Models 15234/15226/15296 Two-Stage V acuum Pump
For use with refrigerants R-12, R-22, R-500, R-502, or R-134a
1.2 cfm
(at 60 Hz)
© 2000, SPX Corporation
2
PARTS IDENTIFICATION
BLACK EXHAUST
PLUG (NOTE VENT HOLE)
RED SHIPPING PLUG
(REMOVE AND
DISCARD)
GAS
BALLAST
VALVE
INLET
CAP
SIGHT
GLASS
OIL LEVEL
INLET
“TEE” FITTING
1
/4" MFL INLET
(R-12, 22, 500, 502)
1
/2" ACME INLET
(R-134a)
WARNING!
Use separate manifolds and hoses for R-134a systems. Cross­contamination with other refrigerant types will cause severe damage to the A/C systems and to service tools and equipment. Do not mix refrigerant types through a system or in the same container!
For use on A/C systems using CFCs, HCFCs, and HFCs in conjunction with mineral oil, ester oil, alkylbenzene oil, and PAG oil as lubricants. Not for use with ammonia or lithium bromide systems. Not for use with flammable refrigerants.
Vacuum Pump Models 15234/15226/15296
OUT OF WARRANTY
Any Robinair high vacuum pump which is beyond the one-year warranty period and fails to operate correctly should be returned to the distributor with a full written explanation of the problem, or you may return it yourself to one of the authorized Robinair Service Centers for repair. Go to Robinair.com or call 1-800-822-5561 for instructions on returning a pump.
Prior to returning an out-of-warranty pump, review all maintenance procedures to avoid an unnecessary return. Note that contaminated oil or an incorrect oil level will adversely affect pump performance. These conditions should be checked before requesting service. Replacement parts are available if you desire to repair your own pump. However, this should be considered only in out-of- warranty situations.
MODEL 15234 15226 15296 Number of Stages 222
Free air Displacement 1.2 cfm* 1.2 cfm* 1.0 cfm Factory Micron Rating 50 50 50 Oil Capacity 5 oz. 5 oz. 5 oz.
Weight 10 lbs. 10 lbs. 10 lbs.
Width 4
Length 9
Height 8
Intake Fittings
Motor Size
Voltage 110-115V 220V 250V
Operating 185 Temperature 85
Because of ongoing product improvements, we reserve the right to change design, materials, and specifications without notice.
Vacuum Pump Models 15234/15226/15296
3
INTRODUCTION
Your vacuum pump has been factory tested and meets Robinair’s stringent quality standards. This high performance pump will provide you with years of trouble-free service if you follow these instructions for operating and maintain­ing the pump.
The pump’s offset rotary vane design provides high efficiency operation. The motor is properly sized to ensure 32oF (0oC) starting at 90 percent of the rated voltage. And the inlet “tee” fitting lets you use one pump for R-12, R-22, R-500, R-502, and R-134a systems.
Be careful when removing the pump and contents from the shipping carton. If there is any apparent shipping damage to the pump, the shipping company should be notified immediately and the container saved for inspection.
OPERATING INSTRUCTIONS
WARNING! Wear safety goggles when working with refrigerants. Contact with refrigerant can cause eye injury.
1. Remove and discard the red shipping plug at the top of the finned reservoir.
2. Fill the pump reservoir to the “OIL LEVEL” line on the sight glass on the front of the pump. Use the oil packaged with the vacuum pump or fresh Robinair Premium High Vacuum Pump Oil, available at your supplier.
3. Install the black plastic operating exhaust plug. Note that the operating plug is notched to allow exhaust flow.
CAUTION! Do not attempt to operate the pump with the exhaust port plugged. To do so could result in permanent damage to the pump or could cause the plug to be blown from the pump reservoir.
4. Note the electric motor voltage rating, and connect to the proper power source.
CAUTION! Avoid the use of extension cords. An exten­sion cord may overheat and cause fire. If you must use an extension cord, use the shortest possible cord with a minimum size of 14 AWG.
You are now ready to remove the inlet cap for the appropriate inlet (1/4" for R-12, R-22, R-500, and R-502; 1/2" Acme for R-134a) to connect the pump to the air conditioning system. Follow the system manufacturer’s directions for evacuation.