RKC OPC-V606E Operation Manual

OPC-V
Operation Manual
Operation Panel
[For SRZ]
E
RKC INSTRUMENT INC.
®
IMS01T08-E1
Modbus is a registered trademark of Schneider Electric. Company names and product names used in this manual are the trademarks or registered trademarks of
the respective companies.
All Rights Reserved, Copyright 2006, RKC INSTRUMENT INC.
Thank you for purchasing this RKC instrument. In order to achieve maximum performance and ensure proper operation of your new instrument, carefully read all the instructions in this manual. Please place this manual in a convenient location for easy reference.
SYMBOLS

WARNING

CAUTION
!
: This mark indicates where additional information may be located.
An external protection device must be installed if failure of this instrument
could result in damage to the instrument, equipment or injury to personnel.
: This mark indicates precautions that must be taken if there is danger of electric
shock, fire, etc., which could result in loss of life or injury.
: This mark indicates that if these precautions and operating procedures are not taken,
damage to the instrument may result.
: This mark indicates that all precautions should be taken for safe usage.
: This mark indicates important information on installation, handling and operating procedures.
: This mark indicates supplemental information on installation, handling and operating procedures.
WARNING
!
All wiring must be completed before power is turned on to prevent electric
shock, fire or damage to instrument and equipment.
This instrument must be used in accordance with the specifications to
prevent fire or damage to instrument and equipment.
This instrument is not intended for use in locations subject to flammable or
explosive gases.
Do not touch high-voltage connections such as power supply terminals, etc.
to avoid electric shock.
RKC is not responsible if this instrument is repaired, modified or
disassembled by other than factory-approved personnel. Malfunction can occur and warranty is void under these conditions.
IMS01T08-E1
i-1

CAUTION

This is a Class A instrument. In a domestic environment, this instrument may cause radio
interference, in which case the user may be required to take adequate measures.
This instrument is protected from electric shock by reinforced insulation. Provide reinforced
insulation between the wire for the input signal and the wires for instrument power supply, source of power and loads.
Be sure to provide an appropriate surge control circuit respectively for the following:
- If input/output or signal lines within the building are longer than 30 meters.
- If input/output or signal lines leave the building, regardless the length.
This instrument is designed for installation in an enclosed instrumentation panel. All
high-voltage connections such as power supply terminals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel.
All precautions described in this manual should be taken to avoid damage to the instrument or
equipment.
All wiring must be in accordance with local codes and regulations. All wiring must be completed before power is turned on to prevent electric shock, instrument
failure, or incorrect action. The power must be turned off before repairing work for input break and output failure including replacement of sensor, contactor or SSR, and all wiring must be completed before power is turned on again.
To prevent instrument damage or failure, protect the power line and the input/output lines from
high currents with a protection device such as fuse, circuit breaker, etc.
Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid
electric shock, fire or malfunction.
Tighten each terminal screw to the specified torque found in the manual to avoid electric shock,
fire or malfunction.
For proper operation of this instrument, provide adequate ventilation for heat dispensation. Do not connect wires to unused terminals as this will interfere with proper operation of the
instrument.
Turn off the power supply before cleaning the instrument. Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or
discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
To avoid damage to instrument display, do not rub with an abrasive material or push front
panel with a hard object.
Do not connect modular connectors to telephone line.
NOTICE
This manual assumes that the reader has a fundamental knowledge of the principles of electricity,
process control, computer technology and communications.
The figures, diagrams and numeric values used in this manual are only for purpose of illustration. RKC is not responsible for any damage or injury that is caused as a result of using this instrument,
instrument failure or indirect damage.
RKC is not responsible for any damage and/or injury resulting from the use of instruments made by
imitating this instrument.
Periodic maintenance is required for safe and proper operation of this instrument. Some components
have a limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all information contained herein. RKC makes no
warranty expressed or implied, with respect to the accuracy of the information. The information in this manual is subject to change without prior notice.
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored,
processed or retrieved through any mechanical, electronic, optical or other means without prior written approval from RKC.
i-2
IMS01T08-E1

CONTENTS

1. OUTLINE............................................................................ 1-1
1.1 Features .......................................................................................................1-2
1.2 Checking the Products .................................................................................1-4
2. PREPARATIONS ...............................................................2-1
2.1 Connections..................................................................................................2-2
2.1.1 Connection to the SRZ............................................................................................2-3
2.1.2 Installation of termination resistor ...........................................................................2-6
2.2 Communication Setting ................................................................................2-9
2.2.1 Module address setting........................................................................................... 2-9
2.2.2 Communication speed, data bit configuration and protocol setting .......................2-12
2.2.3 Confirmation of communication parameter of the OPC-V606E side .....................2-13
Page
2.3 Start-up Procedures ...................................................................................2-15
2.4 Contrast Adjustment ...................................................................................2-16
2.5 Set the Number of Connection Modules.....................................................2-18
3. SCREEN DESCRIPTIONS ................................................3-1
3.1 Screen Configuration....................................................................................3-2
3.2 Basic Operations ..........................................................................................3-6
3.2.1 Data settings ...........................................................................................................3-6
3.2.2 Text editing ...........................................................................................................3-10
3.3 Start-up Screen ..........................................................................................3-14
3.4 Operation Menu Screen .............................................................................3-17
3.4.1 Calling procedure of the operation menu screen ..................................................3-17
3.4.2 Operation menu screen.........................................................................................3-18
3.5 Monitor Screen ...........................................................................................3-19
3.5.1 Calling procedure of the monitor screen ...............................................................3-19
3.5.2 Basic configuration of monitor screen ...................................................................3-21
3.5.3 TIO monitor screen ...............................................................................................3-23
3.5.4 TIO alarm monitor screen .....................................................................................3-25
3.5.5 DIO monitor screen............................................................................................... 3-26
3.5.6 Configuration monitor menu 1 screen ...................................................................3-27
3.5.7 Configuration monitor menu 2 screen ...................................................................3-30
3.6 Trend Graph Screen...................................................................................3-33
3.6.1 Calling procedure of the trend graph screen .........................................................3-33
3.6.2 Trend graph screen...............................................................................................3-33
3.6.3 CH select screen................................................................................................... 3-35
IMS01T08-E1 i-3
Page
3.7 Setting Screen ............................................................................................3-36
3.7.1 Calling procedure of the setting screen.................................................................3-36
3.7.2 TIO setting menu screen.......................................................................................3-38
3.7.3 Event setting menu screen....................................................................................3-39
3.7.4 PID setting menu screen.......................................................................................3-40
3.7.5 Other setting 1 menu screen.................................................................................3-41
3.7.6 Other setting 2 menu screen.................................................................................3-42
3.7.7 Basic configuration of setting screen ....................................................................3-43
3.7.8 Setting item list......................................................................................................3-44
3.8 Operation Mode Screen .............................................................................3-48
3.8.1 Calling procedure of the operation mode screen ..................................................3-48
3.8.2 Operation mode menu screen...............................................................................3-49
3.8.3 Basic configuration of operation mode screen ...................................................... 3-50
3.8.4 Operation mode item list .......................................................................................3-52
3.9 DO Setting Screen......................................................................................3-54
3.9.1 Calling procedure of the DO setting screen ..........................................................3-54
3.9.2 DO setting menu screen .......................................................................................3-54
3.9.3 Basic configuration of DO setting screen ..............................................................3-55
3.9.4 DO setting item list................................................................................................3-56
3.10 Initial Setting Screen.................................................................................3-57
3.10.1 Releasing procedure of the initial setting key protect.......................................... 3-57
3.10.2 Calling procedure of the initial setting screen......................................................3-59
3.10.3 Initial menu screen.............................................................................................. 3-63
3.10.4 Number of modules set screen ...........................................................................3-64
3.10.5 Clock set screen .................................................................................................3-65
3.10.6 Name setting menu screen .................................................................................3-66
3.10.7 Alarm message set screen..................................................................................3-67
3.10.8 TIO CH name set screen ....................................................................................3-68
3.10.9 Screen saver set screen .....................................................................................3-69
3.10.10 TIO controller initial menu screen .....................................................................3-70
3.10.11 Basic configuration of TIO controller initial screen ............................................ 3-71
3.10.12 TIO controller initial item list ..............................................................................3-73
3.10.13 DIO controller initial menu screen .....................................................................3-81
3.10.14 Basic configuration of DIO controller initial screen............................................ 3-82
3.10.15 DIO controller initial item list..............................................................................3-84
3.10.16 Password set screen......................................................................................... 3-88
i-4
3.11 Screen Setting Examples When Using DIO..............................................3-89
3.11.1 Example of using DI............................................................................................ 3-89
3.11.2 Example of using DO ..........................................................................................3-94
IMS01T08-E1

OUTLINE

1.1 Features ...........................................................................................1-2
1.2 Checking the Products......................................................................1-4
IMS01T08-E1 1-1
1. OUTLINE

1.1 Features

This instrument is the operation panel for module type controller SRZ. Through connection with the SRZ, various data monitoring and setting, operation and alarm monitoring, etc. can be carried out.
This manual describes the connection with the SRZ and screen operations of the OPC-V606E. For the mounting, power supply wiring and battery replacement of OPC-V606E, see the instruction manual of Hakko Electronics Co., Ltd.
URL: Web site: http://www.hakko-elec.co.jp/
Manual download: http://www.hakko-elec.co.jp/eng/download/index02.html
In addition, the Model code of the MONITOUCH V606e series of operation panels (made by Hakko Electronics Co., Ltd.) corresponding to our OPC-V606E operation panels is as listed below.
Model code correspondence list
Model code of RKC operation panel
Model code of MONITOUCH (Hakko Electronics Co., Ltd.)
Specifications
STN monochrome,
OPC-V606E-35/ V606eM20
320 × 240 dots, 5.7 inches, 24 V DC
System configuration example
Operation panel OPC-V606E
POWER
RS-485 (Modbus)
SYSTEM
F1
F2
F3
F4
F5
Temperature control
Module type controller SRZ
modules (Z-TIO)
Digital I/O module
(Z-DIO)
[Usable SRZ modules]
Temperature control module: Z-TIO-A (4-channel type), Z-TIO-B (2-channel type)
Digital I/O module: Z-DIO-A (Digital input: 8 channels, Digital output: 8 channels)
[Maximum number of connected SRZ modules]
The maximum number of SRZ modules (including Z-DIO modules) on the same communication line is 31.
Temperature control module (Z-TIO): 1 to 16 modules (Temperature control: 2 to 64 channels)
Digital I/O module (Z-DIO): 0 to 16 modules (Digital input: 0 to 128 channels,
Digital output: 0 to 128 channels)
1-2 IMS01T08-E1
)
r
When two or more SRZ units are connected
Operation panel OPC-V606E
POWER
RS-485 (Modbus
SYSTEM
F1
F2
F3
F4
F5
Module addr ess
Module address
Module type controller SRZ
0
1 2 3 4 5
Z-TIO module Z-DIO module
Internal communicati on line (RS-485)
Module type controller SRZ
6
7 8 9 10 11
Z-TIO module Z-DIO modul e
1.1 Features
16 17 18
19 20 21
Internal communicati on line (RS-485)
RS-485
Module type controller SRZ
Z-TIO: T emperat ure c ontrol module
Z-DIO: Digital I/O module
Module addr ess
RS-485
12
13 14 15 22 23
Z-TIO module Z-DIO modu le
Internal communicati on line (RS-485)
Termination resisto
[Usable SRZ modules]
Temperature control module: Z-TIO-A (4-channel type), Z-TIO-B (2-channel type)
Digital I/O module: Z-DIO-A (Digital input: 8 channels, Digital output: 8 channels)
[Maximum number of connected SRZ modules]
The maximum number of SRZ modules (including Z-DIO modules) on the same communication line is 31.
Temperature control module (Z-TIO): 1 to 16 modules (Temperature control: 2 to 64 channels)
Digital I/O module (Z-DIO): 0 to 16 modules (Digital input: 0 to 128 channels,
Digital output: 0 to 128 channels)
Easy operation using the transparent touch panel
By touching the transparent touch panel on the display of this operation panel OPC-V606E, operations such as changing the settings and switching the displays can be performed. Operations can be easily carried out using the sensation of conducting a dialog with the display.
Dustproof, Splashproof
The front OPC-V606E has a dustproof, splashproof construction equivalent to IP65 (IEC standards). (Only the front section of the OPC-V606E mounted on the control panel.)
IMS01T08-E1
1-3
1. OUTLINE

1.2 Checking the Products

Before using this product, check each of the following:
Model code Check that all of the items delivered are complete. Check that there are no scratch or breakage in external appearance (case, front panel, or terminal, etc).
If any of the products are missing, damaged, or if your manual is incomplete, please contact RKC sales office or the agent.
Model code
OPC – V606E – 3 5 /
(1) Display method
3: STN monochrome LCD (8-step gradation)
(2) Connected equipment
5: SRZ (Modbus protcol)
(3) Language
J: Japanese E: English
(1)(2) (3)
Accessories
Mounting brackets.........4
Operation panel OPC-V606E [For SRZ] Operation Manual (IMS01T08-E1)..........1
Peripheral equipment (Sold separately)
Cable for SRZ connection Type: V6-MLT
Used for the connection of the OPC-V606E and the SRZ.
Cable length: 3 m
8-pin
Protection sheet Package of 5 sheets Type: V606-GS
Protects the OPC-V606E surface.
SD/RD (Green)
SD/RD (Black)
+
SG (Red)
1-4 IMS01T08-E1

PREPARATIONS

2.1 Connections......................................................................................2-2
2.1.1 Connection to the SRZ .............................................................................2-3
2.1.2 Installation of termination resistor............................................................. 2-6
2.2 Communication Setting.....................................................................2-9
2.2.1 Module address setting .............................................................................2-9
2.2.2 Communication speed, data bit configuration and protocol setting..........2-12
2.2.3 Confirmation of communication parameter of the OPC-V606E side........2-13
2.3 Start-up Procedures........................................................................2-15
2.4 Contrast Adjustment .......................................................................2-16
2.5 Set the Number of Connection Modules .........................................2-18
IMS01T08-E1 2-1
2. PREPARATIONS

2.1 Connections

To prevent electric shock or instrument failure, turn off the power before connecting or disconnecting the instrument and peripheral equipment.
CAUTION
Connect connectors correctly in the right position. If it is forcibly pushed in with pins in the
wrong positions, the pins may be bent resulting in instrument failure.
When connecting or disconnecting the connectors, do not force it too far to right and left or
up and down, but move it on the straight. Otherwise, the connector pins may be bent, causing instrument failure.
When disconnecting a connector, hold it by the connector itself. Disconnecting connectors
by yanking on their cables can cause breakdowns.
To prevent malfunction, never touch the contact section of a connector with bare hands or
with hands soiled with oil or the like.
To prevent malfunction, connect cable connectors securely, then firmly tighten the connector
fastening screws.
To prevent damage to cables, do not bend cables over with excessive force.
If the instrument is easily affected by noise, use the ferrite core in the both ends of the
communication cable (nearest the connector).
WARNING
!
2-2 IMS01T08-E1
2.1 Connections

2.1.1 Connection to the SRZ

Use connection cable V6-MLT (Sold separately, Cable length: 3 m) to connect the OPC-V606E and the SRZ.
Operation panel OPC-V606E
(Left side view)
Connect to the [MJ1]
RS-485
Connection cable V6-MLT
Connect to the communication terminals
SRZ module communication terminals
RS-485
T/R(A)
T/R(B)
4
SG
Module type controller SRZ
53
Base part of
the module
SRZ module
Connection cable V6-MLT
SD/RD (Green)
SD/RD (Black)
+
SG (Red)
Bottom of the module
For removing the base of the SRZ module, see the Z-TIO Instruction Manual (IMS01T01-E).
IMS01T08-E1 2-3
2.1 Connections
Pin layout of connector (OPC-V606E)/Terminal configuration (SRZ)
Operation panel OPC-V606E (Left side view)
Base part of
the module
SRZ module
Bottom of the m odule
……………..
1
MJ1
RS-485
T/R(A)
8
T/R(B)
3
SG
53
4
Communication terminals
4
5
Signal details
OPC-V606E [MJ1] SRZ [Communication terminals]
Pin No. Signal name Symbol
1 RS-485
+SD/RD
send/receive data
2 RS-485
SD/RD
send/receive data
3 Unused
4 Unused
Terminal
No.
Signal name Symbol
3 RS-485
send/receive data
4 RS-485
send/receive data
5 Signal ground SG
5 Signal ground SG
6 Signal ground SG
7 Unused
8 Unused
T/R (A)
T/R (B)
2-4 IMS01T08-E1
Wiring contents
2.1 Connections
Module type controller SRZ
Operation panel OPC-V606E
+SD/RD
SD/RD
Unused
Unused
SG
SG
Unused
Unused
Modular connector
MJ1
Turns on a termination resistor setting DIP switches (No. 6) of OPC-V606E side modular connector [MJ1].
Recommended modular connector Modular connector for connect to operation panel OPC-V606E:
TM10P-88P (Manufactured by HIROSE ELECTRIC CO., LTD.)
For installation of termination resistor, see the 2.1.2 Installation of termination resistor (P. 2-6).
1
2
3
4
5
6
7
8
Shielded twisted
Pair wire
Connectied by the internal communication line
pair wire
R1: External termination
resistor (120 Ω 1/2 W)
Maximum number of connected SRZ module: 31 modules
Temperatur control module (Z-TIO): 1 to 16 modules Digital I/O module (Z-DIO): 0 to 16 modules
R1
T/R (A)
3
4
T/R (B)
5
SG
3
4
5
T/R (A)
T/R (B)
SG
  
IMS01T08-E1 2-5
2.1 Connections

2.1.2 Installation of termination resistor

Install terminating resistors to both ends of the RS-485 communication line.
Installation of termination resistor for SRZ
Mounting position
Connect a termination resistor between the communication terminals (No.3 and 4) of the module at the end of the communication line from the host computer.
Termination resistor (Example: 120 1/2 W)
T/R(A) T/R(B)
To operation panel OPC-V606E
When two or more module are connected
Module type controller SRZ
Internal communication line
(RS-485)
Operation
panel
OPC-V606E
RS-485
(Base)
34 5
Recommended tightening torque:
0.4 Nm (4 kgf・cm)
SG
Connect the termination resistor to this module.
Termination resistor
Continued on the next page.
2-6 IMS01T08-E1
r
When two or more SRZ units are connected
Operation
panel
OPC-V606E
RS-485
RS-485
RS-485
Module type controller SRZ
Z-TIO module Z-DIO module
Internal communication line (RS-485)
Module type controller SRZ
Z-TIO module Z-DIO module
Internal communication line (RS-485)
Module type controller SRZ
Z-TIO module
Internal communication line (RS-485)
Termination resisto
Z-DIO module
Connect the termination resistor to this module.
2.1 Connections
IMS01T08-E1 2-7
2.1 Connections
Installation of termination resistor for operation panel OPC-V606E
Set the termination resistor of modular connector [MJ1] with DIP switches No. 6.
Operation panel OPC-V606E (Rear)
CN1
MJ1
24VDC
DIP switch
ON
1 2 3 4 5 6 7 8
Switch No.7 and 8 must be always OFF. Do not set to ON.
Termination resistor of modular connector [MJ1]
OFF:
If the OPC-V606E is other than a termination when connected to the MJ1 modular connector using SRZ and RS-485.
ON:
If the OPC-V606E is a termination when connected to the MJ1 modular connector using SRZ and RS-485.
Factory set value: ON
Switch No.1 to 5 must be always OFF. Do not set to ON.
2-8 IMS01T08-E1
2. PREPARATIONS

2.2 Communication Setting

To prevent electric shock or instrument failure, always turn off the power
before setting the switch.
To prevent electric shock or instrument failure, never touch any section other
than those instructed in this manual.
WARNING
!
Set the communication parameter for communication between the operation panel OPC-V606E and the SRZ.

2.2.1 Module address setting

When using two or more modules, set the desired address to each module. Set the module address by address setting switches of front of module. For this setting, use a small blade screwdriver.
To avoid problems or malfunction, do not duplicate an address on the same communication line.
Set the module addresses in order from “0” without skipping any numbers. If a number is skipped, “no response” will occur.
Setting of “Address setting switch”
( ): Decimal number
RX/TX
Module type controller SRZ
0
1
(0)
(1)
Address setting switch
E
(14)F (15)
(2)
2
Setting range:
0 to F [0 to 15: Decimal numbers] (Factory set value: 0)
D
(13)
(0)
0
1
(1)
(14)
E
[Temperature control module (Z-TIO)]
Set address number from the “0” sequentially. The value obtained by adding “1” to the set address corresponds to the address used for the actual communication.
[Digital I/O module (Z-DIO)]
Set address number from the “0” sequentially. The value obtained by adding “17” to the set address corresponds to the for the actual communication.
address used
Maximum number of connected SRZ module: 31 modules
Temperatur control module (Z-TIO): 1 to 16 modules
Digital I/O module (Z-DIO): 0 to 16 modules
IMS01T08-E1 2-9
2.2 Communication Setting
Relation of module address and display channel number
Channel numbers displayed on the OPC-V606E operation panel screen are determined in order from the “0” module address number.
[Example 1: When constructed unit with the temperature control module of 4-channel type.]
Temperature control module (Z-TIO-A: 4-channel type)
Module type controller SRZ
Address number of module
Channel number of module
The channel number that is displayed on the screen
Screen
CH3
CH3
CH4
CH4
0
CH1
CH1
CH2
CH2
CH3
CH7
CH4
CH8
1
CH1
CH5
CH2
CH6
CH3
CH63
CH64
15
CH4
CH61
CH1
CH2
CH62
The number of channels displayed on the screen is in accordance with the OPC-V606E initial setting: “Number of modules set.” If “Number of modules set” is at “1” in the above system configuration, no data on and after CH5 is displayed.
For details of number of module setting, see the 2.5 Set the Number of Connection Modules (P. 2-18).
2-10 IMS01T08-E1
2.2 Communication Setting
[Example 2: When constructed unit with the temperature control module of 2-channel type and 4-channel type.]
Module type controller SRZ
Address number of module
Channel number of module
The channel number that is displayed on the screen
Screen
Temperature control module
(Z-TIO-B: 2-channel type)
0
CH1
CH1
CH3
CH2
CH7
CH2
Temperature control module
(Z-TIO-A: 4-channel type)
CH4
CH8
1
CH1
CH2
CH5
CH6
CH3
CH63
15
CH4
CH61
CH64
CH1
CH2
CH62
When the temperature control module of 2-channel type is used, the display corresponding to the CH3 and CH4 section becomes blank.
IMS01T08-E1 2-11
2.2 Communication Setting
p

2.2.2 Communication speed, data bit configuration and protocol setting

With the DIP switch which there is on the right side of SRZ module, select communication speed, data bit configuration and protocol. Always make the same communication settings on the OPC-V606E and SRZ. The data changes become valid when the power is turned on again or when changed to RUN with “RUN/STOP transfer” of operation mode.
When two or more modules are connected on the same line, turn each switch in the DIP switches of all of the modules to the same position. Otherwise the module may fail or malfunction.
[Factory set value of operation panel OPC-V606E]
Communication speed (baud rate) 19200 bps
Data 8-bit, without parity, stop 1-bit
Modbus protocol
See 2.2.3 Confirmation of communication parameter of the OPC-V606E side (P. 2-13).
SRZ module main frame
Z-TIO module Z-DIO module
Right side view
[S
etting contents]
1 2 3 4 5 6 7 8
OFF ON OFF OFF ON ON OFF OFF
1 2 Communication speed
OFF OFF 4800 bps
ON OFF 9600 bps
OFF ON 19200 bps
ON ON 38400 bps
Factory set value: 19200 bps
3 4 5 Data bit configuration
OFF OFF OFF Data 7-bit, without parity, Stop 1-bit * OFF OFF ON Data 7-bit, Even parity, Stop 1-bit * OFF ON ON Data 7-bit, Odd parity, Stop 1-bit * OFF OFF ON Data 8-bit, without parity, Stop 1-bit OFF ON ON Data 8-bit, Even parity, Stop 1-bit
ON ON ON Data 8-bit, Odd parity, Stop 1-bit
* When the Modbus communication protocol is selected, this setting becomes invalid.
Factory set value: Data 8-bit, without parity, Stop 1-bit
6 7 Protocol
OFF OFF RKC communication
ON OFF Modbus
Factory set value: RKC communication
Switch No. 8: OFF fixed (Do not change this one)
DIP switch
1234567
8
OFF
Set to 19200 bps
Set to Modbus
ON
ON
Set to data 8-bit, without parity and sto
1-bit
2-12 IMS01T08-E1
2.2 Communication Setting

2.2.3 Confirmation of communication parameter of the OPC-V606E side

The parameter for communication between the operation panel OPC-V606E and SRZ on the operation panel side can be checked on the “Extension Prog. Info.” screen.
< Extension Prog. Info. screen >
Extension Prog. Info.
Temp. CTRL Drv
VER. 1.100
RKC SR-Mini/CB
Temp. CTRLComm. Param.
Signal level:
RS485 Baud Rate: 19200 Data Length: 8 Stop Bit: 1 Parity: None Retry Time: 3 Time-out: 300msec Send Delay: 6msec Return Time: 10sec
Main Menu
Main Menu
Touching this key change to the “Main Menu” screen.
Temperature control communication parameter
The parameter for communication between the operation panel and SRZ is displayed but cannot be set.
The parameter for communication on the OPC-V606E side is changed by the panel editor V-SFTE. For the panel editor V-SFTE, please contact RKC sales office or the agent.
Operation procedures
1. Press and hold the [SYSTEM] switch, and press the [F5] switch at the same time. “Main Menu” screen is displayed. The “Main Menu” screen can be changed on any screen.
SYSTEM switch
SYSTEM
F1
F2
F3
F4
Main Menu
F5
F5 switch
Continued on the next page.
IMS01T08-E1 2-13
2.2 Communication Setting
Continued from the previous page.
2. Touch the [Extension] key. “Extension Prog. Info.” screen is displayed.
enu
Main M
Extension
Exte nsion
3. After the information is checked, touch the [Main Menu] key to call out the “Main Menu” screen.
Extension Prog. Info.
Extension Prog. Info.
Temp. CTRL Drv
VER. 1.100
Temp. CTRL Drv
RKC SR-Mini/CB
VER. 1.100
RKC SR-Mini/CB
Temp. CTRLComm. Param.
Main Men u
Main Menu
Signal level:
Temp. CTRLComm. Param .
RS485
Signal level:
Baud Rate: 19200
RS485
Data Length: 8
Baud Rate: 19200
Stop Bit: 1
Data Length: 8
Parity: None Retry Time: 3
Stop Bit: 1
Time-out : 300msec
Parity: None
Send Delay: 6msec
Retry Time: 3
Return Time: 10sec
Time-out: 300ms ec Send Delay: 6msec Return Time: 10sec
Main Menu
4. Press the [SYSTEM] switch with the “Main Menu” screen being displayed. The menu is displayed at the side of the function switch.
S Y
SYSTEM
S
F1
M O D
F2
E
CT
F3
F4
Menu
F5
5. Press the [F1] switch with the menu being displayed. Pressing the [F1] switch displays the “Opening” screen after an error is checked and then displays the “TIO Monitor” screen.
S Y
SYSTEM
S
F1
M O D E
CT
F2
F3
The menu disappears after a certain lapse of time. If it disappears, press the [SYSTEM] switch again.
F4
Menu
F5
2-14 IMS01T08-E1

2.3 Start-up Procedures

Check prior to power on
Check the following items before turning on the power to the operation panel OPC-V606E.
communication setting of
Check the
mounting and wiring
Check the connections
Check the
termination resistor
Check the
SRZ
Confirms the mounting and wiring.
See the instruction manual of Hakko Electronics Co., Ltd.
Connections conform to 2.1 Connections (P. 2-2).
Termination resistor setting conforms to 2.1.2 Installation of termination resistor (P. 2-6).
Communication setting conforms to 2.2 Communication Setting (P. 2-9).
Power on
First, turn on the power for module type controller SRZ, then for operation panel OPC-V606E.
Setting after power on
2. PREPARATIONS
Set the number of connection
Power on
Contrast adjustment
modules
Operations
If you changed the SRZ initial data in SRZ loader communication, turn off the power of the OPC-V606E and then turn it back on (power reset). The initial data will be effective after the power reset.
Adjust the contrast of the screen display.
For contrast adjustment, see the 2.4 Contrast Adjustment (P. 2-16).
Set the number of the SRZ modules connected to an operation panel.
For the number of module connection, see the 2.5 Set the Number of Connection Modules (P. 2-18).
IMS01T08-E1 2-15
2. PREPARATIONS

2.4 Contrast Adjustment

The contrast adjustment can be set with the function switches.
Operation procedures
1. Press and hold the [SYSTEM] switch, and press the [F5] switch at the same time. “Main Menu” screen is displayed. The “Main Menu” screen can be changed on any screen.
SYSTEM switch
SYSTEM
F1
F2
Main Menu
F3
F4
F5
F5 switch
Continued on the next page.
2-16 IMS01T08-E1
2.4 Contrast Adjustment
Continued from the previous page.
2. Press the [SYSTEM] switch with the “Main Menu” screen being displayed. The menu is displayed at the side of the function switch.
F1: Mode
Main menu mode ends.
S Y S
M O
D E
CT
CT
CT
B K L T
SYSTEM
F1
F2
F3
F4
F5
F2: Contrast adjustment (dark)
This switch adjusts the contrast of LCD. When the [F2] switch is pressed once, the LCD color becomes dark. If this switch is held down for 1 second, the LCD color changes rapidly into darkness.
F3: Contrast adjustment (intermediate)
This switch adjusts the contrast of LCD. When the [F3] switch is pressed once, the LCD color becomes intermediate.
F4: Contrast adjustment (light)
This switch adjusts the contrast of LCD. When the [F4] switch is pressed once, the LCD color becomes light. If this switch is held down for 1 second, the LCD color changes rapidly into lightness.
F5: Invalidity (Ignored)
Menu
3. Press the [F2] to [F4] switches with the menu being displayed. The contrast adjustment can be set.
4. Press the [F1] switch with the menu being displayed.
Pressing the [F1] switch displays the “Opening” screen after an error is checked and then displays the “TIO Monitor” screen.
S Y
SYSTEM
S
F1
M O D
E
CT
Menu
F2
F3
F4
F5
The menu disappears after a certain lapse of time. If it disappears, press the [SYSTEM] switch again.
IMS01T08-E1
2-17
2. PREPARATIONS

2.5 Set the Number of Connection Modules

The number of the module connection sets it after releasing an initial setting the key protection.
Operation procedures
1. Touch the [Menu] key on the “TIO Monitor” screen, to switch to the “Operation Menu” screen.
2. Touch the [Initial Setting] key on the “Operation Menu” screen, to switch to the “Password
confirmation” screen.
3. Enter the password “0000” and touch the [ENT] key. If the password is correct, the screen will change to the “Initial Menu” screen.
The password in shipment becomes “0000.” When changes the password, see the 3.10.16 Password set screen (P. 3-88).
Continued on the next page.
2-18 IMS01T08-E1
2.5 Set the Number of Connection Modules
Continued from the previous page.
4. Touch the [Number of modules set] key on the “Initial Menu” screen, to switch to the “Number of modules set” screen.
5. Set the number of the connection of the Z-TIO modules and Z-DIO modules.
Set the number of the SRZ modules connected to an operation panel OPC-V606E.
Setting range: Number of Z-TIO modules: 1 to 16 (Factory set value: 1) Number of Z-DIO modules: 0 to 16 (Factory set value: 0)
Up to 31 modules including both Z-TIO module and Z-DIO module.
6. When the number of connecting modules is changed, always reset the OPC-V606E in accordance with any of the following procedures. The number of modules thus changed becomes valid after the OPC-V606E is reset.
Reset with power
Turn off the power once and then turn it on again.
Reset with switch operations
1. Press and hold the [SYSTEM] switch, and press the [F5] switch at the same time.
2.
3. Press the [F1] switch with the menu being displayed.
IMS01T08-E1
“Main Menu” screen is displayed. The “Main Menu” screen can be changed on any screen. Press the [SYSTEM] switch with the “Main Menu” screen being displayed. The menu is
displayed at the side of the function switch.
Pressing the [F1] switch displays the “Opening” screen after an error is checked and then displays the “TIO Monitor” screen.
2-19
MEMO
2-20 IMS01T08-E1
Loading...
+ 104 hidden pages