Important User Information2
Module Installation3
Installation in Zone 15
Installation in Zone 225
Electrostatic Charge5
Removal and Insertion Under Power6
European Communities (EC) Directive Compliance6
Inputs7
Wire the Module9
Input/Output Mapping11
Set Input Filter Times11
Specifications14
Entity Parameters17
Publication 1797-5.7 - March 2010
2 FLEX Ex NAMUR Input Module
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Important User Information
Solid state equipment has operational characteristics differing from those of electromechanical
equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls
(Publication SGI-1.1
http://literature.rockwellautomation.com
equipment and hard-wired electromechanical devices. Because of this difference, and also because of
the wide variety of uses for solid state equipment, all persons responsible for applying this equipment
must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the
many variables and requirements associated with any particular installation, Rockwell Automation, Inc.
cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
available from your local Rockwell Automation sales office or online at
Identifies information about practices or circumstances that can cause an explosion
in a hazardous environment, which may lead to personal injury or death, property
damage, or economic loss.
Identifies information that is critical for successful application and understanding of
the product.
Identifies information about practices or circumstances that can lead to personal
injury or death, property damage, or economic loss. Attentions help you identify a
hazard, avoid a hazard and recognize the consequences.
) describes some important differences between solid state
Publication
Labels may be on or inside the equipment (for example, drive or motor) to alert
people that dangerous voltage may be present.
Labels may be on or inside the equipment (for example, drive or motor) to alert
people that surfaces may reach dangerous temperatures.
1797-5.7 - March 2010
FLEX Ex NAMUR Input Module 3
1
2
3
4
5
6
7
Label Here or
Under Here
8
40231
Module Installation
Component Identification
1Keyswitch5Alignment Bar
2Terminal Base Unit6Alignment Groove
3Flexbus Connector7Latching Mechanism
4Module8Cap Plug
This module must be used with a 1797-TB3 or -TB3S intrinsically safe
terminal base unit.
Publication
1797-5.7 - March 2010
4 FLEX Ex NAMUR Input Module
ATTENTION
20128-M
This equipment is considered Group 1, Class A industrial equipment according
to IEC/CISPR Publication 11. Without appropriate precautions, there may be
potential difficulties ensuring electromagnetic compatibility in other
environments due to conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be mounted within
an enclosure that is suitably designed for those specific environmental
conditions that will be present and appropriately designed to prevent personal
injury resulting from accessibility to live parts. The interior of the enclosure
must be accessible only by the use of a tool. Subsequent sections of this
publication may contain additional information regarding specific enclosure
type ratings that are required to comply with certain product safety
certifications.
1. Rotate keyswitch (1) on terminal base unit (2) clockwise to position 6
as required for this type of module.
Do not change the position of the keyswitch after wiring the
terminal base unit.
2. Make certain the flexbus connector (3) is pushed all the way to the left
to connect with the neighboring terminal base/adapter.
You cannot install the module unless the connector is fully extended.
3. Make sure the pins on the bottom of the module are straight so they
will align properly with the connector in the terminal base unit.
4. Position the module (4) with its alignment bar (5) aligned with the
groove (6) on the terminal base.
5. Press firmly and evenly to seat the module in the terminal base unit.
The module is seated when the latching mechanism (7) is locked into
the module.
6. Make certain that you only connect terminal base units to other
intrinsically safe system modules or adapters to maintain the integrity
of the intrinsically-safe backplane.
Publication
1797-5.7 - March 2010
FLEX Ex NAMUR Input Module 5
ATTENTION
7. Remove cap plug (8) and attach another intrinsically safe terminal base
unit to the right of this terminal base unit if required.
Installation in Zone 1
This module must not be exposed to the environment. Provide a suitable
metal enclosure. This module has a protection factor of IP20.
This module cannot be used in an intrinsically safe environment after it has
been exposed to non-intrinsically safe signals.
Installation in Zone 22
When the module is installed in Zone 22, the following cabinets must be used:
IVK-ISRPI-V16LC; IVK-ISRPI-V8HYW; or IVK-ISRPI-V8LC. These
cabinets can be purchased from Pepperl+Fuchs GmbH, Lilienthalstrasse 200,
68307 Mannheim, Germany. Information available at
www.pepperl-fuchs.com.
The IS-RPI cabinets (type IVK2-ISRPI-V8LC, IVK2-ISRPI-V8HYW, or
IVK2-ISPRI-V16LC) ensures the basic protection for the intrinsically safe
apparatus of the FLEX Ex system for use in Zone 22. It corresponds with
category 3D according to RL 94/9 EG and with the type label marked with
the following information:
Pepperl+Fuchs GmbH
68307 Mannheim
IVK2-ISRPI-V8LC (or IVK2-ISRPI-V8HYW or
IVK2-ISRPI-V16LC)
II 3 D Ex tD A22 IP54 T70 °C X
CE
Serial (manufacturing) number
Model
Electrostatic Charge
Protect the system against electrostatic charge. Post a sign near this module:
WARNING Avoid electrostatic charging.
Publication
1797-5.7 - March 2010
6 FLEX Ex NAMUR Input Module
WARNING
ADVERTÊNCIA! PREVENIR CONTRA O ACÚMULO DE CARGA
ELETROSTÁTICA.
For your convenience, a sign that can be cut out and posted is included in this
installation instruction.
Removal and Insertion Under Power
These modules are designed so you can remove and insert them under
power. However, take special care when removing or inserting modules in an
active process. I/O attached to any module being removed or inserted can
change states due to its input/output signal changing conditions.
If you insert or remove the module while backplane power is on, an electrical
arc can occur. This could cause an explosion in hazardous location
installations.
Be sure that power is removed or the area is nonhazardous before proceeding.
European Communities (EC) Directive Compliance
If this product has the CE mark it is approved for installation within the
European Union and EEA regions. It has been designed and tested to meet
the following directives.
EMC Directive
These products are tested to meet the Council Directive 2004/108/EC by
applying the following standards:
• EN 61000-6-4:2007, Electromagnetic Compatibility (EMC) - Part 6-4:
Generic Standard for Industrial Environments (Class A)
• EN 61000-6-2:2005, Electromagnetic Compatibility (EMC) - Part 6-2:
Generic Standards - Immunity for Industrial Environments
• EN61326-1:2006 (Industrial), Electrical Equipment For
Measurement, Control, and Laboratory Use - Industrial EMC
Requirements
Publication
1797-5.7 - March 2010
FLEX Ex NAMUR Input Module 7
+V
-V
-
+
NAMUR
Prox
Lead Break
Defeat
Bus
μC
Flexbus
Power
Supply
ATEX Directive
These products are tested in conjunction with associated I/O modules to
meet the Council Directive 94/9/EC (ATEX) Equipment and Protective
Systems Intended for Use in Potentially Explosive Atmospheres by applying
the following standards:
• EN60079-11:2007, Explosive atmospheres - Part 11 : equipment
protection by intrinsic safety "i"
• EN60079-0:2006, Electrical apparatus for explosive gas atmospheres Part 0 : general requirements
• EN 60079-26 : 2004, Electrical apparatus for explosive gas
atmospheres - Part 26 : construction, test and marking of Group II
Category 1 G electrical apparatus
• EN61241-0 : 2006, Electrical apparatus for use in the presence of
combustible dust - Part 0: General requirements
• EN61241-11:2006, Electrical apparatus for use in the presence of
combustible dust – Part 11: Protection by intrinsic safety 'iD'
Inputs
Each input can be operated from a NAMUR sensor or a mechanical contact
(if mechanical inputs are used). Do not apply any nonintrinsically safe
signals to this module.
When using an intrinsically safe electrical apparatus according to EN50020,
the European Community directives and regulations must be followed.
The channels in this module are electrically connected to each other.
Connect wiring to the 1797-TB3 or 1797-TB3S terminal base unit as shown
below.
1. Connect the individual input wiring to (+) terminals (0, 2, 4, 6, 8, 10,
12, 14) on the 0 to 15 row (A) and on the 16 to 33 row (B) (terminals
17, 19, 21, 23, 25, 27, 29, 31)as indicated in the table below.
2. Connect the associated input to the corresponding (-) terminal (1, 3,
5, 7, 9, 11, 13, 15) on the 0 to 15 row (A), and on the 16 to 33 row (B)
(terminals 18, 20, 22, 24, 26, 28, 30, 32) for each input as indicated in
the table below.
3. Connect +V dc power to terminal 34 on the 34 to 51 row (C).
4. Connect -V to terminal 35 on the 34 to 51 row (C).
Publication
Make certain that you power this module with an intrinsically safe power
supply. Do not exceed the values listed in the specifications for this module.
If you connect or disconnect wiring while the field-side power is on, an
electrical arc can occur. This could cause an explosion in hazardous location
installations. Be sure that power is removed or the area is nonhazardous
before proceeding.
1797-5.7 - March 2010
FLEX Ex NAMUR Input Module 9
ATTENTION
5. If continuing power to the next terminal base unit, connect a jumper
from terminal 50 (+V) on this base unit to terminal 34 on the next
base unit.
6. If continuing common to the next terminal base unit, connect a
jumper from terminal 51 (-V) on this base unit to terminal 35 on the
next base unit.
-VTerminals 35 and 51
Terminals 16, 33, 40, 41, 42, 43, 44, and 45 are connected to chassis ground.
Input Signal InputInput Source Input Signal
Do not use the unused terminals on this terminal base unit. Using these
terminals as supporting terminals can result in damage to the module
and/or unintended operation of your system.
Publication
1797-5.7 - March 2010
10 FLEX Ex NAMUR Input Module
30820-M
Ex
1797-IBN16
PWR
6
A
B
C
40064A
Grounding
All I/O wiring must use shielded wire. Shields must be terminated external to
the module, such as bus bars and shield-terminating feed throughs.
Indicators
A = Status Indicators
yellow - individual input present;
flashing red - channel fault;
solid red - module did not pass powerup check (channel 0 is solid red
while Powerup check is running)
B = Insertable labels for writing individual input designations
C = Power Indicator - green indicates power applied to module
F = Fault Alarm for an individual chann el
CF = Counter Fast - Filter time constant or bypass, depending on setting (when input 15 is in counter mode) -
CR = Counter Reset- Resets the counter value in read word 1 when input 15 is in counter mode.
FC = Fault mode or Counter mode - determines content of read word 1 (counter value of input 15, or
0 = normal, 1 = fast
0 = normal, 1 = reset
fault data of individual channel) . 0 = counter, 1 = fault data - wire off or short
circuit detect
12…15
Input/Alarm
Filter - Ch
0…11
Set Input Filter Times
You can select the input filter time constant for each group of channels
(channels 00 to 11 or channels 12 to 15).
For example, to set a filter time constant of 5 ms for a dc input module, set
bits 05, 04, 03, 02, 01, and 00 as shown below.
Publication
1797-5.7 - March 2010
12 FLEX Ex NAMUR Input Module
OFF
1234
OFF
1234
Input Filter Times
BitsDescriptionMaximum
020100Filter Times 00…11 (00…13)
050403Filter Times 12…15 (14…17)
000Filter Time 0 (default)1 ms
001Filter Time 11 ms
010Filter Time 22 ms
011Filter Time 33 ms
100Filter Time 45 ms
101Filter Time 59 ms
110Filter Time 617 ms
111Filter Time 733 ms
Bits 00…02 also control the filter times of all 16 fault alarm bits of read word 1 when
module is in fault mode
.
Filter Time
Set the Fault Detect Switch
A switch, located on the backside of the module, lets you select the action of
the module when a fault (wire off or short circuit) is detected. Switch position
1 determines the action for channels 0 to 3, position 2 for channels 4 to 7,
position 3 for channels 8 to 11, and position 4 for channels 12 to 15.
Set the switch:
• OFF to disable fault detection for the selected channels.
• ON to enable fault detection for the selected channels.
Publication
1797-5.7 - March 2010
FLEX Ex NAMUR Input Module 13
Repair
This module is not field-repairable. Any attempt to open this module will void
the warranty and IS certification. If repair is necessary, return this module to
the factory.
Publication
1797-5.7 - March 2010
14 FLEX Ex NAMUR Input Module
Specifications
1797-IBN16 16 NAMUR Input Module
AttributeValue
Number of inputs16 (1 group of 16), nonisolated, sinking
IS input typeEx ia IIB/IIC T4,
AEx ia IIC T4,
Class I, II, III Division 1 Group A-G T4
IS module typeEx ib IIB/IIC T4,
AEx ib IIC T4,
Class I, Division 1 Group A-D T4
Input typeNAMUR compatible
ON-state current2.1 mA
OFF-state current1.2 mA
Hysteresis0.2 mA
Input frequency1000 Hz max
Input pulse width>500 µs on or off
Max load voltageU/V = 7.5V DC
Short circuit currentI = 7.5 mA
Short circuit thresholdI > 6 mA
Lead breakage thresholdI < 0.35 mA
Input delay times
OFF to ON
ON to OFF
Indicators (field side
indication, customer device
driven)
1 ms, 2 ms, 3 ms, 5 ms, 9 ms, 17 ms, 33 ms
1 ms, 2 ms, 3 ms, 5 ms, 9 ms, 17 ms, 33 ms
1 ms default - selectable thru output image table (see
Setting Input Filter Times)
16 yellow status indicators
16 red fault indicators
1 green module power indicator
Publication
1797-5.7 - March 2010
FLEX Ex NAMUR Input Module 15
1797-IBN16 16 NAMUR Input Module
AttributeValue
Output (intrinsically safe)
(16 pin male and female
flexbus connector)
Isolation path
Input to power supply
Input to flexbus
Input to input
Power supply to flexbus
Power supply
(+V, -V intrinsically safe)
Module field-side power
consumption
Power dissipation2.8 W
Thermal dissipationMax 9.6 BTU/hr
Module locationCat. No. 1797-TB3 or 1797-TB3S Terminal Base Unit
Conductor wire size
Dimensions46 mm x 94 mm x 75 mm
Weight200 g (approximate)
Keyswitch Position6
U
< 5.8V DC
i
I
< 400 mA
i
= Negligible
L
i
C
= Negligible
i
Isolation Type
Galvanic to DIN EN 60079-11
Galvanic to DIN EN 60079-11
None
Galvanic to DIN EN 60079-11
U
< 9.5V DC
i
< 1 A
I
i
= Negligible
L
i
= Negligible
C
i
2.8 W
2
(12 gauge) stranded max
4 mm
1.2 mm (3/64 in.) insulation max
(1.8 in. x 3.7 in. x 2.95 in.)
Publication
1797-5.7 - March 2010
16 FLEX Ex NAMUR Input Module
Environmental
AttributeValue
Temperature, operating-20…70 °C (-4…+158 °F)
Temperature,
nonoperating
Relative humidity5…95% noncondensing
VibrationTested 2 g @ 10…500 Hz per IEC68-2-6
Shock, operatingTested to 15 g peak acceleration, 11(+1) ms pulse width
Shock, nonoperatingTested to 15 g peak acceleration, 11(+1) ms pulse width
-40…85 °C (-40…185 °F)
Agency Certification
AttributeValue
CENELECII (1) 2G Ex ib[ia] IIC T4
II (1) D [Ex iaD]
U, C-ULClass I, Groups A, B, C and D; Class II, Groups E, F and G;
FMIntrinsically safe Class I, Div 1, Groups A, B, C, D, T4.
IECEx[Zone 0] Ex ib[ia] IIC T4
INMETROBR-Ex ia/ib IIB/IIC T4
Class III hazardous Locations.
Class I, Zone 1, AEx ib[ia] IIC T4.
Associated Apparatus with intrinsically safe
Connections Class I, II, III, Div 1, Groups A--G
Intrinsically safe Class I, Zone 1, AEx ib[ia] IIC T4.
[Ex iaD]
Certificate of Conformity
AttributeValue
CENELECDMT 98 ATEX E013 X
U, C-ULUL, C-UL File Number E197983
Publication
1797-5.7 - March 2010
FLEX Ex NAMUR Input Module 17
Certificate of Conformity
AttributeValue
FMFM Certificate Number 3009806
INMETRO05/UL-BRAE-0012X
IECExIECEx BVS 09.0027X
Entity Parameters
CE/CENELEC I/O Entity Parameters (Each Channel)
ProtectionGroupAllowed
Capacitance
Uo < 14.5V
Io < 15 mA
Po < 40 mW
Characteristic:
linear
Ex iaIIB1 μF10 mH2.6 mH/Ω
Ex iaIIC300 nF2 mH0.65 mH/Ω
UL, C-UL I/O Entity Parameters
If this product has the UL/C-UL mark, it has been designed, evaluated,
tested, and certified to meet the following standards:
• UL 913, 1988, Intrinsically Safe Apparatus and Associated Apparatus
for Use in Class I, II, and III Division 1, Hazardous (Classified)
Locations
• UL 1203, Explosion-Proof and Dust-Ignition-Proof Electrical
Equipment for Use in Hazardous (Classified) Locations
• UL 2279, Electrical Equipment for Use in Class I, Zone 0, 1, and 2
Hazardous (Classified) Locations
• UL 61010, UL Standard for Safety Electrical Equipment For
Measurement, Control, and Laboratory Use; Part 1: General
Requirements
• CSA C22.2 No. 157-92, Intrinsically Safe and Non-Incendive
Equipment for Use in Hazardous Locations
Allowed
Inductance
Publication
Lo/Ro Ratio
1797-5.7 - March 2010
18 FLEX Ex NAMUR Input Module
• CSA C22.2 No. 30-M1986, Explosion-Proof Enclosures for Use in
Class I Hazardous Locations
• CSA-E79-0-95, Electrical Apparatus for Explosive Gas Atmospheres,
Part 0: General Requirements
• CSA-E79-11-95, Electrical Apparatus for Explosive Gas
Atmospheres, Part 11: Intrinsic Safety “i”
• CSA C22.2 No. 14-95, Industrial Control Equipment
Table 1
Wiring
ChannelTerminalsVoc
Method
1 and 2Any one
channel (for
example,
ch0)
0(+), 1(-)14.515--A, B0.380.0
Isc
Vt
It
(V)
(mA)
(V)
Groups Ca (μF) La (mH)
(mA)
C, E0.9320.0
D, F, G2.4640.0
Wiring Methods
• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each
channel is separated in accordance with the National Electric Code
(NEC) or Canadian Electric Code (CEC).
Table 2
Ter mi na lsVt (V)It (mA)GroupsCa (μF)La (μH)
Male Bus
Connector
5.8400A-G3.03.0
The entity concept allows interconnection of intrinsically safe apparatus
with associated apparatus not specifically examined in combination as a
system when the approved values of Vt and It of the associated apparatus are
less than or equal to V
apparatus and the approved values of C
are greater than C
apparatus.
Publication
1797-5.7 - March 2010
+ C
i
and Isc or V
oc
and Li + L
cable
and I
max
cable
of the intrinsically safe
max
and La of the associated apparatus
a
respectively for the intrinsically safe
FLEX Ex NAMUR Input Module 19
WARNING
AVERTISSEMENT
IMPORTANT
Simple apparatus is defined as a device which neither generates nor stores
more than 1.2V, 0.1 A, 20 mJ, or 25 mW.
Wiring methods must be in accordance with the National Electric Code,
ANSI/NFPA 70, Article 504 and 505 or the Canadian Electric Code CSA
C22.1, Part 1, Appendix F. For additional information refer to ANSI/ISA
RP12.6.
This module, 1797-IBN16, must be used with terminal base 1797-TB3
or 1797-TB3S.
Terminals 36 to 39, and 46 to 49 shall not be connected.
Substitution of components may impair intrinsic safety.
La substitution de composant peut compromettre la securite
intrinseque.
For detailed certification information, refer to the FLEX Ex System
Certification Reference Manual, publication 1797-6.5.6.
Publication
1797-5.7 - March 2010
20 FLEX Ex NAMUR Input Module
ATTENTION
1797- IBN16
Allen-Bradley
B-A
7PWR654321098111013121514
6
16 Point NAMUR Input Module
6
FLEX Ex NAMUR Input
I/O Module
Indicators
Female Bus
Connection
Field Wiring
Terminals
Terminal Base
Terminal Base
Key
Male Bus
Connection
Key Position for
Termina l Base
Insertion
A terminal base may or may not have an I/O module installed.
Publication
1797-5.7 - March 2010
FLEX Ex NAMUR Input Module 21
Hazardous (Classified) Location
Class I, Zones 0, 1, & 2 Groups IIC, IIB, IIA
Class I, Div. 1 & 2 Groups A, B, C, D
Class II, Div. 1 & 2 Groups E, F, G
Class III, Div. 1 & 2
Hazardous (Classified) Location
Class I, Zones 1 & 2 Groups IIC, IIB,
IIA
Class I, Div. 1 & 2 Groups A, B, C, D
Any Simple Apparatus or I.S. device
with Entity Concept parameters (V
max
, I
max
,
C
i
, Li) appropriate for connection to
associated apparatus with Entity Concept
To any intrinsically safe
device or associated
apparatus with Entity
Concept parameters of V
oc
< 5.8V; Isc < 400 mA.
To any intrinsically safe
device or associated
apparatus with Entity
Concept parameters of
V
oc
< 9.5V; Isc < 1 A.
To any IS device with Entity
Concept parameters of
(V
max
, I
max
, Ci, Li) appropriate for
connection to associated
apparatus with Entity
Concept parameters listed in
Table 2.
ch0
ch1
ch2
ch3
ch4
ch5
ch6
ch7
29(+)
30(-)
1797-IBN16
16
Shield Connection Only
50
51
35
34
Female Bus Connector
V
max
=5.8V
I
max
=400mA
C
i
=1350nF
L
i
=negligible
V
max
=9.5V
I
max
=1A
C
i
=negligible
L
i
=negligible
Male Bus
Connector
33
40
41
42
43
44
45
31(+)
32(-)
25(+)
26(-)
27(+)
28(-)
21(+)
22(-)
23(+)
24(-)
17(+)
18(-)
19(+)
20(-)
12(+)
13(-)
14(+)
15(-)
8(+)
9(-)
10(+)
11(-)
4(+)
5(-)
6(+)
7(-)
0(+)
1(-)
2(+)
3(-)
ch8
ch9
ch10
ch11
ch12
ch13
ch14
ch15
Publication
1797-5.7 - March 2010
22 FLEX Ex NAMUR Input Module
FM I/O Entity Parameters (Each Channel)
If this product has the FM mark, it has been designed, evaluated, tested and
certified to meet the following standards:
• FM C1. No 3600:1998, Electrical Equipment for Use in Hazardous
(Classified) Locations General Requirements
• FM C1. No 3610:1999, Intrinsically Safe Apparatus and Associated
Apparatus for Use in Class I, II, III Division 1 Hazardous (Classified)
Locations
• FM C1. No 3615:1989, Explosionproof Electrical Equipment General
Requirements
• FM C1. No 3810:1989, 1995, Electrical and Electronic Test,
Measuring and Process Control Equipment
• ANSI/NEMA 250, 1991, Enclosures for Electrical Equipment
Wiring Methods
• Wiring method 1 - Each channel is wired separately.
• Wiring method 2 - Multiple channels in one cable, providing each
channel is separated in accordance with the National Electric Code
(NEC).
Table 1
Wiring
Method
1 and 2Any one
Channel Terminals Voc
(V)
0(+), 1(-)14.5 15--A, B0.380.0
channel
(for
example,
ch0)
Isc
(mA)
Vt
(V)
It
Groups Ca
(mA)
C, E0.9320.0
D, F, G2.4640.0
(μF)
La
(mH)
Publication
1797-5.7 - March 2010
FLEX Ex NAMUR Input Module 23
WARNING
AVERTISSEMENT
Table 2
Ter mi na lsVt (V)It (mA)GroupsCa (μF)La (μH)
Male Bus
Connector
5.8400A-G3.03.0
The entity concept allows interconnection of intrinsically safe apparatus
with associated apparatus not specifically examined in combination as a
system when the approved values of Voc and Isc or Vt and It of the associated
apparatus are less than or equal to V
apparatus and the approved values of C
+ C
are greater than C
i
and Li + L
cable
and I
max
cable
of the intrinsically safe
max
and La of the associated apparatus
a
respectively for the intrinsically safe
apparatus. The internal capacitances Ci of the terminal base must be taken
into account to verify the intrinsic safety.
Simple apparatus is defined as a device which neither generates nor
stores more than 1.2V, 0.1 A, 20 μJ, or 25 mW.
Wiring methods must be in accordance with the National Electric Code,
ANSI/NFPA 70, Article 504 and 505. For additional information refer to
ANSI/ISA RP12.6.
This module, 1797-IBN16, must be used with terminal base 1797-TB3
or 1797-TB3S.
Terminals 36 to 39, and 46 to 49 shall not be connected.
Substitution of components may impair intrinsic safety.
La substitution de composant peut compromettre la securite
intrinseque.
Publication
1797-5.7 - March 2010
24 FLEX Ex NAMUR Input Module
ATTENTION
1797- IBN16
Allen-Bradley
B-A
7PWR654321098111013121514
6
16 Point NAMUR Input Module
6
FLEX Ex NAMUR Input
I/O Module
Indicators
Female Bus
Connection
Field Wiring
Terminals
Terminal Base
Unit
Terminal Base
Key
Male Bus
Connection
Key Position for
Terminal Base
Insertion
42060
A terminal base may or may not have an I/O module installed.
Publication
1797-5.7 - March 2010
FLEX Ex NAMUR Input Module 25
ch0
ch1
ch2
ch3
ch4
ch5
ch6
ch7
29(+)
30(-)
1797-IBN16
16
Shield Connection Only
50
51
35
34
Female Bus Connector
V
max
=5.8V
I
max
=400mA
C
i
=1350nF
L
i
=negligible
V
max
=9.5V
I
max
=1A
C
i
=negligible
L
i
=negligible
Male Bus
Connector
33
40
41
42
43
44
45
31(+)
32(-)
25(+)
26(-)
27(+)
28(-)
21(+)
22(-)
23(+)
24(-)
17(+)
18(-)
19(+)
20(-)
12(+)
13(-)
14(+)
15(-)
8(+)
9(-)
10(+)
11(-)
4(+)
5(-)
6(+)
7(-)
0(+)
1(-)
2(+)
3(-)
ch8
ch9
ch10
ch11
ch12
ch13
ch14
ch15
Any Simple Apparatus or FM approved device
with Entity Concept parameters (V
max
, I
max
, Ci, Li)
appropriate for connection to associated apparatus
For connection to other
modules, refer to the
General FM Certification
Information in publication
1797-6.5.6.
From FM approved devices,
1797-PS2N.
For connection to other
modules, refer to the
General FM Certification
Information in publication
1797-6.5.6.
Hazardous (Classified) Location
Class I, Zone 1 Group IIC
Class I, Div. 1 Groups A, B, C, D
Hazardous (Classified) Location
Class I, Zone 0 Group IIC
Class I, Div. 1 Groups A, B, C, D
Class II, Div. 1 Groups E, F, G
Class III, Div. 1
Publication
1797-5.7 - March 2010
26 FLEX Ex NAMUR Input Module
WARNING Avoid electrostatic charging.
ADVERTÊNCIA! PREVENIR CONTRA O ACÚMULO
DE CARGA ELETROSTÁTICA.
Publication
1797-5.7 - March 2010
Notes:
FLEX Ex NAMUR Input Module 27
Publication
1797-5.7 - March 2010
Rockwell Automation Support
Rockwell Automation provides technical information on the Web to assist you in using
its products. At http://support.rockwellautomation.com
manuals, a knowledge base of FAQs, technical and application notes, sample code and
links to software service packs, and a MySupport feature that you can customize to
make the best use of these tools.
For an additional level of technical phone support for installation, configuration, and
troubleshooting, we offer TechConnect Support programs. For more information,
contact your local distributor or Rockwell Automation representative, or visit
http://support.rockwellautomation.com
.
Installation Assistance
If you experience a problem with a hardware module within the first 24 hours of
installation, please review the information that's contained in this manual. You can also
contact a special Customer Support number for initial help in getting your module up
and running.
United States1.440.646.3434 Monday – Friday, 8am – 5pm EST
Outside United States Please contact your local Rockwell Automation representative for
any technical support issues.
New Product Satisfaction Return
Rockwell tests all of its products to ensure that they are fully operational when shipped
from the manufacturing facility. However, if your product is not functioning, it may
need to be returned.
United StatesContact your distributor. You must provide a Customer Support case
number (see phone number above to obtain one) to your distributor
in order to complete the return process.
Outside United States Please contact your local Rockwell Automation representative for
return procedure.
Allen-Bradley, Rockwell Automation, ControlLogix, RSLinx, TechConnect, and FLEX I/O are trademarks of
Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.