Rockwell Automation 1797-IE8, 1797-IE8H, 1797-IE8NF Installation Instructions Manual

Installation Instructions
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
Catalog Numbers 1797-IE8, 1797-IE8H, 1797-IE8NF
Top ic Page
Important User Information 3 Environment and Enclosure 4 Prevent Electrostatic Discharge 5 Removal and Insertion Under Power 5 EMC Directive 6 Installation in Zone 1 7 Installation in Zone 22 7 Install the Module 8 Wire the Module to a 1797-TB3 or 1797-TB3S Terminal Base Unit 10 Ground the Module 12 Inputs 12 1797-IE8 and 1797-IE8NF Input Map (Read Words) 16 1797-IE8H Input Map (Read Words) 17 1797-IE8H Input Map (Read Words) 18 1797-IE8 and 1797-IE8NF Output Map (Write Words) 19 1797-IE8H Output Configuration Map 19 Fault Mode - Write Words 0 and 1 22 “Add-on” Filter Selections - Write Words 0 and 1 or Filter Cutoff Selections 22
Top ic Pa ge
Remote Transmitter Error Up/Down - Write Words 0 and 1 22 Data Format - Write Words 0 and 1 22 Data Format - Write Words 2 and 3 23 Error Level 0.1 mA Steps 24 1797-IE8H Secondary Master Enable (SME)/ Primary Master Inhibit (PMI) 25 Byte Order Configuration 26 Digital Filter 26 HART Input Data 30 HART Input Data Descriptions 34 HART Read Back Threshold 35 Square Root Threshold 35 Field Descriptions 27 Repair 36 Status Indicators 36 Specifications 37 Entity Parameters 41
Publication
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 3
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD

Important User Information

Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication
http://literature.rockwellautomation.com) describes some important differences between solid state
equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable. In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment. The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams. No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual. Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited. Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
SGI-1.1 available from your local Rockwell Automation sales office or online at
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequences.
Labels may be located on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present.
Labels may be located on or inside the equipment (for example, drive or motor) to alert people that surfaces may be dangerous temperatures.
Publication
1797-5.5 - September 2011
ATTENTION
ATTENTION

Environment and Enclosure

This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating. This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbances. This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications. In addition to this publication, see:
Industrial Automation Wiring and Grounding Guidelines, for additional
installation requirements, Allen-Bradley publication 1770-4.1
NEMA Standards 250 and IEC 60529, as applicable, for explanations of
the degrees of protection provided by different types of enclosure.
This product is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum or plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding. Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately.
.
Publication
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 5
ATTENTION
WARNING

Prevent Electrostatic Discharge

This equipment is sensitive to electrostatic discharge, which can cause internal damage and affect normal operation. Follow these guidelines when you handle this equipment:
Touch a grounded object to discharge potential static.
Wear an approved grounding wriststrap.
Do not touch connectors or pins on component boards.
Do not touch circuit components inside the equipment.
Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in
use.
Post a sign near these modules:
Attention! Avoid electrostatic charging. ATENÇÃO! PREVENIR CONTRA O ACÚMULO DE CARGA
For your convenience, a sign that can be cut out and posted is included in this publication.
ELETROSTÁTICA

Removal and Insertion Under Power

These modules are designed so you can remove and insert them under power. However, take special care when removing or inserting modules in an
active process. I/O attached to any module being removed or inserted can change states due to its input/output signal changing conditions. If you insert or remove the terminal base while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Publication
1797-5.5 - September 2011

European Communities (EC) Directive Compliance

If this product has the CE mark it is approved for installation within the European Union and EEA regions. It has been designed and tested to meet the following directives.

EMC Directive

These products are tested to meet the Council Directive 2004/108/EC by applying the following standards:
EN 61000-6-4:2007, Electromagnetic Compatibility (EMC) - Part 6-4:
Generic Standard for Industrial Environments (Class A)
EN 61000-6-2:2005, Electromagnetic Compatibility (EMC) - Part 6-2:
Generic Standards - Immunity for Industrial Environments
EN61326-1:2006 (Industrial), Electrical Equipment For
Measurement, Control, and Laboratory Use - Industrial EMC Requirements
ATEX Directive
These products are tested in conjunction with associated I/O modules to meet the Council Directive 94/9/EC (ATEX) Equipment and Protective Systems Intended for Use in Potentially Explosive Atmospheres by applying the following standards:
EN60079-11:2007, Explosive atmospheres - Part 11 : equipment
protection by intrinsic safety "i"
EN60079-0:2006, Electrical apparatus for explosive gas atmospheres -
Part 0 : general requirements
EN 60079-26 : 2004, Electrical apparatus for explosive gas
atmospheres - Part 26 : construction, test and marking of Group II Category 1 G electrical apparatus
EN61241-0 : 2006, Electrical apparatus for use in the presence of
combustible dust - Part 0: General requirements
EN61241-11:2006, Electrical apparatus for use in the presence of
combustible dust – Part 11: Protection by intrinsic safety 'iD'
Publication
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 7
WARNING

Installation in Zone 1

These modules must not be exposed to the environment. Provide a suitable metal enclosure. This module has a protection factor of IP20.
These modules cannot be used in an intrinsically safe environment after they have been exposed to non-intrinsically safe signals.

Installation in Zone 22

When the module is installed in Zone 22, the following cabinets must be used: IVK2-ISRPI-V16LC; IVK2-ISRPI-V8HYW; or IVK2-ISRPI-V8LC. These cabinets can be purchased from:
Pepperl+Fuchs GmbH Konigsberger Allee 85-87, D-68307 Mannheim, Germany Attn: PA Sales Dept. Kirsten Becker Telephone +49 776 1298 www.pepperl-fuchs.com
The IS-RPI cabinets (type IVK2-ISRPI-V8LC, IVK2-ISRPI-V8HYW, or IVK2-ISPRI-V16LC) ensures the basic protection for the intrinsically safe apparatus of the FLEX Ex system for use in Zone 22. It corresponds with category 3D according to RL 94/9 EG and with the type label marked with the following information:
Pepperl+Fuchs GmbH 68307 Mannheim IVK2-ISRPI-V8LC (or IVK2-ISRPI-V8HYW or IVK2-ISRPI-V16LC)
II 3 D Ex tD A22 IP54 T70 °C X CE Serial (manufacturing) number Model year
Publication
1797-5.5 - September 2011
ATTENTION
ATTENTION
4
3
7
1
8
2
6
5
Label here or under here
40231

Install the Module

Read this for information about how to install the module which must be used with a 1797-TB3 or 1797-TB3S intrinsically safe terminal base unit.
This equipmment is considered Group 1, Class A industrial equipement
according to IEC/CISPR Publication 11. Without appropriate precautions, there
may be potential difficulties ensuring electromagnetic compatibility in other
environments due to conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be mounted within
an enclosure that is suitably designed for those specific environmental
conditions that will be present and appropriately designed to prevent personal
injury resulting from accessiblity to live parts. The interior of the enclosure must
be accessible only by the use of a tool. Subsequent sections of this publication
may contain additional infromation regarding specific enclosure type ratings
that are required to comply with certain productsafety certifications.
During mounting of all devices, be sure that all debris (such as metal chips or
wire strands) is kept from falling into the module. Debris that falls into the
module could cause damage on power up.
Publication
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 9
ATTENTION
IMPORTANT
IMPORTANT
IMPORTANT
Do not remove or replace a Terminal Base unit while power is applied. Interruption of the backplane can result in unintentional operation or machine motion.
To install the module on a 1797 terminal base, see the figure and complete the following.
1. Rotate keyswitch (1) on terminal base unit (2) clockwise to position 3 (1797-IE8 and 1797-IE8NF) or position 8 (1797-IE8H) as required for the particular type of module.
Do not change the position of the keyswitch after wiring the terminal base unit.
2. Make certain the flexbus connector (3) is pushed all the way to the left to connect with the neighboring terminal base/adapter.
You cannot install the module unless the connector is fully extended.
3. Make sure the pins on the bottom of the module are straight so they align properly with the connector in the terminal base unit.
4. Position the module (4) with its alignment bar (5) aligned with the groove (6) on the terminal base.
5. Press firmly and evenly to seat the module in the terminal base unit, noting that the module is seated when the latching mechanism (7) is locked into the module.
6. Remove cap plug (8) and attach another intrinsically safe terminal base unit to the right of this terminal base unit if required.
Make certain that you only connect terminal base units to other intrinsically safe system modules or adapters to maintain the integrity of the intrinsically safe backplane.
Publication
1797-5.5 - September 2011
10 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
WARNING
41307
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
16 17 18 19 20 21 22 23 24 25 26 27
2
8
29 30 31 32 33
34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51
Row A
Row B
Row C
+- +-+- +-
+-+-+-+-
Ch 0 Ch 1 Ch 2 Ch 3
Ch 7Ch 6Ch 5Ch 4
+V
-V +V
-V
40071
sig sig sig sig
sigsigsigsig
No connections allowed to terminals 16, 33, 36, 40, 41, 42, 43, 44, 45, and 49.

Wire the Module to a 1797-TB3 or 1797-TB3S Terminal Base Unit

If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Module Wiring
1. Connect the individual input wiring to (+) terminals (0, 4, 8, 12) on the 0…15 row (A) and on the 16…33 row (B) (terminals 17, 21, 25,
29) as indicated in the table,
Wire Connections on page 11.
2. Connect the associated input to the corresponding (sig) terminal (1, 5, 9, 13) on the 0…15 row (A), and on the 16…33 row (B) (terminals 18, 22, 26, 30) for each input as indicated in the table,
on page 11.
Publication
1797-5.5 - September 2011
Wire Connections
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 11
WARNING
ATTENTION
3. For other configurations, see the wiring diagrams in the section,
Inputs on page 12.
4. Connect +V DC power to terminal 34 on the 34…51 row (C).
5. Connect -V to terminal 35 on the 34…51 row (C).
Make certain that you power these modules with an intrinsically safe power supply. Do not exceed the values listed in the specifications for these modules. If you connect or disconnect wiring while the field-side power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
6. If continuing power to the next terminal base unit, connect a jumper from terminal 50 (+V) on this base unit to terminal 34 on the next base unit.
7. If continuing common to the next terminal base unit, connect a jumper from terminal 51 (-V) on this base unit to terminal 35 on the next base unit.
To reduce susceptibility to noise, power analog modules and digital modules from separate power supplies.
Wire Connections
Input Input
Source
Input 0 A-0 A-1 A-2 Input 4 B-17 B-18 B-19 Input 1 A-4 A-5 A-6 Input 5 B-21 B-22 B-23 Input 2 A-8 A-9 A-10 Input 6 B-25 B-26 B-27 Input 3 A-12 A-13 A-14 Input 7 B-29 B-30 B-31 +V Terminals 34 and 50
-V Terminals 35 and 51
Input Signal
Input Return
Input Input
Source
Publication
Input Signal
1797-5.5 - September 2011
Input Return
12 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
ATTENTION
IMPORTANT
44862
Do not use the unused terminals on this terminal base unit. Using these terminals as supporting terminals can result in damage to the module, or unintended operation of your system, or both.

Ground the Module

All I/O wiring must use shielded wire. Shields must be terminated external to the module, such as bus bars and shield-terminating feed throughs.

Inputs

Each input can be operated from an analog field device signal. Do not apply any nonintrinsically safe signals to these modules.
When using an intrinsically safe electrical apparatus according to EN50020, the European Community directives and regulations must be followed.
The channels in these modules are electrically connected to each other and have a common plus-line.
Publication
When interconnecting several lines, you must consider the total accumulated power and check for intrinsic safety.
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 13
Flexbus
Bus
uC
+V
-V
+
Sig
4…20 mA Xmit
4…20 mA Xmit
I
P
P
I
40072
22 Ω
273 Ω
21.5V
-
P
I
Isolated Power 4…20 mA Xmit
1797-IE8 and 1797-IE8NF
Flexbus
Bus
uC
+V
-V
+
Sig
4…20 mA Xmit
4…20 mA Xmit
I
P
P
I
43852
10 Ω
-
1797-IE8H
HART
Modem
273 Ω
23.7V
Publication
1797-5.5 - September 2011
14 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
Voltage
mA
16 14 12 10 8
6 4
0 5 10 15 20 25
43002
2 0
18
20
22
V DC
1797-IE8 and 1797-IE8NF Field Transmitter Supply Characteristic
The field transmitter supply can be modeled as a 21.5V source with a 273 Ω series resistance. (See the following graph.) This provides a simple and useful mechanism to determine transmitter and loop compatibility.
The actual transmitter supply contains three ranges of impedance with the following characteristics:
The output voltage is 21.5V for load currents of 0 mA.
If the load is more than 680 Ω but less than ∞Ω, the transmitter supply is in a constant resistance region (273 Ω).
For load impedance between 0 and 680 Ω, the transmitter supply
current is in constant current mode (22 mA).
If an intrinsic safety fault occurs in the field transmitter supply of any channel, every channel’s field transmitter power is shutdown.
The following graph depicts the typical transmitter load characteristic.
The normal module field side power consumption is 7.5 W when all channel
21.5V sources (+) are loaded. If field devices are used that are powered separately, the module field-side power consumption can be determined by Field_Side_Power = 9.5V x (300 mA + n x 55 mA). Where n is the number of field devices that are supplied by the 1797-IE8 or 1797-IE8NF.
Publication
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 15
Voltage
mA
17
04 812 2024
43850
0
24 23
16 15 14
3 2 1
16
V DC
1797-IE8H Field Transmitter Supply Characteristic
The field transmitter supply can be modeled as a 23.7V source with a 273 Ω series resistance. (See the following graph.) This provides a simple and useful mechanism to determine transmitter and loop compatibility.
The actual transmitter supply contains three ranges of impedance with the following characteristics:
The output voltage is 23.7V for load currents of 0 mA.
If the load is more than 750 Ω but less than ∞Ω, the transmitter
supply is in a constant resistance region (
For load impedance between 0 and 750 Ω, the transmitter supply current is controlled by the field device to a maximum of
If an intrinsic safety fault occurs in the field transmitter supply of any channel, every channel’s field transmitter power is shutdown.
The following graph depicts the typical transmitter load characteristic.
273 Ω).
22 mA.
The normal module field side power consumption is 7.1 W when all channel
23.7V sources (+) are loaded. If field devices are used that are powered separately, the module field-side power consumption can be determined by Field_Side_Power = 9.5V x (180 mA + n x 69 mA). Where n is the number of field devices that are supplied by the 1797-IE8H.
Publication
1797-5.5 - September 2011
16 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
1797-IE8 and 1797-IE8NF Input Map (Read Words)
Bit
Word 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 Channel 0 Input Data 1 Channel 1 Input Data 2 Channel 2 Input Data 3 Channel 3 Input Data 4 Channel 4 Input Data 5 Channel 5 Input Data 6 Channel 6 Input Data 7 Channel 7 Input Data 8OA
9RF
10 Diagnostic Status 11 Res
Where: Ch = channel
OA
OA
OA
OA
OA
OA
OA
UA
UA
Ch7
Ch6
Ch5
Ch4
Ch3
Ch2
Ch1
Ch0
Ch7
Ch6
RF
RF
RF
RF
RF
RF
RF
LF
LF
Ch7
Ch6
Ch5
Ch4
Ch3
Ch2
Ch1
Ch0
Ch7
Ch6
Module command response Module response data
Flg
OA = Over Alarm UA = Under Alarm RF = Remote Fault LF = Local Fault Res Flg = Response Flag
UA Ch5
LF Ch5
UA Ch4
LF Ch4
UA Ch3
LF Ch3
UA Ch2
LF Ch2
UA Ch1
LF Ch1
UA Ch0
LF Ch0
Publication
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 17
1797-IE8H Input Map (Read Words)
Bit
Word 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 Channel 0 Input Data 1 Channel 1 Input Data 2 Channel 2 Input Data 3 Channel 3 Input Data 4 Channel 4 Input Data 5 Channel 5 Input Data 6 Channel 6 Input Data 7 Channel 7 Input Data 8OA
9RF
10 Reserved H
11 H Rb
12 H
Where: Ch = channel
OA
OA
Ch7
Ch6
Ch5
RF
RF
Ch7
Ch6
Ch5
H Rb
H Rb
Ch7
Ch6
Ch5
H
H
Tmt
Tmt
Tmt
Ch5
Ch6
Ch7
OA = Over Alarm UA = Under Alarm RF = Remote Fault LF = Local Fault
OA Ch4
RF Ch4
H Rb Ch4
H Tmt Ch4
OA Ch3
RF Ch3
H Rb Ch3
H Tmt Ch3
OA
OA
OA
UA
Ch2
Ch1
Ch0
Ch7
RF
RF
RF
LF
Ch2
Ch1
Ch0
Ch7
Rbd
H Rb
H Rb
H Rb
Ch2
Ch1
Ch0H Fail
Ch7 H
H
H
H
Tmt
Tmt
Ch1
Ch2
H Rbd = HART Rebuild H Rb = HART Readback H Fail = HART Failure H Tmt = HART Transmitter H Cm = HART Communication
Tmt Ch0
Cm Ch7
UA
UA
UA
UA
UA
UA
Ch6
Ch5
Ch4
Ch3
Ch2
Ch1
LF
LF
LF
LF
LF
LF
Ch6
Ch5
Ch4
Ch3
Ch2
Ch1
Reserved Diagnostic Status
H
H
H
H
H
H
Fail
Fail
Fail
Fail
Fail
Fail
Ch1
Ch2
Ch3
Ch4
Ch5
Ch6
H
H
H Cm Ch6
Cm Ch5
Cm Ch4
H Cm Ch3
H Cm Ch2
H Cm Ch1
UA Ch0
LF Ch0
H Fail Ch0
H Cm Ch0
Publication
1797-5.5 - September 2011
18 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
1797-IE8H Input Map (Read Words)
Word Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 Input Data Channel 0 1 Input Data Channel 1 2 Input Data Channel 2 3 Input Data Channel 3 4 Input Data Channel 4 5 Input Data Channel 5 6 Input Data Channel 6 7 Input Data Channel 7 8HA
9
10 Reserved HR Reserved Diagnostic Status 11 HCF
12 HP
Where: HA = high alarm
HA
HA
HA
HA
HA
Ch 7
Ch 6
Ch 5
Ch 4
Ch 3
Ch 2
SA
SA
SA
SA
SA Rem. Ch 7
Ch 7
Ch 7
Rem. Ch 6
HCF Ch 6
HP Ch 6
Rem. Ch 5
HCF Ch 5
HP Ch 5
Rem. Ch 4
HCF Ch 4
HP Ch 4
Rem.
Ch 3
HCF
Ch 3
HP
Ch 3
SA Rem. Ch 2
HCF Ch 2
HP Ch 2
LA = low alarm SA = second alarm OR = out of range Res. = reserved HR = HART rebuilding HCF = HART current fault HF = HART communication fault HP = HART present HC = HART communication
HA Ch 1
SA Rem. Ch 1
HCF Ch 1
HP Ch 1
HA Ch 0
SA Rem. Ch 0
HCF Ch 0
HP Ch 0
LA Ch 7
OR Ch7
HF Ch 7
HC Ch 7
LA Ch 6
OR Ch6
HF Ch 6
HC Ch 6
LA Ch 5
OR Ch5
HF Ch 5
HC Ch 5
LA Ch 4
OR Ch4
HF Ch 4
HC Ch 4
LA Ch 3
OR Ch3
HF Ch 3
HC Ch 3
LA Ch 2
OR Ch2
HF Ch 2
HC Ch 2
LA Ch 1
OR Ch1
HF Ch 1
HC Ch 1
LA Ch 0
OR Ch0
HF Ch 0
HC Ch 0
Publication
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 19
1797-IE8 and 1797-IE8NF Output Map (Write Words)
Bit
Word 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 Reserved High and Low Error Level
0…3
1 Sq Rt Th High and Low Error Level
4…7
2 CF Module Command Module Command Data
u/d = Up/Down
Where:
Flt Md = Fault Module Sq Rt Th = Square Root Threshold CF = Command Flag
u/d 0…3
u/d 4…7
Filter Cutoff 0…3
Filter Cutoff 4…7
Data Format 0…3
Data Format 4…7
1797-IE8H Output Configuration Map
Bit
Word 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0 Reserved High and Low Error Level
0…3
1 Sq Rt Th High and Low Error Level
4…7
Where: u/d = Up/Down
Flt Md = Fault Module Sq Rt Th = Square Root Threshold
u/d 0…3
u/d 4…7
Filter Cutoff 0…3
Filter Cutoff 4…7
Data Format 0…3
Data Format 4…7
Flt Md 0…3
Flt Md 4…7
Flt Md 0…3
Flt Md 4…7
Publication
1797-5.5 - September 2011
20 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
1797-IE8H Configuration Map
Word Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
0NFVRFE
1HD
Ch7 2 Data Format Ch3 Data Format Ch2 Data Format Ch1 Data Format Ch0 3 Data Format Ch7 Data Format Ch6 Data Format Ch5 Data Format Ch4 4 HART Read Back
Threshold Ch1 5 HART Read Back
Threshold Ch3 6 HART Read Back
Threshold Ch5 7 HART Read Back
Threshold Ch7 8 Square
root
Limit
Ch7 9 High Alarm Limit Ch0 10 Low Alarm Limit Ch0 11 High High Alarm Limit (Remote) Ch0 12 Low Low Alarm Limit (Remote) Ch0 13 High Alarm Limit Ch1 14 Low Alarm Limit Ch1 15 High High Alarm Limit (Remote) Ch1 16 Low Low Alarm Limit (Remote) Ch1 17 High Alarm Limit Ch2 18 Low Alarm Limit Ch2 19 High High Alarm Limit (Remote) Ch2 20 Low Low Alarm Limit (Remote) Ch2 21 High Alarm Limit Ch3
HD Ch6
Ch7
HD Ch5
Square root Limit Ch6
FE Ch6
HD Ch4
FE Ch5
HD Ch3
Square root Limit Ch5
FE
Byte
Ch4
Order Group B
HD
HD
Ch2
Ch1
Digital Filter Ch1
Digital Filter Ch3
Digital Filter Ch5
Digital Filter Ch7
Square root Limit Ch4
HS LEDs
(1)
HD
HHE
Ch0
Ch7
HART Read Back Threshold Ch0
HART Read Back Threshold Ch2
HART Read Back Threshold Ch4
HART Read Back Threshold Ch6
Square root Limit Ch3
HSI FE
Ch3
HHE
HHE
Ch6
Ch5
Square root Limit Ch2
FE Ch2
HHE Ch4
FE Ch1
HHE Ch3
Square root Limit Ch1
FE
Byte
Ch0
Order Group A
HHE
HHE
Ch2
Ch1
Digital Filter Ch0
Digital Filter Ch2
Digital Filter Ch4
Digital Filter Ch6
Square root Limit Ch0
(1)
HHE Ch0
Publication
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 21
1797-IE8H Configuration Map
Word Bit
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
22 Low Alarm Limit Ch3 23 High High Alarm Limit (Remote) Ch3 24 Low Low Alarm Limit (Remote) Ch3 25 High Alarm Limit Ch4 26 Low Alarm Limit Ch4 27 High High Alarm Limit (Remote) Ch4 28 Low Low Alarm Limit (Remote) Ch4 29 High Alarm Limit Ch5 30 Low Alarm Limit Ch5 31 High High Alarm Limit (Remote) Ch5 32 Low Low Alarm Limit (Remote) Ch5 33 High Alarm Limit Ch6 34 Low Alarm Limit Ch6 35 High High Alarm Limit (Remote) Ch6 36 Low Low Alarm Limit (Remote) Ch6 37 High Alarm Limit Ch7 38 Low Alarm Limit Ch7 39 High High Alarm Limit (Remote) Ch7 40 Low Low Alarm Limit (Remote) Ch7 41 HR
Where NF: notch filter (50/60 Hz) HCD: HART CMD3 disable
(1)
HR
HR
HR
HR
HR
HR
HR
HCD
HCD
HCD
HCD
Ch7
Ch6
Ch5
Ch4
Ch3
Ch2
Ch1
Ch0
Ch7
Ch6
Ch5
Ch4
FE: fault enable VR: verify replacement HS LED: HART status LEDs HSI: HART status inhibit HD: HART disable HHE: HART handheld enable HR: HART rebuild
Group B and Group A “Not used in some controller software”
HCD Ch3
HCD Ch2
HCD Ch1
HCD Ch0
Publication
1797-5.5 - September 2011
22 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
Fault Mode - Write Words 0 and 1
Word 0 Bit 00 Fault enable for Channels 0...3 Word 1 Bit 00 Fault enable for Channels 4...7 Where: O = disable
1 = enable with wire-off overload
“Add-on” Filter Selections - Write Words 0 and 1 or Filter Cutoff Selections
Word Bits Description
0 07 06 05 Channels 0...3 1 07 06 05 Channels 4...7
000Hardware filtering only (default filtering) 001 01020 Hz (50 ms) 01110 Hz (100 ms) 1004 Hz (250 ms) 1012 Hz (500 ms) 1101 Hz (1 s)
1110.5 Hz (2 s)
40 Hz (25 ms)
Remote Transmitter Error Up/Down - Write Words 0 and 1
Word 0 Bit 08 Up/down for Channels 0...3 Word 1 Bit 08 Up/down for Channels 4...7 Where: O = up
1 = down
Data Format - Write Words 0 and 1
Word
0 04 03 02 01 Channels 0...3 1 04 03 02 01 Channels 4...7
Publication
Bits
0000022 mA = 0...22,000 with error steps (default) 0001022 mA = 0110%, with error steps 0010022 mA = 0104.8%, square root, with error steps
1797-5.5 - September 2011
Description
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 23
Data Format - Write Words 0 and 1
Word
Bits
0011022 mA = 065,535, unsigned integer, with error steps 0100222 mA, with error steps 0101222 mA = -12.5112.5%, with error steps 0110422 mA = 0106%, square root, with error steps 0111420 mA = 065,535, unsigned integer, with error steps 1000Not assigned 1001Not assigned 1010Not assigned 1011022 mA = A/D count, with fixed error
11003.621 mA = NAMUR NE 43, with fixed error 1101321 mA = -6.25106.25% with fixed error 1110222 mA = -12.5112.5% with fixed error 1111Not assigned
Description
Data Format - Write Words 2 and 3
Data Format
0 00000…20 mA as
1 00010…20 mA as %0.00 22.00 0
2 00100…20 mA as ⎟%0.00 22.00 0
3 00110…20 mA as
4 01004…20 mA as mA2.00 22.00 2000
5 01014…20 mA as %2.00 22.00 -1250
Bits Format Signal Range User Range Resolution
15 14 13 12 11 10 9 8 7654 3210
Milliamps
LO HI LO HI
0.00 22.00 0
(0.000 mA)
22000 (22.000 mA)
11000
(0%)
(110.00%) 10488
unsigned
(0%)
0.00 20.00 0
(0.000 mA)
(140.88%) 65535
(20.000 mA)
integer
22000
(2.000 mA)
(22.000 mA) 11250
(-12.50%)
(112.50%)
0.1% of
0...20 mA
0.2% of
0...20 mA
0.19% of
0...20 mA
0.03% of
0...20 mA
0.01% of
4...20 mA
0.16% of
4...20 mA
Publication
1797-5.5 - September 2011
24 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
Data Format - Write Words 2 and 3 (Continued)
Data Format
6 01104…20 mA as ⎟%4.00 22.00 0
7 01114…20 mA as
8 1000Not assigned 9 1001 10 1010 11 10110...20 mA as
12 11004...20 mA as %3.60 21.00 -250
13 11014...20 mA as %3.00 21.00 -625
14 11104...20 mA as %2.00 22.00 -1250
15 1111Not assigned
Bits Format Signal Range User Range Resolution
15 14 13 12 11 10 9 8 7654 3210
LO HI LO HI
10607
unsigned
(0%)
4.00 20.00 0
(4 mA)
(106.07%) 65535
(20 mA)
integer
A/D count
0.00 22.00 0
(0 mA)
55000 (22 mA)
10625
(-2.50%)
(106.25%) 10625
(-6.25%)
(106.25%) 11250
(-12.50%)
(112.50%)
Error Level 0.1 mA Steps
Word Bits Description
Word 0 13 12 11 10 09 Error level channels 0...3 Word 1 13 12 11 10 09 Error level channels 4...7
00000Disabled
0.1 mA * binary valve = remote fault alarm
Examples
Data Format
2...22 mA
-12.5...112.5%
00111Binary value = 7, 0.1 mA * 7 = 0.7 mA
Remote fault alarm at -4.38% or +104.38%
01111Binary value = 15, 0.1 mA * 15 = 1.5 mA
Remote fault alarm at -9.38% or + 109.38%
0.17% of
4...20 mA
0.03% of
4...20 mA
0.04% of
0...20 mA
0.16% of
4...20 mA
0.16% of
4...20 mA
0.16% of
4...20 mA
Publication
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 25
1797-IE8H Analog Input Extended Configuration Data Table
Config
Bits
Word
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
SME
SME
SME
SME
SME
SME
SME
0PMI
1 Reserved HART Read Back
Where Ch = channel
PMI
Ch
Ch
Ch
5
6
7
PMI = primary master inhibit SME = secondary master enable HS LED = HART status LEDs HS Inht = HART status inhibit
Ch
Ch
Ch
2
3
4
Threshold Ch 4...7
PMI
PMI
PMI
PMI
PMI Ch 1
PMI Ch 0
Ch 7
HS LED
Ch 6
HS Inht
Ch 5
Ch 4
Ch 3
Ch 2
HART Read Back Threshold
50/
Ch 0...3
60 Hz
Ch 1
SME Ch 0
1797-IE8H Secondary Master Enable (SME)/ Primary Master Inhibit (PMI)
(1)
Bits PMI 8, 9, 10, 11, 12, 13, 14, 15 0 0 1 1 SME 0, 1, 2, 3, 4, 5, 6, 7 0 1 0 1
HART Smooth Filter Pulsed On Off On Rebuild On On Off Off HART Read Back On On Off Off Primary Master On On Off Off Secondary Master Off On Off On
(1)
Where: Ch 0 - bits 0 and 8; Ch 1 - bits 1 and 9; Ch 2 - bits 2 and 10; Ch 3 - bits 3 and 11 Ch 4 - bits 4 and 12; Ch 5 - bits 5 and 13; Ch 6 - bits 6 and 14; Ch 7 - bits 7 and 15
1 (Default) 2 3 4
These two bits control a few module internal functions individually for channels 0 through 7.
Publication
1797-5.5 - September 2011
26 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
Byte Order Configuration
Byte Order Group B
Byte Order
Group A
Description
Bit 9 Bit 8 Bit 1 Bit 0
0 0 0 0 Little Endian Format (Default) = All data entries in true Little
Endian format.
1 0 1 0 Word Swap = Word swap only values requiring more then one
word, for example: 32 bit float values.
0 1 0 1 Byte Swap (reserved for future implementation) = Byte swap all
words in data table.
1 1 1 1 Big Endian Format (reserved for future implementation) = All data
entries in true Big Endian format.
(1)
All other combinations are invalid. Values will Revert to the last valid configuration (in case of original start-up this would be default configuration) and set module Diagnostic Status to "2" configuration failure.
(1)
Digital Filter
Digital Filter frequency
0.5 Hz 7 0 0 0 10 Hz 3 1 0 0 1 Hz 6 0 0 1
2 Hz 5 0 1 0 Not applicable 1 1 1 0 4 Hz 4 0 1 1 Not applicable 0 1 1 1
(1)
Decimal Values 2, 1 and 0 are not applicable. Values will Revert to the last valid configuration (in case of original start-up this would be default configuration) and set module Diagnostic Status to "2" configuration failure.
Decimal
Bits Digital Filter
Valu e
2 1 0 2 1 0
frequency
Decimal Valu e
10 9 8 10 9 8
(1)
Not applicable
2 1 0 1
Bits
Publication
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 27
Field Descriptions
Analog Input Data Specifies the value of the analog input data from the module. Specific
format is controlled by Module Data Format Control parameter. This data is used when the channel is in analog input mode.
Overrange Alarm Alarm signal for input overrange. This signal is always active.
Range: 0 = normal, 1 = input overrange
Underrange Alarm Alarm signal for input underrange. This signal is always active.
Range: 0 = normal, 1 = input underrange
Remote Fault Alarm Alarm from remote transmitter, indicating transmitter difficulties,
Local Fault Alarm Alarm indicating the loop to the transmitter, or, if there is no transmitter,
HART Rebuild Bit (1797-IE8H)
HART Rebuild Flag (1797-IE8H)
HART Failure (1797-IE8H)
HART Communication Fault (1797-IE8H??)
sensor difficulties, or loop to the sensor is open. If not using a remote transmitter, this alarm can be used as a high-high or low-low alarm. Depending on Data Format, these current values may be indicated by percent, mA, or integer values. Range: 0 = normal, 1 = fault detected
the loop is open or shorted. When active, this alarm triggers at 2 mA and 22 mA for open and short respectively. Depending on Data Format, these current values may be indicated by percent, mA, or integer values. Range: 0 = normal, 1 = fault detected
The HART Rebuild bit will trigger a HART Rebuild on a transition from 0 to 1. The HART Rebuild bit must remain 1 for HART communications to function after the rebuild completes. If the HART Rebuild bit is set to 0, HART communications are disabled.
During the time the system is rebuilding the HART table, the HART rebuild flag is set. Range: 0 = normal, 1 = HART rebuilding
A 1 indicates that HART communications are failing on the associated channel. Range: 0 = normal, 1 = HART communication failure
When this bit is set (1), it indicates that HART communications are failing on the associated channel. Range: 0 = normal, 1 = HART communication fault
Publication
1797-5.5 - September 2011
28 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
Field Descriptions
HART Read Back (1797-IE8H)
HART Read Back Threshold (1797-IE8H)
HART Communication (1797-IE8H)
HART Transmitter List (1797-IE8H)
Square Root Threshold (1797-IE8H)
Extended Configuration (1797-IE8H)
The HART Read Back bits show deviations between the analog measured current value on a loop (by the 1797-IE8H) and the digital real current (sensed by the HART device on its own) received by the 1797-IE8H during HART communication in the background. This functionality can be turned on by defining a HART Readback Threshold greater than 0. See 1797-IE8H CE, CENELEC I/O Entity Parameters
page 42. This functionality is used to recognize loop errors whereby a
parasitic current is bypassing the 1797-IE8H. Range: 0 = normal, 1 = HART Readback threshold is exceeded.
Delivers the percentage value (in steps of 1%) of the threshold for forcing the HART read back indication (input signal deviation HART/Analog) with a 31% maximum deviation. If there is no HART transmitter on the loop or the loop is not in the transmitter list, the function is switched off internally in the I/O module. Range: 0 = disabled, 1…4 = not supported from I/O module (set to 5 internally), 5…31 = percentage threshold data (5…31%).
Range: 0 = normal, 1 = HART communication is currently occurring.
When this bit is set (1), it indicates that a HART field device was found during the rebuild sequence on the associated channel. Range: 0 = transmitter was not found, 1 = HART transmitter was found.
This setting affects all channels using Data Format 2 or 6. It sets low, end-of-scale percent value at which square roots start being reported. Below this level 0% is reported. This compensates for asymptotic values of the square-root function as the input approaches 0. Range: 0 = disabled, 1 = 2%, 2 = 5%, 3 = 10%
Configuration additions are needed for HART communications in Series A mode. An extended configuration area is provided. This Extended Configuration table is configured by writing a CIO or MSG instruction with the following:
Class = 0x7D Instance = Product location on flexbus (Use 1 for the module located next to the adapter.) Attribute = 0x65 Service = Set Attribute Single (0x10)
See 1797-IE8H CE, CENELEC I/O Entity Parameters
on page 42.
on
Publication
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 29
Field Descriptions
HART Status Indicators
HART Status Inhibit When this bit is set (1), the HART communication status is not shown in
50/60 Hz Filter Range: 0 = 50 Hz, 1 = 60 Hz
When this bit is set (1), the status indicators are used for HART diagnostic. Indicator behavior changes to show communication on HART. Each indicator represents a HART loop. Flashing yellow indicates that communication is currently being processed. Solid yellow means that this device is in the transmitter list.
the realtime data table. The appropriate areas are cleared with zeroes. Range: 0 = normal, 1 = inhibit HART
Publication
1797-5.5 - September 2011
30 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
IMPORTANT
Cyclic HART Input Data
The HART input data holds the primary variables for the "live" HART device, and other information gathered during the normal HART scan. Additional "documentary" data is available through the pass through message interface in the device information tables. Pass through messages are defined in detail in the User Manual.
The HART Input Data for a channel may be zeroes if HART communications is disabled for that channel. For more information on disabling HART communications, refer to the Disable HART communications and HART Disable functions in the Configuration Map table.
HART Input Data
Word Bit
1514131211109876543210
0 Reserved Ch7 Ch6 Ch5 Ch4 Ch3 Ch2 Ch1 Ch0
(HART Communications Status) 1 Reserved 2 Ch0 HART Field Device Status Ch0 HART Comm Status 3 Reserved Ch0 HART Loop Status 4 Ch0 HART Primary Value
(IEEE 754-1985 Single-Precision 32 bit floating point)
5 6 Ch0 HART Secondary Value
(IEEE 754-1985 Single-Precision 32 bit floating point)
7 8 Ch0 HART Tertiary Value
(IEEE 754-1985 Single-Precision 32 bit floating point)
9 10 Ch0 HART Fourth (Quaternary) Value
(IEEE 754-1985 Single-Precision 32 bit floating point)
11 12 Ch0 Secondary Value Units Code Ch0 Primary Value Units Code 13 Ch0 Fourth Value Units Code Ch0 Tertiary Value Units Code 14 Ch1 HART Field Device Status Ch1 HART Communication Status 15 Reserved Ch1 HART Loop Status 16 Ch1 HART Primary Value 17
Publication
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 31
HART Input Data
Word Bit
1514131211109876543210
18 Ch1 HART Secondary Value 19 20 Ch1 HART Teritiary Value 21 22 Ch1 HART Fourth Value 23 24 Ch1 HART Secondary Value Units Code Ch1 HART Primary Value Units Code 25 Ch1 HART Fourth Value Ch1 HART Tertiary Value Units Code 26 Ch2 HART Field Device Status Ch2 HART Communication Status 27 Reserved Ch2 HART Loop Status 28 Ch2 HART Primary Value 29 30 Ch2 HART Secondary Value 31 32 Ch 2 HART Tertiary Value 33 34 Ch2 HART Fourth Value 35 36 Ch2 HART Secondary Value Units Code Ch2 HART Primary Value Units Code 37 Ch2 HART Fourth Value Ch2 HART Tertiary Value Units Code 38 Ch3 HART Field Device Status Ch3 HART Communication Status 39 Reserved Ch0 HART Loop Status 40 Ch3 HART Primary Value 41 42 Ch3 HART Secondary Value 43 44 Ch3 HART Tertiary Value 45 46 Ch3 HART Fourth Value 47
Publication
1797-5.5 - September 2011
32 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
HART Input Data
Word Bit
1514131211109876543210
48 Ch3 HART Secondary Value Units Code Ch3 HART Primary Value Units Code 49 Ch3 HART Fourth Value Ch3 HART Tertiary Value Units Code 50 Ch4 HART Field Device Status Ch4 HART Communication Status 51 Reserved Ch4 HART Loop Status 52 Ch4 HART Primary Value 53 54 Ch4 HART Secondary Value 55 56 Ch4 HART Tertiary Value 57 58 Ch4 HART Fourth Value 59 60 Ch4 HART Secondary Value Units Code Ch4 HART Primary Value Units Code 61 Ch4 HART Fourth Value Ch4 HART Tertiary Value Units Code 62 Ch5 HART Field Device Status Ch5 HART Communication Status 63 Reserved Ch5 HART Loop Status 64 Ch5 HART Primary Value 65 66 Ch5 Secondary Value 67 68 Ch5 Tertiary Value 69 70 Ch5 Fourth Value 71 72 Ch5 HART Secondary Value Units Code Ch5 HART Primary Value Units Code 73 Ch5 HART Fourth Value Ch5 HART Tertiary Value Units Code 74 Ch6 HART Field Device Status CH6 HART Communication Status 75 Reserved Ch6 HART Loop Status 76 Ch6 HART Primary Value 77
Publication
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 33
HART Input Data
Word Bit
1514131211109876543210
78 Ch6 Secondary Value 79 80 Ch6 Tertiary Value 81 82 Ch6 Fourth Value 83 84 Ch6 HART Secondary Value Units Code Ch6 HART Primary Value Units Code 85 Ch6 HART Fourth Value Ch6 HART Tertiary Value Units Code 86 Ch7 HART Field Device Status CH7 HART Communication Status 87 Reserved Ch7 HART Loop Status 88 Ch7 HART Primary Value 89 90 Ch7 Secondary Value 91 92 Ch7 Tertiary Value 93 94 Ch7 Fourth Value 95 96 Ch7 HART Secondary Value Units Code Ch7 HART Primary Value Units Code 97 Ch7 HART Fourth Value Ch7 HART Tertiary Value Units Code
Publication
1797-5.5 - September 2011
34 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
HART Input Data Descriptions
CHn: HART Communication Status 0: HART CMD3
Communication Disabled or No Error
CHn: HART Comm Status (HART CMD3 Response first status byte):
CHn: HART Field Device Status (HART CMD3 Response second status byte):
Chn: HART Loop Status: Bit 0: HART enable Bit 1: Device Connected Bit 2: Response Error
Bit 3: CMD 48 Update
Bit 4: HART Loop Tolerance Error
Bit 5: HART Update
Bit 6: HART message
Bit 7: Where PVA = The primary variable for this channel has been acquired.
SVA = The secondary variable for this channel has been acquired. TVA = The tertiary variable for this channel has been acquired. FVA = The fourth (quaternary) variable for this channel has been acquired.
Refer to User Manual
Refer to User Manual
0: Disabled 0: Not Connected 0: No HART message failure 0: CMD 48 not updated 0: No HART Current Fault 0: HART Device information not updated 0: No new message
1: HART CMD3 Communication Error between Adapter & Module
1: Enabled 1: Connected 1: Response ended in error
1: CMD 48 updated
1:HART Current Fault
1: HART Device information updated since last read
1: HART user message queue has completed a message Reserved
Publication
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 35
HART Read Back Threshold
HART Read Back Decimal Bits
Value76543
15 14 13 12 11
Disabled 0 00000 Not applicable
(1)
1 00001
Not applicable 2 0 0 0 1 0 Not applicable 3 0 0 0 1 1 Not applicable 4 0 0 1 0 0 5% 5 00101 6% 6 00110 7% 7 00111 8% 8 01000 9% 9 01001 10% 10 0 1 0 1 0 … …………… 30% 30 1 1 1 1 0 31% 31 1 1 1 1 1
(1)
1, 2, 3, and 4 are not applicable. Values between 1 and 4 will lead the IOM to automatically use an internal value of 5%.
Square Root Threshold
Square Root Limit Decimal Value Bits Channel
1 0 Ch0 3 2 Ch1 5 4 Ch2 7 6 Ch3 9 8 Ch4 11 10 Ch5 13 12 Ch6 15 14 Ch7
Disabled 0 0 0 2% 1 0 1 5% 2 1 0 10% 3 1 1
Publication
1797-5.5 - September 2011
36 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
ATTENTION
42054
1797-IE8 shown

Repair

This module is not field repairable. Any attempt to open the module will void the warranty and IS certification. If repair is necessary, return the module to the factory.

Status Indicators

Interpret the Status Indicators
Status Description
Flashing red Channel fault -
Channel 0 indicator will turn red while power-up check is running
Solid green Power applied to module Flashing green No Flexbus communication -
Adapter not powered or faulty connnection
Solid yellow HART communication functioning normally
Publication
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 37

Specifications

Specifications - 1797-IE8 and -IE8NF
Number of Inputs 8 single-ended, non-isolated IS input type Ex ia IIB/IIC T4
AEx ia IIC T4
IS module type Ex ib IIB/IIC T4
Resolution 16 bits Transfer Characteristics
Accuracy at 20 °C (68 °F) Temperature Drift
Functional Data Range >15V @ 22 mA
Data Format Configurable Step Response to 99% of FS Module from Adapter Best/Worst Update Time Indicators 8 red fault indicators
Inputs (Intrinsically Safe)
(Terminals: 0…2; 4…6; 8…10; 12…14; 17…19; 21…23; 25…27; 29…31)
Class I, II, III Division 1 Group A-G T4
AEx ib IIC T4 Class I, II, III Division 1 Groups A-D T4
0.1% of output signal range
0.05%/C of output signal range
>21.5V @ 0 mA
4 ms (1797-IE8) 80 ms (1797-IE8NF)
200 ms/1600 µs
1 green power indicator Uo < 23.7V
Io < 93.5 mA Po < 555 mW
Publication
1797-5.5 - September 2011
38 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
Specification 1797-IE8 and -IE8NF (Continued)
Isolation Path
Input to Power Supply Input to Flexbus Input to Input Power Supply to
Flexbus
Power Supply
(+V, -V Intrinsically Safe) (Terminals: 34 and 50 (+): 35 and 51 (-))
Module Field-side Power Consumption Power Dissipation 5.2 W Thermal Dissipation 17.75 BTU/hr Module Location Cat. No. 1797-TB3 or 1797-TB3S Conductor Wire Size
Dimensions Metric
Imperial Weight 200 g (approximately) Keyswitch Position 3 Environmental Conditions
Operational Temperature Storage Temperature Relative Humidity 5…95% noncondensing
Shock Operating Tested to 15 g peak acceleration, 11(+1) ms pulse width
Nonoperating Tested to 15 g peak acceleration, 11(+1) ms pulse width
Vibration Tested 2 g @ 10…500 Hz per IEC68-2-6
Isolation Type Galvanic to DIN EN60079-11 Galvanic to DIN EN60079-11 None Galvanic to DIN EN60079-11
Ui < 9.5V dc Ii < 1 A Li = Negligible Ci = Negligible
7.5 W
4mm2 (12 AWG) stranded max
1.2 mm (3/64 in.) insulation max 46 mm x 94 mm x 75 mm (1.8 in. x 3.7 in. x 2.95 in.)
-20…+70 oC (-4…+158 oF)
-40…+85 oC (-40…+185 oF)
Publication
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 39
Class I Division 1 Hazardous
FM
Specification 1797-IE8 and -IE8NF (Continued)
Agency Certification
INMETRO
Certificates
CENELEC
II (1) 2G Ex ib[ia] IIC T4 II (1) D [Ex iaD]
U, C-UL
Class I, Groups A, B, C and D; Class II, Groups E, F and G; Class III hazardous Locations. Class I, Zone 1, AEx ib[ia] IIC T4.
FM
Intrinsically safe Class I, Div 1, Groups A, B, C, D, T4. Associated Apparatus with intrinsically safe Connections Class I, II, III, Div 1, Groups A--G Intrinsically safe Class I, Zone 1, AEx ib[ia] IIC T4. BR-Ex ia/ib IIB/IIC T4
IECEx
[Zone 0] Ex ib[ia] IIC T4 [Ex iaD]
CENELEC DMT 98 ATEX E 020 X
UL, C-UL File No.: E197983
FM FM Certificate Number 3009806
INMETRO
05/UL-BRAE-0013X (1797-IE8 only)
IECEX
IECEx BVS 09.0030X
Specifications - 1797-IE8H
Number of Inputs 8 single-ended, non-isolated IS Input type Ex ia IIB/IIC T4
AEx ia IIC T4 Class I, Division I Groups A-G T4 (FM only)
IS Module type Ex ib IIB/IIC T4
AEx ib IIC T4 Class I, Division I Groups A-D T4 (FM only)
Resolution 16 bits Transfer Characteristics
Accuracy at 20 °C (68 °F) Temperature Drift
0.1% of output signal range
0.05%/C of output signal range
Publication
1797-5.5 - September 2011
40 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
Functional Data Range >17V @ 22 mA
Data Format Configurable Step Response to
99% of FS Module from Adapter
Best/Worst Update Time Indicators 8 red fault indicators
Inputs (Intrinsically Safe)
(Terminals: 0…2; 4…6; 8…10; 12…14; 17…19; 21…23; 25…27; 29…31)
Isolation Path
Input to Power Supply Input to Flexbus Input to Input Power Supply to
Flexbus
Power Supply
(+V, -V intrinsically safe) (Terminals: 34/50 (+): 35/51 (-))
Module Field-side Power Consumption
Power Dissipation 3.9 W Thermal Dissipation 13.5 BTU/hr Module Location Cat. No. 1797-TB3 or 1797-TB3S Conductor Wire Size
Dimensions Metric
Weight 200 g (approximately) Keyswitch Position 8 Environmental Conditions
Operational Temperature Storage Temperature Relative Humidity 5…95% noncondensing
Shock Operating Tested to 15 g peak acceleration, 11(+1) ms pulse width
Vibration Tested 2 g @ 10…500 Hz per IEC68-2-6
Imperial
Nonoperating Tested to 15 g peak acceleration, 11(+1) ms pulse width
>23V @ 0 mA
80 ms
200 ms/1600 µs
8 yellow channel indicators 1 green power indicator
Uo < 24.4V Io < 92.5 mA Po < 565 mW
Isolation Type Galvanic to DIN EN60079-11 Galvanic to DIN EN60079-11 None Galvanic to DIN EN60079-11
Ui < 9.5V dc Ii < 1 A Li = Negligible Ci = 120 nF
7.1 W
4 mm2 (12 AWG) stranded max
1.2 mm (3/64 in.) insulation max 46 mm x 94 mm x 75 mm
(1.8 in. x 3.7 in. x 2.95 in.)
-20…+70 oC (-4…+158 oF)
-40…+85 oC (-40…+185 oF)
Publication
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 41
FM
Agency Certification
Certificates
CENELEC II (1) 2G Ex ib[ia] IIC T4
II (1) D [Ex iaD
FM Intrinsically safe Class I, Div 1, Groups A, B, C, D, T4.
Associated Apparatus with intrinsically safe Connections Class I, II, III, Div 1, Groups A--G Intrinsically safe Class I, Zone 1, AEx ib[ia] IIC T4.
IECEx [Zone 0] Ex ib[ia] IIC T4
[Ex iaD]
CENELEC DMT 98 ATEX E 020 X
FM FM Certificate Number 3009806
IECEx IECEx BVS 09.0030X

Entity Parameters

1797-IE8 and 1797-IE8NF CE, CENELEC I/O Entity Parameters
Measurement input (sig to -) for channels 0…7 (terminals: 1…2; 5…6; 9…10; 13…14; 18…19; 22…23; 26…27; 30…31)
Uo = 5V Io = 1 mA Po = 1.3 mW Ui = 28V Ii = 110 mA Ci and Li negligible
Protection Group Allowed
Capacitance
Ex ia IIB 1000 µF 1 H
IIC 100 µF 1 H
Allowed Inductance
Source output (+ to sig) for ch 0 to ch 7 (terminals: 0 to 1; 4 to 5; 8 to 9; 12 to 13; 17 to 18; 21 to 22; 25 to 26; 29 to 30)
Protection Group Allowed
Uo = 23.7V Io = 92.5 mA Po = 548 mW
Ex ia IIB 560 nF 10 mH
IIC 66 nF 2.5 mH
Capacitance
Publication
1797-5.5 - September 2011
Allowed Inductance
42 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
If concentrated capacitance and/or inductance are available, use the following values.
Ex ia IIB 320 nF 10 mH
IIC 60 nF 2 mH
1797-IE8H CE, CENELEC I/O Entity Parameters
Source output plus measurement input (+ to -) for channels 0…7 (terminals: 0…2; 4…6; 8…10; 12…14; 17…19; 21…23; 25…27; 29…31)
Uo = 24.4V Io = 92.5 mA Po = 565 mW Ci = Negligible Li = Negligible
Protection Allowed
Capacitance
Ex ia 119 nF 4 mH
Allowed Inductance
1797-IE8 and 1797-IE8NF UL, C-UL I/O Entity Parameters
If this product has the UL/C-UL mark, it has been designed, evaluated, tested, and certified to meet the following standards:
UL 913, 1988, Intrinsically Safe Apparatus and Associated Apparatus
for Use in Class I, II, and III Division 1, Hazardous (Classified) Locations
UL 1203, Explosion-Proof and Dust-Ignition-Proof Electrical
Equipment for Use in Hazardous (Classified) Locations
UL 2279, Electrical Equipment for Use in Class I, Zone 0, 1, and 2
Hazardous (Classified) Locations
UL 61010, UL Standard for Safety Electrical Equipment For
Measurement, Control, and Laboratory Use; Part 1: General Requirements
CSA C22.2 No. 157-92, Intrinsically Safe and Non-Incendive
Equipment for Use in Hazardous Locations
CSA C22.2 No. 30-M1986, Explosion-Proof Enclosures for Use in
Class I Hazardous Locations
Publication
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 43
CSA-E79-0-95, Electrical Apparatus for Explosive Gas Atmospheres,
Part 0: General Requirements
CSA-E79-11-95, Electrical Apparatus for Explosive Gas
Atmospheres, Part 11: Intrinsic Safety “i”
CSA C22.2 No. 14-95, Industrial Control Equipment
Publication
1797-5.5 - September 2011
44 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
FLEX Ex Analog Input I/O Module
Indicators
Female Bus
Field Wiring
Terminal Base
Terminal Base Key
Male Bus
Connection
Key Position for Terminal Base
Insertion
42055
Wiring Methods
Wiring method 1 - Each channel is wired separately.
Wiring method 2 - Multiple channels in one cable, providing each
channel is separated in accordance with the National Electric Code (NEC) or Canadian Electric Code (CEC).
Table 1
Wiring
Channel Ter m in al s Voc
Method
1 and 2 Any one
channel,
for
example,
ch0
0(+), 1(sig) 23.7 92.5 - - A, B, IIC 0.06 2.0
1(sig), 2(-) 5 1.0 - - A, B, IIC 100 1000
0(+), 1(sig),
2(-)
Isc
Vt
It
Groups Ca
(V)
(mA)
(V)
(mA)
C, E, IIB 0.18 8.0
D, F, G, IIA 0.48 16.0
C, E, IIB 300 1000
D, F, G, IIA 800 1000
- - 23.7 93.5 A, B, IIC 0.06 2.0 C, E, IIB 0.18 8.0
D, F, G, IIA 0.48 16.0
(μF)
La
(mH)
Publication
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 45
IMPORTANT
Hazardous (Classified) Location Class I, Zones 0, 1, & 2 Groups IIC, IIB, IIA Class I, Div. 1 & 2 Groups A, B, C, D Class II, Div. 1 & 2 Groups E, F, G Class III, Div. 1 & 2
Hazardous (Classified) Location Class I, Zones 1 & 2 Groups IIC, IIB, IIA Class I, Div. 1 & 2 Groups A, B, C, D
To any intrinsically safe device or associated apparatus with Entity Concept parameters of V
oc
< 5.8V; Isc < 400 mA.
To any intrinsically safe device or associated apparatus with Entity Concept  parameters of V
oc
< 9.5V; Isc < 1 A.
To any IS device with Entity Concept parameters of (V
max
, I
max
, Ci, Li) appropriate
for connection to associated apparatus with Entity Concept parameters listed in Table 2.
1797-IE8
or
1797-IE8NF
16
Shield Connection Only
50
51
35
34
V
max
=5.8V
I
max
=400 mA
C
i
=1350 nF
L
i
=negligible
V
max
=9.5V
I
max
=1 A
C
i
=negligible
L
i
=negligible
Male Bus Connector
33 40 41
42 43 44 45
0 (+)
Female Bus Connector
Any Simple Apparatus or I.S. device with Entity Co ncept parameters (V
max
, I
max
, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 1.
1 (sig)
ch0
ch1
ch2
ch3
ch4
ch5
ch6
ch7
2 (-) 4 (+)
5 (sig) 6 (-)
8 (+) 9 (sig) 10 (-)
12 (+) 13 (sig) 14 (-)
17 (+) 18 (sig) 19 (-)
21 (+) 22 (sig) 23 (-)
25 (+) 26 (sig) 27 (-)
29 (+) 30 (sig) 31 (-)
42056
A terminal base may or may not have an I/O module installed.
Table 2
Ter m in al s Vt (V) It (mA) Groups Ca (μF) La (μH)
Male Bus Connector 5.8 400 A…G 3.0 3.0
The entity concept allows interconnection of intrinsically safe apparatus
with associated apparatus not specifically examined in combination as a system when the approved values of V apparatus are less than or equal to V
max
oc
and I
and I
or Vt and It of the associated
sc
of the intrinsically safe
max
Publication
1797-5.5 - September 2011
46 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
apparatus and the approved values of Ca and La of the associated apparatus
+ C
are greater than C
i
and Li + L
cable
apparatus. The internal capacitances of C
respectively for the intrinsically safe
cable
of the terminal base must be taken
i
into account to verify the intrinsic safety.
Simple apparatus is defined as a device which neither generates nor stores
more than 1.2V, 0.1 A, 20 μJ, or 25 mW.
Wiring methods must be in accordance with the National Electric Code,
ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA RP12.6.
This module, 1797-IE8, must be used with terminal base 1797-TB3 or
1797-TB3S.
Terminals 3, 7, 11, 15, 20, 24, 28, 32, 36-39, and 46 to 49 shall not be
connected.
WARNING: Substitution of components may impair intrinsic safety.
AVERTISSEMENT: La substitution de composant peut compromettre la securite intrinseque.
1797-IE8, 1797-IE8H, and 1797-IE8NF FM I/O Entity Parameters
If this product has the FM mark, it has been designed, evaluated, tested, and certified to meet the following standards:
FM C1. No.3600:1998, Electrical Equipment for Use in Hazardous
(Classified) Locations General Requirements
FM C1. No.3610:1999, Intrinsically Safe Apparatus and Associated
Apparatus for Use in Class I, II, III Division 1 Hazardous (Classified) Locations
FM C1. No.3615:1989, Explosionproof Electrical Equipment General
Requirements
FM C1. No.3810:1989, 1995, Electrical and Electronic Test,
Measuring and Process Control Equipment
ANSI/NEMA 250, 1991, Enclosures for Electrical Equipment
Publication
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 47
Wiring Methods
Wiring method 1 - Each channel is wired separately.
Wiring method 2 - Multiple channels in one cable, providing each
channel is separated in accordance with the National Electric Code (NEC).
FM I/O Entity Parameters for 1797-IE8 and 1797-IE8NF
Wiring
Channel Te rm in al s Voc
Method
1 and 2 Any one
channel
(for
0(+), 1(sig) 23.7 92.5 - - - - A, B, IIC 0.06 2.0
(V)
Isc (mA)
V (V)
max
I
max
(mA)
Vt
It
Groups Ca
(V)
(mA)
C, E, IIB 0.18 8.0 D, F, G,
example,
ch0)
1(sig), 2(-) 5 1.0 28.0 93.0 - - A, B, IIC 100 1000
C, E, IIB 300 1000 D, F, G,
0(+), 1(sig),
- - - - 23.7 93.5 A, B, IIC 0.06 2.0
2(-)
C, E, IIB 0.18 8.0 D, F, G,
FM I/O Entity Parameters for 1797-IE8H
Wiring
Channel Te rm in a ls Voc
Method
1 and 2 Any one
channel
(for
example,
ch0)
0(+), 1(sig), 2(-) 24.4 92.5 - - A, B 0.119 4.0
1(sig), 2(-) 28 110 A, B 0.119 4.0
(V)
Isc
(mA)
V
I
max
(mA)
Groups Ca
max
(V)
C, E 0.35 12.0
D, F, G 0.95 32.0
C, E 0.35 12.0
D, F, G 0.95 32.0
IIA
IIA
IIA
(μF)
0.48 16.0
800 1000
0.48 16.0
(μF)
La (mH)
La
(mH)
Publication
1797-5.5 - September 2011
48 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
IMPORTANT
FLEX Ex Analog Input I/O Module
Indicators
Female Bus
Field Wiring
Terminal Base
Terminal Base Key
Male Bus
Connection
Key Position for Terminal Base
Insertion
42055
A terminal base may or may not have an I/O module installed.
Publication
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 49
Hazardous (Classified) Location Class I, Zones 0 Groups IIC, IIB, IIA Class I, Div. 1 Groups A, B, C, D Class II, Div. 1 Groups E, F, G Class III, Div. 1
Hazardous (Classified) Location Class I, Zones 1 Groups IIC Class I, Div. 1 Groups A, B, C, D
For connection to other modules, refer to the General FM Certification Information on page 29-1 in 1797-6.5.6.
From FM approved devices, 1797-PS2N.
For connection to other modules, refer to the General FM Certification Information on page 29-1 in 1797-6.5.6.
16
Shield Connection Only
50
51
35
34
V
max
=5.8V
I
max
=400 mA
C
i
=1350 nF
L
i
=negligible
V
max
=9.5V
I
max
=1 A
C
i
=negligible
L
i
=negligible
Male Bus Connector
33 40 41
42 43 44 45
0 (+)
Female Bus Connector
Any Simple Apparatus or FM approved device with Entity Concept parameters (V
max
, I
max
, Ci, Li) appropriate for connection to associated apparatus with Entity Concept parameters listed in Table 1.
1 (sig)
ch0
ch1
ch2
ch3
ch4
ch5
ch6
ch7
2 (-) 4 (+)
5 (sig) 6 (-)
8 (+) 9 (sig) 10 (-)
12 (+) 13 (sig) 14 (-)
17 (+) 18 (sig) 19 (-)
21 (+) 22 (sig) 23 (-)
25 (+) 26 (sig) 27 (-)
29 (+) 30 (sig) 31 (-)
42056
1797-IE8,
-IE8H, or
-IE8NF
Flexbus Entity Values Which are Allowed for the Next FLEX Ex I/O Module
Ter m in al s Vt (V) It (mA) Groups Ca (μF) La (μH)
Male Bus
Connector
5.8 400 A…G 3.0 3.0
Publication
1797-5.5 - September 2011
50 FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules
IMPORTANT
Flexbus Entity Values for This Module
Any combination of up to eight FLEX Ex I/O modules may be attached on a flexbus.
Ter m in al s Vt (V) It (mA) Groups Ca (μF) La (μH)
Female Bus
Connector
The entity concept allows interconnection of intrinsically safe apparatus
5.8 400 A…D 3.0 3.0
with associated apparatus not specifically examined in combination as a system when the approved values of Voc and I apparatus are less than or equal to V
max
apparatus and the approved values of C
+ C
are greater than C
i
and Li + L
cable
cable
or Vt and It of the associated
sc
and I
of the intrinsically safe
max
and La of the associated apparatus
a
respectively for the intrinsically safe
apparatus.
Simple apparatus is defined as a device which neither generates nor stores
more than 1.2V, 0.1 A, 20 μJ, or 25 mW.
Wiring methods must be in accordance with the National Electric Code,
ANSI/NFPA 70, Article 504 and 505. For additional information refer to ANSI/ISA RP12.6.
This module, 1797-IE8, 1797-IE8H, or 1797-IE8NF must be used with
terminal base 1797-TB3 or 1797-TB3S.
Terminals 3, 7, 11, 15, 20, 24, 28, 32, 36-39, and 46 to 49 shall not be
connected.
WARNING: Substitution of components may impair intrinsic safety.
Publication
For detailed certification information, refer to the FLEX Ex System Certification Reference Manual, publication 1797-6.5.6.
1797-5.5 - September 2011
FLEX Ex 8 Input Analog, HART, and Noise Filter Analog Modules 51
Attention: Avoid electrostatic charging.
ATENÇÃO! PREVENIR CONTRA O ACÚMULO DE
CARGA ELETROSTÁTICA.
FLEX Ex is a trademark of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication
1797-5.5 - September 2011
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using its products. At http://support.rockwellautomation.com
, you can find technical manuals, a knowledge base of FAQs, technical and application notes, sample code and links to software service packs, and a MySupport feature that you can customize to make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and troubleshooting, we offer TechConnect support programs. For more information, contact your local distributor or Rockwell Automation representative, or visit
http://support.rockwellautomation.com
.
Installation Assistance
If you experience a problem within the first 24 hours of installation, please review the information that's contained in this manual. You can also contact a special Customer Support number for initial help in getting your product up and running.
United States 1.440.646.3434
Outside United States Please contact your local Rockwell Automation representative for any
Monday – Friday, 8 a.m. – 5 p.m. EST
technical support issues.
New Product Satisfaction Return
Rockwell Automation tests all of its products to ensure that they are fully operational when shipped from the manufacturing facility. However, if your product is not functioning and needs to be returned, follow these procedures.
United States Contact your distributor. You must provide a Customer Support case number
Outside United States Please contact your local Rockwell Automation representative for the return
Allen-Bradley, Rockwell Automation, TechConnect, and Flex Ex are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
(see phone number above to obtain one) to your distributor in order to complete the return process.
procedure.
Publication 1797-5.5 - September 2011 PN-121053
Supersedes Publication 1797-IN005H-EN-P - October 2005 Copyright © 2011 Rockwell Automation, Inc. All rights reserved. Printed in Singapore.
Loading...