Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application,
Installation and Maintenance of Solid State Controls (Publication SGI-1.1
available from your local Rockwell Automation sales office or online at
http://literature.rockwellautomation.com) describes some important
differences between solid state equipment and hard-wired electromechanical
devices. Because of this difference, and also because of the wide variety of
uses for solid state equipment, all persons responsible for applying this
equipment must satisfy themselves that each intended application of this
equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for
indirect or consequential damages resulting from the use or application of
this equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with
any particular installation, Rockwell Automation, Inc. cannot assume
responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to
use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without
written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual we use notes to make you aware of safety
considerations.
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Identifies information about practices or circumstances
that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property
damage, or economic loss.
Identifies information that is critical for successful
application and understanding of the product.
Identifies information about practices or circumstances
that can lead to personal injury or death, property
damage, or economic loss. Attentions help you:
• identify a hazard
• avoid a hazard
• recognize the consequence
Labels may be located on or inside the equipment to alert people
that dangerous voltage may be present.
Labels may be located on or inside the equipment to alert people
that surfaces may be dangerous temperatures.
Allen-Bradley, FLEX Ex, ControlNet Ex, PLC, RSNetWorx, RSLogix5, and Logix5000 are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Summary of Changes
What’s Changed
The following table lists items changed since the last printing.
ChangesSee
Removed the word bit in Command 12B-2
Removed the word bit in Command 17B-2
Added Device-specific CommandsB-3 to B-24
To help you find new and updated information in this release of the manual,
we have included change bars as shown next to this paragraph.
This manual shows you how to use your FLEX Ex analog modules with the
ControlNet Ex products and ControlNet network. The manual helps you
install, program, and troubleshoot your module.
You must be able to program and operate a ControlNet Ex product and
ControlNet network to make efficient use of a FLEX Ex module.
In this manual, we refer to the:
• 1797-IE8H as the input module
• 1797-OE8H as the output module
The following chart lists each chapter with its corresponding title and a brief
overview of the topics covered in that chapter.
Describes module functionality and physical
Modules
Analog Module Features
features
Describes configurable module features and
configuration bits
3How to Install Your FLEX Ex Analog
Modules
4Input, Output and Configuration Files
for the Analog I/O Modules on the
ControlNet Network
5Calibrate Your ModuleLists the tools needed, and the methods used to
6Apply FLEX Ex Analog I/O ModulesDescribes how FLEX Ex is different from
7Troubleshoot the FLEX Ex Analog I/O
Modules
Appendix TitleContents
AOutlines module specifications and accuracy
BExplains how to program the analog modules
CAdditional HART Protocol Information Discusses the HART protocol and provides
How to install and wire the modules
Describes how to use these I/O modules over the
ControlNet network
calibrate the module
traditional control systems
How to use the indicators to troubleshoot your
module
references for additional information.
1Publication 1797-6.5.3 - January 2006
Preface 2
DConfigure the 1797-OE8H Module in
EConfigure the 1797-IE8H Module in
FFLEX Ex HART Modules Network
For Additional Information
1797 SeriesFLEX Ex Selection Guide1794-SG002
1797 SeriesControlNet Ex System Cable Guide1797-6.2.1
1797-TB3FLEX Ex Terminal Base
1797-TB3SFLEX Ex Spring Clamp Terminal Base
1797-OE8HFLEX Ex HART 8 Output Analog Module1797-5.31797-6.5.3
1797-IRT8FLEX Ex RTD/Thermocouple/mV Module1797-5.41797-6.5.2
1797-IE8HFLEX Ex HART 8 Input Analog Module1797-5.51797-6.5.3
1797-OB4D4 Output Module1797-5.6
1797-IBN16FLEX Ex NAMUR Digital Input Module1797-5.7
1797-PS2E2FLEX Ex Power Supply1797-5.8
1797-IJ22 Frequency Input Module1797-5.91797-6.5.4
1797-PS2N2FLEX Ex Power Supply1797-5.12
1797-BICFLEX Ex Bus Isolator
1797-CECFLEX Ex Flexbus Connector
1797-ACNR15ControlNet Ex Adapter1797-5.14
1797-RPA, -RPFMFiber Hub1797-5.15
1797-TPR, -TPRS,
-TPYR, -TPYS
1797-CE1S, -CE3S,
-CEFTN, -CEFTE
1797-EXMKMarker Kit1797-5.23
1797-PS1EFLEX Ex Power Supply1797-5.33
1797-PS1NFLEX Ex Power Supply1797-5.34
1797-BCNRFLEX Ex Redundant ControlNet Barrier Module1797-5.35
Provides the information necessary to configure
RSLogix 5000 Software Over the
the 1797-OE8H analog output module.
ControlNet Network
Provides the information necessary to configure
RSLogix 5000 Software Over the
the 1797-IE8H analog input module.
ControlNet Network
Discusses how to communicate with the HART
Messaging
modules via the MSG or CIO instruction,
differences between attributes and assembly
indexes, and enhancements to the HART frame.
For additional information on FLEX Ex systems and modules, refer to the
following documents.
Catalog
Number
FLEX Ex Taps
Interconnect Cables
Description
Installation
Instructions
1797-5.1
1797-5.13
1797-5.18
1797-5.20
Publications
User Manual
1797-6.2.1
Publication 1797-6.5.3 - January 2006
Chapter
About the FLEX Ex HART Analog Modules
1
What This Chapter Contains
What the FLEX Ex Analog
I/O Modules Do
Read this chapter to familiarize yourself with the input and output analog
modules.
ForSee
What the FLEX Ex Analog I/O
Modules Do
How FLEX Ex Analog Modules
Communicate with Programmable
Controllers
Physical Features of Your Analog I/O
Module
Chapter Summary1-15
The 1797-IE8H module accepts up to 8 analog inputs. The inputs are
non-isolated and will accept current in either of the following two ranges: 4 to
20 mA or 0 to 20mA. The default input range is 0 to 20 mA. The inputs have
both fixed hardware filters and selectable firmware digital filters.
Similarly, the 1797-OE8H module provides as many as eight analog outputs.
The outputs are nonisolated and will provide current in either of the following
two ranges: 4 to 20 mA or 0 to 20 mA. The default output range is 0 to 20 mA.
1-1
1-2
1-3
Each module offers host of features including:
• Local microprocessor intelligence for advanced features
• Full functionality without switches or jumpers
• Multiple data ranges that can be independently programmed
in channel groups
• Lead breakage detection
• Overrange/underrange alarms
• Remote transmitter alarm
1Publication 1797-6.5.3 - March 2006
1-2 About the FLEX Ex HART Analog Modules
How FLEX Ex Analog
Modules Communicate
with Programmable
Controllers
FLEX Ex analog I/O modules provide best utility when used with ControlNet
Ex products on the ControlNet network. Data connections are established
between the I/O module and an Allen-Bradley programmable controller to
transfer information between the two at a scheduled rate.
Input module information is then automatically made available in the PLC
data table through the data connection. Reciprocally, output data information
determined by the PLC program is also automatically transferred from the
PLC data table to the output module through the data connection.
In addition, when the data connection is originally established, configuration
information for the module is automatically transferred to it via the network.
Events After Cycling Power
You must apply intrinsically safe +/-V power to your FLEX Ex analog I/O
modules. The following sequence of events occurs after power has initially
been applied to your module:
• The module begins an internal diagnostic check. The channel 0 LED
indicator turns ON to indicate the check has begun. The indicator turns
OFF when the check is finished.
• After the diagnostic check, module configuration information, selected
by the user and downloaded over the network, is applied by the module.
For more information on configuration options, see Chapter 2.
• Following the module configuration download for the 1797-IE8H
module, the module begins producing runtime data for the PLC.
• Following the module configuration download for the 1797-OE8H
module, the module applies configuration data to output channels.
• If any diagnostics or alarms are generated during normal module
operation, the data is returned to the PLC controller.
Publication 1797-6.5.3 - March 2006
About the FLEX Ex HART Analog Modules 1-3
Physical Features of Your
Analog I/O Module
The module label identifies the keyswitch position, wiring and module type.
Use the removable label to note individual designations per your application.
Indicators
Indicators are provided to identify input or output fault conditions, and to
show when power is applied to the module. For example, the 1797-IE8H
module is shown below.
1797-IE8H
Module Type
Removable Label
Ex
8 CHANNEL ANALOG INPUT
IN1IN0IN2IN3IN4
Input Designators
IN5
1797-IE8
IN6IN7
PWR
Keyswitch Position
3
Indicator (#3)
Power On Indicator
40070
Using Alarms on the
1797-IE8H Module
The 1797-IE8H FLEX Ex module is capable of generating four alarms:
• Underrange
• Overrange
• Remote Fault
• Local Fault
These alarm conditions are described in general terms and as they relate to bits
on the FLEX Ex I/O module on the following pages. The following graphic
shows at what values these alarms are generated for Data Format 4.
Publication 1797-6.5.3 - March 2006
1-4 About the FLEX Ex HART Analog Modules
0 mA4 mA20 mA22 mA
Remote FaultRemote Fault
Data Format Alarm Example
In this example, the normal active data range is 4 to 20 mA. The alarms are
generated in three overlapping bands.
PHYSICAL INPUT SIGNAL RANGE
UnderrangeOverrange
Local
Fault
Local
Fault
-25.00%
-12.50%
Programmable
in 20 0.1 mA
Steps by Error
Level 0.1 mA
Steps
Parameter
0.00%
Remote Transmitter Error
Up/Down Parameter
Determines Which of These
is Active
100.00%112.50%
Programmable
in 20 0.1 mA
Steps by Error
Level 0.1 mA
Steps
Parameter
Overrange Alarm
The Overrange alarm notifies you when module input is overrange. When the
input signal exceeds 100% (20 mA), an Overrange Alarm is generated.
This alarm stays active at any value above 100% of range and is always enabled
by the module.
Underrange Alarm
41666
Publication 1797-6.5.3 - March 2006
The Underrange alarm works in a fashion converse to the overrange. This
feature notifies you when the input signal falls underrange. If the input signal
falls below 0% (4 mA), an Underrange Alarm is generated.
This alarm stays active at any value below 0% of range and is always enabled by
the module.
About the FLEX Ex HART Analog Modules 1-5
Remote Fault Alarm
The Remote Fault Alarm is primarily intended for use with remote transmitter
loops.
For example, the remote transmitter may be measuring temperature and
converting it to a standard mA signal. In such a loop, though, the input module
cannot determine the state of the loop on the far side of the transmitter.
However, the remote transmitter may be capable of diagnosing a problem in
the remote loop and signal the input module local loop with a preprogrammed
out of range (high or low) value.
The Remote Fault Alarm allows the 1797-IE8H module to work with
transmitters like the one just described. You must use the Remote Transmitter
Error Up or Down feature, see page 2-3, to configure your application for
Remote Fault notification.
For example, you must determine if you want a remote fault to cause
high out of range values or low out of range values to be returned to
the controller.
IMPORTANT
Once the alarm is issued, it remains active as long as the input
signal value remains above the programmed value.
Use Remote Fault Alarm to Determine High High or Low Low Alarm Levels
If you do not have a remote transmitter in your loop, this alarm can also be
used to program a high high or low low alarm level between the levels which
actuate the overrange or underrange alarms and the high or low local fault
alarms.
IMPORTANT
When establishing high high or low low alarms, you can only
select one side (high or low). You must use the Remote
Transmitter Error Up or Down feature in conjunction with this
alarm.
Publication 1797-6.5.3 - March 2006
1-6 About the FLEX Ex HART Analog Modules
Program the Remote Fault Alarm
For the Remote Fault alarm, you must program the threshold in 0.1 mA steps
at any level on the high or low end of input signal range. The Remote Fault
alarm activates if your I/O module receives input signal values of:
• 100.63% (20.1 mA) to 111.88% (21.9 mA) on the high end of input
signal range
or
• -0.63% (3.9 mA) to -11.88% (2.1 mA) on the low end of input
signal range
IMPORTANT
This alarm is only active for one band, either on the high side of
normal operation or the low side.The Remote Transmitter Error
Up/Down parameter determines which side is active. See page
2-3 for a description of the Remote Transmitter Error Up/Down
feature.
Local Fault Alarm
The Local Fault alarm notifies you when the loop to the transmitter or field
device, if no transmitter is used, is open or shorted.
IMPORTANT
• 112.50% (22 mA) or higher on the high end of input signal range - This
value indicates a short in the loop.
or
Once the alarm is issued, it remains active as long as the input
signal value remains in the programmed range.
Publication 1797-6.5.3 - March 2006
• -12.50% (2 mA) or lower on the low end of input signal range
- This value indicates an open wire condition in the loop.
The Remote Fault and Local Fault alarms are issued with the same bit whether
the cause is an under or overrange. Monitor the Overrange and Underrange
bits in your programming software to determine if the problem is a high
current or low current.
About the FLEX Ex HART Analog Modules 1-7
How to Use the
HART Capabilities
HART Implementation
Overview
Before using the HART capabilities, be sure that:
• the I/O module and the associated field device are working properly in
the analog 4 to 20 mA mode.
• the I/O module is configured for 4 to 20 mA range.
• the field device is HART capable.
• no more than one HART field device is connected to each channel.
• input filtering is set to a valid (defined) value.
The FLEX Ex HART modules act as intelligent HART multiplexers. Basically,
the module learns which HART devices are attached to its channels and then
routes HART messages, as appropriate, between the HART field devices and
the Flexbus. Since the HART modules act as intelligent HART multiplexers,
HART commands can be issued to the HART modules themselves.
Communication on the Flexbus occurs between the adapter and the HART
module. The adapter converts these messages to the appropriate network
format for communication with the controlling controller. The controlling
controller gets its command from the user program, storing the responses in
its memory.
Controller
User Program
Command
For Example,
ControlNet
Response
AdapterFLEX Ex HART
I/O Module
Flexbus4 to 20 mA
HART
Field Device
In its basic form, your ladder-logic program issues an MSG instruction
containing a HART command. The MSG instruction is routed to the
appropriate adapter and FLEX Ex I/O module. Upon receiving the message,
the HART module routes the message to the appropriate channel and gathers
the HART field device response. To retrieve this response, your ladder-logic
program issues another MSG instruction.
Publication 1797-6.5.3 - March 2006
1-8 About the FLEX Ex HART Analog Modules
HART Commands
Building a usable HART command for the MSG instruction involves an
understanding of how to create a standard HART command plus the
additional knowledge of how to pack the message into a ControlNet frame. To
simplify this process, you can download the ladder-logic program discussed
here at http://www.ab.com/io. This ladder-logic program consists of a main
program and several subroutines. Modify the main program to meet your
application needs.
The first routine is HART_initialize. Use this routine after a power cycle or
reset to enable HART functionality on a specific FLEX Ex HART module and
to rebuild the associated HART loops to its field device(s). Once a FLEX Ex
HART module is initialized, it remembers the HART addresses of the field
devices and associates them to their corresponding analog channel. This
routine calls the Get_Status_with_retry subroutine to poll an answer from the
target I/O module.
The second routine is Send_Hart_SF. This routine accepts a generic HART
message to a specific I/O channel and returns a generic HART response. This
routine calls the Get_Message_with_retry subroutine to poll a response from
the target I/O module.
The third routine is Purge. If a communication error is found, this routine is
called to empty the HART buffer in the FLEX Ex HART I/O module.
Use the remaining routines to execute specific HART commands. Each
routine is dedicated to its associated HART command. For example, the
HART_CMD_3 issues a HART command 3 to the specified target device.
To issue a HART command, after the FLEX Ex HART I/O module is
initialized, fill the tag HART_Target with the associated information to
uniquely describe the path to the target. If the HART command requires
information to be send to the target device, then fill a second tag with the
appropriate information.
For example, to send a HART command 3, fill the HART_Target tag. As this
is a HART read command, no other information is necessary. Tosend a
HART command 35, fill the HART_Target tag. As this is a HART write
command, also fill the CMD35_cmd tag with appropriate data.
Publication 1797-6.5.3 - March 2006
About the FLEX Ex HART Analog Modules 1-9
HART Target Tags
The HART_Target tag consists of four members:
• Path — HART_Target.Path
The Path specifies the direction the message follows to get to the
desired target node. The data type is string.
• Slot — HART_Target.Slot
The Slot indicates the specific place where the I/O module is attached
to the FLEX Ex adapter. The data type is SINT.
1 = the closest module to the adapter
8 = the module farthest from the adapter
0 = the adapter
• Channel
The Channel indicates which analog channel, 0 to 7, is desired. The data
type is SINT.
• Host_Group
The FLEX Ex HART modules have two message-access ports into
them allowing two systems to gather information from the module
concurrently. The data type is SINT.
The HART_Groups are numbered either 1 or 2. If there are no other
systems accessing the FLEX Ex Hart I/O module, that is, an asset
management system, then select the first HART_Group by setting this
value to 1.
IMPORTANT
If multiple owners access or control the same FLEX Ex HART I/O
module and field device, they must maintain identical
configurations.
Publication 1797-6.5.3 - March 2006
1-10 About the FLEX Ex HART Analog Modules
HART Command Tags
The response from the HART command routines is located in their associated
reply tags:
• CMDx_Status (x is the specific command)
Table 1.1 CMDx_Status Tags
Tag NameDescriptionData Type
CMDx_Status.StartedIndicates when the command is in
process
CMDx_Status.DoneIndicates when the command has
completed without error
CMDx_Status.ErrorIndicates when the command has
completed with error
CMDx_Status.Error_CodeIf the CMDx_Status.Error bit is set,
the associated error code is placed
here
CMDx_Status.Cmd_PerformedIf the CMDx_Status.Done bit is set,
the tag containing the HART
command performed is placed here
BOOL
INT
• CMDx_Reply (x is the specific command)
This tag is only returned when the specific HART command has data in
its reply. The CMDx_Reply tag contains the HART response
reformatted to their associated data type.
Table 1.2 CMD3_Reply Tags Example
Tag NameDescriptionData Type
CMD3_Reply.Current_mAThe measured current valueREAL
CMD3_Reply.PV_Units_CodeThe units code for the primary value INT
Publication 1797-6.5.3 - March 2006
CMD3_Reply.Primary_ValueThe primary valueREAL
CMD3_Reply.SV_Units_CodeThe units code for the secondary
value
CMD3_Reply.Secondary_ValueThe secondary valueREAL
CMD3_Reply.TV_Units_CodeThe units code for the third valueINT
CMD3_Reply.Third_ValueThe third valueREAL
CMD3_Reply.FV_Units_CodeThe units code for the fourth valueINT
CMD3_Reply.Fourth_ValueThe fourth valueREAL
INT
About the FLEX Ex HART Analog Modules 1-11
You r
Ladder-logic
Program
HART_Target
CMDx_cmd
Status
CMDx_reply
HART_CMD_x
Convert CMD
Data Type to
Generic HART
Frame
Convert Generic
HART Reply
Frame to Specific
Reply Data Type
Generic_HART
Command Frame
Generic_HART
Reply Frame
Status
Send_HART_SF
Send Message
to Target and
Poll for a
Response
HART Initialize Tags
The HART_Target tag consists of four members:
• Path — HART_Target.Path
The Path specifies the direction the message follows to get to the
desired target node. The data type is string.
• Slot — HART_Target.Slot
The Slot indicates the specific place where the I/O module is attached
to the FLEX Ex adapter. The data type is SINT.
1 = the closest module to the adapter
8 = the module farthest from the adapter
0 = the adapter
• Channel
The Channel indicates which analog channel, 0 to 7, is desired. The data
type is SINT.
Publication 1797-6.5.3 - March 2006
1-12 About the FLEX Ex HART Analog Modules
• Host_Group
The FLEX Ex HART modules have two message-access ports into
them allowing two systems to gather information from the module
concurrently.
The HART_Groups are numbered either 1 or 2. If there are no other
systems accessing the FLEX Ex Hart I/O module, that is, an asset
management system, then select the first HART_Group by setting this
value to 1. The data type is SINT.
IMPORTANT
If multiple owners access or control the same FLEX Ex HART I/O
module and field device, they must maintain identical
configurations.
HART Initialize Channel Tags
The channel member of the HART_Target tag is a decimal number that
indicates which channel is the target. The channels’ member of the
HART_initialize tag consists of eight one bit flags.
0 = Search for a HART Field Device on the
Ch 7 Ch 6 Ch 5 Ch 4 Ch 3 Ch 2 Ch 1 Ch 0
IMPORTANT
To make the HART_initialize routine run effectively, only enable
channels with active HART field devices.
Associated Channel
1 = Disables Searching for a HART Field
Device on the Associated Channel
Publication 1797-6.5.3 - March 2006
About the FLEX Ex HART Analog Modules 1-13
Table 1.3 HART_Init_Status Tags
Tag NameDescriptionData Type
HART_Init_Status.StartedIndicates when the command is in
process
HART_Init_Status.DoneIndicates when the command has
completed without error
HART_Init_Status.ErrorIndicates when the command has
completed with error
HART_Init_Status.Error_CodeIf the CMDx_Status.Error bit is set,
the associated error code is placed
here
HART_Init_Status.HART_Channels_
Found
If the CMDx_Status.Done bit is set,
the tag containing the list of
channels with active HART field
devices
BOOL
INT
When these tags are initialized, a JSR to the HART_initialize routine is
performed.
Modify Your Ladder-Logic Routine
With this background information, it is now time to modify the routine to
meet the needs of your application. To do so, perform the following steps:
1. Make sure your wiring is correct and make note of your node address,
the slot location of the FLEX Ex HART I/O module and the channel
with your field device.
2. Load the program into Logix5000 software.
3. Modify the members of the HART_initialize tag to match your setup.
4. Modify the members of the HART_Target tag to match your setup.
5. If you plan to use a HART write command, which requires data to be
sent to the field device, modify the associated CMDx_cmd tag with the
associated data.
6. Download the program to the ControlLogix controller.
Publication 1797-6.5.3 - March 2006
1-14 About the FLEX Ex HART Analog Modules
7. Place the controller into RUN mode.
This assumes you will re-write the Main Routine to meet your
application.
8. Refer to the following list of error codes if an error is returned from one
of the following routines:
Table 1.4 HART_Initialize Routine
Error CodeDescription
-1Could not enable HART LEDs
-2Could not rebuild HART loops
-3Routine timed out
-4Could not get status from Rebuild HART
Loops command
Table 1.5 HART_CMD_x Routine
Error CodeDescription
-1Invalid slot number
-2Invalid expected data size
-3Invalid Host Group number
-4Could not get a response
Once you have modified your ladder-logic routine, the ladder logic will now
call the HART_initialize routine. The yellow LEDs on the associated channels
of the selected FLEX Ex HART module will start to flash. This indicates that
the module has received the command and is in the process of searching for
HART field devices on the associated channels. Upon successful completion
of the HART_initialize routine, the HART_Init_Status_Done flag is set. At
this point, the ladder logic will examine the contents of the HART_Cmd tag
and attempt to issue the HART command associated with the decimal number
contained in this tag. Any HART replies are placed in their associated
CMDx_reply tag. To issue a different command, change the value of the
HART_Cmd tag to match the desired HART Command.
Publication 1797-6.5.3 - March 2006
About the FLEX Ex HART Analog Modules 1-15
Selecting the Correct Path
The Path is a string that specifies the direction the message follows to get to a
desired node. The MSG instruction requires a specific format for the string,
consisting of a number sequence with each number separated by a $ sign. The
message sequence is performed in sequential order from the perspective of the
controller.
EXAMPLE
A path of $01$03$02$05 is interpreted as:
$01 = Go out the backplane port of the 1756
controller
$03 = Go to the module in slot 3 of the 1756 chassis
(1)
$02 = Go out the front communications port of the
module
$05 = Go to node address 5
(1)
Assume that a 1756-CNB is in slot 3.
If you are using a ControlLogix system, the numbers $01 and the $02 will
usually be in these sequence locations. The $03 may vary depending on the slot
location of your network module. The $05 will vary according to your target
address. If you need to bridge to other networks, then additional numbers will
be needed in the sequence. For more details on this method, search in the
Logix5000 Help.
Chapter Summary
In this chapter, you learned about FLEX Ex analog I/O modules and HART
module capabilities. Move on to Chapter 2 to learn about configurable features
on your module.
Publication 1797-6.5.3 - March 2006
1-16 About the FLEX Ex HART Analog Modules
Notes:
Publication 1797-6.5.3 - March 2006
Loading...
+ 166 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.