Modbus is a registered trademark of Schneider Electric.
DeviceNet is a registered trademark of Open DeviceNet Vender Association, Inc.
Company names and product names used in this manual are the trademarks or registered trademarks of
the respective companies.
All Rights Reserved, Copyright 2002, RKC INSTRUMENT INC.
Thank you for purchasing this RKC instrument. In order to achieve maximum performance and ensure
proper operation of your new instrument, carefully read all the instructions in this manual. Please
place this manual in a convenient location for easy reference.
NOTICE
This manual assumes that the reader has a fundamental knowledge of the principles of electricity,
process control, computer technology and communications.
The figures, diagrams and numeric values used in this manual are only for purpose of illustration.
RKC is not responsible for any damage or injury that is caused as a result of using this instrument,
instrument failure or indirect damage.
Periodic maintenance is required for safe and proper operation of this instrument. Some
components have a limited service life, or characteristics that change over time.
Every effort has been made to ensure accuracy of all information contained herein. RKC makes no
warranty expressed or implied, with respect to the accuracy of the information. The information in
this manual is subject to change without prior notice.
No portion of this document may be reprinted, modified, copied, transmitted, digitized, stored,
processed or retrieved through any mechanical, electronic, optical or other means without prior
written approval from RKC.
WARNING
!
An external protection device must be installed if failure of this instrument
could result in damage to the instrument, equipment or injury to personnel.
All wiring must be completed before power is turned on to prevent electric
shock, fire or damage to instrument and equipment.
This instrument must be used in accordance with the specifications to
prevent fire or damage to instrument and equipment.
This instrument is not intended for use in locations subject to flammable or
explosive gases.
Do not touch high-voltage connections such as power supply terminals, etc.
to avoid electric shock.
RKC is not responsible if this instrument is repaired, modified or
disassembled by other than factory-approved personnel. Malfunction can
occur and warranty is void under these conditions.
IMR01N02-E6
i-1
CAUTION
This is a Class A instrument. In a domestic environment, this instrument may cause radio
interference, in which case the user may be required to take adequate measures.
This instrument is protected from electric shock by reinforced insulation. Provide
reinforced insulation between the wire for the input signal and the wires for instrument
power supply, source of power and loads.
Be sure to provide an appropriate surge control circuit respectively for the following:
- If input/output or signal lines within the building are longer than 30 meters.
- If input/output or signal lines leave the building, regardless the length.
This instrument is designed for installation in an enclosed instrumentation panel. All
high-voltage connections such as power supply terminals must be enclosed in the
instrumentation panel to avoid electric shock by operating personnel.
All precautions described in this manual should be taken to avoid damage to the
instrument or equipment.
All wiring must be in accordance with local codes and regulations.
All wiring must be completed before power is turned on to prevent electric shock,
instrument failure, or incorrect action.
The power must be turned off before repairing work for input break and output failure
including replacement of sensor, contactor or SSR, and all wiring must be completed
before power is turned on again.
To prevent instrument damage or failure, protect the power line and the input/output lines
from high currents with a protection device such as fuse, circuit breaker, etc.
Prevent metal fragments or lead wire scraps from falling inside instrument case to avoid
electric shock, fire or malfunction.
Tighten each terminal screw to the specified torque found in the manual to avoid electric
shock, fire or malfunction.
For proper operation of this instrument, provide adequate ventilation for heat dispensation.
Do not connect wires to unused terminals as this will interfere with proper operation of the
instrument.
Turn off the power supply before cleaning the instrument.
Do not use a volatile solvent such as paint thinner to clean the instrument. Deformation or
discoloration will occur. Use a soft, dry cloth to remove stains from the instrument.
To avoid damage to instrument display, do not rub with an abrasive material or push front
panel with a hard object.
Do not connect modular connectors to telephone line.
i-2
IMR01N02-E6
DOCUMENT CONFIGURATION
As for the document related to this product, there are six manuals including this manual. According to
application of a customer, please read a manual related together. When you do not have a necessary manual,
please contact RKC sales office or the agent.
Manual Manual NumberRemarks
HA400/HA900/HA401/HA901
Instruction Manual
HA400/HA900/HA401/HA901
Operation Manual
HA400/HA900/HA401/HA901
Communication Instruction Manual *
[RKC communication/MODBUS]
HA400/HA900/HA401/HA901
Communication Instruction Manual *
[PROFIBUS]
IMR01N01-EA product box contains this manual.
This manual explains the mounting and wiring,
a name of the front panel, and outline of
the operation mode of the product.
IMR01N02-E6
IMR01N03-EThis manual explains RKC communication
IMR01N04-EThis manual explains PROFIBUS
This Manual.
This manual explains the method of
the mounting and wiring, the operation of
various functions, and troubleshooting.
protocol, MODBUS, and relating to
the communication parameters setting.
communication connection and configuration.
HA400/HA900/HA401/HA901
Communication Instruction Manual *
[DeviceNet]
Infrared Communication Software RKCIR
for HA Series Controller
PDA INSTALL GUIDE
* Optional function
Read this manual carefully before operating the instrument. Please place this manual in a convenient
location for easy reference.
IMR01N05-EThis manual explains DeviceNet
communication connection and node address
setting.
IMT01C01-E This manual describes downloading of the
"RKCIR infrared communication software" and
installation of this software to the PDA.
IMR01N02-E6
i-3
t
Safety Symbols
WARNING
CAUTION
: This mark indicates precautions that must be taken if there is danger of electric
shock, fire, etc., which could result in loss of life or injury.
: This mark indicates that if these precautions and operating procedures are no
taken, damage to the instrument may result.
!
: This mark indicates that all precautions should be taken for safe usage.
: This mark indicates important information on installation, handling and operating
procedures.
: This mark indicates supplemental information on installation, handling and
operating procedures.
: This mark indicates where additional information may be located.
This Chapter describes features, package contents and model code, etc.
The digital controller of this high performance type has the following features:
High-speed sampling time (25 ms)
Suitable for fast responding control systems.
Autotuning function corresponding to fast response
• The HA400/HA900 is best suited for applications that reach setpoint quickly (within 30 seconds). *
• The HA401/HA901 is best suited for applications that take more than 30 seconds to reach setpoint. *
* Autotuning a process with a fast response may produce PID constants that would fluctuate the process excessively. If the process is less than
5 minutes to setpoint, RKC recommends adjusting the AT differential gap to less than 10 seconds (default value in the HA401/HA901) prior
to autotuning.
Up to two inputs, 2-loop control in one instrument
Control mode is selectable from 1 loop control, 2-loop control (2 input type only) and cascade control.
Direct function keys
Three Direct Function Keys on the front panel are provided for one-key operation to switch Auto/Manual,
Remote/Local, and RUN/STOP.
Up to 16 memory areas or ramp/soak control
HA400/HA900/HA401/HA901 can store up to 16 sets of control parameters. Ramp/Soak control is available by
using the memory area function.
Two communication ports (optional)
HA400/HA900/HA401/HA901 incorporates a maximum of two communication ports to communicate with a
computer, operation panel, programmable controller, etc.
1.1 Checking the Product
Before using this product, check each of the following:
Model code
Check that there are no scratch or breakage in external appearance (case, front panel, or terminal, etc).
Check that all of the items delivered are complete. (See below)
Instrument 1
Mounting brackets Each 2Waterproof/dustproof options: each 4
Instruction Manual (IMR01N01-E) 1 Enclosed with instrument
Operation Manual (IMR01N02-E6) 1 This Manual
Communication Instruction Manual (IMR01N03-E)
[RKC communication/Modbus]
Communication Instruction Manual (IMR01N04-E)
[PROFIBUS]
Communication Instruction Manual (IMR01N05-E)
[DeviceNet]
PDA Install Guide (IMT01C01-E) 1 Infrared communication software “RKCIR”
Power feed transformer (100V type or 200V type) 1 Optional
Current transformer (CTL-6-P-N or CTL-12-S56-10L-N) 1 or 2 Optional (sold separately)
If any of the products are missing, damaged, or if your manual is incomplete, please contact RKC sales
office or the agent.
Accessories Q’TY Remarks
Optional
1
With RKC communication or Modbus
Optional
1
With PROFIBUS
Optional
1
With DeviceNet
IMR01N02-E6 1
1. OUTLINE
1.2 Model Code
Check whether the delivered product is as specified by referring to the following model code list. If the product
is not identical to the specifications, please contact RKC sales office or the agent.
Y : Version symbol (Infrared communication function included)
4
IMR01N02-E6
1. OUTLINE
1.3 Input/Output Functions
This section describes the input/output functions of the instrument. To learn how to set each function, see the
respective page.
INPUT In addition to measured input, 5 optional input functions are available.
Measured input: 1-input or 2-input. (Specify when ordering)
Input types available for measured inputs are shown in the table below.
Thermocouple * K, J, T, S, R, E, B, PLII, N, W5Re/W26Re
RTD * Pt100, JPt100 [Factory set value: Pt100]
Voltage (low) * 0 to 100 mV DC, 0 to 10 mV DC, 0 to 1 V DC [Factory set value: 0 to 1 V DC]
Voltage (High) * 0 to 5 V DC, 1 to 5 V DC, DC 0 to 10 V DC [Factory set value: 1 to 5 V DC]
Current * 0 to 20 mA DC, 4 to 20 mA DC [Factory set value: 4 to 20 mA DC]
*
To change the input type, see 8. ENGINEERING MODE (P. 50).
The second measured input can be used as isolated remote input.
Event input: Optional Event Input hardware is necessary. (Specify when ordering) Event Input can be used for the following functions. (See P. 70.)
Memory area selection (Number of areas: 1 to 16 or 1 to 8)
Operation mode transfer (RUN/STOP, Remote/Local, Auto/Manual.)
Remote input (non-isolated type):
Remote input is to change a control setpoint by using current or voltage input from an
external device.
Remote input is available with 1-input controller. (Specify when ordering)
Measured input at Input 1 is not isolated from remote input at Input 2. If isolated remote
input is necessary, specify 2-input controller when ordering, and use the second input for
remote input.
Any one of the following input types can be selected. (See P. 66.)
Voltage (low) 0 to 100 mV DC, 0 to 10 mV DC, 0 to 1 V DC
Voltage (High) 0 to 5 V DC, 1 to 5 V DC, DC 0 to 10 V DC
Current 0 to 20 mA DC, 4 to 20 mA DC
CT input: CT input is used for Heater Break Alarm function to detect a heater break or short-circuit. Up to two CT inputs can be selected. (Specify when ordering)
Only one CT input is available when power feed forward input is selected.
Measured input is not isolated from CT input.
CT inputs accept signal from dedicated current transformers (CT).
Two types of CT available. (See P. 81.)
CTL-6-P-N (for 0 to 30 A)
CTL-12-S56-10L-N (for 0 to 100 A)
IMR01N02-E6
5
1. OUTLINE
Power feed forward (PFF) input:
Power feed forward input is used for Power Feed Forward function to achieve accurate
control. PFF monitors power supply voltage variation on a device and compensates
control output from the controller.
Two types of dedicated transformer is available. (Specify either of them when ordering)
PFT-01 100 V type transformer (100 to 120 V AC)
PFT-02 200 V type transformer (200 to 240 V AC)
Feedback resistance input:
Feedback resistance input is used to monitor a valve position when position proportioning
PID control is selected as control action.
Measured input is not isolated from feedback resistance input.
OUTPUT Up to five outputs are available. They may be used as control output, event output or
transmission output by specifying the output type or by activating the output logic
function (output logic selection).
Output1 to 3 (OUT1 to OUT3):
Control output, event output, HBA alarm output, or transmission output can be allocated
to output 1 to 3. (See P. 73 to 80.)
Number of outputs and output types must be specified when ordering.
Output types available for OUT1 to OUT3 are shown in the table below.
The following event types can be selected for EV1 to EV4.
Deviation high Band SV high
Deviation low
Deviation high/low
Process high SV low
Process low LBA (Only EV3 and EV4 can be selected)
6
The maximum number of event output is four.
Output allocation is necessary to output the event state from output terminals. (See P. 73.)
IMR01N02-E6
1. OUTLINE
Transmission output 1 to 3 (AO1 to AO3):
Maximum three transmission output can be allocated to OUT1, OUT2, and OUT3.
Maximum number of output available for transmission output varies by other output use
for control output and event output. Parameter values shown in the following table can be
output by transmission output. (See P. 75.)
Input 1 side Measured value (PV), Set value (SV), Manipulated output value (MV),
Deviation (PV−SV)
Input 2 side Measured value (PV), Set value (SV), Manipulated output value (MV),
Deviation (PV−SV)
Output logic function:
Output logic function allocates output functions to output terminals. Logic output such as
OR/AND is available for event output. The following signals are allocated by output logic
function. Transmission output needs to be allocated separately. (See P. 70 to 73.)
Input Analog signal: Control output value (max. 2 points)
Digital signal: Event action state (4 points), HBA action state (max. 2 points),
Position proportioning output state (2 points), Contact input state (max. 7 points), Control area number (4 points) Operation state (3points): LOC/MAN/REM
Output Computed output from OUT1 to OUT5.
COMMUNICATION
Communication 1, Communication 2 (optional):
Up to two communication ports are available to communicate with a computer or
programmable controller. When DI 6 and 7 are used, communication port 1 is not
available. (Specify when ordering)
The protocols available for each port are shown in the table below.
Interface *
Protocol *
Open Network *
* Specify when ordering.
Infrared communication:
Infrared communication can be used when sending and receiving data between this
controller and the PDA installed with the RKCIR software.
Communication 1 function * Communication 2 function *
This chapter describes various display units and the key functions.
HA400/HA401
HA900/HA901
Upper display
rea display
Infrared port
Upper display
rea display
Infrared port
PV1
SET
PV1 PV2 MAN REM AT
AREA PV2 MAN REM AT SV
OUT1 OUT2 OUT3 OUT4 OUT5 ALM
A/M R/L R/S
MODE
SET
PV2 MAN
/M R/L R/S
PV2 MAN REM AT SV
OUT1 OUT2 OUT3 OUT4 OUT5 ALM
MODE
REM
Lower display
Output/Alarm lamp
Bar gragh display
Direct keys
Operation keys
AT
Lower display
Output/Alarm lamp
Bar gragh display
Direct keys
Operation keys
8
IMR01N02-E6
Upper display
Measured value 1 (PV1) lamp [Green] Lights when measured value 1 is displayed on the PV1/PV2 display unit.
Measured value 2 (PV2) lamp * [Green] Lights when measured value 2 is displayed on thePV1/PV2 display unit.
Manual (MAN) mode lamp [Green] Lights when operated in manual mode.
Remote (REM) mode lamp [Green] Lights when remote setting function is activated.
Autotuning (AT) lamp [Green]
Measured value (PV1/PV2) display Displays PV1, PV2 or various parameters’ symbols.
* This lamp is activated only with 2-input controller.
Flashes when autotuning is activated.
(After autotuning is completed: AT lamp will become OFF)
Lower display
Measured value 2 (PV2) lamp * [Green] Lights when measured value 2 is displayed on the SV display unit.
Set value (SV) lamp [Green] Lights when set value (SV) is displayed on the SV display unit.
Manual (MAN) mode lamp * [Green] Lights when operated in manual mode.
Autotuning (AT) lamp * [Green] Flashes when autotuning is activated.
(After autotuning is completed: AT lamp will become OFF)
Set value (SV) display Displays SV, PV2 or various parameters’ set values.
* This lamp is activated only with 2-input controller.
Area display
1. OUTLINE
Area (AREA) lamp [Green] Lights when memory area number is displayed.
Memory area display Displays memory area number (1 to 16).
Output/Alarm lamp
Output (OUT1 to OUT5) lamp [Green] Lights when the output corresponding to each lamp is ON.
Alarm (ALM) lamp [Red] Lights when alarm (Event or HBA function) is turned on.
The type of alarm which is on can be checked on the event monitor display.
These lamps works with outputs (control, alarm, retransmission) which are assigned to OUT1 through OUT5.
For assignment of outputs to OUT1 through OUT5, see Transmission Output Type Selection (P.75) and Output Logic
Selection (P.73).
IMR01N02-E6
9
1. OUTLINE
−
+
Bar graph display [Green] *
One of the displays shown in the table below can be selected for the bar-graph.
Manipulated output value (MV) display
Measured value display
Set value display Displays the set value (SV). Scaling is available within the input range.
Deviation display
Feedback resistance input value (POS)
display
* The number of dots: 10 dots (HA400/HA401) 20 dots (HA900/HA901)
Displays the manipulated output value (MV). When manipulated output value (MV) is
at 0 % or less, the left-end dot of the bar-graph flashes. When MV exceeds 100 %, the
right-end dot flashes.
[Example]
050
100
Displays the measured value (PV). Scaling is available within the input range.
[Example]
050
100
[Example]
050
100
Displays the deviation between the measured value (PV) and the set value (SV).
When the Deviation display is selected, the dots at both ends of bar-graph light.
[Example]
0
Displays the feedback resistance input value (POS).
(Available with position proportioning PID control)
[Example]
050
100
The bar-graph function is not activated at the factory unless the controller is specified as position proportioning PID controller
when ordered Bar graph display can be selected in the Engineering Mode. See selecting the bar graph display (P.64).
Direct keys
A/M
Auto/Manual transfer key Switching the Auto/Manual control mode between Auto (PID control) mode and Manual
mode.
R/L
Remote/Local transfer key Switching the Remote/Local control mode between Remote control and Local control.
R/S
RUN/STOP transfer key Switching the RUN/STOP mode between RUN and STOP.
To avoid damage to the instrument, never use a sharp object to press keys.
For the Auto/Manual transfer key, it is possible to select among Auto/Manual transfer for (1) Input1, (2) Input2, or (3) both
Input 1 and Input 2. (See P. 65.)
Use/Unuse of Direct Key function are programmable. (See P. 65.)
To prevent operator error, a direct key cannot be operated in positioning adjustment (automatic adjustment).
Operation keys
SET
Set (SET) key Used for parameter calling up and set value registration.
MODE
Shift key Shift digits when settings are changed.
Used to selection operation between modes.
Down key Decrease numerals.
Up key Increase numerals.
To avoid damage to the instrument, never use a sharp object to press keys.
Infrared port
Used when sending and receiving data between this controller and the PDA installed with the RKCIR software.
The RKCIR software can be downloaded from our home page. For this purpose, user registration address and password are required.
For details, PDA INSTALL GUIDE (IMT01C01-E).
10
IMR01N02-E6
2. MOUNTING
This chapter describes installation environment, mounting cautions, dimensions and mounting procedures.
To prevent electric shock or instrument failure, always turn off the power before
mounting or removing the instrument.
WARNING
!
2.1 Mounting Environment
(1) This instrument is intended to be used under the following environmental conditions. (IEC61010-1)
[OVERVOLTAGE CATEGORY II, POLLUTION DEGREE 2]
(2) Use this instrument within the following ambient temperature and ambient humidity.
• Allowable ambient temperature: −10 to +50 °C
• Allowable ambient humidity: 5 to 95 % RH
(Absolute humidity: MAX. W. C 29 g/m
(3) Avoid the following conditions when selecting the mounting location:
• Rapid changes in ambient temperature which may cause condensation.
• Corrosive or inflammable gases.
• Direct vibration or shock to the mainframe.
• Water, oil, chemicals, vapor or steam splashes.
• Excessive dust, salt or iron particles.
• Excessive induction noise, static electricity, magnetic fields or noise.
• Direct air flow from an air conditioner.
• Exposure to direct sunlight.
• Excessive heat accumulation.
3
dry air at 101.3 kPa)
2.2 Mounting Cautions
Take the following points into consideration when mounting this instrument in the panel.
• Provide adequate ventilation space so that heat does not build up.
• Do not mount this instrument directly above equipment that generates large amount of heat (heaters,
• If the ambient temperature rises above 50 °C, cool this instrument with a forced air fan, cooler, or the like.
However, do not allow cooled air to blow this instrument directly.
• In order to improve safety and the immunity to withstand noise, mount this instrument as far away as possible
from high voltage equipment, power lines, and rotating machinery.
High voltage equipment: Do not mount within the same panel.
Power lines: Separate at least 200 mm.
Rotating machinery: Separate as far as possible.
• Mount this instrument in the horizontal direction for panel. If you did installation except a horizontal direction,
this causes malfunction.
IMR01N02-E6 11
2. MOUNTING
+
+
2.3 Dimensions
HA400/HA401
(Unit: mm )
48
44.8
11.1
Individual mounting
+0.6
+0.6
45
45
25
25
+0
+0
+0.8
+0
+0.8
+0
92
92
30
*3, *4
30
96
91.8
110.8
Close mounting
0.6
L
+0
*1
10.1 100
(1)
+0.8
+0
92
L = 48×n-3 n: Number of units (2 ≤ n ≤ 6)
HA900/HA901
Individual mounting
(Unit: mm )
25
91.8
96
11.1
*2
96
91.8
110.8
Close mounting
0.8
L
+0
*1
10.1
(1)
L = 96×n-4 n: Number of units (2 ≤ n ≤ 6)
100
*1 Rubber (Option)
*2 Up to 4 mounting brackets may be used.
*3 If the HA400/HA401s or HA900/HA901s have waterproof/dustproof options, protection will be compromised and not
meet IP65 by close mounting.
*4 When controllers are closely mounted, ambient temperature must not exceed 50 °C.
For mounting of the HA400/HA401 or HA900/HA901, panel thickness must be between 1 to 10 mm. When mounting
multiple HA400/HA401s or HA900/HA901s close together, the panel strength should be checked to ensure proper
support.
92
*3, *4
+0.8
+0
0.8
0
92
30
+0.8
+0
92
12
IMR01N02-E6
2. MOUNTING
2.4 Procedures of Mounting and Removing
Mounting procedures
1. Prepare the panel cutout as specified in 2.3 Dimensions. (Panel thickness: 1 to 10 mm)
2. Insert the instrument through the panel cutout.
3. Insert the mounting bracket into the mounting groove of the instrument. (Fig. 1)
4. Pull till click sounds to the direction shown by the arrow. (Fig. 2)
5. Tighten up the screw. (Fig. 3)
6. The other mounting bracket should be installed the same way described in 3. to 5.
Fig. 1
HA900/HA901 is used in the above figures for explanation, but
the same mounting procedures also apply to HA400/HA401.
When the instrument is mounted, always secure with two mounting brackets so that upper and lower
mounting brackets are positioned diagonally.
The waterproof/dustproof option on the front of the instrument conforms to IP65 when mounted on the
panel. For effective waterproof/dustproof, the gasket must be securely placed between instrument and
panel without any gap. If gasket is damaged, please contact RKC sales office or the agent.
Removing procedures
Mounting
bracket
Fig. 2
Fig. 3
When using the mounting
screws, only turn one full
revolution after the screw
touches the panel.
1. Loosen the screw of the mounting bracket.
2. Remove the mounting bracket from the case. (Fig. 4)
3. Pull out the instrument from the mounting cutout while
holding the front panel frame of this instrument.
When pulling out only the internal assembly from
the instrument case after being wired, see
12. REMOVING THE INTERNAL ASSEMBLY
(P. 125).
IMR01N02-E6
Fig.4
Pull out
Front panel
frame
13
3. WIRING
This chapter describes wiring cautions, wiring layout and wiring of terminals.
To prevent electric shock or instrument failure, do not turn on the power
until all the wiring is completed.
WARNING
!
3.1 Wiring Cautions
• For thermocouple input, use the appropriate compensation wire.
• For RTD input, use low resistance lead wire with no difference in resistance between the three or four lead
wires.
• To avoid noise induction, keep input signal wire away from instrument power line, load lines and power lines
of other electric equipment.
• If there is electrical noise in the vicinity of the instrument that could affect operation, use a noise filter.
− Shorten the distance between the twisted power supply wire pitches to achieve the most effective noise
reduction.
− Always install the noise filter on a grounded panel. Minimize the wiring distance between the noise filter
output and the instrument power supply terminals to achieve the most effective noise reduction.
− Do not connect fuses or switches to the noise filter output wiring as this will reduce the effectiveness of the
noise filter.
• About five seconds are required as preparation time for contact output every time the instrument is turned on.
Use a delay relay when the output line is used for an external interlock circuit.
• Power supply wiring must be twisted and have a low voltage drop.
• For an instrument with 24 V power supply, supply power from a SELV circuit.
• This instrument is not furnished with a power supply switch or fuse. Therefore, if a fuse or power supply
switch is required, install close to the instrument.
Recommended fuse rating: Rated voltage 250 V, Rated current 1 A
Fuse type: Time-lag fuse
• Use the solderless terminal appropriate to the screw size.
Screw size: M3 × 6 (With 5.8 × 8 square washer )
Recommended tightening torque: 0.4 N・m (4 kgf・cm)
Recommended dimension:
6 mm
5.9 mm MAX
3.2 mm MIN
14 IMR01N02-E6
3. WIRING
3.2 Terminal Layout
The terminal layout is as follows. HA400/HA401 is used in the figures for explanation, but the same terminal
layouts also apply to HA900/HA901.
1-input controller
Power supply voltage
100 to 240 V AC
24 V AC
24 V AC
Output 5 (OUT5)
Output 4 (OUT4)
Output 3 (OUT3)
Output 2 (OUT2)
Output 1 (OUT1)
2-input controller
1
2
3
4
5
6
7
8
9
10
11
12
25
26
27
28
29
30
31
32
33
34
35
36
13
14
15
16
17
18
19
20
21
22
23
24
Optional
Communication 2
Optional
Communication 1
Event input (DI6 to DI7)
Optional
CT input
Feedback resistance input
Power feed forward input
Optional
Remote input (non-isolated type)
Measured input
Thermocouple/RTD/Voltage/Current
Optional
Event input (DI1 to DI4, DI5)
Power supply voltage
100 to 240 V AC
24 V AC
24 V AC
Output 5 (OUT5)
Output 4 (OUT4)
Output 3 (OUT3)
Output 2 (OUT2)
Output 1 (OUT1)
1
2
3
4
5
6
7
8
9
10
11
12
25
26
27
28
29
30
31
32
33
34
35
36
13
14
15
16
17
18
19
20
21
22
23
24
Optional
Communication 2
Optional
Communication 1
Event input (DI6 to DI7)
Optional
CT input
Feedback resistance input
Power feed forward input
Measured input 2
Thermocouple/RTD/Voltage/Current
Measured input 1
Thermocouple/RTD/Voltage/Current
Optional
Event input (DI1 to DI4, DI5)
IMR01N02-E6
15
3. WIRING
A
A
+
−
3.3 Wiring of Each Terminal
Prior to conducting wiring, always check the polarity of each terminal.
The terminal nameplate of this instrument and its descriptions are shown in the following.
Symbols on the input terminal block
correspond to the type of external input
connected to the instrument
Thermocouple Relay contact output
+
TC
−
[Example]
Instrument
inside
23
Relay
24
23
24
Symbols on the output terminal block
NO
correspond to the type (state) of output
sent from the instrument.
Power supply
• Connect the power to terminal numbers 1 and 2.
L
C
100-240 V
100-240 V AC power
supply type
1
2
N
24 V AC power supply type
• The power supply types must be specified when ordering. Power supply voltage for the controller must be
within the range shown below for the controller to satisfy the control accuracy in the specifications.
Power supply type Power consumption
90 to 264 V AC [Power supply voltage range], 50/60 Hz,
(Rating 100 to 240 V AC)
21.6 to 26.4 V AC [Power supply voltage range],
50/60 Hz, (Rating 24 V AC)
21.6 to 26.4 V DC [Power supply voltage range],
(Rating 24 V DC)
• If there is electrical noise in the vicinity of the instrument that could affect operation, use a noise filter.
• Power supply wiring must be twisted and have a low voltage drop.
• For an instrument with 24 V power supply, supply power from a SELV circuit.
• This instrument is not furnished with a power supply switch or fuse. Therefore, if a fuse or power supply
switch is required, install close to the instrument.
Recommended fuse rating: Rated voltage 250 V, Rated current 1 A
Fuse type: Time-lag fuse
L
C
24 V
1
2
N
HA400/HA401: 16.5 VA max. (at 100 V AC), 22.5 VA max. (at 240 V AC)
HA900/HA901: 17.5 VA max. (at 100 V AC), 24.0 VA max. (at 240 V AC)
HA400/HA401: 15.0 VA max. (at 24 V AC)
HA900/HA901: 16.0 VA max. (at 24 V AC)
HA400/HA401: 430 mA max. (at 24 V DC)
HA900/HA901: 470 mA max. (at 24 V DC)
DC
24 V DC power supply type
1
24 V
2
16
IMR01N02-E6
Loading...
+ 152 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.