Rockwell Automation 1492-CM800-LD003 User Manual

Field Wire Conversion Module for Modicon B805-016 or B853-016 to 1756-IA16
(Cat 1492-CM800-LD003)
10000021858 (Version 00)
Printed in Germany
Local language (French, Italian, German & Spanish) versions of this document can be downloaded by going to www.ab.com. In the left margin click on Publications Library and Literature Library. In the Search Area (right margin), Search by Catalog Number and in the Search box type in the catalog number of the conversion system component.
The 1492-CM800-LD003 conversion module provides field wire signal conversion from a Modicon® B805-016 or B853-016, 80 to 130Vac , 16-pt input module to a ControLogix 1756-IA16, 74 to 132Vac , 16-pt input module. The conversion module provides the mating connections to the B805-016 or B853-016 swing-arm (terminal block) with the attached field wires. It routes those signals via its 20-pin connector and a 1492-CABLEX pre-wired cable to compat­ible terminals of the 1756-IA16 (refer to the Wiring Diagram on pages 2 and 3).
II. Module Installation
The 1492-CM800-LD003 conversion module must be installed in a 1492 conversion base-plate and cover-plate assembly. The installation of the module into the assembly is explained in the Installation Manual that ships with the conversion assembly. For a list of compatible assemblies refer to Appendix A.
III. Conversion Module Compatibility Matrix
This is the cable length in meters and tenths of meters (e.g. 015 = 1.5 meters). Recommended cable length is 003 (00.3 meters).
Conversion Module Compatible 800
Input Module
Compatible 1756
Input Module
Required 1492 Cable
1492-CM800-LD003 B805-016 1756-IA16 1492-CABLE
X
1492-CM800-LD003 B853-016 1756-IA16 1492-CABLE
X
20-pin connector for 1492-CABLEX
Mating connector for B800 Terminal Block
1492-CM800-LD003 Conversion Module
De-energize and lockout any and all power to all I/O field devices connected to the Modicon 800 I/O housing, and the power to the 800 I/O housing itself. Ensure all power is de-energized and locked out to any device in the control cabinet where the conversion is to be performed. Ensure work is performed by qualified personnel.
WARNING
Refer to conversion module Specifications Section: Maximum Operating Voltage
(2)
10000021858 (Version 00)
IV. Conversion Module Wiring Diagram
The following diagrams show the connections from the existing B805-016 and B853-016 swing-arm, through the conver­sion module, 1492 cable and to the 1756-IA16 input module. The diagrams can be used as an aid in possible system troubleshooting.
1756-IA16
1492-CABLE003X
1492-CM800-LD003
Conversion: B805-016 to 1756-IA16 with 1492-CM800-LD003
B805-016 Swing Arm
Conversion Module Installation and Application Considerations
The input delay times for the B805-016 module versus 1756-IA16 module are as follows:
B805-016 1756-IA16
a) Off-to-On Delay 6ms 10ms (plus selectable filter) b) On-to-Off Delay 18ms 8ms (plus selectable filter)
Refer to your B805-016 and 1756-IA16 Installation Manual wiring schematics and diagrams for more details.
[Reference Doc: 41170-752 (Version 03)]
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and output module). Read and understand these considerations before installation.
WARNING
10
L2-0
IN-0
1
IN-1
2
IN-2
3
IN-3
4
IN-4
5
IN-5
6
IN-6
7
IN-7
8
IN-8
11
IN-9
12
IN-10
13
IN-11
14
IN-12
15
IN-13
16
IN-14
17
IN-15
18
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
L2-1
20
9
L2-0
19
L2-1
9 1
1
19
2
3
3
4
4
5
5
6
6
7
7
8
8
9
19
10 1111 12
12
13
13 14
15
15
16
16
17
17 18 18
20
14
2
L1
L2
Input 13
Input 15
Input 14
Input 16
Input 5
Input 7
Input 6
Input 8
Input 1
Input 3
Input 2
Input 4
Input 9
Input 11
Input 10
Input 12
Neutral Grp 1
Neutral Grp 2
10 20
Not Used Not Used