!"Modbus is a registered trademark of Schneider Electric.
!"Company names and product names used in this manual are the trademarks or registered trademarks of
the respective companies.
All Rights Reserved, Copyright 1999, RKC INSTRUMENT INC.
Thank you for purchasing the RKC instrument. In order to achieve maximum performance and ensure
proper operation of your new instrument, carefully read all the instructions in this manual. Please
place this manual in a convenient location for easy reference.
SYMBOLS
WARNING
CAUTION
!
: This mark indicates precautions that must be taken if there is danger of electric
shock, fire, etc., which could result in loss of life or injury.
: This mark indicates that if these precautions and operating procedures are not
taken, damage to the instrument may result.
: This mark indicates that all precautions should be taken for safe usage.
: This mark indicates important information on installation, handling and operating
procedures.
: This mark indicates supplemental information on installation, handling and
operating procedures.
: This mark indicates where additional information may be located.
WARNING
!
An external protection device must be installed if failure of this instrument
!"
could result in damage to the instrument, equipment or injury to personnel.
All wiring must be completed before power is turned on to prevent electric
!"
shock, fire or damage to instrument and equipment.
This instrument must be used in accordance with the specifications to prevent
!"
fire or damage to instrument and equipment.
This instrument is not intended for use in locations subject to flammable or
!"
explosive gases.
Do not touch high-voltage connections such as power supply terminals, etc.
!"
to avoid electric shock.
RKC is not responsible if this instrument is repaired, modified or
!"
disassembled by other than factory-approved personnel. Malfunction can
occur and warranty is void under these conditions.
IMR01D02-E3
i-1
CAUTION
This is a Class A instrument. In a domestic environment, this instrument may cause radio
!
interference, in which case the user may be required to take adequate measures.
This instrument is protected from electric shock by reinforced insulation. Provide
!
reinforced insulation between the wire for the input signal and the wires for instrument
power supply, source of power and loads.
Be sure to provide an appropriate surge control circuit respectively for the following:
!
- If input/output or signal lines within the building are longer than 30 meters.
- If input/output or signal lines leave the building, regardless the length.
This instrument is designed for installation in an enclosed instrumentation panel. All high-
!
voltage connections such as power supply terminals must be enclosed in the
instrumentation panel to avoid electric shock by operating personnel.
All precautions described in this manual should be taken to avoid damage to the
!
instrument or equipment.
All wiring must be in accordance with local codes and regulations.
!
All wiring must be completed before power is turned on to prevent electric shock,
!
instrument failure, or incorrect action.
The power must be turned off before repairing work for input break and output failure
including replacement of sensor, contactor or SSR, and all wiring must be completed
before power is turned on again.
To prevent instrument damage or failure, protect the power line and the input/output lines
!
from high currents with a protection device such as fuse, circuit breaker, etc.
Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid
!
electric shock, fire or malfunction.
Tighten each terminal screw to the specified torque found in the manual to avoid electric
!
shock, fire or malfunction.
For proper operation of this instrument, provide adequate ventilation for heat dispensation.
!
Do not connect wires to unused terminals as this will interfere with proper operation of the
!
instrument.
Turn off the power supply before cleaning the instrument.
!
Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or
!
discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
To avoid damage to instrument display, do not rub with an abrasive material or push front
!
panel with a hard object.
Do not connect modular connectors to telephone line.
!
NOTICE
!
This manual assumes that the reader has a fundamental knowledge of the principles of electricity,
process control, computer technology and communications.
!
The figures, diagrams and numeric values used in this manual are only for purpose of illustration.
!
RKC is not responsible for any damage or injury that is caused as a result of using this instrument,
instrument failure or indirect damage.
!
Periodic maintenance is required for safe and proper operation of this instrument. Some
components have a limited service life, or characteristics that change over time.
!
Every effort has been made to ensure accuracy of all information contained herein. RKC makes no
warranty expressed or implied, with respect to the accuracy of the information. The information in
this manual is subject to change without prior notice.
!
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored,
processed or retrieved through any mechanical, electronic, optical or other means without prior
written approval from RKC.
SA200 interfaces with the host computer via Modbus or RKC communication protocols. For
reference purposes, the Modbus protocol identifies the host computer as master, the SA200 as slave.
The RKC protocol identifies these parts of the control system as the host computer and SA200.
The maximum communication distance will be affected by the
surrounding conditions.
Synchronous method:Start/stop synchronous type
Communication speed:2400 bps, 4800 bps, 9600 bps, 19200 bps (Selectable)
Data bit configuration:Data bit:8 (Byte data corresponding to binary data or bit.)
Parity bit: Without, Odd or Even (Selectable)
Stop bit:1
Protocol:Modbus
Signal transmission mode: Remote Terminal Unit (RTU) mode
Function code:03H (Read holding registers)
06H (Preset single register)
08H (Diagnostics: loopback test)
Error check method:CRC-16
Error code:1: Function code error
2: When written to read only (RO) data, When any address other than
0000H to 001AH is specified, etc.
3: When the data written exceeds the setting range, When the specified
number of data items in the query message exceeds the maximum
number of data items available
4: Self-diagnostic error response
Termination resistor:Externally connected
Maximum connections:32 instruments maximum including a master
Signal logic:RS-485
Signal voltageLogic
V (A) - V (B) ≥ 2 V0 (SPACE)
V (A) - V (B) ≤ -2
V
Voltage between V (A) and V (B) is the voltage of (A) terminal for the
(B) terminal.
2
1 (MARK)
IMR01D02-E3
2.WIRING
(B)
(A)
(B)
(A)
)
)
p
(B)
(A)
WARNING
!
To prevent electric shock or instrument failure, turn off the power before
connecting or disconnecting the instrument and peripheral equipment.
Terminal number and signal details
!"
!"
!"!"
Terminal
No.
SymbolSignal
name
10Signal groundSG
11Send data/Receive dataT/R (A)
12Send data/Receive dataT/R (B)
Wiring method
!"
!"
!"!"
Connection to the RS-485 port of the host computer (master)
#"
#"
#"#"
(Slave)
T/R
T/R
SA200
(Slave)
T/R
T/R
SA200
SG
$
$
$
SG
RS-485
Shielded twisted
pair wire
* R
Paired wire
* R
Host com
SG
T/R
T/R
SD (TXD) and RD (RXD): Negative logic
uter (Master)
SD (TXD
RD (RXD
Send/Receive
transfer signal
Send data
:
Receive data
:
IMR01D02-E3
31 max.
* R: Termination resistors (Example: 120 Ω 1/2 W)
3
2. WIRING
(
(
(
Connection to the RS-232C port of the host computer (master)
#"
#"
#"#"
A RS-232C/RS-485 converter is required.
SA200
(Slave)
SG
T/R (A)
RS-485
Paired wire
SG
T/R (A)
RS-232C
T/R (B)
* R
Shielded twisted
pair wire
* R: Termination resistors (Example: 120 Ω 1/2 W)
* R
T/R (B)
RS-232C/RS-485
converter
When the host computer (master) uses Windows 95/98/NT, use a RS-232C/RS-485
converter with an automatic send/receive transfer function.
Recommended: CD485, CD485/V manufactured by Data Link, Inc. or equivalent.
Wiring example
!"
!"
!"!"
Connection with up to 31 SA200 (slaves) and one host computer (master)
#"
#"
#"#"
Host computer (Master) Host computer (Master)
RS-232C
Host computer
Master)
RS-485
or
Device address
(Slave address)
SA200
Slaves)
4
RS-232C/RS-485 converter
RS-485
Junction terminal
30 29 31 1 2 3 4
SA200
Slaves)
IMR01D02-E3
3.SETTING
To establish communication parameters between host computer (master) and SA200 (slave), it is
necessary to set the device address (slave address), communication speed, data configuration and
interval time on each SA200 (slave) in the communication mode.
3.1 Communication Setting Mode
1. When the power to the SA200 is turned on, the input type, input range and PV/SV display will
be automatically displayed in that order.
2. To go to the communication setting mode, you must be in PV/SV display. Press and hold the
SET key and press the <R/S key at the same time to initiate communication settings. The first
parameter to be displayed will be the device address (slave address), Add.
SA200
SVPV
AT
SV2
OUT1
ALM1
OUT2
ALM2
R/SSET
SA200
R/SSET
SVPV
AT
SV2
OUT1
ALM1
OUT2
ALM2
Device address (Slave address)
PV/SV display
Communication setting mode
To return to the PV/SV display, press and hold the SET key and press the <R/S key at the
same time.
IMR01D02-E3
5
3. SETTING
3.2 Setting the Communication Parameters
To select parameters in communication setting mode, press the SET key. The parameters are
displayed and sequenced in the order of device address (slave address), Add, communication speed,
bPS, data configuration, bIT and interval time set value, InT.
Display flowchart
!"
!"
!"!"
Power ON
Display changes automatically
Input type and input range
display
(Display approx. 4 seconds.)
PV/SV display
Press and hold the SET key and press the <R/S key at same time.
Communication setting mode
PV
SV
Device address
(Slave address)
Press the SET key.
SVPV
Communication
Add
[
speed
bPS
[
]
Press the SET key
]
for 2 seconds.
Press the SET key.
PV
PV
Press the SET key.
6
SV
Data configuration
Press the SET key.
SV
Interval time set value
bIT
[
InT
[
]
]
setting mode
IMR01D02-E3
Parameter
3. SETTING
3.3 Device Address (Slave Address) Setting
The device address (slave address) must be set before communication can begin. The device address
(slave address) number is set with numbers from 0 to 99.
SymbolNameSetting rangeDescriptionFactory
set value
Device address
(Slave address)
0 to 99Set the SA200 device
address (slave address).
Add
If the slave address is set to 0 in Modbus communication, two-way communication cannot
be performed.
When the communication parameter is changed, turn the power on and off again or switch
from STOP to RUN to refresh and make the new value effective. If neither action is taken,
the SA200 will maintain the set value prior to change.
All device address (slave address) settings must be stored by pressing the SET key. If
changes are made and the SET key is not pressed within one minute, the display will
automatically return to the PV/SV display and the device address (slave address) will return
to the value prior to set change.
Setting procedure
!"
!"
!"!"
Example: When setting the device address (slave address) to 15.
1. Go to the communication setting mode so that device address (slave address), Add, is displayed.
0
IMR01D02-E3
3.1 Communication Setting Mode (P. 5),
See
(P. 6).
R/SSET
SA200
Device address (Slave address)
3.2 Select Communication Parameters
SVPV
AT
SV2
OUT1
ALM1
OUT2
ALM2
Continued on the next page.
7
3. SETTING
2. Press the UP key to enter 5 at the first digit from the right.
R/SSET
SA200
3. Press the <R/S key to blink the second digit from the right.
SVPV
AT
SV2
OUT1
ALM1
OUT2
ALM2
SVPV
AT
OUT1
OUT2
R/SSET
SA200
4. Press the UP key to enter 1 at the second digit from the right.
SVPV
AT
OUT1
OUT2
R/SSET
SA200
SV2
ALM1
ALM2
SV2
ALM1
ALM2
5. Press the SET key to store the new device address (slave address). The display automatically
goes to the next communication parameter, bPS.
8
IMR01D02-E3
3. SETTING
3.4 Communication Speed Setting
The communication speed of 2400 bps, 4800 bps, 9600 bps or 19200 bps is selectable. To select the
speed of the bPS setting, press the UP or DOWN key.
SymbolNameSetting rangeDescriptionFactory
set value
Communication
speed
240:2400 bps
480:4800 bps
960:9600 bps
bPS1920: 19200 bps
Set the same communication speed for both the SA200 (slave) and the host computer
(master).
When the communication parameter is changed, turn the power on and off again or switch
from STOP to RUN to refresh and make the new value effective. If neither action is taken,
the SA200 will maintain the set value prior to change.
All communication speed settings must be stored by pressing the SET key. If changes are
made and the SET key is not pressed within one minute, the display will automatically
return to the PV/SV display and the communication speed will return to the value prior to
set change.
Setting procedure
!"
!"
!"!"
Example: Setting communication speed 480: 4800 bps.
Select the communication
speed
960
1. Go to the communication setting mode so that slave address, Add, is displayed. Then, press the
SET key once, so the communication speed symbol, bPS, appears.
3.1 Communication Setting Mode (P. 5),
See
3.2 Select Communication Parameters
(P. 6).
SVPV
AT
SV2
OUT1
ALM1
OUT2
ALM2
R/SSET
SA200
Communication speed
Continued on the next page.
IMR01D02-E3
9
3. SETTING
2. Press the DOWN key to set 480.
SVPV
AT
SV2
OUT1
ALM1
OUT2
ALM2
R/SSET
SA200
3. Press the SET key to store the new communication speed. The display automatically goes to the
next communication parameter, bIT.
10
IMR01D02-E3
3.5 Data Configuration Setting
To select the data configuration setting, press the UP or DOWN key.
SymbolNameSetting rangeDescriptionFactory
3. SETTING
set value
Data configurationSee
Data
configuration
bITtable.
Data configuration table
SettingData bitParity bitStop bit
(7n1)7Without1
(7n2)7Without2
(7E1)7Even1
(7E2)7Even2
(7o1)7Odd1
(7o2)7Odd2
(8n1)8Without1
Select data configuration
during communication
8n1
Setting range of
RKC
communication
(8n2)8Without2
(8E1)8Even1
Setting range of
Modbus
(8E2)8Even2
(8o1)8Odd1
(8o2)8Odd2
Set the same data configuration for both the SA200 (slave) and the host computer (master).
When the communication parameter is changed, turn the power on and off again or switch
from STOP to RUN to refresh and make the new value effective. If neither action is taken,
the SA200 will maintain the set value prior to change.
All data configuration settings must be stored by pressing the SET key. If changes are made
and the SET key is not pressed within one minute, the display will automatically return to
the PV/SV display and the data configuration will return to the value prior to set change.
IMR01D02-E3
11
3. SETTING
Setting procedure
!"
!"
!"!"
The setting procedures are the same as communication speed setting.
1. Go to the communication setting mode so that slave address, Add, is displayed. Press the SET
key until the data configuration symbol, bIT, appears.
2. Set the data bit configuration by pressing the UP or DOWN key.
For details on setting procedure, see 3.4 Communication Speed Setting (P. 9).
12
IMR01D02-E3
Loading...
+ 42 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.