Modbus is a registered trademark of Schneider Electric.
Company names and product names used in this manual are the trademarks or registered trademarks of
the respective companies.
All Rights Reserved, Copyright 2006, RKC INSTRUMENT INC.
Thank you for purchasing this RKC instrument. In order to achieve maximum performance and ensure
proper operation of your new instrument, carefully read all the instructions in this manual. Please place this
manual in a convenient location for easy reference.
SYMBOLS
WARNING
CAUTION
!
: This mark indicates where additional information may be located.
An external protection device must be installed if failure of this instrument
could result in damage to the instrument, equipment or injury to personnel.
: This mark indicates precautions that must be taken if there is danger of electric
shock, fire, etc., which could result in loss of life or injury.
: This mark indicates that if these precautions and operating procedures are not taken,
damage to the instrument may result.
: This mark indicates that all precautions should be taken for safe usage.
: This mark indicates important information on installation, handling and operating
procedures.
: This mark indicates supplemental information on installation, handling and
operating procedures.
WARNING
!
All wiring must be completed before power is turned on to prevent electric
shock, fire or damage to instrument and equipment.
This instrument must be used in accordance with the specifications to
prevent fire or damage to instrument and equipment.
This instrument is not intended for use in locations subject to flammable or
explosive gases.
Do not touch high-voltage connections such as power supply terminals, etc.
to avoid electric shock.
RKC is not responsible if this instrument is repaired, modified or
disassembled by other than factory-approved personnel. Malfunction can
occur and warranty is void under these conditions.
IMS01T04-E1
i-1
CAUTION
This is a Class A instrument. In a domestic environment, this instrument may cause radio
interference, in which case the user may be required to take adequate measures.
This instrument is protected from electric shock by reinforced insulation. Provide reinforced
insulation between the wire for the input signal and the wires for instrument power supply,
source of power and loads.
Be sure to provide an appropriate surge control circuit respectively for the following:
- If input/output or signal lines within the building are longer than 30 meters.
- If input/output or signal lines leave the building, regardless the length.
This instrument is designed for installation in an enclosed instrumentation panel. All
high-voltage connections such as power supply terminals must be enclosed in the
instrumentation panel to avoid electric shock by operating personnel.
All precautions described in this manual should be taken to avoid damage to the instrument or
equipment.
All wiring must be in accordance with local codes and regulations.
All wiring must be completed before power is turned on to prevent electric shock, instrument
failure, or incorrect action.
The power must be turned off before repairing work for input break and output failure including
replacement of sensor, contactor or SSR, and all wiring must be completed before power is
turned on again.
To prevent instrument damage or failure, protect the power line and the input/output lines from
high currents with a protection device such as fuse, circuit breaker, etc.
Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid
electric shock, fire or malfunction.
Tighten each terminal screw to the specified torque found in the manual to avoid electric shock,
fire or malfunction.
For proper operation of this instrument, provide adequate ventilation for heat dispensation.
Do not connect wires to unused terminals as this will interfere with proper operation of the
instrument.
Turn off the power supply before cleaning the instrument.
Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or
discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
To avoid damage to instrument display, do not rub with an abrasive material or push front
panel with a hard object.
Do not connect modular connectors to telephone line.
NOTICE
This manual assumes that the reader has a fundamental knowledge of the principles of electricity,
process control, computer technology and communications.
The figures, diagrams and numeric values used in this manual are only for purpose of illustration.
RKC is not responsible for any damage or injury that is caused as a result of using this instrument,
instrument failure or indirect damage.
RKC is not responsible for any damage and/or injury resulting from the use of instruments made by
imitating this instrument.
Periodic maintenance is required for safe and proper operation of this instrument. Some components
have a limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all information contained herein. RKC makes no
warranty expressed or implied, with respect to the accuracy of the information. The information in this
manual is subject to change without prior notice.
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored,
processed or retrieved through any mechanical, electronic, optical or other means without prior written
approval from RKC.
This chapter describes features, package contents and model code, etc. The module type controller has the
following features:
Module type controller SRZ interfaces with the host computer via Modbus or RKC communication
protocols. The SRZ sets all of the data items via communication (The communication interface used for
both protocols is RS-485.). Therefore before operation, it is necessary to set value of each data item via
communication.
Common to both Z-TIO and Z-DIO module
• A user can select RKC communication or Modbus.
• When each module is connected, the power and communication lines are connected internally within the
modules, and thus it is only necessary to wire one module to the power terminal and communication
terminal; there is no need to individually wire each module to the terminals. This reduces the amount of
wiring needed.
• Compact size
Terminal type: depth 85 mm, Connector type: depth 79 mm
Z-TIO module
• The Z-TIO module is a temperature control module equipped with either two or four control channels.
• The measurement input is a universal input that supports thermocouple input, resistance temperature sensor
input, voltage input, current input, and feedback resistance input.
• The input type can be specified separately for each channel, and different input types can be combined.
• Output types are relay contact output, voltage pulse output, voltage output, current output, open collector output, and
triac output. Output types are specified when the order is placed, and a different output type can be specified for
each channel.
• 4CH Z-TIO module can have 4 CT (current transformer) inputs.
• Up to 16 Z-TIO modules can be connected.
[The maximum number of SRZ modules (including other function modules) on the same communication line is 31.]
Z-DIO module
• The Z-DIO module is an event input/output module equipped with digital inputs and outputs (DI8 points
/ DO8 points).
• DI signal assignment enables switching of various mode states and memory areas of the Z-TIO module.
• DO signal assignment enables output of the event result of the Z-TIO module to the event output (DO),
and output of the DO manual output state of the Z-DIO module.
• Up to 16 Z-DIO modules can be connected.
[The maximum number of SRZ modules (including other function modules) on the same communication line is 31.]
For reference purposes, the Modbus protocol identifies the host computer as master, each module
of SRZ as slave.
1-2 IMS01T04-E1
1.2 Checking the Product
Before using this product, check each of the following:
Model code
Check that there are no scratch or breakage in external appearance (case, front panel, or terminal, etc.)
Check that all of the items delivered are complete. (See below)
If any of the products are missing, damaged, or if your manual is incomplete, please contact RKC
sales office or the agent.
1.2.1 Z-TIO module
Name Q’TY Remarks
Z-TIO module 1
Z-TIO Instruction Manual (IMS01T01-E)
Z-TIO Host Communication Quick Instruction Manual (IMS01T02-E)
Joint connector cover KSRZ-517A 2 Enclosed with instrument
Power terminal cover KSRZ-518A 1 Enclosed with instrument
Connector SRZP-01 (front screw type) 2 For the connector type module
Connector SRZP-02 (side screw type) 2 For the connector type module
CT cable W-BW-03-1000 1 For CT input connector (cable length: 1 m)
CT cable W-BW-03-2000 1 For CT input connector (cable length: 2 m)
CT cable W-BW-03-3000 1 For CT input connector (cable length: 3 m)
Current transformer CTL-6-P-N 1 0.0 to 30.0 A
Current transformer CTL-12-S56-10L-N 1 0.0 to 100.0 A
Terminal cover KSRZ-510A 1 For the terminal type module
Q’TY
Remarks
IMS01T04-E11-3
1. OUTLINE
1.3 Model Code
Check whether the delivered product is as specified by referring to the following model code list. If the
product is not identical to the specifications, please contact RKC sales office or the agent.
1.3.1 Z-TIO module
Suffix code
4-channel type:
Z-TIO-A −□−□□□□/□□−□□□□/Y
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10)
2-channel type:
(1) (2) (3) (4) (5) (6) (7) (8) (9) (10)
Wiring type Terminal type T
Connector type C
Relay contact output M
Voltage pulse output V
Output1 (OUT1) Voltage output, Current output (See Output Code Table)
Triac output T
Open collector output D
Relay contact output M
Voltage pulse output V
Output2 (OUT2) Voltage output, Current output (See Output Code Table)
Triac output T
Open collector output D
Relay contact output M
Output3 (OUT3) Voltage pulse output V
[Z-TIO-A type only] Voltage output, Current output (See Output Code Table)
Triac output T
Open collector output D
Relay contact output M
Output4 (OUT4) Voltage pulse output V
[Z-TIO-A type only] Voltage output, Current output (See Output Code Table)
Triac output T
Open collector output D
input
No quick start code (Configured as factory default) N
Quick start code Specify quick start code 1 1
Specify quick start code 1 and 2 2
Control Method
(all channel common)
[Quick start code 1]
(all channel common)
[Quick start code 1]
Instrument specification Version symbol /Y
1
Z-TIO-A type: CH2 and CH4 are unused Z-TIO-B type: CH2 is unused
2
Z-TIO-A type: CH2 and CH4 are feedback resistance input (for monitor) Z-TIO-B type: CH2 is feedback resistance input (for monitor)
Heat/cool PID action with AT (for Extruder [air cooling]) 1 A
Heat/cool PID action with AT (for Extruder [water cooling]) 1 W
Position proportioning PID action without FBR 2 Z
No specify quick start code No codeMeasured input and Range
See range code table.
Z-TIO-B −□−□□/□ N □−□□□□/Y
(1) (2) (3) (6) (7) (8) (9) (10)
Suffix code
Hardware coding only Quick start code1
1-4 IMS01T04-E1
Output Code Table
Voltage output (0 to 1 V DC) 3 Voltage output (1 to 5 V DC) 6
Voltage output (0 to 5 V DC) 4 Current output (0 to 20 mA DC) 7
Voltage output (0 to 10 V DC) 5 Current output (4 to 20 mA DC) 8
Range Code Table
[Thermocouple (TC) input, RTD input] [Voltage input, Current input]
Type Code Range (Input span) Code Range (Input span) Type Code Range (Input span)
K35 −200.0 to +400.0 °C KA1 0 to 800 °F 0 to 10 mV DC 101
K K40 −200.0 to +800.0 °C KA2 0 to 1600 °F 0 to 100 mV DC 201 Programmable range
K42 −200.0 to +1372.0 °C KC7 −328 to +2501 °F 0 to 1 V DC 301 −19999 to +19999
K09 0.0 to 400.0 °C KA4 0.0 to 800.0 °F 0 to 5 V DC 401 [The decimal point position is selectable]
K10 0.0 to 800.0 °C 0 to 10 V DC 501 (Factory set value: 0.0 to 100.0 %)
J27 −200.0 to +400.0 °C JA1 0 to 800 °F 1 to 5 V DC 601
J J32 −200.0 to +800.0 °C JA2 0 to 1600 °F 0 to 20 mA DC 701
J29 −200.0 to +1200.0 °C JB9 −328 to +2192 °F 4 to 20 mA DC 801
J08 0.0 to 400.0 °C JB6 0.0 to 800.0 °F
J09 0.0 to 800.0 °C
T T19 −200.0 to +400.0 °C TC5 −328 to +752 °F
TC6 0.0 to 752.0 °F
E E20 −200.0 to +1000.0 °C EB2 0.0 to 800.0 °F
EB1 −328 to +1832 °F
S S06 −50 to +1768 °C SA7 −58 to +3214 °F
R R07 −50 to +1768 °C RA7 −58 to +3214 °F
B B03 0 to 1800 °C BB1 32 to +3272 °F
N N07 −200 to +1372 °C NA8 −328 to +2502 °F
PLII A02 0 to 1390 °C AA2 0 to 2534 °F
W5Re/W26Re W03 0 to 2300 °C WB1 32 to 4208 °F
Pt100 D21 −200.0 to +200.0 °C DC6 −328.0 to +752.0 °F
D35 −200.0 to +850.0 °C DD2 328 to +1562 °F
JPt100 P31 −200.0 to +649.0 °C PC6 −328.0 to +752.0 °F
PD2 328 to +1200 °F
Output type Code Output type Code
1. OUTLINE
IMS01T04-E1
1-5
1. OUTLINE
Quick start code 2 (Initial setting code)
Quick start code 2 tells the factory to ship with each parameter preset to the values detailed as specified by
the customer. Quick start code is not necessarily specified when ordering, unless the preset is requested.
These parameters are software selectable items and can be re-programmed in the field via the manual.
□ □ □ □-□ □
(1) (2) (3) (4) (5) (6)
Specifications
Event function 1 (EV1) 1 None N
Event function 1 (See Event type code table)
Event function 2 (EV2) 1 None N
Event function 2 (See Event type code table)
Event function 3 (EV3) 1 None N
Event function 3 (See Event type code table)
Temperature rise completion 6
Event function 4 (EV4) 1 None N
Event function 4 (See Event type code table)
Control loop break alarm (LBA) 5
None N
CT type 2 CTL-6-P-N P
CTL-12-S56-10L-N S
Communication protocol RKC communication (ANSI X3.28) 1
Modbus 2
1
If it is desired to specify the deviation action between channels or the deviation using local SV, the settings must be configured by the customer. (Engineering setting data)
2
The CT assignment and heater break alarm (HBA) type must be configured by the customer. (Engineering setting data)
Event type code table
Code Type Code Type Code Type
A Deviation high H Process high V SV high
B Deviation low J Process low W SV low
C Deviation high/low K Process high with hold action 1 MV high [heat-side]
D Band L Process low with hold action 2 MV low [heat-side]
E Deviation high with hold action Q Deviation high with re-hold action 3 MV high [cool-side]
F Deviation low with hold action R Deviation low with re-hold action 4 MV low [cool-side]
G Deviation high/low with hold action T Deviation high/low with re-hold action
Quick start code 2 (Initial setting code)
(1) (2) (3) (4) (5) (6)
1-6
IMS01T04-E1
00
assignment
1.3.2 Z-DIO module
1. OUTLINE
Z-DIO-A
(1) (2) (3) (4) (5) (6) (7) (8)
−□−□ □ / □−□□□□
Suffix code
(1) (2) (3) (4) (5) (6) (7) (8)
Specifications
Wiring type Terminal type T
Connector type C
Digital input (DI) None N
8 points A
None N
Digital output (DO) Relay contact output (8 points) M Open collector output (8 points) D
Quick start code No quick start code (Configured as factory default) N
(DI/DO assignments) Specify quick start code 1 1
DI signal assignments No specify quick start code No code
(DI1 to DI8) None N
[Quick start code 1] See DI assignment code table.
DO signal assignments No specify quick start code No code
(DO1 to DO4) None N
[Quick start code 1] See DO assignment code table.
DO signal assignments No specify quick start code No code
(DO5 to DO8) None N
[Quick start code 1] See DO assignment code table.
Communication protocol RKC communication (ANSI X3.28) 1
Modbus 2
Hardware coding only Quick start code1
DI assignment code table
Code DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8
No
01 AUTO/MAN
02 REM/LOC
03 Inte rlock re lease EDS start signal 1
04 Soak stop
05 RUN/STOP
06 REM/LOC
07 AUTO /MAN EDS start signal 1
08 Operation mode
09 RUN/STOP
10 EDS start signal 1
11 REM/LOC Soak stop
12 RUN/STOP
13 Area set 2 Soak stop
14
15 Soak stop
16 EDS start signal 1
17 REM/LOC Soak stop
18 Interlock releaseAUTO/MAN RUN/STOP
19 Soak stop
20
21 Soak stop
22 Soak stop
23 AUTO/MAN REM/LOC
24 RUN/STOP
25
26 Memory area
transfer (1, 2)
27 Memory area transfer (1 to 8) 1 Area set
28 Memory area
transfer (1, 2)
29 EDS start signal 1 EDS start signal 2
RUN/STOP: RUN/STOP transfer ( Contact closed: RUN)
AUTO/MAN: Auto/Manual transfer (Contact closed: Manual mode)
REM/LOC: Remote/Local transfer (Contact closed: Remote mode)
Interlock release (Contact closed: Interlock release)
EDS start signal 1 (Contact closed: EDS start signal ON [for disturbance 1])
EDS start signal 2 (Contact closed: EDS start signal ON [for disturbance 2])
Soak stop (Contact closed: Soak stop)
1
Memory area transfer (×:Contact open −: Contact closed)
12 Burnout status (CH1) Burnout status (CH2) Burnout status (CH3) Burnout status (CH4)
13 Temperature rise completion 5 HBA comprehensive output 6 Burnout state comprehensive output 7 DO4 manual output
1
Logical OR of Event 1 (ch1 to ch4)
2
Logical OR of Event 2 (ch1 to ch4)
3
Logical OR of Event 3 (ch1 to ch4)
4
Logical OR of Event 4 (ch1 to ch4)
5
Temperature rise completion status (ON when temperature rise completion occurs for all channels for which event 3 is set to temperature rise completion.)
12 Burnout status (CH1) Burnout status (CH2) Burnout status (CH3) Burnout status (CH4)
13 Temperature rise completion 5 HBA comprehensive output 6 Burnout state comprehensive output 7 DO8 manual output
1
Logical OR of Event 1 (ch1 to ch4)
2
Logical OR of Event 2 (ch1 to ch4)
3
Logical OR of Event 3 (ch1 to ch4)
4
Logical OR of Event 4 (ch1 to ch4)
5
Temperature rise completion status (ON when temperature rise completion occurs for all channels for which event 3 is set to temperature rise completion.)
• If the ambient temperature rises above 50 °C, cool this instrument with a forced air fan, cooler, or the like.
However, do not allow cooled air to blow this instrument directly.
• In order to improve safety and the immunity to withstand noise, mount this instrument as far away as
possible from high voltage equipment, power lines, and rotating machinery.
− High voltage equipment: Do not mount within the same panel.
− Power lines: Separate at least 200 mm
− Rotating machinery: Separate as far as possible
• Mount this instrument in the horizontal direction for panel. If you did installation except a horizontal
direction, this causes malfunction.
3-2 IMS01T04-E1
3.2 Dimensions
[Terminal type] [Connector type]
3. MOUNTING
(Unit: mm)
85
100
5
100
5
76.92.930 6.7
Space required between each module vertically
When the module is mounted on the panel, allow a minimum of 50 mm at the top and bottom of the module
to attach the module to the mainframe.
50 mm or more
Depth for connector mount type module (Connector type)
Space for connectors and cables must be considered when installing.
IMS01T04-E13-3
76.9 mm Approx. 50 mm
Connector
(Plug)
3. MOUNTING
3.3 DIN Rail Mounting
Mounting procedures
1. Pull down the mounting bracket at the bottom of the module (A). Attach the hooks on the top of the
module to the DIN rail and push the lower section into place on the DIN rail (B).
2. Slide the mounting bracket up to secure the module to the DIN rail (C).
DIN rail
Mounting
bracket
(A) Pull down
(B)
Push
Mounting End Plates
To firmly fix the modules, use end plates on both sides of the mounted modules.
End plate
(sold separately)
* It is recommended to use a plastic cover on the connector on both sides of the mounted
modules for protection of connectors.
End plate
Joint connector cover
Joint connector cover
*
(Standard equipment)
Parts code Ordering code Q’ty
DEP-01 00434944 2
KSRZ-517A 00433384 2
End plate
(sold separately)
(C) Locked
3-4 IMS01T04-E1
Removing procedures
1. Pull down a mounting bracket with a blade screwdriver (A).
2. Lift the module from bottom, and take it off (B).
(A) Pull down
3. MOUNTING
(B) Lift and take off
IMS01T04-E1
3-5
3. MOUNTING
3.4 Panel Mounting
Mounting procedures
1. Refer to the mounting dimensions below when selecting the location.
(30)
(Unit: mm)
30±0.2
M3
Recommended screw:
M3 × 10
38
Recommended
tightening torque:
100
70±0.2
0.3 N・m (3 kgf・cm)
Base
Mounting dimensions
2. Remove the base from the module (B) while the lock is pressed (A). (Fig.1)
3. Join bases. Then, lock them by pushing in the mounting brackets.
See the 3.5 Joining Each Module (P.3-7).
4. Fix the base to its mounting position using M3 screws. Customer must provide the screws.
5. Mount the module on the base. (Fig.2)
Lock
(Top of the module mainframe)
(B)
(A)
(Bottom of the module mainframe)
Fig.1: Removing the base
Fig 2: Mounting the module mainframe
(Base)
3-6 IMS01T04-E1
Loading...
+ 316 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.