Because of the variety of uses for the products described in this publication,
those responsible for the application and use of this control equipment must
satisfy themselves that all necessary steps have been taken to assure that each
application and use meets all performance and safety requirements, including
any applicable laws, regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown in this
guide are intended solely for purposes of example. Since there are many
variables and requirements associated with any particular installation,
Allen-Bradley does not assume responsibility or liability (to include
intellectual property liability) for actual use based upon the examples shown
in this publication.
Rockwell Automation publication SGI-1.1, Safety Guidelines for the Application, Installation and Maintenance of Solid-State Control (available from your local
Rockwell Automation sales office or Allen-Bradley distributor), describes
some important differences between solid-state equipment and
electromechanical devices that should be taken into consideration when
applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or
part, without written permission of Rockwell Automation, is prohibited.
Throughout this manual we use notes to make you aware of safety
considerations:
Identifies information about practices or circumstances
that can lead to personal injury or death, property damage
or economic loss
Attention statements help you to:
• identify a hazard
• avoid a hazard
• recognize the consequences
Identifies information that is critical for successful
application and understanding of the product.
European Communities (EC)
Directive Compliance
If this product has the CE mark it is approved for installation within the
European Union and EEA regions. It has been designed and tested to meet
the following directives.
EMC Directive
This product is tested to meet the Council Directive 89/336/EC
Electromagnetic Compatibility (EMC) by applying the following standards, in
whole or in part, documented in a technical construction file:
This product is intended for use in an industrial environment.
Low Voltage Directive
• EN 50081-2 EMC — Generic Emission Standard, Part 2 — Industrial
Environment
• EN 50082-2 EMC — Generic Immunity Standard, Part 2 — Industrial
Environment
This product is tested to meet Council Directive 73/23/EEC Low Voltage, by
applying the safety requirements of EN 61010-1 safety requirements for
electrical equipment for measurement, control and laboratory use--Part 1
General Safety Requirements.
This equipment is classified as open equipment and must be mounted as
instructed in an enclosure during operation to provide safety protection.
Preface
Manual Objectives
Who Should Use This
Manual
Counter/Timer Mode
Explanation
The purpose of this manual is to provide you with the additional information
necessary to apply the 700-HX Multifunction Digital Timer. Described in this
manual are methods for applying and troubleshooting this product.
This manual is intended for qualified personnel responsible for setting up and
servicing these devices. You must have previous experience with and a basic
understanding of wiring diagrams, configuration procedures, related equipment,
and safety precautions.
In this manual we refer to the Timer Output Modes with the following
designations:
A: Signal ON delay 1
A-1: Signal ON delay 2
A-2: Power ON delay 1
A-3: Power ON delay 2
B: Repeat Cycle 1
B-1: Repeat Cycle 2
D: Signal OFF delay
E: One Shot
F: Cumulative
Z: ON/OFF-duty adjustable repeat cycle
S: Stop Watch
toff: Flicker OFF start 1(Timer resets when power comes on)
ton: Flicker ON start 1 (Timer resets when power comes on)
toff-1: Flicker OFF start 2(Timer does not reset when power comes on)
ton-1: Flicker ON start 2 (Timer does not reset when power comes on)
Note: In this manual the 700-HX Multifunction Digital Timer will be referred to
as “700-HX.” For further information, please refer to the Industrial Controls
Catalog or www.ab.com/catalogs.
1Publication 700-UM002B-EN-D June 2010
Preface 2
Publication 700-UM002B-EN-D - June 2010
Product Overview
Chapter
1
Bill of Material
Basic Product Information
Cat. No.Input
Voltage
700-HX86SA17 100…240
V AC
12…24V
700-HX86SU24
DC
24V AC
Output Modes Timing RangesSocketsOutput Pins
A mode: Signal ON-Delay 1
A-1 mode: Signal ON-Delay 2
A-2 mode: Power ON-Delay 1
A-3 mode: Power On-Delay 2
B mode: Repeat Cycle 1
B-1 mode: Repeat Cycle 2
D mode: Signal OFF-delay
E mode: One Shot
F mode: Cumulative
Z mode: On/Off duty adjustable repeat cycle
S mode:stop watch
toff: Flicker OFF start 1
ton: Flicker ON start 1
toff-1: Flicker OFF start 2
ton-1: Flicker ON start 2
Your 700-HX Multifunction Digital Timer product package includes the
following items:
Item No.DescriptionQuantity
700-HXDigital Timing Relay1
—6-Language Instruction Sheet1
— Rubber Gasket1
0.000…9.999 s
0.000…99.99 s
0.000…999.9 s
0.000…9999 s
0.000…99 min. 59 s
0.000…999.9 min.
0.000…9999 min.
0.000…99 h 59 min.
0.000…999.9 h
0.000…9999 h
700-HN100
700-HN125
SPDT8
1Publication 700-UM002B-EN-D - June 2010
1-2 Product Overview
Accessories
(Order Separately)
Cat. No.DescriptionPkg. Qty.
700-HN100Screw Terminal Tube Base Sockets — Panel or DIN Rail
Mounting Guarded Terminal Construction
8-pin for use with Bulletin 700-HX timing relays. Order
must be for 10 sockets or multiples of 10.
700-HN125Screw Terminal Tube Base Sockets — Panel or DIN Rail
Mounting
Open Style Construction
8-pin for use with Bulletin 700-HX timing relays. Order must
be for 10 sockets or multiples of 10. No retainer clip
required.
199-DR1DIN Rail Mounting Pack
Standard 35 x 7.5 mm DIN Rail, 1 meter long, 10 rails per
package. Order must be for 10 rails or multiples of 10.
700-HN108Specialty Socket
8-pin backwired socket with solder terminals for use with
Bulletin 700-HX timing relays. Order must be for 10 sockets
or multiples of 10.
700-HN130Frame Adapter
For flush or door mounting of all Bulletin 700-HR and -HX
timers.
700-HN132Protective Cover
Helps prevent tampering of timing and mode settings.
Provides a degree of protection against water and dirt from
entering the front of the relay. For use with all Bulletin
700-HRs and -HX timing relays.
700-N40Pre-printed identification tags— contains 10 sheets of
pre-printed and blank tags. Each sheet contains 13 sets of
the markings CR…9CR, TR…9TR, M…9M, F, R, 1S, and
117 blank tags. Tags are peel-off with sticky backing for
easy placement on relays.
10
10
10
10
1
1
10
Publication 700-UM002B-EN-D - June 2010
700-N41Blank identification tags— contains 10 sheets of blank
identification tags for customer specialized printing. Each
sheet contains 546 blank tags. Tags are peel-off with sticky
backing for easy placement on relays.
10
Product Features
Input circuit
Internal control
circuit
Power supply
circuit
(Basic
insulation)
Display circuit
Key switch
circuit
(See note.)
Output circuit
Chapter
2
Block diagram
Note: 700-HX86SA17: Basic insulation is provided
700-HX86SU24: Basic insulation is not provided
InputsStart signalStops timing in A-2 and A-3 (power ON delay)
modes.
Starts and stops timing in S mode.
Start timing in other modes.
ResetResets present value. (In elapsed time mode, the
present value returns to 0; in remaining time
mode, the present value returns to the set value.)
Count inputs are not accepted and control output
turns OFF while reset input is ON.
Reset indicator is lit while reset input is ON.
Gate ➊Inhibits timer operation.
OutputsControl output (OUT)Outputs take place according to designated
operating mode when timer reaches
corresponding set value.
Gate capability not available.
➊
1Publication 700-UM002B-EN-D - June 2010
2-2 Product Features
0 12345
1,000
500
100
50
10
Switching operations ( 10
4
)
250V DC/30V
cos =1
250V A C cos =0.4
Load current (A)
30V DC L/R=7 ms
Reference:A maximum current of 0.15 A can be switched
at 125V DC (cosφ=1) and a maximum current of 0.1 A
can be switched if L/R is 7 ms. In both cases, a life of
100,000 operations can be expected. The minimum
applicable load is 10 mA at 5V DC (failure level: P).
120V AC
120V AC
Engineering Data
(Reference Values)
Specifications
Electrical Ratings
Pilot Duty RatingNEMA B300
Rated supply voltage100 to 240V AC, 24V AC/12 to 24V DC (50/60Hz) (permissible
ripple: 20%(p-p) max.)
Operating voltage range85%…110% of rated supply voltage
Power consumption100…240V AC
24V AC/12…24V DC
Inrush Current100…240V AC
24V AC/12…24V DC
4.3 VA
3.4 VA/1.7 W
3 A
5 A
30 A
15 A
Make 240V AC
3 A
1.5 A
Break 240V AC
Hp at 120V AC1/4 Hp
Hp at 240V AC1/3 Hp
Present value (red, 12 mm high characters); Set value (green,
6 mm high characters)
Digits4 digits
TimerTime ranges0.000…9.999 s, 0.00…99.99 s, 0.0…999.9 s, 0…9999 s,
Timer modesElapsed time (Up), remaining time (Down), selectable
Output modesA, A-1, A-2, A-3, B, B-1, D, E, F, Z, S, toff, ton, toff-1, or ton-1
0 min. 0 s…99 min. 59 s, 0.0…999.9 min., 0 h 00 min.…99 h
59 min., 0.0 h…999.9 h, 0 h…9999 h
Publication 700-UM002B-EN-D - June 2010
Product Features 2-3
Electrical Ratings
InputsInput signalsStart, reset
Input methodNo-voltage input via:NPN transistor or switching of contact
Start, resetMinimum input signal width: 1 or 20 ms (selectable)
Power resetMinimum power-opening time: 0.5 s (Except for A-3, B-1, and
F mode)
Control outputSPDT contact output: 5 A at 250V AC, resistive load
(cosine=1)
Minimum applied load: 10 mA at 5V DC (failure level: P,
reference value)
External Power SupplyNo
Key ProtectYes
Memory backupEEP-ROM (overwritten 100,000 times min.), which can store
data for 10 years min.
Accuracy of Operating Time and Setting Error ➊Power-ON start: +-0.01% +-50 ms max.*
* to be rated against set value
Signal start: +- 0.005 +-30 ms max. *
* to be rated against set value
Signal start at transistor output model: +- 0.005% +-3 ms
max. ➋
If the set value is within the sensor waiting time
(250 ms max.)
➊ The values are based on the set value.
❷ The value is applied for a minimum pulse width of 1 ms.
Characteristics
Insulation resistance100 MΩ min. (at 500V DC)
Dielectric strength2000V AC, 50/60Hz for 1 min. between current-carrying terminals and
non-current-carrying metal parts
(1000V AC for 24V AC/12 to 24V DC type),
1000V AC, 50/60 Hz for 1 min. between non-continuous contacts
Noise immunity'+-1.5 kV (between power terminals) for 100 to 240V AC, +-480V for 24V AC/12
to 24VDC, and +-600V (between input terminals), square-wave noise by noise
simulator (pulse width: 100 ns/1 μs, 1-ns rise)
Static immunity±8 kV (malfunction), ±15 kV (destruction)
Vibration resistanceMalfunction10…55 Hz with 0.35 mm single amplitude each in three directions for 10 min.
Shock resistanceMalfunction
Life expectancyMechanical10 million operations min.
Electrical100,000 operations min. (5 A at 250V AC, resistive load)
EMC(EMI) EN61812-1
2
98 m/s
(approx. 10 G) each in three directions
Emission Enclosure: EN55011 Group1 class A
Emission AC mains: EN55011 Group1 class A
(EMS) EN61812-1
Immunity ESD: EN61000-4-2: 4 kV contact discharge (level2)
8 kV air discharge (level3)
Immunity RF-interference: EN61000-4-3: 10 V/m
Publication 700-UM002B-EN-D - June 2010
2-4 Product Features
12mm6mm
1
3
2
8
9
5
4
6
7
10
11
12
Display Section
1. Key Protect Indicator
(orange)
2. Control Output Indicator
(orange)
Front View
Character Size
for Present
Value Display
Character Size
for Set Value
Display
3. Reset Indicator
(orange)
Operation Key
Switches
8. Mode Key
(Changes modes and setting items)
9. Reset Key
(Resets present value and output)
10. Up Keys 1 to 4
11. Down Keys 1 to 4
12. Key-protect Switch
6. Set Value Display
(Sub-display)
(Character height: 6 mm, green)
7. Set Value 1, 2 Indicator
(green)
4. Present Value Display
(Main display)
(Character height: 12 mm, red
*
)
* Characters on models with screw terminals
5. Time Unit Indicators
(Color is same as present value display.)
(If the time range is 0 min, 0 h, 0.0 h, or 0 h
0 min, these indicators flash to indicate
timing operation.)
OFF
(Disabled)
ON
(Enabled)
(Default setting)
can be switched between red, green, and orange.
Approved standardsUL508, CSA C22.2 No.14
Conforms to EN 61812-1
(Pollution degree 2/overvoltage category III)
Conforms to VDE0106/P 100 (Finger Protection), conforms to NEMA output
rating (N/F)
Enclosure ratingsPanel surface:IP66 and NEMA Type 4X (indoors) ➊
WeightApprox. 100 g
➊An attached waterproof packing is necessary to ensure IP66 waterproofing between the
700-HX and installation pan.
Nomenclature
Publication 700-UM002B-EN-D - June 2010
Output ONcount alarm setvalue
Output ONcount monitor
value
(9999 x 1000 times)
(0 x 1000 times)
Note: The monitor value is only displayed.
It cannot be set.
99990
~
(9999)(1)
99991
timr
timm
outm
otim
w
sshs
(1 ms)(20 ms)
……
s
(A-1) (A-2) (A-3)(b-1)(b))Z()S()F()E()d((A)
za-1aa-2 a-3 b b-1 d e fs
m
m
〜
Key protect
level
(KP-1)(KP-2)(KP-3)(KP-4)(KP-5)(KP-6)(KP-7)
kp-2
kp-1
kp-3kp-4kp-5kp-6kp-7
Set the key protect levelusing the keys.
Run mode
Power ON
Note:1. If the mode is switched to the function setting mode during operation,
operation will continue.
2. Changes made to settings in function setting mode are enabled for the
first time when the mode is changed to run mode. Also, when settings
are changed, the timer is reset (time initial ized and output turned OFF).
For details on operations in run mode, refer to 3-10.
See note 1.See note 2.
3 s min.3 s min.
Function setting mode
Timer mode
Output mode
Output time
Input signal
width
Time range
0.01 s to 99.99 s
(default setting)
0.1 s to 999.9 s
1 s to 9,999 s
0 min 01 s to 99 min 59 s
0.1 min to 999.9 min
1 min to 9,999 min
0 h 01 min to 99 h 59 min
Display
0.1 h to 999.9 h
Set Value
1 h to 9,999 h
Time Range List
0.001s to 9.999 s
Set the time range using the keys.
Set the timer mode using the keys.
Set the output mode using the keys.
Set each digit for the output time using the corresponding keys.
Press the mode button f or se veral seconds to display the Time Range setti ng
screen.
(If the output time is set to 0.00,hold is displayed.)
Displayed for modes A, A-1, A-2, A-3, B, and B-1 only.
Set value
upper limit
Output on
count alarm
set value
Output on
count
monitor set
value
Set the key protect level using the keys.
Functions
Settings For Advanced Functions
Chapter
3
1Publication 700-UM002B-EN-D - June 2010
3-2 Functions
Explanations of Functions
Time Range (
Set the range to be timed in the range 0.000 s… 9,999 h. Use the operation
keys if these settings are required.
Timer Mode (
Set either the elapsed time (UP) or remaining time (DOWN) mode.
Output Mode (
Set the output mode. The possible settings are A, A-1, A-2, A-3, B, B-1, D, E,
F, Z and S. (For details on output mode operation, refer to “Timing Charts”
on page 3-11.)
Output Time (
When using one-shot output, set the output time for one-shot output (0.01…
99.99 s). One-shot output can be used only if the selected output mode is A,
A-1, A-2, B, or B-1. If the output time is set to 0.00, hold is displayed, and the
output is held.
timr
timm
outm
otim
)
)
)
)
Input Signal Width (
Set the minimum signal input width (20 ms or 1 ms) for signal and reset
inputs. The same setting is used for all external inputs (signal and reset). If
contacts are used for the input signal, set the input signal width to 20 ms.
Processing to eliminate chattering is performed for this setting.Set the key
protect level.
Set Value Upper Limit (
Set the upper limit for the set value when it is set in Run Mode. The limit can
be set to between 1 and 9999. This setting does not apply to the ON duty in Z
mode.
Output ON Count Alarm Set Value (
Set the alarm value for the output ON count.The limit can be set to between 0
x 1000 times and 9999 x 1000 times. (The rightmost three digits will not be
displayed.) If the total ON count of the output exceeds the alarm set value, e3
will be displayed on the Timer to indicate that the output ON count alarm
value was exceeded.
iflt
sl-h
)
)
on-a
)
Publication 700-UM002B-EN-D - June 2010
Output ON Count Monitor Value (
The monitor value is only displayed. It cannot be set. The value will be
between 0 x 1000 times and 9999 x 1000 times. (The rightmost three digits will
not be displayed.)
on-c
)
Functions 3-3
ON
OFF
Key protect indicator
Note: Factory-set to OFF
(See note)
Key Protect Level (
kypt
)
When the key-protect switch in set to ON, it is possible to prevent setting
errors by prohibiting the use of certain operation keys by specifying the key
protect level (KP-1 to KP-7). The key protect indicator is lit while the
key-protect switch is set to ON. Confirm the ON/OFF status of the
key-protect switch after the 700-HX is mounted to the panel.
LevelMeaning
KP-1
(default
setting)
KP-2Prohibits changing the mode to timer/repeat
KP-3Prohibits changing the mode to timer/repeat
KP-4Prohibits changing the mode to timer/repeat
KP-5Prohibits changing the mode to timer/repeat
KP-6Prohibits changing the mode to timer/repeat
KP-7Prohibits changing the mode to timer/repeat
Prohibits changing the mode to timer/repeat
cycle selection mode or function setting
mode. The 700-HX can only be used in run
mode.
cycle selection mode or function setting
mode. The 700-HX can only be used in run
mode. Also prohibits use of the reset key.
cycle selection mode or function setting
mode. The 700-HX can only be used in run
mode. Also prohibits use of the up and down
keys.
cycle selection mode or function setting
mode. The 700-HX can only be used in run
mode. Also prohibits use of the reset, up and
down keys.
cycle selection mode or function setting
mode. The 700-HX can only be used in run
mode. Also prohibits use of any operation
keys.
cycle selection mode or function setting
mode. The 700-HX can only be used in run
mode. Also prohibits use of the mode key.
cycle selection mode or function setting
mode. The 700-HX can only be used in run
mode. Also prohibits use of mode and reset
keys.
Publication 700-UM002B-EN-D - June 2010
3-4 Functions
Present value
Set value
Present value
ON duty ratio
Present value
Cycle time
When Output Mode Z Is Selected
Set each digit for the ON duty ratio using the corresponding keys.
(The keys for the 4th digit cannot be used.)
Set each digit for the cycle time using the corresponding keys.
Set each digit for the set value using the corresponding keys.
When Output Mode Is Not Z
Operation in Run Mode
Present Value and Set Value
These items are displayed when the power is turned ON. The present value is
displayed in the main display and the set value is displayed in the sub-display.
The values displayed will be determined by the settings made for the time
range and the timer mode in function setting mode.
Present Value and ON Duty Ratio (Output Mode = Z)
The present value is displayed in the main display and the ON duty ratio is
displayed in the sub-display. “SET1” lights at the same time.
Set the ON duty ratio used in ON/OFF-duty adjustable Repeat Cycle (Z) as a
percentage.
If a cycle time is set, cyclic control can be performed in ON/OFF-duty
adjustable Repeat Cycle simply by changing the ON duty ratio.
Present Value and Cycle Time (Output Mode = Z)
The present value is displayed in the main display and the cycle time is
displayed in the sub-display. “SET2” lights at the same time.
Publication 700-UM002B-EN-D - June 2010
Set the cycle time used in ON/OFF-duty adjustable Repeat Cycle (Z).
Functions 3-5
Elapsed cycle time
ON duty set as a percentage
Up/down keys used for analog
adjustment of the ON duty
Cycle time
ON duty (%)
Output control
Close
Open
Opening/closing valve
Fully closed↔Fully open
0%↔100%
ON duty
1
Power ON
Function
selection
Hold down for
1s min.
Switch from timer operation to repeat cycle
operation using the keys.
Timer/repeat cycle selection mode
Run mode
m
Operation (Repeat Cycle
Function)
Switching from Timer to Repeat Cycle
The 700-HX is factory-set for timer operation. To switch to repeat cycle
operation, use the procedure given below. For details, refer to page
Appendix-2.
Set the function (instantaneous or time-limit operation) for the instantaneous output (output 1)
using the Keys.
*1. If the mode is switched to the function setting mode during operation, operation will continue.
*2. Changes made to settings in function setting mode are enabled for the first time when the mode is changed to run mode.
Also, when settings are changed, the timer is reset (time initialized and output turned OFF).
.
keys.
Settings for Advanced Functions
Publication 700-UM002B-EN-D - June 2010
Functions 3-7
~
~
~
(KP-1)(KP-2)(KP-3)(KP-4)(KP-5)(KP-6)(KP-7)
(9999 x 1000 times)
(0 x 1000 times)
(9999 x 1000 times)
(0 x 1000 times)
(9999 x 1000 times)
(0 x 1000 times)
Note: The monitor value is only displayed.
It cannot be set.
Note:
The monitor value is only displayed.
It cannot be set.
Note:
The monitor value is only displayed.
It cannot be set.
To previous
page
From previous
page
Function setting mode
Set the digits for the set value limit using the corresponding keys.
Set the key protect level using the keys.
Set value
upper limit 1
Set the digits for the set value limit using the corresponding keys.
Set value
upper limit 2
Key protect
level
Output ON
count alarm
set value/
monitor value
Output ON
count alarm
set value
Output ON
count monitor
value
Instantaneous
output 1
(OUT1) ON
count alarm
set value
Instantaneous
output 2
(OUT2) ON
count alarm
set value
Instantaneous
output 1
(OUT1) ON
count monitor
value
Instantaneous
output 2
(OUT2) ON
count monitor
value
• Models without Instantaneous Contact Outputs
• Models with Instantaneous Contact Outputs
*1.
Set the digits for the output ON alarm set value using the corresponding
keys.
*1
(9999)(1)
99990
99990
99990
9999
kp-2
kp-1
kp-3kp-4kp-5kp-6kp-7
1
(9999)(1)
99991
Publication 700-UM002B-EN-D - June 2010
3-8 Functions
Explanation of Functions (Repeat Cycle Function)
OFF Time Range (
Set the time range for the OFF time in the range 0.000 s… 9,999 h. Use the
operation keys if another type of setting is required.
ON Time Range (
Set the time range for the ON time in the range 0.000 s …9,999 h. Use the
operation keys if another type of setting is required.
oftr
ontr
)
)
Timer Mode (timm)
Set either UP (incremental) or DOWN (decremental) timer mode. In UP
mode, the elapsed time is displayed, and in DOWN mode, the remaining time
is displayed.
ON/OFF Start Mode (totm)
Set the output mode. Set either Repeat Cycle OFF start or Repeat Cycle ON
start. (For details on output mode operation, refer to 3-11.)
Input Signal Width (
iflt
) (Setting possible using DIP switch.)
Set the minimum signal input width (20 ms or 1 ms) for signal, reset, and gate
inputs. The same setting is used for all external inputs (signal and rese ). If
contacts are used for the input signal, set the input signal width to 20 ms.
Processing to eliminate chattering is performed for this setting.
Key Protect Level (
Set the key protect level.
When the key-protect switch in set to ON, it is possible to prevent setting
errors by prohibiting the use of certain operation keys by specifying the key
protect level (KP-1 to KP-7). The key protect indicator is lit while the
key-protect switch is set to ON. Confirm the ON/OFF status of the
key-protect switch after the 700-HX is mounted to the panel.
kypt
)
Publication 700-UM002B-EN-D - June 2010
Functions 3-9
ON
OFF
Key protect indicator
Note: Factory-set to OFF
(See note)
LevelMeaning
KP-1
(default
setting)
Prohibits changing the mode to timer/repeat
cycle selection mode or function setting
mode. The 700-HX can only be used in run
mode.
KP-2Prohibits changing the mode to timer/repeat
cycle selection mode or function setting
mode. The 700-HX can only be used in run
mode. Also prohibits use of the reset key.
KP-3Prohibits changing the mode to timer/repeat
cycle selection mode or function setting
mode. The 700-HX can only be used in run
mode. Also prohibits use of the up and down
keys.
KP-4Prohibits changing the mode to timer/repeat
cycle selection mode or function setting
mode. The 700-HX can only be used in run
mode. Also prohibits use of the reset, up and
down keys.
KP-5Prohibits changing the mode to timer/repeat
cycle selection mode or function setting
mode. The 700-HX can only be used in run
mode. Also prohibits use of any operation
keys.
KP-6Prohibits changing the mode to timer/repeat
cycle selection mode or function setting
mode. The 700-HX can only be used in run
mode. Also prohibits use of the mode key.
KP-7Prohibits changing the mode to timer/repeat
cycle selection mode or function setting
mode. The 700-HX can only be used in run
mode. Also prohibits use of mode and reset
keys.
Publication 700-UM002B-EN-D - June 2010
3-10 Functions
Present value
OFF set time
Present value
ON set time
Set the digits for the OFF set time using the corresponding keys.
Set the digits for the ON set time using the corresponding keys.
One-shot
Sustained output
One-shot outputs can be to set to 0.1 s, 0.5 s, 1s, 5 s, 10 s, 20 s.
Operation in Run Mode
Operation in Timer/Repeat
Cycle Selection Mode
Present Value and OFF Set Time
The present value is displayed in the main display and the OFF set time is
displayed in the sub-display. “SET1” lights at the same time.
Present Value and ON Set Time
The present value is displayed in the main display and the ON set time is
displayed in the sub-display. “SET2” lights at the same time.
Select whether the 700-HX is used as a timer or a repeat cycle in timer/repeat
cycle selection mode.
Publication 700-UM002B-EN-D - June 2010
Functions 3-11
1
MODE
+
To change the mode to timer/selection mode, hold
down the key for 1 s min. with the key held down.
The key must be pressed before the key.
If the key is pressed first, the mode will not change.
MODE
Select either timer operation or repeat cycle operation.
using the keys.
1
Power ON
Timer/Repeat
Run Mode
Note: factory-set for timer operation.
Timer Repeat cycle/ Selection Mode
1 s min.
1
1
MODE
The 700-HX is
m
repeat cycle
cycle operation
Power
Start signal
Gate
Reset
Control output
Set value
Timing
diagram
UP
DOWN
0
0
Set value
t
t
t
Timing starts when the start signal goes ON.
The control output is controlled using a sustained or
one-shot rime period.
While the start signal is ON, the timer starts when
power comes ON or when the reset input goes OFF.
Basic Operation
Power
**
Start signal
input
Output
* Output is instantaneous when setting is 0.
** Start signal input is enabled during timing.
Timing
Timing Charts
Note:
1. When the mode is changed to timer/repeat cycle selection mode, the
present value is reset and output turns OFF. Timing operation is not
performed in timer/repeat Cycle selection mode.
2. Setting changes made in timer/repeat cycle selection mode are enabled
when the mode is changed to run mode. If settings are changed, the 700-HX is
automatically reset (present value initialized, output turned OFF).
The gate input is not included in the 700-HX.
Output mode A Mode: Signal ON-Delay (Timer resets when power comes ON.)
Publication 700-UM002B-EN-D - June 2010
3-12 Functions
Power
Start signal
Gate
Reset
Control output
Set value
Timing
diagram
UP
DOWN
0
0
Set value
Power
Start signal
Gate
Reset
Control output
Set value
Timing
diagram
UP
DOWN
0
0
Set value
.
Power
Start signal
Gate
Reset
Control output
Set value
Timing
diagram
UP
DOWN
0
0
Set value
t
Timing starts when the reset input goes OFF.
The start signal disables the timing function (i.e., same function as the gate input).
The control output is controlled using a sustained or
one-shot time period.
*Output is instantaneous when setting is 0.
Basic Operation
Power
Timing
Output
Sustained
.
Power
Start signal
Gate
Reset
Control output
Set value
Timing
diagram
UP
DOWN
0
0
Set value
Sustained
Output
Timing starts when the start signal goes ON.
The status of the control output is reversed when time
is up (OFF at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
* Normal output operation will not be possible if the
set time is too short.
Set the value to at least 100 ms (contact output
type).
** Start signal input is disabled during timing.
Basic Operation
Power
**
Start signal
input
Timing
Output
TimingTimingTiming
Output Mode A-1: Signal ON-Delay 2 (Timer resets when power comes ON.)
Timing starts when the start signal goes ON, and is
reset when the start signal goes OFF.
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
The control output is controlled using a sustained or
one-shot time period.
Basic Operation
Power
Start signal
input
Output
*Output is instantaneous when setting is 0.
Timing
Output mode A-2: Power ON Delay 1 (Timer resets when power comes ON)
Timing starts when the reset input goes OFF.
The start signal disables the timing function (i.e., samefunction as the gate input).
The control output is controlled using a sustained or
one-shot time period.
Basic Operation
Power
Output
*Output is instantaneous when setting is 0.
Timing
Output mode A-3 Power ON Delay 2 (Timer does not reset when power comes ON)
Publication 700-UM002B-EN-D - June 2010
Output mode B: Repeat Cycle 1 (Timer resets when power comes ON.)
Output mode B: Repeat Cycle 1 (Timer resets when power comes ON.)
Power
Start signal
Gate
Reset
Control output
Set value
Timing
diagram
UP
DOWN
0
0
Set value
One-shot
Output
Timing starts when the start signal goes ON.
The status of the control output is reversed when time
is up (OFF at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
* Normal output operation will not be possible if the
set time is too short.
Set the value to at least 100 ms (contact output
type).
** Start signal input is disabled during timing.
Sustained
Basic Operation
Power
**
Start signal
input
Output
Timing
Timing
Power
Start signal
Gate
Reset
Control output
Set value
Set value
Timing
diagram
UP
DOWN
0
0
One-shot
Output
tt
t
t
t
Timing starts when the start signal goes ON.
The control output is turned ON when time is up.
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Basic Operation
Power
**
Start signal
input
Output
* Normal output operation will not be possible if the
set time is too short.
Set the value to at least 100 ms (contact output
type).
** Start signal input is disabled during timing.
Output Mode B-1: Repeat Cycle 2 (Timer does not reset when power comes ON)
Functions 3-13
TimingTimingTimingTiming
Sustained
Output
Start signal
Control output
UP
Timing
diagram
DOWN
Power
Gate
Reset
Set value
Set value
0
0
Timing starts when the start signal goes ON.
The control output comes ON when time is up..
While the start signal is ON, the timer starts when
power comes ON or when the reset input goes OFF.
Basic Operation
Power
Start signal
input
Output
* Normal output operation will not be possible if the
set time is too short.
Set the value to at least 100 ms (contact output
type).
** Start signal input is disabled during timing.
Timing
**
Sustained
Timing
Publication 700-UM002B-EN-D - June 2010
3-14 Functions
Power
Start signal
Gate
Reset
Control output
Set value
Timing
diagram
UP
DOWN
0
0
Set value
Power
Start signal
Gate
Reset
Control output
Set value
Timing
diagram
UP
DOWN
0
0
Set value
Timing starts when the start signal comes ON.
The control output is reset when time is up.
While the start signal is ON, the timer starts when
power comes ON or when the reset input goes OFF.
* Output is disabled when the setting is 0.
** Start signal input is enabled during timing.
Basic Operation
Power
**
Start signal
input
Output
Timing
Power
Start signal
Gate
Reset
Control output
Set value
Timing
diagram
UP
DOWN
0
0
Set value
Start signal enables timing (timing is stopped when the
start signal is OFF or when the power is OFF).
A sustained control output is used.
*Output is instantaneous when setting is 0.
Sustained
Basic Operation
Power
Start signal
input
Output
TimingTiming
Output mode D: Signal OFF-delay (Timer resets when power comes ON.)
The control output is ON when the start signal is
ON (except when the power is OFF or the reset is
ON).
The timer is reset when the time is up.
Basic Operation
Power
**
Start signal
input
Output
* Output functions only during start signal input when
setting is 0.
** Start signal input is enabled during timing.
Output mode E: One Shot (Timer resets when power comes ON.)
Timing
Publication 700-UM002B-EN-D - June 2010
Output Mode F: Cumulative (Timer does not reset when power comes ON)
Z Mode
Output quantity can be adjusted by changing the cycle time set in the
adjustment level to 1 and by changing the ON duty (%) set value. The set value
shows the ON duty (%) and can be set to a value between 0 and 100 (%).
When the cycle time is 0, the output will always be OFF. When the cycle time
is not 0 and when ON duty has been set to 0 (%), the output will always be
OFF. When ON duty has been set to 100 (%), the output will always be ON.
Z mode: ON/OFF-duty Adjustable Repeat Cycle
9999
Set time
0
Set time
0
UP
DOWN
Power
Start signal
Gate/Reset
Timing diagram
Output
Functions 3-15
Timing
diagram
Power
Start signal
Gate
Reset
Control output
Cycle time
ON duty setting
(%) ON time
UP
Cycle time
ON duty setting
(%) ON time
DOWN
Timing starts when the start signal goes ON.
The status of the control output is reversed
when time is up (ON at start).
While the start signal is ON, the timer starts when
power comes ON or when the reset input goes OFF.
Basic Operation
Power
**
Start signal
input
0
Timing
(cycle time)
Timing
ON duty (%)
Timing
(cycle time)
Timing
ON duty (%)
Output
0
* Normal output operation will not be possible if the
set time is too short.
Set the value to at least 100 ms (contact output
type).
** Start signal input is enabled during timing.
S mode: Stop Watch (Timer Resets when Power Comes On)
The signal starts and stops timing.
The display is held and timing is continued if the reset
or gate input is received during timing operation.
The timer resets if the reset or gate input is received
when the timing operation is stopped.
Basic Operation
Power
Start signal
input
Gate/Reset
Timing
Display
(for elapsed
time)
*
RST
*
flashes
Note: Output is instantaneous when setting is 0.
Publication 700-UM002B-EN-D - June 2010
3-16 Functions
Power
Start signal
Gate
Reset
Control output
OFF time
Timing
diagram
UP
ON time
Sustained
Output
DOWN
OFF time
ON time
0
0
Repeat Cycle Operation
Output mode TOFF: Flicker OFF start 1 (Timer resets when power comes ON)
Sustained
Output
Control output
Timing
diagram
DOWN
Power
Start signal
Reset
OFF time
UP
ON time
OFF time
ON time
Gate
Timing starts when the start signal goes ON.
The status of the control output is reversed when time
is up (OFF at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Basic Operation
Power
**
Start signal
input
Output
0
0
* Normal output operation will not be possible if the
ON/OFF set time is too short.
Set the value to at least 100 ms (contact output
type).
** Start signal input is disabled during timing.
Timing
OFF
Timing
ON
Timing
OFF
Timing
ON
Output mode TON: Flicker ON start 1 (Timer resets when power comes ON)
Timing starts when the start signal goes ON.
The status of the control output is reversed when time
is up (ON at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Basic Operation
Power
**
Start signal
input
Output
* Normal output operation will not be possible if the
ON/OFF set time is too short.
Set the value to at least 100 ms (contact output
type).
** Start signal input is disabled during timing.
Timing
ON
Timing
OFF
Timing
ON
Timing
OFF
Publication 700-UM002B-EN-D - June 2010
Output mode TOFF-1: Flicker OFF start 2 (Timer does not reset when power comes ON)
0
0
ON time
OFF time
OFF time
ON time
UP
DOWN
Power
Start signal
Gate
Reset
Control output
Timing diagram
Timing starts when the start signal goes ON.
0
0
ON time
OFF time
OFF time
ON time
UP
DOWN
Power
Start signal
Gate
Reset
Control output
Timing diagram
* Start signal input is disabled during timing.
Timing starts when the start signal goes ON.
The status of the control output is reversed when time is
up (ON at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact output
type).
TimingONTiming
OFF
Timing
ON
(a + b = OFF time)
ab
Power
Output
*
Start signal
input
Basic Operation
The status of the control output is reversed when time is
up (OFF at start).
While the start signal is ON, the timer starts when the
power comes ON or when the reset input goes OFF.
Basic Operation
Power
*
Start signal
input
Output
Timing
OFF
TimingONTiming
* Start signal input is disabled during timing.
Note: Normal output operation will not be possible if
the set time is too short.
Set the value to at least 100 ms (contact output
type).
Output mode TON-1: Flicker ON start 2 (Timer does not reset when power comes ON)
ab
OFF
(a + b = ON time)
Functions 3-17
Publication 700-UM002B-EN-D - June 2010
3-18 Functions
Publication 700-UM002B-EN-D - June 2010
700-HX Flush Mounting/
Socket Mounting
Dimensions
Chapter
4
Note: All units are in millimeters unless otherwise noted.
48×48
7.5
63.7
14.3
44.8×44.8
1Publication 700-UM002B-EN-D - June 2010
4-2 Dimensions
60 min.
60 min.
45
+0.6
−0
45
+0.6
−0
15 min.
Panel Cutouts
Panel cutouts are as shown below (according to DIN43700).
Note:
1. The mounting panel thickness should be 1…5 mm.
2. To allow easier operability, it is recommended that adapters are mounted so
that the gap between sides with hooks is at least 15 mm.
3. It is possible to mount timers side by side, but only in the direction without
the hooks.
A = (48n - 2.5)
+1
0
With 700-HN132 attached:
A = (51n - 5.5)
+1
0
n side by side mounting
A
Publication 700-UM002B-EN-D - June 2010
Installation
Internal circuit
4
3
2
18
7
6
5
ϑҤϒϑҥϒ
0V
Signal
Reset
Chapter
5
Terminal Arrangement
Input Circuits
700-HX
(–)
(+)
Note: Do not connect unused terminals as relay terminals.
Start and reset Input
+14 V
1 k
IN
1Publication 700-UM002B-EN-D - June 2010
Internal circuit
5-2 Installation
PC or sensor
0 V
Input
Signal input
Reset input
Contact input
Open Collector
(Connection to NPN open
collector output sensor)
(Connection to a voltage out
put sensor)
Sensor
Signal input
Reset input
0 V
Input
Signal input
Reset input
0 V
Input
Voltage Output
700-HX
➀➂ ➃
700-HX
➀➂ ➃
Operate with transistor ON
Operate with transistor ON
Operate with relay ON
Signal input
Reset input
0 V
Input
Input Connections
The input of the 700-HX is no-voltage input only.
No-voltage Inputs (NPN Inputs)
No-voltage Input Signal Levels
No-contact inputShort-circuit level
Contact inputUse contact which can adequately switch 5 mA at 10V
Two-wire Sensor
Transistor ON
Residual voltage: 2 V max.
Impedance when ON: 1 KΩ max.
(the leakage current is approximately 12 mA when the
impedance is 0Ω)
Open level
Transistor OFF
Impedance when OFF: 100 KΩ minimum.
Maximum applicable voltage: 30V DC max.
700-HX
➀➂ ➃
Publication 700-UM002B-EN-D - June 2010
Applicable Two-wire Sensor
Leakage current: 1.5 mA max.
Switching capacity: 5 mA minimum
Residual voltage: 3V DC max.
Operating voltage: 10V DC
Installation 5-3
Publication 700-UM002B-EN-D - June 2010
5-4 Installation
Publication 700-UM002B-EN-D - June 2010
Precautions
ATTENTION
!
ATTENTION
!
ATTENTION
!
ATTENTION
!
Do not use the product in locations subject to flammable
or explosive gases. Doing so may result in explosion.
Chapter
7
The service life of the output relays depends on the
switching capacity and switching conditions. Consider the
actual application conditions and use the product within
the rated load and electrical service life. Using the product
beyond its service life may result in contact deposition or
burning.
Do not disassemble, repair, or modify the product. Doing
so may result in electric shock, fire, or malfunction.
Do not allow metal objects or conductive wires to enter the
product. Doing so may result in electric shock, fire, or
malfunction.
1Publication 700-UM002B-EN-D - June 2010
7-2 Precautions
Power
supply
Input Impossible
Unstable
PossibleImpossibleUnstable
200 ms
0 to 50 ms
5 ms
0 to 500 ms
ON
OFF
Power Supplies
Make sure that the voltage is applied within the specified range, otherwise the
internal elements of the Timer may be damaged.
When turning the power ON and OFF, input signal reception is possible,
unstable, or impossible as shown in the diagram below.
Turn the power ON and OFF using a relay with a rated capacity of 10 A
minimum to prevent contact deterioration due to inrush current caused by
turning the power ON and OFF.
Apply the power supply voltage through a relay or switch in such a way that
the voltage reaches a fixed value immediately, otherwise they may not be reset
or a timer error may result.
Be sure that the capacity of the power supply is large enough, otherwise the
Timer may not start due to inrush current (approx. 5 A) that may flow for an
instant when the Timer is turned on.
Timer Control with Power
Start
Make sure that the fluctuation of the supply voltage is within the permissible
range.
To allow for the startup time of peripheral devices (sensors, etc.), the 700-HX
starts timing operation between 200 ms…260 ms after power is turned ON.
For this reason, in operations where timing starts from power ON, the time
display will actually start from 250 ms. If the set value is 249 ms or less, the
time until output turns ON will be a fixed value between 200…250. (Normal
operation is possible for set value of 250 ms or more.) In applications in which
a set value of 249 ms or less is required, use start timing with signal input.
When the 700-HX is used with power start in F mode (i.e., accumulative
operation with output on hold), there will be a timer error (approximately
100 ms each time the 700-HX is turned ON) due to the characteristics of the
internal circuitry. Use the 700-HX with signal start if timer accuracy is
required.
Publication 700-UM002B-EN-D - June 2010
Precautions 7-3
Self-diagnostic Function
The following displays will appear if an error occurs.
Confirm the error type using the display, and take the appropriate
countermeasures.
Main display Sub- displayErrorCorrection
e1
e2
e2
e3 ➋
➊ This includes times when the life of the EEPROM has expired.
➋ The normal display and e3 will appear alternately. When the Reset Key is pressed, e3 will
no longer be displayed even if the alarm set value is exceeded. (Monitoring is possible,
however, because the Timer will continue without clearing the output ON count.)
No
display
No
display
sumMemory (EEP)
No Change
CPUEither press the reset key or reset
the power supply.
Memory (RAM)Reset the power supply. If normal
operation is still not restored,
replacement or repair is necesary. If
normal operation is restored, the
cause may have been noise.
Reset to the factory settings using
➊
Output ON count
alarm set value
exceeded
the reset key.
Reset key
Changing the Set Values
Operation with a Set Value
of 0
Power Failure Backup
When changing the set value during a timing operation, the output will turn
ON if the set value is changed as follows because of the use of a constant
read-in system:
Elapsed time mode: Present value ≥ set value
Remaining time mode: Elapsed time ≥ set value (The present value is set to 0.)
NOTE: When in the remaining time mode, the amount the set value is
changed is added to or subtracted from the present value.
Operation with a set value of 0 will vary with the output mode. Refer to 3-11.
All data is stored in the EEPROM when there is power failure. The EEPROM
can be overwritten more than 100,000 times.
Publication 700-UM002B-EN-D - June 2010
7-4 Precautions
It is recommended that the space between
the screw head and the adapter should be
0.5 to 1 mm.
0.5 to 1 mm
Operating modeOverwriting timing
A-3, b-1, F, toff-1/
ton-1 mode
Other modeWhen settings are changed.
When power is turned OFF.
Wiring
Mounting
Wiring input lines in the same conduit as power lines or other high-voltage
lines may result in malfunction due to noise. Wire the input lines separately,
away from lines carrying high-voltages. In addition, make the input wiring as
short as possible and use shield lines or metal wiring conduits.
Dense mounting may result in a reduction in the service life of internal parts.
Tighten the two mounting screws on the Adaptor. Tighten them alternately, a
little at a time, so as to keep them at an equal tightness.
The 700-HX panel surface is water-resistant (conforming to NEMA 4 and
IP66). In order to prevent the internal circuit from water penetration through
the space between the timer and operating panel, attach a waterproof gasket
between the timer and installation panel and secure the waterproof gasket with
the 700-HN130 flush-mounting adapter.
Operating Environment
Publication 700-UM002B-EN-D - June 2010
•Use the product within the ratings specified for submerging in
water, and exposure to oil.
•Do not use the product in locations subject to vibrations or
shocks. Using the product in such locations over a long period
may result in damage due to stress.
•Do not use the product in locations subject to dust, corrosive
gases, or direct sunlight.
•Separate the input signal devices, input signal cables, and the
product from the source of noise or high-tension cables producing
noise.
•Separate the product from the source of static electricity when
using the product in an environment in which a large amount of
static electricity is produced (e.g., forming compounds, powders,
or fluid materials being transported by pipe).
Precautions 7-5
X1TX2
X2/bT/aX1/aX1/a
X
Auxiliary relay (e.g., MY Relay)
Auxiliary relay
(e.g. 700-HC Relay)
•Organic solvents (such as paint thinner), as well as very acidic or
basic solutions might damage the outer casing of the timer.
•Use the product within the ratings specified for temperature
and humidity.
•Do not use the product in locations where condensation may
occur due to high humidity or where temperature changes
are severe.
•Store at the specified temperature. If the 700-HX has been stored
at a temperature of less than –10°C, allow the 700-HX to stand at
room temperature for at least 3 hours before use.
•Leaving the 700-HX with outputs ON at a high temperature for a
long time may hasten the degradation of internal parts (such as
electrolytic capacitors). Therefore, use the product in combination with relays and avoid leaving the product as long as more
than 1 month with the output turned ON.
Insulation
There is no insulation between power supply and input terminals.
Basic insulation between power supply and output terminals.
Input and output terminals are connected to devices without exposed charged
parts.
Input and output terminals are connected to devices with basic insulation that
is suitable for the maximum operating voltage.
Publication 700-UM002B-EN-D - June 2010
7-6 Precautions
Publication 700-UM002B-EN-D - June 2010
Appendix
1
+
1
+
Power ON
Timer/Repeat Cycle selection
Timer (Except for Z mode)
PV/SV
Timer (Z mode)
PV/ON duty ratio
PV/cycle time
Tim e rang e
Timer mode
Output mode
Output time
Input signal width
Key protect level
1 s min.
3 s min.
3 s min.
1 s min.
Timer/Repeat Cycle selection mode
Run mode
Function setting mode
Operation stopped
Can be in operation
Set value upper limit
Output on alarm set
value
Output on alarm monitor
value
1
+
1
+
Power ON
Timer/Repeat Cycle selection
PV/SV
Timer (Z mode)
PV/ON duty ratio
PV/cycle time
1 s min.
3 s min.
3 s min.
1 s min.
Timer/Repeat Cycle selection mode
Run mode
Function setting mode
Operation stopped
Can be in operation
PV/OFF set time
PV/ON set time
Time range
Time r mode
Output mode
Output time
Input signal width
Key protect level
Set value upper limit
Output on alarm set
value
Output on alarm monitor
value
NOTE: All setting changes are performed using
keys .
The flowcharts above outline the procedure for
all models. For details on specific models, refer to
Timer operation and Repeat Cycle operation in
Chapter 3.
Using the Operation Keys
Timer Operation
1Publication 700-UM002B-EN-D - June 2010
Repeat Cycle Operation
Appendix-2
List of Settings
Fill in your set values in the set value column of the following tables for quick
reference.
Timer/Repeat Cycle Selection Mode
Parameter
name
Timer/
Repeat
Cycle
selection
Parameter Setting rangeDafault
value
func
tim
/twin
tim
UnitSet
value
---
Settings for Timer Operation
Run Mode when Output Mode is Not Z
Parameter nameParameter Setting rangeDefault
value
Present
value, set
value
Set value
Present
value
0.00 … 99.99
(Time range: --,--s)
0.0 … 999.9
(Time range: ---,-s)
0 … 9999
(Time range: ----s)
0:00 … 99:59
(Time range: --min--s)
0.0 … 999.9
(Time range: ---,-min)
0 … 9999
(Time range: ----min)
0:00 … 99:59
(Time range: --h--min)
0.0 … 999.9
(Time range: ---,-h)
0 … 9999
(Time range: ----h)
0.000 … 9.999
(Time range: -,---s)
Same as set valueSame
0.00
0.0
0
0:00
0.0
0
0:00
0.0
0
0.000
as left
UnitSet
value
s
s
s
min; s
min
min
h; min
h
h
s
Same
as left
Publication 700-UM002B-EN-D - June 2010
Run Mode when Output Mode = Z
Appendix-3
Parameter
name
Present
value,
Cycle
time
cycle
time
Present
value
Present
value,
ON
duty
ratio
ON
duty
ratio
Present
value
Parameter Setting rangeDafault
value
0.00 …99.99
(Time range: --,--s)
0.0 … 999.9
(Time range: ---,-s)
0 … 9999 (Time range: ----s) 0
0:00 … 99:59
(Time range: --min--s)
0.0 … 999.9
(Time range: ---,-min)
0 … 9999
(Time range: ----min)
0:00 … 99:59
(Time range: --h--min)
0.0 … 999.9
(Time range: ---,-h)
0 … 9999 (Time range:
----h)
0.000 … 9.999
(Time range: -,---s)
0.00
0.0
0:00
0.0
0
0:00
0.0
0
0.000
Same as cycle time aboveSame
as left
0…1000
Same as cycle time aboveSame
as left
UnitSet
value
s
s
s
min; s
min
min
h; min
h
h
s
Same
as left
%
Same
as left
Function Setting Mode
Parameter nameParameter Setting rangeDafault
value
Time range
Timer mode
Output mode
Output time
Input signal width
Key protect level
timr--,--s/---,-s/----s/--min--s/
timmup downup--outma a-1 a-2 a-3 b b-1
otimhold 0.01 to 99.99holds
iflt20ms 1ms20ms--kyptkp-1 kp-2 kp-3
---,-min/----min/--h--min/
---,-h/----h/-,---s
d e f s
kp-4 kp-5 kp-6
kp-7
a---
kp-1---
UnitSet
value
---
Publication 700-UM002B-EN-D - June 2010
Appendix-4
Settings for Repeat Cycle Operation
Run Mode
Parameter name Parameter Setting rangeDafault
value
Present
value,
OFF set
time
Present
value,
ON set
time
OFF set
time
Present
value
ON set
time
Present
value
0.00 …99.99
(Time range: --,--s)
0.0 … 999.9
(Time range: ---,-s)
0 … 9999
(Time range: ----s)
0:00 … 99:59
(Time range: --min--s)
0.0 … 999.9
(Time range: ---,-min)
0 … 9999
(Time range: ----min)
0:00 … 99:59
(Time range: --h--min)
0.0 … 999.9
(Time range: ---,-h)
0 … 9999
(Time range: ----h)
0.000 … 9.999 (Time
range: -,---s)
Same as OFF set time
above
Same as OFF set time
above
Same as OFF set time
above
0.00
0.0
0
0:00
0.0
0
0:00
0.0
0
0.000
Same
as left
Same
as left
Same
as left
UnitSet
value
s
s
s
min; s
min
min
h; min
h
h
s
Same
as left
Same
as left
Same
as left
Publication 700-UM002B-EN-D - June 2010
Function Setting Mode
Parameter nameParameter Setting rangeDafault
value
OFF time range
ON time range
Timer mode
ON/OFF start mode
Input signal width
Key protect level
oftr
ontr
timm
totm
iflt
kypt
--,--s/---,-s/----s/--min--s/
---,-min/----min/--h--min/
---,-h/----h/-,---s
--,--s/---,-s/----s/--min--s/
---,-min/----min/--h--min/
---,-h/----h/-,---s
up
/down
toff
/ton,/toff-1/
ton,-1
/1ms
20ms
/kp-2/kp-3/kp-4
kp-1
kp-5
/ kp-6/ kp-7
--,--s---
--,--s---
up--toff---
20ms--kp-1---
UnitSet
value
Appendix-5
Publication 700-UM002B-EN-D - June 2010
Allen-Bradley is a registered trademark of Rockwell Automation