Robinair RG3000 User Manual

Refrigerant Recovery Machine
by Robinair
®
®
RG3000
Operating Manual
Manuel d’utilisation Manual de operaciones
Safety PrecautionS
WARNING : TO PREVENT PERSONAL INJURY AND / OR EQUIPMENT DAMAGE,
ALLOW ONLY QUALIFIED PERSONNEL TO OPERATE THIS UNIT. Before operating the unit,
read and follow the instructions and warnings in this manual. The operator must be familiar with air conditioning and refrigeration systems, refrigerants, and the dangers of pressurized components. If the operator cannot read this manual, operating instructions and safety precautions must be read and
discussed in the operator’s native language.
PRESSURIZED TANK CONTAINS LIQUID REFRIGERANT. Do not overll storage vessels, because overfilling may cause explosion and personal injury or death. Do not recover refrigerants into nonrellable containers; use only federally authorized rellable containers (DOT spec. 4BW or 4BA).
HOSES MAY CONTAIN LIQUID REFRIGERANT UNDER PRESSURE. Contact with refrigerant may
cause personal injury. Wear protective equipment, including safety goggles and protective gloves. Disconnect hoses using extreme caution.
AVOID BREATHING A/C REFRIGERANT AND LUBRICANT VAPOR OR MIST. Exposure may irritate eyes, nose, and throat. To remove refrigerant from the A/C systen, use only equipment certied for the type of refrigerant being removed. Use the unit in locations with mechanical ventilation that provides at least four air changes per hour. If accidental system discharge occurs, ventilate the work area before resuming service.
TO REDUCE THE RISK OF FIRE, USE THE SHORTEST POSSIBLE EXTENSION CORD WITH A MINIMUM SIZE OF 14 AWG. Using an undersized extension cord may result in electrical equipment
failure.
TO REDUCE THE RISK OF FIRE, do not use the unit in the vicinity of spilled or open containers of gasoline or other ammable substances.
CAUTION – DO NOT PRESSURE TEST OR LEAK TEST EQUIPMENT OR VEHICLE AIR CONDITIONING SYSTEMS WITH COMPRESSED AIR. Some mixtures of air and refrigerant have
been shown to be combustible at elevated pressures. These mixtures, if ignited, may cause injury or
property damage.
DO NOT MIX REFRIGERANT TYPES THROUGH A SYSTEM OR IN THE SAME CONTAINER.
Mixing of refrigerants causes severe damage to the unit and the system being serviced.
HIGH VOLTAGE ELECTRICITY INSIDE THE UNIT HAS A RISK OF ELECTRICAL SHOCK. Exposure may cause personal injury. Disconnect power before servicing the unit.
Additional health and safety information may be obtained from
refrigerant and lubricant manufacturers.
Explanation of SafEty Signal WordS
WARNING : Indicates a potentially hazardous situation which, if not avoided, could result in death or
serious injury.
CAUTION : Indicates a potentially hazardous situation which, if not avoided, may result in minor or
moderate injury.
CAUTION : Used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property damage.
table of contentS
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Explanation of Safety Signal Words . . . . . . . . . . . . . . . . . . . . . . . . .2
Understanding Refrigerant Recovery . . . . . . . . . . . . . . . . . . . . . . . . 4
Standard Operating Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Recovery Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Operating Instructions for Bulk Liquid Systems . . . . . . . . . . . . . . . . . . . 7
Push – Pull Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Liquid Recovery. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Vapor Recovery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Purge Non-Condensable Gas from a Storage Cylinder . . . . . . . . . . . . . . .8
Recovery Cylinder Information. . . . . . . . . . . . . . . . . . . . . . . . . . . .9
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Replacement Parts, Rebuild Kits, & Accessories . . . . . . . . . . . . . . . . . 11
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Installation of the Filter and Filter / Drier . . . . . . . . . . . . . . . . . . 12
Burned-out System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Spanish
French
Warranty Statement . . . . . . . . . . . . . . . . . . . . . . . .Inside Back Cover
underStanding refrigerant recovery
NOTE: Throughout this operating manual the term “unit” is used when referring to the RG3000 refrigerant recovery machine.
Refrigerant recovery is the process of taking refrigerant
out of a system and storing it in a cylinder. The following
information is critical to achieving the best refrigerant recovery results.
Refrigerant
Identify the refrigerant type and quantity in the system to be serviced.
The unit is approved for use with the following category III, IV, and V refrigerants (per ARI-740) :
R-12, R-22, R-134a, R-401a, R-401b,R-401c, R-402a, R-402b, R-404a, R-406a, R-407a, R-407b, R-407c, R-407d, R-408a, R-409a, R-410a, R-411a, R-411b, R-412a, R-500, R-502, R-507 R-509
Filters and Filter / Driers
CAUTION : Filters prevent contamination from entering the unit, which reduces the risk of damage to the unit and the system being serviced.
The unit is shipped with a lter screen installed behind the inlet tting. Promax strongly recommends that a clean lter screen be used for every service job. Failure to use a lter screen will invalidate your warranty.
The unit is also shipped with (1) lter / drier (Part No.
100343) for use at the inlet tting. However, if there is a need to recover multiple, different refrigerants using this unit, a separate lter / drier must be labeled and used for each individual type of refrigerant.
Valves
WARNING : To prevent personal injury, open service and cylinder valves SLOWLY to allow rapid shut-off of gas flow if necessary. Once it is determined there is no danger, the valves may be opened fully.
Isolate large amounts of refrigerant and close valves after use, so if a leak should develop anywhere in the
system, refrigerant will not escape to the atmosphere.
Hoses
Hoses must be equipped with low-loss ttings and have
pressure ratings appropriate for the refrigerant in the
system being serviced.
Shut-off Switch
This unit has an internal, high-pressure, shut-off switch.
If system pressure rises above 550 psi, the unit shuts
off. The shut-off switch automatically resets itself after
pressure drops below 400 psi.
WARNING : The internal pressure shut-off switch does NOT prevent cylinder overfill. If the system shuts off automatically and is connected to a cylinder, the cylinder may be dangerously overfilled. Take immediate measures to relieve the high pressure and / or cylinder overfill situation, or personal injury may result.
Push / Pull Procedure
When recovering large amounts of liquid (over 15 lbs.), use the Push / Pull method described in this manual.
Maximum Vacuum and Recovery Rates
To achieve the deepest nal vacuum, use an evacuated recovery cylinder. To maximize recovery rates :
Use the shortest possible length of 3/8 in. or larger
hose. (A hose no longer than 3 feet is recommended.)
Remove unnecessary hose core depressors, and
remove Schrader valves from port connections.
Deformed rubber seals and core depressors in hoses,
as well as faulty or unnecessary Schrader valves, can restrict ow.
Maintenance
CAUTION : Keep all connections to the refrigeration system dry and clean. Damage will occur if moisture is allowed to enter the system.
Storage Cylinders
WARNING : A storage cylinder is full when it reaches 80% volume. DO NOT OVERFILL. Due to liquid expansion, the cylinder could explode if filled to more than 80% volume, possibly causing personal injury and equipment damage. Use a scale, such as TIF9010A, to avoid overfilling the storage cylinder.
Standard oPerating inStructionS
Manifold
Gauge Set
System Being
Serviced
Vapor
Sight
Glass
Filter / Drier
Liquid
Scale
Inlet
Fitting
Outlet
Fitting
Liquid Port
Recovery
Cylinder
The following instructions are for a standard or
“common” recovery procedure.
Setup Procedure
1. Place the unit on a at, level surface.
2. Verify a clean lter screen is installed behind the inlet tting.
3. Connect a hose from the outlet tting of the unit to the liquid port on the recovery cylinder.
4. Connect a hose from the inlet tting of the unit
to the output port of a manifold gauge set.
Promax recommends using a sight glass and a lter / drier in this line.
5. Connect a hose from the liquid (low pressure) side of the manifold gauge set to the liquid side of the system being serviced.
6. Connect a hose from the vapor (high) side of the manifold gauge set to the vapor side of the system being serviced.
7. Verify the inlet and outlet valves on the unit are
closed.
8. Place the recovery cylinder on a scale (such as TIF9010A) to avoid overlling the cylinder.
WARNING : A storage cylinder is full when it reaches 80% volume. DO NOT OVERFILL. Due to liquid expansion, the cylinder could explode
if lled to more than 80% volume, possibly
causing personal injury and equipment damage.
Tech Tips
The unit will perform at its peak when voltage entering the machine (while operating) is between 115 —122 VAC.
Lower supply voltages may result in difculty
starting under high head pressure, reduced
performance, and / or motor overheating. Use an outlet that does not have other applicances
(such as lights, machines, etc.) plugged into it. Do not use an extension cord unless needed. If
an extension cord is used, it must be 14 AWG
minimum and as short as possible to reduce
voltage drops.
Standard oPerating inStructionS
Recovery Procedure
1. Connect the unit to an appropriate 115 V outlet.
2. Slowly open the liquid valve of the recovery
cylinder while watching hoses and connections
for leaks.
3. Open the liquid valve on the manifold gauge set.
Note: Opening the liquid valve removes liquid from the system rst, greatly reducing recovery time.
4. Open the outlet valve on the unit.
5. Toggle the power switch to the ON position.
6. Slowly open the inlet valve on the unit. Note: If the unit begins to “knock”, slowly throttle back (close)
the inlet valve until the noise stops.
7. Once the liquid has been removed from the system, open the vapor valve on the manifold gauge set to nish evacuating the system.
8. Run the unit until the desired vacuum is achieved.
9. Close the vapor and liquid valves on the manifold gauge set.
10. Turn the inlet valve on the unit to the CLOSED position.
11. Toggle the power switch OFF.
oPerating inStructionS for bulk liquid SyStemS
“Push – Pull” Procedure
The push – pull method removes bulk liquid from a system using the pressure differential created by the unit. This method works only with large systems where the liquid is readily accessible; it may not work on systems that contain less than 15 lbs. (6.8 kg) bulk liquid.
This method is used :
on systems with receiver cylinders.
• on systems containing more than 20 lbs.
(9.1 kg) of refrigerant.
when transferring bulk liquid refrigerant
from one cylinder to another.
System Being
Serviced
Inlet
Fitting
Filter/Drier
Outlet Fitting
Vapor
WARNING : Manually close the valves on both the storage cylinder and the unit to prevent overfilling the cylinder. Once the siphon is started, it can overfill the storage cylinder, even if the cylinder is equipped with a float level sensor. The siphon can continue even when the unit is turned off.
Liquid
Liquid Recovery
1. Place the unit on a at, level surface.
2. Connect a hose from the outlet tting of the unit to the vapor port on the system being serviced.
3. Connect a hose from the inlet tting of the unit to the vapor port of a recovery cylinder. Promax recommends using a lter / drier in this line.
4. Connect a hose from the liquid side of the recovery cylinder to the liquid port of the system being serviced. Promax recommends
using a sight glass in this line as a method of
determining when the liquid has been removed.
5. Place the recovery cylinder on a scale (such as TIF9010A) to avoid overlling the cylinder.
6. Verify inlet and outlet valves on unit are closed.
Vapor
Recovery
Cylinder
Sight
Glass
Scale
Liquid
7. Open the recovery cylinder valves.
8. Open the outlet valve on the unit.
9. Toggle the power switch ON.
10. SLOWLY open the inlet valve on the unit.
11. When the weight reading on the scale stops increasing, close the inlet valve on the unit rst; then close the liquid valve on the recovery
cylinder.
12. Toggle the power switch OFF.
13. Close the valves on the recovery cylinder, and close the outlet valve on the unit.
14. Proceed to Vapor Recovery.
Operating instructiOns fOr Bulk liquid systems
Vapor Recovery
1. Place the unit on a at, level surface.
2. Connect a hose from the inlet side of the unit to
the liquid port of the system being serviced.
Tech Tip
3. Connect a hose from the outlet side of the unit
to the liquid port on a recovery cylinder.
CAUTION: The recovery cylinder should be
on a scale to avoid overlling the cylinder.
4. Open the liquid valve on the recovery cylinder.
5. Open the outlet valve on the unit.
6. Toggle the power switch ON.
7. Slowly open the inlet valve on the unit.
8. Run the unit until the desired vacuum is achieved.
9. Close the inlet and outlet valves on the unit.
10. Toggle the power switch OFF.
11. Close the ports on the recovery cylinder.
For a faster recovery procedure, recover from both the liquid and vapor ports of the system being serviced by using a tee tting or manifold gauge
set in the hose setup.
purge nOn-cOndensaBle gas frOm a stOrage cylinder
1. Allow the storage cylinder to sit undisturbed for 24 hours to allow air to rise to the top.
2. Connect a manifold gauge set to the cylinder. Read the amount of pressure in the cylinder as indicated by the output pressure gauge.
3. Determine the ambient temperature in the room.
4. Refer to a refrigerant pressure / temperature chart and nd the ambient temperature. Read
across the chart to the corresponding pressure for the type of refrigerant in the cylinder. Determine how that relates to the reading on the gauge.
5. If the pressure reading in the cylinder is higher than the pressure shown on the chart,
VERY SLOWLY crack open the vapor port valve. (This is done slowly to cause as little turbulence inside the cylinder as possible.)
Watch the pressure on the gauge decrease. To
prevent venting, add 4–5 psi (0.26—0.34 bar) to the pressure shown on the chart.When the
gauge corresponds to that pressure, close the
vapor port valve.
6. Allow the cylinder to sit for 10 minutes and then check pressure again.
7. Repeat the process, if necessary.
recovery cylinder information
Type of Cylinder
Use only authorized, rellable, refrigerant storage cylinders. Federal regulations require refrigerant to be transported only in containers meeting DOT specs. 4BW or 4BA.
NEVER use a standard disposable 30 lb.
(13.6 kg) cylinder (the type of container in which new refrigerant is sold) to recover refrigerant.
Working Pressure
Recovery cylinders are designed for different working pressures. PROMAX strongly recommends the use of 400 psi (27.6 bar) cylinders.
WARNING: To prevent personal injury, do
not exceed the rated working pressure of the cylinder. At minimum, the RG3000 requires the use of a 350 psi (24.1 bar) recovery cylinder.
NOTE: The use of a 400 psi (27.6 bar) cylinder is mandatory when recovering R-410A refrigerant. Refer to the Parts and Accessories section of this manual for more information.
If you expect temperatures in excess of 135º F (57° C), consult the refrigerant supplier.
Capacity
Safety codes state that closed cylinders should
not be lled with liquid over 80% of volume. (The remaining 20% is called head pressure room.)
Do not exceed 80% of cylinder capacity. PROMAX recommends the use of the TIF9010A Refrigerant
Scale for monitoring cylinder capacity.
Refrigerants
Cylinders and lter / driers should each be
designated for only one type of refrigerant.
If you must use a cylinder previously used for
a different refrigerant, prepare the cylinder by
completely emptying it, perform an evacuation,
purge it using dry nitrogen, and then perform
another evacuation.
Storage
Store refrigerant cylinders in a cool, dry place.
Leakage
Some cylinders have valves that were not correctly
seated when manufactured. Keeping caps on the
valves will guard against refrigerant leakage.
WARNING : To prevent personal injury, never transport an overfilled cylinder.
Refrigerant expands when it gets warm and may cause an overfilled cylinder to explode.
Storage Cylinder Temperature 60°F 70°F 100°F 130°F 150°F
15.6°C 21.1°C 37.8°C 54.4°C 65.6°C
STARTING WITH CYLINDER
80% BY VOLUME
Space Occupied by Liquid 80% 81% 83% 90% 94%
STARTING WITH CYLINDER
90% BY VOLUME
Space Occupied by Liquid 90% 92% 96% 100%
troubleShooting
WARNING: TO PREVENT PERSONAL INJURY AND / OR EQUIPMENT DAMAGE,
ALLOW ONLY QUALIFIED PERSONNEL TO OPERATE AND REPAIR THIS UNIT. Before operating or repairing the unit, read and follow instructions and warnings in this manual. The technician must be familiar with air conditioning and refrigeration systems, refrigerants, and the dangers of pressurized components. If the technician cannot read this manual, operating instructions
and safety precautions must be read and discussed in the technician’s native language.
Symptom Possible Cause Possible Solution
Unit will not turn on 1. Power cord not plugged in.
2. Bad power outlet.
3. Unit is in high-pressure shut-off.
4. Motor is in thermal overload.
5. Blown or bad fuse.
Compressor tries to start, but just buzzes
Unit pumps into high-pressure shut-off
Slow recovery 1. Trapped liquid in system.
1. Low voltage at power source.
2. Extension cord too long, or too
small.
1. Output valve on unit is closed.
2. Recovery cylinder valve closed.
3. Head pressure too high.
2. Restriction in refrigerant ow path.
1. Check power cord at wall and unit.
2. Try a different outlet.
3. Reduce head pressure to below 400 psi (27.6 bar).
4. Allow motor / unit to cool down.
5. Check / replace fuse.
1. Locate / use better outlet.
2. Reduce length of extension cord. Increase size (gauge) of extension cord (14 AWG minimum).
1. Check output valve.
2. Check recovery cylinder valve.
3. Check output hoses for restrictions or kinks. Reduce head pressure.
1. Momentarily cycle system compressor to move trapped refrigerant.
2. Check inlet hose for restrictions or kinks. Remove Schrader valves and core depressers from hoses (if possible). Use larger hoses.
Blown fuse 1. Electrical short in wiring.
2. Mechanical binding.
1. Check for and replace damaged wires and / or electrical connectors.
2. Repair or replace compressor.
10
rePlacement PartS
12
13
20
1
15
16
4
3
17
5
2
7
8
}
18
10
6
9
14
21
Item Part No. No. Qty. Description
1 565505 1 Case Kit (both halves) 2 SK-3001 1 Interface Kit (motor-compressor
interface, coupler, hardware)
3 SK-3003 1 Fan
4 SK-3004 1 Motor Kit
(motor, capacitor, hardware)
5 565504 1 Compressor 6 SK-3006 1 Condenser 7 565502 1 Gauge Lens (1 ea.) 8 565617 1 Motor Start Capacitor 9 SK-3007 1 Low-side Gauge Kit
(low-side gauge, lens)
10 SK-3008 1 High-side Gauge Kit
(high-side gauge, lens)
11 SK-3005 1 High-side Manifold Kit 12 565501 1 Front Bezel 13 SK-6001 1 Inlet Fitting / Filter Screen Kit
(inlet tting, lter screen, o-ring)
11
19
Item Part No. No. Qty. Description
14 565500 1 Fuse 15 550503 1 Grommet (1 ea.) 16 SK-3009 1 Motor Clamp Kit (4 pieces) 17 550502 1 Foot (1 ea.) 18 565616 1 Inlet Tube 19 551628 1 Power Cord 20 EL1310 1 Power Switch 21 SK-3010 1 Low-side Manifold Kit 100343 1 Filter / Drier (not shown) 100345 6 in. Blue Hose (not shown)
Rebuild Kits
SK-3011 Compressor Rebuild Kit (piston
seals, valves, springs, o-rings)
SK-6007 Valve Rebuild / Replacement Kit
(inlet / outlet valves, springs, o-rings)
11
maintenance
CAUTION : To prevent personal injury, disconnect the unit from the power supply before performing maintenance.
Installation of the Filter and Filter / Drier
1. Before performing a refrigerant recovery, inspect and clean the filter screen in the inlet fitting on the unit. Replace the filter screen (p/n SK-6001) if necessary. A filter screen greatly reduces the risk of damage to the unit by preventing foreign material from entering the unit and the system being serviced. Failure to use a filter screen will invalidate the warranty.
Also use an in-line filter / drier (p/n 100343) in the inlet line.
Filter
Screen
Inlet
Fitting
Filter /Drier
p/n 100343
Burned-out System
1. Use two high-acid capacity lter / driers in series when recovering from a “burned-out” system. Promax recommends Alco type EK-162-F or Sporlan type C-162-F lters.
When you have nished recovering from the system, ush the unit with a small amount of clean
refrigerant and refrigerant oil to purge any foreign substances left in the unit.
Storage
1. Empty refrigerant from the unit into a storage cylinder. Liquid refrigerant left in the unit’s condenser may expand, causing damage to components.
2. Completely evacuate the unit of any residual refrigerant and purge it with dry nitrogen before putting it
in storage for a long period of time.
12
full One-year limited Warranty garantie limitée cOmplète dun an
Unit Serial No.
This product is warranted to be free from defects in workmanship, materials, and
components for a period of one year from date of purchase.
The following restrictions apply:
1. This warranty is non-transferable. All warranty claims must be made within the
warranty period. Proof of purchase must be supplied with the product when returned.
2. The warranty applies to product in normal use only, as described in this operating
manual. The product must be maintained and serviced as specied.
3. If the product fails, it will be repaired or replaced at the option of the manufacturer.
Warranty service claims are subject to factory inspection for product defects. The manufacturer is the sole determiner of warranty coverage. If during the warranty evaluation it is determined that appropriate maintenance was not performed, or
that the product has been used in any way other than the purpose for which it was
designed, the manufacturer reserves the right to void the warranty.
4. Normal wear items (seals, lters, etc.) are specically excluded from this warranty, unless found by the manufacturer to be defective.
This warranty does not apply if the product or product part is damaged by accident, misuse, tampering with, or modifying in anyway. The manufacturer is not responsible for any
additional costs associated with a product failure including, but not limited to, loss of work time, loss of refrigerant, or unauthorized shipping and/or labor charges.
Use of this product with any unauthorized refrigerants or chemicals will void the warranty.
Warranty Service:
1. Outside of the United States of America, contact your local Promax distributor.
2. Inside the United States of America, call 1-800-327-5060 for a Return Material Authorization (RMA) number. Instructions on where to send the product will be provided.
Nº de série de l’appareil
Ce produit est garanti contre les défauts matériels et de fabrication pour une durée d’un an à compter de la date d’achat.
Toutefois, les restrictions suivantes s’appliquent :
1. Cette garantie est non transférable. Toute réclamation au titre de la garantie doit être
soumise durant la période de garantie. La preuve d’achat doit être fournie avec le produit lors d’un retour.
2. La garantie s’applique uniquement au produit utilisé dans des conditions de fonctionnement normales conformément au manuel d’utilisation. Il doit être entretenu et réparé conformément aux spécications.
3. Si le produit fait l’objet d’une défaillance, il sera réparé ou remplacé à la discrétion du fabricant. Les réclamations au titre de la garantie sont sujettes à l’inspection en usine du produit défectueux. La couverture de la garantie est à la seule discrétion du fabricant. Si l’évaluation de la garantie démontre qu’aucun entretien approprié n’a été effectué ou que le produit a été utilisé dans un but autre que celui pour lequel il a été conçu, le fabricant se réserve le droit d’annuler la garantie.
4. Les composants d’usure normale (joints, ltres, etc.) sont exclus de cette garantie, à moins que le fabricant ne constate qu’ils sont défectueux.
Cette garantie n’est pas applicable si le produit ou les éléments du produit sont endommagés à la suite d’un accident, d’un usage abusif, d’une altération ou d’une modication quelconque. Le fabricant ne peut être tenu responsable de tout coût supplémentaire lié à la défaillance du produit incluant, sans toutefois s’y limiter, les interruptions de fonctionnement, la perte de uide frigorigène, la contamination des uides frigorigènes et l’expédition et/ou les frais de main-d’œuvre soumis par des ateliers non autorisés.
L’utilisation de ce produit avec des uides frigorigènes ou produits chimiques non autorisés
annulera la garantie.
Assistance à la garantie :
1. À l’extérieur des États-Unis, communiquez avec le concessionnaire Promax de votre
région.
2. Aux États-Unis, composez le 1-800-327-5060 pour obtenir un numéro d’autorisation de retour d’article. Des directives sur l’endroit où retourner le produit vous seront
fournies.
garantía limitada cOmpleta pOr un añO
Número de serie de la unidad
Se garantiza que este producto no posee defectos de mano de obra, materiales y
componentes por el período de un año a partir de la fecha de compra.
Aplican las siguientes restricciones:
1. Esta garantía no es transferible. Todo reclamo de garantía se debe hacer dentro del
período de garantía. Se debe proveer un comprobante de compra con el producto al devolverlo.
2. La garantía aplica al producto en uso normal únicamente, como lo indica este manual de funcionamiento. El producto debe contar con un servicio y mantenimiento según lo especicado.
3. Si falla el producto, será reparado o reemplazado a discreción del fabricante.Los reclamos de servicio de garantía están sujetos a inspección autorizada de defectos del producto. El fabricante es el único determinante de la cobertura de la garantía. Si durante la evaluación de la garantía se determina que no se ha llevado a cabo el mantenimiento apropiado, o que el producto ha sido utilizado para diferentes propósitos de los que fue diseñado, el fabricante se reserva el derecho de invalidar
esta garantía.
4. Los elementos normales de desgaste (sellos, ltros, etc.) están especícamente excluidos de la garantía, a menos que el fabricante los encuentre defectuosos.
Esta garantía no se aplica si el producto o parte del producto es dañado accidentalmente,
por uso inadecuado o ha sido alterado o modicado de cualquier manera. El fabricante no es responsable de los costos adicionales relacionados con fallas en el producto, que incluyen pero no se limitan a: tiempo improductivo, pérdida de refrigerante o envío no autorizado y/o cargos por mano de obra.
La utilización de este producto con cualquier refrigerante o químico no autorizado invalidará
esta garantía.
Servicio de garantía:
1. Fuera de los Estados Unidos de América, contacte a su distribuidor de Promax local.
2. Dentro de los Estados Unidos de América, llame al 1-800-327-5060 para obtener un número de Autorización de retorno de material (RMA). Se proveerán instrucciones sobre a dónde enviar el producto.
13
by Robinair
OWATONNA, MN 55060
PHONE : 800.327.5060
FAX: 866.287.7222
WWW.ROBINAIR.COM
®
Form No. 565466 Rev. B, May 9, 2014 © Bosch Automotive Service Solutions LLC
Loading...