Field Wire Conversion Module for Modicon B804-116 to 1756-OA16 or
B824-016 to 1756-OB16E
(Cat 1492-CM800-LD002)
10000021853 (Version 00)
Printed in Germany
Local language (French, Italian, German & Spanish) versions of this document can be downloaded by going to www.ab.com.
In the left margin click on Publications Library and Literature Library. In the Search Area (right margin), Search by Catalog
Number and in the Search box type in the catalog number of the conversion system component.
I. Module Description
The 1492-CM800-LD002 conversion module provides field wire signal conversion from a Modicon® B804-116, 80 to
130Vac , 16-pt output module to a ControLogix 1756-OA16, 74 to 265Vac , 16-pt output module or a B824-016,
20 to 28Vdc, 16-pt output module to a 1756-OB16E, 10-31.2Vdc, 16-pt electronically fused output module. The
conversion module provides the mating connections to the B804-116 or B824-016 swing-arm (terminal block) with its
attached field wires. It routes those signals via its 20-pin connector and a 1492-CABLEX pre-wired cable to compatible terminals of the 1756-OA16 or 1756-OB16E (refer to the Wiring Diagrams on pages 2 and 3 for details).
II. Module Installation
The 1492-CM800-LD002 conversion module must be installed in a 1492 conversion base-plate and cover-plate assembly. The installation of the module into the assembly is explained in the Installation Manual that ships with the conversion
assembly. For a list of compatible assemblies refer to Appendix A.
III. Conversion Module Compatibility Matrix
This is the cable length in meters and tenths of meters (e.g. 015 = 1.5 meters). Recommended cable
length is 003 (00.3 meters).
20-Pin Connector for 1492-CABLE
X
Mating Connector for
B800 Terminal Block
Conversion Module Compatible 800
Output Module
Compatible 1756
Output Module
Required 1492 Cable
1492-CM800-LD002 B804-116 1756-OA16 1492-CABLE
X
1492-CM800-LD002 B824-016 1756-OB16E 1492-CABLE
X
De-energize and lockout any and all power to all I/O field devices connected to the Modicon 800 I/O
housing, and the power to the 800 I/O housing itself. Ensure all power is de-energized and locked out to
any device in the control cabinet where the conversion is to be performed. Ensure work is performed by
qualified personnel.
WARNING
1492-CM800-LD002 Conversion Module
Refer to conversion module Specifications Section: Maximum Operating Voltage

(2)
10000021853 (Version 00)
IV. Conversion Module Wiring Diagram
The following diagrams show the connections from the existing B804-116 or B824-016 swing-arm, through the conversion
module, 1492 cable and to the 1756-OA16 or 1756-OB16E output module. The diagrams can be used as an aid in
possible system troubleshooting.
Conversion Module Installation and Application Considerations
The B804-116 module output current limits versus 1756-OA16 limits are as follows:
B804-116 1756-OA16 w/ 1492-CABLE003X
a) Current/Point 2A 0.5A
b Current/Group 6A 2A
b) Current/Module 12A 4A
c) Surge Current/Pt 50A for 1 cycle 5A for 43ms
1756-OA16
1492-CABLE003X
1492-CM800-LD002
Conversion: B804-116 to 1756-OA16 with 1492-CM800-LD002
B804-116 Swing Arm
The 1492-CABLE003U current is limited to 2A per pin.
Refer to your B804-116 and 1756-OA16 Installation Manual wiring schematics and diagrams for more details. Ensure
1756 output module ratings are not exceeded.
[Reference Doc: 41170-751 (Version 03)]
10
L1-0
OUT-0
1
OUT-1
2
OUT-2
3
OUT-3
4
OUT-4
5
OUT-5
6
OUT-6
7
OUT-7
8
OUT-8
11
OUT-9
12
OUT-10
13
OUT-11
14
OUT-12
15
OUT-13
16
OUT-14
17
OUT-15
18
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
10 1
9 2
1 3
2 4
3 5
4 6
5 7
6 8
7 9
8 10
11 11
12 12
13 13
14
15 15
16 16
17 17
18 18
20 19
19 20
14
Red/Green
L1-1
20
9
L2-0
19
L2-1
LOAD
L1
L2
Hot Grp 1
Output 13
Output 15
Output 14
Output 16
Neutral Grp 2
Output 5
Output 7
Output 6
Output 8
Output 1
Output 3
Output 2
Output 4
Output 9
Output 11
Output 10
Output 12
Hot Grp 2
Neutral Grp 1
There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and output module). Read and understand these
considerations before installation. In addition, refer to the current draw requirements of the existing
loads for this configuration to ensure they are within the current ratings of the 1756 output module.
WARNING

(3)
10000021853 (Version 00)
IV. Conversion Module Wiring Diagram (Continued)
1756-OB16E
1492-CABLE003X
1492-CM800-LD002
Conversion: B824-016 to 1756-OB16E with 1492-CM800-LD002
B824-016 Swing Arm
10 1
9 2
1 3
2 4
3 5
4 6
5 7
6 8
7 9
8 10
11 11
12 12
13 13
14
15 15
16 16
17 17
18 18
20 19
19 20
14
24 VDC
Output 13
Output 15
Output 14
Output 16
Common Grp 2
Output 5
Output 7
Output 6
Output 8
Output 1
Output 3
Output 2
Output 4
Output 9
Output 11
Output 10
Output 12
24 VDC
Common Grp 1
10
DC-0+
OUT-0
1
OUT-1
2
OUT-2
3
OUT-3
4
OUT-4
5
OUT-5
6
OUT-6
7
OUT-7
8
OUT-8
11
OUT-9
12
OUT-10
13
OUT-11
14
OUT-12
15
OUT-13
16
OUT-14
17
OUT-15
18
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
Red/Green
DC-1+
20
9
RTN OUT-0
19
RTN OUT-1
+
-
LOAD
Conversion Module Installation and Application Considerations
The B824-016 module output current limits versus 1756-OB16E limits are as follows:
B824-016 1756-OB16E w/ 1492-CABLE003X
a) Current/Point 2A 1A
b) Current/Group 6A 2A
c) Current/Module 12A 4A
d) Surge Current/Pt 5A for 10ms 2A for 10ms
The B824-016 provided a single mechanical fuse per group. The 1756-OB16E is electronically fused per group. Refer to the
1756-OB16E Installation Manual for electronic fusing details.
The 1492-CABLE003X current is limited to 2A per pin.
Refer to your B824-016 and 1756-OB16E Installation Manual wiring schematics and diagrams for more details.
Ensure 1756
output module ratings are not exceeded.
[Reference Doc: 41170-757 (Version 03)]
There are several key application considerations and system specifications (bottom of drawing) when
using these components (conversion module, cable and output module). Read and understand these
considerations before installation.
WARNING

10000021853 (Version 00)
Printed in Germany
Article No. 4351850000
V. 1492-CM800-LD002 Conversion Module Specifications
(Operating specifications are when installedin the Conversion System base / cover-plate assembly)
VI. Appendix A - 800 Housing to 1756 Chassis Conversion System Selection Process
1) Determine the number of 800 I/O modules actually used in the 800 I/O Housing to be converted to 1756 I/O.
2) Review the data in Column 5 from the below table, and select a 1756 I/O Chassis which meets your conversion
needs from Step 1. Ensure the information from the I/O Conversion module table is reviewed first since in some
cases, two 1756 modules are needed to replace one 800 I/O module.
3) Once the 1756 Chassis is selected, refer to Column 7 and select the Conversion Assembly.
One chassis slot required for the ControlLogix processor or a remote I/O adapter type module.
The footprint and mounting dimensions of the 1492 Conversion Assembly (base plate and cover plate) match those of the
Modicon I/O Housing.
Width dimension includes the 1756 Chassis power supply.
Surplus Chassis width as compared to the 800 I/O Housing is divided equally when mounting it on the Conversion Assembly.
Mounting holes for the 1756 I/O Chassis are pre-drilled and pre-tapped into the Conversion Assembly cover-plate.
Modicon is a Registered Trademark of Group Schneider.
Specification
288.9 mm (height) x 139.7 mm (depth) x 44.5 mm (width)
11.37 in. (height) x 5.5 in. (depth) x 1.75 in. (width)
Approximate Shipping Weight
300g (0.66 lbs) (includes carton)
-40 to +85°C (-40 to +185°F)
5 to 95% at 55°C (non-condensing)
Shock
Non-operating
Operating
Maximum Operating Voltage
125 Vac at 47 to 63Hz or 150 Vdc
Max. Module Operating Current
Per Point:
Per Module:
2 Amps (1492-CABLE connection pins are limited to 2A per pin)
12 Amps
UL Classified: Under UL File Number E113724
CSA
CE: compliant for all applicable directives
Environmental Rating IP20
AS-H810-xxx
AS-H819-103
AS-H819-209
AS-H819-100
AS-H827-103
AS-H827-209
AS-B827-100
Modicon 800 I/O
Housing Cat Number
1492-MUA4-MB3
1492-MUA7-A10-
MB4679
1492-MUA10-A13-
MB81011
Conversion Assembly
Catalog Number
3
4
6
7
8
10
11
10.25”
17.5”
17.5”
17.5”
27.1”
27.1”
27.1”
10.25”
A7 = 14.49”
A10 = 19.02”
A7 = 14.49”
A10 = 19.02”
A7 = 14.49”
A10 = 19.02”
A10 = 19.02”
A13 = 23.15”
A10 = 19.02”
A13 = 23.15”
A10 = 19.02”
A13 = 23.15”
1756 Chassis
Width
Dimension
3
A7 = 6, A10=9
A7 = 6, A10=9
A7 = 6, A10=9
A10 = 9, A13=12
A10 = 9, A13=12
A10 = 9, A13=12
1756 I/O Chassis
Catalog Number
1 72 3 654
1756-A4
1756-A7
or
1756-A10
1756-A10
or
1756-A13
Max. Number
of 800 Housing
Slots for I/O
800 Housing
Width
Dimension
Max. Number
of 1756 Chassis
Slots for I/O
Refer to the Wiring Diagram(s) for
current limits for a specific configuration.
NOTICE