Robertshaw RS2210 Series Owner's Manual

FEATURES
Structure of thermostat and explanation for the keypads
We are pleased you have selected one of our wall thermostats. Our products are manufactured to high quality standards and are designed for years of service.
Read This Before Installing Thermostat
OPERATION
This thermostat will NOT control 110/220 Volt systems.
IMPORTANT
Read the entire installation section of this Owner’s Manual thoroughly before you begin to install or operate your Thermostat.
REMOVE THE MYLAR LABEL FROM THE LCD DISPLAY WINDOW.
INSTALLATION
All programming is normally performed at your thermostat’s location.
COMPRESSOR PROTECTION
The thermostat provides a 4-minute delay after shutting off the heating or cooling system before it can be restarted. This feature will prevent damage to your compressor caused by rapid cycling. Note that this delay also applies to the heating system control. It does not provide a delay when there are power outages. You can select the function ON or OFF during the configuration.
TEMPERATURE RANGE
This thermostat can be programmed between 45ºF and 95ºF (7ºC and 35ºC). However, it will display room tempera­tures from 30ºF to 99ºF (0ºC and 37ºC). HI will be displayed if the temperature is higher than 99ºF (37ºC), and LO will be displayed if the temperature is lower than 30ºF (0ºC).This thermostat will automatically shut down in Heat mode if the temperature rises above 95ºF (35ºC), and automatically shut down in cool mode if the temperature drops below 45ºF (7ºC).
NOTE: If the thermostat measures a temperature over 99ºF(37ºC), HI will be displayed on the LCD If the tempera­ture is below 32ºF(0ºC), LO will be displayed on the LCD.
POWER FAILURE
Whenever the main power is interrupted or fails, the battery power retains the current time for approximately one minute. This thermostat has permanent memory, although you will have to reset your clock when there are power outages of longer duration than one minute.
POWER SUPPLY
The thermostat is powered by 24 VAC, with batteries providing backup.
BATTERY WARNING
Fresh alkaline batteries should provide about one year of service. However, when the batteries become weak, BATT will alternate on the display with the current time. When this message occurs, install 2 new AA batteries. You have approximately 1 minute to change the batteries and keep thermostat’s clock. Once the batteries have become too weak to ensure proper operation, your system will be turned off, and the display will be cleared except for BATT flashing on the LCD display.
CAUTION: Once the BATT display occurs, the thermostat
is shut down, and your system will no longer operate. In this condition, there is no temperature control. NOTE: The backlight will not function when the thermostat is in low battery condition.
NOTE: If you plan to be away from the premises over 30 days, we recommend that you replace the old batteries with new alkaline batteries prior to leaving.
INSTALLATION
What You Need (Note: A fossil fuel kit is required.):
This thermostat includes two #8 slotted screws and two wall anchors for mounting. To install your thermostat, you should have the following tools and materials.
• Slotted screwdriver(s) • Small Philips screwdriver • Hammer • Electric drill, 3/16” bit • Two 1.5V (AA) size alkaline batteries (included)
CAUTION:
To prevent electrical shock and/or equipment damage, disconnect electric power to system at main fuse or cir­cuit breaker box until installation is complete.
Before removing wires from the old thermostat, label each wire with the terminal designation it was removed from.
1. Shut off electricity at the main fuse box until installation is complete. Ensure that electrical power is disconnected.
2. Remove Old Thermostat: A standard heat/cool thermostat consists of three basic parts:
a. The cover, which may be either a snap-on or hinge
type.
b. The base, which is removed by loosening all screws.
c. The switching subbase, which is removed by
unscrewing the mounting screws that hold it on the wall or adaptor plate.
3. Remove the front cover of the old thermostat. With wires still attached, remove wall plate from the wall. If the old thermostat has a wall mounting plate, remove the ther­mostat and the wall mounting plate as an assembly.
4. Identify each wire attached to the old thermostat.
5. Disconnect the wires from the old thermostat one at a time. DO NOT LET WIRES FALL BACK INTO THE WALL.
6. Install new thermostat using the following procedures.
WARNING
Do not use on circuits exceeding specified voltage. Higher voltage will damage the control and could cause a shock or fire hazard. Do not short out terminals on gas valve or primary control to test. Incorrect wiring will damage thermostat and could cause personal injury and/or property damage.
Selector Switches
Figure 1. Electric/Gas Switch (Fan Option)
This thermostat is configured from the factory to operate a heat/ cool, fossil fuel (gas, oil, etc.), forced air system. It is configured correctly for any system that DOES NOT require the thermostat to energize the fan on a call for heat. If your system is an electric heat or heat-pump system that requires the thermostat to turn on the fan on a call for heat, locate the ELEC/GAS switch on the back of the thermostat (see Figure 1) and switch it to the ELEC position. This will allow the thermostat to energize the fan immediately on a call for heat. If you are unsure if the heating/cooling system requires the thermostat to control the fan, contact a qualified heating and air conditioning service person. When the thermostat is configured for heat pump, the thermostat will always power the circulator fan on a call for heat in the HEAT mode. The ELEC/GAS switch must be set to match the type of auxiliary heat your system uses for proper operation in the EMERGENCY mode.
All wiring diagrams are for typical systems only. Refer to equipment manufacturer’s instructions for specific system wiring information.
Attach Thermostat Base to Wall
1. Remove the packing material from the thermostat. Gently pull the cover straight off the base. Forcing or prying will cause damage to the unit.
2. Connect wires beneath terminal screws on base using appropriate wiring schematic (see Figure 2 through 6).
3. Place base over hole in wall and mark mounting hole locations on wall using base as a template.
4. Move base out of the way. Drill mounting holes.
5. Fasten base loosely to wall, as shown in Figure 1, using two mounting screws. Place a level against bottom of base, adjust until level, and then tighten screws. (Leveling is for appearance only and will not affect thermostat operation.) If you are using existing mounting holes, or if holes drilled are too large and do not allow you to tighten base snugly, use plastic screw anchors to secure base.
6. Push excess wire into wall and plug hole with a fire resistant material (such as fiberglass insulation) to prevent drafts from affecting thermostat operation.
Figure 2. Thermostat Base
Digital Thermostat
Owners Manual Model: RS2210 Series
Description
Heat Pump (No Aux. or Emergency Heat) Yes
Heat Pump (with Aux. or Emergency Heat) Yes
Standard Heat & Cooling Systems Yes
Two Stage Heat & One Stage Cool Yes
Standard Heat Only Systems Yes
Millivolt Heat Only Systems – Floor or Wall Furnaces Yes
Standard Central Air Conditioning Yes
Gas or Oil Heat Yes
Electric Furnace Yes
Hydronic (Hot Water) Zone Heat-2 Wires Yes
Hydronic (Hot Water) Zone Heat–3 Wires No
352-00021-002 Rev A
Figure 3. Typical wiring diagram for single transformer heat pump systems
Figure 4. Typical wiring diagram for two transformer heat pump systems with NO safety circuits
Figure 5. Typical wiring diagram for two transformer heat pump systems with safety circuits in BOTH systems
Figure 6. Typical wiring diagram for single transformer multi-stage systems
Heat Pump Terminal Outputs
Refer to equipment manufacturer’s instructions for specific system wiring information. You can configure the thermo­stat for use with the following heat pump system types: sin­gle stage compressor system; gas or electric backup. This thermostat is designed to operate a single transformer system. If you have a two transformer system, cut and tape off one transformer. If transformer safety circuits are in only one of the systems, remove the transformer of the system with NO safety circuits. If required, replace remaining transformer with a 75VA Class II transformer. After disconnecting one transformer, the two commons must be jumpered together.
Use the terminal output information below to help you wire the thermostat properly for your heat pump system. After wiring, see CONFIGURATION section for proper thermo­stat configuration.
CHECK THERMOSTAT OPERATION
Note:
To prevent static discharge problems, touch side of thermostat to release static build-up before touching any keys.
If at any time during testing your system does not operate properly, contact a qualified service person.
Fan Operation
If your system does not have a G terminal connection, skip to Heating System.
1. Turn on power to system.
2. Move FAN switch to ON position. The blower should begin to operate.
3. Move FAN switch to AUTO position. The blower should stop immediately.
Heating System
1. Move system switch to heat mode. If the auxiliary heating system has a standing pilot, be sure to light it.
2. Press to adjust thermostat setting to 1ºF/1ºC above room temperature. The heating system should begin to operate. The display should show STG1. However, if the setpoint temperature display is flashing, the compressor lockout feature is operating (see CONFIGURATION MENU, item 5).
3. Adjust temperature setting to 3ºF/3ºC above room temperature. If your system configuration is set at MS2, HP2 or HP1, the auxiliary heat system should begin to operate and the display should show STG1+2.
4. Press to adjust the thermostat below room temperature. The heating system should stop operating.
Emergency System
EMER bypasses the heat pump to use the heat source wired to terminal E on the thermostat. EMER is typically used when compressor operation is not desired, or you prefer back-up heat only.
1. Press system switch to select heat. Then press EMER key. EMER will show on the display.
2. Press to adjust thermostat setting above room temperature. The auxiliary heating system will begin to operate. The display will show STG1 EMER to indicate that the auxiliary system is operating.
3. Adjust temperature setting to 2ºF/2°C above room temperature. The auxiliary heat system should begin to operate and the display should show STG1+2.
4. Press to adjust the thermostat below room temperature. The auxiliary heating system should stop operating.
Cooling System
1. Move system switch to select the COOL.
2. Press to adjust thermostat setting below room temperature. The blower should come on immediately on high speed, followed by cold air circulation. The display should show STG1.
3. Press to adjust the temperature setting above room temperature. The cooling system should stop operating.
CONFIGURATION MENU
The configuration menu allows you to set certain thermostat operating characteristics to your system or personal requirements. Set SYSTEM switch to OFF, then simultaneously press up and down keys to enter configura­tion menu. The display will show the first item in the configuration menu. The configuration menu table summarizes the configuration options. An explanation of each option follows. Press F key to change to the next menu item. To exit the menu and return to the normal operation, press RUN. If no keys are pressed within fifteen seconds, the thermostat will revert to normal operation.
1) Single Stage, Multi-stage or Heat Pump System Configuration This control can be configured for heat pump or two stage heat/one stage cool multi-stage operation. The dis­play shows MS 2 (default for multi-stage mode). The multi-stage configuration can be toggled to SS1, or HP1 by pressing the up or down key. In Multi-stage
configuration, EMER mode is not used. In this model, the HP2 is not used.
2) Fast or slow cycle selection (one stage)
3) Select backlight function OFF or ON
4) Fast or slow cycle selection (two stage)
5) Select °F or °C readout
6) Selects 12 hour or 24 hour time format
7) Select Compressor Lockout COMP OFF or ON Selecting COMP ON will cause the thermostat to wait 4 minutes before turning on the compressor if the heat­ing and cooling system loses power. It will also wait a minimum of 4 minutes between cooling and heating cycles. This protects the compressor from short cycling. Some newer compressors already have a time delay built in and do not require this feature. Your compressor manufacturer can tell you if the lockout feature is already present in their system. When the thermostat compressor time delay occurs it will flash the setpoint for about four minutes.
8) This model must select 1
9) This model must select 1 for factory default
Setting Day and Time
• The LCD will show this information when batteries are first installed. The temperature will update after a few seconds.
• During time and day setting mode, the temperature displays will go blank.
Refer to the steps below.
STEP 1:
• Press to enter time and day setting mode. The current hour and the AM/PM indicator will be flashing.
• Press up or down to change the hour to the current hour.
Note the AM/PM indicator, as the display will change at 12AM and 12PM.
STEP 2:
• Press again to change from hour setting to minute setting. The current minute will be flashing.
• Press up or down to change the minute to the current minute.
STEP 3:
• Press again to change from minute setting to day setting. The current days will be flashing.
• Press up or down to change the day to the current day.
STEP 4:
• Press again to change back to the normal display.
Reviewing the Current Temperature Setting
Current time and temperature.
• Press less than 1 second.
• Set temperature is shown above current room temperature.
OPERATION
System Selector Switch
The System Selector Switch on the front of the thermostat determines the operating mode of the thermostat. You may select COOL , OFF, or HEAT to take full advantage of this thermostat’s feature.
NOTE: Anytime you install or remove the thermostat from the wallplate, slide the System Selector to OFF to prevent the possibility of a rapid system ON-OFF.
Fan Switch
The fan switch should normally be set to the AUTO position. The fan will turn on along with normal operation of your system. In a normal gas or oil furnace, the fan will be turned on by your furnace after its warm-up delay. For electric heat, air conditioning, and heat pump operation, the fan will turn on with the sys­tem. To run the fan continuously, slide the fan switch to the ON position.
INSTALLER/CONFIGURATION MENU
Step Press Displayed Press Comments
Button (Factory down key
Default) to select
1 F MS 2 SS1, HP2, Selects Single
HP1 stage, Multi-stage
or Heat Pump
(Single stage or
2-stage) System
Configuration
2 F (RECO)off on No use
3 F (DIFF)2 1,3 DIFF (one stage)
4 F (BLIT)on off BackLight
5 F (SP2)2 1,3 DIFF (Two Stage)
6 F (TEMP)F C Selects temperature
display °F or °C
7 F HOUR(12) 24 Selects time format
display 12 hours
or 24 hours
8 F COMP(OFF) ON Selects Compressor
Lockout OFF or ON
9 F COOL(1) 2 This model must
select 1
10 F FACT(0) 1,2 This model must
select 1 for
factory defaults
THERMOSTAT TERMINALS (HEAT PUMP)
SYSTEM Heat Pump 1
L Malfunction
C* 24 Volt(Common)
R 24 Volt Emergency (hot)
E/W1 Emergency Mode 1st stage
W2 HP 1 and Emergency 2nd stage
Y1 Heat and Cool mode 1st stage
(compressor)
G Blower/Fan Energized on call for Heat and Cool
Set GAS/ELEC switch for Emergency mode
O Energized in Cool Mode
B Energized in Heat Emergency mode
352-00021-002 Rev A 8/07
Loading...
+ 1 hidden pages