Read this document and the documents listed in the additional resources section about installation, configuration, and
operation of this equipment before you install, configure, operate, or maintain this product. Users are required to
familiarize themselves with installation and wiring instructions in addition to requirements of all applicable codes, laws,
and standards.
Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required
to be carried out by suitably trained personnel in accordance with applicable code of practice.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be
impaired.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the
use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and
requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or
liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or
software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation,
Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.
ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.
Identifies information that is critical for successful application and understanding of the product.
Labels may also be on or inside the equipment to provide specific precautions.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.
ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).
Allen-Bradley, Rockwell Software, Rockwell Automation, PanelView, FactoryTalk, RSLinx, CompactLogi x, ControlLogix, SLC, MicroLogix, PLC -5, and RSView are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Summary of Changes
This manual contains new and updated information. Changes throughout this
revision are marked by change bars, as shown to the right of this paragraph.
New and Updated
Information
This table contains the changes made to this revision.
Top icPag e
FactoryTalk® ViewPoint software is now supported.11, 75, 91
Added information for the 1000 terminal to Chapter 1, Overview.11
Added information for the 1000 terminal to Chapter 2, Install the Terminal.17
Updated the hazardous locations information.18
Added information for the 1000 terminal to Chapter 5, Install and Replace
Components.
Added information for the 1000 terminal to Chapter 6, Connections and
Communication.
Added information for the 1000 terminal to Chapter 7, Firmware Upgrades.135
Added information for the 1000 terminal to Chapter 8, Troubleshooting.143
107
125
Rockwell Automation Publication 2711PC-UM002B-EN-P - April 20143
Summary of Changes
Notes:
4Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014
Rockwell Automation Publication 2711PC-UM002B-EN-P - April 20147
Table of Contents
Notes:
8Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014
Preface
This manual describes how to install, configure, operate, and troubleshoot the
PanelView™ Plus 6 Compact terminals. It does not provide procedures on how to
create applications that run on the terminal.
You also need to do the following:
• Use FactoryTalk® View Studio for Machine Edition to create a
human-machine interface (HMI) application to run in the terminal.
• Create ladder logic to interact with the HMI application.
Additional Resources
These documents contain additional information concerning related products
from Rockwell Automation.
ResourceDescription
PanelView Plus Specifications Technical Data, publication
2711P-TD005
Industrial Automation Wiring and Grounding Guidelines,
publication 1770-4.1
Product Certifications website, http://www.ab.comProvides declarations of conformity, certificates, and
Provides technical specifications, environmental
specifications, and certifications for the
PanelView Plus Compact terminals.
Provides general guidelines for installing a Rockwell
Automation® industrial system.
other certification details.
You can view or download publications at
http://www.rockwellautomation.com/literature/
. To order paper copies of
technical documentation, contact your local Allen-Bradley distributor or
Rockwell Automation sales representative.
This product ships with these items:
• Terminal with FactoryTalk View Machine Edition runtime software
installed and activated
• Product information
• Mounting levers for panel installation
• Panel cutout template
Firmware Upgrades
For the latest firmware upgrades and other downloads for PanelView Plus 6
Compact terminals, go to http://www.rockwellautomation.com/support
and
click Firmware Updates.
Rockwell Automation Publication 2711PC-UM002B-EN-P - April 20149
Preface
Notes:
10Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014
Overview
TIP
Top icPa ge
Software Support12
PanelView Plus 6 Compact Applications12
Product Selections12
Ter mi na l Fe atu re s1 3
Operator Input14
Open versus Closed System15
Start-up Options15
Desktop Access15
Product Acc essories16
Chapter 1
PanelView Plus 6 Compact terminals (400/600/1000) are similar to the
PanelView Plus 6 (400/600) terminals but with limited hardware and software
functions. Major differences of the PanelView Plus 6 Compact terminals include
the following items:
• Serial and Ethernet communication only
• Connection to a single logic controller by using either RSLinx® Enterprise
or KEPServer Enterprise software, not both
• Limited number of displays and alarms in FactoryTalk View Machine
Edition (ME) application and runtime software
• Primary HMI for CompactLogix™ controllers
Applications created for PanelView Plus 6 Compact terminals are
referred to as Compact Machine Edition applications. They run on
PanelView Plus 6 and PanelView Plus 6 Compact terminals. You cannot
run a Machine Edition application created for a PanelView Plus 6
terminal on a PanelView Plus 6 Compact terminal.
Rockwell Automation Publication 2711PC-UM002B-EN-P - April 201411
Chapter 1Overview
Software Support
PanelView Plus 6 Compact
Applications
Ta b l e 1 lists software supported by the terminals.
Table 1 - PanelView Plus 6 Compact Software Support
SoftwareDescriptionVersion
FactoryTalk View Machine
Edition Station
FactoryTalk View Studio for
Machine Edition
Windows CE 6.0
operating system
(1) Refer to Display FactoryTalk View ME Station Information on page 66 for a list of ActiveX controls loaded on a terminal.
Runtime environment for FactoryTalk View Machine Edition .mer
applications. Machine Edition Station is preloaded on each terminal
and does not require FactoryTalk View activation.
Configuration software for developing HMI applications that run on
PanelView Plus 6 Compact terminals.
RSLinx Enterprise software is included with FactoryTalk View Studio
software and loaded during installation.
All terminals run the Windows CE 6.0 operating system with an open
or closed desktop environment. Other supported features include
these items:
• FTP server
• VNC client/server
• ActiveX control s
• Third-party device support
• Adobe PDF reader
(1)
6.10 or later
6.10 or later
6.0
PanelView Plus 6 Compact Machine Edition applications are restricted to a
subset of the functions on the PanelView Plus 6 terminals:
• Maximum of 25 screens.
• Maximum of 200 alarm messages.
• One connection or shortcut to a single controller by using either RSLinx
Enterprise or KEPServer Enterprise software.
• Only Serial and Ethernet communication are supported.
Product Selections
If using RSLinx Enterprise software, only serial DF1, serial DH-485, and
Ethernet drivers are supported.
Ta b l e 2 lists the catalog numbers of the PanelView Plus 6 Compact terminals.
Table 2 - PanelView Plus 6 Compact Terminals
Cat. Nos.
2711PC-K4M20D8
2711PC-B4C20D8
2711PC-B4C20D8-LR••••
2711PC-T6M20D8
2711PC-T6C20D8Color••••
2711PC-T10C4D810.4 in. ColorTouch••••
Display
SizeTypeEthernet RS-232 Host Device
Grayscale Keypad••••
3.5-in.
ColorKeypad and Touch
Grayscale
5.7-in.
Input Type
Tou c h
Communication
Port s
••••
••••
USB Ports
Power
DC
12Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014
OverviewChapter 1
8
9
10
12
11
5
7
6
3
2
4
1
1
1
Terminal Features
The PanelView Plus 6 Compact 400, 600, and 1000 terminals are fixed
configurations that do not support modular components.
Table 3 - PanelView Plus 6 Compact Terminal Components
ItemComponent
3.5, 5.7, or 10.4-in. grayscale or color display with one of these operator input
1
2Secure Digital (SD) card slot for external storage
3
4Mounting slots (four)
5Ethernet port for controller communication, 10/100Base-T, Auto MDI/MDI-X
6RS-232 serial port for controller communication, printing, or file transfers
7
8One USB 2.0 high-speed (type B) device port for connecting a host computer
9Reset switch to reset the terminal without having to power off and on
10Default switch to access maintenance operations such as restoring factory defaults
11Battery compartment
12Indicators provide communication and fault status
options:
• Keypad
• Tou ch scr een
• Combination keypad and touch screen
DC power input, non-isolated
24V DC nom (18…30V DC)
One USB 2.0 high-speed (type A) host port for attaching USB peripherals including
mouse, keyboard, printer, and USB drives that are hot-swappable in nonhazardous
locations
Rockwell Automation Publication 2711PC-UM002B-EN-P - April 201413
Chapter 1Overview
1
2
3
4
5
1
2
Operator Input
The terminals feature grayscale or color LCD displays with keypad, touch screen,
or keypad and touch-screen input.
Table 4 - Display and Operator Input Features
Item FeatureDescription
1Product labelProduct identification label can be replaced with custom label.
2Display/touch screen
3Numeric keypad0…9, Backspace, Enter, Left and Right Tab, Esc, Shift, Ctrl, Alt keys
4Navigation keys
Function keys
5
F1…F8
Color or grayscale display with or without a resistive, 4-wire, touch screen (catalog
number dependent)
Use arrow keys for navigation. Use Alt+arrow to initiate these functions:
Keys that can be configured in the application to per form operations. For example,
F1 can be configured to navigate to another screen.
ATT EN TI ON : Use a finger or gloved-finger to operate the keypad. To operate
the touch screen, use a finger, gloved-finger, or plastic stylus with a minimum
tip radius of 1.3 mm (0.051 in.). If you use any other object or tool you can
damage the keypad or touch screen.
ATT EN TI ON : Do not carry out multiple operations simultaneously. Doing so can
result in unintended operation:
• Touch only one operating element on the screen with one finger at one time.
• Press only one key on the terminal at one time.
14Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014
OverviewChapter 1
TIP
Open versus Closed System
Start-up Options
The terminals can be configured to run an open or closed desktop environment:
• An open system launches the Windows Explorer desktop on startup. The
system is configurable via the control panel and supports Windows
operations.
• A closed system launches a FactoryTalk View Machine Edition application
on startup and restricts access to the Windows Explorer desktop.
All terminals are shipped as closed systems restricting access to the desktop. The
first time you start the system, the terminal launches FactoryTalk View ME
Station Configuration mode. At this point, you can change the start-up option to
allow desktop access.
You can configure the terminal to perform one of three actions at startup:
• Launch a FactoryTalk View Machine Edition HMI application.
• Launch the FactoryTalk View Machine Edition Configuration mode of
the terminal where you load and run applications, configure start-up
options and terminal settings, and enable or disable desktop access.
• Launch the Windows Explorer desktop.
The factory default state and start-up option following a firmware upgrade is to
launch the terminal in Configuration mode. Refer to Start-up Options on
page 39 for details on how to change the start-up option.
Desktop Access
Any of the terminals can be configured to allow or restrict desktop access. From
the desktop, you can perform system and control panel operations, or run
third-party applications. You can also enable temporary access to perform specific
tasks, then disable access to prevent unauthorized changes.
All terminals are initially shipped with desktop access disabled.
Refer toDesktop Access on page 42
for details on how to modify desktop access.
Rockwell Automation Publication 2711PC-UM002B-EN-P - April 201415
Chapter 1Overview
Product Accessories
Ta b l e 5 through Ta b l e 1 0 lists accessories for the terminals.
Table 5 - Secure Digital (SD) Cards
Cat. No. Terminal ModelDescription
1784-SD1
1784-SD22 GB SD card
2711C-RCSDUSB to SD adapter for SD card
All terminals
Table 6 - Cables
Cat. No. Terminal ModelDescriptionLength
6189V-USBCBL2400 or 600
2711C-CBL-UU021000
Table 7 - Power Supply and Power Terminal Blocks
Cat. No. Terminal ModelDescriptionQuantity
2711P-RSACDIN
2711P-6RSA
2711-TBDCDC power terminal block10
2711P-RTBAC3
2711P-RTBDC2DC power terminal block10
400 and 600
1000
1 GB SD card
Programming cable that connects the
USB device port of the terminal to a
USB host port of a computer
Programming cable that connects the
USB device port of the terminal to a
USB host port of a computer
DIN-rail power supply, AC-to-DC,
85…265V AC, 47…63 Hz
(1) Three overlays are shipped with each catalog number.
Ter mina l Mo del
KeypadTouchKey/Touch
Operator Input
Table 10 - Mounting Hardware
Cat. No. Terminal ModelDescriptionQuantity
2711P-RTFC400 and 600Replacement mounting levers8
2711P-RTMC1000Replacement mounting clips8
16Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014
Install the Terminal
Top icPa ge
Required Circuit Parameters for USB Peripheral Devices19
Mounting Clearances20
Panel Guidelines20
Panel Cutout Dimensions20
Product Dimensions21
Mount the 400/600 Terminal in a Panel22
Mount the 1000 Terminal in a Panel24
Remove and Install the Power Terminal Block26
DC Power Connections28
Initial Startup31
Reset Terminal31
Chapter 2
ATTENTION: Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as
defined in IEC 60664-1), at altitudes up to 2000 m (6561 ft) without derating.
The terminals are intended for use with programmable logic controllers. Terminals that are AC powered must be connected to
the secondary of an isolating transformer.
This equipment is considered Group 1, Class A industrial equipment according to IEC CISPR 11. Without appropriate
precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to
conducted or radiated disturbances.
Korean Radio Wave Suitability Registration - When so marked this equipment is registered for Electromagnetic Conformity
Registration as business equipment (A), not home equipment. Sellers or users are required to take caution in this regard.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for
those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting
from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. The terminals meet
specified NEMA, UL type, and IEC ratings only when mounted in a panel or enclosure with the equivalent rating. Subsequent
sections of this publication may contain additional information regarding specific enclosure type ratings that are required to
comply with certain product safety certifications.
In addition to this publication, see the following:
• Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1
, for additional installation requirements
• NEMA 250 and IEC 60529, as applicable, for explanations of the degrees of protection provided by different
types of enclosure
Rockwell Automation Publication 2711PC-UM002B-EN-P - April 201417
Chapter 2Install the Terminal
ATTENTION: Wiring and Safety Guidelines
Use publication NFPA 70E, Electrical Safety Requirements for Employee Workplaces, IEC 60364 Electrical Installations in Buildings, or
other applicable wiring safety requirements for the country of installation when wiring the devices. In addition to the NFPA
guidelines, here are some other guidelines to follow:
• Connect the device and other similar electronic equipment to its own branch circuit.
• Protect the input power by a fuse or circuit breaker rated at no more than 15 A.
• Route incoming power to the device by a separate path from the communication lines.
• Cross power and communication lines at right angles if they must cross.
• Communication lines can be installed in the same conduit as low-level DC I/O lines (less than 10V).
• Shield and ground cables appropriately to avoid electromagnetic interference (EMI). Grounding minimizes noise from EMI and is a safety
measure in electrical installations.
For more information on grounding recommendations, refer to the National Electrical Code published by the National Fire Protection
Association.
Hazardous Locations
North American Hazardous Location Approval
The following information applies when operating this equipment in
hazardous locations.
When marked, these products are suitable for use in Class I,
Division 2, Groups A, B, C and D; Class II, Division 2, Groups F and
G; Class III hazardous locations and nonhazardous locations only.
Each product is supplied with markings on the rating nameplate
indicating the hazardous location temperature code. When
combining products within a system, the most adverse
temperature code (lowest "T" number) may be used to help
determine the overall temperature code of the system.
Combinations of equipment in your system are subject to
investigation by the local Authority Having Jurisdiction at the
time of installation.
WARNI NG: EXPLOSION HAZARD
• Do not disconnect equipment unless power has been
removed or the area is known to be nonhazardous.
• Do not disconnect connections to this equipment unless
power has been removed or the area is known to be
nonhazardous.
• Substitution of components may impair suitability for
Class I, Division 2.
• Peripheral equipment must be suitable for the location in
which it is used.
• The battery or real-time clock module in this product must
only be changed in an area known to be nonhazardous.
• All wiring must be in accordance with Class I, Division 2,
Class II, Division 2, or Class III wiring methods of Articles
501, 502 or 503, as appropriate, of the National Electrical
Code and/or in accordance with Section 18-1J2 of the
Canadian Electrical Code, and in accordance with the
authority having jurisdiction.
• When used in Class II and Class III hazardous locations
these products must be installed in a dust tight enclosure
in accordance with Articles 502 and 503 of the National
Electrical Code.
Les informations suivantes s'appliquent pour les équipements utilisés dans des
environnements dangereux.
Les produits marqués "CL I, DIV 2, GP A, B, C, D" ne conviennent qu'à une
utilisation en environnements de Classe I, Division 2, Groupes A, B, C et D ;
Classe II, Division 2, Groupes F et G ; Classe III dangereux et non dangereux.
Chaque produit est livré avec des marquages sur sa plaque d'identification
qui indiquent le code de température pour les environnements dangereux.
Lorsque plusieurs produits sont combinés dans un système, le code de
température le plus défavorable (code de température le plus faible) peut
être utilisé pour déterminer le code de température global du système. Les
combinaisons d'équipements dans le système sont sujettes à inspection
par les autorités locales qualifiées au moment de l'installation.
AVERTISSEMENT : RISQUE D’EXPLOSION
• Couper le courant ou s'assurer que l'environnement est classé non
dangereux avant de débrancher l'équipement.
• Couper le courant ou s'assurer que l'environnement est classé non
dangereux avant de débrancher les connecteurs.
• La substitution de composants peut rendre cet équipement inadapté à
une utilisation en environnement de Classe I, Division 2
• Les équipements périphériques doivent s'adapter à l'environnement
dans lequel ils sont utilisés.
• La batterie ou le module de l'horloge en temps réel de ce produit doit
être changé(e) uniquement dans un environnement classé sans risque.
• Tous les systèmes de câblage doivent être de Classe I, Division 2, Classe
II, Division 2, ou Classe III conformément aux méthodes de câblage
indiquées dans les Articles 501, 502 ou 503 du National Electrical Code
(Code Electrique National) et/ou conformément à la Section 18-1J2 du
Canadian Electrical Code (Code Electrique Canadien), et en fonction de
l'autorité de jurisdiction.
• Quand ces produits sont utilisés dans des environnements dangereux
de Classe II et Classe III, ils doivent être installés dans une enceinte
étanche aux poussières conformément aux Articles 502 et 503 du Code
Electrique National (National Electrical Code).
The terminals have a temperature code of T4 when operating in a 55 °C (131 °F) maximum ambient temperature. Do not
install product in environments where atmospheric gases have ignition temperatures less than 135 °C (275 °F).
18Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014
Install the TerminalChapter 2
Nonincendive
Field- wiring Apparatus
Associated Nonincendive Field-wiring Apparatus
PanelView Plus 6 Compact Host Product
USB Peripheral Device
USB Host Port
Required Circuit Parameters for USB Peripheral Devices
This product contains a USB host port that complies with hazardous location environments. Field-wiring compliance
requirements are provided in compliance with the National Electrical Code, Article 500.
Figure 1 - PanelView Plus 6 Compact Terminals Control Drawing
PanelView Plus 6 Compact terminals provide one separately powered USB host port. Ta b l e 1 1 defines the circuit
parameters of the USB host port.
Table 11 - Circuit Parameters for USB Host Ports
ParameterValueParameter Definition
V
oc (USB)
I
sc (USB)
C
a (USB)
L
a (USB)
5.25V DCOpen circuit voltage of the host USB port.
The maximum applied voltage rating, V
or equal to V
1.68 AMaximum output current of the host USB port.
The maximum current, I
than or equal to I
10 μFThis value is the maximum total capacitance that can be connected to the USB host port. The total
capacitance of the USB peripheral device and its associated cable must not exceed the indicated value.
The maximum total capacitance, C
device must be less that or equal to C
15 μHThis value is the maximum total inductance that can be connected to the USB host port. The total
inductance of the USB peripheral device and its associated cable must not exceed the indicated value.
The maximum total inductance, L
must be less than or equal to L
oc (USB)
.
max (peripheral)
sc (USB).
max (peripheral)
, that each USB peripheral device can be subjected must be greater
i (peripheral)
a (USB)
i (peripheral)
.
a (USB)
, of each USB peripheral device must be greater than
, and cable capacitance of each separate USB peripheral
.
, and cable inductance of the separate USB peripheral device
V
max (peripheral)
as appropriate
I
max (peripheral)
C
i (peripheral)
L
i (peripheral)
+ C
+ L
≥ V
oc (USB)
≥I
sc (USB)
cable(USB)
cable
≤ L
,
≤ C
a (USB)
a (USB)
Application Information
Per the National Electrical Code, the circuit parameters of associated field-wiring apparatus for use in hazardous locations
must be coordinated with the host product such that their combination remains nonincendive. PanelView Plus 6 Compact
terminals and the USB peripheral devices must be treated in this manner.
The USB peripheral devices and their associated cabling must have circuit parameters with the limits given in Ta b l e 1 1
them to remain nonincendive when used with the PanelView Plus 6 Compact USB host port.
If cable capacitance and inductance are not known, use the following values from ANSI/ISA-RP 12.06.01-2003:
C
= 197 pF/m (60 pF/ft)
cable
L
= 0.7 μH/m (0.20 μH/ft)
cable
Nonincendive field-wiring must be wired and separated in accordance with 501.10(B)(3) of the National Electrical Code
(NEC) ANSI/NFPA 70 or other local codes as applicable. This associated nonincendive field-wiring apparatus has not
been evaluated for use in combination with another associated nonincendive field-wiring apparatus.
Rockwell Automation Publication 2711PC-UM002B-EN-P - April 201419
for
Chapter 2Install the Terminal
Mounting Clearances
Panel Guidelines
Plan for adequate space around the terminal, inside the enclosure, for ventilation
and cabling. Consider heat produced by other devices in the enclosure. The
ambient temperature around the terminal must be 0…55 °C (32…131 °F).
Table 12 - Minimum Required Clearances
Product AreaMinimum Clearance
Top 51 mm (2 in.)
Bottom102 mm (4 in.)
Side25 mm (1 in.)
Back0 mm (0 in.)
(1) A clearance of 102 mm (4 in.) is sufficient on the side of the terminal to insert and remove an SD card, and on the bottom of
the terminal for connections.
(1)
(1)
The terminals are panel-mounted devices intended to mount in the door or wall
of a NEMA rated, UL Type rated, or IP rated enclosure:
• Supporting panels must have a mounting thickness of 1.5…4.8 mm
(0.060…0.188 in.).
• The material strength and stiffness of the panel must be sufficient to hold
the terminal and maintain an appropriate seal against water and dust.
• The panel surface must be flat and free of imperfections to maintain an
adequate seal and NEMA and UL Type ratings.
Panel Cutout Dimensions
Use the full-size template shipped with your product to mark the cutout
dimensions.
Table 13 - Panel Cutout Dimensions
Terminal TypeInput TypeHeight, mm (in.)Width, mm (in.)
400 Keypad or keypad/touch123 (4.86)156 (6.15)
600Touch123 (4.86)156 (6.15)
1000Touch224 (8.8)305 (12.00)
20Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014
Install the TerminalChapter 2
6
1
1
6
a
b
c
a
b
c
c
a
b
Product Dimensions
Figure 2 through Figure 4 provide product dimensions.
Figure 2 - PanelView Plus 6 Compact - 400 Keypad or Keypad/Touch
400Keypad or keypad/touch152 (6.0)185 (7.28)60 (2.35)
600Touch152 (6.0)185 (7.28)68 (2.68)
1000Touch248 (9.77)329 (12.97)83 (3.27)
Depth (c)
mm (in.)
Rockwell Automation Publication 2711PC-UM002B-EN-P - April 201421
Chapter 2Install the Terminal
6
1
1
2
3
4
5
6
Notch
Alignment Marks
Orientation of Slot Varies
FAULT
COMM
FAULT
Gasket
Mount the 400/600 Terminal
in a Panel
The terminals are designed for single-person installation. No tools are required
except for those needed to make the panel cutout.
Four mounting levers secure the terminal to the panel. The levers insert into the
mounting slots on the top and bottom of the terminal.
Each mounting slot has six notches with alignment marks that are locking
positions for a lever. The thickness of the panel where you mount the terminal
determines the locking position required to maintain the NEMA/UL Type seal.
Table 15 - Lever Locking Positions
Mounting Slot
Lever Lock
Position
1
2
3
4
5
6
Panel T hickness R ange
1.50…2.01 mm (0.060…0.079 in.)16
2.03…2.64 mm (0.080…0.104 in.)14
2.67…3.15 mm (0.105…0.124 in.)12
3.17…3.66 mm (0.125…0.144 in.)10
3.68…4.16 mm (0.145…0.164 in.)8/9
4.19…4.80 mm (0.165…0.188 in.)7
Typic al
Gauge
Follows these steps to mount the terminal in a panel.
ATT EN TI ON : Disconnect all electrical power from the panel before making the
panel cutout.
Make sure the area around the panel cutout is clear and that the panel is clean of
any debris, oil, or other chemicals.
Make sure metal cuttings do not enter any components already installed in the
panel and that the edges of the cutout have no burrs or sharp edges.
Failure to follow these warnings can result in personal injury or damage to panel
components.
1. Cut an opening in the panel by using the cutout template shipped with the
terminal or the cutout dimensions on page 20
2. Verify the sealing gasket is present on the terminal.
This gasket forms a compression-type seal. Do not use sealing compounds.
22Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014
.
Install the TerminalChapter 2
6
1
6
1
Flat Side of Lever
Mounting Slots
Mounting Levers
TIP
Notch
Rotate lever until notch in lever aligns with
proper alignment mark on terminal.
Alignment Marks
6
1
1
3
4
2
3. Place the terminal in the panel cutout.
4. Insert all mounting levers into the mounting slots on the terminal.
Slide each lever until the flat side of the lever touches the panel surface.
5. When all levers are in place, slide each lever an additional notch or two
until you hear a click.
Refer to Table 15 on page 22
as a guide to determine the locking positions
for your panel thickness.
6. Rotate each lever in the direction indicated until it is in the final position.
Levers rotate in same direction on top and bottom of terminal.
Follow the appropriate locking sequence for the optimal terminal fit.
FAULT
FAULT
COMM
DEFAULT
RESET
7. Inspect all levers to verify that they are in the correct and same locked
position.
ATTENTION: All levers must be locked to provide an adequate gasket
seal between the terminal and the panel. Rockwell Automation
assumes no responsibility for water or chemical damage to the terminal
or other equipment within the enclosure because of improper
installation.
Rockwell Automation Publication 2711PC-UM002B-EN-P - April 201423
Chapter 2Install the Terminal
Sealing Gasket
Mount the 1000 Terminal in a
Panel
Four mounting clips secure the 1000 terminal in a panel. Tools required for
installation include panel cutout tools, a small, slotted screwdriver, and a torque
wrench for tightening the mounting clips.
ATT EN TI ON : Disconnect all electrical power from the panel before making the
panel cutout.
Make sure the area around the panel cutout is clear and that the panel is clean of
any debris, oil, or other chemicals.
Make sure metal cuttings do not enter any components already installed in the
panel and that the edges of the cutout have no burrs or sharp edges.
Failure to follow these warnings can result in personal injury or damage to panel
components.
Follow these steps to mount the terminal in a panel.
1. Cut an opening in the panel by using the panel cutout template shipped
with the terminal or the cutout dimensions on page 20
2. Verify the terminal sealing gasket is properly positioned on the terminal.
This gasket forms a compression type seal. Do not use sealing compounds.
.
Be careful not to pinch the legend strip during installation.
24Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014
Install the TerminalChapter 2
Mounting Clip Slot
Mounting Clip
Tor que Se que nce
4 Clips
23
14
3. Place the terminal in the panel cutout.
4. Slide the ends of the mounting clips into the slots on the terminal.
5. Tighten the mounting clip screws by hand until the gasket seal contacts the
mounting surface uniformly.
6. Tighten the mounting clips screws to a torque of 0.90…1.1 N•m
(8…10 lb•in) by using the specified sequence, making sure not to
overtighten.
ATT EN TI ON : Tighten the mounting clips to the specified torque to provide a
proper seal and to prevent damage to the product. Rockwell Automation
assumes no responsibility for water or chemical damage to the product or other
equipment within the enclosure because of improper installation.
Rockwell Automation Publication 2711PC-UM002B-EN-P - April 201425
Chapter 2Install the Terminal
Remove and Install the
Power Terminal Block
The terminals are shipped with a power terminal block installed. You can remove
the terminal block for ease of installation, wiring, and maintenance.
WARNING: Explosion Hazard
If you connect or disconnect wiring while the power is on, an electrical arc can
occur. This could cause an explosion in hazardous location installations. Be sure
that power is removed and the area is nonhazardous before proceeding.
Failure to remove power can result in electrical shock or damage to the terminal.
The power terminal block is not intended for daisy chaining power.
Use a 0.6 x 3.5 mm flat-blade screwdriver for terminal block wiring.
Table 16 - Wire Specifications for Power Input Terminal Block
TerminalWire TypeDual-wire Size
400, 600
1000
(1) Two-wire max per terminal.
Stranded or solid
Cu 90 °C (194 °F)
0.3…1.3 mm
22…16 AWG
(1)
Single-wire SizeStrip LengthScrew Torque
2
0.3…2.1 mm
(22…14 AWG)
2
7 mm (0.28 in.)
0.45…0.56 N•m
(4…5 lb•in)
0.56 …0.90 N•m
(5…8 lb•in)
400 and 600 Terminals
Follow these steps to remove the terminal block.
1. Insert the tip of a small, flat-blade screwdriver into the terminal block
access slot.
2. Gently pry the terminal block to rotate it away from the terminal; this
releases the locking mechanism.
Follow these steps to install the terminal block.
1. Press the terminal block base in first with the block leaning outward.
26Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014
Install the TerminalChapter 2
Three-position
AC Terminal Block
Two -p os it io n
DC Terminal Block
2. Gently push the top of the terminal block to rotate it into place.
The terminal block snaps into place when seated.
1000 Terminals
Follow these steps to remove the terminal block from a 1000 terminal.
1. Loosen the two screws that secure the terminal block.
2. Gently pull the terminal block away from the connector.
Follow these steps to install the terminal block.
1. Reattach the terminal block to the connector until seated.
2. Tighten the two screws that secure the terminal block to a torque of
0.40…0.51 N•m (3.5…4.5 lb•in).
Rockwell Automation Publication 2711PC-UM002B-EN-P - April 201427
Chapter 2Install the Terminal
IMPORTANT
DC Power Connections
Terminals with an integrated 24V DC power supply have these power ratings.
Table 17 - DC Power Ratings
TerminalPower SupplyInput Voltage, nomPower Consumption, max
400, 600 Nonisolated24V DC (18…30V DC)15 W (0.6 A at 24V DC)
1000Isolated24V DC (18…32V DC)70 W (2.9 A at 24V DC)
The power supply is internally protected against reverse polarity. Connecting
DC+ or DC- to the earth/ground terminal can damage the device.
ATT EN TI ON : Do not connect an AC power source to the terminal. Applying an
AC power source to the terminal can damage the device.
External Power Supply
Use a dedicated 24V DC, safety extra-low voltage (SELV) or protective
extra-low voltage (PELV) power supply to power each PanelView Plus 6
Compact device.
ATT EN TI ON : Use a Class 2 SELV or PELV power supply as required by local wiring
codes for your installation. These power supplies provide protection so that
under normal and single fault conditions, the voltage between conductors and
earth ground does not exceed a safe value.
PanelView Plus 6 Compact terminals were tested to operate with the catalog
number 2711P-RSACDIN power supply. To use another power supply, review
the criteria in Ta b l e 1 8
Table 18 - Power Supply Criteria
If the PanelView Plus 6 DeviceUse aDescription
Connects to equipment with isolated
communication ports
Does not connect to other equipment
Connects to equipment with
nonisolated communication ports
.
SELV or PELV power supplyOther equipment can share this power
Dedicated, isolated, and
ungrounded SELV source to
power each terminal
supply with the PanelView Plus 6 device
provided that no ground loops are created.
A PELV source internally connec ts the
negative power terminal to chassis ground.
This prevents ground loops from damaging
the device.
All ports on the terminals are electrically isolated, except for the USB ports.
28Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014
Install the TerminalChapter 2
IMPORTANT
Earth/Ground Connection
PanelView Plus 6 compact terminals use a DC power input and have an earth/
ground terminal that you must connect to a low-impedance earth/ground:
• On 400 and 600 terminals, the earth/ground connection is on the power
terminal block.
• On 1000 terminals, the earth/ground connection is on the rear of the
display module.
The earth/ground connection to ground is mandatory. This connection is
required for the following:
• Noise immunity, reliability, and Electromagnetic Compliance (EMC) with
the European Union (EU) EMC directive for CE-mark conformance
ATT EN TI ON : Damage or malfunction can occur when a voltage potential exists
between two separate ground points. Make sure the terminal does not serve as
a conductive path between ground points at different potentials.
Rockwell Automation Publication 2711PC-UM002B-EN-P - April 201429
Chapter 2Install the Terminal
7 mm
20 mm
+
–
Earth/Ground to Ground Bus
DC -
DC+
GND
DC+
DC –
Functional Earth to Ground Bus
400 or 600 Terminal1000 Terminal
Connect DC Power
WARNING: Explosion Hazard
Do not disconnect equipment unless power has been switched off and area is
known to be nonhazardous.
Disconnect all power before installing or replacing components. Failure to
disconnect power can result in electrical shock or damage to the terminal.
Follow these steps to connect the terminal to DC power.
1. Verify that the terminal is not connected to a power source.
2. Strip 7 mm (0.28 in.) of insulation from the ends of the wires.
3. Secure the DC power wires to the marked terminals (+ and –) on the
power terminal block.
4. Secure the earth/ground wire:
• On 400 and 600 terminals, secure the earth/ground wire to the
functional earth/ground terminal on the power terminal block.
• On 1000 terminals, secure the earth/ground wire to the functional
earth screw on the back of the display.
5. Apply power to the terminal.
30Rockwell Automation Publication 2711PC-UM002B-EN-P - April 2014
Loading...
+ 132 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.