Rockwell Automation 1492-CM800-LD001 User Manual

Fused Field Wire Conversion Module for Modicon B802-008 to 1756-OA8
(Cat 1492-CM800-LD001)
10000021848 (Version 00)
Printed in Germany
Local language (French, Italian, German & Spanish) versions of this document can be downloaded by going to www.ab.com. In the left margin click on Publications Library and Literature Library. In the Search Area (right margin), Search by Catalog Number and in the Search box type in the catalog number of the conversion system component.
The 1492-CM800-LD001 conversion module provides field wire signal conversion from a Modicon® B802-008, 80 to 130Vac , 8-pt output module to a ControLogix 1756-OA8, 74 to 265Vac , 8-pt output module. The conversion module provides the mating connections to the B802-008 swing-arm (terminal block) with the attached field wires. It routes those signals, via its 20-pin connector and a 1492-CABLEU pre-wired cable to the compatible terminals of the 1756-OA8. To maintain the functionality of the B802-008 output module the conversion module provides a mechanical fuse for each of the two power sources (L1-0 and L1-1) on the 1756-OA8 (refer to the Wiring Diagram and Fuse Installation and Removal sections for details).
II. Module Installation
The 1492-CM800-LD001 conversion module must be installed in a 1492 conversion system base-plate and cover­plate assembly. The installation of the module into the assembly is explained in the Installation Manual that ships with the conversion assembly. For a list of compatible assemblies refer to Appendix A
III. Conversion Module Compatibility Matrix
De-energize and lockout any and all power to all I/O field devices connected to the Modicon 800 I/O housing, and the power to the 800 I/O housing itself. Ensure all power is de-energized and locked out to any device in the control cabinet where the conversion is to be performed. Ensure work is performed by qualified personnel.
WARNING
This is the cable length in meters and tenths of meters (e.g. 015 = 1.5 meters). Recommended
cable length is 003 (00.3 meters).
Refer to conversion module Specifications Section: Maximum Operating Voltage
1492-CM800-LD001 Conversion Module
Conversion Module Compatible 800
Output Module
Compatible 1756
Output Module
Required 1492 Cable
1492-CM800-LD001 B802-008 1756-OA8 1492-CABLE
U
20-Pin Connector for 1492-CABLE
U
Mating Connector for B800 Terminal Block
(2)
IV. Conversion Module Wiring Diagram
The following diagram shows the connections from the existing B802-008 swing-arm, through the conversion module, 1492 cable and to the 1756-OA8 output module. The diagram can be used as an aid in possible system troubleshooting.
2
L1-0 OUT-0
3
OUT-1
5
OUT-2
7
OUT-3
9
OUT-4
4
OUT-5
6
OUT-6
8
OUT-7
10 12 14 16 18 11 13 15 17
Black
White
Red
Green
Orange
Blue
White/Black
Red/Black
Green/Black
Orange/Black
Blue/Black
Black/White
Red/White
Green/White
Blue/White
Black/Red
White/Red
Orange/Red
Blue/Red
1 1 2 2 3 7 4 8 5
6
7 4 8
9 10 10
11
12 14 13 20 11 15 12 16 17 17 18 18
19
20
14
Red/Green
Not Used
19
Output 1
Output 3
Output 2
Output 4
1
Not Used
20
L1-1
LOAD
L1
L2
L1-0 L1-0 L1-0 L1-0 L1-1 L1-1 L1-1 L1-1
Hot Grp 1
Hot Grp 2
Hot Grp 3 Hot Grp 4
Output 5
Output 7
Output 6
Output 8
3Neutral Grp 1 9Neutral Grp 2 13Neutral Grp 3 19Neutral Grp 4 5Not Used 6 15 16Not Used
Not Used
Not Used
10000021848 (Version 00)
Conversion Module Installation and Application Considerations
The B802-008 module output current limits versus 1756-OA8 limits are as follows:
B802-008 1756-OA8 w/ 1492-CABLE003U
a) Current/Point 2A 2A b) Current/Module 12A 5A @ 30˚C, 4A @ 60˚C c) Surge Current/Pt 50A for 1 cycle 20A for 43ms
1756-OA8
1492-CABLE003U
1492-CM800-LD001
Conversion: B802-008 to 1756-OA8 with 1492-CM800-LD001
B802-008 Swing Arm
The B802-008 has 4 groups (allowing 4 separate power supplies) and the 1756-OA8 has 2 groups. This module/cable combination ties Groups 1 & 2 from the B802-008 to Group 0 on the 1756-OA8 and it ties Groups 3 & 4 from the B802-008 to Group 1 on the 1756-OA8. Field wiring modification must be made to accommodate this if multiple supplies were used. If 4 supplies were used, 2 must be removed.
The B802-008 provided a single fuse per group. The 1756-OA8 is NOT fused. The 1492-CM800-LD001 provides a 5x20mm fuse per 1756-OA8 Group. Fuse rating for this configuration 4 Amps.
The 1492-CABLE003U current is limited to 2A per pin.
Refer to your B802-008 and 1756-OA8 Installation Manual wiring schematics and diagrams for more details. Ensure 1756 output module ratings are not exceeded.
[Reference Doc: 41170-750 (Version 03)]
There are several key application considerations and system specifications (bottom of drawing) when using these components (conversion module, cable and output module). Read and understand these considerations before installation. In addition, refer to the current draw requirements of the existing loads for this configuration to ensure they are within the current ratings of the 1756 output module.
WARNING
(3)
V. Fuse Installation and Replacement
The 1492-CM800-LD001 conversion module has two (2) mechanical fuse holders with fuses located on the circuit board inside the modules plastic case. The following explains how to replace the fuses.
1) Remove the screw from the bottom of the conversion module plastic case.
2) Push UP and IN on the locking tab at the other end of the conversion module case.
3) Remove the top cover (part which has the nameplate label) from the module case.
10000021848 (Version 00)
Locking Tab
IN
UP
(4)
V. Fuse Installation and Replacement (Continued)
4) To replace the fuse turn the circuit board over. The fuses and fuse information is visible on the circuit board.
NOTES:
1) For conversion module operation a fuse must be inserted into each of the 2 fuse holders.
2) Physical Fuse Size: 5 x 20 mm
3) Possible Fuse Suppliers: Shurter (Part Number:
0034.3123)
and Cooper Bussmann (Part Number:
GMC-4A)
.
4) Fuse Current Rating Based on Conversion System Components: 4 Amps
VI. Conversion Module Re-assembly After Fuse Insertion/Replacement
1) To re-assemble the fused module, place the circuit board into the label side half of the module case with the fused side of the circuit board UP.
10000021848 (Version 00)
Fuse Holders and Fuse Data
Case surface with module label
(5)
VI. Conversion Module Re-assembly After Fuse Insertion/Replacement (Continued)
2) Take the module case half with the locking tab and partially insert the tab into the mating slot of the other half.
3) At the other end of the module case, ensure the bottom guide/retainer clears the top locking extension. Push the 2 case halves up and in until you here the locking tab snap into place.
4) Replace the module case screw [(maximum torque 0.7 Nm (6.9 lb-in)].
10000021848 (Version 00)
Locking Tab: Partially Inserted
Extension
Guide / retainer
Specification Value
Dimensions 288.9 mm (height) x 139.7 mm (depth) x 44.5 mm (width)
11.37 in. (height) x 5.5 in. (depth) x 1.75 in. (width) Approximate Shipping Weight 300g (0.66 lbs) (includes carton) Storage Temperature -40 to +85°C (-40 to +185°F) Operating Temperature 0 to 55°C (32 to 131°F) Operating Humidity 5 to 95% at 55°C (non-condensing) Shock Non-operating Operating
50g 30g
Operating Vi
bration 2g @ 10-500Hz Maximum Operating Voltage 125Vac at 47 to 63Hz Max. Module Operating Current
Per Point: Per Module:
2 Amps (1492-CABLE connection pins are limited to 2A per pin) 12 Amps
Agency Certifications
UL Classified: Under UL File Number E113724
Fusing Two, 4 Amps, 5 x 20 mm
CSA
CE: compliant for all applicable directives Pollution Degree 2 Environmental Rating IP20
10000021848 (Version 00)
Printed in Germany
Article No. 4351840000
VII. 1492-CM800-LD001 Conversion Module Specifications
(Operating specifications are when installed in the Conversion System base / cover-plate assembly)
VIII. Appendix A - 800 Housing to 1756 Chassis Conversion System Selection Process
1) Determine the number of 800 I/O modules actually used in the 800 I/O Housing to be converted to 1756 I/O .
2) Review the data in Column 5 from the below table, and select a 1756 I/O Chassis which meets your conversion needs from Step 1. Ensure the information from the I/O Conversion module table is reviewed first since in some cases, two 1756 modules are needed to replace one 800 I/O module.
3) Once the 1756 Chassis is selected, refer to Column 7 and select the Conversion Assembly.
One chassis slot required for the ControlLogix processor or a remote I/O adapter type module. The footprint and mounting dimensions of the 1492 Conversion Assembly (base-plate and cover-plate) match those of the
Modicon I/O Housing.
Width dimension includes the 1756 Chassis power supply. Surplus Chassis width as compared to the 800 I/O Housing is divided equally when mounting it on the Conversion Assembly. Mounting holes for the 1756 I/O Chassis are pre-drilled and pre-tapped into the Conversion Assembly cover-plate.
Modicon is a Registered Trademark of Group Schneider.
AS-H810-xxx
AS-H819-103
AS-H819-209
AS-H819-100
AS-H827-103
AS-H827-209
AS-B827-100
Modicon 800 I/O
Housing Cat Number
1492-MUA4-MB3
1492-MUA7-A10-
MB4679
1492-MUA10-A13-
MB81011
Conversion Assembly
Catalog Number
Max. Number
of 800 Housing
Slots for I/O
3
4
6
7
8
10
11
10.25”
17.5”
17.5”
17.5”
27.1”
27.1”
27.1”
800 Housing
Width
Dimension
10.25”
A7 = 14.49”
A10 = 19.02”
A7 = 14.49”
A10 = 19.02”
A7 = 14.49”
A10 = 19.02” A10 = 19.02”
A13 = 23.15” A10 = 19.02”
A13 = 23.15” A10 = 19.02”
A13 = 23.15”
1756 Chassis
Width 
Dimension
Max. Number
of 1756 Chassis
Slots for I/O
3
A7 = 6, A10=9
A7 = 6, A10=9
A7 = 6, A10=9
A10 = 9, A13=12
A10 = 9, A13=12
A10 = 9, A13=12
1756 I/O Chassis
Catalog Number
1 72 3 654
1756-A4
1756-A7
or
1756-A10
1756-A10
or
1756-A13
Refer to the Wiring Diagram(s) for current limits for a specific configuration.
NOTICE