Rkc THV-10 User Manual

t
A
t
A
A
A
Single-phase Thyristor Unit
150 A/200 A
All Rights Reserved, Co pyri ght  2014, RKC INSTRUMENT INC.
Thank you for purchasing this RKC product. In order to achieve maximum performance and ensure proper operation of your new instrument, carefully read all the instructions in this manual. Please place the manual in a convenient location for easy reference. This manual describes the mounting, wiring and specifications only.
For detailed handling procedures and key operations, refer t o separ ate THV-10 Instruction Manual (IMR02W03-E). (On CD-ROM) The manual can be downloaded from the officia l RKC website:
THV-10
Installation Manual
IMR02W02-E3
Product Check
THV-10 Insta llat io n Ma nu al ( IM R02 W02- E3 ) ..................................................................................... 1
CD-ROM ............................................................................................................................................. 1
Accessories (Order separately)
Setter for open loop control [potentiometer, knob and scale plate]
(Code: THVP-S0 1) .............................................................................................. Ord ered quan ti ty
Input/Output connector [plug] (Code: THV4P-C01) ...................................................................... 1
For other accessories not described above, refer to the THV-10 Instruction Manual (IMR02W03-E).
Safety Precautions
An external protection device must be installed if failure of this instrument
could result in damage to the instrument, equipment or injury to personnel.
All wiring must be completed before power is turned on t o prevent electric
shock, fire or damage to instrument and equipment.
This instrument must be used in accordance with the specifications to
prevent fire or damage to instrument and equipment.
This instrument is not intended for us e in locations su bject to fla mmable or
explosive gases.
Do not touch high-voltage connections such as power supply terminals,
etc. to avoid electric shock.
When the withstand voltage test or eac h test is perf ormed, please c ontact
RKC sales office or the agent. If you make a mistake in the test method, the instrument failure may result.
RKC is not responsible if this instrument is repaired, modified or
disassembled by other than factory-appr oved personnel. Malfunction can occur and warranty is void under these conditions.
High temperature caution: Do not touch the heat radiation fin wh ile the po wer is turne d on or just after the power is turned off as it may be at high temperatures. If touched, burning may result.
This product is intended for use with industrial machines, test and measuring equipment. It is not
designed for use with medica l equipm ent and nuc lear ener gy.
This is an Environment A instrument. In a domestic environment, this instrument may cause radio
interference, in which case the user may be required to take additional measures.
Be sure to provide an appropriate surge control circuit respectively for the following:
If input/output o r signal lines wit hin the bu ilding are long er than 30 meters. If input/output o r signal lines leav e the bui lding, r egardle ss the le ngth.
This product is man ufactured on the assumption that it is mounted within a control panel. All
high-voltage connections suc h as power su pply term inals must be enclosed in t he control p anel to avoid electric shock by operating personnel.
All precautions described in this manual sho uld be taken to a void damage to th e instrument or
equipment.
All wiring must be in accordance with local codes and regulations. Always use this product at the rated power supply voltage, load current and power frequency. All wiring must be completed before power is turned on to prevent electric shock, instrument
failure, or incorrect action.
To prevent instru ment dam age or f ailure, p rotect t he power line and the inp ut/outp ut lines with a
protection device such as fuse, etc.
If this product is used for ph ase control, higher harmo nic noise may be generat ed. Therefor e in
this case, take such measures as separating the power line from the high-voltage line for load drive.
Prevent metal fragments or lead wire scr aps from falling inside ins trument case to avoid el ectric
shock, fire or malfuncti on.
Tighten each termin al screw to t he specifie d torque fo und in the ma nual to a void electric s hock,
fire or malfunction.
For proper operation of this instrument, provide adequate ventilation for heat dispensation. D o not connect wires to unused terminals as this will interf ere with proper operation of the
instrument.
Turn off the power supply before cleaning the instrument. Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or
discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
To avoid damage to ins trum ent display, do not rub wit h an abrasi ve materi al or pus h front panel
with a hard object.
WARNING
!
CAUTION
This manual assumes that the reader has a fundamental knowledge of the principles of electricity, process
control, computer technology and communications.
The figures, diagrams and numeric values used in this manual are only for purpose of illustration. RKC is not responsible for any damage or injury that is caused as a result of using this instrument,
instrument failure or indirect damage.
RKC is not responsible for any damage and/or injury resulting from the use of instruments made by
imitating this instrument.
Periodic maintenance is required for safe and proper operation of this instrument. Some components have
a limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all information contained herein. RKC makes no
warranty expressed or implie d, with respect to the accurac y of the information. T he information in this manual is subject to change without prior notice.
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored, processed
or retrieved through any mechanical, electronic, optical or other means without prior written approval from RKC.
1. OUTLINE
NOTICE
This instrument is a single-pha se thyristor unit for power supply voltage 10 0 to 240 V AC. It is possible to adjust power suppl ied to heaters, etc. by setting the sig nal from the controller, setter (variable resistor) or front keys.
Personal computer
Gradient setter
Manual setter
Controller
Communication
converter
COM-K
Loader communication
External gradient setting
External manual mode
uto mode
Load (Heater, etc.)
Front keys Internal manual mode,
Internal gradient setting,
larm setting, etc.
uto/Manual
mode, etc.
Thyristor break-down, Heater break, etc.
Rating: 100 to 240 V AC
Protective earth (PE) terminal
Contact input
Switch, etc.
Alarm output
Alarmer, etc
For instrument
power supply
2. MOUNTING
In order to prevent electric shock or instrument failure, always mount
or remove this instrument after power supplied to the entire system is turned off.
As the temperature of this instrument becomes high, mount the
instrument on a non-inflammable material (metal plate, etc.).
As this instrument generates a large amount of heat, it is cooled by
circulating air by convection. Therefore, if mounted in any direction other than specified, accident or failure may result.
To carry the instrument, wait for the radiation fin to cool down. Grip
the instrument firmly with your fingers on the an ti-slip parts on both sides of the instrument.
2.1 Mounting Environment
(1) This instrument is intended to be used under the followi ng envir onmen tal condi tions.
EN60947-4-3, UL60947-4-1, C22.2 No.60947-4-1 POLLUTION DEGREE 2
(2) Use this instrument within the following environment conditions:
Allowable ambient temperature: 15 to +55 °C
(The rated current drops when the ambient temperature exceeds 40 °C.)
Rated curren
100
80 70 60
40 20
Allowable ambient humidity: 5 to 95 %RH
(3) Do not use this instrument in the following environment:
Sudden chang e in ambi ent t emperat ure Condensation or icing Corrosive or in flammabl e gases. Such a place where there are inflammable materials near this instrument. Strong vibrati on or imp act Water, oil, chemicals, vapor or steam splashes. Excessive dust , salt or ir on parti cles.
(%)
0
10
15
(Absolute humidity: MAX. W. C 29 g/m
10 20 30 40 50 55 0
Temperature characteristic
WARNING
!
The temperature characteristic of 150 A type is the same as that for 200 A type.
mbien
temperature (C)
3
dry air at 101.3 kPa)
Excessive induction noise, static electricity, magnetic fields or noise. Direct air flow from an ai r condit ioner. Exposure to dire ct sun light. Direct radiant heat
Setter (Potentiometer, Knob and Scale plate)
2.2 Mounting Cautions
Take the following points into consideration when mounting this instrument.
The instrument must be mount ed in a pr oper direc tion. W hen installin g the inst rument, o bserve
mounting directions.
Top
Vertical direction
Bottom
Provide adequate heat radiation space so that heat does not build up. At least 19.6 mm is necessary on the left and right and at least 100 mm on the top and bottom.
100 mm or more 100 mm or more
19.6 mm or more
19.6 mm or more
Also consider working sp ace.
Mount the instru ment ti lted with in 10 de grees fr om verti cal (back and fort h and left and right ).
The temperature inside the control panel increases due to heat generation of this instrument itself.
Therefore, take into account full ventilation by mounting forced ventilation fans on the panel.
Table of calorific values (100 to 240 V AC)
Rating current Calorific values
150 A Approx. 200 W 200 A Approx. 250 W
10 10
19.6 mm or more
THV-10
19.6 mm or more
THV-10
Tilted back and forth
Left and right
THV-10
THV-10
19.6 mm or more
100 mm or more 100 mm or more
19.6 mm or more
100 mm or more 100 mm or more
1010
2.4 Mounting Procedures
1. Prepare the holes as specified in 2.3 Dimensions.
2. Place the instrument in mounting position.
3. Insert the mounting screws into the holes, then tighten them with a screwdriver.
3. WIRING
3.1 Wiring of Main Circuit
2.3 Dimensions
Dimensions Mounting dimensions (Unit: mm)
240
130.4
189
93 0.2
226 0.2
150
4-M5
18.7
16.1
Knob
Mounting screw
Customer must provide the set of screws. Screw type: Pan-head screws Recommended tighten tor que: 3.6 Nm [36 kgfcm] Size: M5, Length: 10 mm
(Resistance 5 k, variation characteristic: B)
10
For dimensional details of a fuse holder, and an output voltmeter, refer to the THV-10 Instruction Manual (IMR 02W03-E ).
24
0
2
13.5
10 10
Potentiometer
Set the potentiometer full count erclockwise and combine with a scale plate. When setting the knob on the scale plate, align the arrow on the knob with 0 on the scale plate.
!
10
M9  0.75
6

2.8
Mounting positions (to p)
Mounting positions (bo ttom)
WARNING
405060
30
20
10
0
Scale plate
70
80
90
100
48
Unit: mm
48
To prevent electric shock or instrument failure, do not turn on the power until all wiring is completed. Make sure that the wiring is correct before applying power to the instrument.
CAUTION
Match the ph ase between t he supply voltage for the instrumen t and the suppl y voltage
for the load. Without proper matchi ng, the ins trume nt may not work prop erly.
Caution for conducting control of primary side of a transformer
When a protection function for control of primary side of a transformer is provided:
To conduct control of primary side of a transf or mer , ma ke su re prot ec tio n fu nct io n for cont rol of primary side of a con trol is set. Appropriately adjust the soft -start time for in case of secondary side breakdown depending on the operating condition.
When a protection function for control of primary side of a transformer is not provided:
If the action of the device i s influenced by exc essive current (i nrush current, current due to flux saturation of transformer), use a transformer 1.25 T (magnetic flux density) or less. Make sure soft-start time is appropriately set.
For setting procedure of each function, refer to THV-10 Instruction Manual
(IMR02W03-E).
If the secondary side of the transformer goes open due to a break in the heater, connect resistor
in parallel on the primary side of the transformer to all ow current flow larger than th e minimum load current (0.5 A or more) . (Adjust the resistance value considering the exciting current of the transformer.)
In order to comply with the European EMC- and LV directive the no ise filter (shown in the
following figure) should be applied.
THV-10
Noise filter
Power supply
100 to 240 V AC
The noise filter specified: SOSHIN ELECTRIC CO., LTD.
150 A: HF3150C-SZC 200 A: NF3200C-VZ
IN
OUT
2/T1 1/L1
Load
34
Fast-blow fuse
There are neither fuses nor power switches in the power circuit of this instrument.
y
t
)
)
)
e

Therefore install the fuses and switches near the instrument, if necessary.
To avoid noise induction, keep input signal wire of controller away from instrument power line,
load lines and power lines of other electric equipment. If wiring near high-voltage power is unavoidable, use shielded wires.
Use wires satisfying the rated current capacity. Tighten the hexagon headed bolts on the main circuit terminals using a torque wrench. Always
tighten each of them by contacting the diagonal surfaces of the wrench with those of each hexagon head.
Firmly tighten each terminal hexagon headed bolt with the tightening torque specified below.
Otherwise, electric shock, fire or heat generation may result.
Choose solderless terminals from the following table.
Input terminals (1, 2) and Power supply terminals (3, 4)
150 A/200 A Maker J.S.T Mfg. Co., Ltd. Parts No. V1.25MS3 Applicable wire (twisted wire) 0.5 to 1.25 mm2 Recommended tightening torque 0.4 N・m (4 kgf・cm)
Main circuit terminals (2/T1, 1/L1)
150 A 200 A Maker J.S.T Mfg. Co., Ltd. Parts No. R60-10 (Circular terminal) R100-10 (Circular terminal) Applicable wire
(twisted wire) Recommended
tightening torque
Make sure that the any wiring such as solderless terminal is not in contact with the adjoining
terminals.
42.42 to 60.0 mm
2
96.3 to 100.0 mm2
18.0 Nm (180 kgf⋅cm)
Wiring diagram of main circuit
Match the phase between the supply voltage for the instrument and the supply voltage for the load. Without proper matching, the instrument may
!
not work properly.
Output voltmeter (THVP-V0)
Can use it only in Phase control.
Power supply terminals (3, 4
Main circuit terminal (1/L1 Main circuit terminal (2/T1
3 4
Power supply 100 to 240 V AC (50/60 Hz)
Instrument power supply line (To terminal No. 3)
Load
Fast-blow fus
Terminal screws size
150 A/200 A Main circuit terminals ( 2/T1, 1/L1) M10 × 25 Power supply terminals (3, 4) M3 × 7 (With 5.8 × 5.8 squar e washer )
Instrument power supply line (To terminal No.4)
3.2 Wiring of Input Signal
Input signal is factory preset to your specification. If the input signal type needs to be changed on th e user's side, refer to THV-10 Instruction Manual (IMR02W03-E).
Wiring procedure for input signal
1. Make sure that the Input signal select switch is set to the signal specified at the time of ordering. There is an Input signal select switch under an Input/Output connecter.
Input signal select switch
Convex part
Current
input
This figure illustrates the setting position of the switch for current input.
Voltage input Voltage pulse inpu
2. Connect output signals from a temperature controller, etc. to input terminals 1 (+) and 2 () of this instrument.
+
Input impedance of THV-10 input terminals
Current input: Approx. 50 Voltage input or Voltage pulse input: Approx. 30 k
Terminal screws size
150 A/200 A
Input terminals (1, 2) M3 × 7 (With 5.8 × 5.8 square w asher)
4 to 20 mA DC, 1 to 5 V DC, 0 to 10 V DC or 0/12 V DC
1 2
THV-10 Input terminals (1, 2)
+
Temperature controller 4 to 20 mA DC output 1 to 5 V DC output 0 to 10 V DC output 0/12 V DC output
3.3 Input/Output Connector Pin Number and Details
Input/Output connector (plug) and setting unit are optional and sold separately.
Pin number and details
Pin number Details
1 +2.5 V (Gradient setting input) 2 Gradient setting input (0 to 2.5 V input by gradient setter) 3 0 V (Gradient setting input, Manual mode input) 4 Manual mode input (0 to 2.5 V input by manual setter) 5 +2.5 V (Manual mode input) 6 Contact input: DI (+) 7 0 V (Contact input): DI () 8 Unused (Do not connect any device to this terminal.) 9 Open collector output (alarm output): DO (+)
10 Open collector output (alarm output): DO ()
DI: Digital input DO: Digital output
Wire size used for Input/Out put co nnector
Use the stranded leadwires.
Stranded leadwires: AWG28-20 (cross-section: 0.14 to 0.5 mm Stripping length: 8 mm
Wiring of setting unit
When both of gradient and manual setters are connected, connect the 0 V wires externally. Just connect a single wire to terminal 3.
Wiring of external gradient setter
Connect external gradient setter to pins 1, 2 and 3.
Gradient setter
Wiring of external manual setter
Connect external manual setter to pins 3, 4 and 5.
Manual setter
Wiring of contact input
Connect to pins 6 and 7.
Contact input
Functional assignment is required for contact input. At the time of shipment, it is preset to “0: No function.”
For the setting, refer to THV-10 Instruction Manual (IMR02W03-E).
1 2 3 109 8 7 6 5 4
3 2
1
1 2
3
1 2 3
3 4 5
2
)
Pin number
6 7
DI (+)
Pin number
Input/Output connector (socket)
Stripping length
8 mm
Input/Output connector (plug)
Terminal number
of potentiometer
Pin number
Input/Output connector (plug)
Terminal number
of potentiometer
Pin number
Input/Output connector (plug)
DI ()
Wiring of alarm output
Connect to pins 9 and 10. A diode should be used and connected as show in the diagram, when using a relay.
When the power is turned on, the Heater break alarm output may be turned on for up to
0.5 ms. When an interlock circuit or an y other relat ed circuit i s used, take a necessar y measure externally for delaying the activation of the circuit more than 0.5 ms.
Rela
Diode
DO (+)DO ()
910
Pin number
Input/Output connector (plug)
3.4 Protective Earth (PE) Terminal
Protective earth no other devices to the location where you earth this
device.
Avoid sharing earth lines with electric motors, motorized equipment,
and other equipment that uses large amounts of electrify.
In the earth system, be careful to earth each point and not to create a
earth loop.
Protective earth (PE) terminal
Connect so that the earth resistance is no greater than 100 . Use wire of at least 2.0 mm
2
for earth lines.
4. MODEL CODE
Check whether the delivered product is as specified by referring to the following model code list. If the product is not identical to the specifications, please contact RKC sales office or the agent.
THV- PZ
(1) Power supply for load
10: 100 to 240 V AC
(2) Control method
PZ: Phase control/Zero-cross control (configurable)
(3) Rated current
150: 150 A AC * 200: 200 A AC * *
(4) Input signal
5: Voltage input 0 to 10 V DC 8: Current input 4 to 20 mA DC 6: Voltage input 1 to 5 V DC V: Voltage pulse input 0/12 V DC
(5) Heater break alarm, Current limit function, Constant current control function and Protection
N: No function H: Heater break alarm, Current limit function, Constant current control function and Protection
B: Non-linear resistance heater break alarm, Current limit function, Constant current control
(6) Alarm output
N: No alarm A: Alarm output 1 point
(7) Accessories
1: Setter for open loop control (potentiometer, knob and scale plate) [1 set] and
Input/Output connector (plug)
2: Setter for open loop control (potentiometer, knob and scale plate) [2 sets] and Input/Output connector (plug) 4: Output voltmeter (150 V span) [For Phase control] 5: Output voltmeter (300 V span) [For Phase control] 7: Fuse unit (UL approved instrument) for 150 A and 200 A (fast-blow fuse and holder [1 circuit type]) 9: Input/Output connector (plug)
Combination example of accessories
-1-7: Setter for open loop control [1 set] and Input/Output connector (plug) and Fuse unit (UL
10
(1)
function for control of primary side of a transformer
function for control of primary side of a transformer function and Protection function for control of primary side of a transformer
To control the primary side of the transformer, it is recommended to purchase a THV-10 with a protection function for control of primary side of a transformer.
approved instrument)
For part number of accessories, refer to the THV-10 Instruction Manual (IMR02W03-E).
(2) (3) (4) (5)
* The code for accessory will be more than one if the product has more than one accessory.
(6)
(……)*
(7)
With Heat sink temperature detection function
5. SPECIFICATIONS
Number of phase: Single-phase Maximum rated current: 150 A AC, 200 A AC
Minimum load current: 1 A (When output is 98 %) Supply voltage for load: 85 to 264 V AC [Including power supply voltage variation]
Power frequency: 50/60 Hz (Automatic discriminating) Allowable power frequency variations:
Input signal: Current input 4 to 20 m A DC (Input impedance: Approx. 50 )
Output voltage range: 0 to 98 % of supply voltage for load Applicable load: Phase control: Resistor load (Corresponding utilization category: AC-51)
Overload current profile and duty cycle: Control method: Phase control, Zero-cross control (continuous) or
For the ambient temperature characteristic, refer to temperature characteristic graph.
(Rating: 100 to 240 V AC)
50 Hz 1 Hz, 60 Hz 1 Hz (Performance guar antee) Voltage input 1 to 5 V DC, 0 to 10 V DC (Input impedance: Approx. 30 k)
Voltage pulse input 0/12 V DC (Input impedance: Approx. 30 k)
Control of primary side of a transformer The magnetic flux density must be 1.25 T [12,500 Gauss] or less when the protection function for control of primary side of a transformer is not provided. Zero-cross control (continuous, input synchronous type): Resistor load (Corresponding utilization category: AC-51)
1.1 x I
60s: 10012
e
Zero-cross control (input synchronous type)
Output setting range: Auto mode (control input): 0.0 to 100.0 %
Output mode for phase control:
Power off leakage current: Contact input: Contact input can be assigned the function.
Current transformer (CT) input (optional):
Alarm o ut pu t (op ti on al ): Number of output points: 1 point
Allowable ambient temperature: Allowable ambient humidity:
Supply voltage for instrument:
Power consumption: 12.5 VA MAX. (100 V AC) rush current 21 A or less Withstand voltage: 50/60 Hz 1 minute
Time: 1 minu te
① Radiator fins (PE termi nal) ② Main circuit terminals 2500 V ③ Power terminals for instrument 2000 V 2500 V ④ Input terminals 2500 V 2500 V 2300 V ⑤ Alarm terminals 2500 V 2500 V 2300 V 2000 V
Insulation resistance:
Radiator fins (PE terminal) Main circuit terminals
Power terminals for instrumentInput terminalsAlarm terminals
Rated conditional short-circuit current: Short-circuit protective device (fuse): Cooling method: Forced air cooling (built-in cooling fan) Mounting method: Panel mountintg
Dimensions: Refer to Dimensions Weight: Approx. 3.7 kg Standard: Safety standards: UL: UL60947-4-1 (file No. E177758)
Internal manual set value: 0.0 to 100.0 % (Set by theTHV-10 front keys) External manual set value: 0.0 to 100.0 % (Set by the setter *) Internal gradient set value: 0.00 to 2.00 (Set by theTHV-10 front keys) External gradient set value: 0.0 to 100.0 % (Set by the setter *) Output limiter high/low: 0.0 to 100.0 % (Set by theTHV-10 front keys) Base-up set value: 9.9 to +100.0 % (Set by theTHV-10 front keys)
Output limiter high at operation start:
High setting: 0.0 to 100.0 % (Set by the THV-10 front keys) Time setting: 0 to 600 seconds (Set by the THV-10 front keys)
Output limiter setting in case of a break on the secondary side of the transformer:
15.0 to 50.0 % of phase angle (Set by theTHV-10 front keys)
Ramp (Soft-start/Soft-down) function:
0.0 to 100.0 seconds (Set by the THV-10 front keys)
Soft-start function in case of a break on the secondary side of the transformer:
0.1 to 100.0 seconds (Set by the THV-10 front keys)
Current limite r function (optional): Valid at pha se control
Setting range: 150 A: 0 to 165 A 200 A: 0 to 220 A If a Current limit value is set to its maximum value, the Current limit function is deactivated. Setting the current limiter value to zero turns off the output.
Proportional phase angle, Proportional voltage, Proportional square voltage (electric power) or Constant current control (optional)
Approx. 27 mA AC (load voltage 200 V rms, 60 Hz, Ta = 25 C) Number of input points: 1 point
Input type: Dry contact input OFF state (open): 50 k or more ON state (close): 1 k or less Contact current: 5 mA or less Voltage at open: Approx. 4 V DC Capture judgment time: 50 Hz: 100 ms, 60 Hz: 83.33 ms
Input: Current transformer (Built-in) Input range: 0.0 to Rated current × 2 Sampling cycle: 50 Hz: 10 ms, 60 Hz: 8.33 ms
Output type: Open collector output Output type: Sink type Allowable load current: 100 mA Load voltage: 30 V DC or less Voltage drop at ON: 2 V or less (at maximum load current) Leakage current at OFF: 0.1 mA or less
15 to +55 C (Operation guarantee range) 5 to 95 %RH (Non-condensing)
Absolute humidity MAX. W. C 29 g/m 85 to 264 V AC [Including power supply voltage variation]
(Rating 100 to 240 V AC) 50/60 Hz Frequency variation 50 Hz: 48 to 52 Hz, 60 Hz: 58 to 62 Hz
22.0 VA MAX. (240 V AC) rush current 55 A or less
500 V DC
20 M or more
500 V DC
20 M or more
500 V DC
20 M or more
500 V DC
20 M or more
4200 A (150 A/200 A) Breaking capacity: 200 kA (fast-blow fuse for 150 A/200 A), UL certified The cooling fan service life: 50000 hours (Ambient temperature 23 2C)
cUL: C22.2 No. 60947-4-1 (file No. E177758) CE marking: In order to comply with the European EMC- and LV directive the noise filter (refer to 3.1) should be applied. LVD: EN60947-4-3 (Form 4) POLLUTION DEGREE 2 Rated insulation voltage: 690 V EMC: EN60947-4-3 (Form 4)
Modbus is a registered trademark of Schneider Electric.
Company names and product names used in this manual are the trademarks or registered trademarks of the respective companies.
RKC INSTRUMENT INC.
®
HEADQUARTERS: 16-6, KUGAHARA 5-CHOME, OHTA-KU TOKYO 146-8515 JAPAN
PHONE: 03-3751-9799 (+81 3 3751 9799) E-mail: info@rkcinst.co.jp FAX: 03-3751-8585 (+81 3 3751 8585) Website: http://www.rkcinst.com/ DEC. 2014
500 V DC
20 M or more
500 V DC
20 M or more
500 V DC
20 M or more
3
dry air at 101.3 kPa
500 V DC
20 M以上
500 V DC
20 M or more
The first edition: JUL. 2014 [IMQ00] The third edition: DEC. 2014 [IMQ00]
500 V DC
20 M or more
* Sold separately