Rockwell Automation 1492-CM800-LD004 User Manual

Field Wire Conversion Module for Modicon B806-032 to two 1756-OA16
(Cat 1492-CM800-LD004)
10000021863 (Version 00)
Printed in Germany
Local language (French, Italian, German & Spanish) versions of this document can be downloaded by going to www.ab.com. In the left margin click on Publications Library and Literature Library. In the Search Area (right margin), Search by Catalog Number and in the Search box type in the catalog number of the conversion system component.
The 1492-CM800-LD004 conversion module provides field wire signal conversion from a Modicon® B806-032, 80 to 130Vac , 32-pt output module to two ControLogix 1756-OA16, 74 to 265Vac , 16-pt output modules. The conver­sion module provides the mating connections to the B806-032 swing-arm (terminal block) with the attached field wires. It routes those signals, via its two 20-pin connector and two 1492-CABLEX pre-wired cables to compatible terminals of the two 1756-OA16 modules (refer to the Wiring Diagram on page 2).
II. Module Installation
The 1492-CM800-LD004 conversion module must be installed in a 1492 conversion base-plate and cover-plate assem­bly. The installation of the module into the assembly is explained in the Installation Manual that ships with the conversion assembly. For a list of compatible assemblies refer to Appendix A.
III. Conversion Module Compatibility Matrix
This is the cable length in meters and tenths of meters (e.g. 015 = 1.5 meters). Recommended cable
length is 003 (00.3 meters).
Two 20-pin connectors (P1 and P2) for two 1492-CABLEX cables
Mating connector for B800 Terminal Block
Conversion Module Compatible 800
Output Module
Compatible 1756
Output Module
Required 1492 Cable
1492-CM800-LD004 B806-032 Two 1756-OA16 Two 1492-CABLE
X
1492-CM800-LD004 Conversion Module
De-energize and lockout any and all power to all I/O field devices connected to the Modicon 800 I/O housing, and the power to the 800 I/O housing itself. Ensure all power is de-energized and locked out to any device in the control cabinet where the conversion is to be performed. Ensure work is performed by qualified personnel.
WARNING
Refer to conversion module Specifications Section: Maximum Operating Voltage
(2)
10000021863 (Version 00)
IV. Conversion Module Wiring Diagram
The following diagram shows the connections from the existing B806-032 swing-arm, through the conversion module, 1492 cables and to the 1756-OA16 output modules. The diagram can be used as an aid in possible system troubleshooting.
1756-OA16
1756-OA16
1492-ACABLE003X
1492-ACABLE003X
1492-CM800-LD004
Conversion: B806-032 to 1756-OA16 Qty 2 with 1492-CM800-LD004
B806-032 Swing Arm
1 2 3 4
3
5
22
6
4
7
23
8
5
9
24
10
6
11
25
12
7
13
26
8
15
27
16
9
17
28
18
10
19
29
20
14
12
31
13
32
14
33
15
34
16
35
17
36
18
37
19
38
21
11
Output 1
Output 17
Output 2
Output 18
Output 3
Output 19
Output 4
Output 20
Output 5
Output 21
Output 6
Output 22
Output 7
Output 23
Output 8
Output 24
Output 9
Output 25
Output 10
Output 26
Output 11
Output 27
Output 12
Output 28
Output 13
Output 29
Output 14
Output 30
Output 15
Output 31
Output 16
Output 32
39
20 2Grp 1 Neut
40
1
30
Not Used
Grp 1 Hot
Not Used
1 2 3 4 5 6 7 8 9 10 11 12 13
15 16 17 18 19 20
14
MODULE A
MODULE B
P1
P2
10
L1-0
OUT-0
1
OUT-1
2
OUT-2
3
OUT-3
4
OUT-4
5
OUT-5
6
OUT-6
7
OUT-7
8
OUT-8
11
OUT-9
12
OUT-10
13
OUT-11
14
OUT-12
15
OUT-13
16
OUT-14
17
OUT-15
18
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
L1-1
20
9
L2-0
19
L2-1
10
L1-0
OUT-0
1
OUT-1
2
OUT-2
3
OUT-3
4
OUT-4
5
OUT-5
6
OUT-6
7
OUT-7
8
OUT-8
11
OUT-9
12
OUT-10
13
OUT-11
14
OUT-12
15
OUT-13
16
OUT-14
17
OUT-15
18
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
L1-1
20
9
L2-0
19
L2-1
Grp 2 Neut
Not Used
Grp 2 Hot
Not Used
LOAD
L2
L1
Conversion Module Installation and Application Considerations
This configuration uses two (2) 1756-OA16 output modules to replace a single B806-032 output module. This may require the use
of a larger 1756 I/O Chassis. Ensure there is sufficient panel space to allow for this possibility.
The B806-032 module output current limits versus 1756-OA16 limits are as follows: B806-032 1756-OA16 w/ 1492-CABLE003X a) Current/Point 1A 0.5A b) Current/Group 8A 2A c) Current/Module 16A (32 pts) 4A (16 pts) d) Surge Current/Pt 15A for 1 cycle 5A for 43ms
The B806-032 module did NOT provide fusing. The 1756-OA16 provides a single fuse per group.
The 1492-CABLE003X current is limited to 2A per pin.Refer to your B806-032 and 1756-OA Installation Manual wiring schematics and diagrams for more details.
Ensure 1756 output
module ratings are not exceeded. [Reference Doc: 41170-753 (Version 03)]
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and output module). Read and understand these considerations before installation. In addition, refer to the current draw requirements of the existing loads for this configuration to ensure they are within the current ratings of the 1756 output module.
WARNING
(3)
10000021863 (Version 00)
V. 1492-CM800-LD004 Conversion Module Specifications
(Operating specifications are when installed in the Conversion System base / cover-plate assembly)
Specification
Value
Dimensions
288.9 mm (height) x 139.7 mm (depth) x 44.5 mm (width)
11.37 in. (height) x 5.5 in. (depth) x 1.75 in. (width) Approximate Shipping Weight
300g (0.66 lbs) (includes carton) Storage Temperature
-40 to +85°C (-40 to +185°F) Operating Temperature
0 to 55°C (32 to 131°F) Operating Humidity
5 to 95% at 55°C (non-condensing) Shock Non-operating Operating
50g 30g Operating Vibration
2g @ 10-500Hz Maximum Operating Voltage
125 Vac at 47 to 63 Hz Max. Module Operating Current
Per Point: Per Module:
2 Amps (1492-CABLE connection pins are limited to 2A per pin) 12 Amps
Agency Certifications UL Classified: Under UL File Number E113724 CSA CE: compliant for all applicable directives Pollution Degree
2 Environmental Rating
IP20
Refer to the Wiring Diagram(s) for current limits for a specific configuration.
NOTICE
10000021863 (Version 00)
Printed in Germany
Article No. 4351870000
VI. Appendix A - 800 Housing to 1756 Chassis Conversion System Selection Process
1) Determine the number of 800 I/O modules actually used in the 800 I/O Housing to be converted to 1756.
2) Review the data in Column 5 from the below table, and select a 1756 I/O Chassis which meets your conversion needs from Step 1. Ensure the information from the I/O Conversion module table is reviewed first since in some cases, two 1756 modules are needed to replace one 800 I/O module.
3) Once the 1756 Chassis is selected, refer to Column 7 and select the Conversion Assembly.
One chassis slot required for the ControlLogix processor or a remote I/O adapter type module. The footprint and mounting dimensions of the 1492 Conversion Assembly (base plate and cover plate) match those of the
Modicon I/O Housing.
Width dimension includes the 1756 Chassis power supply. Surplus Chassis width as compared to the 800 I/O Housing is divided equally when mounting it on the Conversion Assembly. Mounting holes for the 1756 I/O Chassis are pre-drilled and pre-tapped into the Conversion Assembly cover plate.
Modicon is a Registered Trademark of Group Schneider.
AS-H810-xxx
AS-H819-103
AS-H819-209
AS-H819-100
AS-H827-103
AS-H827-209
AS-B827-100
Modicon 800 I/O
Housing Cat Number
1492-MUA4-MB3
1492-MUA7-A10-
MB4679
1492-MUA10-A13-
MB81011
Conversion Assembly
Catalog Number
3
4
6
7
8
10
11
10.25”
17.5”
17.5”
17.5”
27.1”
27.1”
27.1”
10.25”
A7 = 14.49”
A10 = 19.02”
A7 = 14.49”
A10 = 19.02”
A7 = 14.49”
A10 = 19.02” A10 = 19.02”
A13 = 23.15” A10 = 19.02”
A13 = 23.15” A10 = 19.02”
A13 = 23.15”
1756 Chassis
Width 
Dimension
3
A7 = 6, A10=9
A7 = 6, A10=9
A7 = 6, A10=9
A10 = 9, A13=12
A10 = 9, A13=12
A10 = 9, A13=12
1756 I/O Chassis
Catalog Number
1 72 3 654
1756-A4
1756-A7
or
1756-A10
1756-A10
or
1756-A13
Max. Number
of 800 Housing
Slots for I/O
800 Housing
Width
Dimension
Max. Number
of 1756 Chassis
Slots for I/O