Rockwell Automation 1492-CM800-LD002 User Manual

Field Wire Conversion Module for Modicon B804-116 to 1756-OA16 or B824-016 to 1756-OB16E
(Cat 1492-CM800-LD002)
10000021853 (Version 00)
Printed in Germany
Local language (French, Italian, German & Spanish) versions of this document can be downloaded by going to www.ab.com. In the left margin click on Publications Library and Literature Library. In the Search Area (right margin), Search by Catalog Number and in the Search box type in the catalog number of the conversion system component.
I. Module Description
The 1492-CM800-LD002 conversion module provides field wire signal conversion from a Modicon® B804-116, 80 to 130Vac , 16-pt output module to a ControLogix 1756-OA16, 74 to 265Vac , 16-pt output module or a B824-016, 20 to 28Vdc, 16-pt output module to a 1756-OB16E, 10-31.2Vdc, 16-pt electronically fused output module. The conversion module provides the mating connections to the B804-116 or B824-016 swing-arm (terminal block) with its attached field wires. It routes those signals via its 20-pin connector and a 1492-CABLEX pre-wired cable to compat­ible terminals of the 1756-OA16 or 1756-OB16E (refer to the Wiring Diagrams on pages 2 and 3 for details).
II. Module Installation
The 1492-CM800-LD002 conversion module must be installed in a 1492 conversion base-plate and cover-plate assem­bly. The installation of the module into the assembly is explained in the Installation Manual that ships with the conversion assembly. For a list of compatible assemblies refer to Appendix A.
III. Conversion Module Compatibility Matrix
This is the cable length in meters and tenths of meters (e.g. 015 = 1.5 meters). Recommended cable length is 003 (00.3 meters).
20-Pin Connector for 1492-CABLE
X
Mating Connector for B800 Terminal Block
Conversion Module Compatible 800
Output Module
Compatible 1756
Output Module
Required 1492 Cable
1492-CM800-LD002 B804-116 1756-OA16 1492-CABLE
X
1492-CM800-LD002 B824-016 1756-OB16E 1492-CABLE
X
De-energize and lockout any and all power to all I/O field devices connected to the Modicon 800 I/O housing, and the power to the 800 I/O housing itself. Ensure all power is de-energized and locked out to any device in the control cabinet where the conversion is to be performed. Ensure work is performed by qualified personnel.
WARNING
1492-CM800-LD002 Conversion Module
Refer to conversion module Specifications Section: Maximum Operating Voltage
(2)
10000021853 (Version 00)
IV. Conversion Module Wiring Diagram
The following diagrams show the connections from the existing B804-116 or B824-016 swing-arm, through the conversion module, 1492 cable and to the 1756-OA16 or 1756-OB16E output module. The diagrams can be used as an aid in possible system troubleshooting.
Conversion Module Installation and Application Considerations
The B804-116 module output current limits versus 1756-OA16 limits are as follows: B804-116 1756-OA16 w/ 1492-CABLE003X a) Current/Point 2A 0.5A b Current/Group 6A 2A b) Current/Module 12A 4A c) Surge Current/Pt 50A for 1 cycle 5A for 43ms
1756-OA16
1492-CABLE003X
1492-CM800-LD002
Conversion: B804-116 to 1756-OA16 with 1492-CM800-LD002
B804-116 Swing Arm
The 1492-CABLE003U current is limited to 2A per pin.
Refer to your B804-116 and 1756-OA16 Installation Manual wiring schematics and diagrams for more details. Ensure
1756 output module ratings are not exceeded.
[Reference Doc: 41170-751 (Version 03)]
10
L1-0
OUT-0
1
OUT-1
2
OUT-2
3
OUT-3
4
OUT-4
5
OUT-5
6
OUT-6
7
OUT-7
8
OUT-8
11
OUT-9
12
OUT-10
13
OUT-11
14
OUT-12
15
OUT-13
16
OUT-14
17
OUT-15
18
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
10 1 9 2 1 3 2 4 3 5 4 6 5 7 6 8 7 9 8 10 11 11 12 12 13 13 14 15 15 16 16 17 17 18 18 20 19 19 20
14
Red/Green
L1-1
20
9
L2-0
19
L2-1
LOAD
L1
L2
Hot Grp 1
Output 13
Output 15
Output 14
Output 16
Neutral Grp 2
Output 5
Output 7
Output 6
Output 8
Output 1
Output 3
Output 2
Output 4
Output 9
Output 11
Output 10
Output 12
Hot Grp 2
Neutral Grp 1
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and output module). Read and understand these considerations before installation. In addition, refer to the current draw requirements of the existing loads for this configuration to ensure they are within the current ratings of the 1756 output module.
WARNING