Rockwell Automation 1797-IRT8 User Manual

FLEX Ex Thermocouple/ RTD/mV Input Module
Cat. No. 1797-IRT8
User Manual

Important User Information

Because of the variety of uses for the products described in this publication, those responsible for the application and use of this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements, including any applicable laws, regulations, codes and standards.
The illustrations, charts, sample programs and layout examples shown in this guide are intended solely for purposes of example. Since there are many variables and requirements associated with any particular installation, Allen-Bradley does not assume responsibility or liability (to include intellectual property liability) for actual use based upon the examples shown in this publication.
Allen-Bradley publication SGI-1.1, Safety Guidelines for the
Application, Installation and Maintenance of Solid-State Control
(available from your local Allen-Bradley office), describes some important differences between solid-state equipment and electromechanical devices that should be taken into consideration when applying products such as those described in this publication.
Reproduction of the contents of this copyrighted publication, in whole or part, without written permission of Rockwell Automation, is prohibited.
Throughout this manual we use notes to make you aware of safety considerations:
ATTENTION
Identifies information about practices or circumstances that can lead to personal injury or death, property damage or economic loss
!
Attention statements help you to:
identify a hazard
avoid a hazard
recognize the consequences
IMPORTANT
Allen-Bradley, FLEX Ex, FLEX I/O, and ControlNet Ex are trademarks of Rockwell Automation
ControlNet is a trademark of ControlNet International
Identifies information that is critical for successful application and understanding of the product.

Using This Manual

Preface

Why Read this Manual

Who Should Read this Manual

About the Vocabulary

What this Manual Contains

This manual shows you how to use your FLEX Ex thermocouple/ RTD/mV module with the ControlNet Ex network. The manual helps you install, program, and troubleshoot
your module.
You must be able to program and operate a ControlNet Ex product and ControlNet
In this manual, we refer to the:
1797-IRT8 as the “input module”. or “module.”
The following chart lists each chapter with its corresponding title and a brief overview of the topics covered in that chapter.
Chapter Title Contents
1 About the FLEX Ex Analog Modules Describes features, capabilities,
2 Understanding Configurable FLEX Ex
network to make efficient use of a FLEX Ex module.
thermocouple/RTD/mV Input Module Features
products and ControlNet
and hardware components Describes configurable features of
the input module
3 How to Install Your Thermocouple/
RTD/mV Module
4 Input, Output and Configuration Files
for the hermocouple/RTD/mV Module on the ControlNet network
5 Calibrating Your Module Lists the tools needed, and the
6 Applying FLEX Ex Analog Modules Learn how to evaluate, define,
7 Troubleshooting Your Module How to use the indicators to
Appendix Title Contents
A Specifications Outlines module specifications and
B Programming the FLEX Ex Analog
Module using RIO
3 Publication 1797-6.5.2 - February 2001
How to install and wire the module
Describes communication over the I/O backplane between the module and the adapter, and how data is mapped into the image table
methods used to calibrate the module
select, match and optimize your system.
troubleshoot your module
accuracy Shows ladder diagramming for
programming.
Using This Manual 4

For Additional Information

For additional information on FLEX Ex systems and modules, refer to the following docum en ts ,
Catalog
Number
1797 Series FLEX Ex Product Data 1797-2.1
1797 Series FLEX Ex System Overview 1797-2.2
1797 Series ControlNet Ex System Cable Guide 1797-6.2.1
1797 Series FLEX Ex System Certification
Reference Manual 1797-TB3 FLEX Ex Terminal Base 1797-5.1 1797-TB3S FLEX Ex Spring Clamp Terminal Base 1797-5.2 1797-OE8 FLEX Ex 8 Output Analog Module 1797-5.3 1797-6.5.1 1797-IRT8 FLEX Ex RTD/Thermocouple/mV
Module 1797-IE8 FLEX Ex 8 Input Analog Module 1797-5.5 1797-6.5.1
Description
Publications
Installation Instructions
(Product data)
(System overview)
(System guide) 1797-6.2.6
1797-5.4 1797-6.5.2
User Manual
1797-IE8NF FLEX Ex 8 Input Analog Module w/
Noise Filter 1797-OB4D 4 Output Module 1797-5.6 1797-IBN16 FLEX Ex NAMUR Digital Input Module 1797-5.7 1797-IJ2 2 Frequency Input Module 1797-5.9 1797-6.5.4 1797-PS2N
1797-PS2E 1797-ACNR15 ControlNetEx Adapter 1797-5.14 1797-6.2.1 1797-RPA, -RPFM Fiber Hub 1797-5.15 1797-6.2.1 1797-BIC Bus Isolator 1797-5.13 1797-TPR,
- TPRS, -TPYR,
-TPYS 1797-CE1S,
-CE3S, -CEFTN,
-CEFTE 1797-EXMK Marker Kit 1797-5.23 1797 FLEX Ex System Certification 1797-6.5.6
FLEX Ex Power Supplies 1797-5.12
FLEX Ex Taps 1797-5.18 1797-6.2.1
Interconnect Cables 1797-5.20
1797-5.31 1797-6.5.1

In Summary

Publication 1797-6.5.2 - Febr uary 2001
This preface gave you information on how to use this manual efficiently. The next chapter introduces you to the 1797-IRT8 Thermocouple/RTD / mV Inpu t module .
Preface Using This Manual

Table of Contents

About the FLEX Ex Thermocouple/ RTD/mV Input Module
Table of Contents
Important User Information. . . . . . . . . . . . . . . . . . . . . . . . . . 2
Why Read this Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Who Should Read this Manual. . . . . . . . . . . . . . . . . . . . . . . . 3
About the Vocabulary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
What this Manual Contains . . . . . . . . . . . . . . . . . . . . . . . . . . 3
For Additional Information . . . . . . . . . . . . . . . . . . . . . . . . . . 4
In Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Chapter 1
What this Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . 1-1
What the FLEX Ex Thermocouple/RTD/mV Modules Do. . . 1-1 How FLEX Ex Thermocouple/RTD/mV Modules
Communicate with Programmable Controllers . . . . . . . . . . 1-2
Events following Power-Up . . . . . . . . . . . . . . . . . . . . . 1-2
Features of Your Module. . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Using Alarms on the 1797-IRT8 Module . . . . . . . . . . . . . . . 1-3
Data Format Alarm Example. . . . . . . . . . . . . . . . . . . . . 1-4
Overrange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Underrange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Open Wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Cold Junction Compensation Alarm . . . . . . . . . . . . . . . . . . . . 1-4
Data Formats and Fault Modes . . . . . . . . . . . . . . . . . . . 1-5
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
Chapter 2 Understanding Configurable FLEX Ex Thermocouple/RTD/mV Input Module Features
i Publication 1797-6.5.2 - February 2001
What this Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . 2-1
Setting a FLEX Ex Thermocouple/RTD Module’s Operating
Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Input Type Select. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Sensor Type Select. . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Input Filter Cutoff . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
Data Format. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
Sensor Mode Select . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Preset Temperature Select . . . . . . . . . . . . . . . . . . . . . . 2-5
RTD Loop Resistance Offset Select . . . . . . . . . . . . . . . . 2-6
Fault Mode Select . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Using Module Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Overrange Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
Underrange Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
Fault Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-9
Table of Contents ii
How to Install Your FLEX Ex Thermocouple/RTD/mV Module
Chapter 3
What this Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . 3-1
Before You Install Your Analog Module. . . . . . . . . . . . . . . 3-1
Compliance to European Union Directives. . . . . . . . . . . . . 3-2
EMC Directive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Ex Directive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Installation in Zone 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
Electrostatic Charge. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Removal and Insertion
Under Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Installing the Module. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Mounting on a DIN Rail . . . . . . . . . . . . . . . . . . . . . . . . 3-3
Panel/Wall Mounting . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
Mounting the 1797-IRT8 Module on the Terminal
Base Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-8
Wiring the Terminal Base Units . . . . . . . . . . . . . . . . . . . . . 3-9
Connecting Wiring to the
FLEX Ex Thermocouple/RTD/mV Module . . . . . . . . . . . . . 3-10
Inputs/Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-10
Wiring connections for the 1797-IRT8 Module. . . . . . . . 3-11
Grounding the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13
Input, Status, Output and Configuration Files for the Thermocouple/RTD/mV Module on the ControlNet Network
Chapter 4
What this Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . 4-1
Using Programming Software in Your FLEX Ex Application. 4-2
About the ControlNet Ex Adapter. . . . . . . . . . . . . . . . . . . . 4-2
Communication Over the FLEX Ex Backplane . . . . . . . . . . 4-2
Scheduled Data-Transfer . . . . . . . . . . . . . . . . . . . . . . . 4-3
Unscheduled Data-Transfer . . . . . . . . . . . . . . . . . . . . . 4-3
Module I/O Mapping . . . . . . . . . . . . . . . . . . . . . . . . . . 4-3
I/O Structure. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
Adapter Status Word . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5
Fault State Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Device Actions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Communication Fault Behavior. . . . . . . . . . . . . . . . . . . 4-6
Idle State Behavior. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
Input Data Behavior upon Module Removal . . . . . . . . . 4-7
Thermocouple/RTD/mV Input Module (1797-IRT8) Image
Table Mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Bit/Word Description for the Thermocouple/RTD/mV Input
Module (1797-IRT8) . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
Publication 1797-6.5.2 - Febr uary 2001
Calibrating Your Module
Applying FLEX Ex Thermocouple/ RTD/mV Input Modules
Table of Contents iii
Chapter 5
What This Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . 5-1
When and How to Calibrate Your FLEX Ex
Thermocouple/RTD/mV Input Module. . . . . . . . . . . . . . . . 5-1
Tools and Equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Calibration Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
Chapter 6
What this Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Evaluate the Application . . . . . . . . . . . . . . . . . . . . . . . . . . 6-1
Define the Area Classification . . . . . . . . . . . . . . . . . . . . . . 6-2
Decide Classification Method . . . . . . . . . . . . . . . . . . . . 6-2
Determine Hazard . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2
Determine Temperature Rating. . . . . . . . . . . . . . . . . . . 6-2
Select Protection Method(s). . . . . . . . . . . . . . . . . . . . . . . . 6-3
Match Field Devices and I/O Modules . . . . . . . . . . . . . . . . 6-3
1797-IRT8 and Thermocouple and RTD Functional and IS
Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-3
Using the Entity Method. . . . . . . . . . . . . . . . . . . . . . . . 6-5
Entity Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-6
General Example . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-7
Interconnect Wiring 6-7
I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-8
Optimize Power Distribution . . . . . . . . . . . . . . . . . . . . . . . 6-8
Assigning Power Supplies . . . . . . . . . . . . . . . . . . . . . . 6-8
Power Supply Considerations. . . . . . . . . . . . . . . . . . . . 6-9
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-10
Troubleshooting the FLEX Ex Thermocouple/RTD/mV Input Module
Specifications
Chapter 7
What this Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-1
Repair. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Chapter Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-2
Appendix A
Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
CE/CENELEC I/O Entity Parameters . . . . . . . . . . . . . . . . . . A-2
UL, C-UL I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . A-3
Table 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3
Wiring Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3
Table 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3
FM I/O Entity Parameters . . . . . . . . . . . . . . . . . . . . . . . . . A-5
Wiring Methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5
Table 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6
Table 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6
Publication 1797-6.5.2 - February 2001
Table of Contents iv
Programming the FLEX Ex I/O Modules Using RIO
Index
Back Cover
Appendix B
What this Chapter Contains . . . . . . . . . . . . . . . . . . . . . . . . B-1
Enter Block Transfer
Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1
Using the PLC-5C Processor. . . . . . . . . . . . . . . . . . . . . . . . B-2
Publication 1797-6.5.2 - Febr uary 2001
Chapter

About the FLEX Ex Thermocouple/RTD/mV Input Module

1

What this Chapter Contains

What the FLEX Ex Thermocouple/RTD/mV Modules Do

Read this chapter to familiarize yourself with the 1797-IRT8 input module.
For information on: See page:
What the FLEX Ex Thermocouple/ RTD/mV Modules Do
How FLEX Ex Thermocouple/RTD/mV Modules Communicate with Programmable Controllers
Features of Your Module 1-2 Chapter Summary 1-5
The 1797-IRT8 module accepts up to 8 thermocouple, RTD or mV inputs. The inputs are nonisolated and are selected with analog multiplexers which have a common-mode input range of -0.5 to +3.6 volts. The inputs will accept a millivolt or resistive input. Default input
spans are –40.00mV to +100.00mV or 0.00 to 500.00 ohms. Fault Indicators are located on the field side.
No switches or jumpers are us ed on t he th ermocouple/RTD/mV input module. The Inputs have both fixed hardware filters and selectable firmware digital filters.
1-1
1-2
This module offers:
local microprocessor intelligence for advanced features
full functionality without switches or jumpers
multiple data ranges that can be independently programmed in
channel groups
lead breakage detection
overrange/underrange alarms
as well as a host of other module features.
1 Publication 1797-6.5.2 - February 2001
1-2 About the FLEX Ex Thermocouple/RTD/mV Input Module

How FLEX Ex Thermocouple/RTD/mV Modules Communicate with Programmable Controllers

FLEX Ex thermocouple/RTD/mV modules provide best utility when used with ControlNet Ex products on the Co ntrolNet network. Data connections are established between the I/O module and an Allen-Bradley programmable controller to transfer information between the two at a scheduled rate.
Input module information is then automatically made available in the PLC data table.
When the data connection is established, configuration information for the module is automatically transferred to it via the network.
Events following Power-Up
You must apply intrinsically safe +/-V power to your FLEX Ex I/O modules. The following sequence of events occurs after power has initially been applied to your module:
1. The module begins an interal diagnostic check. The channel 0 LED
indicator turns ON to indicate the check has begun. The indicator turns OFF when th e che ck is finish ed.

Features of Your Module

2. After the diagnostic check, module configuration information,
selected by the user and downloaded over the network, is applied by the module.
For more information on configuration options, see Chapter 2.
3. Following the module configuration download for the 1797-IRT8
module, the module begins producing runtime data for the PLC.
4. If any diagnostics or alarms are generated during normal module
operation, the data is returned to the PLC.
The module label identifies the keyswitch position, wiring and module type. Use the removable label to note individual designations per your application.
Publication 1797-6.5.2 - Febr uary 2001
About the FLEX Ex Thermocouple/RTD/mV Input Module 1-3
Indicators
Indicators are provided to identify input or output fault conditions, and to show when power is applied to the module.
1797-IRT8
Module Type

Using Alarms on the 1797-IRT8 Module

Removable Label
Keyswitch Position Indicator (#2)
Power On Indicator
40070
Input Designato rs
1797-IRT8
Ex
PWR
The 1797-IRT8 FLEX Ex module is capable of generating four alarms:
Underrange
Overrange
Fault (open wire)
Cold junction compensation Fault
These alarm conditions are described in general terms and as they relate to bits on the FLEX Ex I/O module on the following pages. The graphic below shows at what values these alarms are generated for Data Format 4.
Publication 1797-6.5.2 - February 2001
1-4 About the FLEX Ex Thermocouple/RTD/mV Input Module
Data Format Alarm Example
In this example, the normal active data range is 4-20mA. The alarms are generated in three overlapping bands.
PHYSICAL INPUT SIGNAL RANGE
CJC fault
underrange
overrange
CJC fault
Maximum
Measureable
Value
open w i re fault
Channel Data
Forced to
Maximum for Type
Minumum
Value for
Sensor
Type
normal signal range
Maximum
Value for
Sensor
Type
Overrange
If the input is greater than the maximum temperature of the thermocouple or RTD range, millivolt (+100mV), or resistance (500W) the overrange bit for that channel will be set.
Underrange
If the input is less than the minimum temperature of the thermocouple or RTD range, millivolt (-40mV), or resistance (0W) the underrange bit for that channel will be set.
Publication 1797-6.5.2 - Febr uary 2001
Open Wire
Individual channel fault alarm for broken wire. If a broken wire/ detached lead is detected, the data value is forced to maximum. In RTD/W mode, input levels above 540W will set this bit; in thermocouple/mV mode, input levels above 210mV will set this bit.
Cold Junction Compensation Alarm
Broken or detached lead or shorted lead detection is included for CJCs. This detection is only available when the input type selected is thermocouple and sensor mode is set to CJC compensation.
When either CJC fails its fault is reported. Both CJCs ae normally used in compensation calculations. If one CJC fails, calculations use the remaining good device. If both fail, calculations use the last good value.
About the FLEX Ex Thermocouple/RTD/mV Input Module 1-5
Data Formats and Fault Modes
The tables below shows the bit settings for the data formats and fault modes for your FLEX Ex thermocouple/RTD/mV module.
Data Formats
Bit 11 10 09 08 Data type for channels 0 thru 7
0000 0001 0010 0 0 1 1 -32767 to +32767
0 1 0 0 0 to 65535 0101 thru 1111 not used
Note: Module defaults to -4000 to 10,000 in millivolt mode, and 0 to 5000 in ohms mode
o
C (see note)
o
F (see note)
o
K (see note)

Chapter Summary

Fault Mode
Bit 06 Fault enable for channels 0-3
07 Fault enable for channels 4-7
0 = disabled 1 = enable wire-off detection
In this chapter, we told you about the FLEX Ex system and the thermocouple/RTD/mV module, and how it communicates with programmable controllers.
Publication 1797-6.5.2 - February 2001
1-6 About the FLEX Ex Thermocouple/RTD/mV Input Module
Publication 1797-6.5.2 - Febr uary 2001
Understanding Configurable FLEX Ex Thermocouple/RTD/mV Input Module Features
Chapter
2

What this Chapter Contains

Read this chapter to familiarize yourself with configurable features on the 1797-IRT8 module.
For information on: See page:
Setting a FLEX Ex Thermocouple/RTD
Module’s Operating Status
Input Type Select 2-2 Sensor Type Select 2-2 Data Format 2-4 Preset Temperature Select 2-5 RTD Loop Resistance Offset Select 2-6 Fault Mode Select 2-7
Using Module Alarms 2-7
Overrange Alarm 2-7 Underrange Alarm 2-8 Fault Alarm 2-9
Chapter Summary 2-9
This chapter describes the following features:
2-2
Input type
Sensor type
Data formats
Preset temperature selection
RTD loop resistance offset selections
F a ult mode
Overrange Alarms
Und errange alarms
Fault alarms
Important:You must use your programming software to configure
these features. A brief description of each module feature is provided in this chapter, but you must use the online help included with your programming software to perform specific configuration.
1 Publication 1797-6.5.2 - February 2001
2-2 Understanding Configurable FLEX Ex Thermocou ple/RTD/mV Input Module Features
Setting a FLEX Ex Thermocouple/RTD
Module’s Operating Status
Input Type Select
Select the thermocouple or RTD mode for input channel groups 0-3 and 4-7. If 2 is selected, the module defaults to thermocouple. If 3 is selected, the module defaults to RTD.
Range: 0 = thermocouple, 1 = RTD, 2 and 3 not used
Bits 06-07 Input Type Select
Bit 07 06 Input type sel ect ion for channels 0-3
0 0 Thermocouple 01RTD 10 11
Input type select for channels 4 through 7 use bits in word 1.
Not used
Sensor Type Select
Select the type of sensor for input channel groups 0-3 and 4-7. Thermocouple mode 0 = mV, 1 = B, 2 = E, 3 = J, 4 = K, 5 = TXK/
XK(L), 6 = N, 7 = R, 8 = S, 9 = T, 10-15 not used. RTD mode: 0 = W , 1 = Pt100 IEC 751 Amen dment 2, 2 = Pt200 IEC 751
Amendment 2, 3 = Pt1 00 JIS C1604-1989, 4 = Pt200 JIS C1604- 1989, 5 = Ni100 DIN 43760-1987, 6 = Ni200 DIN 4376 0-1987, 7 = Ni120 Min co, 8 = Cu10 Minco, 9-15 not used.
If unused settings are chosen, diagnostic status “2 = configuration failure” will be set, and the last valid configuration will be used. The default = 0.
Publication 1797-6.5.2 - Febr uary 2001
Understanding Configurable FLEX Ex Thermocouple/RTD/mV Input Module Features 2-3
Bits 00-03 Sensor Type (Thermocouple or RTD)
RTD Type
Bit03020100Sensor type for channels 0 through 3
0000Resistance (default) 0001100 ohm Pt α = 0.00385 Euro (–200 to +870°C)
0010200 ohm Pt α = 0.00385 Euro (–200 to +400°C) 0011100 ohm Pt α = 0.003916 U.S. (–200 to +630°C) 0100200 ohm Pt α = 0.003916 U.S. (–200 to +400°C) 0101100 ohm Nickel (60 to +250°C) 0110200 ohm Nickel (60 to +200°C) 0111120 ohm Nickel (80 to +320°C) 100010 ohm Copper (200 to +260°C)
1001 through 1111 not used
Bits 00-03 Thermocouple Type
Bit03020100Sensor type for channels 0 through 3
0000mV (default) 0001B 300 to 1800°C (572 to 3272°F) 0010E –250 to 1000°C (–418 to 1832°F) 0011J –210 to 1200°C (–346 to 2192°F) 0100K –250 to 1372°C (–418 to 2502°F) 0101L –200 to 800°C (–328 to 1472°F) 0110N –250 to 1300°C (–418 to 2372°F) 0111R –0 to 1768°C (32 to 3214°F) 1000S –0 to 1768°C (32 to 3214°F) 1001T –250 to 400°C (–418 to 752°F)
1010 through 1111 not used
Input Filter Cutoff
A series of eight available input filters – filters are hardware and software – allow you to choose the best rolloff frequency for input channels on your I/O module. When choosing a filter, remember that time frequency rolloff may affect your input signal’s accuracy.
For example, in configuration word 0, if you choose the fastest time frequency of 600Hz (hardware filter only), little noise is added, but the slowest frequency of 0.2Hz will provide the most accurate process noise filtering. See below to decide which input filter to use in your application:
Publication 1797-6.5.2 - February 2001
2-4 Understanding Configurable FLEX Ex Thermocou ple/RTD/mV Input Module Features
Input Filter Cutoff bits
Bit020100Definition
0 0 0 Hardware filtering only (default filtering) 600Hz (1.7ms) 0 0 1 40Hz (25ms) 0 1 0 10Hz (100ms) 0 1 1 4Hz (250ms) 1 0 0 2Hz (500ms) 1011Hz(1s)
1100.5Hz(2s)
1110.2Hz(5s)
Choose the best input filter cutoff in your programming software.
Data Format
You must choose a module data format in your user program. Select the format by setting bits as shown below. Note that this parameter affects channel accuracy.
Data format – module defaults to –4000 to 10000 in millivolt mode, and 0 to 5000 in ohms mode
Bit 11 10 09 08 Data type for channels 0-7
0000°C 0001°F 0010×K 0 0 1 1 –32767 to +32767 0 1 0 0 0 to 65535
0101 through 1111 not used
o
C, oF and oK will have formats appropriate to the selected thermocouple or RTD range (e.g. -xxxx to +xxxx with 1 decimal place implied - 3500 = 350.0). For Cu10 RTD, 2 decimal points are implied.
If using mV, data format defaults to -4000 to +10000 (2 decimal points implied (e.g. -40 to 100.00). If using W mode selection, data format defaults to 0 to 5000 (1 decimal point implied, e.g. 0.- to 500.0).
In the thermocouple and RTD modes, if unused data formats are
o
chosen, the module will default to
C.
Publication 1797-6.5.2 - Febr uary 2001
Understanding Configurable FLEX Ex Thermocouple/RTD/mV Input Module Features 2-5
Sensor Mode Select
Selects the sensor mode for input channels 0-3 and 4-7. If using cold junction compensation, both CJCs must be installed. The
difference between the CJCs will be linearly apportioned to each thermocouple channel based on its position across the base. If one CJC is broken or missing, the remaining CJC is used t o compensate all channels. The appropriate CJC alarm will be set in this case. If the second CJC fails, the last valid reading is frozen for compensation use. The second CJC alarm will also be set.
When using only channels 0-3 for thermocouples, connect the CJCs to terminals 5 and 12. If only using channels 4-7, connect the CJCs to terminals 22 and 29. If all channels are configured for thermocouples, connect the CJCs to terminals 5 and 29.
When CJC thermistor temperature compensation is sele cted for one channel group, all channels configured for thermocouple inputs will use the CJC compensation.
05 04 Sensor mode for channels 0 thru 3
Bit
13 12 Sensor mode for channels 4 thru 7
Thermocoupl e Mode
00 0 1 Internal compensation - Uses the value selected for reference junction
10 1 1 Differential measurement between 2 channels
0 0 2-wire RTD - no compensation 0 1 2-wire RTD with user compensation 1 0 3-wire RTD 1 1 4-wire RTD
External compensation - uses cold junction sensors
o
No compensation (Data is referenced to 0
RTD Mode
C)
Preset Temperature Select
This parameter is used if Input Type Select is set to thermocouple and Sensor Mode Select is set to fixed compensation. This parameter then sets a fixed reference temperature used to compensate all thermocouple channels.
The default = 0.
Publication 1797-6.5.2 - February 2001
2-6 Understanding Configurable FLEX Ex Thermocou ple/RTD/mV Input Module Features
Bits 03-05 Reference Junction – used when input type is set to thermocouple and sensor
mode is set to fixed compensation. Sets a fixed reference junction to compensate all thermocouple channels.
Bit050403Reference Junction
0000°C 00120°C 01025°C 01130°C 10040°C 10150°C 11060°C 11170°C
RTD Loop Resistance Offset Select
This parameter is used if Input Type Select is set to RTD and Sensor Mode Select is set to 2-wire with loop resistance compensation. This parameter then sets total RTD loop resistance compensation for each RTD channel. Either the value stored for each channel during calibration is used to compensate the module RTD channels, or one of 3 fixed values is used to compensate module RTD channels.
This parameter is disabled for Cu10 RTDs.
00-15 (00-17) RTD loop resistance offset select bits – used input type is set to RTD and sensor
mode select is set to 2-wire with loop resistance compensation. Allows you to set the type of RTD loop resistance compensation used for all RTDs or one of three fixed values for all channels. NOTE: Not applicable to 10W copper RTD, which defaults to 0W.
Bit 01 00 RTD channel 0 Bit 03 02 RTD channel 1 Bit 05 04 RTD channel 2 Bit 07 06 RTD channel 3 Bit 09 08 RTD channel 4 Bit 11 10 RTD channel 5 Bit 13 12 RTD channel 6 Bit 15 14 RTD channel 7
0 0 Use channel loop compensation value stored during
calibration procedure for 2-wire RTD (default = 0W) 015W 1 0 10W 1 1 15W
Range: 0 = use channel loop compensation value determined and stored during calibration procedure for 2-wire RTD, 1 = 5, 2 = 10Ω, 3= 15Ω. Default = 0.
Publication 1797-6.5.2 - Febr uary 2001
Understanding Configurable FLEX Ex Thermocouple/RTD/mV Input Module Features 2-7
Fault Mode Select
Select whether the channel fault detection is enabled or disabled for channels 0-3 and 4-7.
Range: 0 = disable, 1 = fault detection enabled (wire off, mV overvoltage, RTD open). Default = 0.

Using Module Alarms

Bits 06-07 Fault Mode bits – when a bit is set (1), fault mode is enabled for that channel.
Bit 06 corresponds to channels 0-3; bi t 07 corresponds to channels 4-7. 0 = disabled 1 = enable wire-off detection
FLEX Ex I/O modules are capable of generating four alarms:
Overrange
Underrange
Fault
Cold Junction Compensation (CJC) Fault
These alarm conditions are described in general terms and as they relate to bits on the FL EX Ex I/O module on the following pages.
Overrange Alarm
The channel overrange alarm is set if the input is greater than the maximum temperature (thermocouple or RTD range dependent), millivolt (+100mV) or resistance (500Ω) range value.
Range: 0 = normal, 1 = input overrange. Default = 0. This alarm stays active at any value above 100% of range and is
always enabled by the module. Refer to the figure below for the sensor dependent signal which causes this alarm to be generated.
Publication 1797-6.5.2 - February 2001
2-8 Understanding Configurable FLEX Ex Thermocou ple/RTD/mV Input Module Features
IRT8 Specific alarming performance
PHYSICA L I NPUT SIGNAL RANGE
underran ge
CJC fault
Sensor Type
IEC PT100 IEC PT200
JIS PT100 JIS PT200
DIN Ni100 DIN Ni200
Minco Ni120
Minco Cu10
0-500 Resistance
millivolt ~ 210mV
B E
J
K
N R
S T
Cold Junction Compensation
normal signal range
-200C + 870C
-200C +400C
-200C +630C
-200C +400C
-60C +250C
-60C +200C
-80C +320C
-200C +260C 0ohm 500ohm
-40mV +100mV 300C +1800C
-250C +1000C
-210C +1200C
-250C
-200C + 800CTXK/XK(L)
-250C +1300C 0C
0C
-250C + 400C
-20C 100C
+1372C
+1768C +1768C
overrange
CJC faul t
open w i re f ault
~ 520ohm equivalent ~ 520ohm equivalent
~ 520ohm equivalent ~ 520ohm equivalent ~ 520ohm equivalent ~ 520ohm equivalent
~ 520ohm equivalent ~ 520ohm equivalent
~ 520ohm
~ 210mV equivalent ~ 210mV equivalent ~ 210mV equivalent ~ 210mV equivalent ~ 210mV equivalent ~ 210mV equivalent ~ 210mV equivalent
~ 210mV equivalent ~ 210mV equivalent
Channel
Data
Forced
to
Maximum
for Type
Publication 1797-6.5.2 - Febr uary 2001
Underrange A l arm
The channel underrange alarm is set if the input is less than the minimum temperature (thermocouple or RTD range dependent), millivolt (-40mV) or resistance (0) range value.
Range: 0 = normal, 1 = input overrange. Default = 0. This alarm stays active at any value below 0% of range and is always
enabled by the module. Range: 0 = normal, 1 = input overrange. Default = 0.
Understanding Configurable FLEX Ex Thermocouple/RTD/mV Input Module Features 2-9
Fault Alarm
The module has individual channel fault alarms for a broken or detached wire. In any mode, if a broken/detached lead is detected, the data value is forced to maximum. Once the alarm is issued, it remains active as long as the input signal is faulted.
In mV mode, for input levels above 210mV, this bit is set. In RTD mode, an open input will set this bit. Range: 0 = normal,1 = wire off, excessive input fault detected. Default = 0.

Chapter Summary

In this chapter , we told you about the F LEX Ex sys tem and the analog I/O modules, and how they communicate with programmable controllers.
Publication 1797-6.5.2 - February 2001
2-10 Understanding Configurable FLEX Ex Thermocouple/RTD/mV Input Module Features
Publication 1797-6.5.2 - Febr uary 2001
Chapter

How to Install Your FLEX Ex Thermocouple/ RTD/mV Module

3

What this Chapter Contains

Before You Install Your Analog Module

Read this chapter to install the 1797-IRT8 thermocouple/RTD/mV module.
For information on: See page:
Before You Install Your Analog Module
Compliance to European Union Directives
Installation in Zone 1 3-2 Removal and Insertion Under Power 3-3 Installing the Module 3-3 Connecting Wiring to the FLEX Ex
Thermocouple/RTD/mV Module Grounding the Module 3-13 Chapter Summary 3-13
Before installing your FLEX Ex analog module:
You need to: As described under:
Verify that the module will be installed in a suitable metal enclosure
3-1
3-2
3-10
Installation in Zone 1, page 3-2
Position the keyswitch on the terminal base
ATTENTION
These modules do not receive primary operational power from the backplane. +/-V dc power must be applied to your module before installation. If power is not applied, the module position will appear to the adapter as an empty slot in your chassis.
Installing the Module, page 3-8
!
1 Publication 1797-6.5.2 - February 2001
3-2 How to Install Your FLEX Ex Thermocouple/RTD/mV Module

Compliance to European Union Directives

If this product has the CE mark, it is approved for installation within the European and EEA regions. It has been designed and tested to meet the following directives.
EMC Directive
This product is tested to meet the Council Directive 89/336/EC Electromagnetic Compatibility (EMC) by applying the following standards, in whole or in part, documented in a technical construction file:
EN 50081-2 EMC - Generic Emission Standard, Part 2 - Industrial
Environment EN 50082-2 EMC - Generic Immunity Standard, Part 2 - Industrial
Environment
This product is intended for use in an industrial environment.
Ex Directive

Installation in Zone 1

This product is tested to meet the Council Directive 94/9/EC (ATEX 100a) Equipment and Protective Systems Intended for Use in Potentially Explosive Atmospheres by applying the following standards:
EN50014:1992, Electrical Apparatus for Potentially Explosive
Atmospheres EN50020:1994, Electrical Apparatus for Potentially Explosive
Atmospheres - Intrinsic Safety “i” prEN50284:1997, Special requirements for construction, test and
marking of electrical apparatus of equipment group II, category 1G
This module must not be exposed to the environment. Provide a suitable metal enclosure.
ATTENTION
This module cannot be used in an intrinsically safe environment after it has been exposed to non-intrinsically safe signals.
Publication 1797-6.5.2 - Febr uary 2001
!
Loading...
+ 58 hidden pages