Rittal SK 3302.100 operation manual

4.3 (6)

Enclosure cooling unit

3302.xxx

3328.xxx

3302.3xx

3329.xxx

3303.xxx

3332.xxx

3304.xxx

3361.xxx

3305.xxx

3366.xxx

Assembly and operating instructions

Contents

Contents

 

EN

 

 

1

Notes on documentation ..................

3

1.1

CE labelling ..................................................

3

1.2

Storing the documents.................................

3

1.3Symbols used in these operating instructions 3

1.4

Other applicable documents ........................

3

2

Safety notes .....................................

3

3

Device description ............................

4

3.1TÜV-tested output measurement to

 

 

DIN EN 14511 ..............................................

4

3.2

 

Functional description ..................................

4

3.2.1

How it works .........................................................

4

3.2.2

Control ..................................................................

5

3.2.3 Bus mode (e-Comfort controller only) ....................

5

3.2.4

Safety devices .......................................................

5

3.2.5

Condensation .......................................................

5

3.2.6

Filter mats .............................................................

5

3.2.7

Door limit switch ...................................................

5

3.2.8

Additional interface X3 ..........................................

6

3.3

Proper use, foreseeable misuse ...................

6

3.4

 

Scope of supply...........................................

6

4

 

Assembly and connection ................

6

4.1

Choosing the installation site........................

6

4.2

 

Notes on assembly ......................................

6

4.2.1

General .................................................................

6

4.2.2 Layout of the electronic components in the

 

 

 

enclosure ..............................................................

7

4.3

Fitting the cooling unit ..................................

7

4.3.1

Making the cut-outs ..............................................

8

4.3.2 External mounting of the cooling unit .....................

8

4.3.3 Partial internal mounting of the cooling unit ...........

8

4.3.4 Full internal mounting of the cooling unit ................

9

4.4

Connecting the condensate discharge .......

10

4.5

Notes on electrical installation ....................

11

4.5.1

Connection data .................................................

11

4.5.2 Overvoltage protection and supply line load ........

11

4.5.3

Three-phase devices ...........................................

11

4.5.4

Door limit switch .................................................

11

4.5.5 Notes on the flicker standard ..............................

11

4.5.6

Potential equalisation ..........................................

12

4.6

Making the electrical connection ................

12

4.6.1 Bus connection (only when interconnecting several

 

units with a Comfort controller) ............................

12

4.6.2 Connection X3 for serial interface ........................

12

4.6.3

Mounting external transformer .............................

12

4.6.4 Installing the power supply ..................................

13

4.7

Finalising assembly ....................................

15

4.7.1

Installing the filter media ......................................

15

4.7.2 Fitting the cooling unit .........................................

15

4.7.3

Setting the filter mat monitor (only with e-Comfort

 

 

controller) ............................................................

16

6

Operation .......................................

16

6.1 Control using the Basic controller...............

16

6.1.1

Properties ...........................................................

16

6.1.2

Operating and error display .................................

17

6.1.3

Test mode with the Basic controller ....................

18

6.1.4

Setting the temperature ......................................

18

6.1.5

Resetting the Basic controller ..............................

18

6.2 Control using the e-Comfort controller........

18

6.2.1

Properties ...........................................................

19

6.2.2

Eco mode ...........................................................

19

6.2.3

Launching test mode ..........................................

19

6.2.4

General information about programming .............

20

6.2.5

Editable parameters ............................................

21

6.2.6

Programming overview .......................................

22

6.2.7

Defining system messages for evaluation ............

23

6.2.8

Setting the master/slave identifier ........................

24

6.2.9

Evaluating system messages ..............................

24

6.2.10

Reset the e-Comfort controller ............................

26

7

Inspection and maintenance ..........

26

7.1Compressed air cleaning 3304.xxx,

3305.xxx ....................................................

26

7.2Compressed air cleaning 3328.xxx,

3329.xxx, 3332.xxx ....................................

30

7.3Installation instructions for NEMA 4X

 

devices ......................................................

35

8

Storage and disposal .....................

36

9

Technical details ............................

36

9.1

Technical specifications..............................

36

9.2

Performance diagrams ...............................

43

10

List of spare parts ..........................

44

11

Appendix .......................................

47

11.1

Cut-out and hole sizes ...............................

47

11.1.1 Dimensions for external mounting .......................

47

11.1.2 Dimensions for partial internal mounting ..............

50

11.1.3 Dimensions for full internal mounting ...................

51

11.2

Electrical wiring plan...................................

52

5

Start-up ..........................................

16

2

Rittal enclosure cooling unit

1 Notes on documentation

1Notes on documentation

1.1CE labelling

Rittal GmbH & Co. KG confirms the conformity of the cooling unit with the European Union's Machinery Directive 2006/42/EC and EMC Directive 2014/30/EC. A corresponding declaration of conformity has been issued. This can be found at the end of this document, or on the Rittal homepage.

1.2Storing the documents

The assembly and operating instructions as well as all other applicable documents are an integral part of the product. They must be issued to everyone who works with the unit and must always be available and on hand for operating and maintenance personnel.

1.3Symbols used in these operating instructions

The following symbols are used in this documentation:

Danger!

A dangerous situation in which failure to comply with the instructions will result in death or severe injury.

Warning!

A dangerous situation which may cause death or serious injury if the instructions are not followed.

Caution!

A dangerous situation which may lead to (minor) injuries if the instructions are not followed.

Note:

Important notices and indication of situations which may result in material damage.

This symbol indicates an "action point" and shows that you should perform an operation or procedure.

1.4Other applicable documents

Assembly and operating instructions in paper and digital format are available for the unit types described here. We cannot accept any liability for damage associated with failure to observe these instructions. Where applicable, the instructions for any accessories used also apply.

2 Safety notes

Please observe the following general safety notes when

EN

 

assembling and operating the unit:

 

Assembly, installation and servicing may only be performed by properly trained specialists.

Screw the enclosure to the floor to prevent it from tipping over when the cooling unit is installed.

Do not obstruct the air inlet and air outlet of the cooling unit inside and outside the enclosure (see sec-

tion 4.2.2 "Layout of the electronic components in the enclosure").

To ensure problem-free opening and closing of the enclosure door, use a ride-up door roller (refer to the accessories in the Rittal Catalogue). This raises the door slightly and balances out the weight of the cooling unit, to prevent buckling of the door and associated seal problems.

The heat loss of the components installed in the enclosure must not exceed the useful cooling power of the cooling unit.

Cooling units with item numbers: 3303.xxx, 3361.xxx, 3304.xxx, 3305.xxx, 3328.xxx, 3329.xxx and 3332.xxx must be transported in an upright position and protected from tipping over.

Units with item numbers 3302.xxx and 3366.xxx must be transported lying flat.

Shipping braces must be used when transporting a unit that has already been mounted (on the enclosure). A wooden structure made from square timbers or boards to support the cooling unit at the bottom (see fig. 1) is suitable for this purpose. The pallet should be big enough to prevent the enclosure and cooling unit overturning. If the cooling unit is mounted on a door, ensure the door is kept closed during transport.

Use only original spare parts and accessories

Do not make any changes to the cooling unit other than those described in these instructions or associated instructions.

Risk of burns! On cooling units with automatic condensate evaporation, the surface of the thermal element will get very hot during operation, and will remain so for some time afterwards.

The mains connector of the cooling unit must only be connected and disconnected with the system de-en- ergised. Connect the protective device specified on the rating plate.

Rittal enclosure cooling unit

3

3 Device description

EN

Enclosure

Cooling unit

 

Support

Fig. 1: Transporting an enclosure/cooling unit combination

3Device description

Depending on the model chosen, your cooling unit may vary in appearance from the illustrations contained in these instructions. However, the functions are identical in principle.

 

8

1

9

 

2

14

10

3

 

4

11

5

 

6

12

 

13

7

 

 

15

 

16

Fig. 2: Device description

Key

1 Blind rivet nut

2Evaporator fan

3Electrical wiring plan

4 X2 master-slave connection

5 X3 optional serial interface

6 X1 terminal strip

7Air outlet hole

8 Front half of the enclosure

9 Rear half of the enclosure

10Louvred grille for air outlet

11Display

12Infill panel

13Louvred grille for air inlet

14Rating plate

15Condensate discharge

16Dispatch bag

3.1TÜV-tested output measurement to DIN EN 14511

All TopTherm cooling units in the output range from 300 to 4000 W are tested to the latest EN 14511-1-4:2013- 12 standard by independent test institute TÜV Nord.

This means you have peace of mind about the design of the climate control solution and you can be sure you are getting the performance you are paying for.

3.2Functional description

3.2.1How it works

The cooling unit (compression refrigeration system) comprises four main components (see fig. 3): the evaporator (1), the refrigerant compressor (2), the condenser (3), and the control or expansion valve (4), which are connected by suitable pipework. This circuit is filled with a readily boiling substance, the refrigerant. The refrigerant R134a (CH2FCF3) is chlorine-free. Its Ozone Depletion Potential (ODP) is 0, making it very eco-friendly. A filter dryer (5) which is integrated into the hermetically sealed cooling circuit provides effective protection against moisture, acid, dirt particles, and foreign bodies within the cooling circuit.

PSAH-

Condenser (3)

 

Pressure

 

switch

 

Compressor (2)

Condenser fan

 

Filter dryer (5)

External circuit

 

Internal circuit

Temperature

 

 

control

 

 

 

 

 

 

 

 

 

 

 

 

Evaporator coil (1)

 

 

Expansion valve (4)

 

 

 

 

 

 

 

 

Evaporator fan

Fig. 3: Cooling circuit

In the evaporator coil (1), the liquid refrigerant is converted to a gaseous state. The energy needed for this purpose is taken from the enclosure air in the form of heat, which has the effect of cooling the enclosure air. In the compressor (2), the refrigerant is heavily compressed, so that it achieves a higher temperature inside the condenser (3) than the ambient air. This means that excess heat may be emitted to the ambient air via the surface of the condenser, as a result of which the temperature of the refrigerant drops and it is converted back into liquid. It is re-injected into the evaporator coil via a thermostatic expansion valve (4), which causes it to cool down further, and is then once again able to absorb the energy from the enclosure air in the evaporator coil. The whole cycle begins again.

4

Rittal enclosure cooling unit

3 Device description

3.2.2Control

Rittal enclosure cooling units are fitted with a controller for setting the functions of the cooling unit.

Depending on the design, this is either a Basic controller (operating status display via LED) or an e-Comfort controller (display plus extended functions, see section 6 "Operation").

3.2.3 Bus mode (e-Comfort controller only)

The serial unit interface X2 allows you to create a bus connection with up to ten cooling units using the masterslave cable (shielded, four-wire cable, Model No. 3124.100). This allows you to implement the following functions:

Parallel unit control (the cooling units in the network can be switched on and off simultaneously)

Parallel door status message ("door open")

Parallel collective fault message

Data is exchanged via the master-slave connection. During commissioning, assign an address to each unit that also includes the identifier "master" or "slave".

3.2.4Safety devices

In the cooling cycle, the cooling units (with the exception of type 3302.xxx) have a tested pressure switch to EN 12 263 which is set to maximum PS (permissible pressure); this operates via an automatic reset device whenever the pressure drops again

Temperature monitoring prevents the evaporator coil from icing over. If there is a risk of icing, the compressor switches itself off and automatically switches itself back on again at higher temperatures

The refrigerant compressor and the fans are equipped with thermal winding shields to protect against excess current and excess temperatures

In order to allow a reduction of pressure inside the compressor and hence a safe restart, once it has been switched off (e.g. upon reaching the set temperature via the door limit switch function or via de-energising), the device will switch back on with a delay of 180 seconds

The device has floating contacts on the connection pins (terminals 3 – 5), via which system messages from the device may be polled, e.g. using a PLC (1 x change-over contact Basic controller, 2 x normally open contacts e-Comfort controller)

3.2.5Condensation

At high levels of humidity and low temperatures inside the enclosure, condensation may form on the evaporator coil.

The cooling units (except 3302.xxx, 3303.xxx and 3361.xxx) have automatic, electric condensate evaporation. The thermal component used for this purpose is based on self-regulating PTC technology. Condensate arising on the evaporator coil is collected in a tank in the external circuit of the cooling unit, and partially evaporated via the airflow. When the water level rises, the water

enters the PTC thermal component and is evaporated (through-flow heater principle). The water vapour EN streams out of the cooling unit with the airflow from the external fan.

The PTC thermal component is permanently connected and has no switchpoint. It is protected against short-cir- cuits with miniature fuses (F1.1, F1.2). If the fuse has tripped, any condensation is drained off via the safety overflow.

For unit types 3302.xxx, 3303.xxx and 3361.xxx, the condensate is routed downwards out of the unit via a drain pipe on the evaporator coil divider panel. For this purpose, a hose must be connected to the condensate nozzle (see section 4.4 "Connecting the condensate discharge"). External condensate evaporators are available as accessories for these unit types (refer also to the accessories in the Rittal Catalogue).

3.2.6Filter mats

The entire cooling unit condenser is covered with a dirtrepelling, easy-to-clean RiNano coating. In many applications, therefore, the use of filter media is unnecessary, particularly with dry dusts.

For dry, coarse dust and lint in the ambient air, we recommend installing an additional PU foam filter mat (available as an accessory) in the cooling unit. Depending on the incidence of dust, you will need to replace the filter mat from time to time.

For air containing oil condensate, we recommend the use of metal filters (also available as an accessory). These may be cleaned with suitable detergents and reused.

Function of the filter mat monitor (with e-Comfort controller only):

Dirt on the filter mat is automatically determined by measuring the temperature difference in the external circuit of the cooling unit. As the level of filter mat soiling increases, the temperature difference will increase. The setpoint value of the temperature difference in the external circuit adapts automatically to the relevant operating points in the performance diagrams. Hence there is no need to readjust the setpoint value for different unit operating points.

3.2.7Door limit switch

The cooling unit may be operated with a floating door limit switch connected. The door limit switch is not included with the supply (available as an accessory, Model No. 4127.010).

The door limit switch function causes the fans and the compressor in the cooling unit to be switched off after approximately 15 seconds when the enclosure door is opened (contacts 1 and 2 closed). This prevents the formation of condensation inside the enclosure while the enclosure door is open. In order to prevent damage to the unit, it is equipped with an ON delay: The evaporator fan cuts back in with a delay of approximately 15 seconds after the door has been closed, while the condens-

Rittal enclosure cooling unit

5

4 Assembly and connection

er fan and compressor switch on after approximately EN 3 minutes.

Note:

No external voltage may be applied to the door contacts (terminals 1 and 2).

For cooling units with basic control, the evaporator fan continues to run even when the door is open.

3.2.8Additional interface X3

Note:

The electrical signals at the interface are of an extra-low voltage (not extra-low safety voltages to EN 60 335).

An additional interface card may be connected to the 9- pole SUB-D connector X3 in order to incorporate the cooling unit into higher-level monitoring systems (available as an accessory, interface card Model No. 3124.200).

3.3Proper use, foreseeable misuse

The cooling unit is only intended for cooling connected enclosures. Any other use is not permitted.

The unit must not be installed and operated in locations which are accessible to the general public (see DIN EN 60335-2-40, paragraph 3.119).

The unit is designed solely for stationary use.

The cooling unit is state of the art and built according to recognised safety regulations. Nevertheless, improper use can pose a threat to the life and limb of the user or third parties, or result in possible damage to the system and other property.

Consequently, the cooling unit must only be used properly and in a technically sound condition! Any malfunctions which impair safety should be rectified immediately.

Proper use also includes the observance of the documentation provided, and compliance with the inspection and maintenance conditions.

Rittal GmbH & Co. KG is not liable for any damage which may result from failure to comply with the documentation provided. The same applies to failure to comply with the valid documentation for any accessories used.

Inappropriate use may be dangerous. Examples of inappropriate include:

Use of the cooling unit over long periods with the enclosure open.

Use of impermissible tools.

Improper operation.

Improper rectification of malfunctions.

Use of accessories not approved by Rittal GmbH & Co. KG.

3.4Scope of supply

The unit is supplied in a packaging unit in a fully assembled state.

Please check the scope of supply for completeness.

Qty. Description

1Enclosure cooling unit

1Dispatch bag:

1– Assembly and operating instructions

1Self-adhesive tape

1– Connector X1

4 – 10

– Grub screws

 

– Nuts, washers

 

 

1

Drilling template

Tab. 1: Scope of supply

4Assembly and connection

4.1Choosing the installation site

When choosing the installation site for the enclosure, please observe the following:

The site for the enclosure, and hence the arrangement of the cooling unit, must be carefully selected so as to ensure good ventilation (clearance between units and clearance between the unit and the wall must be at least 200 mm in each case).

The cooling unit must be installed and operated in a vertical position (maximum deviation: 2°).

The installation site must be free from excessive dirt, aggressive ambient conditions and moisture.

The ambient temperature must be within the limits specified on the rating plate.

It must be possible to fit a condensate discharge (see section 4.4 "Connecting the condensate discharge").

The mains connection data as stated on the rating plate of the unit must be guaranteed.

4.2Notes on assembly

4.2.1General

Check the packaging carefully for signs of damage. Traces of oil on damaged packaging are an indication of refrigerant loss and leakages. Any packaging damage may be the cause of a subsequent functional failure.

The enclosure must be sealed on all sides (IP 54). Increased condensation will occur if the enclosure is not airtight.

In order to avoid excessive condensation inside the enclosure, we recommend installing a door limit switch (e.g. 4127.010) which deactivates the cooling unit when the enclosure door is opened (see section 3.2.7 "Door limit switch").

6

Rittal enclosure cooling unit

4 Assembly and connection

4.2.2Layout of the electronic components in the enclosure

Note:

Risk of condensation!

When arranging the electronic components inside the enclosure, please ensure that the cold airflow from the cooling unit is not directed at active components. Please also ensure that the cold airflow is not directed at the warm exhaust airflow from active components such as converters. This may lead to an air short-circuit and therefore prevent adequate climate control, or may even cause the cooling unit’s internal safety devices to cease cooling operation.

Fig. 4: Never direct the cold airflow at active components

Air diversion components are available as accessories – please refer to the Rittal Catalogue.

It is important to ensure even air circulation inside the enclosure. Under no circumstances should air inlet and outlet openings be obstructed, otherwise the cooling performance of the unit will be reduced. Ensure the distance "x" (see fig. 5) from components and other installed enclosures so that the required air circulation is not obstructed and prevented.

x

EN

 

Fig. 5: Air circulation inside the enclosure

4.3Fitting the cooling unit

The enclosure cooling unit may optionally be externally mounted on the enclosure (1), partially internally mounted (2) or fully internally mounted (3):

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

2

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 6: Installation method

To this end, cut the side panel or door of the enclosure as per the drilling template included with the supply, and drill the relevant holes.

Note:

Units of type 3302.xxx and 3366.xxx can only be either externally mounted or fully internally mounted.

Units of type 3332.xxx can only be either externally mounted or partially internally mounted; they cannot be mounted in lockable doors on 600/1200 wide TS enclosures. To mount units 3328.xxx, 3329.xxx and 3332.xxx in the TS side or rear panel, we recommend using enclosure panel fasteners 8800.071 (see Rittal Catalogue). For high dynamic loads and mounting on the enclosure door, we recommend using reinforced door hinges 8800.710 (see Rittal Catalogue). Units with protection category NEMA 4X are only suitable for external mounting.

Rittal enclosure cooling unit

7

4 Assembly and connection

4.3.1Making the cut-outs

EN Affix the supplied drilling template to the side panel or door of the enclosure using adhesive tape.

There are dimensioning lines on the drilling template to suit the various installation options for your cooling unit.

Using the dimension drawings (see Appendix), identify the valid lines and dimensions for your installation type on the drilling template.

Caution!

Carefully deburr all drilled holes and cut-outs to prevent injuries caused by sharp edges.

Mark, drill and deburr the holes.

Make the cut-outs including the line width as per the drilling template.

Deburr the cut-outs.

4.3.2External mounting of the cooling unit

Cut the supplied sealing tape to the correct length and stick it carefully along the back of the unit so that no gaps are left at the joints.

Fig. 9: Securing the cooling unit (3302.1xx only "external mounting")

4.3.3 Partial internal mounting of the cooling unit

Carefully remove the louvred grille and, where applicable, the infill panel, from the enclosure by pulling forwards.

Carefully disconnect the connector from the rear of the display and gently push it inwards through the cable gland.

Fig. 7: Applying the self-adhesive tape

Screw the supplied grub screws into the blind nuts on the rear of the unit.

Secure the unit using the supplied washers and nuts.

Fig. 8: Securing the cooling unit (all models except 3302.1xx)

Fig. 10: Removing the louvred grille & disconnecting the display

Caution!

Stability of the cooling unit is only guaranteed in its assembled state. Brace the rear half of the enclosure to prevent it from falling over before removing the front half.

Loosen the four nuts on the front half of the enclosure and pull the enclosure forwards by approx. 5 cm.

Loosen the flat-pin connectors of the PE conductor between the two enclosure halves.

Disconnect the fan connection.

Remove the front enclosure tray completely.

8

Rittal enclosure cooling unit

4 Assembly and connection

Fig. 11: Removing the cover

Remove the four spacer bolts.

Cut the supplied sealing tape to the correct length and stick it carefully along the inside of the rear enclosure half so that no gaps are left at the connection points.

EN

Fig. 13: Securing the cooling unit

Connect the fan connector and PE conductor.

Mount the front enclosure tray using the washers and nuts.

Fig. 12: Applying the self-adhesive tape

Push the rear enclosure half into the mounting cut-out and secure it with the four spacer bolts.

Push the display cable through the cable gland of the front enclosure half.

Fig. 14: Connecting the display connector

Carefully connect the display connector.

Push the louvred grille and, where applicable, the infill panel, onto the enclosure.

4.3.4 Full internal mounting of the cooling unit

Carefully remove the louvred grille and the infill panel from the enclosure by pulling forwards.

Carefully disconnect the connector from the rear of the display.

Rittal enclosure cooling unit

9

Rittal SK 3302.100 operation manual

4 Assembly and connection

EN

Fig. 15: Removing the louvred grille & disconnecting the display

Cut the supplied sealing tape to the correct length and stick it carefully along the front enclosure half so that no gaps are left at the connection points.

4x

Fig. 17: 3302.xxx only: removing the four screws

Fig. 16: Applying the self-adhesive tape

Loosen the four nuts and washers from the front enclosure half.

Push the unit into the mounting cut-out from the inside of the enclosure, and secure it to the enclosure from the outside using the washers and nuts.

Only for 3302.xxx:

Note:

The tightening torque for the nuts is 6 Nm.

Before installing, remove the four screws as shown.

Fig. 18: Securing the cooling unit

Where necessary, additionally secure the unit using the supplied mounting plates as shown in fig. 18.

Carefully connect the display connector.

Push the louvred grille and, where applicable, the infill panel, onto the enclosure.

4.4 Connecting the condensate discharge

A condensate discharge hose can be fitted to all types of cooling unit (except NEMA 4X devices).

The condensate discharge

must be laid with a suitable and constant gradient (no siphoning)

must be laid without kinks

must not have a reduced cross-section if extended The condensate hose is available as an accessory (refer also to Accessories in the Rittal Catalogue).

10

Rittal enclosure cooling unit

4 Assembly and connection

Fig. 19: Connecting the condensate discharge

Connect a suitable hose to the condensate nozzle and secure using a hose clip.

Route the condensate hose to a drain or into the external condensate evaporator (refer to Accessories in the Rittal Catalogue).

4.5Notes on electrical installation

When performing the electrical installation, it is important to observe all valid national and regional regulations as well as the provisions of the responsible power supply company. The electrical installation may only be carried out by a qualified electrician who is responsible for compliance with the applicable standards and regulations.

4.5.1Connection data

The connected voltage and frequency must correspond to the values stated on the rating plate

The cooling unit must be connected to the mains via an all-pin isolating device, which ensures at least

3 mm contact opening when switched off

No additional temperature control may be connected upstream of the unit at the supply end

Install the protective device specified on the rating plate to protect the line and equipment from short-cir- cuits.

The mains connection must ensure low-noise potential equalisation

4.5.2 Overvoltage protection and supply line load

The unit does not have its own overvoltage protection. Measures must be taken by the operator at the supply end to ensure effective lightning and overvoltage protection. The mains voltage must not exceed a tolerance of ±10%.

In accordance with IEC 61 000-3-11, the unit is intended solely for use at sites with a continuous cur- rent-carrying capacity (incoming mains power supply) of more than 100 A per phase and with a supply voltage of 400/230 V. If necessary, the electricity supply company must be consulted to ensure that the continuous current-carrying capacity at the point of connection to the public grid is sufficient for connection of such a unit.

The fans and compressors in singleand three-phase units are intrinsically safe (thermal winding protection). This also applies to transformer versions, types

3304.510, 3305.510, 3328.510 and 3329.510, and to

EN

special-voltage units which are likewise equipped with

a transformer.

Install the protective device specified on the rating plate to protect the line and equipment from short-cir- cuits (miniature circuit-breaker with appropriate characteristic – e.g. "K" characteristic – or gG standard type slow fuse, circuit-breaker for plant or transformer protection). Select a suitable circuit-breaker in accordance with the information specified on the rating plate: Set it to the minimum specified value. This will achieve the best short-circuit protection for cables and equipment. Example: Specified setting range 6.3 – 10 A; set to 6.3 A.

4.5.3Three-phase devices

The electrical connection for devices in the threephase version MUST be made with a clockwise rotating field

The three-phase version of models 3304.xxx, 3305.xxx, 3328.xxx, 3329.xxx and 3332.xxx must be connected to a TN network with star earthing via a cir- cuit-breaker for plant protection (current setting as per the rating plate). Three-phase units with special voltages must be protected with a circuit-breaker for transformer protection (category AC-3) as per the rating plate.

Units designed for three phase 400/460 V feature additional monitoring of the rotary field or the absence of a phase. If the rotary field is incorrect or a phase is absent, the unit will not run.

4.5.4Door limit switch

Each door limit switch must only be assigned to one cooling unit.

Several door limit switches may be connected in parallel to one cooling unit.

The minimum cross-section for the connection cable is 0.3 mm2 for a cable length of 2 m.

The line resistance to the door limit switch must not exceed a maximum of 50 Ω.

The door limit switch only supports a floating connection; no external voltages.

The contact of the door limit switch must be closed when the door is open.

The safety extra-low voltage for the door limit switch is provided by the internal power pack: Current approx. 30 mA DC.

Connect the door limit switch to terminals 1 and 2 of the connector.

4.5.5Notes on the flicker standard

The flicker limits specified in standard EN 61 000-3-3 or -3-11 are adhered to, provided the supply impedance is less than approx. 1.5 Ω.

Where necessary, the unit operator should measure the connected impedance or consult the responsible electricity supply company. If there is no way of influencing

Rittal enclosure cooling unit

11

4 Assembly and connection

the supply impedance and sensitive installed compo- EN nents (e.g. BUS) are subjected to interference, a line re-

actor or starting-current limiting device should be connected upstream of the cooling unit to restrict the startup current of the cooling unit.

4.5.6Potential equalisation

If, for EMC reasons, the unit is to be integrated into the customer’s existing potential equalisation system, a conductor with a larger nominal cross-section can be connected to the potential equalisation connection point (attachment points) on the wall-mounted cooling units. According to the standard, the PE conductor in the mains connection cable is not classified as an equipotential bonding conductor.

4.6Making the electrical connection

4.6.1Bus connection

(only when interconnecting several units with a Comfort controller)

When using several cooling units, the serial device interface X2 can be used to connect up to ten cooling units with the bus cable (Model No. 3124.100).

Note:

The electrical signals at the X2 interface are of an extra-low voltage (not extra-low safety voltages in accordance with EN 60 335-1).

When interconnecting, please note the following:

De-energise the cooling units to be connected

Ensure proper electrical insulation

Make sure the cables are not laid in parallel to power lines

Make sure that the lines are short

Note:

With the last slave unit in the group, do not, under any circumstances, connect the remaining socket of the Y cable 3124.100 into interface X3 of the cooling unit!

4.6.2Connection X3 for serial interface

The interface card (Model No. 3124.200) may be connected to X3. This is used to evaluate system messages in a PLC, for remotely setting parameters and monitoring, or for integration into the facility management system.

4.6.3 Mounting external transformer

Only for 3361.x40.

Mounting device

Fastening to 35 mm

rear panel

support rail

 

DIN EN 50 022

Mains connection for

230 V

Cooling unit

 

Customer-side connection

Fig. 20: Mounting external transformer (3361.x40 only)

12

Rittal enclosure cooling unit

4 Assembly and connection

 

 

 

 

CMC

 

 

 

 

 

 

 

 

 

EN

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

I/O unit

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RTT

 

 

Adr.: 09

RTT

 

Adr.: 11

RTT

 

Adr.: 12

RTT

 

Adr.: 19

Master

 

 

Slave

 

 

 

Slave

 

 

 

Slave

 

 

 

 

X1

 

 

 

X1

 

 

 

X1

 

 

 

X1

 

X2

X3

 

 

X2

X3

 

 

X2

X3

 

 

X2

X3

St.

X2

X3

Bu.

St.

X2

 

 

St.

X2

 

 

St.

X2

 

 

 

 

 

 

 

X2

X2

 

 

X2

X2

 

 

X2

 

 

 

 

 

 

Bu. St.

 

 

Bu. St.

 

 

Bu.

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 21: Connection example: Master-slave operation

Key

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X2 Master/slave connection Sub-D, 9-pole

 

1

 

Serial interface (Model No. 3124.200)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X3 Serial interface Sub-D, 9-pole

 

2

 

Serial interface cable

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

St.

 

Sub-D connector, 9-pole

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

Master-slave bus cable (Model No. 3124.100)

 

 

 

 

 

 

 

 

Bu.

 

Sub-D jack, 9-pole

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RTT

Rittal TopTherm cooling units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adr.

 

Address

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X1 Supply connection/door limit switch/alarms

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X2

 

 

 

 

 

 

 

 

 

X2

 

 

 

 

 

 

 

 

 

 

 

 

X2

 

 

 

 

 

 

 

 

 

 

 

 

X2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adr.: 06

 

 

 

 

 

 

 

 

 

Adr.: 11

 

 

 

Adr.: 12

 

 

 

 

 

 

 

Adr.: 13

 

 

 

Adr.: 14

 

 

 

 

 

 

 

 

Adr.: 15

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X10

L1

L2N

PE

1

2

3

4

5

 

X10

L1

L2

L3

PE

1

2

3

4

5

X10

L1

L2N

 

PE

1

2

3

4

5

X10

L1

L2

L3

PE

1

2

3

4

5

X10

L1

L2

L3

PE

1

2

3

4

5

X10

L1

L2

L3

PE

1

2

3

4

5

 

 

X2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

X10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L2N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Adr.: 16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 22:

 

Connection example: Door limit switch and master-slave operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Key

1 Master cooling unit

2Slave cooling units

3 2-door enclosure with two door limit switches

4Enclosure with door limit switch

4.6.4Installing the power supply

Complete the electrical installation by following the wiring plan on the rear of the cooling unit (see fig. 2, for key see page 15).

If you would like the system messages from the cooling unit to be evaluated via the system message relay, you should also connect a suitable low-voltage cable to terminals 3 – 5.

Rittal enclosure cooling unit

13

4 Assembly and connection

EN

3302.100/.110, 3302.300/.310

 

Fig. 23: Electrical wiring plan no. 1

3303.500/.510, 3303.600/.610, 3361.500/.510, 3361.600/.610, 3361.540/.640 3304.500/.510/.504/.514/.520/.600/.610 3305.500/.510/.504/.514/.520, 3328.500/.510/.504/.514/.520, 3329.500/.510/.504/.514/.520, 3305.600/.610, 3328.600/.610, 3329.600/.610, 3366.500/.510/.600/.610

Fig. 24: Electrical wiring plan no. 2

14

Rittal enclosure cooling unit

4 Assembly and connection

 

 

 

 

 

 

3304.540/.544, 3305.540/.544, 3328.504/.544, 3329.504/.544

 

 

EN

 

3304.640, 3305.640, 3328.640, 3329.640, 3366.540/.640, 3332.540/.640

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Fig. 25: Electrical wiring plan no. 3

Key

X1 Main terminal strip

X2 Master/slave connection

X3 Optional interface

K1 Relay collective fault 1

K2 Relay collective fault 2

Door Door limit switch (without door limit switch: terminal 1, 2 open)

Note:

For technical data, refer to the rating plate.

textile plants with heavy lint contamination, lint screens should be used (available as an optional extra).

Pull the louvred air inlet grille off the enclosure.

Insert the filter mat into the louvred grille as shown in fig. 26 and push it back onto the enclosure.

AC

DC

cos φ = 1

Res. Load

 

 

I max. = 2 A

I min. = 100 mA

U max. = 250 V

U max. = 30 V

 

I max. = 2 A

 

 

Tab. 2: Relay contact data

 

4.7Finalising assembly

4.7.1Installing the filter media

The entire cooling unit condenser is covered with a dirtrepelling, easy-to-clean RiNano coating. In many applications, therefore, the use of filter media is unnecessary, particularly with dry dusts.

For dry, coarse dust and lint in the ambient air, we recommend installing an additional PU foam filter mat (available as an accessory) in the cooling unit. For air containing oil condensate, we recommend the use of metal filters (also available as an accessory). When used in

Fig. 26: Installing the filter mat

4.7.2Fitting the cooling unit

For partial and full internal mounting only.

Connect the connector to the rear of the display.

Place the louvred grille onto the unit at the front, and press it down until you hear it snap into place.

Rittal enclosure cooling unit

15

5 Start-up

EN

Fig. 27: Connect the display and attach the louvred grille

4.7.3Setting the filter mat monitor (only with e-Comfort controller)

Function of the filter mat monitor:

Dirt on the filter mat is automatically detected by measuring the temperature difference in the external circuit of the cooling unit (see section 6.2.6 "Programming overview"). As the level of filter mat soiling increases, the temperature difference will increase. The setpoint value of the temperature difference in the external circuit adapts automatically to the relevant operating points in the performance diagrams. Hence there is no need to readjust the setpoint value for different unit operating points.

5Start-up

Note:

The oil must be collected in the compressor in order to ensure effective lubrication and cooling.

Do not operate the cooling unit for at least 30 minutes after assembling the equipment.

Once all the assembly and installation work is complete, switch on the power supply to the cooling unit.

The cooling unit starts running:

With Basic controller: The green operating LED ("line") is illuminated.

With e-Comfort controller: The software version of the controller first appears for approx. 2 seconds, then "ECO" to show Eco mode is enabled. The internal enclosure temperature will then appear in the 7-segment display

You can now make your individual settings on the unit, e.g. set the temperature or (with e-Comfort controller only) assign the network identifier, etc. (refer to section 6 "Operation").

6Operation

You can operate the cooling unit using the controller on the front of the device (fig. 2, item 11). Depending on the model, the unit is equipped with a Basic or e-Comfort controller.

6.1 Control using the Basic controller

For Model Nos. 3302.xxx.

 

1

3

4

 

2

 

5

Fig. 28: Basic controller

Key

1 Controller trim panel

2 Temperature setter

3 LED green ("line")

4 LED red ("alarm")

5Reset button

6.1.1Properties

Rated operating voltage: 115 V or 230 V

Integral start-up delay and door limit switch function

Protective function to prevent icing

Monitoring of all motors (compressor, condenser fan, evaporator fan)

Phase monitoring for three-phase units

Visualisation of the operating status via LED display:

Voltage on, unit operational

Door open (only if door limit switch installed)

Warning of overtemperature

High-pressure monitor has switched

Switching hysteresis: 5 K

If the cooling unit and compressor run times are too long < 1 minute, the switching hysteresis to protect the cooling unit is automatically increased.

Floating system message contact in case of overtemperature

16

Rittal enclosure cooling unit

6 Operation

Temperature setting

(setting range 30 – 55°C) via potentiometer

Test function

Flashing mode to indicate system messages. See section 6.1.2 "Operating and error display"

The cooling unit operates automatically, i.e. after switching on the power supply, the evaporator fan (see fig. 3) will run continuously and permanently circulate the inter-

nal enclosure air. The built-in Basic controller ensures automatic normal shut-down operation of the cooling EN unit by the value of the fixed preset switching difference

of 5 K.

6.1.2Operating and error display

The Basic controller monitors and controls the cooling unit. It indicates the operating and error status via the green and red LEDs (fig. 28, items 3 and 4):

LED

 

Status

Cause

 

 

Solution

 

 

 

 

 

 

 

Green

 

Illuminated

Power supply on,

 

 

(line)

 

 

unit operational

 

 

 

 

 

 

 

 

 

 

 

Flashing

Only with door limit switch installed:

 

In order to avoid condensation, close the enclo-

 

 

 

enclosure door open

 

 

sure door as quickly as possible.

 

 

 

 

 

 

 

 

 

Only with door limit switch installed:

 

Check the position of the door limit switch.

 

 

 

enclosure door closed

 

 

 

 

 

 

 

 

 

Red

 

Alarm/error/warning

Number of flash

Flash interval

(alarm)

 

 

intervals for the

 

 

 

 

 

red LED

 

 

 

 

 

 

 

 

 

 

Implement a

Device reset

(12)

 

|_|_|_|_|_|_|_|_|_|_|_|*****|_|_|_|_|_|_|_|_|_|_|_|

 

 

reset

 

 

 

 

 

 

High pressure alarm

(0)

 

|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|_|

 

 

 

 

 

 

 

 

 

 

 

 

 

Sensors

Potentiometer defective or

(3)

 

|_|_|*****|_|_|*****|_|_|*****|_|_|*****|_|_|*****

 

 

 

display error

 

 

 

 

 

 

 

 

 

 

 

 

 

Internal temperature

(4)

 

|_|_|_|*****|_|_|_|*****|_|_|_|*****|_|_|_|*****

 

 

 

sensor defective

 

 

 

 

 

 

 

 

 

 

 

 

 

Anti-icing sensor defective

(5)

 

|_|_|_|_|*****|_|_|_|_|*****|_|_|_|_|*****|_|_|_|_|

 

 

 

 

 

 

 

 

 

Overload

Compressor overloaded

(6)

 

|_|_|_|_|_|*****|_|_|_|_|_|*****|_|_|_|_|_|*****

 

 

 

 

 

 

 

 

 

 

Interior fan overloaded

(7)

 

|_|_|_|_|_|_|*****|_|_|_|_|_|_|*****|_|_|_|_|_|_|

 

 

 

 

 

 

 

 

 

 

Exterior fan overloaded

(8)

 

|_|_|_|_|_|_|_|*****|_|_|_|_|_|_|_|*****

 

 

 

 

 

 

 

 

 

Device sta-

Overload mode

(9)

 

|_|_|_|_|_|_|_|_|*****|_|_|_|_|_|_|_|_|*****

 

 

tus/state

(heat loss)

 

 

 

 

 

 

 

 

 

 

 

 

Warning

Anti-icing alarm

(2)

 

|_|*****|_|*****|_|*****|_|*****|_|*****|_|*****|_|

 

 

 

 

 

 

 

 

 

 

Overtemperature warning

(1)

 

|*****|*****|*****|*****|*****|*****|*****|*****|*****|

 

 

 

 

 

 

 

Off

 

No display

No power

 

Check power supply

 

 

 

 

 

 

 

 

 

 

Rotary current phase moni-

 

Swap phases

 

 

 

toring:

 

 

 

 

 

 

"LED off" = Incorrect

 

 

 

 

 

 

phase connection

 

 

 

 

 

 

 

 

 

Tab. 3: Operating and error display on the Basic controller

 

 

 

Key to flash intervals

 

 

nection diagrams under section 4.6.4 "Installing the

|

=

500 ms (red LED on)

 

power supply"):

_

=

500 ms (red LED off)

 

– Terminal 3: NC (normally closed)

*****

=

3 s pause (red LED off)

 

– Terminal 4: C (connection of the supply voltage to the

 

 

 

 

 

The overtemperature message may also be polled via an

fault signal relay)

– Terminal 5: NO (normally open)

integral floating contact on the cooling unit terminal (sys-

The NC and NO definitions refer to the de-energised

 

 

 

 

 

tem message relay with changeover contact, see con-

state. As soon as power is applied to the cooling unit,

 

Rittal enclosure cooling unit

17

6 Operation

the system message relay picks up, so that the relay EN contacts change status (contact 3 – 4 open; contact 4 –

5 closed).

This is the normal operating state of the cooling unit. As soon as an error message occurs or the power supply is interrupted, the relay drops out and contact 3 – 4 is closed.

6.1.3 Test mode with the Basic controller

The Basic controller is equipped with a test function whereby the cooling unit commences cooling operation independently of the set temperature or door limit switch function.

First you must remove the controller trim panel.

Switch off the mains voltage.

Remove the louvred grille or infill panel in which the controller is installed.

Release the display lock from behind and pull it forwards slightly.

Fig. 29: Releasing the Basic controller trim panel

Carefully lift the trim panel, e.g. using your thumb or a flat screwdriver, and remove it.

You can now start test mode.

Rotate the potentiometer to the left-hand stop, then hold the rubberised potentiometer display down while you re-connect the mains voltage.

The cooling unit will commence operation and the green LED will flash (I_II_I_II_ . . .). Test mode is completed after approximately 5 minutes. The unit switches off and changes to normal operation.

Key

I= LED 500 ms on

_= LED 500 ms off

In normal operation, the green LED is permanently illuminated.

Next, rotate the potentiometer back to the required setpoint.

6.1.4Setting the temperature

Note:

With the Basic controller, the temperature is preset at the factory to +35°C.

In order to save energy, do not set the temperature lower than that actually necessary.

To change the temperature setting:

Take the trim panel off the controller as described in section 6.1.3 "Test mode with the Basic controller".

Set the required temperature on the temperature setting device (fig. 28).

Carefully push the trim panel onto the display until you hear it snap into place.

Push the display back into the infill panel or louvred grille.

Re-attach the louvred grille or infill panel to the cooling unit.

6.1.5Resetting the Basic controller

Following a high-pressure alarm in the cooling cycle, and once the cause has been rectified, you will need to manually reset the Basic controller:

Take the trim panel off the Basic controller as described in section 6.1.3 "Test mode with the Basic controller".

Press the reset button (fig. 28, item 5) for at least 3 seconds.

The red LED is extinguished.

Re-install the Basic controller.

6.2 Control using the e-Comfort controller

For unit types 33xx.5xx and 33xx.6xx.

1

2

4

3

Fig. 30: e-Comfort controller

Key

1Programming button, also display of the set temperature unit (degrees Celsius)

2Set button

3Programming button, also display of the set temperature unit (degrees Fahrenheit)

47-segment display

18

Rittal enclosure cooling unit

Loading...
+ 40 hidden pages