Installation Instructions
Differential Air-pressure Transmitter
Catalog Numbers
1414-IPZ10FODAA, 1414-IPZ10FNDAA, 1414-IPD10FNRAA,
1414-CPZ10FODAA, 1414-CPZ10FNDAA, 1414-CPD10PNRAA
Top ic Pa ge
Before Installation 1
Important User Information 2
About the Differential Air-pressure Transmitter 3
Differential Air-pressure Transmitter Installation 4
Power-up Instruction 7
Specifications 9
Dimensions 10
Before Installation
Read these installation instructions carefully before commissioning the pressure transmitter.
ATTENTION:
• Failure to follow these instructions may result in product damage. This device must be
installed by a qualified technician.
• Use electrostatic discharge precautions during installation and do not exceed the device
ratings.
WARNING: Do not use in an explosive or hazardous environment, with
combustible or flammable gasses, as safety or emergency stop devices or in any
other application where failure of the product could result in personal injury.
2 Differential Air-pressure Transmitter
Important User Information
Solid-state equipment has operational characteristics differing from those of electromechanical equipment.
Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1
available from your local Rockwell Automation sales office or online at
http://www.rockwellautomation.com/literature/
equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide
variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy
themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages
resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many
variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot
assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits,
equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell
Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
WARNING: Identifies information about practices or circumstances that can cause an
explosion in a hazardous environment, which may lead to personal injury or death, property
damage, or economic loss.
) describes some important differences between solid-state
ATTENTION: Identifies information about practices or circumstances that can lead to personal
injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid
a hazard and recognize the consequences.
SHOCK HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to
alert people that dangerous voltage may be present.
BURN HAZARD: Labels may be on or inside the equipment, for example, drive or motor, to
alert people that surfaces may reach dangerous temperatures.
IMPORTANT Identifies information that is critical for successful application and understanding of the
product.
Publication 1414-IN011B-EN-P - July 2010
Differential Air-pressure Transmitter 3
About the Differential Air-pressure Transmitter
The transmitter can be used to measure positive, negative, or differential pressure in the range of
1.0…20.0 in. wc (water column). The piezoresistive sensor is ideal for monitoring the pressure for
air or other clean inert gas and is limited only to those media that will not attack polyetherimide,
silicon, fluorosilicone, silicone, EPDM, and neoprene seals.
The module features field-selectable pressure ranges and output signal types for the most flexible
application. Typical HVAC applications include monitoring of filter differential pressure or
clean room pressure. The output signal is factory calibrated and temperature compensated for
highest start-up accuracy and trouble-free operation.
The low-pressure room differential transmitter is designed to measure the pressure difference
from one room to another. This is done by mounting the main transmitter unit that is housed in
the ABS enclosure in one room and mounting the AE enclosure in the other. The ABS enclosure
has two ports, one on the side and one on the back. The side port is used to measure the pressure
in the room that it is mounted in while the back port is connected via a supplied tube to the port
that is on the back of the AE enclosure.
There is a second fitting on the back of the ABS enclosure that can be used as a wire entrance. An
electrical box can be used to mount the two enclosures to the wall or a hole can be made in the
wall to accommodate the fittings. Attach the supplied tube to the fittings on the back of the AE
and ABS enclosures.
TIP
The following is the factory setup for the tubing inside the ABS enclosure.
• The LOW side of the sensor is connected to the AE to monitor the remote
room.
• The HIGH side of the sensor is connected to the port on the side of the ABS
enclosure.
The tubes on the sensor can be reversed if required
Publication 1414-IN011B-EN-P - July 2010
4 Differential Air-pressure Transmitter
Differential Air-pressure Transmitter Installation
The transmitter mounts on any surface using the two holes provided on the base of the unit.
Make sure there is enough space around the unit to connect the pressure tubing without kinking
and avoid locations where severe vibrations or excessive moisture are present. Mount the
enclosure with two user-supplied screws but do not over-tighten.
The unit may be mounted in any position but is typically installed on a vertical surface with the
pressure ports on the right and the cable entrance on the left. The enclosure has a standard ½ in.
conduit opening and may be installed with either conduit and a conduit coupler or a cable gland
type fitting.
Room Pressure Monitor - Mount the ABS box in the room where the pressure display is desired.
Mount the AE enclosure in the second room and connect the two using the supplied hose or
equivalent. Note that the unit is factory set with the LOW port in the ABS enclosure and the
HIGH port in the AE enclosure. To change this, reverse the hose connections on the board in
the ABS enclosure.
Differential Air-pressure Transmitter Wiring and Connection
The transmitter has standard screw-block connectors and easy wire access to facilitate wiring. We
recommend that shielded twisted-pair wiring at least 22 AWG be used for all connections and
that the device wires not be run in the same conduit with wiring used to supply inductive loads
such as motors.
ATTENTION: Disconnect the power supply before making any connections to
prevent electrical shock or equipment damage.
Make all connections in accordance with national and local electrical codes.
The device power (12…28V AC or 15…35V DC measured at the transmitter) is connected to
the terminal marked PWR. This terminal is used for the positive DC voltage or the hot side of
the AC voltage. The device is reverse voltage protected and as such will not operate if connected
backwards.
For voltage output signal types (three-wire) or for AC power supply operation (three-wire), the
common of the power supply is connected to the terminal marked COM. Note that this device
has a half-wave type power supply which means the power supply common is the same as the
output signal common. Therefore, several devices may be connected to one power supply and the
output signals all share the same signal common. Use caution when grounding the secondary of
an AC transformer or when wiring multiple devices to ensure that the circuit ground point is the
same on all devices and the controller. This terminal is not used for loop-powered 4…20 mA
output type (2-wire).
Publication 1414-IN011B-EN-P - July 2010