Ethernet is a registered trademark of Xerox Corp.
Modbus is a registered trademark of Schneider Electric.
Windows and Microsoft Internet Explorer are registered trademark of Microsoft Corporation in the
U.S.A. and other countries.
Company names and product names used in this manual are the trademarks or registered trademarks of
the respective companies.
All Rights Reserved, Copyright 2004, RKC INSTRUMENT INC.
t
Thank you for purchasing this RKC instrument. In order to achieve maximum performance and ensure
proper operation of your new instrument, carefully read all the instructions in this manual. Please
place this manual in a convenient location for easy reference.
SYMBOLS
WARNING
CAUTION
!
An external protection device must be installed if failure of this instrument
could result in damage to the instrument, equipment or injury to personnel.
: This mark indicates precautions that must be taken if there is danger of electric
shock, fire, etc., which could result in loss of life or injury.
: This mark indicates that if these precautions and operating procedures are no
taken, damage to the instrument may result.
: This mark indicates that all precautions should be taken for safe usage.
: This mark indicates important information on installation, handling and operating
procedures.
: This mark indicates supplemental information on installation, handling and
operating procedures.
: This mark indicates where additional information may be located.
WARNING
!
All wiring must be completed before power is turned on to prevent electric
shock, fire or damage to instrument and equipment.
This instrument must be used in accordance with the specifications to
prevent fire or damage to instrument and equipment.
This instrument is not intended for use in locations subject to flammable or
explosive gases.
Do not touch high-voltage connections such as power supply terminals, etc.
to avoid electric shock.
RKC is not responsible if this instrument is repaired, modified or
disassembled by other than factory-approved personnel. Malfunction can
occur and warranty is void under these conditions.
IMS01P09-E4
i-1
CAUTION
This is a Class A instrument. In a domestic environment, this instrument may cause radio
interference, in which case the user may be required to take adequate measures.
This instrument is protected from electric shock by reinforced insulation. Provide
reinforced insulation between the wire for the input signal and the wires for instrument
power supply, source of power and loads.
Be sure to provide an appropriate surge control circuit respectively for the following:
- If input/output or signal lines within the building are longer than 30 meters.
- If input/output or signal lines leave the building, regardless the length.
This instrument is designed for installation in an enclosed instrumentation panel. All
high-voltage connections such as power supply terminals must be enclosed in the
instrumentation panel to avoid electric shock by operating personnel.
All precautions described in this manual should be taken to avoid damage to the
instrument or equipment.
All wiring must be in accordance with local codes and regulations.
All wiring must be completed before power is turned on to prevent electric shock,
instrument failure, or incorrect action.
The power must be turned off before repairing work for input break and output failure
including replacement of sensor, contactor or SSR, and all wiring must be completed
before power is turned on again.
To prevent instrument damage or failure, protect the power line and the input/output lines
from high currents with a protection device such as fuse, circuit breaker, etc.
Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid
electric shock, fire or malfunction.
Tighten each terminal screw to the specified torque found in the manual to avoid electric
shock, fire or malfunction.
For proper operation of this instrument, provide adequate ventilation for heat dispensation.
Do not connect wires to unused terminals as this will interfere with proper operation of the
instrument.
Turn off the power supply before cleaning the instrument.
Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or
discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
To avoid damage to instrument display, do not rub with an abrasive material or push front
panel with a hard object.
Do not connect modular connectors to telephone line.
NOTICE
This manual assumes that the reader has a fundamental knowledge of the principles of electricity,
process control, computer technology and communications.
The figures, diagrams and numeric values used in this manual are only for purpose of illustration.
RKC is not responsible for any damage or injury that is caused as a result of using this instrument,
instrument failure or indirect damage.
RKC is not responsible for any damage and/or injury resulting from the use of instruments made by
imitating this instrument.
Periodic maintenance is required for safe and proper operation of this instrument. Some
components have a limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all information contained herein. RKC makes no
warranty expressed or implied, with respect to the accuracy of the information. The information in
this manual is subject to change without prior notice.
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored,
processed or retrieved through any mechanical, electronic, optical or other means without prior
written approval from RKC.
APPENDIX B. DATA PROCESSING TIME......................... 115
INDEX OF DATA ITEMS ...................................................... 117
i-4
IMS01P09-E4
1. OUTLINE
This manual describes Modbus/TCP protocol communication when the temperature control module
for Ethernet V-TIO-P or V-TIO-Q (hereafter called the V-TIO-P/V-TIO-Q module) for the module
type controller SRV is used.
• The V-TIO-P/V-TIO-Q module has one modular connector (RJ-45) for connection to Ethernet.
• Up to 30 temperature control modules (V-TIO-A, B, C or D) can be connected to one
V-TIO-P/V-TIO-Q module.
Modbus/TCP is an open field network provided with the Modbus protocol on the TCP/IP
protocol of Ethernet.
The data request side is called “client” (such as computer) and the data response (supply)
side is called “server” (SRV).
Basically, one client corresponds to one server (SRV) (i.e. one to one). However, one client
can communicate with two or more servers depending on the program on the client side, but
two or more clients cannot communicate with one server.
For specification, parts description and wiring of the V-TIO-P/V-TIO-Q module, see
Temperature Control Module for Ethernet V-TIO-P/V-TIO-Q Instruction Manual
(IMS01P08-E).
Computer
(Client)
Network Hub
Ethernet
Ethernet
Temperature control
module for Ethernet
V-TIO-P/V-TIO-Q
(Server)
Usable modules:
•
Temperature control (TIO) module
[Basic type]: V-TIO-A, V-TIO-C
•
Temperature control (TIO) module
[Extension type]: V-TIO-B, V-TIO-D
(Up to 30 modules)
IMS01P09-E4 1
2. COMMUNICATION SPECIFICATIONS
Ethernet communication
Physical layer: Ethernet
10BASE-T/100BASE-TX automatic recognition
Application layer: Modbus/TCP
Communication data: Based on Modbus message format
Connector type: RJ-45
Maximum connections: Up to 30 temperature control modules can be connected to one
V-TIO-P/V-TIO-Q module.
(Maximum number of temperature control point: 62 channels)
Modbus/TCP message configuration
Modbus ADU (Application Data Unit) on TCP/IP
MBAP Header:Transaction Identifier: 2 bytes
MBAP Header
7 bytes
Modbus TCP/IP ADU
Protocol Identifier: 2 bytes
Data Length: 2 bytes
Unit Identifier: 1 byte
(MBAP: Modbus Application Protocol)
Conduct necessary setting before operation according to the procedure described below.
Address setting
Set the module address.
See 4.1 Module Address Setting (P. 6).
Internal communication
setting
Set the communication speed and data bit configuration.
See 4.2 Internal Communication Setting (P. 8).
Wiring of SRV
Wire a power supply and input/output of SRV (server).
For the V-TIO-P/V-TIO-Q module, see APPENDIX A.1 Terminal
Configuration (P. 102).
For other modules, see the Instruction Manual of each module.
Connection of
communication line
Connect SRV (server) to client.
See 5. Wiring (P. 12).
Power ON
Turn on the power supply of SRV (server) and client.
The V-TIO-P/V-TIO-Q module starts collecting data on each module
connected from the time when the power is turned on. At this time, the
RUN lamp corresponding to indication lamp 2 flashed at very short
intervals.
After data collection is finished and communication becomes enabled *,
the RUN lamp keeps lighting.
* Time required for enabling communication differs depending on the number
of modules connected.
A
Continued on the next page.
IMS01P09-E4 3
3. SETTING PROCEDURE TO OPERATION
y
Continued from the previous page.
A
Do execute
IP address setting
by a Telnet ?
NO
YES
IP address setting
by a Telnet
The IP address is set by using
Telnet.
See 6.1 Setting by Telnet (P. 16).
IP address setting
by a web browser
The IP address is set by using
a web browser.
See 6.2 Setting by the Web Browser (P. 21).
Initial setting data setting
Set the Input scale high/low limit, Input range decimal point position, Control
t
Before setting operation data items, always set initial setting data
items so as to satisfy the specification used.
pe, Event type etc.
For initial setting data items, see 7.6.2 Initial setting data items (P. 51) or
8.2 Initial Setting Data Items (P. 86).
B
Do execute
IP address setting by a
web browser ?
YES
NO
IP address setting
by the DIP switches
The IP address is set by using
the DIP switches.
See 6.3 Setting by the DIP Switch (P. 24).
Continued on the next page.
4
IMS01P09-E4
Continued from the previous page.
B
Power ON again
The initial setting data items thus set are registered by turning on the
SRV power supply again.
Operation data setting
Set data to be related to the control.
Operation mode setting
Select the operation mode in the Auto/Manual transfer.
(Factory set value: AUTO)
Control RUN
Set the control RUN/STOP transfer to the “RUN.”
(Factory set value: STOP)
Operation start
3. SETTING PROCEDURE TO OPERATION
For data, see 7.6.1 Normal setting data items (P. 43) or 8.1 Normal
Setting Data Items (P. 57).
IMS01P09-E4
5
4. COMMUNICATION SETTING
To prevent electric shock or instrument failure, always turn off the power
before setting the switch.
WARNING
!
To prevent electric shock or instrument failure, never touch any section other
than those instructed in this manual.
CAUTION
Do not separate the module mainframe from the terminal base with the power turned on. If
separated, adjusted data may be destroyed; control be stopped, and no return can be made.
Set the following communication setting before operation.
4.1 Module Address Setting
When using two or more modules, set the desired address to each module.
Set the module address by address setting switch of front of module. For this setting, use a small blade
screwdriver.
Address setting switch
FAIL/RUN
RX/TX
EVENT1
EVENT2
EVENT3
EVENT4
3
2
4
1
5
5 5
0
6
9
7
8
3
2
4
1
5
0
6
9
7
8
Setting range: 0 to 30
(Factory set value: 0)
Set the module address such that it is different to the other addresses in the same unit.
Otherwise, problems or malfunction may result.
3
2
4
1
5
55
0
9
8
3
2
1
0
9
8
High-order digit setting
6
7
(set value × 10)
4
5
Low-order digit setting
6
7
(set value × 1)
The above figure is V-TIO-P/V-TIO-Q module. The figure of other TIO module is the same
as a V-TIO-P/V-TIO-Q module.
6 IMS01P09-E4
4. COMMUNICATION SETTING
The channel number for the module address
The module address can be freely set with any numbers from 0 to 30.
In addition, to each module address, the relevant temperature control channel is assigned. Each
temperature control channel number can be calculated from the following equation.
Temperature control channel number of communication
[Setting example]
V-TIO-P module
= (Module address × 2) + Temperature control channel number of module
Temperature control module [extension type] V-TIO-B
Module
address
30
CH1
CH61
CH2
CH62
Temperature contr ol
channel num ber of
module
Temperature contr ol
channel num ber of
communication
CH1
CH1
CH2
CH2
CH1
CH3
CH2
CH4
CH1
CH21
CH2
CH22
CH1
CH23
CH2
CH24
CH1
CH41
CH2
CH42
21201110 10
CH1
CH2
CH43
CH44
For heat/cool control, data in the second channel of each module becomes invalid.
[Example] If module addresses of one V-TIO-Q module and six V-TIO-D modules which
are heat/cool temperature control modules are set as follows by the free setting,
data in odd channels is used because data in even channels is invalid.
Valid channel number: 1, 3, 21, 23, 41, 43, 61
Invalid channel number: 2, 4, 22, 24, 42, 44, 62
V-TIO-Q module
Temperature control module [extension type] V-TIO-D
Module
address
Valid channel
Invalid channel
IMS01P09-E4
CH1
CH1
CH2
CH2
CH1
CH3
CH2
CH4
CH1
CH21
CH2
CH22
CH1
CH23
CH2
CH24
CH1
CH41
CH2
CH42
CH1
CH43
212011101 0
CH2
CH44
CH1
CH61
30
CH2
CH62
Temperature control
channel number of
module
Temperature control
channel number of
communication
7
4. COMMUNICATION SETTING
4.2 Internal Communication Setting
Internal communication is used for data transfer between modules within the SRV unit.
The setting is made on the Ethernet communication and temperature control sides of the
V-TIO-P/V-TIO-Q module.
Setting of Ethernet communication side
With the DIP switch 1 which there is on the left side of V-TIO-P/V-TIO-Q module, select internal
communication speed.
Switch No. 3 to 8: OFF fixed (Don’t change this one)
Set the communication speed to the same value as the setting on the temperature
control side (DIP switch 3).
Left side view
1 2 Communication speed
OFF OFF
ON OFF
OFF ON
ON ON
38400 bps
9600 bps
19200 bps
38400 bps
DIP switch 1
ON
ON
1234567 8
1234567 8
ON
OFF
Factory
set value
8
IMS01P09-E4
4. COMMUNICATION SETTING
Setting of temperature control side
With the DIP switch 3 which there is on the right side of V-TIO-P/V-TIO-Q module, select internal
communication speed and data bit configuration.
Switch No. 6: ON fixed (Don’t change this one)
Switch No. 7, 8: OFF fixed (Don’t change this one)
Set the communication speed to the same value as the setting on the Ethernet
communication side (DIP switch 1).
When connecting two or more modules (V-TIO-A, V-TIO-B, V-TIO-C or V-TIO-D) to
the V-TIO-P/V-TIO-Q module, match all of their communication speed and data bit
configuration settings with the internal settings of the V-TIO-P/V-TIO-Q module.
Right side view
1 2 Communication speed
OFF OFF
ON OFF
OFF ON
ON ON
9600 bps
19200 bps
38400 bps
Don’t set this one
3 4 5 Data bit configuration
OFF OFF OFF
OFF OFF ON
Don’t set this one
OFF ON OFF
OFF ON ON
ON OFF OFF
Data 8-bit, without parity, Stop 1-bit
ON OFF ON
ON ON OFF
Don’t set this one
ON ON ON
DIP switch 3
ON
ON
12345678
12345678
ON
OFF
Factory
set value
Factory
set value
IMS01P09-E4
9
4. COMMUNICATION SETTING
4.3 Termination Resistor Setting of Internal communication
Procedure for setting a termination resistor to internal communication (RS-485) and its setting position
are described in the following.
Termination resistor setting position
Set a termination resistor to the communication line termination in the module located in the position
farthermost from the V-TIO-P/V-TIO-Q module.
V-TIO-P/V-TIO-Q module
Temperature control module
[extension type] V-TIO- B/V-TIO-D
Setting procedure of termination resistor
SRV unit
Internal communication
(RS-485)
Turn on the termination
resistor of this module.
As no termination resistor is externally connected to the temperature control (TIO) module [extension
type] V-TIO-B (or V-TIO-D), the termination resistor built in the module is connected by switch
selection.
1. Turn off the power supply of the module.
Do not separate the module mainframe from the terminal base with the power turned on. If
separated, adjusted data may be destroyed; control be stopped, and no return can be made.
2. Pull out the module mainframe itself toward you while pushing the locks at its top and bottom,
and then separate it from the terminal base.
Upper-side lock
Top view
Terminal base
Module mainframe
(1) Push
(2) Pull out
Lower-side lock
10
Bottom view
(1) Push
Removing the module mainframe
IMS01P09-E4
Ω
3. Turn on the termination resistor transfer switch in the terminal base.
Termination resistor transfer switch
4. COMMUNICATION SETTING
Termination resistor ON (120
1/2 W)
Termination resistor OFF
Factory set value: OFF
A terminal base of the state which removed module mainframe
4. Push the module mainframe thus separated in the terminal base until firmly locked.
Terminal base
Module mainframe
Push the module
mainframe until
firmly locked
Mounting the module mainframe
IMS01P09-E4
11
(
5. WIRING
To prevent electric shock or instrument failure, turn off the power before
connecting or disconnecting the instrument and peripheral equipment.
WARNING
!
CAUTION
Connect connectors correctly in the right position. If it is forcibly pushed in with pins in
the wrong positions, the pins may be bent resulting in instrument failure.
When connecting or disconnecting the connectors, do not force it too far to right and left
or up and down, but move it on the straight. Otherwise, the connector pins may be bent,
causing instrument failure.
When disconnecting a connector, hold it by the connector itself. Disconnecting
connectors by yanking on their cables can cause breakdowns.
To prevent malfunction, never touch the contact section of a connector with bare hands
or with hands soiled with oil or the like.
To prevent malfunction, connect cable connectors securely, then firmly tighten the
connector fastening screws.
To prevent damage to cables, do not bend cables over with excessive force.
If the instrument is easily affected by noise, use the ferrite core in the both ends of the
communication cable (nearest the connector).
5.1 Wiring Configuration
When directly connected to client
Computer
(Client)
Internal Communication
Ethernet
V-TIO-P/V-TIO-Q module
Server)
Up to 30 temperature control modules can be connected to one V-TIO-P/V-TIO-Q module.
SRV unit
(RS-485)
TIO module [extension type]
V-TIO-B/V-TIO-D
12 IMS01P09-E4
(
)
When use network hub
Computer
(Client)
Network Hub
Ethernet
Up to 30 temperature control modules can be connected to one V-TIO-P/V-TIO-Q module.
Basically, one client corresponds to one server (SRV) (i.e. one to one). However, one client
can communicate with two or more servers depending on the program on the client side, but
two or more clients cannot communicate with one server.
The cable is provided by the customer.
Used cable: The cable is based on the 10BASE-T or the 100BASE-TX standard of
Used connector: RJ-45 type
Send data + TX+
Send data − TX−
Receive data + RX+
Receive data − RX−
Ethernet.
14
IMS01P09-E4
+TX−RX+
−
Wiring example
When directly connected to client
Use a cross cable when directly connected to the client (such as computer).
Computer
V-TIO-P/V-TIO-Q
5. WIRING
module
TX
+
TX
−
RX
+
RX
−
Cross cable
When use network hub
Use straight cables when connected to the network hub.
Computer
TX
TX
RX
RX
+
−
+
−
Network Hab
TX+
TX−
RX+
RX−
TX
RX
TX+
TX−
RX+
RX−
V-TIO-P/V-TIO-Q
module
TX+
TX−
RX+
RX−
IMS01P09-E4
Straight cable Straight cable
Cross cables may be used depending on the connecting device used. Therefore, follow the
instructions for the respective device.
15
6. IP ADDRESS SETTING
Set an IP address of a V-TIO-P/V-TIO-Q module.
Three types of IP address setting are available: “setting by Telnet,” “setting by Web browser” and
“setting by DIP switch.”
Confirm the IP address number to the network administrator of the network (LAN) to
which the V-TIO-P/V-TIO-Q module is connected.
6.1 Setting by Telnet
Set the IP address by the software “Telnet” attached to Windows.
Preparations before setting
When setting the IP address by Telnet, it is necessary to coincide the 1st to 3rd bytes and masking
range of the IP address of the client (computer) which starts Telnet with those of the IP address of the
V-TIO-P/V-TIO-Q module.
1. Connect the V-TIO-P/V-TIO-Q module and client, and then turn on the power.
For wiring procedure, see 5. WIRING (P. 12).
2. The IP address of the V-TIO-P/V-TIO-Q module is set to a factory set value of “192.168.1.1.”
As it is necessary to coincide the 1st to 3rd byte values of this IP address with those of the IP
address of the client, change the IP address of the client to “192.168.1.” (: Any value in the
range of 0 to 255, but other than 1).
3. As the subnet mask of the V-TIO-P/V-TIO-Q module is “255.255.255.0,” also change the subnet
mask of the client to “255.255.255.0.”
After the IP address of the server is set, return the present IP address of the client to the
original address or change to the address meeting the network to be connected.
It is possible to set the IP address of the V-TIO-P/V-TIO-Q module using the client already
connected to the network. However, as the IP address of the client is changed, that client is
disconnected from the network so far connected.
In addition, when setting the IP address by this method, confirm to the network administrator
whether or not no problem arises.
16 IMS01P09-E4
6. IP ADDRESS SETTING
Setting example
An example of setting the IP address to “192.168.1.3” is shown in the following.
1. Display the MS-DOS prompt (command prompt); enter the following command and then press
the Enter key.
C:¥>telnet 192.168.1.1 9999
2. Device information on the module (V-TIO-P/V-TIO-Q module) whose IP address is
“192.168.1.1” is displayed. Finally, as the message “Press Enter to go into Setup Mode” is
displayed, press the Enter key to go into Setup Mode.
MAC address 00204A8064BD
Software version 01.3 (030612) XPTE
Press Enter to go into Setup Mode
If the timing of pressing the Enter key is late, the message “Connection with Host was cut
off” is displayed and thus the client is disconnected from the V-TIO-P/V-TIO-Q module.
Therefore if the message “Press Enter to go into Setup Mode” is displayed, immediately
press the Enter key.
If disconnected, try again from “1.”
3. If entered into Setup Mode, the present Ethernet information is displayed.
Finally, eight choices are displayed as “Change Setup:.” Therefore enter “0” after “Your
choice ?” and then press the Enter key.
*** basic parameters
Hardware: Ethernet TPI
IP addr 192.168.1.1, no gateway set,netmask 255.255.255.000
*************** Security ***************
SNMP is enabled
SNMP Community Name: public
Telnet Setup is enabled
TFTP Download is enabled
Port 77FEh is enabled
Web Server is enabled
ECHO is disabled
Enhanced Password is disabled
*************** E-mail *****************
Mail server: 0.0.0.0
Unit :
Domain :
Recipient 1:
Recipient 2:
*** Trigger 1
Serial Sequence: 00,00
CP1: X
CP2: X
CP3: X
Message:
Priority : L
Min. notification interval: 1 s
Re-notification interval : 0 s
*** Trigger 2
Serial Sequence: 00,00
CP1: X
CP2: X
CP3: X
Message:
Priority : L
Min. notification interval: 1 s
Re-notification interval : 0 s
*** Trigger 3
Serial Sequence: 00,00
CP1: X
CP2: X
CP3: X
Message:
Priority : L
Min. notification interval: 1 s
Re-notification interval : 0 s
Change Setup:
0 Server configuration
1 Channel 1 configuration
3 E-mail settings
5 Expert settings
6 Security
7 Factory defaults
8 Exit without save
9 Save and exit Your choice ? 0
Enter “0” (Server configuration),
and press the Enter key.
18
IMS01P09-E4
4. Selecting “0: Server configuration” makes ready to set the IP address.
Enter the IP address one byte by one byte.
As the following display appears, enter “192” into the first byte and then press the Enter key.
IP Address : (192) 192
Next, enter “168” into the second byte and then press the Enter key.
IP Address : (192) 192.(168) 168
Enter “1” into the third byte and then press the Enter key.
IP Address : (192) 192.(168) 168.(001) 1
6. IP ADDRESS SETTING
Enter “3” into the fourth byte and then press the Enter key.
IP Address : (192) 192.(168) 168.(001) 1.(001) 3
5. After the IP address is entered, the following display appears. Therefore press the Enter key to
proceed to the next.
IP Address : (192) 192.(168) 168.(001) 1.(001) 3
Set Gateway IP Address (N) N
In addition, as one line is displayed, press the Enter key to proceed to the next.
IP Address : (192) 192.(168) 168.(001) 1.(001) 3
Set Gateway IP Address (N) N
Netmask: Number of Bits for Host Part (0=default) (16)
Further, as more one line is displayed, press the Enter key to proceed to the next.
IP Address : (192) 192.(168) 168.(001) 1.(001) 3
Set Gateway IP Address (N) N
Netmask: Number of Bits for Host Part (0=default) (16)
Change telnet config password (N) N
IMS01P09-E4
19
6. IP ADDRESS SETTING
6. As “Change Setup:” is displayed again, enter “9” after “Your choice ?” and then press the Enter
key.
Enter “9” (Save and exit),
and press the Enter key.
6 Security
7 Factory defaults
8 Exit without save
9 Save and exit Your choice ? 9
7. “Parameters stored ...” is displayed and thus the setting is finished.
Parameters stored ...
Connection with Host was cut off
20
IMS01P09-E4
6. IP ADDRESS SETTING
6.2 Setting by the Web Browser
It is possible to set the IP address by using the Web browser (such as Internet Explorer).
Preparations before setting
When setting the IP address by Web browser, it is necessary to coincide the 1st to 3rd bytes and
masking range of the IP address of the client (computer) which starts Web browser with those of the
IP address of the V-TIO-P/V-TIO-Q module.
1. Connect the V-TIO-P/V-TIO-Q module and client, and then turn on the power.
For wiring procedure, see 5. WIRING (P. 12).
2. The IP address of the V-TIO-P/V-TIO-Q module is set to a factory set value of “192.168.1.1.”
As it is necessary to coincide the 1st to 3rd byte values of this IP address with those of the IP
address of the client, change the IP address of the client to “192.168.1. ” (: Any value in the
range of 0 to 255, but other than 1).
3. As the subnet mask of the V-TIO-P/V-TIO-Q module is “255.255.255.0,” also change the subnet
mask of the client to “255.255.255.0.”
After the IP address of the server is set, return the present IP address of the client to the
original address or change to the address meeting the network to be connected.
It is possible to set the IP address of the V-TIO-P/V-TIO-Q module using the client already
connected to the network. However, as the IP address of the client is changed, that client is
disconnected from the network so far connected.
In addition, when setting the IP address by this method, confirm to the network administrator
whether or not no problem arises.
IMS01P09-E4
21
6. IP ADDRESS SETTING
Setting example
An example of setting the IP address to “192.168.1.3” is shown in the following.
1. Start the Web browser; enter the present IP address “192.168.1.1” into the address bar and then
press the Enter key.
2. The initial setting applet starts. “Selected Channel: 1” is displayed on the main display with “Port
Properties” selected on the Menu display on the left side of the screen.
Under this condition, click the Server Properties button on the Menu display.
Do not change the contents of “Selected Channel: 1.” If changed, device failure or
error may result.
Click
22
IMS01P09-E4
6. IP ADDRESS SETTING
3. Display the Server Properties screen.
Set “192.168.1.3” in IP Address.
Set
192.168.1.3
Do not change any items other than the IP Address. If so, device failure or error
may result.
4. Clicking the Update Settings button on the Menu display updates the setting to display the
following message.
Click
5. Enter the new IP address “192.168.1.3” into the address bar as instructed by message and then
press the Enter key. Thus, a new IP address setting screen appears to end the setting.
IMS01P09-E4
23
6. IP ADDRESS SETTING
6.3 Setting by the DIP Switch
It is possible to set the IP address by DIP switch with Ethernet not connected.
DIP switches used are “DIP switch 1” and “DIP switch 2” on the left side of the module.
DIP switch 1
DIP switch 2
Left side view of V-TIO-P/V-TIO-Q module
Factory set value of an IP address of a V-TIO-P/V-TIO-Q module is “192.168.1.1.”
Setting example
An example of setting the IP address to “192.168.1.3” is shown in the following.
1. Setting preparations
Turn on No. 6 and off No. 7 of DIP switch 1 with the power turned off.
It does not matter whether Nos. 1 to 5 and No. 8 of DIP switch 1 is turned on or off.
2. Power ON
Turning the power on goes to IP address setup mode. Thus, the FAIL lamp lights.
In addition, the first byte (most significant byte) of the IP address is set to the entry wait state.
(RUN lamp: ON, TX lamp: ON, RX lamp: OFF)
DIP switch 1
ON
ON
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ON
OFF
FAIL lamp
ON
No. 6: ON
No. 7: OFF
RUN lamp
ON
RX lamp
OFF
TX lamp
ON
24
IMS01P09-E4
Loading...
+ 100 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.