing the mode to timer/repeat
cycle selection mode or function setting mode. The 700-HX can only be used in run mode. Also prohibits use of the reset, up and down keys.
KP-5 Prohibits changing the mode to timer/repeat
cycle selection mode or function setting mode. The 700-HX can only be used in run mode. Also prohibits use of any operation keys.
KP-6 Prohibits changing the mode to timer/repeat
cycle selection mode or function setting mode. The 700-HX can only be used in run mode. Also prohibits use of the mode key.
KP-7 Prohibits changing the mode to timer/repeat
cycle selection mode or function setting mode. The 700-HX can only be used in run mode. Also prohibits use of mode and reset keys.
Publication 700-UM002B-EN-D - June 2010
3-10 Functions
Present value
OFF set time
Present value
ON set time
Set the digits for the OFF set time using the corresponding keys.
Set the digits for the ON set time using the corresponding keys.
One-shot
Sustained output
One-shot outputs can be to set to 0.1 s, 0.5 s, 1s, 5 s, 10 s, 20 s.
Operation in Run Mode
Operation in Timer/Repeat Cycle Selection Mode
Present Value and OFF Set Time
The present value is displayed in the main display and the OFF set time is displayed in the sub-display. “SET1” lights at the same time.
Present Value and ON Set Time
The present value is displayed in the main display and the ON set time is displayed in the sub-display. “SET2” lights at the same time.
Select whether the 700-HX is used as a timer or a repeat cycle in timer/repeat cycle selection mode.
Publication 700-UM002B-EN-D - June 2010
Functions 3-11
1
MODE
+
To change the mode to timer/ selection mode, hold down the key for 1 s min. with the key held down. The key must be pressed before the key. If the key is pressed first, the mode will not change.
MODE
Select either timer operation or repeat cycle operation. using the keys.
1
Power ON
Timer/Repeat
Run Mode
Note: factory-set for timer operation.
Timer Repeat cycle/ Selection Mode
1 s min.
1
1
MODE
The 700-HX is
m
repeat cycle
cycle operation
Power
Start signal
Gate
Reset
Control output
Set value
Timing diagram
UP
DOWN
0
0
Set value
t
t
t
Timing starts when the start signal goes ON.
The control output is controlled using a sustained or one-shot rime period.
While the start signal is ON, the timer starts when power comes ON or when the reset input goes OFF.
Basic Operation
Power
** Start signal input
Output
* Output is instantaneous when setting is 0.
** Start signal input is enabled during timing.
Timing
Timing Charts
Note:
1. When the mode is changed to timer/repeat cycle selection mode, the present value is reset and output turns OFF. Timing operation is not performed in timer/repeat Cycle selection mode.
2. Setting changes made in timer/repeat cycle selection mode are enabled when the mode is changed to run mode. If settings are changed, the 700-HX is automatically reset (present value initialized, output turned OFF).
The gate input is not included in the 700-HX.
Output mode A Mode: Signal ON-Delay (Timer resets when power comes ON.)
Publication 700-UM002B-EN-D - June 2010
3-12 Functions
Power
Start signal
Gate
Reset
Control output
Set value
Timing diagram
UP
DOWN
0
0
Set value
Power
Start signal
Gate
Reset
Control output
Set value
Timing diagram
UP
DOWN
0
0
Set value
.
Power
Start signal
Gate
Reset
Control output
Set value
Timing diagram
UP
DOWN
0
0
Set value
t
Timing starts when the reset input goes OFF. The start signal disables the timing function (i.e., same function as the gate input). The control output is controlled using a sustained or one-shot time period.
*Output is instantaneous when setting is 0.
Basic Operation
Power
Timing
Output
Sustained
.
Power
Start signal
Gate
Reset
Control output
Set value
Timing diagram
UP
DOWN
0
0
Set value
Sustained Output
Timing starts when the start signal goes ON. The status of the control output is reversed when time
is up (OFF at start). While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
* Normal output operation will not be possible if the
set time is too short. Set the value to at least 100 ms (contact output type).
** Start signal input is disabled during timing.
Basic Operation
Power
**
Start signal input
Timing
Output
TimingTimingTiming
Output Mode A-1: Signal ON-Delay 2 (Timer resets when power comes ON.)
Timing starts when the start signal goes ON, and is reset when the start signal goes OFF. While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF. The control output is controlled using a sustained or one-shot time period.
Basic Operation
Power
Start signal input
Output
*Output is instantaneous when setting is 0.
Timing
Output mode A-2: Power ON Delay 1 (Timer resets when power comes ON)
Timing starts when the reset input goes OFF. The start signal disables the timing function (i.e., same function as the gate input). The control output is controlled using a sustained or one-shot time period.
Basic Operation
Power
Output
*Output is instantaneous when setting is 0.
Timing
Output mode A-3 Power ON Delay 2 (Timer does not reset when power comes ON)
Publication 700-UM002B-EN-D - June 2010
Output mode B: Repeat Cycle 1 (Timer resets when power comes ON.)
Output mode B: Repeat Cycle 1 (Timer resets when power comes ON.)
Power
Start signal
Gate
Reset
Control output
Set value
Timing diagram
UP
DOWN
0
0
Set value
One-shot Output
Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (OFF at start). While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.
* Normal output operation will not be possible if the
set time is too short. Set the value to at least 100 ms (contact output type).
** Start signal input is disabled during timing.
Sustained
Basic Operation
Power
**
Start signal input
Output
Timing
Timing
Power
Start signal
Gate
Reset
Control output
Set value
Set value
Timing diagram
UP
DOWN
0
0
One-shot Output
tt
t
t
t
Timing starts when the start signal goes ON. The control output is turned ON when time is up. While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.
Basic Operation
Power
**
Start signal input
Output
* Normal output operation will not be possible if the
set time is too short. Set the value to at least 100 ms (contact output type).
** Start signal input is disabled during timing.
Output Mode B-1: Repeat Cycle 2 (Timer does not reset when power comes ON)
Functions 3-13
TimingTimingTimingTiming
Sustained Output
Start signal
Control output
UP
Timing diagram
DOWN
Power
Gate
Reset
Set value
Set value
0
0
Timing starts when the start signal goes ON.
The control output comes ON when time is up..
While the start signal is ON, the timer starts when power comes ON or when the reset input goes OFF.
Basic Operation
Power
Start signal input
Output
* Normal output operation will not be possible if the
set time is too short. Set the value to at least 100 ms (contact output type).
** Start signal input is disabled during timing.
Timing
**
Sustained
Timing
Publication 700-UM002B-EN-D - June 2010
3-14 Functions
Power
Start signal
Gate
Reset
Control output
Set value
Timing diagram
UP
DOWN
0
0
Set value
Power
Start signal
Gate
Reset
Control output
Set value
Timing diagram
UP
DOWN
0
0
Set value
Timing starts when the start signal comes ON. The control output is reset when time is up. While the start signal is ON, the timer starts when power comes ON or when the reset input goes OFF.
* Output is disabled when the setting is 0. ** Start signal input is enabled during timing.
Basic Operation
Power
**
Start signal input
Output
Timing
Power
Start signal
Gate
Reset
Control output
Set value
Timing diagram
UP
DOWN
0
0
Set value
Start signal enables timing (timing is stopped when the start signal is OFF or when the power is OFF). A sustained control output is used.
*Output is instantaneous when setting is 0.
Sustained
Basic Operation
Power
Start signal input
Output
Timing Timing
Output mode D: Signal OFF-delay (Timer resets when power comes ON.)
The control output is ON when the start signal is ON (except when the power is OFF or the reset is ON). The timer is reset when the time is up.
Basic Operation
Power
**
Start signal input
Output
* Output functions only during start signal input when
setting is 0.
** Start signal input is enabled during timing.
Output mode E: One Shot (Timer resets when power comes ON.)
Timing
Publication 700-UM002B-EN-D - June 2010
Output Mode F: Cumulative (Timer does not reset when power comes ON)
Z Mode
Output quantity can be adjusted by changing the cycle time set in the adjustment level to 1 and by changing the ON duty (%) set value. The set value shows the ON duty (%) and can be set to a value between 0 and 100 (%). When the cycle time is 0, the output will always be OFF. When the cycle time is not 0 and when ON duty has been set to 0 (%), the output will always be OFF. When ON duty has been set to 100 (%), the output will always be ON.
Z mode: ON/OFF-duty Adjustable Repeat Cycle
9999
Set time
0
Set time
0
UP
DOWN
Power
Start signal
Gate/Reset
Timing diagram
Output
Functions 3-15
Timing diagram
Power
Start signal
Gate
Reset
Control output
Cycle time
ON duty setting (%) ON time
UP
Cycle time
ON duty setting (%) ON time
DOWN
Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (ON at start). While the start signal is ON, the timer starts when power comes ON or when the reset input goes OFF.
Basic Operation
Power
**
Start signal input
0
Timing (cycle time)
Timing ON duty (%)
Timing (cycle time)
Timing ON duty (%)
Output
0
* Normal output operation will not be possible if the
set time is too short. Set the value to at least 100 ms (contact output type).
** Start signal input is enabled during timing.
S mode: Stop Watch (Timer Resets when Power Comes On)
The signal starts and stops timing. The display is held and timing is continued if the reset or gate input is received during timing operation. The timer resets if the reset or gate input is received when the timing operation is stopped.
Basic Operation
Power
Start signal
input
Gate/Reset
Timing
Display
(for elapsed
time)
*
RST
*
flashes
Note: Output is instantaneous when setting is 0.
Publication 700-UM002B-EN-D - June 2010
3-16 Functions
Power
Start signal
Gate
Reset
Control output
OFF time
Timing diagram
UP
ON time
Sustained Output
DOWN
OFF time
ON time
0
0
Repeat Cycle Operation
Output mode TOFF: Flicker OFF start 1 (Timer resets when power comes ON)
Sustained Output
Control output
Timing diagram
DOWN
Power
Start signal
Reset
OFF time
UP
ON time
OFF time
ON time
Gate
Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (OFF at start). While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.
Basic Operation
Power
**
Start signal input
Output
0
0
* Normal output operation will not be possible if the
ON/OFF set time is too short. Set the value to at least 100 ms (contact output type).
** Start signal input is disabled during timing.
Timing OFF
Timing ON
Timing OFF
Timing ON
Output mode TON: Flicker ON start 1 (Timer resets when power comes ON)
Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (ON at start). While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.
Basic Operation
Power
**
Start signal input
Output
* Normal output operation will not be possible if the
ON/OFF set time is too short. Set the value to at least 100 ms (contact output type).
** Start signal input is disabled during timing.
Timing ON
Timing OFF
Timing ON
Timing OFF
Publication 700-UM002B-EN-D - June 2010
Output mode TOFF-1: Flicker OFF start 2 (Timer does not reset when power comes ON)
0
0
ON time
OFF time
OFF time
ON time
UP
DOWN
Power
Start signal
Gate
Reset
Control output
Timing diagram
Timing starts when the start signal goes ON.
0
0
ON time
OFF time
OFF time
ON time
UP
DOWN
Power
Start signal
Gate
Reset
Control output
Timing diagram
* Start signal input is disabled during timing.
Timing starts when the start signal goes ON. The status of the control output is reversed when time is up (ON at start). While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short. Set the value to at least 100 ms (contact output type).
TimingONTiming
OFF
Timing
ON
(a + b = OFF time)
ab
Power
Output
*
Start signal
input
Basic Operation
The status of the control output is reversed when time is up (OFF at start). While the start signal is ON, the timer starts when the power comes ON or when the reset input goes OFF.
Basic Operation
Power
*
Start signal
input
Output
Timing
OFF
TimingONTiming
* Start signal input is disabled during timing.
Note: Normal output operation will not be possible if
the set time is too short. Set the value to at least 100 ms (contact output type).
Output mode TON-1: Flicker ON start 2 (Timer does not reset when power comes ON)
ab
OFF
(a + b = ON time)
Functions 3-17
Publication 700-UM002B-EN-D - June 2010
3-18 Functions
Publication 700-UM002B-EN-D - June 2010
700-HX Flush Mounting/ Socket Mounting
Dimensions
Chapter
4
Note: All units are in millimeters unless otherwise noted.
48×48
7.5
63.7
14.3
44.8×44.8
1 Publication 700-UM002B-EN-D - June 2010
4-2 Dimensions
60 min.
60 min.
45
+0.6
0
45
+0.6
0
15 min.
Panel Cutouts
Panel cutouts are as shown below (according to DIN43700).
Note:
1. The mounting panel thickness should be 1…5 mm.
2. To allow easier operability, it is recommended that adapters are mounted so that the gap between sides with hooks is at least 15 mm.
3. It is possible to mount timers side by side, but only in the direction without the hooks.
A = (48n - 2.5)
+1
0
With 700-HN132 attached:
A = (51n - 5.5)
+1
0
n side by side mounting
A
Publication 700-UM002B-EN-D - June 2010
Installation
Internal circuit
4
3
2
1 8
7
6
5
ϑҤϒϑҥϒ
0V
Signal
Reset
Chapter
5
Terminal Arrangement
Input Circuits
700-HX
(–)
(+)
Note: Do not connect unused terminals as relay terminals.
Start and reset Input
+14 V
1 k
IN
1 Publication 700-UM002B-EN-D - June 2010
Internal circuit
5-2 Installation
PC or sensor
0 V
Input
Signal input
Reset input
Contact input
Open Collector
(Connection to NPN open collector output sensor)
(Connection to a voltage out put sensor)
Sensor
Signal input
Reset input
0 V
Input
Signal input
Reset input
0 V
Input
Voltage Output
700-HX
➀➂ ➃
700-HX
➀➂ ➃
Operate with transistor ON
Operate with transistor ON
Operate with relay ON
Signal input
Reset input
0 V
Input
Input Connections
The input of the 700-HX is no-voltage input only.
No-voltage Inputs (NPN Inputs)
No-voltage Input Signal Levels
No-contact input Short-circuit level
Contact input Use contact which can adequately switch 5 mA at 10V
Two-wire Sensor
Transistor ON Residual voltage: 2 V max. Impedance when ON: 1 KΩ max. (the leakage current is approximately 12 mA when the impedance is 0Ω)
Open level Transistor OFF Impedance when OFF: 100 KΩ minimum.
Maximum applicable voltage: 30V DC max.
700-HX
➀➂ ➃
Publication 700-UM002B-EN-D - June 2010
Applicable Two-wire Sensor
Leakage current: 1.5 mA max.
Switching capacity: 5 mA minimum
Residual voltage: 3V DC max.
Operating voltage: 10V DC
Installation 5-3
Publication 700-UM002B-EN-D - June 2010
5-4 Installation
Publication 700-UM002B-EN-D - June 2010
Precautions
ATTENTION
!
ATTENTION
!
ATTENTION
!
ATTENTION
!
Do not use the product in locations subject to flammable or explosive gases. Doing so may result in explosion.
Chapter
7
The service life of the output relays depends on the switching capacity and switching conditions. Consider the actual application conditions and use the product within the rated load and electrical service life. Using the product beyond its service life may result in contact deposition or burning.
Do not disassemble, repair, or modify the product. Doing so may result in electric shock, fire, or malfunction.
Do not allow metal objects or conductive wires to enter the product. Doing so may result in electric shock, fire, or malfunction.
1 Publication 700-UM002B-EN-D - June 2010
7-2 Precautions
Power supply
Input Impossible
Unstable
Possible ImpossibleUnstable
200 ms
0 to 50 ms
5 ms
0 to 500 ms
ON OFF
Power Supplies
Make sure that the voltage is applied within the specified range, otherwise the internal elements of the Timer may be damaged.
When turning the power ON and OFF, input signal reception is possible, unstable, or impossible as shown in the diagram below.
Turn the power ON and OFF using a relay with a rated capacity of 10 A minimum to prevent contact deterioration due to inrush current caused by turning the power ON and OFF.
Apply the power supply voltage through a relay or switch in such a way that the voltage reaches a fixed value immediately, otherwise they may not be reset or a timer error may result.
Be sure that the capacity of the power supply is large enough, otherwise the Timer may not start due to inrush current (approx. 5 A) that may flow for an instant when the Timer is turned on.
Timer Control with Power Start
Make sure that the fluctuation of the supply voltage is within the permissible range.
To allow for the startup time of peripheral devices (sensors, etc.), the 700-HX starts timing operation between 200 ms…260 ms after power is turned ON. For this reason, in operations where timing starts from power ON, the time display will actually start from 250 ms. If the set value is 249 ms or less, the time until output turns ON will be a fixed value between 200…250. (Normal operation is possible for set value of 250 ms or more.) In applications in which a set value of 249 ms or less is required, use start timing with signal input.
When the 700-HX is used with power start in F mode (i.e., accumulative operation with output on hold), there will be a timer error (approximately 100 ms each time the 700-HX is turned ON) due to the characteristics of the internal circuitry. Use the 700-HX with signal start if timer accuracy is required.
Publication 700-UM002B-EN-D - June 2010
Precautions 7-3
Self-diagnostic Function
The following displays will appear if an error occurs.
Confirm the error type using the display, and take the appropriate countermeasures.
Main display Sub- display Error Correction
e1
e2
e2
e3
This includes times when the life of the EEPROM has expired.
The normal display and e3 will appear alternately. When the Reset Key is pressed, e3 will
no longer be displayed even if the alarm set value is exceeded. (Monitoring is possible, however, because the Timer will continue without clearing the output ON count.)
No display No display
sum Memory (EEP)
No Change
CPU Either press the reset key or reset
the power supply.
Memory (RAM) Reset the power supply. If normal
operation is still not restored, replacement or repair is necesary. If normal operation is restored, the cause may have been noise.
Reset to the factory settings using
Output ON count alarm set value exceeded
the reset key. Reset key
Changing the Set Values
Operation with a Set Value of 0
Power Failure Backup
When changing the set value during a timing operation, the output will turn ON if the set value is changed as follows because of the use of a constant read-in system:
Elapsed time mode: Present value ≥ set value
Remaining time mode: Elapsed time ≥ set value (The present value is set to 0.)
NOTE: When in the remaining time mode, the amount the set value is changed is added to or subtracted from the present value.
Operation with a set value of 0 will vary with the output mode. Refer to 3-11.
All data is stored in the EEPROM when there is power failure. The EEPROM can be overwritten more than 100,000 times.
Publication 700-UM002B-EN-D - June 2010
7-4 Precautions
It is recommended that the space between the screw head and the adapter should be
0.5 to 1 mm.
0.5 to 1 mm
Operating mode Overwriting timing
A-3, b-1, F, toff-1/ ton-1 mode Other mode When settings are changed.
When power is turned OFF.
Wiring
Mounting
Wiring input lines in the same conduit as power lines or other high-voltage lines may result in malfunction due to noise. Wire the input lines separately, away from lines carrying high-voltages. In addition, make the input wiring as short as possible and use shield lines or metal wiring conduits.
Dense mounting may result in a reduction in the service life of internal parts.
Tighten the two mounting screws on the Adaptor. Tighten them alternately, a little at a time, so as to keep them at an equal tightness.
The 700-HX panel surface is water-resistant (conforming to NEMA 4 and IP66). In order to prevent the internal circuit from water penetration through the space between the timer and operating panel, attach a waterproof gasket between the timer and installation panel and secure the waterproof gasket with the 700-HN130 flush-mounting adapter.
Operating Environment
Publication 700-UM002B-EN-D - June 2010
Use the product within the ratings specified for submerging in water, and exposure to oil.
Do not use the product in locations subject to vibrations or shocks. Using the product in such locations over a long period may result in damage due to stress.
Do not use the product in locations subject to dust, corrosive gases, or direct sunlight.
Separate the input signal devices, input signal cables, and the product from the source of noise or high-tension cables producing noise.
Separate the product from the source of static electricity when using the product in an environment in which a large amount of static electricity is produced (e.g., forming compounds, powders, or fluid materials being transported by pipe).
Precautions 7-5
X1T X2
X2/b T/a X1/a X1/a
X
Auxiliary relay (e.g., MY Relay)
Auxiliary relay (e.g. 700-HC Relay)
Organic solvents (such as paint thinner), as well as very acidic or basic solutions might damage the outer casing of the timer.
Use the product within the ratings specified for temperature and humidity.
Do not use the product in locations where condensation may occur due to high humidity or where temperature changes are severe.
Store at the specified temperature. If the 700-HX has been stored at a temperature of less than –10°C, allow the 700-HX to stand at room temperature for at least 3 hours before use.
Leaving the 700-HX with outputs ON at a high temperature for a long time may hasten the degradation of internal parts (such as electrolytic capacitors). Therefore, use the product in combina­tion with relays and avoid leaving the product as long as more than 1 month with the output turned ON.
Insulation
There is no insulation between power supply and input terminals.
Basic insulation between power supply and output terminals.
Input and output terminals are connected to devices without exposed charged parts.
Input and output terminals are connected to devices with basic insulation that is suitable for the maximum operating voltage.
Publication 700-UM002B-EN-D - June 2010
7-6 Precautions
Publication 700-UM002B-EN-D - June 2010
Appendix
1
1
Power ON
Timer/Repeat Cycle selection
Timer (Except for Z mode)
PV/SV
Timer (Z mode)
PV/ON duty ratio
PV/cycle time
Tim e rang e
Timer mode
Output mode
Output time
Input signal width
Key protect level
1 s min.
3 s min.
3 s min.
1 s min.
Timer/Repeat Cycle selection mode
Run mode
Function setting mode
Operation stopped Can be in operation
Set value upper limit
Output on alarm set value
Output on alarm monitor value
1
1
Power ON
Timer/Repeat Cycle selection
PV/SV
Timer (Z mode)
PV/ON duty ratio
PV/cycle time
1 s min.
3 s min.
3 s min.
1 s min.
Timer/Repeat Cycle selection mode
Run mode
Function setting mode
Operation stopped Can be in operation
PV/OFF set time
PV/ON set time
Time range
Time r mode
Output mode
Output time
Input signal width
Key protect level
Set value upper limit
Output on alarm set value
Output on alarm monitor value
NOTE: All setting changes are performed using keys .
The flowcharts above outline the procedure for all models. For details on specific models, refer to Timer operation and Repeat Cycle operation in Chapter 3.
Using the Operation Keys
Timer Operation
1 Publication 700-UM002B-EN-D - June 2010
Repeat Cycle Operation
Appendix-2
List of Settings
Fill in your set values in the set value column of the following tables for quick reference.
Timer/Repeat Cycle Selection Mode
Parameter name
Timer/ Repeat Cycle selection
Parameter Setting range Dafault
value
func
tim
/twin
tim
Unit Set
value
---
Settings for Timer Operation
Run Mode when Output Mode is Not Z
Parameter name Parameter Setting range Default
value
Present value, set value
Set value
Present value
0.0099.99 (Time range: --,--s)
0.0 999.9 (Time range: ---,-s)
09999 (Time range: ----s)
0:00 99:59 (Time range: --min--s)
0.0 999.9 (Time range: ---,-min)
09999 (Time range: ----min)
0:0099:59 (Time range: --h--min)
0.0999.9 (Time range: ---,-h)
09999 (Time range: ----h)
0.0009.999 (Time range: -,---s)
Same as set value Same
0.00
0.0
0 0:00
0.0
0 0:00
0.0
0
0.000
as left
Unit Set
value
s
s
s
min; s
min
min
h; min
h
h
s
Same as left
Publication 700-UM002B-EN-D - June 2010
Run Mode when Output Mode = Z
Appendix-3
Parameter name
Present value,
Cycle
time cycle time
Present
value Present value,
ON duty ratio
ON
duty
ratio
Present
value
Parameter Setting range Dafault
value
0.0099.99 (Time range: --,--s)
0.0 999.9 (Time range: ---,-s)
0 … 9999 (Time range: ----s) 0 0:00 … 99:59
(Time range: --min--s)
0.0 999.9 (Time range: ---,-min)
09999 (Time range: ----min)
0:0099:59 (Time range: --h--min)
0.0999.9 (Time range: ---,-h)
09999 (Time range:
----h)
0.0009.999 (Time range: -,---s)
0.00
0.0
0:00
0.0
0 0:00
0.0
0
0.000
Same as cycle time above Same
as left
0100 0
Same as cycle time above Same
as left
Unit Set
value
s
s
s min; s
min
min
h; min
h
h
s
Same as left
%
Same as left
Function Setting Mode
Parameter name Parameter Setting range Dafault
value
Time range
Timer mode Output mode
Output time Input signal width Key protect level
timr --,--s/---,-s/----s/--min--s/
timm up down up --­outm a a-1 a-2 a-3 b b-1
otim hold 0.01 to 99.99 hold s iflt 20ms 1ms 20ms --­kypt kp-1 kp-2 kp-3
---,-min/----min/--h--min/
---,-h/----h/-,---s
d e f s
kp-4 kp-5 kp-6 kp-7
a ---
kp-1 ---
Unit Set
value
---
Publication 700-UM002B-EN-D - June 2010
Appendix-4
Settings for Repeat Cycle Operation
Run Mode
Parameter name Parameter Setting range Dafault
value
Present value, OFF set time
Present value, ON set time
OFF set time
Present value ON set time Present value
0.0099.99 (Time range: --,--s)
0.0 999.9 (Time range: ---,-s)
09999 (Time range: ----s)
0:00 99:59 (Time range: --min--s)
0.0 999.9 (Time range: ---,-min)
09999 (Time range: ----min)
0:0099:59 (Time range: --h--min)
0.0999.9 (Time range: ---,-h)
09999 (Time range: ----h)
0.0009.999 (Time range: -,---s)
Same as OFF set time above Same as OFF set time above Same as OFF set time above
0.00
0.0
0 0:00
0.0
0 0:00
0.0
0
0.000
Same as left Same as left Same as left
Unit Set
value
s
s
s
min; s
min
min
h; min
h
h
s
Same as left Same as left Same as left
Publication 700-UM002B-EN-D - June 2010
Function Setting Mode
Parameter name Parameter Setting range Dafault
value
OFF time range
ON time range
Timer mode ON/OFF start mode
Input signal width Key protect level
oftr
ontr
timm totm
iflt kypt
--,--s/---,-s/----s/--min--s/
---,-min/----min/--h--min/
---,-h/----h/-,---s
--,--s/---,-s/----s/--min--s/
---,-min/----min/--h--min/
---,-h/----h/-,---s
up
/down
toff
/ton,/toff-1/
ton,-1
/1ms
20ms
/kp-2/kp-3/kp-4
kp-1 kp-5
/ kp-6/ kp-7
--,--s ---
--,--s ---
up --­toff ---
20ms --­kp-1 ---
Unit Set
value
Appendix-5
Publication 700-UM002B-EN-D - June 2010
Allen-Bradley is a registered trademark of Rockwell Automation
Publication 700-UM002B-EN-D - June 2010 1 © 2010 Rockwell Automation, Inc. All Rights Reserved. Printed in the U.S.A.
Loading...