Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local
Rockwell Automation sales office or online at http://www.ab.com/manuals/gi)
describes some important differences between solid state equipment and hard-wired
electromechanical devices. Because of this difference, and also because of the wide
variety of uses for solid state equipment, all persons responsible for applying this
equipment must satisfy themselves that each intended application of this equipment is
acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or
consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes.
Because of the many variables and requirements associated with any particular
installation, Rockwell Automation, Inc. cannot assume responsibility or liability for
actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of
information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written
permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual we may use notes to make you aware of safety considerations.
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Identifies information about practices or circumstances that can
cause an explosion in a hazardous environment, which may lead
to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application
and understanding of the product.
Identifies information about practices or circumstances that can
lead to personal injury or death, property damage, or economic
loss. Attentions help you:
• identify a hazard
• avoid a hazard
• recognize the consequence
Labels may be located on or inside the equipment to alert people
that dangerous voltage may be present.
Labels may be located on or inside the equipment to alert people
that surfaces may be dangerous temperatures.
Summary of Changes
The information below summarizes the changes to this manual since the last
printing.
To help you find new and updated information in this release of the manual,
we have included change bars as shown to the right of this paragraph.
The table below lists the sections that document new features and additional
or updated information about existing features.
For this informationSee
New Related PublicationsP-2
EMC Directive3-2
ATEX Directive3-2
Installation in Zone 13-3
Installation in Zone 223-3
1797-IE8 and -IE8NF SpecificationsA-1
1797-IE8 and -IE8NF UL, C-UL I/O Entity ParametersA-4
3How to Install Your Analog ModuleHow to install and wire the modules
4Input, Output and Configuration Files
for the Analog I/O Modules on the
ControlNet network
5Calibrating Your ModuleLists the tools needed, and the
6Applying FLEX Ex Analog I/O
Modules to the System
7Troubleshooting Your ModuleHow to use the indicators to
Appendix TitleContents
AAbout the SpecificationsOutlines module specifications and
BProgramming the FLEX Ex I/O
Modules Using RIO
Describes how to use these I/O
modules over the ControlNet
network
methods used to calibrate the
module
Describes how FLEX Ex is different
from traditional control systems
troubleshoot your module
accuracy
Explains how to program the analog
modules
1Publication 1797-6.5.1 - May 2005
Preface 2
For Additional Information
For additional information on FLEX Ex systems and modules, refer to the
following documents.
Catalog
Number
1797 SeriesFLEX Ex Selection Guide1794-SG002
1797 SeriesControlNet Ex System Cable Guide1797-6.2.1
1797-TB3FLEX Ex Terminal Base
1797-TB3SFLEX Ex Spring Clamp Terminal Base
1797-OE8FLEX Ex 8 Output Analog Module
1797-OE8HFLEX Ex HART 8 Ouput Analog
Module
1797-IRT8FLEX Ex RTD/Thermocouple/mV
Module
1797-IE8FLEX Ex 8 Input Analog Module
1797-IE8NFFLEX Ex 8 Input Analog Module with
Noise Filter
1797-IE8HFLEX Ex HART 8 Input Analog Module1797-6.5.3
1797-OB4D4 Output Module1797-5.6
Description
Installation
Instructions
1797-5.1
1797-5.3
1797-5.41797-6.5.2
1797-5.5
Publications
User Manual
1797-6.5.1
1797-6.5.3
1797-6.5.1
1797-IBN16FLEX Ex NAMUR Digital Input Module 1797-5.7
1797-PS2E2FLEX Ex Power Supply1797-5.8
1797-IJ22 Frequency Input Module1797-5.91797-6.5.4
1797-PS2N2FLEX Ex Power Supply1797-5.12
1797-BICFLEX Ex Bus Isolator
1797-CECFLEX Ex Flexbus Connector
1797-ACNR15ControlNet Ex Adapter1797-5.14
1797-RPA,
-RPFM
1797-TPR,
- TPRS, -TPYR,
-TPYS
1797-CE1S,
-CE3S, -CEFTN,
-CEFTE
1797-EXMKMarker Kit1797-5.23
1797-PS1EFLEX Ex Power Supply1797-5.33
1797-PS1NFLEX Ex Power Supply1797-5.34
1797-BCNRFLEX Ex Redundant ControlNet
Fiber Hub
FLEX Ex Taps
Interconnect Cables
Barrier Module
1797-5.13
1797-5.15
1797-6.2.1
1797-5.18
1797-5.20
1797-5.35
Publication 1797-6.5.1 - May 2005
Chapter
About the FLEX Ex Analog Modules
1
What this Chapter Contains
What the FLEX Ex Analog
I/O Modules Do
Read this chapter to familiarize yourself with the input and output analog
modules.
For information on:See page:
What the FLEX Ex Analog I/O
Modules Do
How FLEX Ex Analog Modules
Communicate with Programmable
Controllers
Physical Features of Your Analog I/O
Module
Chapter Summary1-6
The 1797-IE8 and -IE8NF modules accept up to 8 analog inputs. The inputs
are non-isolated and will accept current in either of the following two ranges:
4-20mA or 0-20mA. The default input range is 0-20mA. The inputs have both
fixed hardware filters and selectable firmware digital filters.
Similarly, the 1797-OE8 module provides as many as 8 analog outputs. The
outputs are nonisolated and will provide current in either of the following two
ranges: 4-20mA or 0-20mA. The default output range is 0-20mA.
1-1
1-2
1-3
Each module offers:
• local microprocessor intelligence for advanced features
• full functionality without switches or jumpers
• multiple data ranges that can be independently programmed
in channel groups
• lead breakage detection
• overrange/underrange alarms
• remote transmitter alarm
as well as a host of other module features.
1Publication 1797-6.5.1 - May 2005
1-2 About the FLEX Ex Analog Modules
How FLEX Ex Analog
Modules Communicate
with Programmable
Controllers
FLEX Ex analog I/O modules provide best utility when used with ControlNet
Ex products on the ControlNet network. Data connections are established
between the I/O module and an Allen-Bradley programmable controller to
transfer information between the two at a scheduled rate.
Input module information is then automatically made available in the PLC
data table through the data connection. Reciprocally, output data information
determined by the PLC program is also automatically transferred from the
PLC data table to the output module through the data connection.
In addition, when the data connection is originally established, configuration
information for the module is automatically transferred to it via the network.
Events following Power-Up
You must apply intrinsically safe +/-V power to your FLEX Ex analog I/O
modules. The following sequence of events occurs after power has initially
been applied to your module:
1. The module begins an internal diagnostic check. The channel 0 LED
indicator turns ON to indicate the check has begun. The indicator turns
OFF when the check is finished.
2. After the diagnostic check, module configuration information, selected
by the user and downloaded over the network, is applied by the module.
For more information on configuration options, see Chapter 2.
3. Following the module configuration download for the 1797-IE8 or
-IE8NF modules, the module begins producing runtime data for the
PLC.
Following the module configuration download for the 1797-OE8
module, the module applies configuration data to output channels.
4. If any diagnostics or alarms are generated during normal module
operation, the data is returned to the PLC.
Publication 1797-6.5.1 - May 2005
About the FLEX Ex Analog Modules 1-3
Physical Features of Your
Analog I/O Module
The module label identifies the keyswitch position, wiring and module
type. Use the removable label to note individual designations per
your application.
Indicators
Indicators are provided to identify input or output fault conditions, and to
show when power is applied to the module. For example, the 1797-IE8
module is shown below.
1797-IE8
Module Type
Removable Label
Ex
8 CHANNEL ANALOG INPUT
IN1IN0IN2IN3IN4
IN5
1797-IE8
IN6IN7
PWR
Keyswitch Position
3
Indicator (#3)
Power On Indicator
Using Alarms on the
1797-IE8 and -IE8NF
Modules
Input Designators
40070
The 1797-IE8 and -IE8NF FLEX Ex modules are capable of generating four
alarms:
• Underrange
• Overrange
• Remote Fault
• Local Fault
These alarm conditions are described in general terms and as they relate to bits
on the FLEX Ex I/O module on the following pages. The following graphic
shows at what values these alarms are generated for Data Format 4.
Publication 1797-6.5.1 - May 2005
1-4 About the FLEX Ex Analog Modules
0mA4mA20mA22mA
Data Format Alarm Example
In this example, the normal active data range is 4-20mA. The alarms are
generated in three overlapping bands.
PHYSICAL INPUT SIGNAL RANGE
underrangeoverrange
remote faultremote fault
local
fault
local
fault
-25.00%
-12.50%
programmable
in 20 0.1mA
steps by Error
Level 0.1mA
Steps
parameter
0.00%
Remote Transmitter Error
Up/Down parameter
determines which of these
is active
100.00%112.50%
programmable
in 20 0.1mA
steps by Error
Level 0.1mA
Steps
parameter
Overrange Alarm
The Overrange alarm notifies you when module input is overrange. When the
input signal exceeds 100% (20mA), an Overrange Alarm is generated.
This alarm stays active at any value above 100% of range and is always enabled
by the module.
Underrange Alarm
41666
Publication 1797-6.5.1 - May 2005
The Underrange alarm works in a fashion converse to the overrange. This
feature notifies you when the input signal falls underrange. If the input signal
falls below 0% (4mA), an Underrange Alarm is generated.
This alarm stays active at any value below 0% of range and is always enabled by
the module.
About the FLEX Ex Analog Modules 1-5
Remote Fault Alarm
The Remote Fault Alarm is primarily intended for use with remote transmitter
loops.
For example, the remote transmitter may be measuring temperature and
converting it to a standard mA signal. In such a loop, though, the input module
cannot determine the state of the loop on the far side of the transmitter.
However, the remote transmitter may be capable of diagnosing a problem in
the remote loop and signal the input module local loop with a preprogrammed
out of range (high or low) value.
The Remote Fault Alarm allows the 1797-IE8 and -IE8NF modules to work
with transmitters like the one just described. You must use the Remote
Transmitter Error Up or Down feature, see page 2-3, to configure your
application for Remote Fault notification.
For example, you must determine if you want a remote fault to cause
high out of range values or low out of range values to be returned to
the controller.
IMPORTANT
Once the alarm is issued, it remains active as long as the
input signal value remains above the programmed value.
Using Remote Fault Alarm to Determine High High or Low Low Alarm Levels
If you do not have a remote transmitter in your loop, this alarm can also be
used to program a high high or low low alarm level between the levels which
actuate the overrange or underrange alarms and the high or low local fault
alarms.
IMPORTANT
When establishing high high or low low alarms, you can
only select one side (high or low). You must use the
Remote Transmitter Error Up or Down feature in
conjunction with this alarm.
Publication 1797-6.5.1 - May 2005
1-6 About the FLEX Ex Analog Modules
Programming the Remote Fault Alarm
For the Remote Fault alarm, you must program the threshold in 0.1mA steps
at any level on the high or low end of input signal range. The Remote Fault
alarm activates if your I/O module receives input signal values of:
• 100.63% (20.1mA) to 111.88% (21.9mA) on the high end of input
signal range
or
• -0.63% (3.9mA) to -11.88% (2.1mA) on the low end of input
signal range
IMPORTANT
This alarm is only active for one band, either on the high
side of normal operation or the low side.The Remote
Transmitter Error Up/Down parameter determines which
side is active. See page 2-3 for a description of the Remote
Transmitter Error Up/Down feature.
Local Fault Alarm
The Local Fault alarm notifies you when the loop to the transmitter or field
device, if no transmitter is used, is open or shorted.
IMPORTANT
• 112.50% (22mA) or higher on the high end of input signal range - This
value indicates a short in the loop.
or
Once the alarm is issued, it remains active as long as the
input signal value remains in the programmed range.
Chapter Summary
Publication 1797-6.5.1 - May 2005
• -12.50% (2mA) or lower on the low end of input signal range - This
value indicates an open wire condition in the loop.
The Remote Fault and Local Fault alarms are issued with the same bit whether
the cause is an under or overrange. Monitor the Overrange and Underrange
bits in your programming software to determine if the problem is a high
current or low current.
In this chapter, you learned what FLEX Ex analog I/O modules do. Move on
to Chapter 2 to learn about configurable features on your module.
Chapter
Understanding Configurable FLEX Ex
Analog Module Features
2
What this Chapter Contains
Read this chapter to familiarize yourself with configurable features on the
input and output analog modules.
For information on:See page:
Selecting a 1797-IE8 or -IE8NF FLEX
Ex Analog Input Module’s Operating
Features
Selecting a 1797-OE8 FLEX Ex
Analog Output Module’s Operating
Features
Understanding Image Table Mapping
and Bit/Word Descriptions
Chapter Summary2-18
Use the table below to see what features this chapter describes.
Table 2.1 Configurable Features on the FLEX Ex Analog I/O Modules
1797-IE8 and -IE8NF input module
features:
Fault ModeOutput Enable
Remote Transmitter Error Up or DownModule Fault State Mode
2-2
2-7
2-13
1797-OE8 output module features:
High Low Error LevelLocal Fault Mode
Input Filter CutoffDigital Output
Data FormatLatch Retry Mode
Global Reset
Analog Digital State
Analog Fault State
Digital Fault State
Data Format
Fault Alarm
1Publication 1797-6.5.1 - May 2005
2-2 Understanding Configurable FLEX Ex Analog Module Features
You must use the I/O configuration portion of your PLC programming
software to select and configure these features. This manual assumes
familiarity with the programming software. A brief description of each
module feature is provided here. For more information on your
programming software, see the software user manual.
Selecting a 1797-IE8 or
-IE8NF FLEX Ex Analog
Input Module’s Operating
Features
All features of the 1797-IE8 and -IE8NF analog input modules are
independently configurable in two four-channel groups (channel 0-3 &
channel 4-7).
IMPORTANT
The default selection value for all parameters is 0.
Fault Mode
Your input modules are capable of indicating various fault conditions,
depending on the input signal value. Use the Fault Mode feature to enable or
disable two alarms:
• Remote Fault alarm
• Local Fault alarm
Use your programming software to set the Fault Mode bit to 0 to disable these
alarms. Set the bit to 1 to enable them.
Publication 1797-6.5.1 - May 2005
IMPORTANT
For more information on Remote and Local Fault alarms, see page 1-5.
Fault Mode will only enable or disable the Remote and
Local Fault alarms. It does not affect the Underrange and
Overrange alarms. They are always active.
Understanding Configurable FLEX Ex Analog Module Features 2-3
Remote Transmitter Error Up or Down
A second feature of your input modules that affects use of the Remote Fault
alarm is the Remote Transmitter Error Up or Down feature. Used in
conjunction with the High Low Error level, this feature designates whether
remote faults are displayed with input signal readings beyond the high or low
signal levels normally used by the module.
When setting the Remote Transmitter Error Up or Down feature in your
programming software, set this feature’s bit to 0 to select up. Set the bit to 1 to
select down.
For more information on Remote and Local Fault alarms, see page 1-5.
High Low Error Level
High Low Error level sets the high and low signal levels at which your input
modules will indicate a signal fault. This feature works in conjunction with the
Remote Transmitter Error Up or Down.
If the Remote Fault Alarm feature is enabled and a remote fault occurs, the
module will detect and report the fault, depending on how the High Low
Error level is configured.
Use your programming software to set the high or low error levels.
Input Filter Cutoff
Eight available input filter settings allow you to choose the best rolloff
frequency for input channels on your I/O module. When choosing a filter,
remember that time filter selection affects your input signal’s accuracy.
For example, if you choose the highest frequency of 1200Hz (filter 0), signal
noise is more likely to affect the reading, but the slowest frequency
of 0.5Hz (filter 7) provides the most accurate signal due to incoming
noise filtering.
See Table 2.2 to decide which input filter to use in your FLEX Ex
analog I/O application:
Choose the best input filter cutoff in your programming software.
Publication 1797-6.5.1 - May 2005
2-4 Understanding Configurable FLEX Ex Analog Module Features
(
)
(
)
Data Format
You must choose a module data format in your user prog ram. See Table 2.3 on
page 2-4 for an explanation of each bit. Formats 8, 9, 10 and 15 are not used. If
they are selected for a channel quad, a configuration fault will occur and will be
reported as Diagnostic Data “2”. All data for that channel quad will be set to
zero (0).
When using Table 2.3, remember the following:
• Formats 5, 12, 13 and 14 are 2’s complement data formats, and will
return data in that form.
• 12 Formats are available
• Default format is 0-20mA
• The data format selected interprets input readings and returns them to
the PLC
Data
Format
FormatResolution Input
00-20mA as mA0.1% of
10-20mA as %0.2% of
20-20mA
as √%
30-20mA as
unsigned
integer
44-20mA as mA0.1% of
0-20mA
0-20mA
0.19% of
0-20mA
0.03% of
0-20mA
4-20mA
Table 2.3 1797-IE8 and -IE8NF Data Formats
Module Data ProcessingData Table Value
Range
0-22mAdatatable = 1,000 (input)0-22000
0-22mA0-11000
0-22mA0-10488
0-20mA0-65,535
2-22mAdatatable = 1,000 (input) 2000-22000
datatable = 10,000
datatable = 10,000
IF . . . Square_Root_Threshold
< 10,000
Else . . . datatable = 0
datatable = 65,535
√
input
20
√
input
20
input
20
input
20
(interpretation)
(0-22.000mA)
(0-110.00%)
(0-104.88%)
(0-22mA)
(2.000-22.000mA)
Count
per mA
1000with
500with
524with
3276with
1000with
Error
Steps
error
steps
error
steps
error
steps
error
steps
error
steps
Publication 1797-6.5.1 - May 2005
Understanding Configurable FLEX Ex Analog Module Features 2-5
(
)
(
)
(
)
(
)
(
)
(
)
Table 2.3 1797-IE8 and -IE8NF Data Formats
Data
Format
FormatResolution Input
Range
54-20mA as %0.16% of
4-20mA
64-20mA
as √%
74-20mA as
unsigned
integer
80-20mAnot assignedall fixed
90-20mAnot assignedall fixed
100-20mAnot assignedall fixed
110-20mA as
A/D count
124-20mA as %0.16% of
0.17% of
4-20mA
0.03% of
4-20mA
0.04% of
0-20mA
4-20mA
2-22mA-1250 - +11250
4-22mA0-10607
4-20mA0-65,535
0-22mA0-55000
3.6-21mA-250 - +10625
Module Data ProcessingData Table Value
(interpretation)
√
input-4
16
input-4
16
input-4
16
input-4
16
input
22
input-4
16
(2’s complement)
(-12.50% +112.50%)
(0-106.07%)
(4-20mA)
(0-22mA)
( 2 ’ s c o m p l e m e n t )
(-2.50% +106.25%)
datatable = 10,000
datatable = 10,000
IF . . . Square_Root_Threshold
< 10,000
Else . . . datatable = 0
datatable = 65,535
datatable = 55,000
datatable = 10,000
√
Count
per mA
625with
589with
4095with
2500all fixed
625NAMUR
Error
Steps
error
steps
error
steps,
underrange not
allowed
error
steps
NE 4
all fixed
134-20mA
as %
144-20mA
as %
154-20mAnot assignedall fixed
0.16% of
4-20mA
0.16% of
4-20mA
3-21mA-625 - +10625
2-22mA-1250 - +11250
datatable = 10,000
datatable = 10,000
input-4
16
input-4
16
( 2 ’ s c o m p l e m e n t )
(-6.25% +106.25%)
( 2 ’ s c o m p l e m e n t )
(-12.50% +112.50%)
625all fixed
625all fixed
Publication 1797-6.5.1 - May 2005
2-6 Understanding Configurable FLEX Ex Analog Module Features
Data Formats and Error Ranges
The graphic below shows the data formats and error ranges for your
FLEX Ex analog I/O modules.
PHYSICAL INPUT SIGNAL RANGE
0mA20mA22mA
normal signal rangeoverrange
Format 0
Format 1
Format 2
Format 3
Format 4
Format 5
Format 6
Format 7
Format 8
Format 9
Format 10
Format 11
0.00mA
0.00%
0.00%
0
0mA20mA22mA
underrange
remote fault
local
fault
2mA
-12.50%
0.00mA
-25.00%
0mA20mA22mA
2mA
2mA
programmable
in 20
0.1mA steps
normal signal range
0
normal signal range
4.00mA
0.00%
0.00%
0
Not assigned
Not assigned
Not assigned
20.00mA
100.00%
100.00%
65,535
20.00mA
100.00%
100.00%
65,535
50,00055,00055,000
programmable
0.1mA steps
programmable
0.1mA steps
in 20
overrange
in 20
overrange
remote fault
22.00mA
110.00%
104.88%
22mA
remote fault
22.00mA
112.50%
106.07%
22mA
remote fault
local
fault
local
fault
local
fault
0mA20mA22mA
Format 12
Format 13
Format 14
Format 15
-25.00%
-25.00%
-25.00%
Publication 1797-6.5.1 - May 2005
remote fault
-12.50%
-12.50%
-12.50%
underrange
local
fault
-2.50%
-6.25%
-12.50%
normal signal range
Not assigned
-0.00%
-0.00%
-0.00%
100.00%
100.00%
100.00%
overrange
106.25%
106.25%
112.50%
remote fault
112.50%
112.50%
112.50%
local
fault
41667
Understanding Configurable FLEX Ex Analog Module Features 2-7
Selecting a 1797-OE8 FLEX
Ex Analog Output Module’s
Operating Features
All features of the 1797-OE8 analog output module are independently
configurable in two four-channel groups (channel 0-3 & channel 4-7).
IMPORTANT
The default selection value for all parameters is 0.
Output Enable
The Output Enable feature provides user control of the FLEX Ex I/O
module’s output channels.
At power-up, the ControlNet Ex adapter (1797-ACNR15) and the
FLEX Ex I/O modules use a default state of no communications over the
network. Use your programming software to change the Output Enable
bit to 1 to begin communications over the network.
If network communication is ever lost during normal operations, the adapter
resets the Output Enable bit to 0, and any connected I/O modules execute
their fault routine, including transitioning to fault state and setting outputs to a
user-defined fault state. When network communications resume, the adapter
sets the Output Enable bit to 1 and normal I/O operations continue.
Local Fault Mode
The Local Fault Mode can be programmed to determine how the module
responds to communications faults and internal module faults.
When setting the Local Fault Mode feature in your programming software, set
this feature’s bit to 0 to use the analog fault state or digital fault state only if a
communications fault occurs. Set the bit to 1 to use the analog fault state or
digital fault state if any fault occurs.
Publication 1797-6.5.1 - May 2005
2-8 Understanding Configurable FLEX Ex Analog Module Features
Latch Retry Mode
Latch Mode determines channel operation under wire off or lead break fault
conditions. This feature controls the operation of two channel groups,
channels 0-3 and channels 4-7. Channel detection occurs on a continuous
basis. If a fault is detected, the channel fault alarm is set.
If Latch Mode is enabled when a fault occurs, the fault will remain latched in
its fault state until a Global Reset (see below) is issued. If Latch Mode is
disabled when a fault occurs, the channel reports a fault until the fault is
corrected. Global Reset is not necessary if Latch Mode is disabled.
When using your programming software, set the Latch Mode bit to 0 to
disable the feature. Set the bit to 1 to enable it.
Global Reset
Global Reset works in conjunction with Latch Mode during fault conditions. If
Latch Mode is enabled and a fault condition occurs, the channel operating with
a fault remains in this condition (with analog or digital fault state implied) until
a Global Reset is issued. The Global Reset feature resets all outputs of a
particular channel group to accept normal system output data.
The Global Reset feature is an edge triggered signal. Use your programming
software to set the Global Reset bit to 1 for normal operation. Resetting of
outputs occurs during the 1 to 0 transition.
Analog Digital State
You can configure your FLEX Ex analog I/O modules to work in an analog
mode or digital mode using the Analog Digital State feature. Depending on
which state you choose for your application, additional parameters (see the
descriptions of Analog Fault State and Digital Fault State on page 2-9) must be
configured for your module to react to fault conditions.
Set the Analog Digital State bit in your programming software to 0 for your
module to operate in an analog state. Set the bit to 1 for your module to
operate in a digital state. A selection bit is available to each channel.
Publication 1797-6.5.1 - May 2005
Understanding Configurable FLEX Ex Analog Module Features 2-9
Analog Fault State
The Analog Fault State feature determines how your I/O module reacts to
faults when a channel is used in analog mode. After a fault condition occurs,
the module may got to minimum value, maximum value, hold last state or 50%
of range.
Use your programming software to set the Analog Fault State bits on the
I/O module for one of the following fault reactions:
• 0 = minimum value
• 1 = maximum value
• 2 = hold last state
• 3 = 50% of range
You can set these parameters independently for channels 0-1, 2-3, 4-5, 6-7.
Digital Fault State
The Digital Fault State feature determines how your I/O module reacts to
faults when a channel is used in digital mode. After a fault condition occurs,
the module may reset channel outputs or hold last state of the outputs.
Use your programming software to set the Digital Fault State bit to 0 to reset
outputs. Set to 1 to hold last state of the outputs after a fault occurs. This
feature is available on a per channel basis.
Publication 1797-6.5.1 - May 2005
2-10 Understanding Configurable FLEX Ex Analog Module Features
Data Format
You must choose a module data format in your user prog ram. See Table 2.4 on
page 2-11 for an explanation of each bit. Data Formats 2, 5, 6, 8, 9, 10, 12 and
15 are not assigned.
When choosing a data format, remember the following:
• If a non-assigned Analog Data Format is selected, the module sets
Diagnostic Data to “2” for configuration failure and puts affected
channels affected in the corresponding fault state.
• An unconfigured module channel pair can be assumed to have the
default configuration Analog Data Format “0”, 0-20mA and Analog
Mode Fault State “minimum range”. If a non-assigned format is
selected, then the diagnostic “2” for configuration failure is set and the
module channel pair goes to the default fault state minimum range.
• If on the other hand, the configuration had been changed, from the
default, and then it was changed again to a non-assigned format, then
the diagnostic bit “2” for configuration failure is set and the module
goes to the fault state for the last valid configuration.
• Formats 13 and 14 are 2’s complement data formats, and require data to
the module in that form.
• Range: 0-15, See Table 13
• Default: 0
• Data Table Reference: data format, word 12 and 13, bits 0-3, bits 4-7
If data is sent to the module which is out of range, the value will be clipped
and Diagnostic Data will be set to “11” data out of range. See the graphic
below.
datatable
20.000
16.000
12.000
8.000
4.000
Diagnostic Data error
11=data out of range
Publication 1797-6.5.1 - May 2005
Diagnostic Data error
11=data out of range
0.000
-4.000
04812162024
Output mA
Understanding Configurable FLEX Ex Analog Module Features 2-11
(
)
(
)
(
)
(
)
(
)
Table 2.4 1797-OE8 Data Formats
Data
Format
0mA as
1% as
20-20mA0-22mAnot assigned
3unsigned
4mA as
54-20mA4-20mAnot assigned
FormatResolution Full
Output
Range
0-20mA
0-20mA
integer as
0-20mA
4-20mA
0.1% of
0-20mA
0.2% of
0-20mA
0.03% of
0-20mA
0.1% of
4-20mA
0-22mA0-22000
0-22mA0-11000
0-20mA0-65,535
2-22mA2000-22000
Module Data ProcessingData Table Value
output =
output = 20
output = 20
output =
datatable
1,000
datatable
10,000
datatable
65,535
datatable
1,000
(Interpretation)
(0-22.000mA)
(0-110.00%)
(0-22mA)
(2.000-22.000mA)
Count
per mA
1000min=0mA
500min=0mA
3276min=0mA
1000min=2mA
Analog Fault
State
max=22mA
hold
last=hold
50%=11mA
max=22mA
hold
last=hold
50%=11mA
max=20mA
hold
last=hold
50%=10mA
max=22mA
hold
last=hold
50%=12mA
64-20mA4-20mAnot assigned
7unsigned
integer as
4-20mA
80-20mA0-20mAnot assigned
90-20mA0-20mAnot assigned
0.03% of
4-20mA
4-20mA0-65,535
output = 16
datatable
65,535
+ 4
(4-20mA)
4095min=4mA
max=20mA
hold
last=hold
50%=12mA
Publication 1797-6.5.1 - May 2005
2-12 Understanding Configurable FLEX Ex Analog Module Features
(
)
(
)
(
)
Table 2.4 1797-OE8 Data Formats
Data
Format
100-20mA0-20mAnot assigned
11D/A count
124-20mAnot assigned
13% as
14% as
154-20mA4-20mAnot assigned
FormatResolution Full
Output
Range
as 0-20mA
4-20mA
4-20mA
0.28% of
0-20mA
0.16% of
4-20mA
0.16% of
4-20mA
0-22mA0-8000
3-21mA-625 - +10625
2-22mA-1250 - +11250
Module Data ProcessingData Table Value
output = 22
output = 16
output = 16
datatable
8,000
datatable
10,000
datatable
10,000
+ 4
+ 4
(Interpretation)
(0-22mA)
( 2 ’ s c o m p l e m e n t )
(-6.25% +106.25%)
( 2 ’ s c o m p l e m e n t )
(-12.50% +112.50%)
Count
per mA
363min=0mA
625min=3mA
625min=2mA
Analog Fault
State
max=22mA
hold
last=hold
50%=11mA
max=21mA
hold
last=hold
50%=12mA
max=22mA
hold
last=hold
50%=12mA
Fault Alarm
Fault Alarm selects whether the channel pair fault detection is enabled or
disabled. There is a 100Hz (10ms) filter for wire off/lead break detection.
Use your programming software to set the Fault Alarm. Set the feature bit
to 0 to disable the alarm. Set the bit to 1 to enable wire off/lead break
fault detection.
Publication 1797-6.5.1 - May 2005
Understanding Configurable FLEX Ex Analog Module Features 2-13
Understanding Image Table
Mapping and Bit/Word
Descriptions
Bit Descriptions
Use the table below to understand bits used in image table mapping and
bit/word descriptions. Complete definitions of these feature documented
below can be found in Chapter 2.
Table 2.5 Bit/Word Descriptions
Bit: (s):Location:Definition:
Ch1797-IE8 and -IE8NF Input and output maps
1797-OE8 Input and output maps
Ovr Alm1797-IE8 and -IE8NF Input mapOverrange Alarm
Und Alm1797-IE8 and -IE8NF Input mapUnderrange Alarm
Rm Flt1797-IE8 and -IE8NF Input mapRemote Fault
Lo Flt1797-IE8 and -IE8NF Input mapLocal Fault
Res Flg1797-IE8 and -IE8NF Input map
1797-OE8 Input map
Out Enbl1797-OE8 Output mapOutput Enable
U/D1797-IE8 and -IE8NF Output mapUp/down
Flt Md1797-IE8 and -IE8NF Output mapFault Module
Cd Flg1797-IE8 and -IE8NF Output map
1797-OE8 Output map
Channel
Response Flag
Command Flag
Flt Alm1797-OE8 Input mapFault Alarm
Glbl Rst1797-OE8 Output mapGlobal Reset
Lo Flt Md1797-OE8 Output mapLocal Fault Module
Alg Flt Ste1797-OE8 Output mapAnalog Fault State
Lth Rty1797-OE8 Output mapLatch Retry
Dig Flt Ste1797-OE8 Output mapDigital Fault State
Alg Dig Md1797-OE8 Output mapAnalog Digital Module
Diagnostic
Status
1797-IE8 and -IE8NF Input map
1797-OE8 Input map
Diagnostic Status
Publication 1797-6.5.1 - May 2005
2-14 Understanding Configurable FLEX Ex Analog Module Features
Analog Input Modules (1797-IE8 and -IE8NF) Image Table
Mapping
Table 2.6 Input Map (Read Words)
Bit
→
Word
15141312111009080706050403020100
↓
Read
0Channel 0 Input Data
1Channel 1 Input Data
2Channel 2 Input Data
3Channel 3 Input Data
4Channel 4 Input Data
5Channel 5 Input Data
6Channel 6 Input Data
7Channel 7 Input Data
Und
Und
Und
Und
Und
Und
Ovr
Ovr
Ovr
Ovr
Ovr
Ovr
Alm
ch
7
Flt
ch
7
Ovr
Alm
ch
6
Rm
Flt
ch
6
Alm
ch
5
Rm
Flt
ch
5
Alm
ch
4
Rm
Flt
ch
4
Alm
ch
3
Rm
Flt
ch
3
Alm
ch
2
Rm
Flt
ch
2
Alm
ch
1
Rm
Flt
ch
1
Alm
ch
0
Rm
Flt
ch
0
Alm
ch
7
Lo
Flt
ch
7
Alm
ch
6
Lo
Flt
ch
6
Alm
ch
5
Lo
Flt
ch
5
Alm
ch
4
Lo
Flt
ch
4
Alm
ch
3
Lo
Flt
ch
3
Alm
ch
2
Lo
Flt
ch
2
8Ovr
9Rm
10Diagnostic Status
11Res
Module command responseModule response data
Flg
Where:ch = channel
Ovr Alm = Overrange Alarm
Und Alm = Underrange Alarm
Rm Flt = Remote Fault
Lo Flt = Local Fault
Res Flg = Response Flag
Und
Alm
ch
1
Lo
Flt
ch
1
Und
Alm
ch
0
Lo
Flt
ch
0
Table 2.7 Output Map (Write Words)
Bit →
Word
15141312111009080706050403020100
↓
0High and Low Error LevelU/D
1High and Low Error LevelU/D
2Cd
Module commandModule command data
Flg
Where:Out Enbl = Output Enable
U/D = up/down
Flt Md = Fault Module
Cd Flg = Command Flag
Publication 1797-6.5.1 - May 2005
0-3
0-3
Write
Filter Cutoff 0-3Data FormatFlt
Md
Filter Cutoff 0-3Data FormatFlt
Md
Loading...
+ 74 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.