RKC COM-JH Data List

DeviceNet Communication Converter
A
M
-JH
t
Communication
CO
ll Rights Reserved, Copyright 2007, RKC INSTRUMENT INC.
[For SRZ]
Data Lis
IMR01Y32-E1
This manual describes the communication data of the COM-JH. For the installation, the detail handling procedures and various function settings, please refer to the following separate manuals.
COM-JH [For SRZ] Quick Instruction Manual (IMR01Y28-E): Enclosed with COM-JH
COM-JH [For SRZ] Instruction Manual (IMR01Y36-E): Separate
(Download or sold separately)
The above manuals can be downloaded from our website:
URL: http://www.rkcinst.com/english/manual_load.htm
1. USAGE OF COMMUNICATION DATA ITEMS
“Communication items,” the “Number of communication controllers” and the “Number of communication words” necessary for polling I/O communication are set via Explicit message communication or using the configuration tool.
Communication items
The measured data item (IN) and setting data item (OUT) communicating via polling I/O communication set the attribute ID, “Controller object (0x64: 64Hex, 0x65: 65Hex, 0x66: 66Hex)” to object instance 1 corresponding to the device profile, “Controller communication item setting object (0xC7: C7Hex).”
Number of communication controllers
The number of communication controllers means the number of controllers connected to the COM-JH. The number of communication controllers is set to attribute ID: 236 of the Z-TIO module object (0x64: 64Hex).
Number of communication words
The number of communication words means the number of words corresponding to the measured data item (IN) and setting data item (OUT) communicating via polling I/O communication. The number of communication words is set to attribute ID: 240 [Measured data item (IN)] and 241 [Setting data item (OUT)] of the Z-TIO module object (0x64: 64Hex)
The number of communication words can be calculated from the following equation.
Number of communication words
For Explicit message communication and the configuration tool, see COM-JH [For SRZ] Instruction Manual (IMR01Y36-E).
For “Controller communication item setting object (0xC7: C7Hex)” and “Controller object (0x64: 64Hex, 0x65: 65Hex, 0x66: 66Hex),” see 3. DEVICE PROFILES and the COM-JH [For SRZ] Instruction Manual (IMR01Y36-E).
The number of communication controllers can be set even by the communication environment setting made by the COM-JH rotary switch.
For details of the number of communication controllers, see COM-JH [For SRZ] Instruction Manual (IMR01Y36-E).
For communication environment setting made by the rotary switch, see
COM-JH [For SRZ] Quick Instruction Manual (IMR01Y28-E).
= (Number of words of first communication item for one module + Number of words of next communication item for one module
+ Number of words of last communication item for one module) × Number of communication controllers + Fixed communication date items: 5 words *
* Measured data items (IN)
Receive counter: 1 word, Alarm state: 2 words, RUN/STOP state: 2 words Setting data items (OUT) Setting state selection: 3 words, RUN/STOP transfer: 2 words
The number of communication words can be set even by the communication
environment setting made by the COM-JH rotary switch.
For details of the number of communication words, see COM-JH [For SRZ] Instruction Manual (IMR01Y36-E).
For communication environment setting made by the rotary switch and fixed communication data items, see COM-JH [For SRZ] Quick Instruction
Manual (IMR01Y28-E).
2. CONTROLLER OBJECT DATA ITEMS
The controller objects consist of the three types below. The content of each object is indicated by the order of the attribute IDs.
Z-TIO module object (0x64: 64Hex)
Z-TIO module extended object (0x65: 65Hex)
Z-DIO module object (0x66: 66Hex)
ID: Attribute ID
Number of data items: 1: Only object instance 1 is valid
2: Only object instance 1 and 2 are valid 16: Valid for object instance 1 to 16 31: Valid for object instance 1 to 31 64: Valid for object instance 1 to 64 128: Valid for object instance 1 to 128
Attribute: RO: Only reading data is possible (Get: Yes, Set: No) R/W: Reading and writing data is possible (Get: Yes, Set: Yes)
Data range: For 16-bit data
For details of data item, see COM-JH [For SRZ] Instruction Manual
(IMR01Y36-E).
Z-TIO Module Object (0x64: 64Hex)
ID Name
1 Measured value (PV) 64 RO Input scale low to Input scale high 2 Current transformer (CT)
input value monitor 3 Unused 4 Set va lue (SV) mo nitor 64 RO Setting limiter (low) to Setting limiter (high )
5 Remote setting (RS) input
value monitor 6 Burnout state monitor 64 RO 0: OFF
7 Unused 8 Event 1 state monitor 64 RO 9 Event 2 state monitor 64 RO
10 Event 3 state monitor 11 Event 4 state monitor 64 RO 12 Heater break alarm (HBA)
state monitor
13 Unused 14 Manipulated output value
(MV) monitor [heat-side]
15 Manipulated output value
(MV) monitor [cool-side]
16 Error code 16 RO Bit data
17 Unused 18 Output state monitor 16 RO Bit data
19 Operation mode state
monitor
20 Memory area soak time
monitor
21 Integrated operating time
monitor
22 Holding peak value ambient
temperature monitor
23 Unused 24 Backup memory state
monitor
25
Unused
32
PID/AT transfer 2
33
34 Auto/Manual transfer 64 R/W 0: Auto mode
35 Remote/Local transfer 64 R/W 0: Local mode
36 RUN/STOP transfer 16 R/W 0: STOP (control stop)
1
If the Event 3 type is temperature rise completion, check the temperature rise completion state in the comprehensive event state [Z-TIO module extended object (0x65: 65Hex) ID: 1]. (The Event 3 state monitor does not turn ON.)
2
When using PID/AT transfer by polling I/O communication, it is necessary to set action mode selection to "PID/AT transfer by polling I/O communication is valid."
1
64 RO
…………….……………………
b15
Number
Attri-
of data
bute
items
64 RO CTL-6-P-N: 0.0 to 30.0A
64 RO Setting limiter (low) to Setting limiter (high )
64 RO 0: OFF
64 RO PID control or heat/cool PID control:
64 RO −5.0 to +105.0 %
64 RO Bit data
64 RO 0 to 11999 seconds or 0 to 5999 minutes
16 RO 0 to 19999 hours
64 RO −10.0 to +100.0 °C or 14 to 212 °F
16 RO 0: The content of the backup memory
64 R/W 0: PID control
CTL-12-S56-10L-N: 0.0 to 100.0 A
1: ON
0: OFF 1: ON
1: ON
5.0 to +105.0 % Position proportioning control with feedback resistance (FBR) input:
0.0 to 100.0 %
b0: Adjustment data error b1: Data back-up error b2: A/D conversion error b3, b4: Unused b5: Logic output data error b6 to b15: Unused Data 0: OFF 1: ON [Decimal number: 0 to 39]
b0: OUT1 state b2: OUT3 state b1: OUT2 state b3: OUT4 state b4 to b15: Unused Data 0: OFF 1: ON [Decimal number: 0 to 15]
b0: Control STOP b1: Control RUN b2: Manual mode b3: Remote mode b4 to b15: Unused Data 0: OFF 1: ON [Decimal number: 0 to 15]
Data range of Area soak time can be selected on the Soak time unit.
does not coincide with that of the RAM.
1: The content of the backup memory
coincides with that of the RAM.
1: Autotuning (AT) *
Automatically reverts to 0 after autotuning ends.
*
1: Manual mode
1: Remote mode
1: RUN (control start)
Data range
b0
Factory
set value
 
0
0
0
0
ID Name
37 Memory area transfer 64 R/W 1 to 8 1 38 Interlock release 64 R/W 0: Normal state
39 Event 1 set value 64 R/W 50
40 Event 2 set value 64 R/W 50
41 Event 3 set value 64 R/W 50
42 Event 4 set value 64 R/W
43 Control loop break alarm
(LBA) time
44 LBA deadband 64 R/W 0 (0.0) to Input span 0 (0.0) 45 Set value (SV) 64 R/W Setting limiter (low) to
46 Proportional band
[heat-side]
47 Integral time [heat-side] 64 R/W PID control or heat/cool PID control:
48 Derivative time [heat-side] ★ 64 R/W
49 Control response
parameter
50 Proportional band
[cool-side]
51 Integral time [cool-side] ★ 64 R/W
52 Derivative time [cool-side] ★ 64 R/W
53 Overlap/Deadband 64 R/W TC/RTD inputs:
54 Manual reset ★ 64 R/W 100.0 to +100.0 % 0.0 55 Setting change rate limiter
(up)
56 Setting change rate limiter
(down)
57 Area soak time 64 R/W 0 to 11999 seconds or 0 to 5999 minute s
58 Link area number 64 R/W 0 to 8 (0: No link) 0 59 Heater break alarm (HBA)
set value
60 Heater break
determination point
61 Heater melting
determination point 62 Unused 63 Unused
64 Unused 65 PV bias 64 R/W Input span to + Input span 0 66 PV digital filter 64 R/W 0.0 to 100.0 seconds (0.0: Unused) 0.0 67 PV ratio 64 R/W 0.500 to 1.500 1.000 68 PV low input cut-off 64 R/W 0.00 to 25.00 % of input span 0.00
69 70 71 72 Proportional cycle time 64 R/W 0.1 to 100.0 seconds
73 Unused 74 Manual manipulated output
: Data related to multi-memory area function
1
Varies with the setting of the integral/derivative time decimal point position selection.
2
The RS bias, RS ratio, and RS digital filter are data for cascade control and proportion setting control.
2
RS bias
RS digital filter 2
RS ratio 2
value
It is possible to change only the data of the control area which is selected by the memory area transfer (ID: 37).
Number
Attri-
of data
bute
items
1: Interlock release execution Deviation action, Deviation action between channels, Temperature rise completion range *:
Input span to +Input span Process action, SV action: Input scale low to Input scale high Manipulated output value (MV):
5.0 to +105.0 % * When temperature rise completion is
64 R/W 0 to 7200 seconds (0: Unused) 480
64 R/W TC/RTD inputs:
64 R/W 0: Slow
64 R/W TC/RTD inputs:
64 R/W 0 (0.0)
64 R/W
64 R/W CTL-6-P-N:
64 R/W 0.0 to 100.0 % of HBA set value
64 R/W 0.0 to 100.0 % of HBA set value
64 R/W Input span to + Input span 0 64 R/W 0.0 to 100.0 seconds (0.0: Unused) 0.0 64 R/W 0.001 to 9.999 1.000
64 R/W PID control:
selected at Event 3 action type.
Setting limiter (high)
0 (0.0) to Input span (Unit: °C [°F]) Voltage (V)/current (I) inputs:
0.0 to 1000.0 % of Input span (0, 0.0: ON/OFF action)
0 to 3600 seconds or
0.0 to 1999.9 seconds 1 (0, 0.0: PD action) Position proportioning control: 1 to 3600 seconds or
0.1 to 1999.9 seconds 1 0 to 3600 seconds or
0.0 to 1999.9 seconds (0, 0.0: PI action)
1: Medium 2: Fast [P or PD action: 2 (Fast) fixed]
1 (0.1) to Input span (Unit: °C [°F]) Voltage (V)/current (I) inputs:
0.1 to 1000.0 % of Input span 0 to 3600 seconds or
0.0 to 1999.9 seconds 1 (0, 0.0: PD action)
00 to 3600 seconds or
0.0 to 1999.9 seconds 1 (0, 0.0: PI action)
Input span to +Input span (Unit:°C [°F]) Voltage (V)/current (I) inputs:
100.0 to +100.0 % of Input span Minus () setting results in overlap.
0 (0.0) to Input span/unit time * 0 (0.0): Unused * Unit time: 60 seconds (f actory set value)
Data range of Area soak time can be selected on the Soak time unit
0.0 to 30.0 A (0.0: Unused) CTL-12-S56-10L-N:
0.0 to 100.0 A (0.0: Unused)
(0.0: Heater break determination is invalid)
(0.0: Heater melting determination is invalid)
M: Relay contact output V: Voltage pulse output T: Triac output D: O pen collector output
Output limiter (low) to Output limiter (high) Heat/cool PID control:
Output limiter (high) to +Output limiter (high) Position proportioning control with feedback resistance (FBR) input: Output limiter (low) to Output limiter (high) Position proportioning control (without FBR input): 0: Close-side output OFF, Open-side output OFF 1: Close-side output ON, Open-side output OFF 2: Close-side output OFF, Open-side output ON
Data range
1
Factory
set value
TC/RTD
inputs: 0 °C
V/I inputs:
0.0 %
TC/RTD inputs: 30 V/I inputs:
30.0
240
PID control,
Position
proportioning
control: 0 Heat/cool
PID control: 2
TC/RTD inputs: 30 V/I inputs:
30.0 240
0 (0.0)
0.0
30.0
30.0
M output:
20.0
V, T, D
output: 2.0
0.0
0
50
60
60
0
0
ID Name
75
Unused
82 83
Engineering setting data
For the data, see COM-JH [For SRZ] Instruction Manual (IMR01Y36-E).
203 204 Startup tuning (ST) 64 R/W 0: Startup tuning (ST) unused
205
Engineering setting data
For the data, see COM-JH [For SRZ] Instruction Manual (IMR01Y36-E).
209 210 Automatic temperature rise
learning
211
Engineering setting data
For the data, see COM-JH [For SRZ] Instruction Manual (IMR01Y36-E).
224 225 Controller state 1 31 RO Bit data
226 Controller state 2 31 RO Bit data
227
Unused
230 231
Comprehensive alarm state 1
232
Controller alarm state
Error state
RUN/STOP 1
1
233
234
1
Valid only when Explicit message communication is used.
Number
of data
items
64 R/W 0: Unused
1 RO Bit data
1
2 RO Bit data
2 RO Bit data
2 R/W Bit data
Attri­bute
1: Execute once * 2: Execute always * Automatically reverts to 0 after Startup tuning
(ST) ends.
1: Learning * * Automatically reverts to 0 after automatic
temperature rise learning ends.
Z-TIO module: b0: Burnout state b1: Unused b2: Event 1 state b3: Event 2 state b4: Event 3 state b5: Event 4 state b6: Heater break alarm (HBA) state b7 to b15: Unused OR data for each Z-TIO module.
Z-DIO module: b0 to b15: Unused
Data 0: OFF 1: ON [Decimal number: 0 to 125]
Z-TIO module: b0: Adjustment data error b1: Data back-up error b2: A/D conversion error b3: Unused b4: Unused b5: Logic output data error b6 to b14: Unused b15: Controller communication error
Z-DIO module: b0: Unused b1: Data back-up error b2 to b14: Unused b15: Controller communication error
Data 0: OFF 1: ON [Decimal number: 0 to 32807]
b0: Burnout state b1: Unused b2: Event 1 state b3: Event 2 state b4: Event 3 state b5: Event 4 state b6: Heater break alarm (HBA) state b7 to b15: Unused Data 0: OFF 1: ON [Decimal number: 0 to 125]
Object instance 1: b0 to b15: Controller 1 to 16 Object instance 2: b0 to b14: Controller 17 to 31 Data 0: OFF 1: ON [Decimal number: 0 to 65535]
OR of Controller state 1 (ID: 225)
Object instance 1: b0 to b15: Controller 1 to 16 Object instance 2: b0 to b14: Controller 17 to 31 Data 0: OFF 1: ON [Decimal number: 0 to 65535]
OR of Controller state 2 (ID: 226)
Object instance 1: b0 to b15: Controller 1 to 16 Object instance 2: b0 to b14: Controller 17 to 31 Data: RUN/STOP state is depending on the value of RUN/STOP logic selection (ID: 242)
ID: 242 = 0 0: RUN (control start), 1: STOP (control stop)
ID: 242 = 1 0: STOP (control stop), 1: RUN (control start) [Decimal number: 0 to 65535]
Link RUN/STOP transfer (ID: 36)
Data range
(Continued on the next page )
Factory
set value
0
0
1
A
)
e
ID Name
235 Setting update flag
236 Number of polling I/O
communication controllers
237
Unused
238 COM-JH error code
239 Number of connected
controller in controller communication 1
240 Number of communication
measured data items (IN) when conducting polling I/O communication
241 Number of communication
setting data items (OUT) when conducting polling I/O communication
242 RUN/STOP logic
selection
243 Setting validity selection
244
Unused 245 Controller address setting 246 Action mode selection
247 Automatic acquisition of
controller address 248
Unused
255
: It is possible to set in the communication environment setting by the rotary switch of COM-JH or
configuration tool.
: Communication environment setting by rotary switch of COM-JH is possible.
1
Valid only when Explicit message communication is used.
2
The setting is validated when the power is turned off once after the setting is changed and it is turned on again.
1, 2
1, 2
1, 2
For communication environment setting by the rotary switch, see COM-JH [For SRZ] Quick Instruction
Manual (IMR01Y28-E).
Number
Attri-
of data
bute
items
1
1 RO 0: Setting update is completed
1 R/W 1 to 31 10
1
1
1 RO Bit data
1 RO 0 to 31
1 R/W 0: Depends on the DIP switch setting
1, 2
1 R/W 0: Depends on the DIP switch setting
1 R/W 0: RUN = 0, STOP = 1
1
1 R/W 0: The setting is validated when the power
1, 2
1 R/W 0 to 32 (0: No communication) 1 to 31
1, 2
1 R/W Bit data
1 R/W 0: Do not execute the automatic acquisition
1: During setting update
b0: Back-up error b1: Controller communication error b2 to b15: Unused Data 0: OFF 1: ON [Decimal number: 0 to 3]
1 to 5: 5 words 6 to 200: 6 to 200 words
1 to 5: 5 words 6 to 200: 6 to 200 words
1: RUN = 1, STOP = 0 Valid to RUN/STOP (ID: 234) and the 4th word and the 5th word in the polling I/O communication setting item (OUT). However, invalid to the RUN/STOP transfer (ID: 36).
is turned off once after the setting is changed and it is turned on again. 1: The setting is validated just after the setting is changed. Object data
The data of “Controller communication item setting object (0xC7)”
The data of “Number of polling I/O communication controllers (ID: 236)”
b0: Address setting method transfer 0: Continuous setting 1: Free setting b1: PID/AT transfer by polling I/O communication 0: Invalid 1: Valid b2 to b15: Unused [Decimal number: 0 to 3]
1: Execute the automatic acquisition
Data range
Factory
set value
Z-TIO Module Extended Object (0x65: 65Hex)
Number
Attri-
ID Name
1 Comprehensive event state 64 RO Bit data
2 Logic output monitor 16 RO Bit data
3 Output distribution selection 64 R/W 0: Control output
4 Output distribution bias 64 R/W 100.0 to +100.0 % 0.0 5 Output distribution ratio 64 R/W −9.999 to +9.999 1.000 6 Minimum ON/OFF time
of proportioning cycle
7 Area soak time stop function 64 R/W 0: No function 3: Event 3
8 EDS mode (for disturbance 1) 64 R/W 0
9 EDS mode (for disturbance 2) 64 R/W
10 EDS value 1 (for disturbance 1) 64 R/W 0.0 11 EDS value 1 (for disturbance 2) 64 R/W 0.0 12 EDS value 2 (for disturbance 1) 64 R/W 0.0 13 EDS value 2 (for disturbance 2) 64 R/W 14 EDS transfer time
(for disturbance 1)
15 EDS transfer time
(for disturbance 2)
16 EDS action time
(for disturbance 1)
17 EDS action time
(for disturbance 2)
of data
items
bute
b0 to b3: Event 1 state to Event 4 state b4: Heater break alarm state b5: Temperature rise completion b6: Burnout b7 to b15: Unused Data 0: OFF 1: ON [Decimal number: 0 to 127]
b0 to b7: Logic output 1 to 8 b8 to b15: Unused Data 0: OFF 1: ON [Decimal number: 0 to 255]
Data range
1: Distribution output
64 R/W 0 to 1000 ms 0
1: Event 1 4: Event 4 2: Event 2 0: No function 1: EDS function mode 2: Learning mode 3: Tuning mode
EDS function: External disturbance suppression function
100.0 to +100.0 %
64 R/W 0
0 to 3600 seconds or 0.0 to 1999.9 seconds
64 R/W
64 R/W 600
1 to 3600 seconds
64 R/W
Factory
set value
ID Name
18 EDS action wait time
(for disturbance 1)
19 EDS action wait time
(for disturbance 2)
20 EDS value learning times 64 R/W 0 to 10 times (0: No learning mode) 1
21 EDS start signal 64 R/W 0: EDS start signal OFF
22 Operation mode 64 R/W 0: Unused
23 Communication switch for
0
0
1
logic
24
Engineering setting data
For the data, see COM-JH [For SRZ] Instruction Manual (IMR01Y36-E).
42 43
Unused
255
Z-DIO Module Object (0x66: 66Hex)
0
ID Name
1 Digital input (DI) state 16 RO Bit data
2 Digital output (DO) state 16 RO Bit data
1
3 Error code 16 RO 2: Data back-up error 4 Inte grated operating time
monitor
5 Backup memory state
monitor
0
6 RUN/STOP transfer 16 R/W 0: STOP (Control stop)
7 DO manual output 16 R/W Bit data
8 DO output distribution
selection
9 DO output distribution bias 128 R/W −100.0 to +100.0 % 0.0 10 DO output distribution ratio 128 R/W 9.999 to +9.999 1.000 11 DO proportional cycle time 128 R/W 0.1 to 100.0 seconds Depends on
12 DO minimum ON/OFF time
of proportional cycle
13
Engineering setting data
For the data, see COM-JH [For SRZ] Instruction Manual (IMR01Y36-E).
26 27
Unused
255
3. DEVICE PROFILES
A device profile is the specification that defined each necessary parameter with DeviceNet.
3.1 Basic Data
0
General Device Data
Conforms to DeviceNet specification Volume I - Release 2.0, Volume II - Release 2.0 Vendor name RKC INSTRUMENT INC. (Vendor ID = 394) Device profile name Generic Device
Product catalog number
0
Product revision 2.1
Physical Conformance Data
0
Network power consumption 2 mA @ 11 V DC, 4 mA @ 24 V DC Connector type Open-style connector or Micro-style connector Insulated physical layer Provided LEDs supported Module, Network MAC ID setting Rotary switch (Node address setting)
0.0
600
Default MAC ID 63 Communication speed setting Rotary switch (DeviceNet communication sp eed setting) Communication speed supported 125 kbps, 250 k bps, 500 kbps
0
Communication Data
Predefined master/slave connection set Dynamic connection supported (UCMM)
Fragmented Explicit Messaging None
Number
Attri-
of data
bute
items
64 R/W 0.0
0.0 to 600.0 seconds
Data range
64 R/W
1: EDS start signal ON (for disturbance 1) 2: EDS start signal ON (for disturbance 2)
1: Monitor 2: Monitor + Event function
16 R/W Bit data
Number
of data
items
3: Control
b0 to b3: Communication switch 1 to 4 b4 to b15: Unused Data 0: OFF 1: ON [Decimal number: 0 to 15]
Attri­bute
b0 to b7: DI1 to DI8 b8 to b15: Unused Data 0: Contact open 1: Contact closed [Decimal number: 0 to 255]
b0 to b7: DO1 to DO8 b8 to b15: Unused Data 0: OFF 1: ON [Decimal number: 0 to 255]
Data range
Factory
set value
0.0
Factory
set value
16 RO 0 to 19999 hours
16 RO 0: The content of the backup memory
does not coincide with that of the RAM. 1: The content of the backup memory coincides with that of the RAM.
1: RUN (Control start)
b0 to b7: DO1 manual output to DO8 manual output b8 to b15: Unused Data 0: OFF 1: ON
128 R/W 0: DO output
128 R/W 0 to 1000 ms 0
Instruction manual number: Japanese: IMR01Y24-J, IMR01Y28-J, IMR01Y32-J, IMR01Y36-J English: IMR01Y24-E, IMR01Y28-E, IMR01Y32-E, IMR01Y36-E
Group 2 Only server
Not supported
[Decimal number: 0 to 255]
1: Distribution output
specifications
3.2 Object Mounting
Identity Object (0x01: 01Hex)
Object class
Attributes Not supported Services Not supported
Object instance 1
0
ID Description Get Set Type Value Attributes 1 Vendor Yes No UINT 39 4 2 Product type Yes No UINT 0
3
3 Product code Yes No UI NT 5 4 Revision
0
5 Status (bits supported) Yes No WORD Note 6 Serial number Yes No UDINT 7 Product name
DeviceNet service Parameter option Services 0x05 Reset 0 0x0E Get_Attribute_Single None
Note bit 0: Owned
bit 7:
Set to 1 when a self-diagnostic error occurs. Self-diagnostic error: When attribute ID: 238 (COM-JH error code) of the controller object (0x64)
is set to 1, a self-diagnostic error occurs. bit 1 to 6 and bit 8 to 15: Unused
Message Router Object (0x02: 02Hex)
Object class
Attributes Not supported Services Not supported
Object instance
Attributes Not supported Services Not supported
DeviceNet Object (0x03: 03Hex)
Object class
ID Description Get Set Type Value Attributes 1 Revision Yes No UINT 2 DeviceNet service Parameter option Services 0x0E Get_Attribute_Single None
Object instance 1
ID Description Get Set Type Value Attributes 1 MAC ID Yes No UINT 0 to 63 2 Baud rate Yes No UINT 0 to 2 3 BOI Yes No BOOL 0 4 Bus-off counter Yes Yes USINT 5 Allocation information
0
6 MAC ID switch changed Yes No BOOL 0, 1 7 Baud rate switch changed Yes No BOOL 0, 1
0
8 MAC ID switch value Yes No USINT 0 to 63 9 Baud rate switch value Yes No USI NT 0 to 2 DeviceNet service Parameter option Services 0x0E Get_Attribute_Single None 0x10 Set _Attribute_Single None 0x4B Allocate_Master/Slave_
0
0x4C Release_Group_2_Identifire_Set None
Assembly Object (0x04: 04Hex)
Object class
ID Description Get Set Type Value Attributes 1 Revision Yes No UINT 2 DeviceNet service Parameter option Services 0x0E Get_Attribute_Single None
Object instance 100
ID Description Get Set Type Value Attributes 3 Data Yes No INT CH1: Measured value (PV) DeviceNet service Parameter option Services 0x0E Get_Attribute_Single None
Object instance 101
ID Description Get Set Type Value Attributes 3 Data Yes Yes INT C H1: Set value (SV) DeviceNet service Parameter option Services 0x0E Get_Attribute_Single None 0x10 Set _Attribute_Single None
Connection Object (0x05: 05Hex)
Object class
Attributes Not supported Services Not supported Number of maximum possible active connection 1
Object instance 1
Section Information Instance type Explicit Message 1 Production trigger Cyclic Transport type Server Transport class 3 ID Description Get Set Type Value Attributes 1 State Yes No USINT 2 Instance type Yes No U SINT 0x00 3 Transport class trigger Y es No BYTE 0x83 4 Produced connection ID Yes No UINT 5 Consumed connection ID Yes No UINT 6 Initial comm. Characteristics Yes No BYTE 0x21 7 Produced connection size Yes No UINT 7 8 Consumed connection size Yes No UINT 7 9 Expected packet rate Yes Yes UINT Def ault: 2500 12 Watchdog time-out act ion Yes Yes USINT 1, 3 13 Produced connection pat h length Yes No UINT 0 14 Produced connection pat h Yes No (null) 15 Consumed connection path length Yes No UINT 0 16 Consumed connection pat h Yes No (null) DeviceNet service Parameter option Services 0x05 Reset None 0x0E Get_Attribute_Single None 0x10 Set _Attribute_Single None
Major revision Minor revision
Length Name
Allocation choice byte Master’s MAC ID
Connection_Set
Yes No
Yes No
Yes No
None
UINT
2
UINT
1
UINT
5
STRING
COM01
BYTE USINT
Number of maximum instance
Object instance 2
Instance type Polled I/O 1 Production trigger Cyclic Transport type Server Transport class 3 ID Description G et Set Type Value Attributes 1 State Yes No U SINT 2 Instance type Yes No U SINT 0x01 3 Transport class trigger Yes N o BYTE 0x82 4 Produced connection ID Yes No UINT 5 Consumed connection ID Yes No UINT 6 Initial comm. Characteristics Yes No BYT E 0x01 7 Produced connection size Yes No UI NT Note 8 Consumed connection size Yes No UINT Note 9 Expected packet rate Yes Yes UINT Default: 0 12 Watchdog t ime-out action Yes No USINT 0 13 Produced co nnection path length Yes No UINT 6 14 Produced co nnection path
15 Consumed connect ion path length Yes N o UINT 6 16 Consumed connect ion path
DeviceNet service Parameter option Services 0x05 Reset None 0x0E Get_Attribute_Single None 0x10 Set _Attribute_Single None
Note: Make the setting by any of the f ollowing methods. (The value is validated with the power turned on)
Section Information
Logic Segment, Class Class Number Logic Segment, Instance Instance Number Logic Segment, Attributes Attributes Number
Logic Segment, Class Class Number Logic Segment, Instance Instance Number Logic Segment, Attributes Attributes Number
Select with the DIP s witch [14 (7 words), 50 (25 words), 90 (45 words), 200 (100 words)]
Set with number setting ( attribute ID: 240 and 241) of communication data of controller object (0x64).
Yes No
Yes No
USINT USINT USINT USINT USINT USINT
USINT USINT USINT USINT USINT USINT
Number of maximum instance
0x20 0x04 0x24 0x64 0x30 0x03
0x20 0x04 0x24 0x65 0x30 0x03
Controller Object (0x64: 64Hex, 0x65: 65Hex, 0x66: 66Hex)
Object class
Attributes Not supported Services Not supported
Object instance  (: 1 to 64): Z-TIO module object
Object instance  (: 1 to 64): Z-TIO module extended object
Object instance  (: 1 to 128): Z-DIO module object
For details of object instance, see 2. CONTROLLER OBJECT DATA ITEMS.
Controller Communication Item Setting Object (0xC7: C7Hex)
Measured data item (IN) and setting data item (OUT) communicating via polling I/O communication are set by the attribute ID in “Controller object (0x64 to 0x66).”
0x64: 64Hex: Attributes ID 0x65: 65Hex: Attributes ID + 1000 0x66: 66Hex: Attributes ID + 2000
When setting the communication items of a object (0x65
or (0x66), set the attribute ID number with the appropriat
offset value (1000 or 2000) added.
Object class
Attributes Not supported Services Not supported
Object instance 1
ID Description Get Set Type Value * Attributes 1 Measured data item (IN) 1 Yes Yes UINT 1: Measured value (PV) 2 Measured data item (IN) 2 Yes Yes UINT 0
32 Measure d data item (IN) 32 Yes Yes UINT 0 33 Sett ing data item (OUT) 1 Yes Yes UINT 45: Set value (SV) 34 Sett ing data item (OUT) 2 Yes Yes UINT 0
64 Sett ing data item (OUT) 32 Yes Yes UINT 0 DeviceNet service Parameter option Services 0x0E Get_Attribute_Single None 0x10 Set _Attribute_Single None
* Attribute ID 2 to 32 and Attribute I D 34 to 64: 0 (factory set value)
DeviceNet is a registered trademark of Open DeviceNet Vendor Association, Inc. Modbus is a registered trademark of Schneider Electric. Company names and product names used in this manual are the trademarks or registered trademarks of the respective companies. This product has been self-tested by RKC at DeviceNet Protocol Conformance Test Software Version
-17.
RKC INSTRUMENT INC.
®
HEADQUARTERS: 16-6, KUGAHARA 5-CHOME, OHTA-KU TOKYO 146-85 15 JAPAN
PHONE: 03-3751-9799 (+81 3 3751 9799) E-mail: info@rkcinst.co.jp FAX: 03-3751-8585 (+81 3 3751 8585) JUN. 2007
The first edition: JUN. 2007 [IMQ00]