Rinnai Water Heater Q205SP Specifications

Q205S Condensing Boiler
Standard Features
Factory Installed Boiler/System Modulating Pump Onboard Outdoor Reset Control System with Sensor Standard Priority Domestic Hot Water (DHW) Standard (with Optional 3-way
Valve, Not Included)
Modulating Ceramic Premix Burner 5.0:1 Turndown Ratio Spark Ignition Exceeds SCAQMD 1146.2 Low NO
Requirements
x
Stainless Steel Water Tube Condensing Heat Exchanger Direct Vent Sealed Combustion Concentric and Twin Pipe Venting Adapters Included Approved for Room and Closet Installations
SPECIFICATIONS
General Specifications
Water Content 1.8 Gal / 7.0 L
Max Supply Boiler Temperature
Max Operating Pressure 45 PSI / 310 kPa
Relief Valve Rating 375 MBH / 110 kWh
Relief Valve Pressure Rating 30 PSI / 207 kPa
Unit Weight 141 lbs / 64 kg
Min Inlet Gas Pressure NG 4.0" WC / 10.0 mbar
176 °F / 80 °C
Optional Accessories
3-way Valve DHW Kit RS100 Single Zone Controller Flue Gas Temperature Sensor Room Air Filter NG to LP Conversion Kit NG to LP Conversion Kit
Performance Specifications
Fuel Types NG and LP
Input (Heating) 205 MBH / 60.0 kWh
Heating Capacity 186 MBH / 54.5 kWh
Input (DHW) N/A
Minimum Input
Turndown Ratio 5.0:1 / 2.8:1 TDR
NG: 41 MBH / 12.0 kWh LP: 74 MBH / 21.7 kWh
Max Inlet Gas Pressure NG 10.5" WC / 26.2 mbar
Min Inlet Gas Pressure LP 8.0" WC / 19.9 mbar
Max Inlet Gas Pressure LP 13.5” WC / 33.6 mbar
Electrical Voltage Mains 120 V / 60 Hz
Electrical Voltage Controls 24 V
Power Consumption Max Load 234 W
Power Consumption Standby Load
Recommended Circuit Breaker Rating
Sound Level 57 dB
14 W
15 A
System Pump Model UPER 20-78
Max Head Pressure at Flow Rate
AFUE 95.0%
DHW Flow Rate 75°F ΔT N/A
DHW Minimum Activation N/A
Flow Restrictor Color N/A
Max Equivalent Exhaust Vent Length
Max Equivalent Combustion Air Vent Length
Approved Venting Materials
23.1 ft at 5.0 GPM
7.0 m at 18.9 LPM
40 ft / 12.2 m
40 ft / 12.2 m
Polypropylene, Stainless
Steel, PVC, CPVC
Rinnai is continually updating and improving products; therefore, specifications are subject to change without prior notice. Local, state, provincial and federal codes must be adhered to prior to installation.
© 2017 Rinnai Corporation
Q205S-SP-2 8/2017
Q205S Condensing Boiler
DIMENSIONS
A Height
B Width 26” / 660 mm
C Depth 15.2” / 385 mm
D Left Side / Vent 19.5” / 495 mm
Center to Center / Vent and Air
E
Supply
F Back / Vent 10.6” / 270 mm
G Left Side / Gas Pipe 2.6” / 65 mm
H Left Side / Supply Pipe 7.8” / 199 mm
J Left Side / Return Pipe 19.8” / 504 mm
K Left Side / Condensate Pipe 20.9” / 530 mm
P Pipe Length of G 0.7” / 18 mm
Q Pipe Length of C 2” / 50 mm
R Pipe Length of F and R 18.5” / 470 mm
T Back / Center of Pipe C 1” / 25 mm
U Back / Center of Pipe G 1.6” / 40 mm
V1 Back / Center of Pipes f1 and r1 2” / 50 mm
V2 Back/ Center of Pipes f2 and r2 2.1” / 54 mm
26.8” / 680 mm
4.7” / 121 mm
Pipe Length Vent Co-axial
W
Pipe Length Vent Parallel
Bottom Side Boiler to Center
X
Pressure Relief Valve
Bottom Side Boiler to Center
Y
Low Loss Header
Z Center to Center f2 to r2 9” / 229 mm
aa Depth of Low Loss Header 5.6” / 142 mm
2.6” / 65 mm
5.8” / 147 mm
7.7” / 195 mm
10.2” / 260 mm
Clearances
Minimum required
Top 2” / 50 mm 10” / 250 mm
Back 0 0
Front 6” / 150 mm 24” / 600 mm
Left Side 2” / 50 mm 2” / 50 mm
Right Side 2” / 50 mm 2” / 50 mm
Floor / Ground 12” / 300 mm 30” / 762 mm
Floor / Ground to Bottom of Low Loss Header
Vent 0 0
clearance to
combustibles and
non-combustibles
0 12” / 300 mm
Recom-
mended
service
clearances
Rinnai Corporation • 103 International Drive • Peachtree City, GA 30269 • Toll-Free: 1-800-621-9419 • Fax: 678-364-8643 • www.rinnai.us
© 2017 Rinnai Corporation
Q205S-SP-2 8/2017