Ethernet is a registered trademark of Xerox Corp.
Modbus is a registered trademark of Schneider Electric.
Windows and Microsoft Internet Explorer are registered trademark of Microsoft Corporation in the
U.S.A. and other countries.
Company names and product names used in this manual are the trademarks or registered trademarks
of the respective companies.
All Rights Reserved, Copyright 2005, RKC INSTRUMENT INC.
Thank you for purchasing this RKC instrument. In order to achieve maximum performance and ensure
proper operation of your new instrument, carefully read all the instructions in this manual. Please place this
manual in a convenient location for easy reference.
SYMBOLS
WARNING
CAUTION
!
: This mark indicates where additional information may be located.
An external protection device must be installed if failure of this instrument
could result in damage to the instrument, equipment or injury to personnel.
: This mark indicates precautions that must be taken if there is danger of electric
shock, fire, etc., which could result in loss of life or injury.
: This mark indicates that if these precautions and operating procedures are not taken,
damage to the instrument may result.
: This mark indicates that all precautions should be taken for safe usage.
: This mark indicates important information on installation, handling and operating
procedures.
: This mark indicates supplemental information on installation, handling and
operating procedures.
WARNING
!
All wiring must be completed before power is turned on to prevent electric
shock, fire or damage to instrument and equipment.
This instrument must be used in accordance with the specifications to
prevent fire or damage to instrument and equipment.
This instrument is not intended for use in locations subject to flammable or
explosive gases.
Do not touch high-voltage connections such as power supply terminals, etc.
to avoid electric shock.
RKC is not responsible if this instrument is repaired, modified or
disassembled by other than factory-approved personnel. Malfunction can
occur and warranty is void under these conditions.
IMS01S01-E1
i-1
CAUTION
This is a Class A instrument. In a domestic environment, this instrument may cause radio
interference, in which case the user may be required to take adequate measures.
This instrument is protected from electric shock by reinforced insulation. Provide reinforced
insulation between the wire for the input signal and the wires for instrument power supply,
source of power and loads.
Be sure to provide an appropriate surge control circuit respectively for the following:
- If input/output or signal lines within the building are longer than 30 meters.
- If input/output or signal lines leave the building, regardless the length.
This instrument is designed for installation in an enclosed instrumentation panel. All
high-voltage connections such as power supply terminals must be enclosed in the
instrumentation panel to avoid electric shock by operating personnel.
All precautions described in this manual should be taken to avoid damage to the instrument or
equipment.
All wiring must be in accordance with local codes and regulations.
All wiring must be completed before power is turned on to prevent electric shock, instrument
failure, or incorrect action.
The power must be turned off before repairing work for input break and output failure including
replacement of sensor, contactor or SSR, and all wiring must be completed before power is
turned on again.
To prevent instrument damage or failure, protect the power line and the input/output lines from
high currents with a protection device such as fuse, circuit breaker, etc.
Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid
electric shock, fire or malfunction.
Tighten each terminal screw to the specified torque found in the manual to avoid electric shock,
fire or malfunction.
For proper operation of this instrument, provide adequate ventilation for heat dispensation.
Do not connect wires to unused terminals as this will interfere with proper operation of the
instrument.
Turn off the power supply before cleaning the instrument.
Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or
discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
To avoid damage to instrument display, do not rub with an abrasive material or push front
panel with a hard object.
Do not connect modular connectors to telephone line.
NOTICE
This manual assumes that the reader has a fundamental knowledge of the principles of electricity,
process control, computer technology and communications.
The figures, diagrams and numeric values used in this manual are only for purpose of illustration.
RKC is not responsible for any damage or injury that is caused as a result of using this instrument,
instrument failure or indirect damage.
RKC is not responsible for any damage and/or injury resulting from the use of instruments made by
imitating this instrument.
Periodic maintenance is required for safe and proper operation of this instrument. Some components
have a limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all information contained herein. RKC makes no
warranty expressed or implied, with respect to the accuracy of the information. The information in this
manual is subject to change without prior notice.
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored,
processed or retrieved through any mechanical, electronic, optical or other means without prior written
approval from RKC.
This manual describes communication specification, wiring, setting, and data instructions for Ethernet
[Modbus/TCP] communication module H-LNK-B for SR Mini HG SYSTEM (hereafter called the
H-LNK-B).
Modbus/TCP is an open field network provided with the Modbus protocol on the TCP/IP protocol of
Ethernet.
The data request side is called “client” (such as computer) and the data response (supply) side is
called “server” (H-LNK-B).
Basically, one client corresponds to one server (i.e. one to one). However, one client can
communicate with two or more servers depending on the program on the client side, but two or
more clients cannot communicate with one server.
A control unit of SR Mini HG SYSTEM consists of a dedicated power supply /CPU module (H-PCP-J or
H-PCP-A module), an Ethernet communication module (H-LNK-B module) and each function module
used to the temperature control.
Computer
(Client)
Ethernet
Network Hub
Communication
Ethernet
module for Ethernet
H-LNK-B (Server)
Power supply/CPU
module
(H-PCP-J/H-PCP-A)
RS-422A
Controller communication
SR Mini HG control unit
(Up to 16 units)
RS-422A
SR Mini HG control unit
Function modules:
Up to 9 modules
(Only temperature control module:
Up to 8 modules)
IMS01S01-E1 1
1. OUTLINE
Usable PCP module
Power supply/CPU module
Power supply/CPU module H-PCP-J (Usable protocol is Modbus/TCP and no-protocol)
H-PCP-A Z-1021 specification (Usable protocol is Modbus/TCP and
no-protocol)
H-PCP-A standard specification (Usable protocol is only
no-protocol)
For the power supply/CPU module, see H-PCP-J Instruction Manual (IMS01J02-E) and
Hardware Instruction Manual (IMSRM15-E).
Usable function module
The following function module can be used in combination with the H-PCP-J or H-PCP-A module.
H-PCP-J module
Function module Type
Temperature control module H-TIO-A H-TIO-B H-TIO-C H-TIO-D H-TIO-E
H-TIO-F H-TIO-G H-TIO-H H-TIO-J H-TIO-P
H-TIO-R
Position proportioning control module H-TIO-K
Speed control module H-SIO-A
Temperature input module H-TI-A H-TI-B H-TI-C
Cascade control module H-CIO-A
Current transformer input module H-CT-A
Digital input module H-DI-A H-DI-B
Digital output module H-DO-A H-DO-B H-DO-C H-DO-D H-DO-G
Analog input module H-AI-A H-AI-B
Analog output module H-AO-A H-AO-B
H-PCP-A module
Function module Type
Temperature control module H-TIO-A H-TIO-B H-TIO-C H-TIO-D H-TIO-E
H-TIO-F H-TIO-G H-TIO-H H-TIO-J H-TIO-P
H-TIO-R
Position proportioning control module H-TIO-K
Temperature input module H-TI-A H-TI-B H-TI-C
Cascade control module H-CIO-A
Current transformer input module H-CT-A
Digital input module H-DI-A H-DI-B
Digital output module H-DO-A H-DO-B H-DO-C H-DO-D
Analog input module H-AI-A H-AI-B
Analog output module H-AO-A H-AO-B
For the function modules, see Hardware Instruction Manual (IMSRM15-E), H-DO-G
Instruction Manual (IMS01K01-E) and H-SIO-A Instruction Manual (IMS01L01-E).
IMS01S01-E1
2
1. OUTLINE
1.1 Product Check
Before using this product, check each of the following.
Model code
Check that there are no scratch or breakage in external appearance (case, front panel, terminal, etc).
Check that all of the accessories delivered are complete. (See below)
Accessories Q’TYRemarks
Connection cable (W-BF-02-200)
[A connection for H-LNK-B and H-PCP module:
Cable length 200 mm]
Instruction Manual (IMS01S01-E1) 1 This manual
If any of the products are missing, damaged, or if your manual is incomplete, please contact
RKC sales office or the agent.
If the H-LNK-B module is installed at the right end of the SR Mini HG control unit, the length of
an attached cable may not be enough to reach the module. In that case, make an order placement
of the connection cable, W-BF-02-500 (cable length: 500 mm) separately.
1 Enclosed with instrument
1.2 Model Code
Check whether the delivered product is as specified by referring to the following model code list. If the
product is not identical to the specifications, please contact RKC sales office or the agent.
(1) Communication protocol
1: Modbus/TCP
H-LNK- B-1
(1)
IMS01S01-E1
3
1. OUTLINE
1.3 Parts Description
H-LNK-B module
Indication lamp 1
Indication lamp 2
Connector for
Ethernet
Indication lamp 3
Mother block
Module connector
Connector for
H-PCP module
IP address
setting switch
(SW1 to SW3)
Front view
Right side view
[Details of indication lamp 1]
RX
TX
RX
TX
Indication lamp 1
FAIL [Red] When instrument abnormally: Turns on
RUN [Green]
• When normally: Flashes
• Operation error: Turns on
RX [Yellow] During controller communication data receive: Flashes
TX [Yellow] During controller communication data send: Flashes
Indication lamp 2
Activity
Half-duplex; activity: [Amber] Turns on
Full-duplex; activity: [Green] Turns on
Indication lamp 3
Link
10 Mbps: [Amber] Turns on
100 Mbps: [Green] Turns on
Connector
Connector for Ethernet Modular connector for Ethernet (RJ-45 specification)
Connector for H-PCP module Modular connector for H-PCP module
Switch
IP address setting switch
Set the IP address of Ethernet
(SW1 to SW3)
Others
Mother block Base block for module connection
Module connector Connector for power supply
LNK
FAIL
RUN
FAIL
RUN
IMS01S01-E1
4
2. HANDLING PROCEDURES
Conduct the setting necessary for performing communication in accordance with the following procedure.
Setting of DIP switch
Mounting
Wiring
IP address setting
Set the controller communication speed and data bit configuration
of H-LNK-B, and also set the action mode of Ethernet
communication.
See 5.1 DIP Switch Setting (P. 21).
Mount the H-LNK-B.
See 3. MOUNTING (P. 6).
Connect the H-LNK-B to Ethernet, and also connect the H-LNK-B
to the H-PCP.
See 4. WIRING (P. 11).
Set the IP address of Ethernet communication.
See 5.2 IP Address Setting (P. 23).
IMS01S01-E1 5
3. MOUNTING
This chapter describes installation environment, mounting cautions, dimensions and mounting procedures.
To prevent electric shock or instrument failure, always turn off the power before
mounting or removing the instrument.
WARNING
!
3.1 Mounting Cautions
(1) This instrument is intended to be used under the following environmental conditions. (IEC61010-1)
[OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]
(2) Use this instrument within the following ambient temperature and ambient humidity.
• Allowable ambient temperature: 0 to +50 °C
• Allowable ambient humidity: 45 to 85 % RH
(Absolute humidity: MAX.W.C 29 g/m
(3) Avoid the following conditions when selecting the mounting location.
• Rapid changes in ambient temperature which may cause condensation.
• Corrosive or inflammable gases.
• Direct vibration or shock to the mainframe.
• Water, oil, chemicals, vapor or steam splashes.
• Excessive dust, salt or iron particles.
• Excessive induction noise, static electricity, magnetic fields or noise.
• Direct air flow from an air conditioner.
• Exposure to direct sunlight.
• Excessive heat accumulation.
(4) Take the following points into consideration when mounting this instrument.
• Ensure at least 50 mm space on top and bottom of the instrument for maintenance and
environmental reasons.
• Do not mount this instrument directly above equipment that generates large amount of heat (heaters,
transformers, semi-conductor functional devices, large-wattage resistors).
• If the ambient temperature rises above 50 °C, cool this instrument with a forced air fan, cooler, or
the like. However, do not allow cooled air to blow this instrument directly.
• In order to improve safety and the immunity to withstand noise, mount this instrument as far away
as possible from high voltage equipment, power lines, and rotating machinery.
High voltage equipment: Do not mount within the same panel.
Power lines: Separate at least 200 mm.
Rotating machinery: Separate as far as possible.
3
dry air at 101.3 kPa)
6 IMS01S01-E1
3.2 Dimensions
External dimensions
96
3. MOUNTING
(Unit: mm)
9
23.5
24
3.5
100
Module mounting depth
The mounting depth of each module is 108 mm from the mounting surface inside the panel to the front of
the module with the module mounted on the DIN rail. However, when modular connector cables are
plugged in, additional depth is required.
Approx. 50
108
(Unit: mm)
IMS01S01-E1
DIN rail
7
3. MOUNTING
3.3 Mounting the Mother Block
The mother block can be mounted to a panel or DIN rail.
Panel mounting directions
1. Refer to both the panel mounting dimensions below and the external dimensions in previous section
when selecting the location.
2-M3
24
24
(Unit: mm)
24
77
77
Dimensions for multiple module mounting
2. Remove the module from the mother block. For details of removing the module, see 3.5 Removing
the Module Mainframe (P. 10).
3. Connect the mother blocks together before tightening the screws on the panel.
(Customer must provide the set screws)
M3 × 10
Recommended tightening torque:
0.3 N⋅m (3 kgf⋅cm)
When the mother block is mounted on the panel,
50 mm or more space is required at the top and
bottom of the mother block to attach the module
mainframe.
Mother block
8
IMS01S01-E1
3. MOUNTING
DIN rail mounting directions
1. Remove the module mainframe from the mother block. For details of removing the module
mainframe, see 3.5 Removing the ModuleMainframe(P. 10).
2. Pull down the locking devices at the bottom of the mother block. (A)
For the double type, as there are two locking devices, pull down both of them.
3. Attach the top bracket of the mother block to the DIN rail and push the lower section into place on the
DIN rail. (B)
4. Slide the locking devices up to secure the mother block to the DIN rail. (C)
5. Slide connectors together to complete mother block installation. (D)
(A)
(B)
(C)
Locking device
When the mother block is mounted on panel, 50 mm or more space is required at the top
and bottom of the mother block to attach the module mainframe
Mother block mounting
(D)
IMS01S01-E1
9
3. MOUNTING
3.4 Mounting the Module Mainframe
It engages the module with the mother block that is mounted on DIN rail or a panel.
1. Place the module mainframe opening on top of the mother block tab. (A)
2. Snap the lower part of module mainframe on to the mother block. (B)
Opening at top of module
(A)
Tab at top of mother block
(B)
A snapping sound will be heard when module mainframe is securely connected to mother block.
3.5 Removing the Module Mainframe
It detaches the module from the mother block that is mounted on DIN rail or a panel.
To separate the module mainframe from the mother block, press the bottom on the module, lifting upward,
to release connection.
Mother block
Module mainframe
Module mainframe
Upper
section
Lower
section
10
Mother block
Press bottom of module
and lift upward to release
IMS01S01-E1
4. WIRING
This chapter describes wiring cautions and wiring method.
4.1 Wiring Cautions
To prevent electric shock or instrument failure, turn off the power before
connecting or disconnecting the instrument and peripheral equipment.
CAUTION
Connect connectors correctly in the right position. If it is forcibly pushed in with pins in the
wrong positions, the pins may be bent resulting in instrument failure.
When connecting or disconnecting the connectors, do not force it too far to right and left or
up and down, but move it on the straight. Otherwise, the connector pins may be bent,
causing instrument failure.
When disconnecting a connector, hold it by the connector itself. Disconnecting connectors
by yanking on their cables can cause breakdowns.
To prevent malfunction, never touch the contact section of a connector with bare hands or
with hands soiled with oil or the like.
To prevent malfunction, connect cable connectors securely, then firmly tighten the connector
fastening screws.
To prevent damage to cables, do not bend cables over with excessive force.
If the instrument is easily affected by noise, use the ferrite core in the both ends of the
communication cable (nearest the connector).
WARNING
!
IMS01S01-E1 11
4. WIRING
e
4.2 Connection to Ethernet
4.2.1 Wiring configuration
When directly connected to client
Computer
(Client)
Power supply/CPU module
(H-PCP-J/H-PCP-A)
Ethernet
SR Mini HG control unit
When use network hub
Computer
(Client)
Power supply/CPU module
(H-PCP-J/H-PCP-A)
Function modules
Ethernet communication module
(H-LNK-B)
Ethernet
Ethernet
Network Hub
SR Mini HG control unit
12
Function modules
Ethernet communication modul
(H-LNK-B)
IMS01S01-E1
4. WIRING
Basically, one client corresponds to one server (i.e. one to one). However, one client can
communicate with two or more servers depending on the program on the client side, but two or
more clients cannot communicate with one server.
The cable is provided by the customer.
Used cable: The cable is based on the 10BASE-T or the 100BASE-TX standard of Ethernet.
Used connector: RJ-45 type
14
IMS01S01-E1
+TX−RX+RX−
Wiring example
When directly connected to client
Use a cross cable when directly connected to the client (such as computer).
Computer H-LNK-B module
4. WIRING
TX
+
TX
−
RX
+
RX
−
Cross cable
When use network hub
Use straight cables when connected to the network hub.
Computer
TX
TX
RX
RX
+
−
+
−
Network Hub
TX+
TX−
RX+
RX−
TX
TX+
TX−
RX+
RX−
H-LNK-B module
TX+
TX−
RX+
RX−
Straight cable Straight cable
Cross cables may be used depending on the connecting device used. Therefore, follow the
instructions for the respective device.
IMS01S01-E1
15
4. WIRING
4.3 Connection to H-PCP Module
4.3.1 Wiring configuration
When connect to the H-PCP-J module
When use COM.PORT1 of H-PCP-J
Connect the “COM” connector on the H-LNK-B module to the “COM.PORT1” connector on the H-PCP-J
module.
Operation panel or
Host computer
Ethernet
SR Mini HG control unit
COM. PORT1
connector
Connect between COM
COM connector
and COM. PORT1
(Controller communication:
RS-422A)
RS-422A
SR Mini HG control unit
(Up to 16 units can be connected)
Power supply/CPU module
H-PCP-J
Ethernet communication module
Function modules
Up to 9 modules can be connected
(Only temperature control module:
Up to 8 modules)
H-LNK-B
When use COM.PORT3 of H-PCP-J
Connect the “COM” connector on the H-LNK-B module to the “COM.PORT3” connector on the H-PCP-J
module.
16
Operation panel, PLC or
Host computer
COM. PORT3
Connect between COM
and COM. PORT3
(Controller communication:
RS-422A
SR Mini HG control unit
(Up to 16 units can be connected)
Ethernet
connector
RS-422A)
Power supply/CPU module
H-PCP-J
SR Mini HG control unit
COM connector
Function modules
Up to 9 modules can be connected
(Only temperature control module:
Up to 8 modules)
Ethernet communication module
H-LNK-B
IMS01S01-E1
4. WIRING
When connect to the H-PCP-A module
Connect the “COM” connector on the H-LNK-B module to the “COM.PORT1” connector on the H-PCP-A
module.
Ethernet
SR Mini HG control unit
COM. PORT1
connector
Connect between COM
COM connector
and COM. PORT1
(Controller communication:
RS-422A)
RS-422A
SR Mini HG control unit
(Up to 16 units can be connected)
Power supply/CPU module
H-PCP-A
Ethernet communication module
Function modules
Up to 9 modules can be connected
(Only temperature control module:
Up to 8 modules)
H-LNK-B
If the H-LNK-B module is installed at the right end of the SR Mini HG control unit, up to ten
function modules can be connected. However, if configured only with temperature control
modules, up to 8 function modules can be connected.
When in the above case, the length of an attached cable (cable length: 200 mm) may not be
enough to reach the module. In that case, make an order placement of the connection cable,
W-BF-02-500 (cable length: 500 mm) separately.
Ethernet
COM. PORT1
SR Mini HG control unit
connector
Connect between COM
(Controller communication:
RS-422A
Power supply/CPU module
SR Mini HG control unit
(Up to 16 units can be connected)
IMS01S01-E1
and COM. PORT1
RS-422A)
H-PCP-J or H-PCP-A
Function modules
Up to 10 modules can be connected
(Only temperature control module:
Up to 8 modules)
COM connector
The H-LNK-B module is
installed at the right end
17
4. WIRING
4.3.2 Wiring details
Pin layout of modular connector
H-LNK-B module
Modular connector
for H-PCP module
Ethernet communication module
H-LNK-B
COM
1: T (A)
2: T (B)
3: SG
4: R (B)
5: R (A)
6: SG
• Connector pin number and signal details
Pin No. Signal name Symbol
1 Send data T (A)
2 Send data T (B)
3 Signal ground SG
4 Receive data R (B)
5 Receive data R (A)
6 Signal ground SG
18
IMS01S01-E1
H-PCP-J module
COM.PORT1
4. WIRING
Power supply/CPU module
H-PCP-J
COM.PORT3
1: R (A)
2: R (B)
3: SG
4: T (B)
5: T (A)
6: SG
• Connector pin number and signal details
Pin No. Signal name Symbol
1
2
3
4
5
6
Receive data
Receive data
Signal ground
Send data
Send data
Signal ground
H-PCP-A module
Power supply/CPU module
H-PCP-A
R (A)
R (B)
SG
T (B)
T (A)
SG
COM. PORT1
6: SG
5: T (A)
4: T (B)
3: SG
2: R (B)
1: R (A)
• Connector pin number and signal details
Pin No. Signal name Symbol
1
2
3
4
5
6
IMS01S01-E1
Receive data
Receive data
Signal ground
Send data
Send data
Signal ground
R (A)
R (B)
SG
T (B)
T (A)
SG
1: R (A)
2: R (B)
3: SG
4: T (B)
5: T (A)
6: SG
19
4. WIRING
Wiring example
Connect the H-LNK-B module to the H-PCP module using the cable (W-BF-02-200) attached to the
H-LNK-B module.
Connection to H-PCP-J moduleConnection to H-PCP-A module
COM. PORT3
COM. PORT1
COM. PORT1
or
Shields of the cable are connected to SG (No. 6 pin) of the H-PCP-J (or H-PCP-A) connector.
• Wiring details
H-PCP-J/H-PCP-A
T (A)
5
T (B)
4
SG
3
R (A)
R (B)
H-PCP-J: COM. PORT1 or
COM. PORT3 connector
H-PCP-A: COM. PORT1 connector
SG
1
2
6
COMCOM
Connection cable
W-BF-02-200
(Cable length: 200 mm)
Pair wire
Shielded twisted pair wire
5
4
3
1
2
6
R (A)
R (B)
SG
T (A)
T (B)
COM
H-LNK-B
connector
20
The 6-pin type modular connector should be used for the connection to the H-PCP-J (or
H-PCP-A) module.
Recommended model: TM4P-66P (Manufactured by HIROSE ELECTRIC CO., LTD., )
IMS01S01-E1
5. SETTING
5.1 DIP Switch Setting
To prevent electric shock or instrument failure, always turn off the power
before setting the switch.
To prevent electric shock or instrument failure, never touch any section other
than those instructed in this manual.
Communication speed of controller communication, data bit configuration and protocol of Ethernet
communication can be set with the DIP switch located in the H-LNK-B module.
1. To separate the module mainframe from the mother block, press the bottom on the module, lifting
upward, to release connection.
Mother block
Module mainframe
WARNING
!
Module mainframe
Upper
section
Lower
section
Mother block
2. Remove the MCU board from the case while holding the connector by hand with the stopper pulled in
the direction shown by the arrow.
(View with the mother block removed)
MCU board
Connector
Rear
DIP switch
Stopper
IMS01S01-E1 21
5. SETTING
3. Communication speed of controller communication, data bit configuration and protocol of Ethernet
communication can be set with the DIP switch.
Connector
DIP switch
1 8765432
ON
MCU board
1 2 Data bit configuration
OFF OFF
ON OFF
OFF ON
ON ON
Data 8-bit, Without parity, Stop 1-bit
Data 7-bit, Odd parity, Stop 1-bit
Data 7-bit, Even parity, Stop 1-bit
Data 7-bit, Even parity, Stop 2-bit
Factory set value: Data 8-bit, Without parity, Stop 1-bit
3 4 Communication speed
OFF OFF
ON OFF
OFF ON
ON ON
9600 bps
19200 bps
38400 bps
Do not set this one
Factory set value: 9600 bps
5 6 7 Protocol
OFF OFF OFF
ON OFF OFF
Modbus/TCP
No-protocol
OFF ON OFF
ON ON OFF
OFF OFF ON
ON OFF ON
Do not set this one
OFF ON ON
ON ON ON
Factory set value: Modbus/TCP
8
OFF Fixed
4. After setting is complete, install the MCU board.
5. Place the module mainframe opening on top of the mother block tab and snap the lower part of
module mainframe on to the mother block. A snapping sound will be heard when module mainframe
is securely connected to mother block.
22
IMS01S01-E1
5. SETTING
5.2 IP Address Setting
Set an IP address of a H-LNK-B module.
Three types of IP address setting are available: “setting by Telnet,” “setting by Web browser” and “setting
by rotary switch.”
Confirm the IP address number to the network administrator of the network (LAN) to
which the H-LNK-B module is connected.
5.2.1 Setting by telnet
Set the IP address by the software “Telnet” attached to Windows.
Preparations before setting
When setting the IP address by Telnet, it is necessary to coincide the 1st to 3rd bytes and masking range of
the IP address of the client (computer) which starts Telnet with those of the IP address of the H-LNK-B
module.
1. Connect the H-LNK-B module and client, and then turn on the power.
For wiring procedure, see 4. WIRING (P. 11).
2. The IP address of the H-LNK-B module is set to a factory set value of “192.168.1.1.” As it is
necessary to coincide the 1st to 3rd byte values of this IP address with those of the IP address of the
client, change the IP address of the client to “192.168.1.” (: Any value in the range of 0 to 255,
but other than 1).
3. As the subnet mask of the H-LNK-B module is “255.255.255.0,” also change the subnet mask of the
client to “255.255.255.0.”
After the IP address of the server is set, return the present IP address of the client to the original
address or change to the address meeting the network to be connected.
It is possible to set the IP address of the H-LNK-B module using the client already connected to
the network. However, as the IP address of the client is changed, that client is disconnected from
the network so far connected.
In addition, when setting the IP address by this method, confirm to the network administrator
whether or not no problem arises.
IMS01S01-E1
23
5. SETTING
Setting example
An example of setting the IP address to “192.168.1.3” is shown in the following.
1. Display the MS-DOS prompt (command prompt); enter the following command and then press the
Enter key.
C:¥>telnet 192.168.1.1 9999
2. Device information on the module (H-LNK-B module) whose IP address is “192.168.1.1” is
displayed. Finally, as the message “Press Enter to go into Setup Mode” is displayed, press the Enter
key to go into Setup Mode.
MAC address 00204A8064BD
Software version 01.3 (030612) XPTE
Press Enter to go into Setup Mode
If the timing of pressing the Enter key is late, the message “Connection with Host was cut
off” is displayed and thus the client is disconnected from the H-LNK-B module. Therefore if
the message “Press Enter to go into Setup Mode” is displayed, immediately press the Enter
key. If disconnected, try again from “1.”
3. If entered into Setup Mode, the present Ethernet information is displayed.
Finally, eight choices are displayed as “Change Setup:.” Therefore enter “0” after “Your choice ?”
and then press the Enter key.
*** basic parameters
Hardware: Ethernet TPI
IP addr 192.168.1.1, no gateway set,netmask 255.255.255.000
*************** Security ***************
SNMP is enabled
SNMP Community Name: public
Telnet Setup is enabled
TFTP Download is enabled
Port 77FEh is enabled
Enter “0” (Server configuration),
and press the Enter key.
6 Security
7 Factory defaults
8 Exit without save
9 Save and exit Your choice ? 0
24
IMS01S01-E1
4. Selecting “0: Server configuration” makes ready to set the IP address.
Enter the IP address one byte by one byte.
As the following display appears, enter “192” into the first byte and then press the Enter key.
IP Address : (192) 192
Next, enter “168” into the second byte and then press the Enter key.
IP Address : (192) 192.(168) 168
Enter “1” into the third byte and then press the Enter key.
IP Address : (192) 192.(168) 168.(001) 1
Enter “3” into the fourth byte and then press the Enter key.
5. SETTING
IP Address : (192) 192.(168) 168.(001) 1.(001) 3
5. After the IP address is entered, the following display appears. Therefore press the Enter key to
proceed to the next.
IP Address : (192) 192.(168) 168.(001) 1.(001) 3
Set Gateway IP Address (N) N
In addition, as one line is displayed, press the Enter key to proceed to the next.
IP Address : (192) 192.(168) 168.(001) 1.(001) 3
Set Gateway IP Address (N) N
Netmask: Number of Bits for Host Part (0=default) (16)
Further, as more one line is displayed, press the Enter key to proceed to the next.
IP Address : (192) 192.(168) 168.(001) 1.(001) 3
Set Gateway IP Address (N) N
Netmask: Number of Bits for Host Part (0=default) (16)
Change telnet config password (N) N
IMS01S01-E1
25
5. SETTING
6. As “Change Setup:” is displayed again, enter “9” after “Your choice ?” and then press the Enter key.
Enter “9” (Save and exit),
and press the Enter key.
7 Factory defaults
8 Exit without save
9 Save and exit Your choice ? 9
7. “Parameters stored ...” is displayed and thus the setting is finished.
Parameters stored ...
Connection with Host was cut off
26
IMS01S01-E1
5. SETTING
5.2.2 Setting by the web browser
It is possible to set the IP address by using the Web browser (such as Internet Explorer).
Preparations before setting
When setting the IP address by Web browser, it is necessary to coincide the 1st to 3rd bytes and masking
range of the IP address of the client (computer) which starts Web browser with those of the IP address of
the H-LNK-B module.
1. Connect the H-LNK-B module and client, and then turn on the power.
For wiring procedure, see 4. WIRING (P. 11).
2. The IP address of the H-LNK-B module is set to a factory set value of “192.168.1.1.” As it is
necessary to coincide the 1st to 3rd byte values of this IP address with those of the IP address of the
client, change the IP address of the client to “192.168.1. ” (: Any value in the range of 0 to 255,
but other than 1).
3. As the subnet mask of the H-LNK-B module is “255.255.255.0,” also change the subnet mask of the
client to “255.255.255.0.”
After the IP address of the server is set, return the present IP address of the client to the original
address or change to the address meeting the network to be connected.
It is possible to set the IP address of the H-LNK-B module using the client already connected to
the network. However, as the IP address of the client is changed, that client is disconnected from
the network so far connected.
In addition, when setting the IP address by this method, confirm to the network administrator
whether or not no problem arises.
IMS01S01-E1
27
5. SETTING
Setting example
An example of setting the IP address to “192.168.1.3” is shown in the following.
1. Start the Web browser; enter the present IP address “192.168.1.1” into the address bar and then press
the Enter key.
2. The initial setting applet starts. “Selected Channel: 1” is displayed on the main display with “Port
Properties” selected on the Menu display on the left side of the screen.
Under this condition, click the Server Properties button on the Menu display.
Do not change the contents of “Selected Channel: 1.” If changed, device failure or error
may result.
Click
28
IMS01S01-E1
3. Display the Server Properties screen.
Set “192.168.1.3” in IP Address.
Do not change any items other than the IP Address. If so, device failure or error may
result.
4. Clicking the Update Settings button on the Menu display updates the setting to display the following
message.
5. Enter the new IP address “192.168.1.3” into the address bar as instructed by message and then press
Click
the Enter key. Thus, a new IP address setting screen appears to end the setting.
Set
192.168.1.3
5. SETTING
IMS01S01-E1
29
5. SETTING
5.2.3 Setting by the rotary switch
It is possible to set the IP address by rotary switch with Ethernet not connected.
Rotary switches used are “SW1,” “SW2” and “SW3” on the front side of the module.
Factory set value of an IP address of a H-LNK-B module is “192.168.1.1.”
Setting example
IP address setting switch
SW1: For IP address setting
0: None
1: First byte setting of IP address
2: Second byte setting of IP address
3: Third byte setting of IP address
4: F
ourth byte
5: Decision of IP address setting
6 to F: None
SW2: For high-order digit setting
0 to F × 10h
SW3: For low-order digit setting
0 to F × 1h
setting of IP address
An example of setting the IP address to “192.168.1.3” is shown in the following.
1. Setting preparations
Set SW1 to “1” with the power turned off.
2. First byte setting mode
Turning the power on goes to the first byte setting mode.
The RUN lamp goes on and the FAIL lamp goes off if set to the first byte setting mode.
SW1
RX
FAIL
RUN
TX
Setting: 1
FAIL lamp: OFF
RUN lamp: ON
3. Input the first byte “192”
Enter the first byte (most significant byte) by SW2 and SW3.
As the first byte (most significant byte) is entered with “192,” this number corresponds to a
hexadecimal number of “C0.”
Conduct the following setting with SW2 and SW3.
SW2
SW3
30
Setting: C
Setting: 0
IMS01S01-E1
4. Second byte setting mode
Change SW1 to “2.”
The RUN lamp goes off and the FAIL lamp goes on if set to the second byte setting mode.
5. SETTING
SW1
RX
FAIL
RUN
TX
FAIL lamp: ON
RUN lamp: OFF
Setting: 2
5. Input the second byte “168”
Enter the second byte by SW2 and SW3.
As the second byte is entered with “168,” this number corresponds to a hexadecimal number of “A8.”
Conduct the following setting with SW2 and SW3.
SW2
Setting: A
SW3
Setting: 8
6. Third byte setting mode
Change SW1 to “3.”
The RUN lamp goes on and the FAIL lamp goes off if set to the third byte setting mode.
SW1
RX
FAIL
RUN
TX
FAIL lamp: OFF
RUN lamp: ON
7. Input the third byte “1”
Enter the third byte by SW2 and SW3.
As the third byte is entered with “1,” this number corresponds to a hexadecimal number of “01.”
Conduct the following setting with SW2 and SW3.
IMS01S01-E1
Setting: 3
SW2
Setting: 0
SW3
Setting: 1
31
5. SETTING
A
8. Fourth byte setting mode
Change SW1 to “4.”
The RUN lamp goes off and the FAIL lamp goes on if set to the fourth byte setting mode.
SW1
RX
FAIL
RUN
TX
FAIL lamp: ON
RUN lamp: OFF
Setting: 4
9. Input the fourth byte “3”
Enter the fourth byte by SW2 and SW3.
As the fourth byte is entered with “3,” this number corresponds to a hexadecimal number of “03.”
Conduct the following setting with SW2 and SW3.
SW2
Setting: 0
SW3
Setting: 3
10. Decision of the IP address
Change SW1 to “5.”
After a lapse of a few seconds, the RUN lamp lights and the IP address is established.
The FAIL and RUN lamps flash until the IP address is established
SW1
RX
FAIL
RUN
TX
FAIL lamp: Flashing
RUN lamp: Flashing
Setting: 5
few seconds later
FAIL lamp: OFF
RUN lamp: Flashing
(State of being lit if abnormally ended.)
11. Power OFF
If the power is turned off once and turned on again, operation starts at the preset IP address.
If incorrect IP address setting operation is conducted, turn the power off once and then try the
setting again from the beginning. However, if no Procedure 10 (IP address establishment)
operation is performed, it is possible to try again from Procedure 2 after SW1 is returned to "0"
once without turning off the power.
Setting the IP address to “0.0.0.0” results in the automatic IP address acquisition mode, thereby
automatically acquiring the IP address from the address server on LAN. However, the special
tool (Device Installer produced by LANTRONIX) is required for checking the IP address thus
acquired.
32
IMS01S01-E1
t
6. COMMUNICATION PROTOCOL
As an Ethernet communication protocol, the H-LNK-B module supports Modbus/TCP and No-protocol.
6.1 Modbus/TCP
Modbus/TCP is an open field network provided with the Modbus protocol on the TCP/IP protocol of
Ethernet.
The data request side is called “client” (such as computer) and the data response (supply) side is called
“server” (H-LNK-B module).
<Procedure for data distribution>
Client
(Host computer)
Client
(Host computer)
6.1.1 Message configuration
1. Establishment of the TCP/IP connection
2. Issuance of a request
Server
(H-LNK-B)
4. Return of collected
data to the client as
a response
SR Mini HG
control unit
3. Collection of data on the
SR Mini HG control uni
in response to the request
Modbus ADU (Application Data Unit) on TCP/IP is in the following configuration.
Modbus TCP/IP ADU
MBAP Header
7 bytes
PDU (Protocol Data Unit)
2 to 255 bytes
Function code
1 byte
Data
1 to 254 bytes
Transaction
Identifier
2 bytes
Protocol
Identifier
2 bytes
Data Length
2 bytes
Unit Identifier
1 byte
IMS01S01-E1 33
6. COMMUNICATION PROTOCOL
MBAP Header
MBAP (Modbus Application Protocol) header contains the following fields: Transaction Identifier,
Protocol Identifier, Data Length and Unit Identifier.
Fields Length Request (Client) Response (Server)
Transaction
Identifier
2 bytes
Unused
However, data corresponding to
Returns data from the client as is
two bytes is sent
Protocol
Identifier
Data Length 2 bytes
Unit Identifier 1 byte
2 bytes
“0” fixed
(Modbus protocol = 0)
The total number of bytes of
Unit Identifier and PDU
(256 bytes max.)
Send the unit address of the
Returns data from the client as is
The total number of bytes of
Unit Identifier and PDU
(256 bytes max.)
Returns data from the client as is
communicating SR Mini HG.
(Value obtained by adding “1” to
the H-PCP module rotary switch
setting)
However, unused if in unit ID
fixed mode *. (Send any data
corresponding to 2 bytes.)
* See 6.1.5 Unit ID fixed mode
(P. 43)
PDU
PDU (Protocol Data Unit) consists of two blocks: function codes and data.
Exception code
01H: Illegal function code
02H: Illegal register address
03H: Illegal data value
04H: Server failure
34
IMS01S01-E1
6.1.2 Function code
Function code contents
Function code
03H
06H
08H
10H
Read holding registers
Write single register Set value, PID constants, event set value, etc.
Diagnostics (loopback test) Loopback test
Write multiple registers Set value, PID constants, event set value, etc.
Function Contents
Message (PDU) length of each function [Unit: byte]
Function code Function
03H
06H
08H
10H
Read holding registers
Write single register
Diagnostics (loopback test)
Write multiple registers
6.1.3 Server (H-LNK-B) responses
6. COMMUNICATION PROTOCOL
Measured value, Control output value, Current
transformer input value, Event status, etc.
Request message Response message
Min Max Min Max
5 5 4 252
5 5 5 5
5 5 5 5
8 252 5 5
Normal response
• In the response message of the read holding registers, the server (H-LNK-B) returns the “Function
code,” “Number of data items” and the “Read out data” as the response message.
• In the response message of the write single register and diagnostics (loopback test), the server
(H-LNK-B) returns the same message as the request message.
• In the response message of the write multiple registers, the server (H-LNK-B) returns the “Function
code,” the “Register address number” and the “Number of register” as the response message.
IMS01S01-E1
35
6. COMMUNICATION PROTOCOL
Defective message response
• If the request message from the client is defective, except for
Function code
transmission error, the server (H-LNK-B) returns the exception
response message without any action.
• If the self-diagnostic function of the server (H-LNK-B) detects an
error, the server will return an exception response message to all
Exception code
Exception response
message
request messages.
• The function code of each exception response message is obtained by adding “80H” to the function
code of the request message.
Exception
code
01H
02H
03H
Illegal function code An unsupported function code was specified
Illegal register address When the mismatched register address is specified.
Illegal data value
Contents Causes
• The number of specified data points was out of the
following range during data read or write.
Function code 03H: 1 to 125
Function code 10H: 1 to 123
• When the data written exceeds the setting range
04H
Server failure State under which the server cannot normally respond
(An error occurred in the server)
Exception code priority order
No response in PDU data length error > 04H > 01H, 02H or 03H
• Order when reading/writing the register contents
When there is 02H or 03H only for read processing: 01H > 04H > 03H > 02H
• Order when out of the setting range
For 03H when out of the setting range: 01H > 02H > 04H > 03H
No response
The server (H-LNK-B) ignores the request message and does not respond when:
• The IP address does not coincide.
• The server (H-LNK-B) is not connected to the network.
• The PDU (Protocol Data Unit) data length is abnormal.
When the PDU data length specified by the request message does not coincide with the number of bytes
received as one TCP packet.
H-LNK-B determines whether or not communication messages correspond to one packet by time-out
(approx. 12 ms) between characters.
36
IMS01S01-E1
6. COMMUNICATION PROTOCOL
N
6.1.4 Message format
Read holding registers [03H]
The request message specifies the starting register address number and quantity of register addresses to be
read.
The contents of the registers are entered in the response message as data, divided into two parts: the
high-order eight bits and low-order eight bits, arranged in the order of the register numbers.
Example: The contents of the three registers from 0000H to 0002H are the read out.
Request message [Client]
Transaction Identifier High 00H
Low 00H
Protocol Identifier High 00H
Low 00H
Data Length High 00H
Low 06H
Unit Identifier 01H
Function code 03H
Register address High 00H
Low 00H
Quantity High 00H
(Number of words) Low 03H
MBAP Header
First register address
The setting must be between 1 (0001H) and
125 (007DH).
Normal response message [Server]
Transaction Identifier High 00H
Low 00H
Protocol Identifier High 00H
Low 00H
MBAP Header
Data Length High 00H
Low 09H
Unit Identifier 01H
Function code 03H
Number of data (byte) 06H
umber of registers× 2
First register High 00H
contents Low 78H
Next register High 00H
contents Low 00H
Next register High 00H
contents Low 14H
IMS01S01-E1
37
6. COMMUNICATION PROTOCOL
Exception response message [Sever]
Transaction Identifier High 00H
Low 00H
Protocol Identifier High 00H
Low 00H
MBAP Header
Data Length High 00H
Low 03H
Unit Identifier 01H
80H + Function code
Exception code 03H
83H
When the data exceeds the setting range
38
IMS01S01-E1
6. COMMUNICATION PROTOCOL
Write single register [06H]
The request message specifies data to be written into the designated register.
Write data items are arranged in the request message in order starting from the smallest register address
number. In addition, each register address is assigned in the order of high-order eight bits and low-order
eight bits, respectively.
Example: When 100 (64H) is written to the register 0010H
Request message [Client]
Transaction Identifier High 00H
Low 00H
Protocol Identifier High 00H
Low 00H
Data Length High 00H
Low 06H
Unit Identifier 01H
Function code 06H
Register address High 00H
Low 10H
Write data High 00H
Low 64H
Normal response message [Server]
Transaction Identifier High 00H
Low 00H
Protocol Identifier High 00H
Low 00H
Data Length High 00H
Low 06H
Unit Identifier 01H
Function code 06H
Register address High 00H
Low 10H
Write data High 00H
Low 64H
Exception response message[Sever]
Transaction Identifier High 00H
Low 00H
Protocol Identifier High 00H
Low 00H
Data Length High 00H
Low 03H
Unit Identifier 01H
80H + Function code
86H
Exception code 03H
MBAP Header
Any data within the range
Contents will be the same as request message data
MBAP Header
When the data exceeds the setting range
IMS01S01-E1
39
6. COMMUNICATION PROTOCOL
Diagnostics (Loopback test) [08H]
The client's request message will be returned as the response message from the server.
This function checks the communication system between the client and server.
Example: Loopback test
Request message [Client]
Transaction Identifier High 00H
Low 00H
Protocol Identifier High 00H
Low 00H
Data Length High 00H
Low 06H
Unit Identifier 01H
Function code 08H
Test code High 00H
Low 00H
Data High 1FH
Low 34H
MBAP Header
Test code must be set to 00H
Any pertinent data
Normal response message [Server]
Transaction Identifier High 00H
Low 00H
Protocol Identifier High 00H
Low 00H
Data Length High 00H
Low 06H
Contents will be the same as request message data
Unit Identifier 01H
Function code 08H
Test code High 00H
Low 00H
Data High 1FH
Low 34H
Exception response message[Sever]
Transaction Identifier High 00H
Low 00H
Protocol Identifier High 00H
Low 00H
MBAP Header
Data Length High 00H
Low 03H
Unit Identifier 01H
80H + Function code
Exception code 06H
88H
When server is busy
40
IMS01S01-E1
6. COMMUNICATION PROTOCOL
N
Write multiple registers [10H]
Each data is written to registers in specified quantities starting from the specified register address.
Write data items are arranged in the request message in order starting from the smallest register address
number. In addition, each register address is assigned in the order of high-order eight bits and low-order
eight bits, respectively.
Example: When 100 (64H) and 30 (1EH) are written to the register 0010H and 0011H (two in total)
Request message [Client]
Transaction Identifier High 00H
Low 00H
Protocol Identifier High 00H
Low 00H
Data Length High 00H
Low 0BH
Unit Identifier 01H
Function code 10H
Register address High 00H
Low 10H
Quantity High 00H
(Number of words) Low 02H
Number of data (byte) 04H
Data to first High 00H
register Low 64H
Data to next High 00H
register Low 1EH
MBAP Header
First register address
The setting must be between 1 (0001H) and
123 (007BH).
umber of registers × 2
Normal response message [Server]
Transaction Identifier High 00H
Low 00H
Protocol Identifier High 00H
Low 00H
MBAP Header
Data Length High 00H
Low 06H
Unit Identifier 01H
Function code 10H
Register address High 00H
Low 10H
First register address
Quantity High 00H
(Number of words) Low 02H
IMS01S01-E1
41
6. COMMUNICATION PROTOCOL
Exception response message [Sever]
Transaction Identifier High 00H
Low 00H
Protocol Identifier High 00H
Low 00H
MBAP Header
Data Length High 00H
Low 03H
Unit Identifier 01H
80H + Function code
Exception code 03H
90H
When the data exceeds the setting range
42
IMS01S01-E1
6. COMMUNICATION PROTOCOL
6.1.5 Unit ID fixed mode
The unit ID fixed mode is used if the client cannot freely specify any unit ID in the Modbus/TCP packet.
If in unit ID fixed mode, the number of SR Mini HG control units connectable to the
H-LNK-B module is only one.
Setting procedure
1. Turn off the power supply.
2. Set Nos. 5, 6 and 7 of the DIP switch inside the H-LNK-B module to OFF [Protocol: Modbus/TCP
(factory set value)].
For setting procedure of the DIP switch, see 5.1 DIP Switch Setting (P. 21).
3. Set SW1 at the front of the H-LNK-B module to “F.” Next, set the unit ID by SW2 and SW3. Set the
unit ID to the same number as the unit address (rotary switch number) of the H-PCP module in the SR
Mini HG.
SW1
SW2
SW3
SW1
SW2
SW3
Set “F”
High-order digit
setting
(0 to F × 10h)
Set “0”
Low-order digit
setting
(0 to F × 1h)
Unit address
setting switch
Set to the
same address
4. Turning on the power starts communicating in unit ID fixed mode.
H-PCP module
IMS01S01-E1
43
6. COMMUNICATION PROTOCOL
6.2 No-Protocol
When No-protocol is used, it is possible to communicate with the SR Mini HG controller with only the
communication line set to Ethernet without changing the software (RKC communication or Modbus) on the
computer side already under operation by setting the virtual COM port to such higher-level equipment as a
host computer, etc.
Communication outline
The TCP packet received from the host computer is sent to the SR Mini HG controller without any
modification via controller communication and data received from the SR Mini HG controller side is sent
without any modification to the host computer as a TCP packet.
Host computer
Communication protocol:
RKC communication or
Modbus
Ethernet communication line
(Sending/receiving by TCP packet)
Virtual COM port
SR Mini HG control unit
Controller communication
Communication protocol:
RKC communication or
Modbus
Power supply/CPU module
H-PCP-J
Function modules
Ethernet communication module
H-LNK-B
Communication requirements
• TCP packet: 256 bytes or less (Characters exceeding 256 bytes are all discarded.)
• Communication with such higher-level equipment as a host computer, etc. is of the request & response
type and should be via half-duplex communication. (RKC communication and Modbus fall into this
category.)
44
IMS01S01-E1
6. COMMUNICATION PROTOCOL
Setting of virtual COM port
The virtual COM port is set by using the following software which can be downloaded from the Internet.
• DeviceInstaller (by LANTRONIX)
• Com Port Redirector (by LANTRONIX)
LANTRONIX URL: http://www.lantronix.com
Operating environment
− OS: Windows2000
− Ethernet implementation
− It is assumed that communication (IP address setting, etc.) with XPort (Ethernet connector of H-LNK-B)
has been established.
Setting procedure
The TCP port is set by using the software already downloaded from the Internet.
1. Start XPort Web-Manager by using the DeviceInstaller Web button or Web browser (Internet
Explorer, etc.).
2. Set “Local Port” in the Dedicated Connection setting in the range of “14000 to 14009.”
(For Modbus/TCP: Fixed to 502)
IMS01S01-E1
Set in the range of
“14000 to 14009.”
45
6. COMMUNICATION PROTOCOL
3. Start running the ComPort Redirector program produced by LANTRONIX to set the COM port and
the XPort IP address and port number by “AddIP.” Set a port number to any number in the range of
“3000 to 3009.”
As a port number, set the value obtained by subtracting “11000” from the “Local Port”
number set in Procedure 2.
Set the COM port
Press the “Add IP” button
to set the IP address and
port number by “IP Service
Setup.”
Set all of the port values using decimal numbers.
4. Thus, it becomes possible conduct communication by No-protocol used with the Ethernet
communication line.
46
IMS01S01-E1
6. COMMUNICATION PROTOCOL
6.3 Ethernet Response Time
The maximum Ethernet response time is obtained as follows.
Maximum Ethernet response time (Recovery processing time-out time during communication failure)
If the following sending is made from the host computer in response to the sending from the host
computer before the H-LNK-B responds (within Ethernet response time), the sending message
becomes invalid and is discarded.
Example: Response time when the number of SR Mini HG controller temperature control points
corresponds to 8 channels
Requirements: • Delay time of Ethernet: 0
• Communication speed of controller communication: 38400 bps
Response time
= [0 (Delay time of Ethernet) + Approx. 25 ms (Response time of controller communication) × 2]
= Approx. 50 ms
= Ethernet delay time + Controller communication response time × 2
IMS01S01-E1
47
7. COMMUNICATION DATA LIST
• Name
: Item stored in the memory area.
[ ]: The functional module name that data becomes valid is written.
• Attributes
RO: Read only SR Mini HG controller → Host computer
R/W: Read and Write SR Mini HG controller ↔ Host computer
WO: Write only SR Mini HG controller ← Host computer
• Structure
C: Data of each channel L: Data of each event input losic circuit
M: Data of each module U: Data of each unit address
For data configuration, data processing precautions and identifier of RKC communication, see
H-PCP-J Instruction Manual (IMS01J02-E), H-PCP-A Z-1021 Instruction Manual
(IMSRM65-E) and SR Mini HG SYSTEM Communication Instruction Manual
(IMSRM09-E).
7.1 Communication Data List of H-PCP-J Module
Modbus
Name
address
HEX DEC
Temperature measured value
(PV)
[H-TIO-, H-CIO-A]
0000
•
•
•
0013
Moter speed measured value
[H-SIO-A]
Heat-side manipulated output
value
[H-TIO-, H-CIO-A,
H-SIO-A]
Cool-side manipulated output
value
[H-TIO-, H-CIO-A]
Current tramsformer input
measured value 1
[H-TIO-A/C/D]
Current tramsformer input
measured value 2
(CH1 to CH20) [H-CT-A]
Status
[H-TIO-, H-CIO-A,
H-SIO-A]
0014
•
•
•
0027
0028
•
•
•
003B
003C
•
•
•
004F
0050
•
•
•
0063
0064
•
•
•
0077
Continued on the next page.
Attri-
0
19
•
•
•
Struc-
bute
ROC
ture
TC/RTD input: Within input range
Current (V)/Voltage (I) input:
Within display scale range
Data range
Within display scale range
20
ROC −0.5 to +105.0 %
•
•
•
39
40
ROC −0.5 to +105.0 %
•
•
•
59
60
ROC 0.0 to 100.0 A or 0.0 to 30.0 A
•
•
•
79
80
ROC 0.0 to 100.0 A or 0.0 to 30.0 A
•
•
•
99
100
ROC The respective channel status is assigned to each
•
•
•
119
Current tramsformer (CT) input measured value of
the H-TIO-A/C/D module
Current tramsformer (CT) input measured value of
the H-CT-A module
bit in the holding register.
Bit data
bit 0: Alarm 1 state
bit 1: Alarm 2 state
bit 2: Burnout state
bit 3: Heater break alarm state
OR operation of the H-TIO-A/C/D module
and H-CT-A module
bit 4: Control leep break alarm (LBA) state
bit 5: Temperature rise completion state
bit 6: Heat-side manipulated output state
bit 7 to 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 127]
For H-SIO-A module, only alarm 1 state (bit 0),
alarm 2 state (bit 1) and Heat-side manipulated
output state (bit 6) are effective.
Factory
set value
48 IMS01S01-E1
7. COMMUNICATION DATA LIST
Continued from the previous page.
Name
Temperature rise
completion state
Modbus
address
HEX DEC
Attri-
bute
Struc-
ture
0078 120 ROU 0: Rise not complete
1: Rise completed
Data range
Factory
set value
[H-TIO-, H-CIO-A]
Error code
[H-PCP-J]
0079 121 ROU 0: Operations normal
1: Backup data check error
2: RAM read/write error
3: System structure error
4: Internal communications error
5: A/D converter error
6: Adjustment data error
Comprehensive alarm state
[H-PCP-J]
007A 122 ROU The respective channel status is assigned to each bit
in the holding register.
Bit data
bit 0: Logical OR of alarm 1 state in all channels
bit 1: Logical OR of alarm 2 state in all channels
bit 2: Logical OR of burnout alarm state in all
channels
bit 3: Logical OR of heater break alarm state in all
channels
bit 4: Temperature rise completion state
bit 5: Logical OR of AI alarm 1 state in all
channels
bit 6: Logical OR of AI alarm 2 state in all
channels
bit 7: Logical OR of control loop break alarm state
in all channels
bit 8: Logical OR of TI alarm 1 state in all
channels
bit 9: Logical OR of TI alarm 2 state in all
channels
bit 10: Logical OR of TI burnout alarm state in all
channels
bit 11 to 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 2047]
Unused 007B
008B
Set value monitor
008C
[H-TIO-, H-CIO-A,
H-SIO-A]
Current tramsformer input
009F
00A0
measured value 2
(CH21 to CH60)
00C7
123
•
•
•
•
•
•
139
140
•
•
•
•
•
•
ROC TC/RTD input: Within input range
•
•
•
159
160
ROC 0.0 to 100.0 A or 0.0 to 30.0 A
•
•
•
199
Current/Voltage input:
Within display scale range
Current tramsformer (CT) input measured value of
the H-CT-A module
[H-CT-A]
Temperature set value
(SV)
[H-TIO-, H-CIO-A]
00C8
00DB
200
•
•
•
•
•
•
R/WC
219
TC/RTD input:
Within input range (Within setting limiter)
Current/Voltage input:
Within display scale range (Within setting limiter)
The position of the decimal point differs depending
on the input range.
Motor speed set value
[H-SIO-A]
Within display scale range (Within setting limiter)
The position of the decimal point differs depending
on the input range.
Continued on the next page.
0
0
IMS01S01-E149
7. COMMUNICATION DATA LIST
Continued from the previous page.
Name
PID/AT transfer
[H-TIO-, H-CIO-A,
H-SIO-A]
Heat-side proportional
band
[H-TIO-, H-CIO-A,
H-SIO-A]
Cool-side proportional
band
[H-TIO-, H-CIO-A]
Integral time
[H-TIO-, H-CIO-A,
H-SIO-A]
Derivative time
[H-TIO-, H-CIO-A,
H-SIO-A]
Overlap/deadband
[H-TIO-, H-CIO-A]
Control response
parameters
[H-TIO-, H-CIO-A,
H-SIO-A]
Modbus
address
HEX DEC
00DC
•
•
•
00EF
00F0
•
•
•
0103
0104
•
•
•
0117
0118
•
•
•
012B
012C
•
•
•
013F
0140
•
•
•
0153
0154
•
•
•
0167
Attri-
bute
220
R/WC 0: PID control operation
•
•
•
239
240
R/WC 0.1 to 1000.0 % of span H-TIO-,
•
•
•
259
260
R/WC 0.1 to 1000.0 % of span 3.0
•
•
•
279
280
R/WC 1 to 3600 seconds H-TIO-,
•
•
•
299
300
R/WC 0 to 3600 seconds (0: PI action) H-TIO-,
•
•
•
319
320
R/WC −10.0 to +10.0 % of span 0.0
•
•
•
339
340
R/WC 0: Slow
•
•
•
359
* Heat control (H-TIO-/H-CIO-A): 0
Heat/cool control (H-TIO-/H-CIO-A): 2
Position proportioning control (H-TIO-K): 0
Speed control (H-SIO-A): 0
Struc-
ture
Data range
1: AT (Autotuning) operation
1: Medium
2: Fast
In order to perform PID control by using the fuzzy
function, specify “Fast.” The fuzzy function is
effective to restrict overshoot or undershoot occurring
at operation start, or resulting from set value changes.
(Fuzzy function correspond to H-TIO-P/R module
only.)
Continued on the next page.
Factory
set value
0
H-CIO-A:
3.0
H-SIO-A:
300.0
H-CIO-A:
240
H-SIO-A:
2
H-CIO-A:
60
H-SIO-A:
0
0 *
50
IMS01S01-E1
Continued from the previous page.
Modbus
Name
address
HEX DEC
Alarm 1 set value
[H-TIO-, H-CIO-A,
H-SIO-A]
Alarm 2 set value
[H-TIO-, H-CIO-A,
H-SIO-A]
Heater break alarm
set value 1
[H-TIO-A/C/D]
Heater break alarm
set value 2
(CH1 to CH20)
[H-CT-A]
Operation mode transfer
[H-TIO-, H-CIO-A,
H-SIO-A]
Heat-side proportioning
cycle time
[H-TIO-, H-CIO-A]
Cool-side proportioning
cycle time
[H-TIO-, H-CIO-A]
a
Factory set value table of Alarm 1/Alarm 2 set value
Input type Alarm type Alarm 1 set value Alarm 2 set value
TC/RTD input
Current/voltage input
H-SIO-A
b
Relay contact output: 20 seconds
0168
•
•
•
017B
017C
•
•
•
018F
0190
•
•
•
01A3
01A4
•
•
•
01B7
01B8
•
•
•
01CB
01CC
•
•
•
01DF
01E0
•
•
•
01F3
Process high alarm Input range (high limit) Input range (high limit)
Process low alarm Input range (low limit) Input range (low limit)
Deviation high alarm, Deviation
high/low alarm, Band alarm
Deviation low alarm
No alarm function Input range (high limit) Input range (low limit)
Process high alarm 100.0 % 100.0 %
Process low alarm 0.0 % 0.0 %
Deviation high alarm, Deviation
high/low alarm, Band alarm
Deviation low alarm
No alarm function 100.0 % 0.0 %
Attri-
Struc-
bute
ture
360
R/WC
•
•
•
379
380
R/WC
•
•
•
399
400
R/WC 0.0 to 100.0 A or 0.0 to 30.0 A
•
•
•
419
420
R/WC 0.0 to 100.0 A or 0.0 to 30.0 A
•
•
•
439
440
R/WC 0: Unused
•
•
•
459
460
R/WC 1 to 100 seconds
•
•
•
479
480
R/WC 1 to 100 seconds
•
•
•
499
Voltage pulse output, Open collector output, Triac output: 2 seconds
7. COMMUNICATION DATA LIST
Data range
TC/RTD input:
Within input range or span range
Current/voltage input, H-SIO-A:
Within display scale range or span range
For the current tramsformer (CT) input of the
H-TIO-A/C/D module
For the current tramsformer (CT) input of the H-CT-A
module
If set to “Unused,” no control, monitor or alarm
monitor is performed.
1: Monitor
If set to “Monitor,” only the monitor is performed.
No control or alarm monitor is performed.
2: Alarm
If set to “Alarm,” monitor or alarm monitor is
performed. No control is performed.
3: Normal
Selected to normal mode to perform control,
monitor or alarm monitor.
Setting will be invalid in current/voltage output.
Setting will be invalid in current/voltage output and
heat control.
50 °C 50 °C
−50 °C −50 °C
50 % 50 %
−50 % −50 %
Continued on the next page.
Factory
set value
See Factory
set value
table of
Alarm 1/
Alarm 2
set value
a
0.0
0.0
3
b
20
b
20
IMS01S01-E1
51
7. COMMUNICATION DATA LIST
Continued from the previous page.
Name
Auto/Manual transfer
[H-TIO-, H-CIO-A]
Manual output value
[H-TIO-, H-CIO-A]
Modbus
address
HEX DEC
01F4
•
•
•
0207
0208
•
•
•
021B
Attri-
Struc-
bute
ture
500
R/WC 0: Auto
•
•
•
519
520
R/WC −5.0 to +105.0 %
•
•
•
539
1: Manual
Setting will be invalid in ON/OFF control and
heat/cool control.
Setting will be invalid in ON/OFF control and
heat/cool control.
Data range
H-TIO-C/D [Z-1017 specification]:
−105.0 to 0.0 % (cool-side)
0.0 to +105.0 % (heat-side)
LBA use selection
[H-TIO-, H-CIO-A]
LBA time
[H-TIO-, H-CIO-A]
LBA deadband
[H-TIO-, H-CIO-A]
PV bias
[H-TIO-, H-CIO-A,
H-SIO-A]
021C
•
•
•
022F
0230
•
•
•
0243
0244
•
•
•
0257
0258
•
•
•
026B
540
R/WC 0: Unused
•
•
•
1: Used
559
560
R/WC 1 to 7200 seconds 480
•
•
•
579
580
R/WC Input span
•
•
•
599
600
R/WC −5.00 to +5.00 % of span
•
•
•
619
The position of the decimal point differs depending
on the input range.
ZK-1103 specification:
−Input span to +Input span
Unit (°C, °F, etc.) and decimal point position (No
decimal place, One decimal place, Two decimal
places or Three decimal places) depends on input
range type.
Temperature rise
completion range
[H-TIO-, H-CIO-A]
Temperature rise
completion trigger
[H-TIO-, H-CIO-A]
026C
•
•
•
027F
0280
•
•
•
0293
620
R/WC 1 to 10 °C or 1 to 20 °F
•
•
•
639
640
R/WC 0: Unused
•
•
•
659
The position of the decimal point differs depending
on the input range.
1: Used
Do not set “1: Used” in H-TIO-H/J module and
H-SIO-A module, because temperature rise
b
completion is not judged.
CT channel setting
(CH1 to CH20)
[H-CT-A]
0294
•
•
•
02A7
660
R/WC 0 to 20 (0: Unused)
•
•
•
679
Allocates the channels for H-TIO- module to the
input channels of H-CT-A module.
The factory set
value varies
depending
on the
specifications
when ordering.
Unused 02A8
02BB
Control RUN/STOP
02BC 700 R/WU 0: Control STOP
transfer
[H-PCP-J]
a
TC/RTD input: 10 °C or 20 °F
Current/voltage input, H-SIO-A: 10 % of display scale
b
If the channel of each of the H-TIO-H/J and H-SIO-A modules is set “1: Used,” it does no reach the completion of
680
•
•
•
•
•
•
699
1: Control RUN
temperature rise. As a result, the state of this completion (control unit) which is judged by performing the OR operation of
all the channels cannot be attained, thereby continuing the incompletion of temperature rise.
Continued on the next page.
Factory
set value
0
0.0
0
0
0.00
ZK-1103:
0
10 a
0
0
52
IMS01S01-E1
7. COMMUNICATION DATA LIST
Continued from the previous page.
Name
Memory area number
Modbus
address
HEX DEC
02BD 701 R/WU 1 to 8 1
Attribute
Struc-
ture
Data range
[H-TIO-, H-CIO-A,
H-SIO-A]
Temperature rise
02BE 702 R/WU 0 to 360 minutes 0
completion soak time
[H-TIO-, H-CIO-A]
Module initialization *
[H-PCP-J]
02BF 703 R/WU 0: Normal state (Initialization is not executed)
1: Initialize only the new module
(Only modules which are not recognized by the
H-PCP-J module are initialized)
2: Initialize all modules
Returns to 0 after the module is initialized.
Alarm interlock release
02C0 704 WOU 1: Release (1 only)
[H-TIO-, H-CIO-A,
H-TI-, H-AI-]
Unused 02C1
02CF
CT channel setting
02D0
(CH21 to CH60)
[H-CT-A]
Cascade ON/OFF
02F7
02F8
[H-CIO-A]
030B
Cascade gain
030C
[H-CIO-A]
031F
Cascade bias
0320
[H-CIO-A]
0333
Positioning output neutral
0334
zone
[H-TIO-K]
Motor time
0347
0348
[H-TIO-K]
035B
705
•
•
•
•
•
•
719
720
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
R/WC 0 to 20 (0: Unused)
•
•
•
759
760
R/WC 0: OFF
•
•
•
779
780
R/WC −9.999 to +10.000
•
•
•
799
800
R/WC −99.99 to +100.00 %
•
•
•
819
820
R/WC 0.1 to 10.0 % of motor time 2.0
•
•
•
Allocates the channels for H-TIO- module to the
input channels of H-CT-A module.
1: ON
Setting will be valid in master channel.
As the cascade gain is valid only in the slave
channel, the polling or selecting of the same value is
made also in the master channel.
As the cascade bias is valid only in the slave
channel, the polling or selecting of the same value is
made also in the master channel.
839
840
•
•
•
R/WC 5 to 1000 seconds 10
•
•
•
859
* Initialize method for changing the module composition
To change module configuration, use the following procedures:
• When a module is added to the control unit............................................................. Initialize only the new module
• When a module is deleted from the control unit ...................................................... Initialize only the new module
• When a module is inserted (Added) between the modules in the control unit ......... Initialize all modules
• To change the arrangement of the modules in the control unit ................................ Initialize all modules
Note that when all modules are initialized all internal data of all modules are set to the
default values.
Continued on the next page.
Factory
set value
0
The factory set
value varies
depending
on the
specifications
when ordering.
Heat control (H-TIO-/H-CIO-A): 100.0 Heat/cool control (H-TIO-/H-CIO-A): 100.0
Position proportioning control (H-TIO-K): 100.0 Speed control (H-SIO-A): 100
b
Heat control (H-TIO-/H-CIO-A): 0.0 Heat/cool control (H-TIO-/H-CIO-A): 100.0
0473
940
•
•
•
•
•
•
999
1000
•
•
•
R/WC 0.0 to 100.0 % of span/minute 0.0
•
•
•
1019
1020
•
•
•
R/WC [Heat control, Position proportioning control and
0.0 to 100.0 %/second (0.0: OFF)
Setting will be invalid in ON/OFF control.
1079
1080
•
•
•
R/WC
•
•
•
1099
1100
•
•
•
•
•
•
R/WC Span 10000 or less
•
•
•
1119
1120
R/WC Span 10000 or less
•
•
•
1139
(Within −9999 to +10000)
The position of the decimal point differs depending
on Decimal point position setting.
(Within −9999 to +10000)
The position of the decimal point differs depending
on Decimal point position setting.
Position proportioning control (H-TIO-K): 0.0 Speed control (H-SIO-A): 0
Continued on the next page.
Factory
set value
0.0
100.0 a
0.0 b
0.0
H-TIO-H/J,
H-CIO-A:
100.0
H-SIO-A:
300
H-TIO-H/J,
H-CIO-A:
0.0
H-SIO-A:
0
54
IMS01S01-E1
Continued from the previous page.
Name
Digital filter
[H-TIO-, H-CIO-A,
H-SIO-A]
H-SIO-A control range
[H-SIO-A]
H-SIO-A input frequency
at full scale
[H-SIO-A]
H-SIO-A output scale high
[H-SIO-A]
H-SIO-A output scale low
[H-SIO-A]
H-SIO-A correction trigger
[H-SIO-A]
H-SIO-A correction actual
measured value
[H-SIO-A]
H-SIO-A measuring
method
[H-SIO-A]
H-SIO-A divide ratio
[H-SIO-A]
H-SIO-A gate time
[H-SIO-A]
H-SIO-A auto zero time
[H-SIO-A]
H-SIO-A open/closed loop
control transfer
[H-SIO-A]
H-SIO-A
Modbus
address
HEX DEC
0474
•
•
•
0487
0488
•
•
•
049B
049C
•
•
•
04AF
04B0
•
•
•
04C3
04C4
•
•
•
04D7
04D8
•
•
•
04EB
04EC
•
•
•
04FF
0500
•
•
•
0513
0514
•
•
•
0527
0528
•
•
•
053B
053C
•
•
•
054F
0550
•
•
•
0563
0564 1380 R/WU 1 to 255 seconds
Attri-
bute
1140
R/WC H-TIO-A/B/C/D/K/P
•
•
•
1159
1160
R/WC 0.00 to 50.00 % 10.00
•
•
•
1179
1180
R/WC 10 to 50000 Hz 130
•
•
•
1199
1200
R/WC H-SIO-A output scale low to 10000
•
•
•
1219
1220
R/WC −9999 to H-SIO-A output scale high
•
•
•
1239
1240
R/WC 0: Normal (Not executed)
•
•
•
1259
1260
R/WC Within display scale range
•
•
•
1279
1280
R/WC 0: Periodic computation method
•
•
•
1299
1300
R/WC 1 to 1000
•
•
•
1319
1320
R/WC 0.1 to 4.0 seconds
•
•
•
1339
1340
R/WC 1 to 100 seconds 5
•
•
•
1359
1360
R/WC 0: Closed loop control (PID control)
•
•
•
1379
alarm hold cancel time
[H-SIO-A]
Unused 0565
•
•
•
0577
1381
•
•
•
1399
Struc-
ture
7. COMMUNICATION DATA LIST
Data range
0 to 100 seconds (0: OFF)
H-TIO-E/F/G/H/J/R, H-CIO-A, H-SIO-A
0.0 to 100.0 seconds (0.0: OFF)
The position of the decimal point differs depending
on Decimal point position setting.
The position of the decimal point differs depending
on Decimal point position setting.
1: Correction executed
2: Correction canceled
Processing time of correction execution or cancel is
about 1 second. Do not turn OFF the power during
the processing time. In addition, maintain the setting
more than 0.5 second in order to let it recognize
modification in setting modification.
The position of the decimal point differs depending
on Decimal point position setting.
1: Pulse count method
Effective only for periodic computation method.
Effective only for pulse count method.
1: Open loop control
Setting will be invalid in no alarm hold action.
Continued on the next page.
Factory
set value
0 or 0.0
400
0
0
0
0
10
1.0
0
60
IMS01S01-E1
55
7. COMMUNICATION DATA LIST
Continued from the previous page.
Modbus
Name
Decimal point position
[H-TIO-H/J, H-CIO-A,
H-SIO-A]
Input range number
[H-TIO-, H-CIO-A,
H-SIO-A]
Setting limiter (high)
[H-TIO-, H-CIO-A,
H-SIO-A]
Setting limiter (low)
[H-TIO-, H-CIO-A,
H-SIO-A]
Input error determination
point (high)
[H-TIO-, H-CIO-A,
H-SIO-A]
Input error determination
point (low)
[H-TIO-, H-CIO-A,
H-SIO-A]
Action at input error (high)
[H-TIO-, H-CIO-A,
H-SIO-A]
Action at input error (low)
[H-TIO-, H-CIO-A,
H-SIO-A]
AT bias
[H-TIO-, H-CIO-A,
H-SIO-A]
ON/OFF control
differential gap (upper)
[H-TIO-, H-CIO-A,
H-SIO-A]
ON/OFF control
differential gap (lower)
[H-TIO-, H-CIO-A,
H-SIO-A]
Manipulated output value
at input error
[H-TIO-, H-CIO-A,
H-SIO-A]
address
HEX DEC
0578
•
•
•
058B
058C
•
•
•
059F
05A0
•
•
•
05B3
05B4
•
•
•
05C7
05C8
•
•
•
05DB
05DC
•
•
•
05EF
05F0
•
•
•
0603
0604
•
•
•
0617
0618
•
•
•
062B
062C
•
•
•
063F
0640
•
•
•
0653
0654
•
•
•
0667
Attri-
Struc-
bute
ture
1400
R/WC 0: No decimal place
•
•
•
1419
1420
R/WC H-TIO-A/B/C/D/K/P: 0 to 63
•
•
•
1439
1: One decimal place
2: Two decimal places
3: Three decimal places
H-TIO-E/F/G/R, H-CIO-A: 0 to 120
H-TIO-H/J, H-CIO-A: 0 to 12
H-SIO-A: 0 (Fixed)
Data range
If the input range number is changed, all of the
settings corresponding to the channels in the
relevant module return to the default values.
See Input range table(P. 75).
1440
•
•
•
1459
R/WC
TC/RTD input:
Setting limiter (low) to Input range (high)
Current/voltage input, H-SIO-A:
Setting limiter (low) to Display scale high
1460
•
•
•
1479
R/WC
TC/RTD input:
Input range (low) to Setting limiter (high)
Current/voltage input, H-SIO-A:
Display scale low to Setting limiter (high)
1480
•
•
•
1499
R/WC
TC/RTD input:
Within input range
Current/voltage input, H-SIO-A:
Within display scale range
1500
•
•
•
1519
R/WC
TC/RTD input:
Within input range
Current/voltage input, H-SIO-A:
Within display scale range
1520
R/WC 0: Normal control
•
•
•
1: Manipulated output value at input error
1539
1540
R/WC 0: Normal control
•
•
•
1: Manipulated output value at input error
1559
1560
R/WC Within ± input span range
•
•
•
1579
1580
R/WC 0.00 to 10.00 % of span 0.02
•
•
•
The position of the decimal point differs depending
on the input range.
1599
1600
R/WC 0.00 to 10.00 % of span 0.02
•
•
•
1619
1620
R/WC −5.0 to +105.0 %
•
•
•
1639
(Heat control, Position proportioning control, Speed
control)
−105.0 to +105.0 %
(Heat/cool control)
Factory
set value
H-TIO-H/J,
H-CIO-A: 1
H-SIO-A: 0
The factory set
value varies
depending
on the
specifications
when ordering.
Input range
(high)
Display scale
high
Input range
(low)
Display scale
low
Input range
(high)
Display scale
high
Input range
(low)
Display scale
low
0 *
0
0
0.0
* Heat control (H-TIO-/H-CIO-A): 0 Heat/cool control (H-TIO-/H-CIO-A): 1
Position proportioning control (H-TIO-K): 0 Speed control (H-SIO-A): 0
Continued on the next page.
56
IMS01S01-E1
7. COMMUNICATION DATA LIST
Continued from the previous page.
Name
Direct/Reverse action
selection
[H-TIO-, H-CIO-A,
H-SIO-A]
Modbus
address
HEX DEC
0668
•
•
•
067B
Attri-
Struc-
bute
ture
1640
R/WC 0: Direct action
•
•
•
1659
Data range
1: Reverse action
If the Direct/Reverse action selection is changed, all
of the settings corresponding to the channels in the
relevant module return to the default values.
Setting will be invalid in heat/cool control.
1660
Hot/Cold start selection
[H-TIO-, H-CIO-A,
H-SIO-A]
067C
•
•
•
068F
R/WC 0: Hot start
•
•
•
1679
At restarting
Operation mode
→ Same as mode before the power failure
Output value
→ Same as value before the power failure
1: Cold start
At restarting
Operation mode
→ Same as mode before the power failure
Output value
→ Output limiter (low)
Start determination point 1
[H-TIO-, H-CIO-A]
Control RUN/STOP
holding
2
[H-PCP-J]
0690
06A3
1680
•
•
•
R/WC 0.0 to 100.0 % of span
•
•
•
1699
(Deviation setting from the temperature set value)
Setting will be invalid in H-SIO-A module.
06A4 1700 R/WU 0: Not hold
Start-up from control stop status
1: Hold
Start-up from before the stop status
2: Start-up from control run status
Temperature rise
completion hold function
06A5 1701 R/WU 0: Not hold
1: Hold
[H-PCP-J]
Interval time setting
06A6 1702 R/WU 0 to 100 ms 1
COM. PORT1/
COM. PORT2
[H-PCP-J]
Interval time setting
06A7 1703 R/WU 0 to 100 ms 1
COM. PORT3
[H-PCP-J]
1
On restarting after power failure, if the temperature measured value (PV) is within the setting range by the start
determination points, the hot start will definitely be carried out. If the temperature measured value (PV) is outside this
range, the operation will begin with the start condition with was selected by the hot/cold start selection.
2
Action after power-ON differs depending on control RUN/STOP holding setting.
Control RUN/STOP holding
0: Not hold Same as mode before the power failure “0: Control STOP”
1: Hold Same as mode before the power failure Same as status before the power failure
2: Start-up from control run status “1: Monitor” mode
Operation mode transfer Control RUN/STOP transfer
However if the operation mode is set to
“0: Unused,” “0: Unused” remains unchanged.
Status after power-ON
Stopped until “1: Control RUN” is instructed from
the PLC or host computer.
Control before power failure is maintained even if no
PLC or host computer is connected.
“1: Control RUN”
However, no control is performed until the operation
mode is set to “3: Normal (perform control).”
Continued on the next page.
Factory
set value
The factory set
value varies
depending
on the
specifications
when ordering.
1
3.0
1
1
IMS01S01-E1
57
7. COMMUNICATION DATA LIST
Continued from the previous page.
Name
PLC scanning time setting a
Modbus
address
HEX DEC
06A8 1704 R/WU 0 to 3000 ms 10
Attri-
bute
Struc-
ture
Data range
[H-PCP-J]
Power supply frequency
selection
06A9 1705 R/WU 0: 50 Hz
1: 60 Hz
[H-PCP-J]
H-PCP-J module
DO de-energized selection
[H-PCP-J]
06AA 1706 R/WU The respective channel status is assigned to each bit
in the holding register.
Bit data
bit 0: CH1 (DO1)
bit 1: CH2 (DO2)
bit 2: CH3 (DO3)
bit 3: CH4 (DO4)
bit 4: CH5 (DO5)
bit 5: CH6 (DO6)
bit 6: CH7 (DO7)
bit 7: CH8 (DO8)
bit 8 to 15: Unused
Data 0: Energized 1: De-energized
[Decimal number: 0 to 255]
Number of HBA trigger
06AB 1707 R/WU 0 to 255 times 5
points
[H-CT-A]
PV bias unit selection
[H-TIO-, H-CIO-A,
06AC 1708 R/WU 0: % (of span)
1: Unit of input range
H-SIO-A]
Integral time limiter at AT
end
06AD 1709 R/WU 1 to 3600 seconds
Setting will be valid in heat/cool control.
[H-TIO-, H-CIO-A,
H-SIO-A]
Unused 06AE
06B7
Alarm 1 differential gap
06B8 1720 R/WU 0.00 to 10.00 % of span 0.10
1710
•
•
•
1719
•
•
•
[H-TIO-, H-CIO-A,
H-SIO-A]
Alarm 2 differential gap
06B9 1721 R/WU 0.00 to 10.00 % of span 0.10
[H-TIO-, H-CIO-A,
H-SIO-A]
Alarm 1 type selection
[H-TIO-, H-CIO-A,
H-SIO-A]
06BA 1722 R/WU 0: Process high alarm
1: Process low alarm
2: Deviation high alarm
3: Deviation low alarm
4: Deviation high/low alarm
5: Band alarm
a
Set the PLC scanning time (time of waiting for a response from the PLC) so as to adapt to the environment used.
6: No alarm function
Setting example: Set PLC scanning time to any value more than twice as long as the maximum scanning time of
PLC.
If PLC scanning time is extremely short (When at a factory set value of 10 ms as an example), the SR Mini HG SYSTEM
may detect the time-out not conducting normal communication processing.
The maximum scanning time of PLC differs depending on the CPU processing speed, I/O unit configuration and the user
program capacity of the PLC.
b
For the ZK-1103 specification, the factory set value is 1 (Unit of input range).
Continued on the next page.
Factory
set value
0
0
0 b
3600
The factory set
value varies
depending
on the
specifications
when ordering.
58
IMS01S01-E1
Continued from the previous page.
Name
Alarm 2 type selection
Modbus
address
HEX DEC
06BB 1723 R/WU 0: Process high alarm
Attri-
bute
[H-TIO-, H-CIO-A,
H-SIO-A]
Alarm 1 hold action
06BC 1724 R/WU
[H-TIO-, H-CIO-A,
H-SIO-A]
Alarm 2 hold action
06BD 1725 R/WU
[H-TIO-, H-CIO-A,
H-SIO-A]
Alarm 1 interlock
06BE 1726 R/WU
[H-TIO-, H-CIO-A,
H-SIO-A]
Alarm 2 interlock
06BF 1727 R/WU
[H-TIO-, H-CIO-A,
H-SIO-A]
Alarm 1 action at input error
06C0 1728 R/WU
[H-TIO-, H-CIO-A,
H-SIO-A]
Alarm 2 action at input error
06C1 1729 R/WU
[H-TIO-, H-CIO-A,
H-SIO-A]
Number of alarm delay times
06C2 1730 R/WU 0 to 255 times 0
[H-TIO-, H-CIO-A,
H-SIO-A]
Unused 06C3
06CB
DO function selection
06CC
[H-DO-A/B/D]
06D5
1731
•
•
•
1739
1740
•
•
•
1749
•
•
•
R/WM 00~88 * The factory set
•
•
•
* DO function selection (H-DO-A/B/D module)
H-DO-A/B module
0 0
Setting will be valid for only block 1 (DO1 to DO4) in case of
H-DO-B module.
Block 2 (DO5 to DO8)
Block 1 (DO1 to DO4)
H-DO-D module
0 0
Block 2 (DO9 to DO16)
Block 1 (DO1 to DO8)
Struc-
ture
7. COMMUNICATION DATA LIST
Data range
1: Process low alarm
2: Deviation high alarm
3: Deviation low alarm
4: Deviation high/low alarm
5: Band alarm
6: No alarm function
0: Not provided
1: Provided
2: Re-hold action
Re-hold action will be valid in deviation alarm.
0: Not provided
1: Provided
0: Normal alarm action
1: Forced alarm ON when temperature measured
value exceeds abnormal input trigger input.
Data range
0: No alarm function
1: Alarm 1
2: Alarm 2
3: Burnout
4: Heater break alarm (HBA)
5: AI alarm 1
6: AI alarm 2
7: Control loop break alarm (LBA)
8: (Not settable)
Continued on the next page.
Factory
set value
The factory set
value varies
depending
on the
specifications
when ordering.
The factory set
value varies
depending
on the
specifications
when ordering.
0
0
value varies
depending
on the
specifications
when ordering.
IMS01S01-E1
59
7. COMMUNICATION DATA LIST
Continued from the previous page.
Modbus
Name
address
HEX DEC
Unused 06D6
•
•
•
06DF
DI function selection
[H-DI-A]
06E0
•
•
•
06E9
Attri-
Struc-
bute
ture
1750
•
•
•
1759
1760
R/WM 0: Unused
•
•
•
1769
Data range
1: Function mode 1
− Memory area transfer (ENABLE terminal is used)
After area selection setting, the actual area is
changed by detecting the ENABLE edge.
− Control RUN/STOP transfer
− Alarm interlock release
2: Function mode 2
− Memory area transfer
The actual area is changed approximately 2
seconds after area selection setting.
− Control RUN/STOP transfer
− Alarm interlock release
Unused 06EA
06F3
DI using selection
06F4
[H-DI-A]
06FD
Unused 06FE
0707
1770
•
•
•
•
•
•
1779
1780
•
•
•
R/WM 0 to 255 * 255
•
•
•
1789
1790
•
•
•
•
•
•
1799
* DI using selection (H-DI-A module) ×: Used −: Unused
Setting data Memory area transfer
63
127
191
255
48
47
32
31
16
15
0
× × ×
− × ×
× − ×
− − ×
× × −
− × −
× − −
− − −
Control RUN/STOP
transfer
Alarm interlock release
Continued on the next page.
Factory
set value
1
60
IMS01S01-E1
Continued from the previous page.
Name
H-PCP-J module
DO type selection
(CH1 to CH8)
Modbus
address
HEX DEC
0708
•
•
•
070F
Attri-
bute
1800
R/WC 0: No alarm function
•
•
•
1807
[H-PCP-J]
Unused 0710
071B
Cascade tracking
071C
[H-CIO-A]
Unused 0726
Cascade data selection
[H-CIO-A]
Unused 073A
•
•
•
•
•
•
0725
•
•
•
072F
0730
•
•
•
0739
•
•
•
0743
1808
•
•
•
1819
1820
R/WM 0: Not provided
•
•
•
1829
1830
•
•
•
1839
1840
R/WM 0: Manipulated outpur value
•
•
•
1849
1850
•
•
•
1859
Struc-
ture
7. COMMUNICATION DATA LIST
Data range
1: Alarm 1/TI alarm 1
2: Alarm 2/TI alarm 2
3: Burnout
4: Heater break alarm (HBA)
5: Temperature rise completion output
6: AI alarm 1
7: AI alarm 2
8: Control loop break alarm (LBA)
9: FAIL output
10: PLC communication status
[Action]
1 to 4, 6 to 8:
Closed at alarm occurrence
5: Closed at temperature rise completion
9: Open at fail occurrence
10: Closed at communication with PLC
Be action of energized case. Action reverses in case
of de-energized.
(For the energize/de-energized, see H-PCP-J module
DO de-energized selection.)
Cascade monitored value becomes zero.
1: Provided
Cascade monitored value just before is hold.
1: Temperature measured value (PV)
2: Temperature set value (SV)
3: Set value monitor
4: Temperature deviation
H-CT-A module
heater break alarm state
(CH1 to CH60)
[H-CT-A]
H-DI-A module
input state
[H-DI-A]
085C
•
•
•
0897
0898
•
•
•
08A1
Attri-
bute
1860
R/WM
•
•
•
1869
1870
•
•
•
1879
1880
R/WC 0 to 100
•
•
•
1899
1900
•
•
•
2139
2140
ROC 0: Normal
•
•
•
2199
2200
ROM The respective channel status is assigned to each bit in
•
•
•
2209
Struc-
ture
Data range
0: Unused
1: Cascade control ON/OFF only
2: Auto/Manual transfer only
3: DI1 valid
DI2 valid
(Cascade control ON/OFF),
Auto/Manual transfer)
0: Unused
1: H-SIO-A open/closed loop control transfer only
2: Control RUN/STOP transfer only
3: H-SIO-A open/closed loop control transfer and
Control RUN/STOP transfer
The opening adjustment and the motor time are taken
in. When the specified setting counter value is input,
the operations begin. (This is only valid when control
is stopped.)
For details of data item, see Positioning adjustment counter (P. 71).
1: Break
2: Welding
the holding register.
Bit data
bit 0: CH1 (DI1)
bit 1: CH2 (DI2)
bit 2: CH3 (DI3)
bit 3: CH4 (DI4)
bit 4: CH5 (DI5)
bit 5: CH6 (DI6)
bit 6: CH7 (DI7)
bit 7: CH8 (DI8)
bit 8 to 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 255]
Factory
set value
3
3
0
* DI process selection setting or communication setting ×: Valid −: Invalid
Transfer by external contact input Transfer via communication
DI process selection
0: Unused
1: H-SIO-A open/closed loop control transfer
only
2: Control RUN/STOP transfer only
3: H-SIO-A open/closed loop control transfer and
Control RUN/STOP transfer
H-SIO-A open/closed loop control
transfer
× ×
− ×
× −
− −
Control RUN/STOP transfer
Continued on the next page.
62
IMS01S01-E1
Continued from the previous page.
Modbus
Name
address
HEX DEC
Unused 08A2
•
•
•
08AB
Cascade monitor
[H-CIO-A]
08AC
•
•
•
08BF
Positioning monitor
[H-TIO-K]
08C0
•
•
•
08D3
Unused 08D4
•
•
•
0BB7
H-DO-G
manipulated output value
(CH1 to CH160)
[H-DO-G]
H-DO-G
output limiter (high)
(CH1 to CH160)
[H-DO-G]
H-DO-G
output limiter (low)
(CH1 to CH160)
[H-DO-G]
H-DO-G
output cycle time
(CH1 to CH160)
[H-DO-G]
H-DO-G
master channel setting
(CH1 to CH160)
[H-DO-G]
H-DO-G
output ratio set value
(CH1 to CH160)
[H-DO-G]
H-DO-G
Auto/Manual transfer
(CH1 to CH160)
[H-DO-G]
H-DO-G
manual output value
(CH1 to CH160)
[H-DO-G]
Unused 10B8
0BB8
•
•
•
0C57
0C58
•
•
•
0CF7
0CF8
•
•
•
0D97
0D98
•
•
•
0E37
0E38
•
•
•
0ED7
0ED8
•
•
•
0F77
0F78
•
•
•
1017
1018
•
•
•
10B7
•
•
•
1193
AI measured value
(CH1 to CH40)
[H-AI-A/B]
1194
•
•
•
11BB
Attri-
bute
2210
•
•
•
2219
2220
ROC ± Input span
•
•
•
2239
2240
ROC −5.0 to +105.0 %
•
•
•
2259
2260
•
•
•
2999
3000
ROC −5.0 to +105.0 %
•
•
•
3159
3160
R/WC Output limiter (low) to 105.0 % 100.0
•
•
•
3319
3320
R/WC −5.0 % to Output limiter (high) 0.0
•
•
•
3479
3480
R/WC 1 to 100 2
•
•
•
3639
3640
R/WC 0 to The number of H-TIO- module use channel
•
•
•
3799
3800
R/WC 0.001 to 9.999 1.00
•
•
•
3959
3960
R/WC 0: Auto
•
•
•
4119
4120
R/WC −5.0 to +105.0 %
•
•
•
4279
4280
•
•
•
4499
4500
ROC Within display scale range
•
•
•
4539
Struc-
ture
7. COMMUNICATION DATA LIST
Data range
Data will be valid in slave channel
(0: Unused)
1: Manual
Setting will be invalid in ON/OFF control and
heat/cool control.
Setting will be invalid in ON/OFF control and
heat/cool control.
The position of the decimal point differs depending on
AI decimal point position setting.
Continued on the next page.
Factory
set value
0
0
0.0
IMS01S01-E1
63
7. COMMUNICATION DATA LIST
Continued from the previous page.
Modbus
Name
AI status
(CH1 to CH40)
[H-AI-A/B]
AI alarm 1 set value
(CH1 to CH40)
[H-AI-A/B]
AI alarm 2 set value
(CH1 to CH40)
[H-AI-A/B]
AI zero point correction
(CH1 to CH40)
[H-AI-A/B]
AI full scale correction
(CH1 to CH40)
[H-AI-A/B]
AI operation mode transfer
(CH1 to CH40)
[H-AI-A/B]
AI input range number
(CH1 to CH40)
[H-AI-A/B]
AI display scale high
(CH1 to CH40)
[H-AI-A/B]
address
HEX DEC
11BC
•
•
•
11E3
11E4
•
•
•
120B
120C
•
•
•
1233
1234
•
•
•
125B
125C
•
•
•
1283
1284
•
•
•
12AB
12AC
•
•
•
12D3
12D4
•
•
•
12FB
Attri-
Struc-
bute
ture
4540
ROC The respective channel status is assigned to each bit
•
•
•
4579
in the holding register.
Bit data
bit 0: AI alarm 1 state
Data range
Factory
set value
bit 1: AI alarm 2 state
bit 2 to 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 3]
4580
R/WC Process high
•
•
•
4619
Within display scale range
The position of the decimal point differs depending
on AI decimal point position setting.
alarm: 100.0
Process low
alarm: 0.0
No alarm
function: 100.0
4620
•
•
•
4659
R/WC
Process high
alarm: 100.0
Process low
alarm: 0.0
No alarm
function: 0.0
4660
R/WC 0: Cancel
•
•
•
1: Execution
0
4699
4700
R/WC 0: Cancel
•
•
•
1: Execution
0
4739
4740
R/WC 0: Unused
•
•
•
4779
Neither monitor nor alarm monitor is done in this
mode.
1: Normal mode
1
Normal mode in which monitor and alarm are
done.
4780
R/WC 0: 0 to 10 mV DC
•
•
•
4819
1: −10 to +10 mV DC
2: 0 to 100 mV DC
3: −100 to +100 mV DC
4: 0 to 1 V DC
5: −1 to +1 V DC
The factory set
value varies
depending
on the
specifications
when ordering.
6: 0 to 5 V DC
7: 1 to 5 V DC
8: −5 to +5 V DC
9: 0 to 10 V DC
10: −10 to +10 V DC
11: 0 to 20 mA DC
12: 4 to 20 mA DC
Voltage (low) input group: 0 to 8
Voltage (high) input group: 9 to 10
Current input group: 11 to 12
An input type change may only be made within the
input groups. If the input range number is changed,
all of the settings corresponding to the channels in
the relevant module return to the default values.
4820
R/WC Span 10000 or less (Within −9999 to +10000)
•
•
•
4859
The position of the decimal point differs depending
on AI decimal point position setting.
100.0
Continued on the next page.
64
IMS01S01-E1
Continued from the previous page.
Name
AI display scale low
(CH1 to CH40)
[H-AI-A/B]
AI decimal point position
(CH1 to CH40)
[H-AI-A/B]
AI digital filter
(CH1 to CH40)
[H-AI-A/B]
AI moving average
(CH1 to CH40)
[H-AI-A/B]
AI alarm 1 differential gap
Modbus
address
HEX DEC
12FC
•
•
•
1323
1324
•
•
•
134B
134C
•
•
•
1373
1374
•
•
•
139B
139C 5020 R/WU
Attri-
bute
4860
R/WC Span 10000 or less (Within −9999 to +10000)
•
•
•
4899
4900
R/WC 0: No decimal place
•
•
•
4939
4940
R/WC 0.0 to 100.0 seconds (0.0: OFF) 0.0
•
•
•
4979
4980
R/WC 0: Not provided
•
•
•
5019
[H-AI-A/B]
AI alarm 2 differential gap
139D 5021 R/WU
[H-AI-A/B]
AI alarm 1 type selection
139E 5022 R/WU
[H-AI-A/B]
AI alarm 2 type selection
139F 5023 R/WU
[H-AI-A/B]
AI alarm 1 hold action
13A0 5024 R/WU
[H-AI-A/B]
AI alarm 2 hold action
13A1 5025 R/WU
[H-AI-A/B]
AI alarm 1 interlock
13A2 5026 R/WU
[H-AI-A/B]
AI alarm 2 interlock
13A3 5027 R/WU
[H-AI-A/B]
Number of AI alarm delay
13A4 5028 R/WU 0 to 255 times 0
times
[H-AI-A/B]
Unused 13A5
13EB
TI measured value
13EC
(CH1 to CH40)
[H-TI-A/B/C]
TI status
1413
1414
(CH1 to CH40)
[H-TI-A/B/C]
143B
5029
•
•
•
•
•
•
5099
5100
•
•
•
ROC Within input range
•
•
•
5139
5140
•
•
•
ROC The respective channel status is assigned to each bit
•
•
•
5179
Struc-
ture
7. COMMUNICATION DATA LIST
Data range
The position of the decimal point differs depending
on AI decimal point position setting.
1: One decimal place
2: Two decimal places
3: Three decimal places
1: Provided
0.00 to 10.00 % of span 0.10
0: Process high alarm
1: Process low alarm
2 to 6: No alarm function
0: Not provided
1: Provided
0: Not provided
1: Provided
The position of the decimal point differs depending
on the input range.
in the holding register.
Bit data
bit 0: TI alarm 1 state
bit 1: TI alarm 2 state
bit 2: TI burnout state
bit 3 to 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 7]
Factory
set value
0.0
1
0
The factory set
value varies
depending
on the
specifications
when ordering.
The factory set
value varies
depending
on the
specifications
when ordering.
0
Continued on the next page.
IMS01S01-E1
65
7. COMMUNICATION DATA LIST
Continued from the previous page.
Name
TI alarm 1 set value
(CH1 to CH40)
[H-TI-A/B/C]
TI alarm 2 set value
(CH1 to CH40)
[H-TI-A/B/C]
TI_ PV bias
(CH1 to CH40)
[H-TI-A/B/C]
TI operation mode transfer
(CH1 to CH40)
[H-TI-A/B/C]
Modbus
address
HEX DEC
143C
•
•
•
1463
1464
•
•
•
148B
148C
•
•
•
14B3
14B4
•
•
•
14DB
Attri-
Struc-
bute
ture
5180
•
•
•
5219
5220
•
•
•
R/WC
R/WC
Within input range
The position of the decimal point differs depending
on the input range.
5259
5260
R/WC −5.00 to +5.00 % of span 0.00
•
•
•
5299
5300
R/WC 0: Unused
•
•
•
5339
Neither monitor nor alarm monitor is done in this
mode.
1: Normal mode
Normal mode in which monitor and alarm are
done.
TI input range number
(CH1 to CH40)
[H-TI-A/B/C]
14DC
•
•
•
1503
5340
R/WC 0 to 120
•
•
•
5379
If the input range number is changed, all of the
settings corresponding to the channels in the relevant
module return to the default values.
See Input range table(P. 75).
TI digital filter
(CH1 to CH40)
[H-TI-A/B/C]
TI alarm 1 differential gap
1504
152B
5380
•
•
•
R/WC 0.0 to 100.0 seconds (0.0: OFF) 0.0
•
•
•
5419
152C 5420 R/WU
0.00 to 10.00 % of span 0.10
[H-TI-A/B/C]
TI alarm 2 differential gap
152D 5421 R/WU
[H-TI-A/B/C]
TI alarm 1 type selection
[H-TI-A/B/C]
TI alarm 2 type selection
152E 5422 R/WU
152F 5423 R/WU
0: Process high alarm
1: Process low alarm
2 to 6: No alarm function
[H-TI-A/B/C]
TI alarm 1 hold action
[H-TI-A/B/C]
TI alarm 2 hold action
1530 5424 R/WU
1531 5425 R/WU
0: Not provided
1: Provided
[H-TI-A/B/C]
TI alarm 1 interlock
[H-TI-A/B/C]
TI alarm 2 interlock
1532 5426 R/WU
1533 5427 R/WU
0: Not provided
1: Provided
[H-TI-A/B/C]
TI alarm 1 action at input
error
[H-TI-A/B/C]
1534 5428 R/WU 0: Normal alarm action
1: Forced alarm ON when temperature measured
value exceeds abnormal input trigger input.
* Process high alarm: Input range (high)
Process low alarm: Input range (low)
No alarm function: Input range (high) for TI alarm 1 set value or
Input range (low) for TI alarm 2 set value
Data range
Factory
set value
The factory set
value varies
depending on
the alarm
type. *
1
The factory set
value varies
depending
on the
specifications
when ordering.
The factory set
value varies
depending
on the
specifications
when ordering.
The factory set
value varies
depending
on the
specifications
when ordering.
0
0
Continued on the next page.
66
IMS01S01-E1
Continued from the previous page.
Modbus
Name
address
HEX DEC
TI alarm 2 action at input
1535 5429 R/WU 0: Normal alarm action
error
[H-TI-A/B/C]
Number of TI alarm delay
1536 5430 R/WU 0 to 255 times 0
times
[H-TI-A/B/C]
Unused 1537
•
•
•
157B
AO output value monitor
(CH1 to CH40)
[H-AO-A/B]
AO output set value
(CH1 to CH40)
[H-AO-A/B]
AO function selection
(CH1 to CH40)
[H-AO-A/B]
AO corresponding channel
setting
(CH1 to CH40)
[H-AO-A/B]
AO zooming high limit
(CH1 to CH40)
[H-AO-A/B]
AO zooming low limit
(CH1 to CH40)
[H-AO-A/B]
AO zero point correction
(CH1 to CH40)
[H-AO-A/B]
AO full scale correction
(CH1 to CH40)
[H-AO-A/B]
AO display scale high
(CH1 to CH40)
[H-AO-A/B]
AO display scale low
(CH1 to CH40)
[H-AO-A/B]
157C
•
•
•
15A3
15A4
•
•
•
15CB
15CC
•
•
•
15F3
15F4
•
•
•
161B
161C
•
•
•
1643
1644
•
•
•
166B
166C
•
•
•
1693
1694
•
•
•
16BB
16BC
•
•
•
16E3
16E4
•
•
•
170B
Attri-
bute
5431
•
•
•
5499
5500
ROC
•
•
•
5539
5540
R/WC
•
•
•
5579
5580
R/WC 0: Unused
•
•
•
5619
5620
R/WC 1 to 20 (TIO channel)
•
•
•
5659
5660
R/WC AO zooming low limit to 100.0 %
•
•
•
5699
5700
R/WC 0.0 % to AO zooming high limit
•
•
•
5739
5740
R/WC −5.00 to +5.00 % 0.00
•
•
•
5779
5780
R/WC −5.00 to +5.00 % 0.00
•
•
•
5819
5820
R/WC 100.0
•
•
•
5859
5860
R/WC
•
•
•
5899
Struc-
ture
7. COMMUNICATION DATA LIST
Data range
1: Forced alarm ON when temperature measured
value exceeds abnormal input trigger input.
Display scale range
Data will be valid in manual mode.
The position of the decimal point differs depending on
AO decimal point position setting.
1: Manual mode (outputs data given by the AO output
set value)
2: Temperature measured value (PV)
3: Set value monitor
4: Temperature deviation value (deviation between the
temperature measured value and set value monitor)
5: Heat-side manipulated output value
6: Cool-side manipulated output value
7: AI measured value
8: TI measured value
9: Opening monitor
(2 to 9: Recorder output mode)
1 to 40 (AI and TI channel)
Setting will be valid in recorder output mode.
Setting will be valid in recorder output mode.
Setting will be valid in recorder output mode.
Span 10000 or less
The position of the decimal point differs depending on
AO decimal point position setting.
Factory
set value
0
0.0
1
1
100.0
0.0
0.0
IMS01S01-E1
Continued on the next page.
67
7. COMMUNICATION DATA LIST
Continued from the previous page.
Modbus
Name
address
HEX DEC
AO decimal point position
(CH1 to CH40)
[H-AO-A/B]
AO output change rate limiter
(CH1 to CH40)
[H-AO-A/B]
Unused 175C
170C
•
•
•
1733
1734
•
•
•
175B
•
•
•
176F
Event DI contact input
monitor
[H-DI-B]
Unused 177A
1770
•
•
•
1779
•
•
•
1783
Event DI logic output
monitor
[H-DI-B]
Unused 178E
1784
•
•
•
178D
•
•
•
1797
Event DI logic input monitor
[H-DI-B]
1798
•
•
•
17E7
Attri-
bute
5900
R/WC 0: No decimal place
•
•
•
5939
5940
R/WC 0.0 to 100.0 %/second (0.0: OFF) 0.0
•
•
•
5979
5980
•
•
•
5999
6000
ROM The respective channel status is assigned to each bit
•
•
•
6009
6010
•
•
•
6019
6020
ROM The respective channel status is assigned to each bit
•
•
•
6029
6030
•
•
•
6039
6040
ROL The respective channel status is assigned to each bit
•
•
•
6119
Struc-
ture
Data range
1: One decimal place
2: Two decimal places
3: Three decimal places
in the holding register.
Bit data
bit 0: CH1 (DI1)
bit 1: CH2 (DI2)
bit 2: CH3 (DI3)
bit 3: CH4 (DI4)
bit 4: CH5 (DI5)
bit 5: CH6 (DI6)
bit 6: CH7 (DI7)
bit 7: CH8 (DI8)
bit 8 to 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 255]
in the holding register.
Bit data
bit 0: Logic output 1
bit 1: Logic output 2
bit 2: Logic output 3
bit 3: Logic output 4
bit 4: Logic output 5
bit 5: Logic output 6
bit 6: Logic output 7
bit 7: Logic output 8
bit 8 to 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 255]
in the holding register.
Bit data
bit 0: Logic input 1
bit 1: Logic input 2
bit 2: Logic input 3
bit 3: Logic input 4
bit 4 to 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 15]
Factory
set value
1
68
Continued on the next page.
IMS01S01-E1
Continued from the previous page.
Modbus
Name
address
HEX DEC
Event DI type selection 1
[H-DI-B]
17E8
•
•
•
1837
Event DI type selection 2
[H-DI-B]
1838
•
•
•
1887
Event DI type selection 3
[H-DI-B]
1888
•
•
•
18D7
Event DI type selection 4
[H-DI-B]
18D8
•
•
•
1927
Event DI corresponding
channel selection 1
[H-DI-B]
Event DI corresponding
channel selection 2
[H-DI-B]
Event DI corresponding
channel selection 3
[H-DI-B]
Event DI corresponding
channel selection 4
[H-DI-B]
Event DI
reversal selection 1
[H-DI-B]
Event DI
reversal selection 2
[H-DI-B]
Event DI
reversal selection 3
[H-DI-B]
Event DI
reversal selection 4
[H-DI-B]
Event DI logic circuit
selection
[H-DI-B]
Event DI delay timer
setting
[H-DI-B]
Unused 1C48
1928
•
•
•
1977
1978
•
•
•
19C7
19C8
•
•
•
1A17
1A18
•
•
•
1A67
1A68
•
•
•
1AB7
1AB8
•
•
•
1B07
1B08
•
•
•
1B57
1B58
•
•
•
1BA7
1BA8
•
•
•
1BF7
1BF8
•
•
•
1C47
•
•
•
1C83
Attri-
bute
6120
R/WL 0
•
•
•
6199
6200
R/WL 0
•
•
•
6279
6280
R/WL 0
•
•
•
6359
6360
R/WL
•
•
•
6439
6440
R/WL 1
•
•
•
6519
6520
R/WL 1
•
•
•
6599
6600
R/WL 1
•
•
•
6679
6680
R/WL
•
•
•
6759
6760
R/WL 0
•
•
•
6839
6840
R/WL 0
•
•
•
6919
6920
R/WL 0
•
•
•
6999
7000
R/WL
•
•
•
7079
7080
R/WL 0: AND (1 active)
•
•
•
7159
7160
R/WL 0 to 255 times 1
•
•
•
7239
7240
•
•
•
7299
Struc-
ture
7. COMMUNICATION DATA LIST
Data range
0 to 30 (17 to 30: Not settable)
Set the type and corresponding channel of Event DI.
Event DI uses it with logic input function.
Each contact status can be monitored by the following
data.
Digital input (1 to 8):
Event DI contact input monitor
Logic input (1 to 4)/Logic section:
Event DI logic input monitor
Logic input (1 to 8):
Event DI logic output monitor
For details of data item, see Logic input function(P. 72).
1 to 80
Set the type and corresponding channel of Event DI.
Event DI uses it with logic input function.
Each contact status can be monitored by the following
data.
Digital input (1 to 8):
Event DI contact input monitor
Logic input (1 to 4)/Logic section:
Event DI logic input monitor
Logic input (1 to 8):
Event DI logic output monitor
For details of data item, see Logic input function(P. 72).
0: Normal
1: Reversal
1: NAND (0 active)
2: OR (1 active)
3: NOR (0 active)
Continued on the next page.
Factory
set value
0
1
0
0
IMS01S01-E1
69
7. COMMUNICATION DATA LIST
Continued from the previous page.
Modbus
Name
address
HEX DEC
Event DO state
[H-DO-C]
1C84
•
•
•
1C8D
Unused 1C8E
•
•
•
1C97
Event DO manual output
value
[H-DO-C]
Unused 1CA2
1C98
•
•
•
1CA1
•
•
•
1CAB
Event DO extension alarm
set value
[H-DO-C]
Event DO function
selection
[H-DO-C]
Event DO corresponding
channel setting
[H-DO-C]
1CAC
•
•
•
1CFB
1CFC
•
•
•
1D4B
1D4C
•
•
•
1D9B
Attri-
bute
7300
ROM The respective channel status is assigned to each bit in
•
•
•
7309
7310
•
•
•
7319
7320
R/WM The respective channel status is assigned to each bit in
•
•
•
7329
7330
•
•
•
7339
7340
R/WC TC/RTD input:
•
•
•
7419
7420
R/WC 0 to 30
•
•
•
7499
7500
R/WC 1 to 40
•
•
•
7579
Struc-
ture
Data range
the holding register.
Bit data
bit 0: CH1 (DO1)
bit 1: CH2 (DO2)
bit 2: CH3 (DO3)
bit 3: CH4 (DO4)
bit 4: CH5 (DO5)
bit 5: CH6 (DO6)
bit 6: CH7 (DO7)
bit 7: CH8 (DO8)
bit 8 to 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 255]
the holding register.
Bit data
bit 0: CH1 (DO1)
bit 1: CH2 (DO2)
bit 2: CH3 (DO3)
bit 3: CH4 (DO4)
bit 4: CH5 (DO5)
bit 5: CH6 (DO6)
bit 6: CH7 (DO7)
bit 7: CH8 (DO8)
bit 8 to 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 255]
Within input range or span range
Current/voltage input, H-SIO-A:
Within display scale range or span range
The position of the decimal point differs depending on
the input range.
Set the function, corresponding channel and mode
select of Event DO. Event DO uses it with event
output function.
For details of data item, see Event output function(P. 73).
Set the function, corresponding channel and mode
select of Event DO. Event DO uses it with event
output function.
For details of data item, see Event output function(P. 73).
Continued on the next page.
Factory
set value
0
0
0
1
70
IMS01S01-E1
Continued from the previous page.
Modbus
Name
Event DO mode select
setting
[H-DO-C]
Event DO extension alarm
differential gap
[H-DO-C]
Event DO extension alarm
interlock
[H-DO-C]
Number of Event DO
extension alarm delay times
[H-DO-C]
address
HEX DEC
1D9C
1DEB
1DEC 7660 R/WU 0.00 to 10.00 % 0.10
1DED 7661 R/WU 0: Not provided
1DEE 7662 R/WU 0 to 255 times 0
7580
•
•
•
•
•
•
7659
Positioning adjustment counter
Attri-
Struc-
bute
ture
R/WC 0 to 40
Set the function, corresponding channel and mode
select of Event DO. Event DO uses it with event
output function.
For details of data item, see Event output function(P. 73).
2 Capture the open-side opening value after 3 seconds stop
3 Close-side output start (Motor time: 110 %)
4 Capture the close-side opening value after 3 seconds stop
5 Above data stored in H-TIO-K module
6 Hold status
7 Outputs the close-side until the positioning becomes 0 %.
8 After the motor time has been captured, close-side output comes ON
9 Hold status
10 to 100 Not settable
Description Status
Open-side output start if the positioning is less than 0 %.
Stops at an positioning of more than 100 %, and capture the motor time
by H-TIO-K module
(Motor time: 110 %)
When you input setting counter 1, the opening adjustment starts, operations are carried out automatically
up to setting counter 6, then the system goes on hold status. When you input setting counter 7, the motor
time capture starts, operations are carried out automatically up to setting counter 9, then the system goes
on hold status. After the settings are complete, always set to “0: Normal status.”
Always adjust the opening first and capture the motor time after the adjustment is
complete.
Motor time
FBR opening
adjustment
Capture the
motor time
Setting to normal
status
Automatic
Automatic
IMS01S01-E1
71
7. COMMUNICATION DATA LIST
p
•
Logic input function
Each logic is built by four event inputs. Up to eight logic results (logic outputs) per H-DI-B module can be
monitored through communication or can be output from H-DO-C module. In addition, this function can
assign the input of the H-DI-B module to any channel number of the H-DO-C module to output the result.
The logic section of event DI module consists of 4 logic input points, input reversal selection, logic circuit
type selection, input delay timer and logic output.
0 Input always OFF Always ON at “Reversal” selection
1 Event DI input 1 to 80 0: OFF 1: ON
2 Event DI logic output 1 to 80 0: OFF 1: ON
3 Event DO output 1 to 72 0: OFF 1: ON
4 PCP error code 0: Not provided 1: Provided
5 Temperature rise completion 0: Rise not complete 1: Rise completed
6 PID/AT logical OR 0: All PID 1: Any one is in AT
7 Alarm 1 1 to18 0: OFF 1: ON
8 Alarm 2 1 to18 0: OFF 1: ON
9 Burnout 1 to18 0: OFF 1: ON
10 Heater break alarm (HBA) 1 to18 0: OFF 1: ON
11 Control loop break alarm (LBA)1 to18 0: OFF 1: ON
12 AI alarm 1 1 to 36 0: OFF 1: ON
13 AI alarm 2 1 to 36 0: OFF 1: ON
14 TI alarm 1 1 to 36 0: OFF 1: ON
15 TI alarm 2 1 to 36 0: OFF 1: ON
16 TI burnout 1 to 36 0: OFF 1: ON
17 to 30 Not settable
Event DI corresponding
channel selection
(Modbus address:
1928H to 1A67)
Note
Each contact status can be monitored by the following Modbus address.
Digital input 1 to 8 → Event DI contact input monitor (Modbus address: 1770H to 1779H)
Logic input 1 to 4/Logic section → Event DI logic input monitor (Modbus address: 1798H to 17E7H)
Logic output 1 to 8 → Event DI logic output monitor (Modbus address: 1784H to 178DH)
Output from
H-DO-C module
Monitoring via
communication
72
IMS01S01-E1
7. COMMUNICATION DATA LIST
(
Event output function
The event output function enables up to eight points to be output per module of unique alarms different from
ordinary temperature and AI alarms (Extension alarm output function), control unit operations (Status output
function) and comparison results which are output only under certain conditions (Data comparison output
function). The function can be set for each channel of the H-DO-C module.
Extension alarm output function
An extension alarm is output independently of H-TIO- module alarms. As it is independently set, it
can be provided as a dedicated alarm output.
Event DO function selection
Modbus address: 1CFCH to 1D4BH)
Setting
data
13 AI process alarm 1 to 40 CH (H-AI- module) 0: High alarm
20 TI process alarm 1 to 40 CH (H-TI- module) 0: High alarm
Function name
Temperature deviation alarm 1 to 20 CH (H-TIO- module) 10
Motor speed deviation alarm 1 to 20 CH (H-SIO-A module)
Temperature process alarm 1 to 20 CH (H-TIO- module) 11
Motor speed process alarm 1 to 20 CH (H-SIO-A module)
Temperature set value alarm 1 to 20 CH (H-TIO- module) 12
Motor speed set value alarm 1 to 20 CH (H-SIO-A module)
This output is different from the ordinary alarm output from the H-DO-A/B type module.
Similarly, the ordinary alarm cannot be output from the H-DO-C type module (for event output).
Event DO corresponding
channel setting
(Modbus address:
1D4CH to 1D9BH)
Event DO mode select setting
(Modbus address:
1D9CH to 1DEBH)
0: High alarm
1: Low alarm
2: High/low alarm
3: Band alarm
4: High alarm with hold action
5: Low alarm with hold action
6: High/low alarm with hold action
7: Band alarm with hold action
8: High alarm with re-hold action
9: Low alarm with re-hold action
10: High/low alarm with re-hold action
0: High alarm
1: Low alarm
2: High alarm with hold action
3: Low alarm with hold action
0: High alarm
1: Low alarm
1: Low alarm
2: High alarm with hold action
3: Low alarm with hold action
1: Low alarm
2: High alarm with hold action
3: Low alarm with hold action
The alarm differential gap and alarm delay timer are commonly set.
Continued on the next page.
IMS01S01-E1
73
7. COMMUNICATION DATA LIST
(
)
)
)
)
Continued from the previous page.
Status output function
This function is used to output the control unit action state other than the extension alarm output in
addition to the ordinary alarm output state (Alarm 1 state, etc.).
Event DO function selection
Modbus address: 1CFCH to 1D4BH
Setting data
0 Unused (Manual mode)
1 Alarm 1 1 to 20 CH (H-TIO-/H-SIO-A module)
2 Alarm 2 1 to 20 CH (H-TIO-/H-SIO-A module)
3 Burnout 1 to 20 CH (H-TIO- module)
4 Heater break alarm (HBA) 1 to 20 CH (H-TIO- module)
5 AI alarm 1 1 to 40 CH (H-AI- module)
6 AI alarm 2 1 to 40 CH (H-AI- module)
7 Control loop break alarm (LBA)1 to 20 CH (H-TIO- module)
8 PID/AT 1 CH
17 TI alarm 1 1 to 40 CH (H-TI- module)
18 TI alarm 2 1 to 40 CH (H-TI- module)
19 TI burnout 1 to 40 CH (H-TI- module)
22 Event DI logic output status 1 to 40 CH (H-DI-B module)
9 Not settable
23 to 30 Not settable
Function name
Event DO corresponding
(Modbus address: 1D4CH to 1D9BH)
channel setting
Event DO mode
select setting
(Modbus address:
1D9CH to 1DEBH
Data comparison output function
This function is used to output the result of comparison between the measured value and measured
value (or set value and set value) within the same group.
Event DO function selection
(Modbus address: 1CFCH to 1D4BH)
Setting data
14 Temperature measured value comparison
Comparison between the temperature measured
value and temperature measured value
Motor speed measured value comparison
Comparison between the motor speed measured
value and motor speed measured value
15 Temperature set value comparison
Comparison between the temperature set value
and temperature set value
Motor speed set value comparison
Comparison between the motor speed set value
and motor speed set value
16 AI measured value comparison
Comparison between the AI measured value and
AI measured value
21 TI measured value comparison
Comparison between the TI measured value and
TI measured value
[Relationship between output and comparison]
Computing equation: The output turns ON at (Data 2) − (Data 1) ≤ 0
This means:
The output turns ON if (Data 2) is smaller than or equal to (Data 1). {Data 2 ≤ Data 1}
The output turns OFF if (Data 2) is larger than (Data 1). {Data 2 > Data 1}
The range with the resolution of 1/100 can be specified
only by H-TIO-E module.
2
The range can be specified only by H-TIO-F module (high
accuracy type).
Current input and Voltage input (H-TIO-H/J, H-CIO-A)
Input type Range No. Input group
0 to 10 mV DC 0.0 to 100.0 % 0
−
10 to +10 mV DC 0.0 to 100.0 % 1
0 to 100 mV DC 0.0 to 100.0 % 2
−
100 to +100 mV DC 0.0 to 100.0 % 3
Voltage
input
Current
input *
* Display scale of the current and voltage input can be changed.
0 to 1 V DC 0.0 to 100.0 % 4
−
1 to +1 V DC 0.0 to 100.0 % 5
*
0 to 5 V DC 0.0 to 100.0 % 6
1 to 5 V DC 0.0 to 100.0 % 7
−
5 to +5 V DC 0.0 to 100.0 % 8
0 to 10 V DC 0.0 to 100.0 % 9
−
10 to +10 V DC 0.0 to 100.0 % 10
0 to 20 mA DC 0.0 to 100.0 % 11
4 to 20 mA DC 0.0 to 100.0 % 12
An input type change may only be made within the input groups as shown above.
Pulse input (H-SIO-A)
Pulse
input
Input type
•
Dry contact input (Power supply for sensor, 12 V DC)
•
Voltage input (Power supply for sensor, 12 V DC)
Specify when ordering with model code.
Do not set any number other than 0, as this may cause malfunction.
Voltage (low) input group
Voltage (high) input group
Current input group
Range No.
0
76 IMS01S01-E1
7. COMMUNICATION DATA LIST
7.2 Communication Data List of H-PCP-A Module
Name
Temperature measured
value (PV)
[H-TIO-, H-CIO-A]
Heat-side manipulated
output value
[H-TIO-, H-CIO-A]
Cool-side manipulated
output value
[H-TIO-, H-CIO-A]
Current tramsformer input
measured value 1
[H-TIO-A/C/D]
Current tramsformer input
measured value 2
[H-CT-A]
Status
[H-TIO-, H-CIO-A]
Temperature rise
Modbus
address
HEX DEC
0000
•
•
•
0013
0014
•
•
•
0027
0028
•
•
•
003B
003C
•
•
•
004F
0050
•
•
•
0063
0064
•
•
•
0077
0078 120 ROU 0: Rise not complete
Attri-
Struc-
bute
ture
0
ROC TC/RTD input: Within input range
•
•
•
19
20
ROC −0.5 to +105.0 %
•
•
•
39
40
ROC −0.5 to +105.0 %
•
•
•
59
60
ROC 0.0 to 100.0 A or 0.0 to 30.0 A
•
•
•
79
80
ROC 0.0 to 100.0 A or 0.0 to 30.0 A
•
•
•
99
100
ROC The respective channel status is assigned to each bit in
•
•
•
119
completion state
[H-TIO-, H-CIO-A]
Unused 0079
00C7
Temperature set value
00C8
(SV)
[H-TIO-, H-CIO-A]
PID/AT transfer
00DB
00DC
[H-TIO-, H-CIO-A]
00EF
Heat-side proportional
00F0
band
[H-TIO-, H-CIO-A]
Cool-side proportional
0103
0104
band
[H-TIO-, H-CIO-A]
0117
121
•
•
•
•
•
•
199
200
•
•
•
R/WC TC/RTD input:
•
•
•
219
220
•
•
•
R/WC 0: PID control operation
•
•
•
239
240
•
•
•
R/WC 0.1 to 1000.0 % of span 3.0
•
•
•
259
260
•
•
•
R/WC 0.1 to 1000.0 % of span 3.0
•
•
•
279
Data range
Current (V)/Voltage (I) input:
Within display scale range
Current tramsformer (CT) input measured value of the
H-TIO-A/C/D module
Current tramsformer (CT) input measured value of the
H-CT-A module
the holding register.
Bit data
bit 0: Alarm 1 state
bit 1: Alarm 2 state
bit 2: Burnout state
bit 3: Heater break alarm state
OR operation of the H-TIO-A/C/D module
and H-CT-A module
bit 4: Control leep break alarm (LBA) state
bit 5: Temperature rise completion state
bit 6: Heat-side manipulated output state
bit 7 to 15: Unused
Data 0: OFF 1: ON
[Decimal number: 0 to 127]
1: Rise completed
Within input range (Within setting limiter)
Current/Voltage input:
Within display scale range (Within setting limiter)
The position of the decimal point differs depending on
the input range.
1: AT (Autotuning) operation
Continued on the next page.
Factory
set value
0
0
IMS01S01-E1
77
7. COMMUNICATION DATA LIST
Continued from the previous page.
Modbus
Name
address
HEX DEC
Integral time
[H-TIO-, H-CIO-A]
0118
•
•
•
012B
Derivative time
[H-TIO-, H-CIO-A]
012C
•
•
•
013F
Overlap/deadband
[H-TIO-, H-CIO-A]
0140
•
•
•
0153
Control response
parameters
[H-TIO-, H-CIO-A]
Alarm 1 set value
[H-TIO-, H-CIO-A]
0154
•
•
•
0167
0168
•
•
•
017B
Alarm 2 set value
[H-TIO-, H-CIO-A]
017C
•
•
•
018F
Heater break alarm
set value 1
[H-TIO-A/C/D]
Heater break alarm
set value 2
[H-CT-A]
a
Heat control (H-TIO-/H-CIO-A): 0
0190
•
•
•
01A3
01A4
•
•
•
01B7
Attri-
bute
280
R/WC 1 to 3600 seconds 240
•
•
•
299
300
R/WC 0 to 3600 seconds (0: PI action) 60
•
•
•
319
320
R/WC −10.0 to +10.0 % of span 0.0
•
•
•
339
340
R/WC 0: Slow
•
•
•
359
360
R/WC
•
•
•
379
380
R/WC
•
•
•
399
400
R/WC 0.0 to 100.0 A or 0.0 to 30.0 A
•
•
•
419
420
R/WC 0.0 to 100.0 A or 0.0 to 30.0 A
•
•
•
439
Heat/cool control (H-TIO-/H-CIO-A): 2
Position proportioning control (H-TIO-K): 0
b
Factory set value table of Alarm 1/Alarm 2 set value
Input type Alarm type Alarm 1 set value Alarm 2 set value
TC/RTD input
Current/voltage input
Process high alarm Input range (high limit) Input range (high limit)
Process low alarm Input range (low limit) Input range (low limit)
Deviation high alarm, Deviation
high/low alarm, Band alarm
Deviation low alarm
No alarm function Input range (high limit) Input range (low limit)
Process high alarm 100.0 % 100.0 %
Process low alarm 0.0 % 0.0 %
Deviation high alarm, Deviation
high/low alarm, Band alarm
Deviation low alarm
No alarm function 100.0 % 0.0 %
Struc-
ture
Data range
1: Medium
2: Fast
In order to perform PID control by using the fuzzy
function, specify “Fast.” The fuzzy function is
effective to restrict overshoot or undershoot occurring
at operation start, or resulting from set value changes.
(Fuzzy function correspond to H-TIO-P/R module
only.)
TC/RTD input:
Within input range or span range
Current/voltage input, H-SIO-A:
Within display scale range or span range
For the current tramsformer (CT) input of the
H-TIO-A/C/D module
For the current tramsformer (CT) input of the H-CT-A
module
50 °C 50 °C
−50 °C −50 °C
50 % 50 %
−50 % −50 %
Continued on the next page.
Factory
set value
a
0
See Factory
set value
table of
Alarm 1/
Alarm 2
set value
b
0.0
0.0
78
IMS01S01-E1
Continued from the previous page.
Modbus
Name
address
HEX DEC
Operation mode transfer
[H-TIO-, H-CIO-A]
01B8
•
•
•
01CB
Heat-side proportioning
cycle time
[H-TIO-, H-CIO-A]
Cool-side proportioning
cycle time
[H-TIO-, H-CIO-A]
Auto/Manual transfer
[H-TIO-, H-CIO-A]
01CC
•
•
•
01DF
01E0
•
•
•
01F3
01F4
•
•
•
0207
Manual output value
[H-TIO-, H-CIO-A]
0208
•
•
•
021B
LBA use selection
[H-TIO-, H-CIO-A]
021C
•
•
•
022F
LBA time
[H-TIO-, H-CIO-A]
0230
•
•
•
0243
LBA deadband
[H-TIO-, H-CIO-A]
0244
•
•
•
0257
PV bias
[H-TIO-, H-CIO-A]
0258
•
•
•
026B
Temperature rise
completion range
[H-TIO-, H-CIO-A]
a
Relay contact output: 20 seconds
Voltage pulse output, Open collector output, Triac output: 2 seconds
b
TC/RTD input: 10 °C or 20 °F
Current/voltage input, H-SIO-A: 10 % of display scale
026C
•
•
•
027F
Attri-
Struc-
bute
ture
440
R/WC 0: Unused
•
•
•
459
460
R/WC 1 to 100 seconds
•
•
•
479
480
R/WC 1 to 100 seconds
•
•
•
499
500
R/WC 0: Auto
•
•
•
519
520
R/WC −5.0 to +105.0 %
•
•
•
539
540
R/WC 0: Unused
•
•
•
559
560
R/WC 1 to 7200 seconds 480
•
•
•
579
580
R/WC Input span
•
•
•
599
600
R/WC −5.00 to +5.00 % of span
•
•
•
619
620
R/WC 1 to 10 °C or 1 to 20 °F
•
•
•
639
7. COMMUNICATION DATA LIST
Data range
If set to “Unused,” no control, monitor or alarm
monitor is performed.
1: Monitor
If set to “Monitor,” only the monitor is performed.
No control or alarm monitor is performed.
2: Alarm
If set to “Alarm,” monitor or alarm monitor is
performed. No control is performed.
3: Normal
Selected to normal mode to perform control,
monitor or alarm monitor.
Setting will be invalid in current/voltage output.
Setting will be invalid in current/voltage output and
heat control.
1: Manual
Setting will be invalid in ON/OFF control and
heat/cool control.
Setting will be invalid in ON/OFF control and
heat/cool control.
H-TIO-C/D [Z-1017 specification]:
−105.0 to 0.0 % (cool-side)
0.0 to +105.0 % (heat-side)
1: Used
The position of the decimal point differs depending on
the input range.
ZK-1103 specification:
−Input span to +Input span
Unit (°C, °F, etc.) and decimal point position (No
decimal place, One decimal place, Two decimal
places or Three decimal places) depends on input
range type.
The position of the decimal point differs depending on
the input range.
Continued on the next page.
Factory
set value
3
a
20
a
20
0
0.0
0
0
0.00
ZK-1103:
0
b
10
IMS01S01-E1
79
7. COMMUNICATION DATA LIST
Continued from the previous page.
Name
Temperature rise
completion trigger
[H-TIO-, H-CIO-A]
Modbus
address
HEX DEC
0280
•
•
•
0293
Attri-
Struc-
bute
ture
640
R/WC 0: Unused
•
•
•
659
Data range
a
1: Used
Do not set “1: Used” in H-TIO-H/J module and
H-SIO-A module, because temperature rise
completion is not judged.
CT channel setting
[H-CT-A]
0294
•
•
•
02A7
660
R/WC 0 to 20 (0: Unused)
•
•
•
679
Allocates the channels for H-TIO- module to the
input channels of H-CT-A module.
The factory set
value varies
depending
on the
specifications
when ordering.
Unused 02A8
02BB
Control RUN/STOP
02BC 700 R/WU 0: Control STOP
transfer
680
•
•
•
•
•
•
699
1: Control RUN
[H-PCP-A]
Memory area number
02BD 701 R/WU 1 to 8 1
[H-TIO-, H-CIO-A]
Temperature rise
02BE 702 R/WU 0 to 360 minutes 0
completion soak time
[H-TIO-, H-CIO-A]
Module initialization
[H-PCP-A]
b
02BF 703 R/WU 0: Normal state (Initialization is not executed)
1: Initialize only the new module
(Only modules which are not recognized by the
H-PCP-A module are initialized)
2: Initialize all modules
Returns to 0 after the module is initialized.
Unused 02C0
02EE
a
If the channel of each of the H-TIO-H/J modules is set “1: Used,” it does no reach the completion of temperature rise. As a
704
•
•
•
•
•
•
750
result, the state of this completion (control unit) which is judged by performing the OR operation of all the channels cannot
be attained, thereby continuing the incompletion of temperature rise.
1
Initialize method for changing the module composition
To change module configuration, use the following procedures:
• When a module is added to the control unit............................................................. Initialize only the new module
• When a module is deleted from the control unit ...................................................... Initialize only the new module
• When a module is inserted (Added) between the modules in the control unit ......... Initialize all modules
• To change the arrangement of the modules in the control unit ................................ Initialize all modules
Note that when all modules are initialized all internal data of all modules are set to the
default values.
Factory
set value
0
0
0
80
IMS01S01-E1
8. TROUBLESHOOTING
This section explains probable causes and treatment procedures if any abnormality occurs in the instrument.
For any inquiries, please contact RKC sales office or the agent, to confirm the specifications of the product.
If it is necessary to replace a device, always strictly observe the warnings below.
To prevent electric shock or instrument failure, always turn off the system
power before replacing the instrument.
To prevent electric shock or instrument failure, always turn off the power
before mounting or removing the instrument.
To prevent electric shock or instrument failure, do not turn on the power until
all the wiring is completed.
To prevent electric shock or instrument failure, do not touch the inside of the
instrument.
All wiring must be performed by authorized personnel with electrical
experience in this type of work.
CAUTION
All wiring must be completed before power is turned on to prevent electric shock, instrument
failure, or incorrect action. The power must be turned off before repairing work for input break
and output failure including replacement of sensor, contactor or SSR, and all wiring must be
completed before power is turned on again.
When replacing the module with a new one, always use the module with the same model
code. If the module is replaced, it is necessary to re-set each data item.
WARNING
!
IMS01S01-E1 81
8. TROUBLESHOOTING
Problem Probable cause Solution
RUN lamp does not light up Power supply section defect Replace H-LNK-B module
RX/TX lamp does not flash Imperfect connection of H-LNK-B and
H-PCP module
Confirm the connection condition or
connector and connect correctly
FAIL lamp is lit CPU section defect Replace H-LNK-B module
• Can not set the IP address
• The client and the server are
not in the connected state
(the client cannot recognize
the server)
The IP address class and subnet mask of
the client do not coincide with those of
the server
The network related software was
started before the connection of the
Coincide the IP address class and
subnet mask of the client with those
of the server
First connect the Ethernet cable and
then start the network related software
Ethernet cable
No response
Wrong connection, no connection or
disconnection of the communication
Confirm the connection method or
condition and connect correctly
cable
Breakage, wrong wiring, or imperfect
contact of the communication cable
Wrong IP address setting
There is length of query message
Confirm the wiring or connector and
repair or replace the wrong one
Confirm the settings and set them
correctly
exceeds set range
The number of data points is not twice
the specified number of data points at
the time of data write
Error code: 01H Function code error
Confirm the function code
(Specifying nonexistent function code)
Error code: 02H When the mismatched address is
specified
Error code: 03H
When the data written exceeds the
Confirm the address of holding
register
Confirm the setting data
setting range
When the number of specified data
points was out of a range of 1 to 125
during data read (function code: 03H)
When the number of specified data
points was out of a range of 1 to 123
during data write (function code: 10H)
Error code: 04H State under which the server
(H-LNK-B) cannot normally respond
Remove the cause of the error
occurring in the server (H-LNK-B)
[An error occurred in the server
(H-LNK-B)]
82
IMS01S01-E1
9. SPECIFICATIONS
Ethernet communication
Physical layer: Ethernet
10BASE-T/100BASE-TX automatic recognition
Application layer: Modbus/TCP or No-protocol
Communication data: Based on Modbus message format (Modbus/TCP)
Based on ANSI X3.28 subcategory 2.5 A4 (No-protocol)
IP address: 0.0.0.0 to 255.255.255.255
Connector type: RJ-45
Maximum connections: Up to sixteen SR Mini HG control units can be connected to one H-LNK-B