Rkc MA901, MA900 User Manual

Multi-point Digital Controller
MA900/MA901
Initial Setting Manual
RKC INSTRUMENT INC.
®
IMR01H03-E4
!"Modbus is a registered trademark of Schneider Electric. !"Company names and product names used in this manual are the trademarks or registered trademarks of
the respective companies.
All Rights Reserved, Copyright  2001, RKC INSTRUMENT INC.
Thank you for purchasing this RKC instrument. In order to achieve maximum performance and ensure proper operation of your new instrument, carefully read all the instructions in this manual. Please place this manual in a convenient location for easy reference.
SYMBOLS

WARNING

CAUTION
!
: This mark indicates precautions that must be taken if there is danger of electric
shock, fire, etc., which could result in loss of life or injury.
: This mark indicates that if these precautions and operating procedures are not
taken, damage to the instrument may result.
: This mark indicates that all precautions should be taken for safe usage. : This mark indicates important information on installation, handling and operating
procedures.
: This mark indicates supplemental information on installation, handling and
operating procedures.
: This mark indicates where additional information may be located.
WARNING
!
An external protection device must be installed if failure of this instrument
!"
could result in damage to the instrument, equipment or injury to personnel. All wiring must be completed before power is turned on to prevent electric
!"
shock, fire or damage to instrument and equipment. This instrument must be used in accordance with the speci fications to pr ev ent
!"
fire or damage to instrument and equipment. This instrument is not intended for use in locations subject to flammable or
!"
explosive gases. Do not touch high-voltage connections such as power supply terminals, etc.
!"
to avoid electric shock. RKC is not responsible if this instrument is repaired, modified or
!"
disassembled by other than factory-approved personnel. Malfunction can occur and warranty is void under these conditions.
IMR01H03-E4
i-1

CAUTION

This is a Class A instrument. In a domestic environment, this instrument may cause radio
!
interference, in which case the user may be required to take adequate measures. This instrument is protected from electric shock by reinforced insulation. Provide
!
reinforced insulation between the wire for the input signal and the wires for instrument power supply, source of power and loads.
Be sure to provide an appropriate surge contr ol cir c uit r espectively for the following:
!
- If input/output or signal lines within the building are longer than 30 mete r s.
- If input/output or signal lines leave the building, regardless the length. This instrument is designed for installat ion in an enclosed instrument ation panel. All high-
!
voltage connections such as power supply terminals must be enclosed in the instrumentation panel to avoid electric shock by operating personnel.
All precautions described in this manual should be taken to avoid damage to the
!
instrument or equipment. All wiring must be in accordance with local codes and regulations.
!
All wiring must be completed before power is turned on to prevent electric shock,
!
instrument failure, or incor r ect action. The power must be turned off before repairing work for input break and output failure including replacement of sensor, contactor or SSR, and all wiring must be completed before power is turned on again.
To prevent instrument damage or f ailure, protect t he power line and the input/output lines
!
from high currents with a protect ion device such as f use, circuit breaker, etc. Prevent metal fragment s or lead wire scraps from falling inside instrum ent case to avoid
!
electric shock, fire or malfunction. Tighten each terminal screw t o the specified torq ue found in the manual to avoid electric
!
shock, fire or malfunction. For proper operation of this instrument, provide adequate ventilation for heat dispensation.
!
Do not connect wires to unused terminals as this will interf er e with proper operation of the
!
instrument. Turn off the power supply befor e cleaning the instrument.
!
Do not use a volatile solvent such as paint thinner to clean the inst rum ent. Def ormat ion or
!
discoloration will occur. Use a soft, dry cloth to rem ove stains from the instrument. To avoid damage to instrument display, do not rub with an abrasive material or push f ront
!
panel with a hard object. Do not connect modular connectors to telephone line.
!
NOTICE
!
This manual is written for RKC service engineers or qualified technicians. This manual is also prepared especially for readers who already have a fundamental knowledge of electricity, control, computer and communication.
!
The figures, diagrams and numeric values used in this manual are only for purpose of illustration.
!
RKC is not responsible for any damage or injury that is caused as a result of using this instrument, instrument failure or indirect damage.
!
Periodic maintenance is required for safe and proper operation of this instrument. Some components have a limited service life, or characteristics that change over time.
!
Every effort has been made to ensure accuracy of all information contained herein. RKC makes no warranty expressed or implied, with respect to the accuracy of the information. The information in this manual is subject to change without prior notice.
!
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored, processed or retrieved through any mechanical, electronic, optical or other means without prior written approval from RKC.
i-2
IMR01H03-E4

CONTENTS

Page
1. PROCEDURE FOR INITIALIZATION....................................1
1. 1 Transfer to Engineering Mode.........................................................................2
1.2 Procedure for Parameter Setting.....................................................................4
1.3 End of Engineering Mode................................................................................9
2. DETAILS OF PARAMETER SETTING ...............................10
2.1 Attention Items in Setting...............................................................................12
2.2 F10 Display function......................................................................................17
2.3 F21 Input Specification..................................................................................18
2.4 F22 Current Transformer (CT) Input Specification ........................................20
2.5 F24 Contact Input Specification.....................................................................22
2.6 F31 Output Function......................................................................................24
2.7 F32 Alarm Output Function............................................................................26
2.8 F41 Alarm 1 Function/F42 Alarm 2 Function/F43 Alarm 3 Function..............27
2.9 F51 Control Action.........................................................................................29
2.10 F61 Communication Function......................................................................30
2.11 F91 Displayed for Maintenance Information................................................31
3. INITIALIZE COMMUNICATION DATA................................32
3.1 RKC Communication Protocol.......................................................................32
3.2 Modbus Communication Protocol..................................................................42
3.2.1 Communication data list ...................................................................................42
3.2.2 Data map..........................................................................................................49
4. INPUT RANGE TABLES.....................................................55
IMR01H03-E4
i-3
MEMO
i-4
IMR01H03-E4

1. PROCEDURE FOR INITIALIZATION

Initialization is to set parameters relating to instrument specifications (input type, input range, alarm type, etc.). Engineering mode that can do this setting.
Initialization flowchart
!"
Power ON
1.1 Transfer to Engineering Mode.
Change from RUN to STOP
See
Unlock the engineering mode
Setting the initial parameter
Lock the engineering mode
End of initialization
1.1 Transfer to Engineering Mode.
See
1.2 Procedure for Paramet er Setting
See
2. DETAILS OF PARAMETER SETTING
See
1.3 End of Engineering Mode
See
.
.
.
IMR01H03-E4
1
1. PROCEDURE FOR INITIALIZATION

1.1 Transfer to Engineering Mode

MA900 is used in the below figures for explanation, but the same setting procedures also apply to MA901.
The parameter of engineering mode can be changed only in the control STOP state.
1. Press the <R/S key with states of the PV/SV monitor mode for 1 second, to change the STOP
from RUN.
PV
CH
SV
AREA
SET
CH
MA900
R/S
STOP display
If set to the STOP state (dSTP) by the contact input, no parameters in Engineering mode can be changed. They can be changed in case of the following.
The instrument changed the STOP state (KSTP) by the key operation.
The instrument changed the STOP state by both the key operation and contact input
operation.
For the RUN/STOP transfer, see the Instruction Manual (IMR01H01-E
####
)
2. Press the <R/S key while pressing the SET key with the PV/SV monitor mode change the
instrument to setup setting mode.
For the setup setting mode, see Instruction Manual (IMR01H01-E
####
).
3. Press the SET key several times to change to the lock level 2 display (LCK2).
4. Press the <R/S key to light brightly the hundreds digit on the SV display.
CH
PV
SV
AREA
SET
CH
MA900
R/S
Lock level 2 display
2
IMR01H03-E4
1. PROCEDURE FOR INITIALIZATION
5. Press the UP key to change 0 to 1 in the hundreds digit.
CH
PV
AREA
SV
Set value 0000: Lock
0100: Unlock
SET
CH
MA900
R/S
Lock level 2 display
6. Press the SET key to unlock the engineering mode. The display changes to the first parameter in
setup setting mode.
AREA
PV
CH
SV
SET
CH
MA900
R/S
AREA
PV
CH
SV
SET
CH
MA900
R/S
Lock level 2 display Autotuning display
7. Press the <R/S key for 2 seconds while pressing the SET key to change the engineering mode.
The display changes to the function block F10.
AREA
CH
PV
SV
SET
CH
MA900
R/S
AREA
CH
PV
SV
SET
CH
MA900
R/S
Autotuni ng d isplay
Function block F10 display
Engineering mode
IMR01H03-E4
3
1. PROCEDURE FOR INITIALIZATION

1.2 Procedure for Parameter Setting

Flowchart of displaying parameter items
!"
!"
!"!"
Display flowcharts in engineering mode are shown in the following.
[ : Press the SET key : Press the UP or DOWN key]
STOP display selection
PV
SV
(F10.)
(SPCH)
Return to the
F10
Input type selection
(F21.)
(F22.)
(F24.)
(F31.) (LGo1) (LGo2)
(InP) (UnIT) (PGdP) (SLH) (SLL)
CT ratio 1 selection
(CTr1)
Contact input logic selection
(dlSL)
Control output logic selection 1
Alarm output logic selection
Display unit selection
CT ratio 2 selection
(CTr2)
Return to the
Control output logic selection 2
F24
.
Decimal point position setting
Return to the
Return to the
F22
F31
.
.
Setting limiter (high limit) setting
Setting limiter (low limit) setting
Return to the
F21
Any parameter whose channel number is displayed can be set for each channel. (Check the channel number on the
channel display of instrument.) All of the channels can be simultaneously s et as the same value.
All the setting item is displayed regard less of the contents of the instrument specification.
.
A B
4
(F32.)
(F41.)
Return to the
(LGA)
Alarm type selectionAlarm 1
(AS1) (AHo1) (AH1) (ALT1) (AEo1)
Alarm hold action selection
F32
.
Alarm differential gap setting
Alarm timer setting
Action selection at input error
Return to the
.
F41
IMR01H03-E4
1. PROCEDURE FOR INITIALIZATION
A
(F42.) (AS2)
(F43.) (AS3)
(F61.) (CMPS)
B
Alarm 2
Alarm 3
Alarm type selection
Alarm type selection
Control action type selection
(oS) (oH)(F51.)
Communication protocol selection
ROM version display
Alarm hold action selection
(AHo2)
Alarm hold action selection
(AHo3)
ON/OFF action differential gap setting
RUN/STOP transfer logic selection
(CMLG)
Integrated operating time display (Upper 3 digits)
Alarm differential gap setting
(AH2)
Alarm differential gap setting
(AH3)
Return to the
Return to the
F51
F61
Integrated operating time display (Lower 4 digits)
Alarm timer setting
(ALT2)
Alarm timer setting
(ALT3)
.
.
Holding peak ambient temperature display
Action selection at input error
(AEo2)
Action selection at input error
(AEo3)
Return to the
.
F42
Return to the
.
F43
(F91.) ( E261) (WTH)
(WTL) (TCJ)
Return to the
F91
.
IMR01H03-E4
5
1. PROCEDURE FOR INITIALIZATION
!"
!"Example of changing the setting
!"!"
As setting procedure example, show procedure at setting with each channel (Usual setting) and channel common (Batch setting).
MA900 is used in the below figures for explanation, but the same setting procedures also apply to MA901.
Example 1:
The following procedure is for changing the CH1 input type from “K” to “J.” (Usual setting)
1. Press the UP key to change the display to F21.
PV
CH
SV
AREA
SET
CH
MA900
R/S
Function block display
2. Press the SET key to change to input type selection (InP).
PV
CH
SV
AREA
SET
CH
MA900
Input type selection
R/S
3. Press the UP key to enter 1 in the least significant digit of the set value (SV) display.
PV
CH
SV
AREA
SET
CH
MA900
Input type selection
6
R/S
IMR01H03-E4
1. PROCEDURE FOR INITIALIZATION
4. Press the SET key to register the value thus set. The display changes to the next parameter.
AREA
CH
PV
SV
SET
CH
MA900
R/S
AREA
CH
PV
SV
SET
CH
MA900
R/S
Display unit selection Input type selection
Example 2:
The following procedure is for changing all channels of the input type from “K” to “J.” (Batch setting)
1. Press the UP key to change the display to F21.
PV
CH
SV
AREA
SET
CH
MA900
Function block display
R/S
2. Press the SET key to change to input type selection (InP).
PV
CH
SV
AREA
SET
CH
MA900
Input type selection
R/S
IMR01H03-E4
7
1. PROCEDURE FOR INITIALIZATION
3. Press the CH key several times. Display the character A on th e CH d isp lay and “ ----” on the SV
display. The character A indicates that the batch setting.
PV
CH
SV
AREA
SET
CH
MA900
R/S
Input type selection
Every time the CH key is pressed, the channel number changes as follows.
4. Press the UP key several times to enter 1 in the least significant digit of the set value (SV)
display.
PV
CH
SV
AREA
SET
CH
MA900
Input type selection
R/S
5. Press the SET key to register the value thus set. The display changes to the next parameter.
Press the CH key to return to the usual setting from the batch setting.
CH
PV
AREA
SV
SET
CH
MA900
R/S
Input type selection
CH
PV
AREA
SV
SET
CH
MA900
R/S
Display unit selection
(Batch setting)
CH
PV
AREA
SV
SET
CH
MA900
R/S
Display unit selection
(Usual setting)
If the selected parameter corresponds to the setting item in common to all channels, the simultaneous setting state returns to the normal setting state.
8
IMR01H03-E4
1. PROCEDURE FOR INITIALIZATION

1.3 End of Engineering Mode

MA900 is used in the above figures for explanation, but the same setting procedures also apply to MA901.
##
1. Transfer to function block symbol display (F
2. Press the <R/S key for 2 seconds while pressing the SET key to change to the PV/SV monitor
mode from the engineering mode.
3. Press the <R/S key while pressing the SET key with the PV/SV monitor mode change the
instrument to setup setting mode.
4. Press the SET key several times to change to the lock level 2 display (LCK2).
5. Press the <R/S key to light brightly the hundreds digit on the SV display.
) after each parameter is set.
6. Press the DOWN key to change 1 to 0 in the hundreds digit.
PV
AREA
CH
SV
Set value
0000:Lock
0100: Unlock
SET
CH
MA900
Lock lev el 2 display
R/S
7. Press the SET key to lock the engineering mode. The display changes to the first parameter in
setup setting mode.
PV
AREA
CH
SV
SET
CH
MA900
R/S
AREA
PV
CH
SV
SET
CH
MA900
R/S
Lock level 2 display
Autotuning display
8. Press the <R/S key while pressing the SET key to change to the PV/SV monitor mode from the
setup setting mode. Thus, the initialization ends.
IMR01H03-E4
9

2. DETAILS OF PARAMETER SETTING

!"Parameter list
Function block Parameter Page
Display function STOP display selection (SPCH) P. 17
(F10.)
(F21.)
Input specification
Input type selection (InP) P. 18
Display unit selection (UnIT)
Decimal point position selection (PGdP) P. 19
(F22.)
(F24.)
(F31.)
(F32.)
(F41.)
Setting limiter (high limit)
(SLH)
setting Setting limiter (low limit)
(SLL)
setting
Current
CT ratio 1 selection (CTr1) P. 20 transformer (CT) input
CT ratio 2 selection (CTr2) specification Contact input
Contact input logic selection (dISL) P. 22 specification
Output function Control output logic selection 1 (LGo1) P. 24
(MA900)
Control output logic selection 2 (LGo2) P. 25
(MA901)
Alarm output
Alarm output logic selection (LGA) P. 26 function
Alarm 1
Alarm 1 type selection (AS1) P. 27 function
Alarm 1 hold action selection (AHo1)
Alarm 1 differential gap setting (AH1) P.28
10
Alarm 1 timer setting (ALT1)
Alarm 1 action selection at
(AEo1) P. 29
input error
Continued on the next page.
IMR01H03-E4
Continued from the previous page.
Function block Parameter Page
2. DETAILS OF PARAMETER SETTING
(F42.)
(F43.)
(F51.)
(F61.)
(F91.)
Alarm 2
Alarm 2 type selection (AS2) P. 27 function
Alarm 2 hold action selection (AHo2)
Alarm 2 differential gap setting (AH2) P. 28
Alarm 2 timer setting (ALT2)
Alarm 2 action selection at
(AEo2) P. 29
input error Alarm 3
Alarm 3 type selection (AS3) P. 27 function
Alarm 3 hold action selection (AHo3)
Alarm 3 differential gap setting (AH3) P. 28
Alarm 3 timer setting (ALT3)
Alarm 3 action selection at
(AEo3) P. 29
input error Control action Control action type selection (oS1) P. 29
ON/OFF action differential gap
(oH)
setting Communication function
Communication protocol
selection
RUN/STOP transfer logic
(CMPS) P. 30
(CMLG)
selection Displayed for
ROM version display (E261) P. 31 maintenance information Integrated operating time
(WTH) (Upper 3 digits) display Integrated operating time
(WTL) (Lower 4 digits) display Holding peak ambient
(TCJ) temperature display
IMR01H03-E4
11
2. DETAILS OF PARAMETER SETTING

2.1 Attention Items in Setting

If any of the following parameter is changed, the relevant set value is initialized or is automatically converted.
Before changing the set values, always record all of them (SV setting & CT monitor mode, setup setting mode, parameter setting mode and engineering mode).
After changing the set values, always check all of them (SV setting & CT monitor mode, setup setting mode, parameter setting mode and engineering mode).
When changed parameter of input type selection or engineering unit setting
!"
!"
!"!"
When change a input type and unit, all the set value of a list shown below is initialized. Set it in value to use once again.
Mode Description Default value
TC input RTD input Voltage input
Decimal point position 0
1
1
2
Setting limiter [high limit] Maximum settable value 100.0 % Setting limiter [low limit] 0.0 % Alarm 1 hold action
0 (Without alarm hold action)
Alarm 1 differential gap 2 °C [°F] 2.0 °C [°F] 0.2 % of span Alarm 1 action at input error 0 (Without action at input error)
Engineering Alarm 2 hold action 0 (Without alarm hold action) mode Alarm 2 differential gap 2 °C [°F] 2.0 °C [°F] 0.2 % of span
Alarm 2 action at input error 0 (Without action at input error) Alarm 3 hold action 0 (Without alarm hold action) Alarm 3 differential gap 2 °C [°F] 2.0 °C [°F] 0.2 % of span Alarm 3 action at input error 0 (Without action at input error) ON/OFF action differential gap 2 °C [°F] 2.0 °C [°F] 0.2 % of span Heater break alarm 1 OFF
Setup setting Heater break alarm 2
3
OFF
mode PV bias 0 °C [°F] 0.0 °C [°F] 0.0 %
Digital filter OFF
1
0: No digit below decimal point
2
1: 1 digit below decimal point
3
In case of MA901, this item is not provided.
12
Continued on the next page.
IMR01H03-E4
2. DETAILS OF PARAMETER SETTING
Continued from the previous page.
Mode Description Default value
TC input RTD input Voltage input
Control loop break alarm 8.0 minutes Control loop break alarm
0 °C [°F] 0.0 °C [°F] 0.0 %
deadband Alarm 1 50 °C [°F] 50.0 °C [°F] 5.0 % of span
Alarm 2
Parameter Alarm 3 setting mode Heat-side proportional band 30 °C [°F] 30.0 °C [°F] 3.0 % of span
Integral time 240 seconds Derivative time 60 seconds Anti-reset windup 100 % Cool-side proportional band * 100 % of heat-side proportional band Overlap/deadband * 0 °C [°F] 0.0 °C [°F] 0.0 % Setting changing rate limiter OFF
SV setting &
Set value (SV) 0 °C [°F] 0.0 °C [°F] 0.0 %
CT monitor mode
* In case of MA901, these items are not provided.
IMR01H03-E4
13
2. DETAILS OF PARAMETER SETTING
When changed parameter of decimal point position setting
!"
!"
!"!"
When change a decimal point position, it is converted into about set value of a list shown below automatically. However, the set value may change as a result of changing the position of the decimal point. Therefore in that case, re-set it to the value to be used.
Mode Description
Setting limiter [high limit] Setting limiter [low limit]
Engineering mode Alarm 1 differential gap
Alarm 2 differential gap Alarm 3 differential gap ON/OFF action differential gap
Setup setting mode PV bias
Control loop break alarm deadband Alarm 1 Alarm 2
Parameter setting mode Alarm 3
Heat-side proportional band Overlap/deadband * Setting changing rate limiter
SV setting & CT monitor mode Set value (SV)
* In case of MA901, this item is not provided.
Example and caution of automatic conversion
Decimal point location moves in accordance with it when increases decimal point location.
Example: When the position of the decimal point changed from 0 to 1 with SLH set to 800 °C.
(Changed from 800 to 800.0)
(SLH)(SLH)
If the setting range is not between 1999 and +9999 regardless of the position of the decimal point, it is limited by the range from 1999 to +9999.
Example: Suppose set SLH is 1372 °C, if change decimal point position from 0 to 1.
SLH becomes 999.9 as it exceeds the setting range.
(SLH)(SLH)
14
Continued on the next page.
IMR01H03-E4
2. DETAILS OF PARAMETER SETTING
Continued from the previous page.
If the number of digits below the decimal point is changed in the decreasing direction, the decreased number of digits is omitted.
Example: Suppose set SLH is 99.99, if change decimal point position from 0 to 2.
The figures below the decimal point are omitted, and as a result SLH becomes 99.
(SLH) (SLH)
In the above example, it the position of the decimal point is returned to 2 from 0, SLH becomes 99.00.
Set SLL and SLH so that SLL may not be equal to SLH when the position of the decimal point is changed. Otherwise malfunction may result.
Example: When the position of the decimal point is changed to 0 at SLL=999.1 and SLH=999.9
(SLL) (SLH) (SLL)
When changed parameter of setting limiter [high limit/low limit]
!"
!"
!"!"
(SLH)
When change setting limiter [high limit/low limit], all the set value of a list shown below is initialized. Set it in value to use once again. However no change is made if the set value is within the range changed.
Mode Description
Alarm 1 differential gap
Engineering mode Alarm 2 differential gap
Alarm 3 differential gap ON/OFF action differential gap
Setup setting mode PV bias
Control loop break alarm deadband Alarm 1 Alarm 2
Parameter setting mode Alarm 3
Heat-side proportional band Overlap/deadband * Setting change rate limiter
SV setting & CT monitor mode Set value (SV)
* In case of MA901, this item is not provided.
Example: For temperature input, voltage/current inputs If the setting is made so that the span becomes narrower, there may be a case where the related set value becomes smaller or 0.
IMR01H03-E4
15
2. DETAILS OF PARAMETER SETTING
When changed parameter of alarm type selection
!"
!"
!"!"
When change alarm 1 type and alarm 2 type, all the set value of a list shown below is initialized. Set it in value to use once again.
Mode Description Default value
TC input RTD input Voltage input
Alarm 1 hold action 0 (Without alarm hold action) Alarm 1 differential gap 2 °C [°F] 2.0 °C [°F] 0.2 % of span Alarm 1 action at input error 0 (Without action at input error) Alarm 2 hold action 0 (Without alarm hold action)
Engineering Alarm 2 differential gap 2 °C [°F] 2.0 °C [°F] 0.2 % of span mode Alarm 2 action at input error 0 (Without action at input error)
Alarm 3 hold action 0 (Without alarm hold action) Alarm 3 differential gap 2 °C [°F] 2.0 °C [°F] 0.2 % of span
Alarm 3 action at input error 0 (Without action at input error) Setup setting Heater break alarm 1 OFF mode Heater break alarm 2 * OFF
Control loop break alarm 8.0 minutes
Control loop break alarm Parameter setting mode Alarm 1 50 °C [°F] 50.0 °C [°F] 5.0 % of span
deadband
Alarm 2
Alarm 3
0 °C [°F] 0.0 °C [°F] 0.0 %
* In case of MA901, this item is not provided.
16
IMR01H03-E4
2. DETAILS OF PARAMETER SETTING

2.2 F10 Display function

(1) STOP display selection (SPCH)
Details of setting Factory set value
0000 STOP is displayed on the PV display unit. (TYPE 1) 0000 0001 STOP is displayed on the SV display unit. (TYPE 2)
Displays in the STOP mode become as follows.
TYPE 1 (SPCH=0000)
TYPE 2 (SPCH=0001)
PV
SV
PV
SV
(KSTP)
(KSTP)
PV
SV
PV
SV
(dSTP)
(dSTP)
(SToP)
PV
SV
PV
SV
(SToP)
IMR01H03-E4
17
2. DETAILS OF PARAMETER SETTING

2.3 F21 Input Specification

The setting items (InP, UnIT, PGdP, SLH and SLL) in the function block F21 are set for each channel. In addition, they can be set simultaneously for all channels.
(1) Input type selection (InP)
Details of setting Factory set value
0000 K Factory set value 0001 J varies depending on 0002 R the input type. 0003 S 0004 B 0005 E Thermocouple * 0006 N (TC) 0007 T 0008 W5Re/W26Re 0009 PL II 0010 U 0011 L 0012 Pt100 RTD * 0013 JPt100 0014 0 to 5 V DC Voltage * 0015 1 to 5 V DC 0016 0 to 10 V DC
* Input type cannot be changed because the hardware is different.
See 2.1 Attention Items in Setting (P. 12).
(2) Display unit selection (UnIT)
Details of setting Factory set value
0000 °C 0000 0001 °F
The invalidity in case of the voltage inputs. See 2.1 Attention Items in Setting (P. 12).
18
IMR01H03-E4
2. DETAILS OF PARAMETER SETTING
(3) Decimal point position setting (PGdP)
Details of setting Factory set value
0000 No digit below decimal point (!!!!) Note 1 0001 1 digit below decimal point (!!!.!) 0002 2 digits below decimal point (!!.!!) * 0003 3 digits below decimal point (!.!!!) *
* When input type is thermocouple and RTD, no setting can be changed. Note 1 Factory set value varies depending on the instrument specification.
See. 2.1 Attention Items in Setting (P. 12).
(4) Setting limiter [high limit] (SLH)
Setting limiter [low limit] (SLL)
Details of setting Factory set
K 199 to +1372 °C (326 to +2502 °F) Factory set
199.9 to +999.9 °C (199.9 to +999.9 °F) value varies
J 199 to +1200 °C (326 to +2192 °F) depending on
199.9 to +999.9 °C (199.9 to +999.9 °F) the instrument
R 0 to 1769 °C (0 to 3216 °F) specification.
S 0 to 1769 °C (0 to 3216 °F) B 0 to 1820 °C (0 to 3308 °F) E 0 to 1000 °C (0 to 1832 °F)
Thermocouple N 0 to 1300 °C (0 to 2372 °F)
0 to 999.9 °C (0 to 999.9 °F)
T 199 to +400 °C (326 to +752 °F)
199.9 to +400.0 °C (199.9 to +752.0 °F)
W5Re/W26Re 0 to 2320 °C (0 to 4208 °F)
PL II 0 to 1390 °C (0 to 2534 °F)
U 199 to +600 °C (326 to +1112 °F)
199.9 to +600.0 °C (199.9 to +999.9 °F)
L 0 to 900 °C (0 to 1652 °F)
RTD Pt100 (JIS/IEC 1) 199.9 to +649.0 °C
JPt100 (JIS) (199.9 to +999.9 °F) 0 to 5 V DC 1999 to +9999 SLH: 100.0
Voltage
2
1 to 5 V DC (programmable scale) SLL: 0.0
0 to 10 V DC
1
IEC (International Electrotechnical Commission) is equivalent to JIS, DIN and ANSI.
2
In case of voltage/current inputs, SLH can be set below SLL.
Set the setting limiter referring to the 4. INPUT RANGE TABLES (P. 55). See. 2.1 Attention Items in Setting (P. 12).
value
IMR01H03-E4
19
2. DETAILS OF PARAMETER SETTING

2.4 F22 Current Transformer (CT) Input Specification

If the heater break alarm is selected as the alarm 2, the number of turns * of the current transformer (CT) used is set for each channel. In addition, it can be set simultaneously for all channels.
* The number of turns = CT ratio
The heater break alarm for three-phase heater can not be specified with MA901. When the MA901 instrument specification corresponds to contact input or communication
function, the heater break alarm can't be added. Therefore, do not use this parameter.
CT ratio 1 selection (CTr1) [Heater break alarm for single-phase heater or
"#
"#
"#"#
heater break alarm for three-phase heater (Z-168) ] CT ratio 2 selection (CTr2) [Heater break alarm for three-phase heater (Z-168) ]
The setting the CT ratio from CT1 to CT4 can be made when the CT ratio 1 (CTr1) of MA900 is selected. The setting the CT ratio from CT1 to CT8 can be made when the CT ratio 1 (CTr1) of MA901 is selected. The setting the CT ratio from CT5 to CT8 can be made when the CT ratio 2 (CTr2) is selected.
PV
SV
SET
CH
MA900
R/S
AREA
CH
PV
SV
SET
CH
MA900
R/S
Set the CT ratio.
CH
AREA
CT ratio 2 selecti on (CTr 2) CT ratio 1 selecti on (CTr 1)
Setting method
When the CTL-6-P-N current transformer is used, set the CT ratio to 800. When the CTL-12-S56-10L-N current transformer is used, set the CT ratio to 1000.
Details of setting Factory set value
0 to 9999 CTL-6-P-N: 800
CTL-12-S56-10L-N: 1000
MA900 (Heater break alarm for sing le- phase heater)
CH display PV display Details of setting
1 CTr1 Set the CT ratio of CT1. 2 Set the CT ratio of CT2. 3 Set the CT ratio of CT3. 4 Set the CT ratio of CT4.
Continued on the next page.
20
IMR01H03-E4
Continued from the previous page.
MA900 (Heater break alarm for thr ee- phase heat er)
CH display PV display Details of setting
1 CTr1 Set the CT ratio of CT1. 2 Set the CT ratio of CT2. 3 Set the CT ratio of CT3. 4 Set the CT ratio of CT4. 1 CTr2 Set the CT ratio of CT5. 2 Set the CT ratio of CT6. 3 Set the CT ratio of CT7.
2. DETAILS OF PARAMETER SETTING
4 Set the CT ratio of CT8.
The CT ratio 2 selection (CTr2) is displayed when the instrument specification is three-phase heater.
MA901 (Heater break alarm for sing le- phase heater)
CH display PV display Details of setting
1 CTr1 Set the CT ratio of CT1. 2 Set the CT ratio of CT2. 3 Set the CT ratio of CT3. 4 Set the CT ratio of CT4. 5 Set the CT ratio of CT5. 6 Set the CT ratio of CT6. 7 Set the CT ratio of CT7. 8 Set the CT ratio of CT8.
IMR01H03-E4
21
2. DETAILS OF PARAMETER SETTING

2.5 F24 Contact Input Specification

Setting is common to all channels. When the MA901 instrument specification corresponds to heater break alarm, the contact
input can't be added. Therefore, do not use this parameter.
Contact input logic selection (diSL)
"#
"#
"#"#
The contact input logic selection sets the set value about the following contents.
STOP selection
Selected whether to stop when the contact is opened or when the contact is closed.
Memory area selection
Memory area selection 1 to 8: These contents are selected when any of the memory areas from 1
to 8 is selected by the contact input.
Memory area selection 1 to 7: For example, when a digital switch starting from “0” is used,
select the memory area number when the memory area number must match the digital switch number.
If the selection of the memory areas from 1 to 7 is chosen, no memory area 8 can be selected by the contact input. In this case, select the memory area by the front key.
Used/unused of DI SET term inal (No. 43)
The method of establishment is set when the memory area is selected. When the DI SET terminal (No. 43) is used:
Select the area 0.5 seconds after the DI SET terminal is closed.
When the DI SET terminal (No. 43) is not used:
Select the memory area 2 seconds after the area is selected.
Details of
setting
0000 When contact input
0001 When contact input
0002 When contact input
STOP selection Memory area
selection
Memory area transfer (RUN/STOP transfer) opens, stop.
Memory area transfer (RUN/STOP transfer) opens, stop.
Memory area transfer (RUN/STOP transfer) opens, stop.
1 to 8
1 to 8
1 to 7
Used/unused of DI SET terminal
(No. 43)
Used 0000
Unused
Used
Factory
set value
22
Continued on the next page.
IMR01H03-E4
Continued from the previous page.
2. DETAILS OF PARAMETER SETTING
Details of
STOP selection Memory area
setting
0003 When contact input
(RUN/STOP transfer) opens, stop.
0004 When contact input
(RUN/STOP transfer) opens, stop.
0005 When contact input
(RUN/STOP transfer) is closed, stop.
0006 When contact input
(RUN/STOP transfer) is closed, stop.
0007 When contact input
(RUN/STOP transfer) is closed, stop.
0008 When contact input
(RUN/STOP transfer) is closed, stop.
0009 When contact input
(RUN/STOP transfer) is closed, stop.
selection
Memory area transfer
1 to 7
There is no memory area transfer function.
Memory area transfer
1 to 8
Memory area transfer
1 to 8
Memory area transfer
1 to 7
Memory area transfer
1 to 7
There is no memory area transfer function.
Used/unused of DI SET terminal
(No. 43)
Unused
Unused
Used 0000
Unused
Used
Unused
Unused
Factory
set value
IMR01H03-E4
23
2. DETAILS OF PARAMETER SETTING

2.6 F31 Output Function

"#
"#
MA900
"#"#
(1) Control output logic selection 1 (LGo1)
This data is 0000 fixation. This data must not set the set value besides 0000.
Channel
display
1OUT1 2OUT2 3OUT3 4OUT4
Output
number
Details of setting Factory set
value
0000: Heat-side control output of CH1 0000 0000: Heat-side control output of CH2 0000: Heat-side control output of CH3 0000: Heat-side control output of CH4
(2) Control output logic selection 2 (LGo2)
Select the output logic of the output 2 (OUT5 to OUT8). The channel number displayed on the CH display unit corresponds to the relevant output number. The setting is made for each channel number. In addition, OUT5 to OUT8 can be simultaneously set.
Conduct setting so as to meet the instrument specification. An incorrect setting may cause a malfunction.
Channel
display
1OUT5
2OUT6
3OUT7
1
Setting becomes effective at the time of heat/cool control.
2
Not output when alarm 3 corresponds to the FAIL alarm.
Output
number
Details of setting Factory set
0000: No output 0001: Cool-side control output of CH1 0002: No output 0003: No output 0004: Alarm 3 of CH1 0005: Alarm 3 of CH2 0006: Alarm 3 of CH3 0007: Alarm 3 of CH4
2 2 2 2
0008 to 0011: No output 0000: No output 0001: Cool-side control output of CH2 0002 to 0007: Same as OUT5 0008 to 0011: No output 0000: No output 0001: Cool-side control output of CH3 0002 to 0007: Same as OUT5 0008 to 0011: No output
value
Factory set
1
value varies depending on the instrument specification.
1
1
Continued on the next page.
24
IMR01H03-E4
Continued from the previous page.
MA900
Channel
display
Output
number
2. DETAILS OF PARAMETER SETTING
Details of setting Factory set
value
4OUT8
0000: No output 0001: Cool-side control output of CH4
*
0002 to 0007: Same as OUT5 0008 to 0011: No output
*
Setting becomes effective at the time of heat/cool control.
"#
"#
MA901
"#"#
(1) Control output logic selection 1 (LGo1)
This data is 0000 fixation. This data must not set the set value besides 0000.
Channel
display
1OUT1 2OUT2 3OUT3 4OUT4
Output
number
Details of setting Factory set
0000: Heat-side control output of CH1 0000 0000: Heat-side control output of CH2 0000: Heat-side control output of CH3 0000: Heat-side control output of CH4
Factory set value varies depending on the instrument specification.
value
(2) Control output logic selection 2 (LGo2)
This data is 0000 fixation. This data must not set the set value besides 0000.
Channel
display
1OUT5 2OUT6 3OUT7 4OUT8
Output
number
Details of setting Factory set
0000: Heat-side control output of CH5 0000 0000: Heat-side control output of CH6 0000: Heat-side control output of CH7 0000: Heat-side control output of CH8
value
IMR01H03-E4
25
2. DETAILS OF PARAMETER SETTING

2.7 F32 Alarm Output Function

Alarm output logic selection (LGA)
"#
"#
"#"#
Select the alarm output logic of alarm 1 (Normal equipment), alarm 2 (Option) and alarm 3 (Option). The channel number displayed on the CH display unit corresponds to the relevant alarm. The setting is made for each channel number. In addition, output logic of alarm 1 to alarm 3 can be simultaneously set.
Conduct setting so as to meet the instrument specification. An incorrect setting may cause a malfunction.
Channel
display
1ALM1
2ALM2
3ALM3
Alarm Detail s of set t i ng Factory
[Alarm 1]
[Alarm 2]
[Alarm 3]
set value
0000: FAIL alarm 0001: Logical OR of alarm 1 in all channels (E 0002: Logical OR of alarm 2 in all channels (E 0003: Logical OR of alarm 3 in all channels (E 0004: Logical OR of alarm 1 and alarm 2 in all channels
nergized
(E
0005: Logical OR of alarm 1 and alarm 3 in all channels
nergized
(E
0006: Logical OR of alarm 2 and alarm 3 in all channels
nergized
(E
0007: Logical OR of alarm 1, alarm 2 and alarm 3 in all
channels (E 0008: Logical OR of alarm 1 in all channels (De-e 0009: Logical OR of alarm 2 in all channels (De-e 0010: Logical OR of alarm 3 in all channels (De-e 0011: Logical OR of alarm 1 and alarm 2 in all channels
(De-e 0012: Logical OR of alarm 1 and alarm 3 in all channels
(De-e
0013: Logical OR of alarm 2 and alarm 3 in all channels
(De-e 0014: Logical OR of alarm 1, alarm 2 and alarm 3 in all
channels (De-e 0000 to 0014: Same as ALM1 0002
0000 to 0014: Same as ALM1 0003
)
)
)
nergized
nergized
nergized
nergized
)
)
)
)
nergized
)
nergized nergized nergized
nergized nergized nergized
) ) )
) ) )
0001
26
Alarm output is only relay contact output.
IMR01H03-E4
2. DETAILS OF PARAMETER SETTING

2.8 F41 Alarm 1 Function F42 Alarm 2 Function F43 Alarm 3 Function

(1) Alarm type selection (AS1, AS2, AS3)
Details of setting Factory set value
0000 Alarm not provided 0001 SV high alarm varies depending 0002 SV low alarm on the instrument 0003 Process high alarm specification. 0004 Process low alarm 0005 Deviation high alarm 0006 Deviation low alarm 0007 Deviation high/low alarm 0008 Band alarm 0009 Control loop break alarm 0010 Heater break alarm
1
When instrument specification is failure alarm, set 0000.
2
When control action type is heat/cool control, do not select.
3
When control output is current output, do not select.
4
When the contact input or the communication function is selected as instrument specifications of MA901, the heater break alarm can’t be added.
See 2.1 Attention Items in Setting (P. 12).
1
3, 4
Factory set value
2
(2) Alarm hold action selection (AHo1, AHo2, AHo3)
Details of setting Factory set value
0000 Without alarm hold action 0001 Effective when the power is turned on, or operation is changed
from STOP to RUN.
0002 Valid when:
the power is turned on,
operation is changed from STOP to RUN,
the SV is changed, or
the memory area (control area) is changed.
The alarm hold action function can not be added to the FAIL alarm, SV alarm, control loop break alarm and heater break alarm.
IMR01H03-E4
Without alarm hold action: 0000 With alarm hold action: 0002
27
2. DETAILS OF PARAMETER SETTING
t
(3) Alarm differential gap setting (AH1, AH2, AH3)
Set the alarm differential gap for each channel. In addition, they can be set simultaneously for all channels.
Details of setting Factory set value
Thermocouple 0 (0.0) to span Note 1
RTD
Voltage
Note 1 TC and RTD inputs: 2 °C [°F] or 2.0 °C [°F]
Voltage inputs: 0.2 % of span
(4) Alarm timer setting (ALT1, ALT2, ALT3)
Set the time until an alarm is actually output after being set to the alarm state.
Details of setting Factory set value
0 to 6000 seconds 0
Setting is common to all channels. The alarm timer function:
The alarm timer function regards the period until the alarm timer is set after measured value (PV) or deviation exceeds the alarm set value as a non-alarm state and outputs an alarm after the alarm timer setting time elapses. The alarm timer starts being activated if the alarm is turned on. In addition, if the alarm state is released while the alarm timer is being activated, no alarm is output.
Example: When set the alarm timer for 100 seconds
Measur ed v al ue (P V)
Alarm set value
Set value (SV)
28
Alarm out p u
Alarm timer
(100 seconds)
Alarm state
ON
Alarm timer
seconds)
(100
Alarm state
When instrument specification is FAIL alarm, the alarm timer function does not operate.
IMR01H03-E4
2. DETAILS OF PARAMETER SETTING
(5) Action selection at input error (AEo1, AEo2, AEo3)
Set the alarm action in input abnormality by input break (when the input is over-scaled or underscaled).
Details of setting Factory set value
0000 Normal processing:
0000 The alarm action set by alarm type selection (AS1/AS2) is taken even if the input is abnormal.
0001 Forcibly turned on when abnormal:
The alarm is forcibly turned on regardless of the alarm action set by alarm type selection (AS1/AS2) when the input is abnormal.
For a voltage input of 0 to 5 V DC or 0 to 10 V DC, as over-scale or underscale does not occur when the input breaks, no alarm is turned on.

2.9 F51 Control Action

The setting items (oS and oH) in the function block F51 are set for each channel. In addition, they can be set simultaneously for all channels.
(1) Control action type selection (oS1)
Match the setting with the instrument specification. Otherwise malfunction may result. The MA901 does not perform heat/cool control.
Details of setting Factory set value
0000 D type: PID control with autotuning (Direct action) 0001 F type: PID control with autotuning (Reverse action) 0002 W type: Heat/cool PID control with autotuning (Water cooling) 0003 A type: Heat/cool PID control with autotuning (Air cooling)
1
When instrument specification corresponds to heat/cool control, this set value can’t be set.
2
When instrument specification corresponds to heat control, this set value can’t be set.
1
1
2
2
Note 1 Factory set value varies depending on the instrument specification.
(2) ON/OFF action differential gap setting (oH)
Details of setting Factory set value
Thermocouple 0 (0.0) to span Note 1
RTD
Voltage
Note 1 TC and RTD inputs: 2 °C [°F] or 2.0 °C [°F]
Voltage inputs: 0.2 % of span
Note 1
IMR01H03-E4
29
2. DETAILS OF PARAMETER SETTING

2.10 F61 Communication Function

(1) Communication protocol selection (CMPS)
If the protocol is selected, always turn the power on again or select RUN from STOP.
When the MA901 instrument specification corresponds to heater break alarm, the communication function can't be added. Therefore, do not use this parameter.
Details of setting Factory set value
0000 RKC communication protocol (Multi-point mode) 0001 Modbus communication protocol Note 1 0002 RKC communication protocol (Single mode)
Note 1 Factory set value varies depending on the instrument specification.
(2) RUN/STOP transfer logic selection
Select the logic of RUN/STOP transfer in the communication mode.
Details of setting Factory set value
0000 Set in 0: STOP mode
Set in 1: RUN mode
0001 Set in 0: RUN mode
Set in 1: STOP mode
0000
30
IMR01H03-E4
2. DETAILS OF PARAMETER SETTING

2.11 F91 Displayed for Maintenance Information

Only displayed for the F91 function block.
(1) ROM version displayed (E261)
Display the version of loading software.
(2) Integrated operating time display (WTH) [upper 3 digits]
Display the integrated operating time (upper 3 digits) of instrument.
Details of display : 0 to 100 (Resolution of display: 10,000 hours)
Up to 1,000,000 from 0 including the upper and lower digits can be displayed.
(3) Integrated operating time display (WTL) [lower 4 digits]
Display the integrated operating time (lower 4 digits) of instrument. However, as the integral time is increments by 1 when the power is turned on or off. If the total integrated operating time exceeds 9,999 hours, these digits move to the integrated operating time display (upper 3 digits).
Details of display : 0 to 9999 (Resolution of display: 1 hours)
(4) Holding peak value ambient temperature display (TCJ)
The maximum ambient temperature on the rear terminal board of the instrument is stored and displayed on the set value (SV) display.
Details of display : 10 to +100 °C [°F] (Resolution of display: 1°C [°F])
IMR01H03-E4
31

3. INITIALIZE COMMUNICATION DATA

3.1 RKC Communication Protocol

Reference to communication identifier list
!"
!"
!"!"
(1) (2) (3) (4) (5) (6) (7)
Name Iden-
tifier
STOP display selection
Input type selection
(1) Name: A name of identifier is written. (2) Identifier: The code to identify the data is written. (3) No. of digits: The number of maximum digits is written. (4) Data range: The range of reading or writing data is written. (5) Factory set value: The factory set value of data is written. (6) Attribute: The data accessing direction is written.
(7) CH: ×: Identifier with channel
DX 1 0: It makes display “STOP” in
XI 6 0 to 16 (See P. 18)Note 1R/W×
No. of
digits
PV display.
1: It makes display “STOP” in
SV display.
RO: Read only (Data direction: Controller Host computer) R/W: Read and Write (Data direction: Controller Host computer)
: Identifier without channel
Data range Factory set
Attri-
value
0R/W
bute
CH
Data sending during polling
!"
!"
!"!"
Each time the host computer sends ACK (acknowledgement), the controller sends data corresponding to the respective identifier in the order specified in a list of communication identifiers.
Communication is not possible when an identifier is specified that the controller can not recognize.
To be send in this order.
32
Name Iden-
STOP display selection
Input type selection
tifier
DX 1 0: It makes display “STOP”
XI 6 0 to 16 (See P. 18)
No. of
digits
Data range
PV display.
1: It makes display “STOP”
SV display.
IMR01H03-E4
!"Communication identifier list
For details on the structure of communication data, see Communication Instruction Manual (IMR01H02-E#).
3. INITIALIZE COMMUNICATION DATA
Name Iden-
STOP display selection
tifier
DX 1 0: It makes display “STOP” in
No. of
digits
Data range Factory set
PV display.
Attri-
value
bute
0R/W
1: It makes display “STOP” in
SV display.
Input type
XI 6 0 to 16 (See P. 18)Note 1R/W×
selection Display unit
selection Decimal point
position setting
PU 10: °C
1: °F
XU 1 0: No digit below decimal point
1: 1 digit below decimal point
0R/W×
Note 2 R/W ×
2: 2 digits below decimal point 3: 3 digits below decimal point
Setting limiter
XV 6 Within input range. Note 3 R/W ×
[high limit] setting Setting limiter
[low limit] setting CT ratio 1
1
XW See 4. INPUT RANGE
TABLES (P. 55)
XR 6 0 to 9999 (See P. 20)Note 4R/W×
selection CT ratio 2
1, 2
XS
selection
1
When selecting CT ratio 1 or 2, as a channel number specified after the identifier, specify the
channel number corresponding to the CT ratio selection.
For the CT ratio selection channel number, see the 2.4 F22 Current Transformer (CT) Input Specification (P. 20).
2
Do not use CT ratio 2 for the MA901. Note 1 Factory set value varies depending on the input type. Note 2 Factory set value varies depending on the instrument specification. However, factory set value
of a case of voltage input is 1.
Note 3 Factory set value varies depending on the instrument specification. However, factory set value
of a case of voltage input is 100.0 (high limit) and 0.0 (low limit).
Note 4 CTL-6-P-N: 800
CTL-12-S56-10L-N: 1000
CH
IMR01H03-E4
Continued on the next page.
33
3. INITIALIZE COMMUNICATION DATA
Continued from the previous page.
Name Iden-
Contact input logic selection *
tifier
XK
No. of
digits
1 0 to 9
Data range Factory set
See contact input logic tables
* This is the identifier effective when the contact input is provided.
Contact input logic tables
Set value STOP selection Memory area
selection
0 When contact input (RUN/STOP
transfer) opens, stop.
1 When contact input (RUN/STOP
transfer) opens, stop.
2 When contact input (RUN/STOP
transfer) opens, stop.
3 When contact input (RUN/STOP
transfer) opens, stop.
4 When contact input (RUN/STOP
transfer) opens, stop.
Memory area transfer 1 to 8
Memory area transfer 1 to 8
Memory area transfer 1 to 7
Memory area transfer 1 to 7
There is no memory area transfer function.
5 When contact input (RUN/STOP
transfer) is closed, stop.
6 When contact input (RUN/STOP
transfer) is closed, stop.
7 When contact input (RUN/STOP
transfer) is closed, stop.
8 When contact input (RUN/STOP
transfer) is closed, stop.
9 When contact input (RUN/STOP
transfer) is closed, stop.
Memory area transfer 1 to 8
Memory area transfer 1 to 8
Memory area transfer 1 to 7
Memory area transfer 1 to 7
There is no memory area transfer function.
value
Attri-
bute
CH
0R/W
Used/Unused of
DI SET terminal (No.43)
Used
Unused
Used
Unused
Unused
Used
Unused
Used
Unused
Unused
×
34
For details of the selection item, see the 2.5 F24 Contact Input Specification (P. 22).
Continued on the next page.
IMR01H03-E4
Continued from the previous page.
3. INITIALIZE COMMUNICATION DATA
Name Iden-
Control output logic selection 1
tifier
E0
No. of
digits
6
Data range Factory set
OUT1
0: Heat-side control output of
CH1
*
OUT2
0: Heat-side control output of
*
CH2
OUT3
0: Heat-side control output of
*
CH3
OUT4
0: Heat-side control output of
*
CH3
* This data is 0 fixation. This data must not set the set value besides 0.
Attri-
value
bute
0R/W
CH
×
IMR01H03-E4
Continued on the next page.
35
3. INITIALIZE COMMUNICATION DATA
Continued from the previous page.
Name Iden-
Control output logic selection 2
tifier
No. of
digits
Data range Factory set
E1 6 ••• MA900 (OUT5 to OUT8)
OUT5
0: No output 1: Cool-side control output of
CH1
1
2: No output 3: No output 4: Alarm 3 of CH1 5: Alarm 3 of CH2 6: Alarm 3 of CH3 7: Alarm 3 of CH4
2 2 2 2
8 to 11: No output
OUT6
0: No output 1: Cool-side control output of
CH2
1
2 to 11: Same as OUT5
OUT7
0: No output 1: Cool-side control output of
CH3
1
2 to 11: Same as OUT5
OUT8
0: No output 1: Cool-side control output of
CH4
1
2 to 11: Same as OUT5
value
Factory set value varies depending on the instrument specification.
Attri-
bute
R/W ×
CH
•••• MA901 (OUT5 to OUT8) OUT5
0: Heat-side control output of
3
CH5
OUT6
0: Heat-side control output of
3
CH6
OUT7
0: Heat-side control output of
3
CH7
OUT8
0: Heat-side control output of
3
CH8
1
Setting becomes effective at the time of heat/cool control.
2
Not output when alarm 3 corresponds to the FAIL alarm.
3
This data is 0 fixation. This data must not set the set value besides 0.
36
Continued on the next page.
IMR01H03-E4
Continued from the previous page.
3. INITIALIZE COMMUNICATION DATA
Name Iden-
Alarm output logic selection *
tifier
No. of
digits
Data range Factory set
EA 6 0: FAIL alarm
1: Logical OR of alarm 1 in all
channels (Energized)
2: Logical OR of alarm 2 in all
channels (Energized)
3: Logical OR of alarm 3 in all
channels (Energized)
4: Logical OR of alarm 1 and
alarm 2 in all channels (Energized)
5: Logical OR of alarm 1 and
alarm 3 in all channels (Energized)
6: Logical OR of alarm 2 and
alarm 3 in all channels (Energized)
7: Logical OR of alarm 1,
alarm 2 and alarm 3 in all channels (Energized)
8: Logical OR of alarm 1 in all
channels (De-energized)
9: Logical OR of alarm 2 in all
channels (De-energized)
10: Logical OR of alarm 3 in all
channels (De-energized)
11: Logical OR of alarm 1 and
alarm 2 in all channels (De-energized)
12: Logical OR of alarm 1 and
and 3 of all channels (De-energized)
13: Logical OR of alarm 2 and
alarm 3 in all channels (De-energized)
14: Logical OR of alarm 1,
alarm 2 and alarm 3 in all channels (De-energized)
value
Alarm 1: 1 Alarm 2: 2 Alarm 3: 3
Attri-
bute
R/W
CH
* The logic of alarm output can be set for each alarm (alarm 1 to alarm 3). When selecting the logic,
as a channel number specified after the identifier, specify any of the following numbers. Alarm 1: 01 Alarm 2: 02 Alarm 3: 03
For the data structure, see the Communication Instruction Manual (IMR01H02-E
Continued on the next page.
IMR01H03-E4
####
.
)
37
3. INITIALIZE COMMUNICATION DATA
Continued from the previous page.
Name Iden-
Alarm 1 type selection
1
tifier
XA 6 0: No alarm
No. of
digits
Data range Factory set
1: SV high alarm 2: SV low alarm 3: Process high alarm 4: Process low alarm
value
Factory set value varies depending on the instrument specification.
Attri-
bute
R/W
5: Deviation high alarm 6: Deviation low alarm 7: Deviation high/low alarm 8: Band alarm
2
Without
R/W
alarm hold action: 0
With alarm hold action: 2
Alarm 1 hold action selection
9: Control loop break alarm
WA 1 0: Without alarm hold action
3
1: Effective when the power is
turned on, or operation is changed from STOP to RUN.
2: Valid when:
the power is turned on,
operation is changed from
STOP to RUN,
the SV is changed, or
the memory area (control
area) is changed.
Alarm 1
HA 6 0 (0.0) to span Note 1 R/W ×
differential gap setting
Alarm 1
TD 6 0 to 6000 seconds (See P. 28)0R/W
timer setting Alarm 1
action selection at input error
OA 1 0: Normal processing
1: Forcibly turned on when
abnormal
0R/W
(See P. 29)
1
When using the FAIL alarm, always set the alarm type to “0:No alarm.”
2
Control loop break alarm can not be specified in case of heat/cool control.
3
The alarm hold action can not be added to the FAIL alarm, SV high alarm, SV low alarm, control
loop break alarm and heater break alarm.
Note 1 TC and RTD inputs: 2 °C [°F] or 2.0 °C [°F]
Voltage input: 0.2 % of span
CH
38
Continued on the next page.
IMR01H03-E4
Continued from the previous page.
3. INITIALIZE COMMUNICATION DATA
Name Iden-
Alarm 2 type selection
1
tifier
XB 6 0: No alarm
No. of
digits
Data range Factory set
1: SV high alarm 2: SV low alarm 3: Process high alarm 4: Process low alarm
value
Factory set value varies depending on the instrument specification.
Attri-
bute
R/W
5: Deviation high alarm 6: Deviation low alarm 7: Deviation high/low alarm 8: Band alarm 9: No alarm
2, 3
Without alarm hold action: 0
With alarm hold action: 2
R/W
Alarm 2 hold action selection
10: Heater break alarm
WB 1 0: Without alarm hold action
4
1: Effective when the power is
turned on, or operation is changed from STOP to RUN.
2: Valid when:
the power is turned on,
operation is changed from
STOP to RUN,
the SV is changed, or
the memory area (control
area) is changed.
Alarm 2
HB 6 0 (0.0) to span Note 1 R/W ×
differential gap setting
Alarm 2
TG 6 0 to 6000 seconds (See P. 28)0R/W
timer setting Alarm 2
action selection at input error
OB 1 0: Normal processing
1: Forcibly turned on when
abnormal
0R/W
(See P. 29)
1
When using the FAIL alarm, always set the alarm type to “0:No alarm.”
2
When the control output is current output, no setting can be changed.
3
When the contact input or the communication function is selected as instrument specifications of
MA901, the heater break alarm cannot be added.
4
The alarm hold action can not be added to the FAIL alarm, SV high alarm, SV low alarm, control
loop break alarm and heater break alarm.
Note 1 TC and RTD inputs: 2 °C [°F] or 2.0 °C [°F]
Voltage input: 0.2 % of span
CH
IMR01H03-E4
Continued on the next page.
39
3. INITIALIZE COMMUNICATION DATA
Continued from the previous page.
Name Iden-
Alarm 3 type selection
1
Alarm 3 hold action selection
2
Alarm 3 differential gap setting
tifier
XC
WC
HC
No. of
digits
6 0: No alarm
1: SV high alarm 2: SV low alarm 3: Process high alarm 4: Process low alarm
Data range Factory set
value
Factory set value varies depending on the instrument
specification. 5: Deviation high alarm 6: Deviation low alarm 7: Deviation high/low alarm 8: Band alarm
1 0: Without alarm hold action
1: Effective when the power is
turned on, or operation is changed from STOP to RUN.
2: Valid when:
Without
alarm hold
action: 0
With alarm
hold action: 2
the power is turned on,
operation is changed from
STOP to RUN,
the SV is changed, or
the memory area (control
area) is changed.
6 0 (0.0) to span Note 1 R/W
Attri-
bute
R/W
R/W
CH
×
Alarm 3 timer setting
Alarm 3 action selection at input error
TH
OC
6 0 to 6000 seconds
(See P. 28)
1 0: Normal processing
1: Forcibly turned on when
abnormal
0R/W
0R/W
(See P. 29)
1
When using the FAIL alarm, always set the alarm type to “0:No alarm.”
2
The alarm hold action can not be added to the FAIL alarm, SV high alarm, SV low alarm, control
loop break alarm and heater break alarm.
Note 1 TC and RTD inputs: 2 °C [°F] or 2.0 °C [°F]
Voltage input: 0.2 % of span
Continued on the next page.
40
IMR01H03-E4
Continued from the previous page.
3. INITIALIZE COMMUNICATION DATA
Name Iden-
ON/OFF action differential gap
tifier
IV 6 0 (0.0) to span
No. of
digits
Data range Factory set
However, 9999 digits of less
setting Control action
type selection
ROM version display
Integrated operating time
XE 1 0: PID control (Direct action)
1: PID control (Reverse action) 2: Heat/cool action
(Water cooling)
2
3: Heat/cool action
(Air cooling)
2
VR 10 Display the version of loading
software.
UT 6 0000 to 0100
(See P. 31)
1
Factory set
1
value varies
depending on
the instrument
specification.
display [upper 3 digits]
Integrated operating time
UU 6 0000 to 9999
(See P. 31)
display [lower 4 digits]
Holding peak
HP 6 10 to +100 RO
ambient temperature display
Communication protocol selection
IS 1 0: RKC communication protocol
(Multi-point mode)
1: Modbus communication
protocol
2: RKC communication protocol
Factory set
value varies
depending on
the instrument
specification.
(Single mode)
RUN/STOP transfer
RS 1 0: 0 (STOP) 1 (RUN)
1: 0 (RUN) 1 (STOP)
logic selection
1
When the instrument specification is heat/cool control, no setting can be changed.
2
When the instrument specification is only heat control, no setting can be changed.
The MA901 does not perform heat/cool control.
Note 1 TC and RTD inputs: 2 °C [°F] or 2.0 °C [°F]
Voltage input: 0.2 % of span
value
Attri-
bute
CH
Note 1 R/W ×
R/W ×
RO
RO
RO
R/W
0R/W
IMR01H03-E4
41
3. INITIALIZE COMMUNICATION DATA

3.2 Modbus Communication Protocol

3.2.1 Communication data list
The communication data list summarizes names, descriptions, factory set values and attributes.
Attribute (RO: Read only, R/W: Read and Write) The communication data whose name is marked with ! indicates that corresponding to the
memory area.
Name Data range Factory set value Attri-
bute
Setting change rate limiter !
Setting limiter [high limit] setting
Setting limiter [low limit] setting
Digital filter 0 to 100 seconds
Input type selection 0 to 16 (See P. 18)Note 2R/W Display unit selection 0: °C 1: °F0R/W Decimal point position
setting
CT ratio 1 selection 0 to 9999 (See P. 20)Note 4R/W CT ratio 2 selection * ON/OFF action
differential gap setting
0 (0.0) to span/minute (0: Setting change rate limiter OFF)
Within input range. See 4. INPUT RANGE TABLES (P. 55)
(0: No digital filter function)
0: No digit below decimal point 1: 1 digit below decimal point 2: 2 digits below decimal point 3: 3 digits below decimal point
0 (0.0) to span However, 9999 digits of less
0R/W
Note 1 R/W
0R/W
Note 3 R/W
Note 5 R/W
* Do not use CT ratio 2 for the MA901. Note 1 Factory set value varies depending on the instrument specification. However, factory set value
of a case of voltage input is 100.0 (high limit) and 0.0 (low limit). Note 2 Factory set value varies depending on the input type. Note 3 Factory set value varies depending on the instrument specification. However, factory set value
of a case of voltage input is 1. Note 4 CTL-6-P-N: 800
CTL-12-S56-10L-N: 1000
Note 5 TC and RTD inputs: 2 °C [°F] or 2.0 °C [°F]
Voltage input: 0.2 % of span
Continued on the next page.
42
IMR01H03-E4
Continued from the previous page.
Name Data range Factory set value Attri-
Control action type selection
0: PID control (Direct action) 1: PID control (Reverse action) 2: Heat/cool control (Water cooling) 3: Heat/cool control (Air cooling)
3. INITIALIZE COMMUNICATION DATA
bute
1
1
2
2
Note 1 R/W
Alarm 1 type selection
3
0: No alarm 1: SV high alarm 2: SV low alarm 3: Process high alarm
Factory set value varies depending on the instrument specification.
R/W
4: Process low alarm 5: Deviation high alarm 6: Deviation low alarm 7: Deviation high/low alarm 8: Band alarm
4
Without alarm hold
R/W action: 0 With alarm hold action: 2
Alarm 1 hold action selection
5
9: Control loop break alarm 0: Without alarm hold action 1: Effective when the power is turned on,
or operation is changed from STOP to RUN.
2: Valid when:
the power is turned on,
operation is changed from STOP to
RUN,
the SV is changed, or
the memory area (control area) is
changed.
Alarm 1 timer setting 0 to 6000 seconds (See P. 28)0R/W Alarm 1
action selection at input error
Alarm 1
0: Normal processing 1: Forcibly turned on when abnormal (See P. 29)
0 (0.0) to span Note 2 R/W
0R/W
differential gap setting
1
When the instrument specification is heat/cool control, no setting can be changed.
2
When the instrument specification is only heat control, no setting can be changed.
The MA901 does not perform heat/cool control.
3
When using the FAIL alarm, always set the alarm type to “0: No alarm.”
4
Control loop break alarm can not be specified in case of heat/cool control.
5
The alarm hold action can not be added to the FAIL alarm, SV high alarm, SV low alarm, control
loop break alarm and heater break alarm.
Note 1 Factory set value varies depending on the instrument specification. Note 2 TC and RTD inputs: 2 °C [°F] or 2.0 °C [°F]
Voltage input: 0.2 % of span
IMR01H03-E4
Continued on the next page.
43
3. INITIALIZE COMMUNICATION DATA
Continued from the previous page.
Name Data range Factory set value Attri-
bute
Alarm 2 type selection
1
0: No alarm 1: SV high alarm 2: SV low alarm 3: Process high alarm
Factory set value varies depending on the instrument specification.
R/W
4: Process low alarm 5: Deviation high alarm 6: Deviation low alarm 7: Deviation high/low alarm 8: Band alarm 9: No alarm
2, 3
Without alarm hold action: 0 With alarm hold action: 2
R/W
Alarm 2 hold action selection
4
10: Heater break alarm 0: Without alarm hold action 1: Effective when the power is turned on,
or operation is changed from STOP to RUN.
2: Valid when:
the power is turned on,
operation is changed from STOP to
RUN,
the SV is changed, or
the memory area (control area) is
changed.
Alarm 2 timer setting 0 to 6000 seconds (See P. 28)0R/W Alarm 2
action selection at input error
Alarm 2
0: Normal processing 1: Forcibly turned on when abnormal (See P. 29)
0 (0.0) to span Note 1 R/W
0R/W
differential gap setting
1
When using the FAIL alarm, always set the alarm type to “0: No alarm.”
2
When the control output is current output, no setting can be changed.
3
When the contact input or the communication function is selected as instrument specifications of
MA901, the heater break alarm cannot be added.
4
The alarm hold action can not be added to the FAIL alarm, SV high alarm, SV low alarm, control
loop break alarm and heater break alarm.
Note 1 TC and RTD inputs: 2 °C [°F] or 2.0 °C [°F]
Voltage input: 0.2 % of span
44
Continued on the next page.
IMR01H03-E4
Continued from the previous page.
Name Data range Factory set value Attri-
3. INITIALIZE COMMUNICATION DATA
bute
Alarm 3 type selection
1
0: No alarm 1: SV high alarm 2: SV low alarm 3: Process high alarm
Factory set value varies depending on the instrument specification.
R/W
4: Process low alarm 5: Deviation high alarm 6: Deviation low alarm 7: Deviation high/low alarm 8: Band alarm
Alarm 3 hold action selection
2
0: Without alarm hold action 1: Effective when the power is turned on,
or operation is changed from STOP to RUN.
Without alarm hold action: 0 With alarm hold action: 2
R/W
2: Valid when:
the power is turned on,
operation is changed from STOP to
RUN,
the SV is changed, or
the memory area (control area) is
changed.
Alarm 3 timer setting 0 to 6000 seconds (See P. 28)0R/W Alarm 3
action selection at input error
Alarm 3
0: Normal processing 1: Forcibly turned on when abnormal (See P. 29)
0 (0.0) to span Note 1 R/W
0R/W
differential gap setting Control output logic
selection 1
OUT1
0: Heat-side control output of CH1
3
0
OUT2
3
0: Heat-side control output of CH2
OUT3
3
0: Heat-side control output of CH3
OUT4
3
0: Heat-side control output of CH4
1
When using the FAIL alarm, always set the alarm type to “0: No alarm.”
2
The alarm hold action can not be added to the FAIL alarm, SV high alarm, SV low alarm, control
loop break alarm and heater break alarm.
3
This data is 0 fixation. This data must not set the set value besides 0.
Note 1 TC and RTD inputs: 2 °C [°F] or 2.0 °C [°F]
Voltage input: 0.2 % of span
Continued on the next page.
IMR01H03-E4
45
3. INITIALIZE COMMUNICATION DATA
Continued from the previous page.
Name Data range Factory set value Attri-
bute
Control output logic selection 2
•••• MA900 (OUT5 to OUT8) OUT5
0: No output 1: Cool-side control output of CH1 2: No output 3: No output 4: Alarm 3 of CH1 5: Alarm 3 of CH2 6: Alarm 3 of CH3 7: Alarm 3 of CH4
2 2 2 2
8 to 11: No output
OUT6
0: No output 1: Cool-side control output of CH2 2 to 11: Same as OUT5
OUT7
0: No output 1: Cool-side control output of CH3 2 to 11: Same as OUT5
OUT8
0: No output 1: Cool-side control output of CH4 2 to 11: Same as OUT5
Factory set value
R/W varies depending on the instrument
1
1
1
1
specification.
•••• MA901 (OUT5 to OUT8) OUT5
0: Heat-side control output of CH5
OUT6
0: Heat-side control output of CH6
OUT7
0: Heat-side control output of CH7
OUT8
0: Heat-side control output of CH8
1
Setting becomes effective at the time of heat/cool control.
2
Not output when alarm 3 corresponds to the FAIL alarm.
3
This data is 0 fixation. This data must not set the set value besides 0.
46
3
3
3
3
Continued on the next page.
IMR01H03-E4
3. INITIALIZE COMMUNICATION DATA
Continued from the previous page.
Name Data range Factory set value Attri-
bute
Alarm output logic selection *
STOP display selection
0: FAIL alarm
1: Logical OR of alarm 1 in all channels
(Energized)
2: Logical OR of alarm 2 in all channels
(Energized)
3: Logical OR of alarm 3 in all channels
(Energized)
4: Logical OR of alarm 1 and alarm 2 in all
channels (Energized)
5: Logical OR of alarm 1 and alarm 3 in all
channels (Energized)
6: Logical OR of alarm 2 and alarm 3 in all
channels (Energized)
7: Logical OR of alarm 1, alarm 2 and alarm 3 in
all channels (Energized)
8: Logical OR of alarm 1 in all channels
(De-energized)
9: Logical OR of alarm 2 in all channels
(De-energized)
10: Logical OR of alarm 3 in all channels
(De-energized)
11: Logical OR of alarm 1 and alarm 2 in all
channels (De-energized)
12: Logical OR of alarm 1 and 3 of all channels
(De-energized)
13: Logical OR of alarm 2 and alarm 3 in all
channels (De-energized)
14: Logical OR of alarm 1, alarm 2 and alarm 3 in
all channels (De-energized) 0: It makes display “STOP” in PV display. 1: It makes display “STOP” in SV display.
Alarm 1: 1
R/W Alarm 2: 2 Alarm 3: 3
0R/W
* The logic of alarm output can be set for each alarm (alarm 1 to alarm 3).
IMR01H03-E4
Continued on the next page.
47
3. INITIALIZE COMMUNICATION DATA
Continued from the previous page.
Name Data range Factory set value Attri-
bute
Contact input logic selection
Communication protocol selection
0 to 9 See contact input logic tables
0: RKC communication protocol
(Multi-point mode) 1: Modbus communication protocol 2: RKC communication protocol
(Single mode)
RUN/STOP transfer logic selection
0: 0 (STOP) 1 (RUN) 1: 0 (RUN) 1 (STOP)
Contact input logic tables
Set value STOP selection Memory area
selection
0 When contact input (RUN/STOP
transfer) opens, stop.
1 When contact input (RUN/STOP
transfer) opens, stop.
2 When contact input (RUN/STOP
transfer) opens, stop.
3 When contact input (RUN/STOP
transfer) opens, stop.
4 When contact input (RUN/STOP
transfer) opens, stop.
Memory area transfer 1 to 8
Memory area transfer 1 to 8
Memory area transfer 1 to 7
Memory area transfer 1 to 7
There is no memory area transfer function.
5 When contact input (RUN/STOP
transfer) is closed, stop.
6 When contact input (RUN/STOP
transfer) is closed, stop.
7 When contact input (RUN/STOP
transfer) is closed, stop.
8 When contact input (RUN/STOP
transfer) is closed, stop.
9 When contact input (RUN/STOP
transfer) is closed, stop.
Memory area transfer 1 to 8
Memory area transfer 1 to 8
Memory area transfer 1 to 7
Memory area transfer 1 to 7
There is no memory area transfer function.
0R/W
Factory set value
R/W varies depending on the instrument specification.
0R/W
Used/Unused of
DI SET terminal (No.43)
Used
Unused
Used
Unused
Unused
Used
Unused
Used
Unused
Unused
48
For details of the selection item, see the 2.5 F24 Contact Input Specification (P. 22).
IMR01H03-E4
3. INITIALIZE COMMUNICATION DATA
3.2.2 Data map
Reference to data map
!"
This data map summarizes the data addresses, channels and names that can be used with Modbus protocol. For details on each data range, see 3.2.1 Communication Data List (P. 42).
(1)
Address CH Name
03E8H (1000) CH1 03E9H (1001)
03EAH (1002) CH3 limiter
03EBH (1003) CH4 03ECH (1004)
044BH (1099) 044CH (1100) CH1 044DH (1101) CH2 Setting limiter
044EH (1102) CH3 [high limit] setting 044FH (1103) CH4
(1) Address: Data addresses are written in hexadecimal numbers.
Characters in ( ) are decimal numbers.
(2) CH: The input channel number, output number (OUT1 to OUT8, ALM1 to ALM3) or
CT ratio 1 and 2 selection channel number is written.
(2)
CH2
(3)
Setting change rate
Unused
(3) Name: Data names
IMR01H03-E4
49
3. INITIALIZE COMMUNICATION DATA
MA900 data map list
!"
!"
!"!"
(Read/Wr ite data)
Address CH Name
03E8H (1000) CH1 03E9H (1001) CH2 Setting change rate 03EAH (1002) CH3 limiter
1
03EBH (1003) CH4 03ECH (1004)
Unused 044BH (1099) 044CH (1100) CH1 044DH (1101) CH2 Setting limiter 044EH (1102) CH3 [high limit] setting 044FH (1103) CH4 0450H (1104)
Unused 045FH (1119) 0460H (1120) CH1 0461H (1121) CH2 Setting limiter 0462H (1122) CH3 [low limit] setting 0463H (1123) CH4 0464H (1124)
Unused 0473H (1139) 0474H (1140) CH1 0475H (1141) CH2 Digital filter
1
0476H (1142) CH3 0477H (1143) CH4 0478H (1144)
Unused 0487H (1159) 0488H (1160) CH1 0489H (1161) CH2 Input type selection 048AH (1162) CH3 048BH (1163) CH4 048CH (1164)
Unused 049BH (1179)
049CH (1180) CH1 049DH (1181) CH2 Display unit selection 049EH (1182) CH3 049FH (1183) CH4
Address CH Name
04A0H (1184)
Unused 04AFH (1199) 04B0H (1200) CH1 04B1H (1201) CH2 Decimal point position 04B2H (1202) CH3 setting 04B3H (1203) CH4 04B4H (1204)
Unused 04C3H (1219) 04C4H (1220) CH1
2
04C5H (1221) CH2 2CT ratio 1 selection 04C6H (1222) CH3 04C7H (1223) CH4
2 2
04C8H (1224) CH1 3CT ratio 2 selection
3
04C9H (1225) CH2 04CAH (1226) CH3 04CBH (1227) CH4 04CCH (1228)
(Heater break alarm for
3
three-phase heater)
3
Unused 04D7H (1239) 04D8H (1240) CH1 04D9H (1241) CH2 ON/OFF action 04DAH
CH3 differential gap setting
(1242) 04DBH (1243) CH4 04DCH (1244)
Unused 04EBH (1259) 04ECH (1260) CH1 04EDH (1261) CH2 Control action type 04EEH (1262) CH3 selection 04EFH (1263) CH4
1
The limiter for the setting change rate limiter or
digital filter described in the Communication
Instruction Manual (IMR01H02-E
####
) can
also be set.
2
Channel number of the CT ratio 1 selection
3
Channel number of the CT ratio 2 selection
50
Continued on the next page.
IMR01H03-E4
Continued from the previous page.
3. INITIALIZE COMMUNICATION DATA
Address CH Name
04F0H (1264)
Unused
04FFH (1279) 0500H (1280) Alarm 1 type selection 0501H (1281) Alarm 1 hold action
selection
0502H (1282) Alarm 1 timer setting 0503H (1283) Alarm 1
action selection at
input error 0504H (1284) CH1 0505H (1285) CH2 Alarm 1 0506H (1286) CH3 differential gap setting 0507H (1287) CH4 0508H (1288)
Unused
0513H (1299) 0514H (1300) Alarm 2 type selection 0515H (1301) Alarm 2 hold action
selection 0516H (1302) Alarm 2 timer setting 0517H (1303) Alarm 2
action selection at
input error 0518H (1304) CH1 0519H (1305) CH2 Alarm 2 051AH (1306) CH3 differential gap setting 051BH (1307) CH4 051CH (1308)
Unused 0527H (1319) 0528H (1320) Alarm 3 type selection 0529H (1321) Alarm 3 hold action
selection 052AH (1322) Alarm 3 timer setting 052BH (1323) Alarm 3
action selection at
input error 052CH (1324) CH1 052DH (1325) CH2 Alarm 3 052EH (1326) CH3 differential gap setting 052FH (1327) CH4
Address CH Name
0530H (1328)
Unused 053BH (1339) 053CH (1340) OUT1 053DH (1341) OUT2 Control output logic 053EH (1342) OUT3 selection 1 053FH (1343) OUT4 0540H (1344) OUT5 0541H (1345) OUT6 Control output logic 0542H (1346) OUT7 selection 2 0543H (1347) OUT8 0544H (1348) ALM1 Alarm output logic 0545H (1349) ALM2 selection 0546H (1350) ALM3 0547H (1351)
Unused 054FH (1359) 0550H (1360) STOP display selection 0551H (1361) Unused 0552H (1362) Contact input logic
selection 0553H (1363) Communication
protocol selection 0554H (1364) RUN/STOP transfer
logic selection
IMR01H03-E4
51
3. INITIALIZE COMMUNICATION DATA
MA901 data map list
!"
!"
!"!"
(Read/Wr ite data)
Address CH Name
03E8H (1000) CH1 03E9H (1001) CH2 03EAH (1002) CH3 03EBH (1003) CH4 Setting change rate 03ECH (1004) CH5 limiter * 03EDH (1005) CH6 03EEH (1006) CH7 03EFH (1007) CH8 03F0H (1008)
044BH (1099) 044CH (1100) CH1 044DH (1101) CH2 044EH (1102) CH3 044FH (1103) CH4 Setting limiter 0450H (1104) 0451H (1105) CH6 0452H (1106) CH7 0453H (1107) CH8 0454H (1108)
045FH (1119) 0460H (1120) CH1 0461H (1121) CH2 0462H (1122) CH3 0463H (1123) CH4 Setting limiter 0464H (1124) 0465H (1125) CH6 0466H (1126) CH7 0467H (1127) CH8 0468H (1128)
0473H (1139) 0474H (1140) CH1 0475H (1141) CH2 0476H (1142) CH3 0477H (1143) CH4 Digital filter * 0478H (1144) 0479H (1145) CH6 047AH (1146) CH7 047BH (1147)
CH5
CH5
CH5
CH8
Unused
[high limit] setting
Unused
[low limit] setting
Unused
Address CH Name
047CH (1148)
0487H (1159) 0488H (1160) CH1 0489H (1161) CH2 048AH (1162) CH3 048BH (1163) CH4 Input type selection 048CH (1164) 048DH (1165) CH6 048EH (1166) CH7 048FH (1167) CH8 0490H (1168)
049BH (1179) 049CH (1180) CH1 049DH (1181) CH2 049EH (1182) CH3 049FH (1183) CH4 Display unit selection 04A0H (1184) 04A1H (1185) CH6 04A2H (1186) CH7 04A3H (1187) CH8 04A4H (1188)
04AFH (1199) 04B0H (1200) CH1 04B1H (1201) CH2 04B2H (1202) CH3 04B3H (1203) CH4 Decimal point position 04B4H (1204) 04B5H (1205) CH6 04B6H (1206) CH7 04B7H (1207) CH8
* The limiter for the setting change rate limiter or
digital filter described in the Communication instruction manual (IMR01H02-E
also be set.
CH5
CH5
CH5 setting
Unused
Unused
Unused
####
) can
Continued on the next page.
52
IMR01H03-E4
Continued from the previous page.
3. INITIALIZE COMMUNICATION DATA
Address CH Name
04B8H (1208)
Unused 04C3H (1219) 04C4H (1220) CH1 * 04C5H (1221) CH2 * 04C6H (1222) CH3 * 04C7H (1223) CH4 * CT ratio 1 selection 04C8H (1224) CH5 * 04C9H (1225) CH6 * 04CAH (1226) CH7 * 04CBH (1227) CH8 * 04CCH (1228)
Unused 04D7H (1239) 04D8H (1240) CH1 04D9H (1241) CH2 04DAH (1242) CH3 04DBH (1243) CH4 ON/OFF action 04DCH (1244) CH5 differential gap setting 04DDH (1245) CH6 04DEH (1246) CH7 04DFH (1247) CH8 04E0H (1248)
Unused 04EBH (1259) 04ECH (1260) CH1 04EDH (1261) CH2 04EEH (1262) CH3 04EFH (1263) CH4 Control action type 04F0H (1264) CH5 selection 04F1H (1265) CH6 04F2H (1266) CH7 04F3H (1267) CH8 04F4H (1268)
Unused 04FFH (1279) 0500H (1280) Alarm 1 type selection 0501H (1281) Alarm 1 hold action
selection 0502H (1282) Alarm 1 timer setting
Address CH Name
0503H (1283) Alarm 1
action selection at
input error 0504H (1284) CH1 0505H (1285) CH2 0506H (1286) CH3 0507H (1287) CH4 Alarm 1 0508H (1288) CH5 differential gap setting 0509H (1289) CH6 050AH (1290) CH7 050BH (1291) CH8 050CH (1292)
Unused
0513H (1299) 0514H (1300) Alarm 2 type selection 0515H (1301) Alarm 2 hold action
selection 0516H (1302) Alarm 2 timer setting 0517H (1303) Alarm 2
action selection at
input error 0518H (1304) CH1 0519H (1305) CH2 051AH (1306) CH3 051BH (1307) CH4 Alarm 2 051CH (1308) CH5 differential gap setting 051DH (1309) CH6 051EH (1310) CH7 051FH (1311) CH8 0520H (1312)
Unused 0527H (1319) 0528H (1320) Alarm 3 type selection 0529H (1321) Alarm 3 hold action
selection 052AH (1322) Alarm 3 timer setting 052BH (1323) Alarm 3
action selection at
input error
* Channel number of the CT ratio 1 selection
IMR01H03-E4
Continued on the next page.
53
3. INITIALIZE COMMUNICATION DATA
Continued from the previous page.
Address CH Name
052CH (1324) CH1 052DH (1325) CH2 052EH (1326) CH3 052FH (1327) CH4 Alarm 3 0530H (1328) 0531H (1329) 0532H (1330) 0533H (1331) 0534H (1332)
CH5 differential gap setting CH6 CH7 CH8
Unused 053BH (1339) 053CH (1340) OUT1 053DH (1341) OUT2 Control output logic 053EH (1342) OUT3 selection 1 053FH (1343) OUT4 0540H (1344) OUT5 0541H (1345) OUT6 Control output logic 0542H (1346) OUT7 selection 2 0543H (1347) OUT8 0544H (1348) ALM1 Alarm output logic 0545H (1349) ALM2 selection 0546H (1350) ALM3 0547H (1351)
Unused 054FH (1359) 0550H (1360) STOP display
selection 0551H (1361) Unused 0552H (1362) Contact input logic
selection 0553H (1363) Communication
protocol selection 0554H (1364) RUN/STOP transfer
logic selection
54
IMR01H03-E4

4. INPUT RANGE TABLES

Input Range Table 1
Input type Input range Code
Input Range
0 to 200 °C 0 to 400 °C 0 to 600 °C
0 to 800 °C 0 to 1000 °C 0 to 1200 °C 0 to 1372 °C
199.9 to +300.0 °C *
0.0 to 400.0 °C
0.0 to 800.0 °C
K
Thermocouple
J
* Accuracy is not guaranteed between 199.9 to −100.0 °C (199.9 to −148.0 °F)
0 to 100 °C
0 to 300 °C
0 to 450 °C
0 to 500 °C
0.0 to 200.0 °C
0.0 to 600.0 °C
199.9 to +800.0 °C * 0 to 800 °F
0 to 1600 °F 0 to 2502 °F
0.0 to 800.0 °F 20 to 70 °F
199.9 to +999.9 °F * 0 to 200 °C 0 to 400 °C 0 to 600 °C 0 to 800 °C
0 to 1000 °C 0 to 1200 °C
199.9 to +300.0 °C *
0.0 to 400.0 °C
0.0 to 800.0 °C 0 to 450 °C
0.0 to 200.0 °C
0.0 to 600.0 °C
199.9 to +600.0 °C *
K01 K02 K03 K04 K05 K06 K07 K08 K09 K10 K13 K14 K17 K20 K29 K37 K38 KA1 KA2 KA3 KA4 KA9 KB2
J01 J02 J03 J04 J05 J06 J07 J08 J09 J10 J22 J23 J30
IMR01H03-E4
Continued on the next page.
55
4. INPUT RANGE TABLES
Continued from the previous page.
Input type Input range Code
0 to 800 °F
0 to 1600 °F 0 to 2192 °F
J
0 to 400 °F
199.9 to +999.9 °F
0.0 to 800.0 °F 0 to 1600 °C 0 to 1769 °C
R
0 to 1350 °C 0 to 3200 °F 0 to 3216 °F 0 to 1600 °C
S
0 to 1769 °C 0 to 3200 °F 0 to 3216 °F
2 2
2 2 2 2 2 2 2
400 to 1800 °C
Thermocouple B
0 to 1820 °C
2
800 to 3200 °F
0 to 3308 °F
2
0 to 800 °C
E
0 to 1000 °C 0 to 1600 °F 0 to 1832 °F 0 to 1200 °C
N
0 to 1300 °C
0.0 to 800.0 °C 0 to 2300 °F 0 to 2372 °F
0.0 to 999.9 °F
199.9 to +400.0 °C
199.9 to +100.0 °C
100.0 to +200.0 °C
0.0 to 350.0 °C
T
199.9 to +752.0 °F
100.0 to +200.0 °F
100.0 to +400.0 °F
0.0 to 450.0 °F
0.0 to 752.0 °F
1
Accuracy is not guaranteed between 199.9 to −100.0 °C (199.9 to −148.0 °F)
2
Accuracy is not guaranteed between 0 to 399 °C (0 to 751 °F)
Input Range
JA1 JA2 JA3 JA6
1
JA9
JB6 R01 R02 R04 RA1 RA2 S01 S02 SA1 SA2 B01 B02 BA1 BA2 E01 E02 EA1 EA2 N01 N02 N06 NA1 NA2 NA5
1 1
T01 T02 T03 T04
1
TA1 TA2 TA3 TA4 TA5
56
Continued on the next page.
IMR01H03-E4
Continued from the previous page.
Input type Input range Code
4. INPUT RANGE TABLES
Input Range
W5Re/W26Re
0 to 2000 °C 0 to 2320 °C 0 to 4000 °F 0 to 1300 °C 0 to 1390 °C
PL II
0 to 1200 °C 0 to 2400 °F 0 to 2534 °F
Thermocouple
199.9 to +600.0 °C *
199.9 to +100.0 °C *
0.0 to 400.0 °C
U
199.9 to +999.9 °F *
100.0 to +200.0 °F
0.0 to 999.9 °F 0 to 400 °C
L
0 to 800 °C 0 to 800 °F
0 to 1600 °F
199.9 to +649.0 °C
199.9 to +200.0 °C
100.0 to +50.0 °C
100.0 to +100.0 °C
100.0 to +200.0 °C
0.0 to 50.0 °C
0.0 to 100.0 °C
0.0 to 200.0 °C
0.0 to 300.0 °C
RTD Pt100
0.0 to 500.0 °C
199.9 to +999.9 °F
199.9 to +400.0 °F
199.9 to +200.0 °F
100.0 to +100.0 °F
100.0 to +300.0 °F
0.0 to 100.0 °FDA6
0.0 to 200.0 °FDA7
0.0 to 400.0 °FDA8
0.0 to 500.0 °FDA9
* Accuracy is not guaranteed between 199.9 to −100.0 °C (199.9 to −148.0 °F)
W01 W02 WA1
A01 A02 A03 AA1 AA2 U01 U02 U03 UA1 UA2 UA3 L01 L02 LA1 LA2 D01 D02 D03 D04 D05 D06 D07 D08 D09 D10 DA1 DA2 DA3 DA4 DA5
IMR01H03-E4
Continued on the next page.
57
4. INPUT RANGE TABLES
Continued from the previous page.
Input type Input range Code
Input Range
199.9 to +649.0 °C
199.9 to +200.0 °C
100.0 to +50.0 °C
100.0 to +100.0 °C
RTD JPt100
100.0 to +200.0 °C
0.0 to 50.0 °C
0.0 to 100.0 °C
0.0 to 200.0 °C
0.0 to 300.0 °C
0.0 to 500.0 °C
Input Range Table 2
Input type Input range Code
Input Range
0 to 5 V DC 4 01
Voltage 0 to 10 V DC 0.0 to 100.0 % 5 01
1 to 5 V DC 6 01
P01 P02 P03 P04 P05 P06 P07 P08 P09 P10
58
IMR01H03-E4
The first edition: JUL. 2001 The fourth edition: JUL. 2002 [IMQ00]
RKC INSTRUMENT INC.
HEADQUARTERS: 16-6, KUGAHARA 5-CHOME, OHTA-KU TOKYO 146-8515 JAPAN
PHONE: 03-3751-9799 (+81 3 3751 9799) E-mail: info@rkcinst.co.jp FAX: 03-3751-8585 (+81 3 3751 8585)
IMR01H03-E4 JUL. 2002
Loading...