Rockwell Automation 1797-OB4D User Manual

Installation Instructions
FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module
Catalog Number 1797-OB4D
Top ic Page
Important User Information 2
Installation in Zone 1 5
Installation on Zone 22 5
Module Installation 3
Outputs 8
Wire to a 1797-TB3 or 1797-TB3S Terminal Base Unit 9
Ground the Module 11
Indicators 11
Memory Mapping 12
Field Descriptions 12
Repair 14
Specifications 15
FLEX Ex Output Module Operation 18
Entity Parameters 19
Output Voltage versus Current Capability 29
17
Publication 1797-5.6 - June 2011
2 FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1
http://www.literature.rockwellautomation.com
state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual we use notes to make you aware of safety considerations.
available from your local Rockwell Automation sales office or online at
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
) describes some important differences between solid
Publication
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
Labels may be located on or inside the equipment to alert people that dangerous voltage may be present.
1797-5.6 - June 2011
FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module 3
3
5
1
8
7
6
2
Label here or under here
4
40231

Module Installation

Component identification
1 FlexBus connector 5 Terminal base unit
2 Latching mechanism 6 Alignment groove
3 Keyswitch 7 Alignment bar
4 Cap plug 8 Module
Publication
1797-5.6 - June 2011
4 FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module
ATTENTION

Install the Module

This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance. This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
This module must be used with a 1797-TB3 or 1797-TB3S intrinsically safe terminal base unit.
otate keyswitch (3) on terminal base unit (5) clockwise to position 7
1. R
as required for this type of module.
Do not change the position of the keyswitch after wiring the
minal base unit
ter
e certain the FlexBus connector (1) is pushed all the way to the
2. Mak
left to connect with the neighboring terminal base/adapter.
You cannot install the module unless the connector is fully
d.
extende
e sure the pins on the bottom of the module are straight so they
3. Mak
will align properly with the connector in the terminal base unit.
osition the module (8) with its alignment bar (7) aligned with the
4. P
groove (6) on the terminal base.
5. Press f
irmly and evenly to seat the module in the terminal base unit. The module is seated when the latching mechanism (2) is locked into the module.
Publication
1797-5.6 - June 2011
FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module 5
WARNING
41307
6. Make certain that you only connect terminal base units to other
intrinsically safe system modules or adapters to maintain the integrity of the intrinsically-safe backplane.
emove the cap plug (4) and attach another intrinsically safe terminal
7. R
base unit to the right of this terminal base unit if required.

Installation in Zone 1

This module must not be exposed to the environment and must have a suitable metal enclosure. It has a protection factor of IP20.
This module cannot be used in an intrinsically safe environment after it has been exposed to nonintrinsically safe signals.

Installation on Zone 22

When the module is installed in Zone 22, the following cabinets must be used: IVK-ISRPI-V16LC; IVK-ISRPI-V8HYW; or IVK-ISRPI-V8LC. These cabinets can be purchased from:
Pepperl+Fuchs GmbH Lilienthalstrasse 200 68307 Mannheim, Germany Attn: PA Sales Dept. Kirsten Becker Telephone +49 776 1298 www.pepperl-fuchs.com
Publication
1797-5.6 - June 2011
6 FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module
The IS-RPI cabinets (type IVK2-ISRPI-V8LC, IVK2-ISRPI-V8HYW, or IVK2-ISPRI-V16LC) ensures the basic protection for the intrinsically safe apparatus of the FLEX Ex system for use in Zone 22. It corresponds with category 3D according to RL 94/9 EG and with the type label marked with the following information:
Pepperl+Fuchs GmbH 68307 Mannheim IVK2-ISRPI-V8LC (or IVK2-ISRPI-V8HYW or IVK2-ISRPI-V16LC)
II 3 D Ex tD A22 IP54 T70 °C X
CE Serial (manufacturin Model
g) number

Electrostatic Charge

Protect the system against electrostatic charge. Post a sign near this module:
WARNING Avoid electrostatic charging.
ADVERTÊNCIA! PREVENIR CONTRA O ACÚMULO DE CARGA ELETROSTÁTICA.
For your convenience, a sign that can be cut out is included in this installation instr
uction.
Publication
1797-5.6 - June 2011
FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module 7
WARNING

Removal and Insertion Under Power

These modules are designed so you can remove and insert them under power. However, take special care when removing or inserting modules in an
active process. I/O attached to any module being removed or inserted can change states due to its input/output signal changing conditions. If you insert or remove the terminal base while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

European Communities (EC) Directive Compliance

If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.

EMC Directive

These products are tested to meet the Council Directive 2004/108/EC by applying the following standards:
EN 6100 Generic Standard for Industrial Environments (Class A)
EN 6100 Generic Standards - Immunity for Industrial Environments
EN6132 Measurement, Control, and Laboratory Use - Industrial EMC Requirements
0-6-4:2007, Electromagnetic Compatibility (EMC) - Part 6-4:
0-6-2:2005, Electromagnetic Compatibility (EMC) - Part 6-2:
6-1:2006 (Industrial), Electrical Equipment For

ATEX Directive

These products are tested in conjunction with associated I/O modules to meet the Council Directive 94/9/EC (ATEX) Equipment and Protective Systems Intended for Use in Potentially Explosive Atmospheres by applying the following standards:
Publication
1797-5.6 - June 2011
8 FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module
FlexBus
Bus
uC
+V
-V
+
-
Power supply
Valve
Audible alarm
Solenoid
40069
EN60079-11:2007, Explosive atmospheres - Part 11 : equipment protection by intrinsic safety "i"
EN6007
9-0:2006, Electrical apparatus for explosive gas atmospheres -
Part 0 : general requirements
EN 60
079-26 : 2004, Electrical apparatus for explosive gas atmospheres - Part 26 : construction, test and marking of Group II Category 1 G electrical apparatus
EN6124
1-0 : 2006, Electrical apparatus for use in the presence of
combustible dust - Part 0: General requirements
EN6124
1-11:2006, Electrical apparatus for use in the presence of
combustible dust – Part 11: Protection by intrinsic safety 'iD'

Outputs

Each output can operate a digital field device.
Do not apply any nonintrinsically safe signals to this module.
When using an intrinsically safe electrical apparatus according to EN50020, the European Community directives and regulations must be followed.
The channels in this module are electrically connected to each other.
Publication
1797-5.6 - June 2011
FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module 9
No connections allowed to terminals 2, 3, 6, 7, 10, 11, 14, 15, 17 to 32, 36, 37, 38, 39, 46, 47, 48, 49.
40068A
Row A
Row B
Row C

Wire to a 1797-TB3 or 1797-TB3S Terminal Base Unit

Connect wiring to the terminal base as shown below.
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
_
+
CH 0 CH 1 CH 2 CH 3
16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49
nnect the individual output wiring to (+) terminals (0, 4, 8, 12) on
1. Co
_
+
_
+
_
+
the 0…15 row (A) as indicated in the table below.
nnect the associated output to the corresponding (-) terminal (1, 5,
2. Co 9, 13) on the 0…15 row (A) for each output as indicated in the table below.
nect +V DC power to terminal 34 on the 34…51 row (C).
3. Con
4. Con
nect -V to terminal 35 on the 34…51 row (C).
32 33
50 51
+V -V+V -V
Publication
1797-5.6 - June 2011
10 FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module
WARNING
ATTENTION
Make certain that you power this module with an intrinsically safe power supply. Do not exceed the values listed in the specifications for this module. If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
5. If continuing power to the next terminal base unit, connect a jumper from terminal 50 (+V) on this base unit to terminal 34 on the next base unit.
ntinuing common to the next terminal base unit, connect a
6. If co jumper from terminal 51 (-V) on this base unit to terminal 35 on the
next base unit.
Module Wire Connections
Output Output + Output -
Output 0 A-0 A-1
Output 1 A-4 A-5
Output 2 A-8 A-9
Output 3 A-12 A-13
+V Terminals C-34 and C-50
-V Terminals C-35 and C-51
Publication
Do not use the unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module or unintended operation of your system, or both.
1797-5.6 - June 2011
FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module 11
30820-M
Shield terminating feed-through
Bus bar
PWR
40067
A = Status indicators B = Insertable labels for writing individual input designations C = Power indicator (green indicates power applied to the module)

Ground the Module

All I/O wiring must use shielded wire. Shields must be terminated external to the module, such as bus bars and shield-terminating feed throughs.

Indicators

1797-OB4D
A B C
Publication
Ex
PWR
1797-5.6 - June 2011
12 FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module
Status Indicators
Indicator Status Description
Yel low Individual input present
Flashing red Channel fault
Solid red Module did not pass power up check
Channel 0 is solid red while power-up check is running

Memory Mapping

Dec Bit
Oct Bit
Read 0 OVL 3OVL 2OVL 1OVL 0F3 F2 F1 F0
Write 0 Out
Configuration 1 RA Alarm Filter
Where: OVL = Overload alarm for individual channel
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
17 16 15 14 13 12 11 10 07 06 05 04 03 02 01 00
Enb
F = Fault alarm for individual channel DA = Detect Alarms, Detection of Output faults (0 = Disable, 1 = Enable) FS = Fault state (0 is reset and 1 is hold last state) D = Data, Output data 0 = Off 1 = On L = Latch alarms (0 = Disable, 1 = Enable) Out Enb = Output Enable RA = Reset Alarms (0 = Normal, 1 = Reset)
LDA 3DA 2DA 1DA 0FS 3FS 2FS 1FS 0D3 D2 D1 D0
Ch 0…3
Field Descriptions
Field Description
Fault Alarm 0 = No fault
1 = Wire-off fault or overload 100 Hz (10 ms) filter is integrated
A wire-off fault or overload can be detected using this single bit.
Note:
Publication
1797-5.6 - June 2011
FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module 13
Field Descriptions
Overload Alarm 0 = No fault
Data Output data
Fault State 0 = Output goes to 0 during fault
Detect Alarms These bits can be used to activate/deactivate
1 = Output channel overloaded (Load resistance range 30…5000 Ω) 100 Hz (10 ms) filter is integrated
0 = Off 1 = On Default = 0
1 = Hold last state Default = 0
overload monitoring of the outputs for each channel.
0 = Wire-off detection/overload monitorin 1 = Wire-off detection/overload monitorin
g deactivated g activated
wire-off detection and
Note: Leakag detection is activated. The normal load range is defined as 30 this range, no faults will occur. Wire off is assured to be reported for loads > 75
Latch Alarms
Outputs Enable 0 = Outputs disabled
This bit defines for all channels, whether, in the event of a wire off or overload fault, the corresponding fault bit (Overload Alarm, Fault Alarm) remains set until the Reset Alarms bit in the configuration data word is reset by the user. This ensures that a fault message is sent to the control system in the event of a fault that is short in duration. The alarms should be latched if the Latch Alarms bit is 1 and the outputs go to 0 state until the Reset Alarm occurs.
0 = Alarms and outputs are automatically reset 1 = Alarms and outputs are blocked and must be reset by setting the bit Re
set Alarms through the user program.
Default = 0
1 = Outputs enabled Default = 0
This bit must be set to 1 by the program for normal operation of the outpu
e current will be present when output is at 0 state if Wire Off
kΩ.
It does not matter if the output is OFF or ON.
ts. When set to 0 the outputs will follow the Fault State status.
Publication
Ω…5
kΩ.
In
1797-5.6 - June 2011
14 FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module
Value Binary Time constant
000 0.25 ms (Hardware)
001 0.5 ms
010 1 ms
011 2 ms
100 4 ms
101 8 ms
110 16 ms
111 32 ms
Field Descriptions
Alarm Filter These 3 bits are used to set the time constant of the fault/overload alarm
filter for channels 0…3.
Default = 0
Reset Alarms With this bit, wire off/overload fau
the outputs cancelled. See Latch Alarms (LA). To reset the wire off/overload faults set the RA bit to 1 and back to 0. The reset will not occur until a 0 > 1 > 0 transition occurs.
RSLogix 5000 Software Tip: The Reset Alarms bit is found in the Module
nfiguration word. Program a Module Reconfigure typed MSG to set and
Co then clear the RA bit.
0 = Normal

Repair

This module is not field-repairable. Any attempt to open this module will void the warranty and IS certification. If repair is necessary, return this module to the factory.
Publication
1 = Reset Default: 0
1797-5.6 - June 2011
lts are reset and the latch condition of
FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module 15

Specifications

General
Attribute Valu e
Number of outputs 4, nonisolated, sourcing
IS output type Ex ia IIB/IIC T4,
AEx ia IIC T4, Class I, II, III Division 1 Groups
IS module type Ex ib IIB/IIC T4,
AEx ib IIC T4, Class I Division 1 Groups A…D T4
V-I Characteristics Refer to Output Voltage versus Current Capability on
page 29
Load range 30…5000 Ω
Fault detection Fault bits in data table and LED (per channel)
blinking red (1 Hz)
Electronic protection Lead break, overload, short circuit
Maximum output delay times
OFF to ON ON to OFF
<1.2 ms <1.2 ms
Indicators 4 yellow status indicators
4 red fault indicators 1 green module power indicator
Output (intrinsically safe)
(16 pin male and female FlexBus connector)
< 5.8V DC
U
i
I
< 400 mA
i
L
= Negligible
i
C
< 1.35 μF
i
A, B, C, D, E, F, G T4
Isolation path
Output to power supply Output to FlexBus Power supply to FlexBus Output to output
Isolation type Galvanic to DIN EN 60079-11 Galvanic to DIN EN 60079-11 Galvanic to DIN EN 60079-11 None
Publication
1797-5.6 - June 2011
16 FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module
General
Power supply
(+V, -V Intrinsically safe)
Module field-side
wer consumption
po
Ui < 9.5V DC I
< 1 A
i
L
= Negligible
i
C
= Negligible
i
7.5 W
Power dissipation 5 W
Thermal dissipation 17.07 BTU/hr
Module location 1797-TB3 or 1797-TB3S Terminal base unit
Conductors wire size, max
2
(12 gauge) stranded
4 mm
1.2 mm (3/64 in.) insulation
Dimensions HxWxD
46 x 94 x 75 mm (1.8 x 3.7 x 2.95 in.)
Weight, approx. 200 g (7.05 oz.)
Keyswitch position 7
Environmental Specification
Attribute Value
Temperature, operating
Temperature, storage
Relative humidity 5…95% noncondensing
Shock, operating Tested to 15 g peak acceleration, 11(+1) ms pulse width
Shock, nonoperating Tested to 15 g peak acceleration, 11(+1) ms pulse width
Vibration Tested 2 g @ 10…500 Hz per IEC68-2-6
-20…+70
-40…+85
°
C (-4…+158 °F)
°
C (-40…+185 °F)
Publication
1797-5.6 - June 2011
Certifications
FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module 17
Certifications when product
is marked
CENELEC II (1) 2G Ex ib[ia] IIC T4
UL, C-UL Class I, Groups A, B, C and D; Class
FM Intrinsically safe Class I, Div
INMETRO BR-Ex ia/ib IIB/IIC T4
IECEx [Zone 0] Ex ib[ia] IIC T4
(1)
(1)
See the Product Certification link at http://www.ab.com for Declaration of Conformity, Certificates, and other certification details.
Valu e
I (1) D [Ex iaD]
I
G; Class III Hazardous Locations Class I, Zone 1, AEx ib[ia] IIC T4.
Associated Apparatus with instrincally safe connections Class I, II, III, Div 1, Groups A-G. Intrinsically safe Class I, Zone 1, AEx ib[ia] IIC T4.
[Ex iaD]
II, Groups E, F and
1, Groups A, B, C, D, T4.

Cooperative Operation of the ControlNet Ex Adapter and FLEX Ex Output Modules

The ControlNet Ex adapter (1797-ACNR15) combined with FLEX Ex output module provides a two-tier fault state mechanism. It is important to consider and understand the operation of this mechanism when designing your system.
Two sets of programmable fault states are and output module. This two-tier method is meant to give you a wider fault coverage compared with normal methods.
available, one each in the adapter
Publication
1797-5.6 - June 2011
18 FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module

Adapter Operation

Network Communication Monitoring
The adapter is the primary monitor of network activity. If it detects loss of network communication, it can be programmed to:
• continue writing the last valid receiv state).
• apply local module safe states.
ed data to the module (hold last
(1)
• write a programmable fault state value to the module, depending upon
(2)
the module type.
This mechanism primarily targets fault behavior for loss of network communication.
Program Mode Behavior
The adapter also monitors the state of the controlling processor or scanner. Two states can be detected: Run mode and Program mode (idle).
When Program mode is detected, the adapter can be configured to:
ntinue writing the last valid received data to the module (hold last
co state).
appl
y local module safe states to zero.
(1)
write a programmable fault state value to the module, depending upon
the module type.
(2)

FLEX Ex Output Module Operation

The following describes the output module operation.
(1)
This selection is shown as Reset Outputs in RSNetWorx software, but its action is Apply Local Module Safe States.
(2)
This option is only available in some adapters.
Publication
1797-5.6 - June 2011
FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module 19

Flexbus Communication Monitoring

The module monitors FlexBus communication activity and the state of its Output Enable bit. If it detects loss of FlexBus communication activity or the Output Enable bit transitioning to 0, it can be programmed to:
ntinue writing the last valid received data to the outputs (hold last
co state).
reset the
write th
the module type.
This mechanism primarily targets fault behavior for loss of backplane
mmunication.
co
outputs.
e local module fault state value to the output, depending upon
Power-up State Behavior
The system and modules use the Output Enable bit at system power-up. The power-up state of the Output Enable bit is 0 and must be transitioned to 1 through application program control to initialize activity of a module’s outputs.
Before the Output Enable bit is transition Once the initial power-up and application-program control transitions the Output Enable bit to 1, and module output activity begins, subsequent transitions of the Output Enable bit by any source will cause the output module to apply the local module fault state.
ed to 1, module outputs remain off.

Entity Parameters

CE, CENELEC I/O Entity Parameters

Signal output (+ to -) for ch 0…ch 3 (terminals: 0 and 1; 4 and 5; 8 and 9; 12 and 13).
Publication
1797-5.6 - June 2011
20 FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module
Entity Parameters
1797-OB4D
= 27.4V
U
o
I
= 110 mA
o
If concentrated capacitance
or inductance are available,
and/ use the following values.
Protection Group Allowed
Capacitance
Ex ia IIB 677 nF 8 mH
IIC 87 nF 2 mH
Ex ia IIB 150 nF 5 mH
IIC 30 nF 2 mH
Allowed Inductance
The values of Lo and Co listed in the table above are allowed if one of the
following conditions is met:
• The total L
of the external circuit (excluding the cable) is < 1% of the
i
Lo value or
• The total C
of the external circuit (excluding the cable) is < 1% of the
i
Co value.
The values of L
and Co listed in the table above shall be reduced to 50%
o
when both of the following conditions are met:
• The total L
value and
L
o
• The total C
value.
C
o
The reduced capacitance of the external circuit (including cable) shall
Note:
of the external circuit (excluding the cable) is 1% of the
i
of the external circuit (excluding the cable) is ≥ 1% of the
i
not be greater than 1µF for IIB and IIA and 600nF for IIC.

UL, C-UL I/O Entity Parameters

If this product has the UL/C-UL mark, it has been designed, evaluated, tested, and certified to meet the following standards:
UL 91
Publication
3, 1988, Intrinsically Safe Apparatus and Associated Apparatus for Use in Class I, II, and III Division 1, Hazardous (Classified) Locations
1797-5.6 - June 2011
FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module 21
UL 1203, Explosion-Proof and Dust-Ignition-Proof Electrical Equipment for Use in Hazardous (Classified) Locations
UL 22
79, Electrical Equipment for Use in Class I, Zone 0, 1, and 2
Hazardous (Classified) Locations
61010, UL Standard for Safety Electrical Equipment For
UL Measurement, Control, and Laboratory Use; Part 1: General Requirements
CSA C22.2 No
. 157-92, Intrinsically Safe and Non-Incendive
Equipment for Use in Hazardous Locations
CSA C22.2 No
. 30-M1986, Explosion-Proof Enclosures for Use in
Class I Hazardous Locations
CSA-E79
-0-95, Electrical Apparatus for Explosive Gas Atmospheres,
Part 0: General Requirements
CSA-E79
-11-95, Electrical Apparatus for Explosive Gas
Atmospheres, Part 11: Intrinsic Safety “i”
C22.2 No. 14-95, Industrial Control Equipment
CSA
Wiring Methods
ring method 1: Each channel is wired separately.
Wi
ring method 2: Multiple channels in one cable, providing each
Wi channel is separated in accordance with the National Electric Code (NEC) or Canadian Electric Code (CEC).
Wiring Method
Wiring Me
1 and 2 Any one
Channel Te rm in al s Voc
thod
channel (fo
r example, ch0)
0(+), 1(-) 27.4 110.0 - - A, B, IIC 0.03 2.0
(V)
Isc (mA)
Vt (V)
It (mA)
Groups Ca
C, E, IIB 0.09 8.0
D, F, G, IIA 0.24 16.0
(μF)
La (mH)
Publication
1797-5.6 - June 2011
22 FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module
IMPORTANT
PWR
FLEX Ex digital
output I/O module
Indicators
Female bus
connection
Field wiring
terminals
Terminal base
Terminal base key
Male bus connection
Key position for terminal base insertion
42058
Ex
1797-OB4D
PWR
A terminal base may or may not have an I/O module installed.
Publication
1797-5.6 - June 2011
FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module 23
Hazardous (Classified) Location Class I, Zones 0, 1, & 2 Groups IIC, IIB, IIA Class I, Div. 1 & 2 Groups A, B, C, D Class II, Div. 1 & 2 Groups E, F, G Class III, Div. 1 & 2
Hazardous (Classified) Location Class I, Zones 1 & 2 Groups IIC, IIB, IIA Class I, Div. 1 & 2 Groups A, B, C, D
To any intrinsically safe device or associated apparatus with Entity Concept parameters of V
oc
< 5.8V; Isc < 400 mA.
To any intrinsically safe
device or associated apparatus with Entity Concept parameters of V
oc
< 9.5V; Isc < 1 A.
To any IS device with Entity Concept parameters of (V
max
, I
max
, Ci, Li) appropriate
for connection to associated apparatus with Entity Concept parameters listed in the table, Wiring Method.
1797-OB4D
16
Shield connection only
50
51
35
34
V
max
=5.8V
I
max
=400mA
C
i
=1350nF
L
i
=negligible
V
max
=9.5V
I
max
=1A
C
i
=negligible
L
i
=negligible
Male Bus Connector
33 40 41
42 43 44 45
0 (+)
Female Bus Connector
1 (-)
ch0
ch1
ch2
ch3
4 (+) 5 (-)
8 (+) 9 (-)
12 (+) 13 (-)
42059
Any Simple Apparatus or I.S. device with Entity Concept parameters (V
max
, I
max
, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in the table, Terminal Connections.
Terminal Connections
Ter mi na ls Vt (V) It (mA) Groups Ca (μF) La (μH)
Male bus
5.8 400 A to G 3.0 3.0
connector
The entity concept allows interconnection of intrinsically safe apparatus
with associated apparatus not specifically examined in combination as a system when the approved values of V apparatus are less than or equal to V apparatus and the approved values of C are greater than C
+ C
i
apparatus. The internal capacitances Ci of the terminal base must be taken into account to verify the intrinsic safety.
and I
oc
sc
and I
max
max
and La of the associated apparatus
a
respectively for the intrinsically safe
cable
and Li + L
cable
or Vt and It of the associated of the intrinsically safe
Publication
1797-5.6 - June 2011
24 FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module
The values of Lo and Co listed in the table above are allowed if one of the
following conditions is met:
• The total L
value or
L
o
• The total C
value.
C
o
The values of L
of the external circuit (excluding the cable) is < 1% of the
i
of the external circuit (excluding the cable) is < 1% of the
i
and Co listed in the table above shall be reduced to 50%
o
when both of the following conditions are met:
• The total L
value, and
L
o
• The total C
value.
C
o
Note:
The reduced capacitance of the external circuit (including cable) shall
of the external circuit (excluding the cable) is 1% of the
i
of the external circuit (excluding the cable) is ≥ 1% of the
i
not be greater than 1µF for IIB and IIA and 600nF for IIC.
Simple apparatus is defined as a device which neither generates nor stores
more than 1.2V, 0.1 A, 20
Wiring methods must be in accordance with the National Electric Code,
μJ, or 25 mW.
ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA RP12.6.
This module, 1797-OB4D, must be used with terminal base 1797-TB3 or
1797-TB3S.
Terminals 2, 3, 6, 7, 10, 11, 14, 15, 17 to 32, 36 to 39, and 46 to 49 shall
not be connected.
WARNING: Substitution of components may impair intrinsic safety.
AVERTISSEMENT: La subs
titution de composant peut compromettre la
securite intrinseque.

FM I/O Entity Parameters

If this product has the FM mark, it has been designed, evaluated, tested, and certified to meet the following standards:
Publication
1797-5.6 - June 2011
FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module 25
FM C1. No.3600:1998, Electrical Equipment for Use in Hazardous (Classified) Locations General Requirements
FM C1
. No.3610:1999, Intrinsically Safe Apparatus and Associated Apparatus for Use in Class I, II, III Division 1 Hazardous (Classified) Locations
FM C1. No
.3615:1989, Explosionproof Electrical Equipment General
Requirements
FM C1
. No.3810:1989, 1995, Electrical and Electronic Test, Measuring and Process Control Equipment
ANSI/NEMA 250
, 1991, Enclosures for Electrical Equipment
Wiring Methods
ring method 1: Each channel is wired separately.
Wi
Wiring method 2: Multiple channels in one cable, providing each
channel is separated in accordance with the National Electric Code (NEC).
Wiring Method
Wiring Method
1 and 2 Any one
Channel Te rm in al s Voc
(V)
channel (fo example, ch0)
0(+), 1(-) 27.4 110.0 - - A, B 0.105 3.0
r
Isc (mA)
Vt (V)
It
Groups Ca
(mA)
C, E 0.315 9.0
D, F, G 0.840 24.0
(μF)
La (mH)
Publication
1797-5.6 - June 2011
26 FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module
IMPORTANT
PWR
FLEX Ex digital
output I/O module
Indicators
Female bus
connection
Field wiring
terminals
Terminal base
Terminal base key
Male bus connection
Key position for terminal base insertion
42058
Ex
1797-OB4D
PWR
A terminal base may or may not have an I/O module installed.
Publication
1797-5.6 - June 2011
FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module 27
Hazardous (Classified) Location Class I, Zones 0, 1, & 2 Groups IIC, IIB, IIA Class I, Div. 1 & 2 Groups A, B, C, D Class II, Div. 1 & 2 Groups E, F, G Class III, Div. 1 & 2
Hazardous (Classified) Location Class I, Zones 1 Groups IIC, IIB, IIA Class I, Div. 1 Groups A, B, C, D
For connection to other modules refer to the General FM Certification Information on page 29-1 of 1797-6.5.6
.
From FM approved devices,
1797-PS2N
.
For connection to other modules refer to the General FM Certification Information on page 29-1 of 1797-6.5.6
.
1797-OB4D
16
Shield connection only
50
51
35
34
V
max
=5.8V
I
max
=400mA
C
i
=1350nF
L
i
=negligible
V
max
=9.5V
I
max
=1A
C
i
=negligible
L
i
=negligible
Male Bus Connector
33 40 41
42 43 44 45
0 (+)
Female Bus Connector
1 (-)
ch0
ch1
ch2
ch3
4 (+) 5 (-)
8 (+) 9 (-)
12 (+) 13 (-)
42059
Any Simple Apparatus or FM approved device with Entity Concept parameters (V
max
, I
max
, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in the table, Terminal Connections.
Terminal Connections
Ter m in al s Vt (V) It (mA) Groups Ca (μF) La (μH)
Male bus
5.8 400 A…G 3.0 3.0
connector
The entity concept allows interconnection of intrinsically safe apparatus
with associated apparatus not specifically examined in combination as a system when the approved values of V apparatus are less than or equal to V apparatus and the approved values of C are greater than C
+ C
i
apparatus.
cable
and Li + L
and I
oc
and I
max
and La of the associated apparatus
a
respectively for the intrinsically safe
cable
or Vt and It of the associated
sc
of the intrinsically safe
max
Publication
1797-5.6 - June 2011
28 FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module
The values of Lo and Co listed in the table above are allowed if one of the
following conditions is met:
• The total L
value or
L
o
• The total C
value.
C
o
The values of L
of the external circuit (excluding the cable) is < 1% of the
i
of the external circuit (excluding the cable) is < 1% of the
i
and Co listed in the table above shall be reduced to 50%
o
when both of the following conditions are met:
• The total L
value, and
L
o
• The total C
of the external circuit (excluding the cable) is 1% of the
i
of the external circuit (excluding the cable) is ≥ 1% of the
i
Co value.
The reduced capacitance of the external circuit (including cable) shall
Note: not be greater than 1µF for IIB and IIA and 600nF for IIC.
Simple apparatus is defined as a device which neither generates nor stores
more than 1.2V, 0.1 A, 20 μJ, or 25 mW.
Wiring methods must be in accordance with the National Electric Code,
ANSI/NFPA 70, Article 504 and 505. For additional information refer to ANSI/ISA RP12.6.
This module, 1797-OB4D, must be used with terminal base 1797-TB3 or
1797-TB3S.
Terminals 2, 3, 6, 7, 10, 11, 14, 15, 17 to 32, 36 to 39, and 46 to 49 shall
not be connected.
WARNING: Substitution of components may impair intrinsic safety.
Publication
1797-5.6 - June 2011
FLEX Ex I/O 24V DC 4 Non-Isolated Source Output Module 29
IMPORTANT
Voltage
mA
30
25
20
15
10
5
0
0 5 10 15 20 25 30 35 40 45 50
41313
WARNING Avoid electrostatic charging.
ADVERTÊNCIA! PREVENIR CONTRA O ACÚMULO DE CARGA ELETROSTÁTICA.

Output Voltage versus Current Capability

For detailed certification information, refer to the FLEX Ex System Certification Reference Manual, publication 1797-6.5.6
.
Publication
1797-5.6 - June 2011
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect Support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit
http://support.rockwellautomation.com
.
Installation Assistance
If you experience a problem with a hardware module within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your module up and running.
United States 1.440.646.3434 Monday – Friday, 8am – 5pm EST
Outside United States Please contact your local Rockwell Automation representative for
any technical support issues.
New Product Satisfaction Return
Rockwell tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning, it may need to be returned.
United States Contact your distributor. You must provide a Customer Support case
Outside United States Please contact your local Rockwell Automation representative for
Allen-Bradley, Rockwell Automation, FLEX Ex, ControlLogix, RSLinx, and TechConnect are trademarks of Rockwell Automation, Inc.
number (see phone number above to obtain one) to your distributor in order to complete the return process.
return procedure.
, you can find technical
Publication 1797-5.6 - June 2011 PN -110744
Supersedes Publication 1797-5.6 - February 2006 Copyright © 2011 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.
Loading...