Rinnai RHFE-750ETR User Manual

Page 1
Owner’s Operation and Installation Manual for the
RHFE-750ETR
Direct Vent Fireplace
Table of Contents .......... 2
Safety Information.......... 2
Operating Instructions.... 6
Care and Maintenance... 11
Fault Codes ................... 14
Installation Instructions .. 15
Consumer Support......... 36
WARNING: If the information in these instructions are not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life.
— Do not store or use gasoline or other flammable vapors and
liquids in the vicinity of this or any other appliance.
— WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do not use any phone in
your building.
Immediately call your gas supplier from a neighbor’s phone.
If you cannot reach your gas supplier, call the fire
department.
— Installation and service must be performed by a qualified
installer, service agency or the gas supplier.
INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.
Page 2
This appliance may be installed in an aftermarket, permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes.
This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
Table of Contents
Consumer Safety Information
Safety Definitions........................................ 2
Safety Behaviors and Practices.................. 3
Safety Features........................................... 3
Specifications................................................. 4
Features ..................................................... 5
Dimensions................................................. 5
Flue Manifolds............................................. 5
Operating Instructions
Front Panel ................................................ 6
Remote Control Features ........................... 7
Remote Control Care..................................7
Sequence of Operations............................. 8
Basic Fireplace Operations
Turning ON and OFF............................. 8
Remote Control Operation..................... 8
Adjusting the Temperature .................... 9
Obstruction of Warm Air Discharge ....... 9
Lock Function ........................................ 9
Flame Function ...................................... 9
Auto Off Function................................... 9
Timers
Programming the Clock and Timers .... 10
Using the Timers.................................. 10
Using the Override............................... 10
Pre-heat ............................................... 10
Care and Maintenance
Maintenance ........................................ 11
Filters ................................................... 11
Visual Inspection of Flame .................. 11
Care of Exterior.................................... 12
Cleaning Combustion Chamber Glass 12
Troubleshooting........................................13
Fault Codes............................................... 14
Installation Instructions
General Instructions..................................15
Clearances to Combustibles.....................15
Flue Terminal Clearances................... 16, 17
Location ..............................................18, 19
Drilling Flue and Gas Supply Holes..........20
Flue Manifold Installation.................... 20, 21
Extension Kit Installation..................... 22, 23
Connections........................................ 24, 25
Final Assembly
Install the Logs..................................... 26
Open the Air Guide Vanes................... 27
Install the Front Panel.......................... 27
Operating Instructions............................... 28
Wiring and Schematic Diagram................29
Parts List..............................................30-36
Consumer Support
................................. 36, 37
Consumer Safety Information
Safety Definitions
This is the safety alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and
others.
DANGER
WARNING CAUTION
2 Rinnai Corporation RHFE-750ETR
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
Indicates a potentially hazardous situation which, if not avoided, could result in minor or moderate injury. It may also be used to alert against unsafe practices.
Page 3
Safety Behavior and Practices
WARNING
Keep the area around the appliance clear and free from combustible materials, gasoline, and other flammable vapors and liquids.
Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
CAUTION
Do not block the warm air discharge. Do not allow anyone to sleep directly in front of the appliance.
Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.
Children and adults should be alerted to the hazards of high surface temperature and should stay away to avoid burns or clothing ignition. Hand or body contact with the warm air discharge louvers and glass must be avoided.
Young children should be carefully supervised when they are in the same room as the appliance.
Do not operate appliance with the glass front removed, cracked, or broken. Replacement of the glass should be performed by a licensed or qualified service technician.
Broken or damaged components should be removed or repaired by a licensed or qualified service technician.
Never store liquid propane containers indoors.
Do not spray aerosols near the appliance while it is
operating. Most aerosols contain butane gas which is flammable.
Do not place items on or against the appliance. If there is a power failure while the appliance is ON then the overheat vent on top of the panel may open to release internal heat. An item placed on top of the appliance could prevent the overheat vent from opening resulting in damage to the appliance.
Any safety filter or guard removed for servicing must be replaced prior to operating the appliance.
Clothing or other flammable material should not be placed on or near the appliance.
Do not insert items into the louvers.
Safety Features
Overheat: The appliance will automatically shut
down when the appliance exceeds a predetermined temperature.
Flame Failure: The appliance will automatically
shut down if the burner flame is extinguished.
Power Failure: The appliance will cut off the gas if
it loses electrical power.
Power Surge Fuse: A glass fuse power supply
harness protects against overcurrent. If the fuse blows then all indicator lamps will be off.
Spark Detector: The appliance automatically
shuts down if there is an abnormal spark at ignition.
Rinnai Corporation RHFE-750ETR 3
Page 4
Specifications
Application Inbuilt only; for residential installation, commercial setting, or manufactured
home; not designed for installation in a solid-fuel burning fireplace
General Description Inbuilt convector, glass and steel fronted, ceramic log space heater with
forced convection and power flue system
Operation Push button electronic / remote control
Gas Connection Flex line is 3/8 inch flare nut;
ball valve is 1/2 inch female x 3/8 inch flare
Gas Control Electronic
Burners Flame burners
Temperature Control Electronic thermostat
Logs Ceramic
Ignition System Electronic spark ignition
Flue System The flue must be terminated to atmosphere. Only flue components listed with
the appliance’s certification can be used. Warranty will be voided if non-listed components are installed.
Electrical Connection AC 120V, 60 Hz
Fan 3 speed
Weight 154.3 lb (70 kg)
Minimum supply gas pressure 4.3 in (109 mm) W.C. 9.8 in (249 mm) W.C.
Maximum supply gas pressure 10.5 in (267 mm) W.C. 13.0 in (330 mm) W.C.
Manifold test pressure Factory Set Factory Set
BTU/hour input Natural Gas: Low - 10000 BTU/h; High - 29000 BTU/h
Propane: Low - 10000 BTU/h; High - 28000 BTU/h
BTU/hour output Natural Gas: Low - 7850 BTU/h; High - 21900 BTU/h
Propane: Low - 8050 BTU/h; High - 21840 BTU/h
Rinnai is continually updating and improving products. Therefore, specifications are subject to change without prior notice.
Natural Gas Propane Gas
4 Rinnai Corporation RHFE-750ETR
Page 5
Features
Direct Vent: Intake air is taken from the outside
and the combustion products are exhausted to the outside. Therefore the furnace has no effect on the quality of the indoor air.
Push Button Ignition: Only one push of the
STANDBY/ON switch is all that is required to operate the heater.
Lock: The buttons on the remote control can be
locked to prevent any unintended operation.
Dual Timer: The appliance can be programmed to
operate at two separate periods during the day.
Pre-heat: The appliance will turn on before the
programmed ON time and begin raising the room temperature to that of the programmed temperature by the ON time.
Memory: The computer memory records preset
temperatures, timer programming, and, operational modes.
Remote Control: The appliance has a fully
functioning cordless remote control.
Auto-Off Function: You have the option of having
the flame display remain on or off once the room temperature reaches the temperature setting.
Dimensions
33 3/16 (842)
33 3/16 (842)
GAS CONNECTION
2 1/4 (57)
15 3/4 (400)
FLUE CONNECTION
14 7/8 (378)
4 15/16 (126)
21 5/16 - 23 5/16 (542 - 592)
2 15/16 (71)
35 7/16 (900)
B
23 5/8 (600)
10 13/16 (274)
B
27 9/16 (700)
26 3/4 (679)
14 1/2 (369)
25 13/16 (655)
3 5/16 (84)
17 13/16 (453)
Flue Manifolds
See the installation instructions for the parts list of the vent kit.
The “A” Vent Kit is included with the appliance.
The following flue manifold sizes are available:
Name Kit No. fits walls
A Vent Kit FOT-203 4 1/3 - 9 1/2 inch (110 - 240 mm)
B Vent Kit FOT-204 9 1/2 - 15 3/4 inch (240 - 400 mm)
Rinnai Corporation RHFE-750ETR 5
Page 6
Operating Instructions
Front Panel
FAULT CODE DISPLAY
OVERHEAT
DISCHARGE VENT
TEMPERED GLASS IN THE
FRONT PANEL
CERAMIC GLASS PAN EL AT
THE COMBUSTION CHAM BER
TIMER INDICATOR
OPERATION INDICATOR
ON/OFF BUTTON
CONTROL PANEL
LOG SET
BLOCKAGE INDICATOR
for FILTERS (flashes red)
for WARM AIR DISCHARGE
(glows red)
REMOTE CONTROL
RECEIVER WINDOW
ROOM AIR RETURN
LOUVER, WARM AIR DISCHARGE
Front Panel
(features are the same for flat and cu rved models)
Front Panel Models
Description Part Number
Flat Metal - Black Front R2700
Flat Metal - Stainless Steel Front R2701
Radius (curved) Glass - Silver Front R2702
Radius (curved) Glass - Black Front R2703
6 Rinnai Corporation RHFE-750ETR
Page 7
Remote Control Features
INFRA RED
EMITTER
DISPLAY
UP and DOWN
BUTTONS
Changes temperature,
flame level, or time
TIMER 1 BUTTON
Sets timer program 1
TIMER 2 BUTTON
Sets timer program 2
OVERRIDE BUTTON
Overrides timer
operation
STANDBY / ON
BUTTON
Stops and operates the
heater remotely
FLAME BUTTON
Controls the flame level
AUTO OFF
AUTO OFF BUTTON
Turns the flame off when
the temperature setting is
reached.
Lo ck
Override Aut o Off
AM PM
Te m p e r a t u r e
Se t
Cl o c k Ti m e r 1
Se t O N O FF
STA N D B Y
ON
Fl a m e
Auto
Off
Lock
Fl a m e
Ti m e
ON OFFTi m e r 2 Set
Ti mer 1
Ti mer 2
Overrid e
Ti m e
Se t
LOCK BUTTON
Locks out control to prevent unintended
operation
TIME SET BUTTON
Sets the clock and timers
Remote Control Care
Use two 1.5V AAA batteries.
To replace batteries unscrew the battery
compartment cover located on the back of the remote control counter clockwise. Ensure that the correct polarity is observed. The polarity is engraved into the battery compartment. Replace the cover by turning clockwise until a soft click is heard.
To avoid damage from leaking batteries, remove batteries if the remote control is not going to be used for a long period.
Some fluorescent lights may interfere with the transmission of remote control signals.
Do not place it close to the warm air discharge louvers.
Avoid dropping the remote control or getting it wet.
Celsius (0)/ Fahrenheit (1) switch
0
1
O - I
Avoid leaving the remote control in direct sunlight.
Rinnai Corporation RHFE-750ETR 7
Page 8
Sequence of Operations
The combustion fan will run for several seconds before ignition to purge the combustion chamber of any gas.
If the front burner fails to ignite the appliance will turn off and fault code 11 will be displayed. If the rear burner fails to ignite the appliance will turn off and make another attempt to ignite. If this second attempt fails, the appliance will automatically turn off and fault code 11 will be displayed. This may occur when using the appliance for the first time or if it has not been used for a while. Try operating the appliance again.
The appliance may make noises after ignition or extinction of the flame. This is normal and is due to the thermal expansion or contraction of its components.
If the ON/OFF or the STANDBY/ON button is pressed immediately after the flame has been extinguished, the appliance will delay ignition for about 1 minute.
The normal ignition sequence is as follows:
1. When the ON/OFF or the STANDBY/ON button is pressed the Operation Indicator LED will glow red and the combustion fan will rotate to purge the combustion chamber.
2. Electric ignitor operates.
3. Gas is allowed to flow to the pilot when a spark is sensed.
4. When the pilot flame is established gas will flow to the front burners and then to the rear burners.
5. When all burners are established the appliance will automatically maintain the temperature setting.
NOTE: The appliance will wait until the heat
exchanger is warmed up before discharging air. This ensures that any discharge air will be warm and not cold.
Basic Fireplace Operations
Turning ON and OFF
Remote Control Operation
The Operation Indicator will glow red when the appliance is ON.
The appliance will turn ON ­and attempt ignition:
when you press the ON/ OFF button on the appliance panel while the appliance is OFF.
when you press the STANDBY/ON button on the remote control while the appliance is in STANDBY.
at the TIMER setting after you have activated the TIMER and while the appliance is in STANDBY.
Pressing the STANDBY/ON button on the remote control while the appliance is ON will put the
appliance in STANDBY mode, extinguishing
STA N D BY
ON
appliance is ON or in STANDBY will turn the appliance OFF.
all flames and cause the Operation Indicator to glow green.
Pressing the ON/OFF button while the
Operation Indicator
The remote control emits an infrared (IR) signal and must be aimed at the receiver located to the right of the warm air discharge louvers. The normal operating range is about 16 feet (4.9 m) with an angle of about 40 degrees to the horizontal. This range will vary depending on the position of the installation and the strength of the remote control batteries.
Signal transmissions are confirmed by
a brief illumination of the Transmission Signal Indicator on the Remote Display
a flash by the Remote Control Receiver to the right of the louvers
a beep from the appliance
The remote control transmits information whenever a button is pressed except as follows:
when the lock function is activated
when setting the timers, timer information is
transmitted only when the “TIME SET” button is pressed
8 Rinnai Corporation RHFE-750ETR
Page 9
Basic Fireplace Operations
Adjusting the Temperature
Pressing the UP and DOWN buttons will change the
temperature setting by 2 degree (F) increments. The display will show “Temperature” and the new temperature as confirmation.
The temperature can be set to:
L (Low) - burner is on minimum combustion
Lock
Override Auto Off Flam e
PM
Te m p e r a t u r e
Cl o c k
Se t
Ti mer 1
Se t O N O F F
ON OFFTi mer 2 Set
The temperatures 16-26° C are available in one degree increments. To return to Fahrenheit scale move the switch toward “1”.
60° F - 80° F in two degree increments
H (High) - burner is on maximum combustion
To use Celsius scale, open the battery compartment and move the switch toward “0”.
Obstruction of Warm Air Discharge
Obstructing the louvers for the warm air discharge will cause the appliance to operate inefficiently.
When an obstruction is detected the Blockage Indicator LED above the Receiver Window will glow red and combustion reduces to front burner, low operation only.
To restore normal operation, remove the obstruction, turn the appliance OFF and then ON.
Lock Function
Pressing the LOCK button will cause all
Lock
Lock AM
PM
functions of the remote control to be locked except for the STANDBY/ON button.
Override
Te m p e r a t u r e
Ti me
The remote control display will show the word “Lock” in the top left corner.
To cancel the Lock function press down and hold the LOCK button for 3 seconds.
Flame Function
Press the FLAME button to control the flame
Fl am e
Lock
AM
PM
Cl o c k Ti me r 1
flame automatically.
If the room temperature reaches 104° F (40° C) while the flame function is on then the appliance will turn off automatically as a safety precaution.
The FLAME function is not available during TIMER operation.
level. There are seven levels of flame available.
The display will show the
Over ri d e
Te m p e r a t u r e
Se t
Se t ON O FF
ON OFFTi me r 2 Set
Ti m e
Fl am e
word “Flame” and a series of short bars (one for each flame level).
Use the UP or DOWN buttons to select the desired flame level.
Pressing the FLAME button again will allow the appliance to control the
Auto Off Function
When the appliance is not in AUTO OFF mode and the room temperature reaches the temperature
setting the appliance will reduce the gas
Aut o
Off
Lock
AM
PM
Cl o ck Ti m e r 1
mode press the AUTO OFF button. The words “Auto Off” will be displayed above the time. To exit this mode press the AUTO OFF again.
Whether this mode is on or off, the appliance will attempt to maintain the temperature setting.
flow and maintain the flame on the lowest flame level. The temperature may continue to rise even on this low setting. If the
temperature reaches
Override Aut o Off
Te m p e r a t u r e
Ti m e
Se t
Se t ON O FF
ON OFFTi m e r 2 Set
Fl a m e
104° F (40° C) then the appliance will automatically shut down with fault code 16.
In AUTO OFF mode the gas flow will be reduced to pilot operation with no visible flame when the temperature setting is reached. To enter this
Rinnai Corporation RHFE-750ETR 9
Page 10
Timers
Programming the clock and timers
The clock must be set before the timers will operate. The temperature setting during timer operation is the temperature last used when the appliance was on. During the steps below, if no button is pressed for 90 seconds then the screen will return to the current time display.
Ti me
Se t
Lock
AM
Cl o ck
Ti me r 1
Lock
AM
PM
Cl o ck
Ti me r 1
1. Press the TIME SET button. The display will show the words “Clock Set” and “AM 12:00” or the time.
2. Use the UP or DOWN buttons to set the desired clock time.
NOTE: If you do not want to set the timers now then press the TIME SET button five more times to finish setting the clock.
3. Press the TIME SET button. “Timer 1 Set ON” and “AM 6:00” or
Override Aut o Of f
Te m p e r a t u r e
Se t
Se t O N OFF
ON OFFTi me r 2 Set
Override Aut o Of f
Te m p e r a t u r e
Se t
Se t O N O FF
ON OFFTi me r 2 Set
and Timer 1.
Ti me
Ti me
the last programmed time
Fl a m e
will be displayed. Use the UP or DOWN buttons to set the desired on time. When finished press the TIME SET button.
4. “Timer 1 Set OFF” and “AM 9:00” or the last programmed time will be displayed. Use the UP or DOWN buttons to set the
Fl a m e
desired off time. When finished press the TIME SET button.
5. To set Timer 2 repeat steps 3 and 4. If finished press the TIME SET button two more times to complete setting the clock
Using the Timers
Check the temperature setting before using the timers.
go into standby mode and the Timer Indicator will glow green.
To turn the timers off press the appropriate timer button again. If the appliance was on, it will return to standby mode and the Operation Indicator will glow green.
The Timer Indicator will not display if both timers are turned off.
Using the Override
This function is used to manually override
Override
Lock
AM
PM
Cl o ck
Ti me r 1
for operation then pressing OVERRIDE will turn the appliance ON.
OVERRIDE does not change the programmed times.
Timer programmed operation.
If the appliance is
Override Auto Off
Te m p e r a t u r e
Ti m e
Se t
Se t O N OFF
ON OFFTi me r 2 Set
Fl am e
operating in Timer mode then pressing OVERRIDE will turn the it OFF and cause the word “Override” to be displayed for 10 seconds.
If the appliance is in Timer mode but outside of the programmed time
Pre-heat
The appliance may operate up to one hour before the programmed ON time in order to allow the room to reach the desired temperature by the programmed ON time. The pre-heat time (how long before the programmed ON time that the appliance will provide heat) is determined by the difference between the temperature setting and the room temperature one hour before the programmed ON time.
One or both timers can be used. To allow
Ti m er 1
Ti m er 2
10 Rinnai Corporation RHFE-750ETR
the appliance to operate during the pre­programmed times press the TIMER 1 and/ or TIMER 2 button. The display will briefly show the “on” and “off” times for each timer. If the current time is outside of the programmed times then the appliance will
Page 11
Care and Maintenance
Maintenance
Repairs should be performed by a qualified service technician. The appliance should be inspected annually by a qualified service agency.
More frequent cleaning may be required due to excessive lint from carpeting, bedding material, etc. It is imperative that control compartments, burners, and circulating air passage ways of the appliance be kept clean.
When the appliance has cooled off, gain access by removing the front panel, combustion chamber glass panel, and ceramic logs. Refer to the Parts List and the sections Cleaning Combustion Chamber Glass and Final Assembly for disassembly / assembly instructions. Vacuum, use pressurized air, and then vacuum again to remove dust from the burners, compartments, and convection fan.
Any filter or guard removed for servicing the appliance must be replaced prior to operating the appliance.
The vent should be inspected annually for blockages or damage.
Motors are permanently lubricated and do not need periodic lubrication. Keep fan and motor free of dust and dirt by cleaning annually.
Verify proper operation after servicing.
ability to produce heat. The filters should be cleaned once a week during the heating season. If the filters become blocked the blockage indicator will flash red. The filters should be cleaned whenever the blockage indicator flashes red. If not cleaned the appliance may turn off and display fault code 14 (overheat) on the control panel display.
To clean the filters, the appliance should be OFF and cool. Open the louver by pushing inward and releasing. Slide the filter upwards until the bottom tab clears the lower retaining slot. Then slide the filter down and away to remove. Clean the filter using a soft dry cloth or vacuum.
Visual Inspection of Flame
Check that the pilot and burner flames are operating normally.
If flames appear either very short or very long and streaky or are producing smoke or soot deposits then there may be a problem with the appliance or gas supply.
The appliance should not be used if you suspect there is a problem. Call a qualified service technician to inspect the appliance.
The burners are designed to produce two rows of yellow flame but not smoke or soot.
Filters
This appliance has two filters which are behind the louvers on either side of the heater. The louvers are hinged to allow access to the filters.
Dirty filters reduce the air flow and the appliance’s
NORMAL
ABNORMAL
Rinnai Corporation RHFE-750ETR 11
Page 12
Care and Maintenance
Over time combustion products may leave a film on the combustion chamber glass. Continued use of the appliance may permanently stain the glass. If filming occurs, this glass panel needs to be removed, cleaned, and installed only by a qualified service technician.
WARNING
Do not clean glass when hot.
Do not clean glass with abrasive cleaners.
12 Rinnai Corporation RHFE-750ETR
Page 13
Troubleshooting
Problem Possible Solutions or Explanation
No display on remote Replace the remote control batteries.
No ignition or no panel indications Ensure the appliance has power.
Press the control panel ON/OFF button.
Burners fail to ignite Air may need to be purged from the gas line. Several
ignition attempts may purge the gas line.
Turn on the gas supply.
Combustion stops during operation Remove any obstructions from the louvers.
Turn on the gas supply.
Smell of gas Follow the instructions in the warning block on the front of
this manual.
Remote control does not work Ensure the appliance has power.
Press the control panel ON/OFF button.
Press the LOCK button for 3 seconds if LOCK is displayed.
Press the STANDBY/ON button.
Warm air does not start immediately after burner lights
Smoke or odors are produced when first operated This is caused by grease or oil on the heat exchanger or by
Clicking noises at ignition or shutdown Internal components are cooling (contracting) or heating up
Clunking noise when the thermostat operates This is the sound of the solenoid gas valves opening and
Convection fan continues to run after appliance is turned OFF
Steam is discharged from the flue outside Steam discharge is normal.
Does not start while in STANDBY and the temperature is below the setting
Timers do not turn the appliance ON or OFF Timers may be turned off or incorrectly programmed.
Timer turns the appliance ON briefly and then the appliance turns OFF before the OFF time setting.
The appliance will wait until the heat exchanger is warmed up before discharging air. This ensures that any discharge air will be warm and not cold.
dust and should stop after a short time.
(expanding) at different rates.
closing to regulate the gas flow.
The fan will continue to run to prevent internal components from over heating.
Timers must be turned off (or press OVERRIDE) for manual operation.
The room temperature may be higher than the temperature setting.
Rinnai Corporation RHFE-750ETR 13
Page 14
Fault Codes
If there is a malfunction the appliance may shut down as a safety precaution and display a fault code to assist in diagnosing the problem. The fault code will flash in the Fault Code Display window and the Operation Indicator will flash green.
Code Fault Remedy
Confirm that the gas supply is turned on. Switch appliance to
11 Ignition failure
12 Incomplete combustion Service call
14 Filter blocked or Overheat
16 Room overheat
31 Room temperature sensor faulty Service call
STANDBY and then ON again. If ignition failure continues then a Service call is required.
Clean filters If overheating continues then a service call is required to determine the cause. Thermal fuse; a qualified service technician must replace the fuse following the procedure below.
The temperature has reached 104° F (40° C). Turn the appliance off or engage the AUTO OFF function to prevent the display of flame. See AUTO OFF section.
32 Overheat temperature sensor faulty Service call
53 Spark sensor faulty Service call
61 Fan motor faulty Service call
71 Solenoids faulty Service call
72 Flame detection circuit fault Service call
73 Communication fault Service call
99 Flue block Check around flue terminal for obstructions to air flow
Replacement of Thermal Fuse
The cause of the overheat condition needs to be determined and remedied before replacing the thermal fuse.
A qualified service technician needs to:
1. Disconnect the appliance from the power supply.
2. Remove the right hand side panel to allow access to the gas control and main PCB.
3. Unplug the thermal fuse harness (including the control plug for the POV on the gas control) and unscrew thermal fuse.
Thermal Fuse
PCB
POV
4. Re-assemble with replacement thermal fuse.
14 Rinnai Corporation RHFE-750ETR
Page 15
Installation Instructions
General Instructions
The appliance must not be connected to a chimney
WARNING
Do not use substitute materials.
Use only parts certified with the appliance.
A qualified service technician should install the appliance and inspect it before use.
The installation must conform with local codes or, in
the absence of local codes, with the National Fuel Gas
Code, ANSI Z223.1/NFPA 54, or the Natural Gas and Propane Installation Code, CSA B149.1.
A manufactured home (USA only) must conform with
the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or, when such a
standard is not applicable, the standard for
Manufactured Home Installations, ANSI/NCSBCS A225.1, or the standard for Gas Equipped Recreational Vehicles and Mobile Housing, CSA Z240.4.
The appliance, when installed, must be electrically grounded in accordance with local codes or, in the
absence of local codes, with the National Electrical
Code, ANSI/NFPA 70, or the Canadian Electrical Code, CSA C22.1.
Two 1/8 in test plugs are provided for testing of manifold differential pressure.
flue serving a separate solid-fuel burning appliance.
The appliance and its appliance main gas valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its equipment shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psi (3.5 kPa).
If the flooring is carpet, tile, or other combustible material other than wood, then the appliance must be installed on a metal or wood panel extending the full width and depth of the appliance.
This appliance discharges a large volume of warm air next to the floor. Any particles in the air such as cigarette smoke could cause discoloration in carpet. The warm air flow could discolor nylon carpets containing dyes or vinyl surfaces. To prevent discoloration of the floor covering place a mat under the appliance which extends about 30 inches in front of it.
Refer to the conversion manual for high altitude installations.
Clearances to Combustibles
The clearances to combustibles as stated on the rating plate and as shown in the figures must be followed. Also refer to the Safety Behaviors and Practices section.
combustible projections (ex. mantles)
Wall
1"
3"
2"
3"
5"
4"
Top Panel of Fireplace
4"
45°
CLEARANCES FROM THE SIDES
Rinnai Corporation RHFE-750ETR 15
CLEARANCES
FROM THE TOP
45°
Top Front
Edge
6"
4"
5"
3"
4"
2"
1"
Wall
3"
Page 16
X
Flue Terminal Clearances
K
M
I
INSIDE
H
AIR SUPPLY INLET
VENT TERMINAL AREA WHERE
TERMINAL IS NOT
PERMITTTED
V
B
FIXED
CLOSED
OPERABLE
B
G
CORNER D ETAI L
A
J
A
B
B
FIXED
CLOSED
OPERABLE
C
B
F
B
L
E
D
16 Rinnai Corporation RHFE-750ETR
Page 17
Flue Terminal Clearances
terminate directly above
a sidewalk or paved
driveway that is located
between two single
family dwellings and
serves both dwellings.
veranda, porch, deck,
or balcony is fully open
on a minimum of two
sides beneath the floor.
specified in ANSI
Z223.1/NFPA 54 or
CSA B149.1,
clearances are in
accordance with local
installation codes and
the requirements of the
gas supplier.
1 A vent shall not
12 inches (30 cm) 12 inches (30 cm)
12 inches (30 cm) 9 inches (23 cm)
Canadian Installations US Installations
2 Permitted only if
* For clearances not
*
within 10 feet (3 m)
3 feet (91 cm) above if
* *
above the meter/
3 feet (91 cm) within a
height 15 feet (4.57 m)
regulator assembly
12 inches (30 cm) 9 inches (23 cm)
6 feet (1.83 m)
horizontally
7 feet (2.13 m) 1 *
12 inches (30 cm) 2 *
Description
Clearance above grade, veranda, porch,
A
Ref
deck, or balcony
Clearance to window or door that may be
opened
B
Vertical clearance to ventilated soffit,
located above the terminal within a
horizontal distance of 2 feet (61 cm) from
the center line of the terminal
C Clearance to permanently closed window * *
D
E Clearance to unventilated soffit * *
Rinnai Corporation RHFE-750ETR 17
Clearance to each side of center line
extended above meter/regulator assembly
F Clearance to outside corner * *
G Clearance to inside corner * *
H
Clearance to nonmechanical air supply
inlet to building or the combustion air inlet
to any other appliance
I Clearance to service regulator vent outlet 3 feet (91 cm) *
J
Clearance to a mechanical air supply inlet
K
Clearance above paved sidewalk or
paved driveway located on public property
L
Clearance under veranda, porch, deck, or
balcony
M
Page 18
Location
This appliance has a cool outer casing that allows it to be installed in a recessed application consisting of combustible materials such as wood and plaster.
The location needs to have a level surface that allows the appliance to be rolled in or out of the enclosure.
If the surface is elevated and there is not enough room for it to be rolled out then a base and joists may be used as shown.
The appliance will have to be rolled out for maintenance. After installation do not place any permanent fixtures that would prevent pulling the appliance out for access. To pull the appliance completely out of the enclosure a minimum of 15 inches from the front panel would be needed.
Do not vent the exhaust into ‘natural draft’ flue pipes or a chimney flue.
The enclosure must be within these limits:
Enclosure Dimensions
Width (w) 33.8 in (860 mm)
Height (h) 26.0 - 26.2 in (660-665 mm)
Depth (d) 15.0 - 16.9 in (380-430 mm)
The front panel extends below the surface on which the appliance rests. Ensure that clearance is maintained in order to install the front panel.
LEFT
WHEEL
JOIST JOIST
28.3 in (720 mm)
RIGHT
WHEEL
w
h
d
For installation in the corner of the room refer to the diagram at the right and the table below for dimensions. These dimensions are the minimum required if using the minimum width, height, and depth dimensions above.
Enclosure Dimensions in a Corner
x
x 63.8 in (1620 mm)
y 45.1 in (1146 mm)
z 31.9 in (810 mm)
z
18 Rinnai Corporation RHFE-750ETR
y
Page 19
Location
Use the adjustment feet so that the appliance is level and not tilted. They are initially installed immediately behind the side louvers but can be moved forward for better access in hearth or floor installations.
The hearth should not block the appliance.
Correct Floor
Level Installation
Wall Lining
Particle Board, MDF, Plywood etc.
Rinnai Corporation RHFE-750ETR 19
Wall Lining
Particle Board, MDF, Plywood etc.
Wall Lining
Particle Board, MDF, Plywood etc.
Page 20
Drilling Flue and Gas Supply Holes
Check for water and gas pipes as well as electric cables. Use the template supplied to mark the wall locations for the flue manifold and the gas supply. Drill the flue hole using a 3 1/2 inch (90 mm) drill.
For weatherboard walls, drill through the center of the weatherboard from the outside first and then through the plasterboard.
Flue Manifold Installation
1. Disassemble the Flue Manifold
The flue consists of 3 parts:
sleeve
inside connection
terminal
Disassemble the flue manifold by first pulling out the inside connection. To remove the outer terminal pull and release the two internal ties and then pull out the outer terminal.
Clearance to combustibles for the sleeve and flanges is zero inches.
2. Assemble and Adjust the Sleeve Length
Measure wall thickness through previously drilled 3 1/2 inch (90 mm) hole.
Inside Connection
Sleeve
Terminal
The end of the sleeve should protrude 3/16 - 3/8 inch (5-10 mm) from the outside wall.
a
In the “A” vent kit there are 4 parts provided with which to assemble the sleeve. Use the table to determine which pieces to assemble.
In both the “A” and “B” vent kits, two parts are threaded for additional adjustment.
Adjust the sleeve length to wall thickness plus 3/16 - 3/8 inch (5-10 mm).
For wall thickness plus 3/16 - 3/8 in (5-10 mm) Assemble these parts (“A” Vent Kit)
4 1/3 - 6 1/8 in (110 - 155 mm)
6 1/8 - 7 3/4 in (155 - 195 mm)
7 3/4 - 9 1/2 in (195 - 240 mm)
a
++c+
a
b
Sleeve Parts
+
a
++
b
b
b
c
c
c
20 Rinnai Corporation RHFE-750ETR
Page 21
Flue Manifold Installation
3. Attach the sleeve
Attach to the inside wall using 3 screws arranging
the flange so that the marking “TOP” is at the top.
The flange is offset 2° to allow the condensate to
drain to the outside.
3 screws
4. Install the Terminal
Check that the terminal seal is in place. For
weatherboard or vinyl siding, add the second seal next to the terminal seal to compensate for the angle.
From the outside insert the terminal into the
sleeve with the marking “TOP” at the top. The left hand side locking tie should be marked “LEFT”.
sleeve should extend 3/16 - 3/8 in (5-10 mm)
Terminal seal
Terminal
5. Lock the ties
Pulling hard on the left and right hand ties, clip
the ties over the notches inside the sleeve. You should be able to pull the ties 2 or 3 notches past the starting point. Cut the ties, leaving about 3/4 inch (20 mm) past the notch. Bend the ties back into the sleeve and parallel to the wall.
6. Attach Inside Connection Assembly
Push the assembly into the terminal tube.
Attach the inside connection with 3 screws. The
inside connection can still be turned if necessary.
Locking tie
Locking ties
Sleeve
Rinnai Corporation RHFE-750ETR 21
Page 22
Extension Kit Installation
If necessary, extension kits are available to extend the exhaust line and air line between the manifold and the appliance. The maximum extension allowed is shown in the table below and is based on the number of 90° elbows used. Vertical extensions are not allowed.
maximum vent length 7.2 ft (2.2 m) 6.5 ft (2.0 m) 5.9 ft (1.8 m)
no elbows 1 elbow 2 elbows
Clamps
Both the exhaust line and air intake hose are supported by clamps which are attached to the wall. A wall fixture can be used to offset the clamp from the wall. If the wall fixture is not used then use Screw A and the nut to attach the clamp to the wall.
The air line should always be underneath the exhaust line so that in case the air line sags it will not come into contact with the exhaust line.
Installing the Exhaust Line
The exhaust line is connected between the joint pipe at the rear of the heater and the exhaust port on the flue pipe.
Slope the exhaust line 3° to the outside so that any condensate will drain away from the appliance. The figures below show two examples of horizontal exhaust line extensions.
1. Attach the clamp with one screw to secure the
extension pipe to the flue manifold.
2. Use pipe stopper A to clamp the connections with
all other components.
3. Use pipe stopper B to fix the length on the
adjustable exhaust pipes. Do not extend these pipes beyond the red line.
Pipe Clamp and Wall Fixture
Screw B
Air Line
Flue Manifold
Exhaust Line
Air Line
Screw A
Pipe Stopper A
Tie
Pipe Stopper B
Clamp
Example with One Elbow
4. Do not cut the exhaust pipe.
5. To bend the elbow, insert exhaust pipes into both
ends for additional leverage. Bend to desired angle.
Example with No Elbows (straight out)
6.5 ft (2m) Maximum
7.2 ft(2.2 m)Maximum
3° SLOPE
3° SLOPE
22 Rinnai Corporation RHFE-750ETR
Page 23
Extension Kit Installation
Connecting the Air Line
The air line is connected between the air connection at the rear of the heater and the air intake port on the flue manifold.
Push the air intake hose onto the flue manifold and secure with the plastic cable tie.
Join air intake hoses by screwing the hose joint half of its length into the air intake hose and then screwing another air intake hose into the hose joint.
Clearances
exhaust pipe to combustibles 1 inch (25.4 mm)
exhaust pipe to non-combustibles zero
Extension Kits and Parts
The hose can be cut to the required length. Deburr all rough edges.
Support the air line with pipe clamps.
Description FOT-102 FOT-103 FOT-114 FOT-115
Exhaust Pipe (adjustable)
11.4-20.3 in (290-515 mm)
Exhaust Pipe (adjustable)
21.0-39.6 in (533-1005 mm)
Exhaust Pipe
40 in (1016 mm)
Air Intake Hose
29.5 in (750 mm)
Air Intake Hose
49.2 in (1.25 m)
Air Intake Hose
90.6 in (2.3 m)
Elbow (flexible) 1
Hose Joint 1 1 1
Pipe Stopper A 1 1 2 2
Pipe Stopper B 1 1 1
Top Stopper 1 1 1
Pipe Clamp 2 sets 3 sets 4 sets
1
1 1
1
1
1
1
Wall Fixture 2 3 4
Nut 2 3 4
Screw A 2 3 4
Screw B 4 6 8
Rinnai Corporation RHFE-750ETR 23
Page 24
Connections
1. Carefully remove the packaged ceramic logs and
place in a safe location.
2. To ensure the correct positioning, terminate the
gas supply so that it is 5.9 inches (150 mm) from the front of the enclosure.
3. Gain access to the gas connection by removing
the right hand side access panel by unscrewing the four retaining screws. Pry the front edge of the panel open to the right and pull forwards.
4. Position the appliance in front of the enclosure so
that the end of the gas supply aligns with the gas fitting opening. Connect the flexible gas connection to the gas supply.
5. Replace the right hand panel and secure with the
four retaining screws.
remove 4 screws to remove side panel
6. Unscrew the flue access panel held by two screws located inside the top left-hand corner of the appliance. Slide this panel to the right behind the convection fan.
7. Attach the electrical connection and place in the junction box.
8. Leak test the gas connection using a soapy solution. Do not allow the soapy solution to contact electrical components. Remove any residue.
gas fitting opening gas connection
24 Rinnai Corporation RHFE-750ETR
Page 25
Connections
9. Remove clamp L and slide the vertical pipe M down into the lower elbow N to remove parts J and K. Separate J and K.
10. Attach pipe J to the flue manifold with clamp and screw. (If using extension pipes, attach pipe J to the extension pipe using pipe stopper A.)
11. Push the air intake line onto the flue manifold and secure with the plastic cable tie. Make sure the hose does not kink. (This may have been done when installing extension pipes.)
13. Slide tube M up into elbow K and clamp together with clamp L.
14. Slide the flue access panel back into position and attach with two screws.
15. Open both of the air return louvers on both sides. Secure the appliance using the four mounting points.
12. Carefully slide the appliance into the enclosure lining up the gas supply and exhaust pipe. Fit elbow K to pipe J making sure that the clip in elbow K goes beyond the groove in the pipe. The gas supply flexible hose is designed to coil inside the appliance as it is pushed into the enclosure.
Rinnai Corporation RHFE-750ETR 25
Page 26
s
Final Assembly
Install the Logs
The log set consists of seven pieces as follows:
rear
left hand middle
right hand middle
center top
1. Remove the two retaining screws that secure the combustion chamber glass panel.
2. Rotate and lift the combustion chamber glass clear of the combustion chamber and place in a safe location.
right hand top
left hand front
right hand front
retaining screw
J
Step 3
3. Seat the rear log into the combustion chamber onto its location pins.
4. Seat the left hand middle log onto its location pins.
5. Seat the right hand middle log onto its location pins.
6. Seat the center top log onto the location pins.
7. Seat the right hand top log onto the location pins.
8. Place the left hand front log and the right hand front log on the pins.
9. Install the glass panel with two retainer screws at the top of the panel.
Steps
6 & 7
left hand front
right hand front
Step 8
26 Rinnai Corporation RHFE-750ETR
Page 27
Install the Front Panel
1. Install the front panel by hooking the top into the body and rotating the bottom towards the appliance.
Air Guide Vanes
To move the air flow more to the right or to the left, bend the air guide vanes using only light hand pressure.
Do not bend repeatedly (no more than 5 times) or else the vane will break.
2. Secure the front panel to the appliance using two screws through the front of the warm air discharge louvers.
Rinnai Corporation RHFE-750ETR 27
Page 28
Operating Instructions
If you do not follow these instructions exactly, a fire or explosion
WARNING
A. This appliance is equipped with an ignition device
that automatically lights the pilot. Do not light the burner by hand.
B. BEFORE OPERATING smell all around the
appliance area for gas. Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electric switch; do not use any
phone in your building.
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
1. STOP! Read the safety information above.
FOR YOUR SAFETY READ BEFORE OPERATING
may result causing property damage, personal injury or loss of life.
try to
OPERATING INSTRUCTIONS
On/Off Button Error Code
If you cannot reach your gas supplier, call the fire department.
C. Use only your hand to push the gas control
buttons. Never use tools. If the knob will not push in or turn by hand, don’t try to repair it, call a qualified service technician. Force or attempted repair may result in a fire or explosion.
D. Do not use this appliance if any part has been
under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water.
4. If the appliance does not light it will automatically shut down and an error code will display. Check the this manual for error code definitions.
5. To re-attempt ignition, press the On/Off button twice.
2. Wait five (5) minutes to clear out any gas. Then smell for gas, including near the floor. If you smell gas, STOP! Follow “B” in the safety information above. If you don’t smell gas, go to the next step.
3. Press the On/Off button on the top panel on the appliance. This will start the ignition sequence.
Turn off electric power to the appliance using the On/ Off button located on the control panel. The fan will continue to operate until the appliance is cool. Once the fan has stopped operating, isolate the appliance power by unplugging it from the wall or turning off the isolating breaker switch.
TO TURN OFF GAS TO APPLIANCE
6. To adjust the heat, press the up or down buttons on the remote control to adjust the thermostat.
7. To turn the unit off, press the On/Off button on the top control panel.
8. If the appliance will not operate, follow the instructions “To Turn Off Gas To Appliance” and call your service technician or gas supplier. See this manual for additional information.
NOTE: Do not turn the appliance off by unplugging it
from the wall. Keep burner and control compartment clean. See installation and operating instructions.
28 Rinnai Corporation RHFE-750ETR
Page 29
Wiring and Schematic Diagrams
CAUTION
Label all wires prior to disconnection when servicing controls.
Wiring errors can cause improper and dangerous operation.
If any of the original wire as supplied with the
appliance must be replaced, it must be replaced with
type 18 AWG wire or its equivalent.
Rinnai Corporation RHFE-750ETR 29
Page 30
Parts List
For replacement parts call Rinnai at 1-800-621-9419.
30 Rinnai Corporation RHFE-750ETR
Page 31
Parts List
Rinnai Corporation RHFE-750ETR 31
Page 32
Parts List
32 Rinnai Corporation RHFE-750ETR
Page 33
Parts List
ITEM QTY PART NO. DESCRIPTION COMMENTS
1 1 10201 PANEL BASE RHFE750ETR 2 2 10777 FOOT KIT RHFE 3 1 BRACKET COMB CHAMBER SUPPORT RH R750 NON SERVICEABLE PART 4 1 BRACKET COMB CHAMBER SUPPORT LH R750 NON SERVICEABLE PART 5 2 10458 BRACKET FRONT MOUNT RHFE 6 2 10751 WHEEL KIT RHFE750/IBOF 7 2 10778 GLASS RETAINER SPRING KIT RHFE750 8 1 10232 PANEL AIR DIVERTER RH RHFE750
9 1 10231 PANEL AIR DIVERTER LH RHFE750 10 1 10209Z PANEL LOWER AIR GUIDE POWDER COAT RHFE 11 1 COMBUSTION CHAMBER ASSEMBLY PAINTED R750 NON SERVICEABLE PART 12 2 10780 GLASS RETAINER SLIDE ASSEMBLY RHFE750 13 2 10390 GLASS RETAINER SLIDE COVER RHFE750 14 1 10224Z PANEL BURNER SHIELD PAINTED R750 15 1 10204 PANEL HEAT SHIELD REAR RHFE750 16 1 10202 PANEL HEAT SHIELD RH RHFE750 17 1 10203 PANEL HEAT SHIELD LH RHFE750 18 1 10262 PANEL COMB FAN FLUE DIVIDER 19 1 10208 PANEL FAN INFILL RHFE750 20 1 10205 PANEL OUTER RH RHFE750ETR 21 1 10206 PANEL OUTER LH RHFE750ETR 22 1 10263 PANEL COMB FAN INLET "A" 23 1 10264 PANEL REAR AIR INLET "B" 24 1 10781 COMBUSTION FAN COVER RHFE750 25 1 10213 PANEL COVER FLUE OUTLET 26 1 10412 PANEL COVER TRANS RHFE 27 1 10207 TOP PANEL RHFE ENGINE ASSEMBLY 28 1 10296Z LOUVRE SIDE SUPPORT RH BLACK 750 29 1 10297Z LOUVRE SIDE SUPPORT LH BLACK 750 30 31 32 1 10750 DOOR LATCH KIT CONTAINS 4 x LATCHES 33 1 10782 COMB CHAMBER GLASS ASSEMBLY RHFE750 34 2 10783 LOUVRE SIDE ASSEMBLY RHFE750 35 2 10784 SCREEN KIT RHFE750 36 1 10785 WAX ELEMENT ASSEMBLY RHFE750 37 1 10786 MAIN PCB BRACKET ASSEMBLY RHFE750 38 1 10418 BRACKET REAR BURNER SUPPORT RHFE 39 1 10255 BRACKET RECEIVER RHFE750 40 1 10226 BRACKET INJECTOR SUPPORT RHFE750 41 3 10462 PACKING INJECTOR BLOCK 42 2 10753 INJECTOR BLOCK KIT REAR RHFE750 43 1 10754 INJECTOR BLOCK KIT FRONT RHFE750 44 2 7185 INJECTOR 1.45 NG ** 44 2 5436 INJECTOR 0.9 LPG ** 45 1 5425 INJECTOR 1.75 NG ** 45 1 5548 INJECTOR 1.05 LPG ** 46 1 10413 BRACKET TRANSFORMER MOUNT RHFE 47 1 10275A BURNER BRAY 450 NG + BUSH NG ** 47 1 10277A BURNER BRAY 450 LP Ø5.0 LPG **
2 10752 LOUVRE HINGE KIT
** Always refer to the data plate for correct information.
KIT CONTAINS 1 x UPPER AND 1 x LOWER HINGE
Rinnai Corporation RHFE-750ETR 33
Page 34
Parts List
ITEM QTY PART NO. DESCRIPTION COMMENTS
48 2 10359F BURNER ASSEMBLY BRAY 250 Ø3.0 x 2 NG LEFT AND RIGHT ** 48 1 10359B BURNER ASSEMBLY BRAY 250 Ø6.0 x 2 LPG LEFT ONLY ** 48 1 10359G BURNER ASSEMBLY BRAY 250 Ø6.5 x 2 LPG RIGHT ONLY ** 49 1 10764 PILOT ASSEMBLY RHFE750
INCLUDES DOUBLE
50 1 10772 PILOT ELECTRODE KIT RHFE750
51 1 10419 BRACKET REAR BURNER CLAMP RHFE 52 1 10212 PANEL BURNER SURROUND REAR BLACK 53 1 10549 PANEL BURNER SURROUND FRONT BLACK 54 1 10760 AERATION PLATE SET RHFE750 NG US NG ** 54 1 10761 AERATION PLATE SET RHFE750 LPG US LPG **
55 1 10757 LOG PIN SET RHFE US
56 1 10215 PANEL AIR INLET COVER RHFE750 57 2 10211 BRACKET BURNER EXP PLATE RHFE750 58 1 7795 INJECTOR NG 62 NG ** 58 1 7873 INJECTOR NG 35 LPG ** 59 1 10272 PILOT CONVERTIBLE HOOD 3 FLAME 60 1 10425 BRACKET CROSS LIGHTING RHFE NG NG ** 60 1 10426 BRACKET CROSS LIGHTING RHFE LPG LPG ** 61 1 10288 GAS SUPPLY TUBE PILOT B 62 1 10787 REGULATOR ASSEMBLY RHFE750 7~13 mbar US NG ** 62 1 10788 REGULATOR ASSEMBLY RHFE750 15~25 mbar US LPG ** 63 1 10267 BRACKET REGULATOR MOUNT RHFE750 64 1 6313 GAS TUBE RETAINER 65 1 10287 GAS SUPPLY TUBE ASSEMBLY PILOT A 66 1 10248 GAS SUPPLY TUBE FRONT RHFE750 67 1 10247 GAS SUPPLY TUBE RR RHFE750 68 1 10249A GAS SUPPLY TUBE ASSEMBLY RL RH RHFE 69 1 10249B GAS SUPPLY TUBE ASSEMBLY RL LH R750 70 1 10520 JOINER 8MM 71 72 73 74 1 10774 GAS CON SUB ASSEMBLY RHFE750ETR INCLUDES WIRING HARNESS 75 1 10518 TEST POINT CC US RHFE750ETR 76 1 10355 US LOG SET NZ/AU RHFE750ETR US 77 1 FRONT HEAT EXCHANGER ASSEMBLY NON SERVICEABLE PART 78 1 HEAT EXCHANGER REAR RHFE750 NON SERVICEABLE PART 79 1 10227 BRACKET HEAT EXCHANGER TOP R750 80 1 10794 COMBUSTION FAN ASSEMBLY RHFE750 US INCLUDES THERMISTOR (134) 81 1 10341 TUBE COMB EXHAUST LOWER RHFE 82 1 10345 BRACKET EXHAUST TUBE RHFE 83 1 4326 EXHAUST AIR SIDE 84 1 10279 EXHAUST ELBOW RHFE750ETR 85 1 10270 EXHAUST STRAIGHT RHFE750ETR 86 1 10478 CLAMP FLUE 50MM 87 1 10530 FLUE ASSEMBLY RHFE750ETR 88 1 10550 BRACKET FLUE RETAINER RHFE750ETR
1 10756
O-RING KIT RHFE750
** Always refer to the data plate for correct information.
ELECTRODE, FLAME ROD AND CLAMPS
6 x LONG PINS + SCREWS 4 x SHORT SCREWS
KIT INCLUDES 8 ASSORTED ORINGS AND INSTRUCTION SHEET
34 Rinnai Corporation RHFE-750ETR
Page 35
Parts List
ITEM QTY PART NO. DESCRIPTION COMMENTS
89 1 10234 AIR INLET BOX FRONT RHFE750ETR 90 1 10271 PACKING FOR AIR INLET BOX 91 1 10278 PACKING COMB FAN RHFE750ETR 92 1 10796 AIR INLET ASSEMBLY RHFE750 US 93 1 10349 AIR INLET HOSE 94 1 4328 AIR INLET ELBOW B 50x50 95 1 10330 HOSE SS 10 530 3/8SAE RHFE750 96 1 10567 VALVE 3/8" SAEM-FLARE 1/2"NPTF 97 1 10797 PCB ASSEMBLY RHFE750 98 1 10768 FLAME ROD KIT RHFE750 CONTAINS 3 x FLAME RODS 99 1 10770 FLAME ROD BRACKET KIT RHFE750 CONTAINS 3 x BRACKETS
100 1 10792 CONVECTION FAN ASSEMBLY RHFE750 US 101 1 10769 FLAME ROD SLEEVE KIT RHFE750 CONTAINS 3 x SLEEVES 102 1 10798 RECEIVER ASSEMBLY RHFE750 103 1 10765 CONTROL PCB KIT RHFE750 CONTAINS 4 x PCB SPACERS 104 1 10771 BODY PLUG KIT RHFE750 CONTAINS 2 x BODY PLUGS 105 1 10253 PCB DISPLAY RHFE750ETR 106 1 10256 PRESSURE SWITCH RHFE US 107 1 10528 TUBE SILICON BLACK 7x4x1200 108 1 10527 TUBE SILICON CLEAR 6x3x700 109 1 10377 ELECT JUNCTION BOX BODY R750 110 1 7972 ELECTRICAL JUNCTION BOX COVER 111 1 9073 SCREW M4 X 20 PAN PHIL ZINC 112 1 9233 WASHER SPRING M4 ZP 113 2 9186 NUT M4 ZP 114 2 9231 WASHER FLAT M4 ZP 115 1 10378 HARNESS FUSED POWER USA RHFE 116 1 10281 HARNESS FLAME ROD 117 1 10282 HARNESS THERMISTOR 118 1 10283 HARNESS OHS THERMAL FUSE 119 1 10284 HARNESS CONTROL PANEL 120 1 10285 HARNESS RECEIVER 121 1 10286 HT LEAD 122 1 10289 HARNESS COMB FAN 123 1 10348 HARNESS MAIN RHFE750ETR 124 1 10480 HARNESS COMB FAN SPEED 125 1 10539 HARNESS PRESSURE SW US 126 1 10507 HARNESS COMB FAN THERMISTOR FLY 127 128 129 1 10776 PLASTIC CLIP KIT RHFE750 130 1 10766 SPARKER KIT RHFE750 INCLUDES PCB SPACERS 131 1 10773 CONTROL PAN COVER KIT RHFE750 INCLUDES BUTTON 132 1 10259 TRANSFORMER US RHFE750ETR 133 1 10563 CABLE CLAMP RHFE750 USA
134 1 10506 HARNESS COMB FAN THERMISTOR
1 10767
GROMMET KIT RHFE750
** Always refer to the data plate for correct information.
CONTAINS 4 x Ø4 AND 2 x 2Ø1.8 HOLED GROMMETS
ALSO COMES AS PART OF COMBUSTION FAN
Rinnai Corporation RHFE-750ETR 35
Page 36
Consumer Support
Warranty Information
The installer is responsible for your heater’s correct installation.
Please complete the information below to keep for your records:
Purchased from: ___________________________________________________________
Address: _____________________________ Phone: ___________________________
_____________________________
Date of Purchase: __________________________________
Model No.: ________________________________________
Serial No.: ________________________________________
Installed by: ___________________________ Installer’s License No.: _________________
Address: _____________________________ Phone: _____________________________
Date of Installation: __________________________________
Limited Warranty
RHFE-750ETR Direct Vent Fireplace
What is covered?
This Warranty covers any defects in materials or workmanship, subject to the terms stated below. This Warranty extends to the original purchaser and subsequent transferees, but only while the product remains at the site of the original installation. This Warranty only extends through the first installation of the product and terminates if the product is moved or reinstalled at a new location.
How long does coverage last?
All parts…………………..2 years from date of purchase
What will Rinnai do?
Rinnai will repair any part or component that is defective in materials or workmanship as set forth as follows. All repair parts must be genuine Rinnai parts. All repairs or replacements must be performed by an individual or servicing company that has been authorized by Rinnai.
Replacement of the product may be authorized by Rinnai only. Rinnai does not authorize any person or company to assume for it any obligation or liability in connection with the replacement of a product. If Rinnai determines that repair of a product is not possible, Rinnai will replace the product with a comparable product, at Rinnai’s discretion.
36 Rinnai Corporation RHFE-750ETR
Page 37
Limited Warranty - continued
How do I get service?
You must contact a qualified/authorized service provider for the repair of a product under this Warranty. For the name of a qualified/authorized service provider please contact your place of purchase, visit the Rinnai website (www.rinnai.us Georgia 30269.
Proof of purchase is required. You may show proof of purchase with a dated sales receipt, or by completing and mailing the enclosed Registration card within 30 days of purchasing the product. Please complete the enclosed Registration card and mail it to Rinnai at the address shown on the card. Receipt of this card by Rinnai will constitute proof-of-purchase for this product. However, return of the Registration card is not necessary in order to validate this Warranty.
What is not covered?
This Warranty does not cover any failures or operating difficulties due to accident, abuse, misuse, alteration, misapplication, force majeure, improper installation, improper conversion, improper maintenance or service, or for any other causes other than defects in materials or workmanship. This Warranty does not apply to any product whose serial number or manufacture date has been defaced.
Rinnai is not liable for any special, incidental, indirect or consequential damages that may arise, including damage to person or property, loss of use, or inconvenience. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation may not apply to you.
Limitation on implied warranties
), call Rinnai at 1-800-621-9419 or write to Rinnai at 103 International Drive, Peachtree City,
Any implied warranties of merchantability and fitness arising under state law are limited in duration to the period of coverage provided by this limited Warranty, unless the period provided by state law is less. Some states do not allow limitations on how long an implied Warranty lasts, so the above limitation may not apply to you.
This Warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
Rinnai Corporation RHFE-750ETR 37
Page 38
Notes
38 Rinnai Corporation RHFE-750ETR
Page 39
Notes
Rinnai Corporation RHFE-750ETR 39
Page 40
Manufactured by
Rinnai New Zealand LTD
691 Mt Albert Road
Royal Oak, Auckland
For information on Rinnai’s products contact
103 International Drive
Peachtree City, GA 30269
Phone: 1-800-621-9419
Fax: 1-888-474-6624
15237 (Issue B)
Loading...